Professional Documents
Culture Documents
Article
A Study on the Improvement of Double-Skin Facade
Operation for Reducing Heating Load in Winter
Uk-Joo Sung 1 and Seok-Hyun Kim 2, *
1 Center for Climatic Environment Real-scale Testing, Korea Conformity Laboratories, Jincheon 27872, Korea;
suj21c@kcl.re.kr
2 Energy ICT·ESS Laboratory, Korea Institute of Energy Research, Daejeon 34101, Korea
* Correspondence: ksh7000@kier.re.kr
Received: 29 September 2019; Accepted: 28 October 2019; Published: 7 November 2019
Abstract: A double-skin facade makes it possible to gain irradiance through the glass on the outer
side in summer, and to increase the temperature of air flowing in the cavity so as to induce the flow
of air current. Therefore, a double-skin facade is able to reduce the load of the outer skin, which is
delivered from the outside to the inside in summer, and to serve as a buffer space for the internal
and external environments in winter, and thereby prevent heat loss from the building envelope.
Theoretical analysis was conducted to review the heat effects of a double-skin facade and to evaluate
the performance of a plan for indoor load reduction. This study carried out a field measurement
of a building with a double-skin facade and then analyzed the thermal phenomenon occurring in
between the outer skin of the outside and the skin of the inside facing the building surface, according
to the effects of irradiance going into the double-skin facade cavity. In order to propose an indoor air
conditioning energy reduction plan using preheated air through the double-skin facade, this study
utilized a building simulation to be implemented on the target building and then analyzed the
effects of the improvement plan for the double-skin facade. A simulation model was suggested that
implemented the aforementioned airflow network and analyzed the ventilation performance and
energy performance according to the application of alternative plans and thermal effect. To find
the actual state of operation of the double-skin facade in winter, this study measured the target
building. A solar chimney-based double-skin facade was analyzed in winter. As a result, with the
application of a solar chimney and a rise in its height, the available capacity of relatively larger solar
heat increased, and therefore the proposed plan had excellent performance in terms of heating energy
saving. When the thermal effect was applied to the solar chimney, the heating energy use effect of the
solar irradiance of the double-skin facade was larger. When thermal effect was applied to a three-floor
solar chimney, the heating energy use increased to about 7.6 times higher than that of the original
performance of the double-skin facade.
Keywords: double skin facade; ventilation; heating load; solar chimney; Energy Simulation
1. Introduction
In order to save heating energy in a building in winter, passive techniques for enhancing building
insulation can be applied. In particular, a double-skin facade makes it possible to gain irradiance
through the glass on the outer side in summer, and to increase the temperature of air flowing in the
cavity so as to induce the flow of air current. Therefore, a double-skin facade is able to reduce the load
of the outer skin, which is delivered from the outside to the inside in summer, and to serve as a buffer
space for the internal and external environments in winter [1,2], and thereby to prevent heat loss from
the building envelope. To verify the effects of double-skin facades with multiple functions, there are
many studies focusing on various aspects. By analysis of the results, the energy saving effects have
been verified.
Research on the evaluation of double-skin facade applicability draws its conclusions through
testing and simulation. Generally, results drawn from tests are used as a verification tool to secure
the validity of a simulation model. Stec et al. analyzed the effects of double-skin facades on air
conditioning systems [3,4]. With the use of the SimulinkTM program, they analyzed the performance
of air conditioning systems in terms of whether or not to apply a double-skin facade, the application of
blinds, and control. Based on the measurement results of the test cell applied to a real building, they
proved the validity of their analysis model in comparison. In addition, these researchers proposed a
simulation model in which plants are applied to a double-skin facade cavity, established the test facility
to verify the proposed model, and proved the simulation model on the basis of the test results. As a
result, the research concluded that a double-skin facade whose cavity had plants improved the comfort
and energy saving of the internal environment of building. There has been research to quantitatively
evaluate the energy of irradiance going through double-skin facades and to effectively analyze heat
transfer in consideration of radiative heat transfer. In the case of double-skin facades, the SHGC (solar
heat gain coefficient) of the total system, which includes the outer skin of the internal side along with
the transparent outer skin with solar heat transmittance, is a main indication needed to judge the
optical performance of the building envelope, just as the window and door with a general outer skin
of transmittance. Chou et al. established the SHGC calculation test system based on the Hot Box
method in order to analyze the influence of double-skin facades in terms of the energy management of
buildings, and then calculated the SHGC of each azimuthal angle of the installation of a double-skin
facade [5]. In addition, these researchers analyzed the correlation between the WWR (Window to Wall
Ratio) of the inner wall of a double-skin facade and the ETTV (Envelope Thermal Transfer Value),
the heat performance judgment indication of the outer skin according to the SHGC of the whole
outer skin.
In order to find the effects of double-skin facades in winter, Lei Xu et al. utilized the double-skin
facade of a two-floor residential building and analyzed the cooling effect through ventilation in summer,
the greenhouse effect in winter, and the internal environment through the natural air conditioning
effect and energy saving in the intermediate period [6]. Their field test showed that the cooling load
reduced by about 10–15% thanks to natural ventilation in summer, and the cooling load reduced by 20%
and lower in winter. Simulation-based research was conducted to optimize the system of a double-skin
facade. Elisabeth Gratia et al. evaluated a variety of options by utilizing the multistory double-skin
facade of the building suggested in IES (Illuminating Engineering Society) TASK 27 ‘Performance of
solar facade components’ [7–13]. A typical applicability evaluation item was the performance of the
natural ventilation that occurred in the double-skin facade cavity. These researchers analyzed the
performance of the ventilation of the double-skin facade in the daytime and nighttime according to
installation direction, wind direction, and wind velocity. In addition, they evaluated applicability
differently depending on what type of double-skin facade was selected out of eight different types, and
thereby drew the optimal design plan of the double-skin facade to be installed in the south side and
compared the cooling and heating energy consumption. As a result, they suggested the possibility
of inefficient operation, which means that if the natural ventilation of the double-skin facade cavity
during a cooling period is not active, the application effect can be lowered. In addition, in order
to analyze the greenhouse effect of the double-skin facade, they drew passive design factors and
thereby looked into the temperature distribution of the double-skin facade cavity. The design factors
of the double-skin facade were the external environment and components of the double-skin facade,
including the intensity of inflow irradiance, external wind direction and wind velocity, azimuthal
angle of the installation of the double-skin facade, awning apparatus and its color, width of the cavity,
inlet and outlet areas of ventilation [14,15], and window-to-wall ratio and window type of the inner
skin. The temperature concentration problem of the double-skin facade cavity in summer by inefficient
operation was able to be solved by improvement plans, such as appropriate inlet and outlet areas of
Sustainability 2019, 11, 6238 3 of 24
Figure 1.
Figure 1. Research
Research method.
method.
Figure2.
Figure Overviewof
2.Overview ofthe
thebasic
basictheory
theoryof
ofheat
heattransfer
transferin
indouble-skin
double-skinfacades.
facades.
Theheat
The heattransfer
transfer equation
equation of heat
of the the heat flow direction
flow direction in eachin each
zone zone is presented
is presented as the
as the Equations
Equations
1, 2, and 3, (1)–(3), respectively,
respectively, each of each
whichofiswhich is the of
the formula formula of the
the outer skin,outer
cavityskin,
flowcavity
space,flow
and space,
inner
skin. In this case, the transfer rates of conduction, convection, and radiation coming to the inside to
and inner skin. In this case, the transfer rates of conduction, convection, and radiation coming the
from
inside
the from
inner theare
skin inner skin are into
integrated integrated into one coefficient.
one coefficient. If the
If the cavity cavity is
is closed, α closed, = 1;the
= 1; if itαhas if itstate
has the
of
state of airflow,
airflow, α = 0. α = 0.
∂Tv1
Kv1 == Q+
1+(1(−
1 − α)Q+
2 + αQ+
5 + Q+ +8 + Q
5+Q +9 + Q+12 + αv1 Sol (1)
(1)
∂t
∂T f s ∂T5s
K(f s ++ Vfs = −(1
= −−(1 − α)Q−2 (1
− (−
1 − α)Q−
3 − αQ−
5 − αQ6 (2)
(2)
∂t ∂Y
∂Tv2
Kv2 1 − α)Q+
(1(−
== 4 + αQ
3 + Q+ +6 + Q
+7 + Q+10 + Q+11 + Q
+12 + Q Q14 +∙ τv1 ·αv2 Sol
+13 + + (3)
(3)
∂t
Figure3.
Figure 3.Concept
Conceptmap
mapof
ofthe
theairflow
airflownetwork
networkmodel.
model.
In order
In order toto verify
verify and
and prove
prove the
the performance
performance improvement
improvement plan
plan for
for the
the double-skin
double-skin facade
facade
installedin
installed inthe
thetarget
targetbuilding
buildingon
onthe
thebasis
basisofofthe
thesimulation
simulationtheory
theoryfor
forairflow
airflowanalysis,
analysis,this
thisresearch
research
investigated the
investigated the overheating
overheating problem
problem of of the
the upper
upper side
side of
of the
the double-skin
double-skin facade
facade through
through field
field
measurement and
measurement and analyzed
analyzed the
the effects
effects of
of the
the improvement
improvement plan.
plan.
3. Verification
3. Verification of
of the
the Current
Current State
State of
of Double-Skin
Double-Skin Facade
Facade Operation
Operation by
by Field
Field Measurement
Measurement in
in
Winter
Winter Figure 3. Concept map of the airflow network model.
Figure 3. Concept map of the airflow network model.
3. Verification
This studyof
This study the Current
carried
carried out Statemeasurement
out aa field
field of Double-Skin
measurement of aaFacade
of Operation
building
building by Field Measurement
with aa double-skin
with double-skin facade and
facade and then
then
in In order to verify and prove the performance improvement plan for the double-skin facade
Winter
analyzedthe
analyzed thethermal
thermalphenomenon
phenomenonoccurring
occurringin inbetween
betweenthe theouter
outerskin
skinof
ofthe
theoutside
outsideandandthe
theskin
skinofof
installed in the target building on the basis of the simulation theory for airflow analysis, this research
theinside
the inside facing
facing
This study the
the building
building surface
surface according
according to
to the
the effects
effects of
of irradiance
irradiance going
going into
into the
the double-skin
double-skin
investigated the carried out aproblem
overheating field measurement
of the upper of aside
building
of thewith a double-skin
double-skin facadefacade andfield
through then
facade
facade cavity.
cavity.
analyzed the thermal phenomenon occurring in between the outer skin of the outside and the skin of
measurement and analyzed the effects of the improvement plan.
the inside facing the building surface according to the effects of irradiance going into the double-skin
3.1.
3.1. The Current
The Current State
State of
of Double-Skin
Double-Skin Facade
Facade Installation
Installation and
and Field
Field Measurement
Measurement Methodology
Methodology
3.facade cavity.
Verification of the Current State of Double-Skin Facade Operation by Field Measurement in
Winter This study
This study chose
chose as as its
its target
target building
building thethe double-skin
double-skin facade
facade installed
installed in in the
the research
research and
and
3.1. The Current State of Double-Skin Facade Installation and Field Measurement Methodology
business facility
business facility of
of KK Research
Research Institute
Institute inin Daejeon,
Daejeon, South
South Korea.
Korea. This
This building
building withwith aa steel-frame
steel-frame
This study carried out a field measurement of a building with a double-skin facade and then
structure
structure has
Thishas onechose
one
study flooras
floor below
below theground
the
its target ground
building and
and five
thefive floorsabove
floors
double-skinabove ground.
ground.
facade Thein
The
installed 1st
1st floor
floor
the is4.5
is 4.5m
research min
andinbusiness
height,
height,
analyzed the thermal phenomenon occurring in between the outer skin of the outside and the skin of
and
and the2nd
the
facility 2nd to
of Kto 5thfloors
5th floors
Research are3.9
are
Institute3.9in
mmDaejeon,
inheight.
in height.South
Asshown
As shown inthe
in
Korea. theoverview,
This overview, thebuilding
the
building with building hasits
has
a steel-frame its multistory
multistory
structure has
the inside facing the building surface according to the effects of irradiance going into the double-skin
double-skin
double-skin facade
facade
one floor below the onon the
the south
ground south
and five side,
side, andabove
and
floors the architectural
the architectural information
ground. The information
1st ofmthe
floor is 4.5of the target building
target
in height, building
and is
is
the 2nd
facade cavity.
presented
presented in Table
in
to 5th floors Table
are 1.m in height. As shown in the overview, the building has its multistory double-skin
3.91.
facade on the south side, and the architectural information of the target building is presented in Table 1.
3.1. The Current State of Double-Skin Facade Installation and Field Measurement Methodology
Table1.
Table 1.Details
Detailsof
ofmeasurement
measurementfactors.
factors.
This study chose as its target building the double-skin factors.
Table 1. Details of measurement facade installed in the research and
Summerand
Summer and
Overview
Overview
business facility of K Research Institute in Daejeon, South Korea. Winter
This buildingWinter
with a steel-frame
Overview Summer Intermediate
Intermediate
and Intermediate Winter
structure has one floor below the ground and five floors above ground. The 1st floor is 4.5 m in height,
and the 2nd to 5th floors are 3.9 m in height. As shown in the overview, the building has its multistory
double-skin facade on the south side, and the architectural information of the target building is
presented in Table 1.
Summer and
Overview Winter
Intermediate
Dimensions
Dimensions
Dimensions 16m
16 16 mⅩ
m(W)
(W) Ⅹ 23.5
23.5
(W) m(H)
m
× 23.5(H) Ⅹ 1.2
Ⅹ
m (H) ×1.2 mm
m
1.2 (D)
(D)
(D)
Direction
Direction South
South
Direction South
Exterior:99mm
Exterior: mmGN GNGreen(Glazing)
Green(Glazing)++Aluminum
AluminumCurtain
Curtainwall
wall(Frame)
(Frame)
Windowcomposition
Window composition
Exterior:
Interior: 9 mm
Interior:22
22 mmGN
mm Green(Glazing)
Clear
Clear + Aluminum
(Glazing)++Aluminum
(Glazing) Aluminum Fix&
Fix Curtain
&PJ wall (Frame)
PJ(Frame)
(Frame)
Window composition
Interior: 22 mm Clear (Glazing) + Aluminum Fix & PJ (Frame)
Inner wall finish 30 mm granite burner finishing
Lower air inlet area 44.6 m2
Dimensions 16 m (W) Ⅹ 23.5 m (H) Ⅹ 1.2 m (D)
Upper air outlet area 37.1 m2
Direction South
Exterior: 9 mm GN Green(Glazing) + Aluminum Curtain wall (Frame)
Window composition
Interior: 22 mm Clear (Glazing) + Aluminum Fix & PJ (Frame)
Inner wall finish 30 mm granite burner finishing
Sustainability 2019, 11, 6238 6 of 24
The actual state of double-skin facade operation was analyzed. The inlet and outlet areas of the
upper and lower sides of the double-skin facade are opened in summer. In this case, internal air with
increased temperature by irradiance is emitted outside through natural ventilation. In winter, the outlet
of the upper side of the double-skin facade is closed, and internal air with increased temperature
is made to flow through the OA (outdoor air) inlet of the air conditioning system. At this time,
the double-skin facade is used as the preheating path of outdoor air. In this way, it is possible to reduce
outdoor air load and prevent heat loss. Therefore, if the double-skin facade is operated as shown in its
design, it is possible to save energy.
In order to analyze the environmental factors of the double-skin facade influenced by the external
environment, measurement factors and measurement points were chosen. Irradiance, regional surface
temperature, and internal air temperature, which influence the inside of the double-skin facade,
were measured. In order to quantitatively analyze the effects of the natural ventilation that occurs in
the double-skin facade, the wind velocity of each one of the air inlet and outlet in the upper and lower
sides of the double-skin facade was measured. Table 2 presents measurement factors and the applied
measuring device.
Figure 4 illustrates each measurement point of the measuring device, and the installation of
the measuring sensor. In terms of irradiance, the irradiance on the external vertical surface of the
double-skin facade was measured. As the measurement factors of the internal side, the surface
temperature of the double-skin facade (outdoor side), air temperature, the surface temperature of the
wall, and the temperature of the center of the glass window were measured on each floor. In the air
inlet and outlet, air temperature and wind velocity were measured.
Sustainability 2019, 11, x FOR PEER REVIEW 7 of 24
Sustainability 2019, 11, 6238 7 of 24
Field measurement
3.2. Analysis of the CurrentwasStatecarried out from
of Double-Skin JuneOperation
Facade to December in order to analyze the actual
in Winter
3.2. Analysis of the Current State of Double-Skin Facade Operation in Winter
operation state of the double-skin facade. As shown in Figure 5, daily average outdoor air
Field measurement was carried out from June to December in order to analyze the actual operation
Field measurement
temperature and accumulated was irradiance
carried outoffrom June to December
the multistory double-skin in facade
order were
to analyze
analyzedtheduring
actual
state of the double-skin facade. As shown in Figure 5, daily average outdoor air temperature and
operation
the state of
measurement the double-skin
period. facade. As shown
Outdoor air temperature graduallyin decreased
Figure 5, with
dailya seasonal
average change
outdoorfrom
air
accumulated irradiance of the multistory double-skin facade were analyzed during the measurement
temperature
summer and
(June) to accumulated irradiance
winter (December), andofthethe multistory
irradiance of double-skin facade
the vertical side were
of the analyzed during
double-skin facade
period. Outdoor air temperature gradually decreased with a seasonal change from summer (June) to
the measurement
slowly increased as period. Outdoor
solar altitude air temperature
lowered. gradually
To find the decreased
actual operation with
state ofathe
seasonal change
double-skin from
facade
winter (December), and the irradiance of the vertical side of the double-skin facade slowly increased
summer
in winter,(June) to winter
the results of (December),
measurements andwhich
the irradiance
were made of the vertical
from side 26
October of the double-skin
to December 30facade
were
as solar altitude lowered. To find the actual operation state of the double-skin facade in winter, the
slowly increased
analyzed. The main as solar altitude
influence lowered.
factors of theTo find the
thermal actual operation
environment werestate of thefor
analyzed double-skin facade
the categories of
results of measurements which were made from October 26 to December 30 were analyzed. The main
in winter, the results of measurements which were made from October 26 to December
irradiance level (high, middle low) on the basis of the irradiance of the vertical side, as shown in Table 30 were
influence factors of the thermal environment were analyzed for the categories of irradiance level (high,
analyzed.
3. AnalysisThe main
days for influence
each rangefactors of the thermal
were selected, environment
and then the actualwere analyzed
operation stateforof the
the categories of
double-skin
middle low) on (high,
irradiance the basis of the irradiance of the vertical side, as shown in Table 3. Analysis days for
facade waslevel
analyzed. middle low) on the basis of the irradiance of the vertical side, as shown in Table
each range were
3. Analysis days selected, and then
for each range theselected,
were actual operation
and then state of theoperation
the actual double-skin facade
state of thewas analyzed.
double-skin
facade was analyzed.
Figure 5. Solar
Solar irradiance
irradiance and
and outdoor
outdoor air
air temperature
temperature during the measurement period.
Figure 5. Solar irradiance and outdoor air temperature during the measurement period.
Sustainability 2019, 11, 6238 8 of 24
Sustainability 2019, 11, x FOR PEER REVIEW 8 of 24
As shown in Figures 6 and 7, outdoor air temperature and irradiance were analyzed. When solar
As shown in Figures 6 and 7, outdoor air temperature and irradiance were analyzed. When solar
irradiance was at the high level, average outdoor air temperature and daily average accumulated
irradiance was at the high level, average outdoor air◦ temperature and daily 2average accumulated
irradiance in the daytime (8:00–17:00) were 5.79 C and 5249.49 Wh/m ·day. When irradiance was
irradiance in the daytime (8:00–17:00) were 5.79 ℃ and 5249.49 Wh/㎡·day. When irradiance was at
atthe
themiddle
middle level, they were ◦ C and 3519.29 Wh/m2 ·day. When irradiance was at the low level,
level, they were 1.9 1.9
℃ and 3519.29 Wh/㎡·day. When irradiance was at the low level,
they ◦ Wh/m2 ·day.
they were
were 2.04
2.04 ℃C andand1102.23
1102.23Wh/㎡·day. Outdoor
Outdoor air temperature
air temperature in winter
in winter was lowerwasthan
lower
in than in
summer
summer and theintermediate
and the intermediate period.
period. However,
However, the inflow
the inflow irradiance
irradiance of the multistory
of the multistory (vertical (vertical
side) side)
double-skin facade increased in winter as solar altitude was lowered.
double-skin facade increased in winter as solar altitude was lowered.
Figure6.6.
Figure Average
Average outdoor
outdoor air temperature
air temperature andirradiance
and solar solar irradiance in winter.
in winter.
Sustainability 2019, 11, 6238 9 of 24
Sustainability 2019, 11, x FOR PEER REVIEW 9 of 24
As
As presented
presentedinin Figure 8, the
Figure 8, internal air temperature
the internal for irradiance
air temperature was analyzed.
for irradiance When irradiance
was analyzed. When
was at the high level, the analysis date was December 16. Average outdoor
irradiance was at the high level, the analysis date was December 16. Average outdoor air temperature air temperature in the
◦ (max: ℃ ◦
daytime (8:00–17:00)
in the daytime was −0.36
(8:00–17:00) wasC –0.36 3.13(max: 3.13 ℃,
C, 13:00), and13:00),
the daily
and total
theaccumulated irradiance of
daily total accumulated
the multistory double-skin 2 ·day (max: 823.87 Wh/m2 , 13:00). When solar
irradiance of the multistoryfacade was 5583.18
double-skin facadeWh/m
was 5583.18 Wh/㎡·day (max: 823.87 Wh/㎡, 13:00).
irradiance
When solar was at the middle
irradiance was atlevel,
the the analysis
middle date
level, thewas December
analysis 31. Average
date was December outdoor air temperature
31. Average outdoor
in
airthe daytime (8:00–17:00)
temperature in the daytime −4.09 ◦ C (max:
was(8:00–17:00) −2.62℃
was –4.09 ◦ C, 15:00), and the daily total accumulated
(max: –2.62 ℃, 15:00), and the daily total
irradiance
accumulated of the multistory
irradiance double-skin
of the multistory facade was 3491.63
double-skin facade was23491.63
Wh/m ·day (max: (max:2 ,760.55
760.55 Wh/m
Wh/㎡·day 12:00;
min: 13.69 Wh/m 2
Wh/㎡, 12:00; min:, 8:00).
13.69 When
Wh/㎡,solar irradiance
8:00). When solar wasirradiance
at the lowwaslevel,
atthe
theanalysis date
low level, thewas December
analysis date
13. ◦ C (max: 5.29 ◦ C, 16:00), and
wasAverage
Decemberoutdoor air temperature
13. Average outdoorinair thetemperature
daytime (8:00–17:00) was 3.74
in the daytime (8:00–17:00) was 3.74℃ (max:
the ℃, 16:00),
5.29daily total accumulated
and the dailyirradiance of the multistory
total accumulated irradiance double-skin facade double-skin
of the multistory facade2 ·day
was 345.42 Wh/m was
(max: 2
345.4274.75 Wh/m (max:
Wh/㎡·day , 13:00).
74.75 Wh/㎡, 13:00).
Sustainability 2019, 11, 6238 10 of 24
Sustainability 2019, 11, x FOR PEER REVIEW 10 of 24
Figure 8.
Figure Air temperature
8. Air temperature at
at double
double skin
skin façade
façade by
by solar
solar irradiance
irradiance in
in winter.
winter.
In winter, the
In winter, the outlet
outletofofthe theupper
upperside side is is closed.
closed. TheThe cavity’s
cavity’s air with
air with increased
increased temperature
temperature is in
is in connection with the OA (available air volume: 9600
connection with the OA (available air volume: 9600 CMH (cubic meter per hour)) of CMH (cubic meter per hour)) of the
the air
air
conditioning system in the upper side. In other words, the double-skin
conditioning system in the upper side. In other words, the double-skin facade is used not only as the facade is used not only as the
preheating
preheating path path ofof OA
OA to to reduce
reduce outdoor
outdoor air air load,
load, but
but for
for the
the complex
complex function
function of of preventing
preventing heatheat
loss from the inside to the outside resulting from air with increased
loss from the inside to the outside resulting from air with increased temperature. In terms temperature. In terms of of the
the air
air
temperature of the cavity, with a rise in solar irradiance, the temperature
temperature of the cavity, with a rise in solar irradiance, the temperature difference between the difference between the upper
and
upperlowerandairlower
inlet and
air outlet
inlet andareasoutlet
increased,
areasand the floor-to-floor
increased, and thestratification
floor-to-floor of air temperature
stratification ofwas
air
more distinct. On December 16 (when solar irradiance was at the high
temperature was more distinct. On December 16 (when solar irradiance was at the high level), the level), the temperature difference
between the upper andbetween
lower airthe
inlet andand outlet areas ◦ C at 13:00, the maximum time of
temperature difference upper lower airwas
inlet24.15
and outlet areas was 24.15 ℃ at 13:00,
solar irradiance.
the maximum Onof
time December 31 (whenOn
solar irradiance. solar irradiance
December was at solar
31 (when the middle level),
irradiance wastheattemperature
the middle
difference ◦
level), the temperature difference between the upper and lower air inlet and outlet areas maximum
between the upper and lower air inlet and outlet areas was 24.31 C at 12:00, the was 24.31
time
℃ atof solarthe
12:00, irradiance.
maximum Ontime
December
of solar13irradiance.
(when solar Onirradiance
Decemberwas at the low
13 (when solarlevel), the temperature
irradiance was at the
difference ◦ C at 13:00, the maximum
low level),between the upperdifference
the temperature and lowerbetween
air inlet and outlet areas
the upper was 24.15
and lower air inlet and outlet areas was
time of solar irradiance. Therefore, the overall temperature
24.15 ℃ at 13:00, the maximum time of solar irradiance. Therefore, the overall difference was large in winter, compared
temperature
to other seasons. The stratification of cavity air temperature on each
difference was large in winter, compared to other seasons. The stratification of cavity air temperaturefloor (height) was the most
distinct
on each when solar irradiance
floor (height) was the mostwas at the high
distinct when level in winter,
solar irradiance justwas
likeat inthe
summer.
high level Thein floor-to-floor
winter, just
temperature gradient was reduced as solar irradiance was lowered. The
like in summer. The floor-to-floor temperature gradient was reduced as solar irradiance was lowered. temperature gradient of the
second and third floors was relatively larger in winter than in other seasons,
The temperature gradient of the second and third floors was relatively larger in winter than in other and the temperature
seasons, and the temperature from the fourth floor to the exit was somewhat concentrated. It is
judged that in winter, compared to other seasons, this temperature concentration was attributable to
Sustainability 2019, 11, 6238 11 of 24
from the fourth floor to the exit was somewhat concentrated. It is judged that in winter, compared to
the seasons,
other reason thatthisthe low floorsconcentration
temperature had more distinct stratification
was attributable duereason
to the to inflow andlow
that the interference
floors hadof
outdoor
more air stratification
distinct with low temperature,
due to inflowbutandtheinterference
high floorsof had their air
outdoor outletlow
air with closed and did not
temperature, have
but the
high floors had their air outlet closed and did not have enough preheated air through the double-skinair
enough preheated air through the double-skin facade in the way of utilizing OA of the
conditioning
facade in the way system in the OA
of utilizing duct in order
of the to constantly
air conditioning systemkeep in the stratification
the duct in order tostructure.
constantlyThe
temperature
keep of eachstructure.
the stratification region of The the temperature
cavity was analyzed on theofbasis
of each region of thewas
the cavity average temperature
analyzed on the
measured at 11:00–16:00, a time slot that accounts for just over 60% of
basis of the average temperature measured at 11:00–16:00, a time slot that accounts for just over 60%the daily accumulated
ofirradiance of the multistory
the daily accumulated double-skin
irradiance facade. Just
of the multistory as in other
double-skin seasons,
facade. Just asininwinter, the surface
other seasons, in
temperature
winter, of the
the surface outer skinofexposed
temperature the outerto skin
solarexposed
irradiance was irradiance
to solar the highest. However,
was on the
the highest. analysis
However,
onday
thewhen solarday
analysis irradiance
when solarwas irradiance
at the low level,
was at there
the was
low the lowest
level, theretemperature
was the lowest distribution due to
temperature
the interference
distribution due toof low
the outdoor air
interference temperature
of low outdoor air fortemperature
low irradiance heatirradiance
for low absorption. With
heat regard to
absorption.
the temperature difference of each region, the temperature of indoor
With regard to the temperature difference of each region, the temperature of indoor window glass
window glass relatively
vulnerable to heat resistance was high due to heat loss, since indoor heating air conditioning was
relatively vulnerable to heat resistance was high due to heat loss, since indoor heating air conditioning
applied. For this reason, the temperature difference of each region on the low floors was the largest.
was applied. For this reason, the temperature difference of each region on the low floors was the largest.
It was somewhat reduced on higher floors because of a rise in cavity air temperature. Just as with
It was somewhat reduced on higher floors because of a rise in cavity air temperature. Just as with
cavity air temperature, the temperature difference of each region was decreased as solar irradiance
cavity air temperature, the temperature difference of each region was decreased as solar irradiance
was lowered.
was lowered.
As shown in Figure 9, the wind velocity of the air inlet in the lower side in winter was analyzed.
As shown in Figure 9, the wind velocity of the air inlet in the lower side in winter was analyzed.
Unlike in other seasons, in winter, the air outlet in the upper side was closed and the preheated air
Unlike in other seasons, in winter, the air outlet in the upper side was closed and the preheated air
through the double-skin facade was used as OA. For this reason, although the wind velocity of the
through the double-skin facade was used as OA. For this reason, although the wind velocity of the air
air inlet in the lower side was somewhat different due to buoyancy according to irradiance, it
inlet in the lower side was somewhat different due to buoyancy according to irradiance, it remained at
remained at 0.8–1.2 m/s on average in the daytime (8:00–17:00).
0.8–1.2 m/s on average in the daytime (8:00–17:00).
Figure 9. 9.Wind
Figure Windvelocity distribution
velocity ofof
distribution the Outlet
the inin
Outlet winter.
winter.
InInterms
terms ofofmeasuring
measuring the
thedouble-skin
double-skinfacadefacadecavity
cavityininwinter,
winter, the
theoutlet ofof
outlet the theupper
upper side
sidewaswas
closed in order to use the facade as the preheating path of air conditioning
closed in order to use the facade as the preheating path of air conditioning OA, and the cavity OA, and the cavity andand
airair
conditioning system interacted in terms of OA. According to the field
conditioning system interacted in terms of OA. According to the field measurement, the air with measurement, the air with
increased
increased temperature
temperature through
through thethedouble-skin
double-skin facade
facade had
had little OA
little OA utilization
utilizationsosothat
thatairair
stood
stood still
still
from the 4th floor to the exit area, and consequently temperature concentration
from the 4th floor to the exit area, and consequently temperature concentration occurred in the upper occurred in the upper
side.
side.Nevertheless,
Nevertheless,ininwinter,winter,the thedirection
directionofofintensive
intensiveheat heatflowflowininthetheupper
upperside
sidewas waslostlosttotothe
the
outside, not to the inside, due to the influence of low outdoor air temperature,
outside, not to the inside, due to the influence of low outdoor air temperature, and therefore, overheatand therefore, overheat
transfer
transfer was
was notnotfound
found ininthe upper
the upper side.
side.InInwinter,
winter, if if
outer
outerskin
skinload
loadand
andoutdoor
outdoor airair
load
loadare arereduced
reduced
ininthe
thewaywayofofapplying
applying anan appropriate
appropriate airair
volume
volume control
control strategy
strategy forfor
OAOA utilization
utilization ofofthe
the preheated
preheated
airair
through
through thethedouble-skin
double-skin facade,
facade, it is possible
it is possibleto to
save
savea great
a great deal
dealof of
energy.
energy.
4. Analysis of the Effects of the Improvement Plan for Double-Skin Facade Operation
Sustainability 2019, 11, 6238 12 of 24
Sustainability 2019, x11, x FOR Table 5. Solar chimney systems as alternative plans.
PEER REVIEW
Sustainability
Sustainability
Sustainability
Sustainability 2019,
2019, 2019,
11,x 2019,
11, 11,
xFOR
FOR x11,
FOR
PEER
PEER FOR
PEER PEER
REVIEW
REVIEW
REVIEW REVIEW 13 of13
24of13 of1324
24of
13 of 24
24
Type Baseline ALT1 ALT2 ALT3
Concept
Concept map Concept
Concept
map mapmapmap
Concept
Concept map
Figure
Figure 10. Figure
Figure
10.
Concept 10.
Concept Concept
10. Concept
of the of simulation
the model
ofsimulation
the
of the simulation
simulation model
model
for model
for for
outdoor outdoor
for outdoor
outdoor air (OA)-based
air (OA)-based
air (OA)-based
air (OA)-based air conditioning
air conditioning
air conditioning
air conditioning in winter.
in winter.
in winter.
in winter.
The total area of the air conditioning zone of the double-skin facade was 19,440 ㎥. As shown in
the table, the indoor heating load and OA-based heat of the installation side of the double-skin facade
were calculated according to the OA-based air volume (air changes 0.2/h–2/h) through the double-
Sustainability 2019, 11, 6238 14 of 24
The total area of the air conditioning zone of the double-skin facade was 19,440 m3 . As shown in
Sustainability 2019, 11, x FOR PEER REVIEW 14 of 24
the table, the indoor heating load and OA-based heat of the installation side of the double-skin facade
were calculated according to the OA-based air volume (air changes 0.2/h–2/h) through the double-skin
skin facade in each alternative plan with an SC. The indoor heating load and OA-based heat were
facade in each alternative plan with an SC. The indoor heating load and OA-based heat were added
added together (OA-based heat-indoor heating load), and then an appropriate air volume for the
together (OA-based heat-indoor heating load), and then an appropriate air volume for the designed
designed air change in each alternative plan was selected. On the basis of the baseline model (OA-
air change in each alternative plan was selected. On the basis of the baseline model (OA-based air
based air volume: 9600 CMH) actually operated by the double-skin facade, the relative energy
volume: 9600 CMH) actually operated by the double-skin facade, the relative energy performance
performance improvement value of the selected appropriate air volume in each alternative plan with
improvement value of the selected appropriate air volume in each alternative plan with an SC was
an SC was analyzed. According to the daily accumulated irradiance of the multistory double-skin
analyzed. According to the daily accumulated irradiance of the multistory double-skin facade as the
facade as the dominant influential factor on the thermal behavior of the double-skin facade, they were
dominant influential factor on the thermal behavior of the double-skin facade, they were divided
divided into high (4000 Wh/㎡ and more), middle (2000–4000 W/㎡), and low (2000 Wh/㎡ or less)
into high (4000 Wh/m2 and more), middle (2000–4000 W/m2 ), and low (2000 Wh/m2 or less) types.
types. The simulation period was 95 days of heating operation from Nov. 1 to Mar. 15. Heating load
The simulation period was 95 days of heating operation from 1 November to 15 March. Heating load
was calculated only in the south air conditioning zone (1F–5F) directly influenced by the double-skin
was calculated only in the south air conditioning zone (1F–5F) directly influenced by the double-skin
facade. In terms of climate data, outdoor air temperature and humidity, measured data of solar
facade. In terms of climate data, outdoor air temperature and humidity, measured data of solar
irradiance, and wind direction and velocity data of relevant regions, which are offered by Korea
irradiance, and wind direction and velocity data of relevant regions, which are offered by Korea
Meteorological Administration, were used.
Meteorological Administration, were used.
4.2.
4.2. Analysis
Analysis Results
Results of
of the
the Operation
Operation Improvement
Improvement Plan
Plan
Figure
Figure 11
11 shows
shows thethe measurement
measurement results
results on
on the
the x-axis
x-axis andand the
the simulation
simulation results
results onon the
the y-axis
y-axis
in
in the same time zones, reacting to the same external environments on the selected analysis days,
the same time zones, reacting to the same external environments on the selected analysis days,
according
according toto the
the solar
solar irradiance
irradiance levels
levels inin terms
terms of
of cavity
cavity airair temperature
temperature in in order
order to
to verify
verify the
the airflow
airflow
network
network simulation
simulation baseline
baseline model
model in in summer.
summer. Based
Based onon thethe linear
linear equation
equation withwith aa y-intercept
y-intercept ofof ‘0′,
‘0’,
if the coefficient of x value and R2 value are close to ‘1′, it is proved that the measurement
if the coefficient of x value and R2 value are close to ‘1’, it is proved that the measurement values are values are
highly
highly consistent
consistent with
with simulation
simulation values.
values. According
According toto the
the comparison,
comparison, the the coefficient
coefficient to
to xx value
value was
was
0.98, and R2 was 0.96. As a result, there was a considerably high level
0.98, and R2 was 0.96. As a result, there was a considerably high level of consistency. of consistency.
Figure 11.
Figure Comparison of
11. Comparison of air
air temperature
temperature between
between measurement
measurement and simulation results.
Figure 12
Figure 12 shows
shows thethe double-skin facade-based heat
double-skin facade-based heat and
and indoor
indoor heating
heating load
load for
for the
the period
period
(November to
(November to March)
March) according
according to
to the
the OA-based
OA-based air
air volume.
volume. InIn terms
terms of
of double-skin
double-skin facade-based
facade-based
heat, when solar irradiance was at the high and middle levels, each alternative plan showed
heat, when solar irradiance was at the high and middle levels, each alternative plan showed that that with
with
aa rise
rise in
in OA-based
OA-based airair volume,
volume, the
the double-skin
double-skin facade-based
facade-based heat
heat gradually
gradually increased
increased and
and remained
remained
almost unchanged in the range of about 26,000 CMH and above. When solar irradiance wasthe
almost unchanged in the range of about 26,000 CMH and above. When solar irradiance was at at low
the
low level, each alternative plan showed that with a rise in OA-based air volume, the double-skin
facade heat gradually increased, and remained almost unchanged and then decreased to a value in
the range of about 15,000 CMH and above. In each alternative plan, with the application of an SC and
a rise in its height, the double-skin facade-based heat also increased. The ALT3, which implemented
thermal effect, showed the highest heat value. On balance, with an increase in the amount of
Sustainability 2019, 11, 6238 15 of 24
level, each alternative plan showed that with a rise in OA-based air volume, the double-skin facade
heat gradually increased, and remained almost unchanged and then decreased to a value in the range
of about 15,000 CMH and above. In each alternative plan, with the application of an SC and a rise in
its height, the double-skin facade-based heat also increased. The ALT3, which implemented thermal
Sustainability 2019, 11, x FOR PEER REVIEW 15 of 24
effect, showed the highest heat value. On balance, with an increase in the amount of irradiance of the
double-skin facade, the OA-based air volume also went up. Additionally, with the application of an SC
irradiance of the double-skin facade, the OA-based air volume also went up. Additionally, with the
to the upper side of the double-skin facade, solar heat was used more, and therefore the OA utilization
application of an SC to the upper side of the double-skin facade, solar heat was used more, and
through the double-skin facade was larger.
therefore the OA utilization through the double-skin facade was larger.
Figure12.
Figure 12.Heat
Heatgain
gainand
andheating
heatingload
loadfrom
fromsimulation
simulationresults.
results.
Interms
In termsofofannual
annual heating
heating load
load according
according to the
to the double-skin
double-skin facade-based
facade-based air volume,
air volume, with with
a risea
inrise in OA-based
OA-based air volume,
air volume, the temperature
the temperature distribution
distribution by cavityby cavity
height andheight and the
the surface heatsurface heat
resistance
ofresistance
the innerof the inner wall were lowered and therefore indoor heating load gradually increased, but
wall were lowered and therefore indoor heating load gradually increased, but it was lower
it was
than lower
of the thethan of the the
double-skin double-skin
facade-based facade-based
heat. Comparedheat. to theCompared to the each
baseline model, baseline model,plan
alternative each
alternative
showed that plan
with showed that with
the application theSC
of an application
and a rise of in an
its SC and the
height, a rise in its height,
buoyancy of the the buoyancy
air of the cavity of
the airheat
caused of the cavity caused
concentration heat
on the SCconcentration
path and thereby on the
the 1FSCtopath and thereby
5F cavity the 1F towas
air temperature 5F relatively
cavity air
temperature
lowered was relatively
and indoor loweredincreased.
load somewhat and indoor load somewhat
Nevertheless, ALT1, increased.
ALT2, and Nevertheless, ALT1,
ALT3 had a similar
ALT2, and ALT3
distribution had heating
of annual a similarload
distribution
without anyof annual heating load without any great difference.
great difference.
Figure13
Figure 13illustrates
illustratesthetheanalysis
analysisresults
resultsofofthe
thedouble-skin
double-skinfacade-based
facade-basedheat heatproduction
productioninineacheach
alternativeplan
alternative planaccording
accordingtotoOA-based
OA-basedheat heatandandsolar
solarirradiance.
irradiance.TheThedouble-skin
double-skinfacade-based
facade-basedheat heat
productionproposed
production proposedin inthis
thisstudy
studyisisthe
thetotal
totalofofthe
thedouble-skin
double-skinfacade-based
facade-basedheat heatand
andindoor
indoorheat
heat
lossload
loss loadbybyeach
eachOA-based
OA-basedair airvolume.
volume. ItIt refers
refers toto the
the net
netheat
heatproduction
productionatatthe thetime
timewhen
whenthe the
double-skin facade is used as the preheating path of OA. When the daily accumulated irradiance of
the multistory double-skin facade was 2000 Wh/㎡ and more, the double-skin facade-based heat was
larger than the indoor heat loss load. When it was less than 2000 Wh/㎡, indoor heat loss load was
relatively larger, and therefore, general loss occurred. In the analysis of each alternative plan, the heat
produced by the double-skin facade increased in the order of Baseline < ALT1 < ALT2 < ALT3 as an
Sustainability 2019, 11, 6238 16 of 24
double-skin facade is used as the preheating path of OA. When the daily accumulated irradiance of
the multistory double-skin facade was 2000 Wh/m2 and more, the double-skin facade-based heat16was
Sustainability 2019, 11, x FOR PEER REVIEW of 24
larger than the indoor heat loss load. When it was less than 2000 Wh/m2 , indoor heat loss load was
relatively larger, and
SC was applied andtherefore,
its heightgeneral
went up.loss
Theoccurred. In theimplemented
ALT3, which analysis of each alternative
thermal plan,
effect on thethe
SCheat
path,
Sustainability 2019, 11, x FOR PEER REVIEW 16 of 24
produced by the double-skin
produced the highest heat. facade increased in the order of Baseline < ALT1 < ALT2 < ALT3 as an
SC was
SC wasapplied
appliedand and itsitsheight
heightwent up.The
went up. TheALT3,
ALT3, which
which implemented
implemented thermal
thermal effecteffect
on theon
SCthe
path,SC path,
produced the highest
produced the highest heat. heat.
Figure 13. Heat gain of the double skin facade by ALT and solar irradiance.
Figure 13.Heat
Figure13. Heat gain of the
gain of thedouble
doubleskin
skin facade
facade by by
ALTALT
andand
solarsolar irradiance.
irradiance.
Figure 14 presents the air temperature of the cavity in each alternative plan on the analysis days
Figure
of solar 14 14
Figure presents
irradiancepresentsthetheair
airtemperature
selected at the timeofof
temperature of themeasurement.
the cavity
cavity in in
eacheach alternative
alternative
With riseplan
a plan in on
on the the irradiance,
analysis
analysis
solar days days
the
of solar
oftemperature
solar irradiance
irradiance selected
selected at at time
the the time
of of measurement.
measurement. With With
a rise ainrise
solarinirradiance,
solar irradiance,
the the
temperature
difference between the upper and lower sides in the double-skin facade was larger. With
temperature
difference between difference
the between
upper and the upper
lower andin
sides lower
the sides in the double-skin
double-skin facade was facade was
larger. larger.
With anWith
increase inof
ananincrease
increase
ininthe
the
installation
installation
height
height of
of the
the
SC,
SC,
there
there was
was
no
no great
great
difference
difference in the
in
air
the air temperature
temperature of close
the installation
thethe
cavity height of the(1F–5F)
SC, there was no great difference inairthe air temperature of the cavity
cavityclose
closeto to indoor
indoor (1F–5F) inineach
each plan.
plan. However,
However, thetemperature
the air temperaturein the SCin the
pathSC path gradually
gradually
toincreased
indoor (1F–5F) in each plan. However, the highest
air temperature in theincrease
SC pathoccurred
graduallyinincreased with a
increasedwith
withaariserise in theSC
in the SC height.The
height. The temperature
highest temperature increase occurred in ALT3. ALT3.
rise in the SC height. The highest temperature increase occurred in ALT3.
Figure 14. Heat production of the double skin facade by the OA airflow of the ALT.
Figure
This study
Figure 14.Heat
14.
chose aHeat
rangeproduction
of constant
production ofofthe
thedouble
increase of skin
double skinfacade
facadeby
double-skin bythetheOAOAairflow
facade-based heatof
airflow ofthe
with aALT.
the rise
ALT. in OA-
based air volume as an appropriate OA-based air volume range. Therefore, when solar irradiance
This
was at study
This the high
study chose aa range
and middle
chose of constant
rangelevels,
of constant
2600 CMH increase ofofdouble-skin
was chosen
increase double-skin
as the maximum facade-based
OA-based
facade-based heatheat
air
withwith
volume; a rise
a rise in
in OA-
OA-based
whenair
based atair
the volume
volume asasan
low level, anappropriate
1500 appropriate
CMH was chosen OA-based
OA-based air
as theair volumeOA-based
maximum
volume range.
range. Therefore,
air volume.when
Therefore, Whensolar
when irradiance
the solar
solar irradiance
was at the
irradiancehigh of and
all themiddle
air levels,
conditioning 2600
zones CMHof was
the chosen
building
was at the high and middle levels, 2600 CMH was chosen as the maximum OA-based air as
was the
at themaximum
high and OA-based
middle levels,airthevolume;
volume;
when at
number the oflow level,
maximum 1500 CMH
air changes was
waschosen as
1.3 times/h; the maximum
when the solarOA-based
when at the low level, 1500 CMH was chosen as the maximum OA-based air volume. When the solar
irradiance airwasvolume.
at the low When
level,theit solar
was 0.7 of
irradiance times/h.
all all These
thethe numbers met
air conditioning the ventilation
zones requirement
of theofbuilding was atof the0.7high
times/h and
andhigh above
middle prescribed
irradiance of air conditioning zones the building was at the andlevels,
middle thelevels,
number the
in
ofnumber‘Rules
maximum of Building
air changes Facilities
was Standards,
1.3 times/h; Etc. (2006)’
when theof the
solarMinistry of
irradiance Land,
was Transport
at the and
low Maritime
level, it was 0.7it
Affairs. of maximum
Air changes air
formet changes
introducing was 1.3 times/h;
fresh outdoor when
air canof the
be0.7 solar
different irradiance
depending was at the
onprescribed low
the operation level,
times/h.
was 0.7These
times/h. numbers
Theseand the ventilation
numbers met the requirement
ventilation requirement times/h and above
of 0.7 in ‘Rules
intention of building on irradiance. Therefore, when solar irradiance wastimes/h andand
at the high above
middle prescribed
ofinBuilding
‘RulesthreeFacilities
of Building Standards,
Facilities Etc. (2006)’
Standards, of the Ministry of Land, Transport and Maritime Affairs.
levels, operation plans (number of airEtc. (2006)’0.7,
changes: of 1,
theand
Ministry of Land,
1.3 times/h) wereTransport
established, andand Maritime
Affairs.
then the Air changes for
temperature, introducing
pressure, and heat fresh outdoor
production of air
the can be different
double-skin facadedepending
cavity wereon the operation
analyzed
according
intention ofto the number
building andofonairirradiance.
changes. Therefore, when solar irradiance was at the high and middle
levels, three operation plans (number of air changes: 0.7, 1, and 1.3 times/h) were established, and
then the temperature, pressure, and heat production of the double-skin facade cavity were analyzed
according to the number of air changes.
Sustainability 2019, 11, 6238 17 of 24
Air changes for introducing fresh outdoor air can be different depending on the operation intention
of building and on irradiance. Therefore, when solar irradiance was at the high and middle levels,
three operation plans (number of air changes: 0.7, 1, and 1.3 times/h) were established, and then the
temperature, pressure, and heat production of the double-skin facade cavity were analyzed according
Sustainability 2019, 11, x FOR PEER REVIEW 17 of 24
to the number of air changes.
The
The cavity
cavity air air temperature
temperature on on the
the analysis
analysis days
days forfor solar
solar irradiance
irradiance in in winter
winter was was analyzed
analyzed
according to the number of air changes. Figure 15 shows the average cavity
according to the number of air changes. Figure 15 shows the average cavity air temperatures in the air temperatures in
the daytime
daytime (11:00–16:00)
(11:00–16:00) on on analysis
analysis days
days when
when solarirradiance
solar irradiancewas wasatatthe
the high
high and
and middle
middle levels
levels
according
according to the number of air changes. The lower the solar irradiance was, the smaller thethe
to the number of air changes. The lower the solar irradiance was, the smaller cavity
cavity air
air temperature
temperature difference
difference and and overall
overall temperaturedistribution
temperature distributionininthe theupper
upperand and lower
lower sides
sides of
of the
the
double-skin
double-skin facade facade were.
were. The
The cavity
cavity air
air temperatures
temperatures in in each
each alternative
alternative plan
plan were
wereanalyzed.
analyzed. AsAs aa
result, in all alternative plans, a similar temperature rise inclination remained from
result, in all alternative plans, a similar temperature rise inclination remained from 1F to TOP. With 1F to TOP. With the
application of an SC and a rise in its height, the temperature rise inclination found
the application of an SC and a rise in its height, the temperature rise inclination found in the lower in the lower side of
the
sideSCof(1F–TOP)
the SC (1F–TOP)remainedremained
constant,constant,
and the temperature in the SC zone
and the temperature in thegradually increased. increased.
SC zone gradually However,
in
However, in the ALT 3 that implemented thermal effect, the temperature rise inclination in thewas
the ALT 3 that implemented thermal effect, the temperature rise inclination in the SC zone SC
relatively larger, and thereby the temperature was the highest. With an increase
zone was relatively larger, and thereby the temperature was the highest. With an increase in the in the number of air
changes,
number of theairtemperature
changes, the rise inclination in
temperature allinclination
rise zones of the in double-skin facade
all zones of the became smaller
double-skin facade and the
became
temperature went down overall.
smaller and the temperature went down overall.
Figure
Figure15.15. Air
Air temperature
temperature distribution
distribution by
by ACH
ACH (air
(air change
change per
per hour)
hour) with
with high
high and
and middle
middle levels
levelsof
of
solar
solar irradiance.
irradiance.
Figure
Figure16 16 illustrates
illustratesthe
theaverage
averagecavity
cavitypressure
pressureininthe
the daytime
daytime (11:00–16:00)
(11:00–16:00)on onthethe analysis
analysis days
days
when
whensolar
solarirradiance
irradiancewaswasat atthe
thehigh
highlevel,
level,according
accordingto tothe
thenumber
numberof ofair
airchanges.
changes. With
With aa decrease
decrease
in
in solar
solar irradiance,
irradiance, thethe pressure
pressure difference
difference and
and overall
overall pressure
pressure inin the
the upper
upper and
and lower
lower sides
sides of
of the
the
double-skin facade were smaller. Each alternative plan had the following
double-skin facade were smaller. Each alternative plan had the following cavity pressure: cavity pressure:
In
In all
all the
the alternative
alternative plans,
plans, aa similar
similar pressure
pressure rise
rise inclination
inclination remained
remained from
from 1F1F to
to TOP.
TOP. With
With the
the
application
application of an SC and a rise in its height, the pressure rise inclination found in the lower side
of an SC and a rise in its height, the pressure rise inclination found in the lower side of
of
the
the SC
SC (1F–TOP)
(1F–TOP) remained
remained constant,
constant, andand the
the pressure
pressure inin the
the SC
SC zone
zone gradually
gradually increased.
increased. However,
However,
in the ALT 3 that implemented thermal effect, the pressure rise inclination in the SC zone was
relatively larger, and thereby the pressure was the highest. With an increase in the number of air
changes, the temperature difference and air density difference in the vertical direction of the double-
skin facade became smaller and the pressure went down overall.
Sustainability 2019, 11, 6238 18 of 24
in the ALT 3 that implemented thermal effect, the pressure rise inclination in the SC zone was relatively
larger, and thereby the pressure was the highest. With an increase in the number of air changes,
the temperature difference and air density difference in the vertical direction of the double-skin facade
became smaller and the pressure went down overall.
Sustainability 2019, 11, x FOR PEER REVIEW 18 of 24
Figure
Figure 17 17 presents
presents the
the average
average cavity
cavity air
air temperature
temperature and and pressure
pressure in
in the
the daytime
daytime (11:00–16:00)
(11:00–16:00)
when
when solar irradiance was at the low level. In terms of cavity air temperature, in
solar irradiance was at the low level. In terms of cavity air temperature, in all
all the
the alternative
alternative
plans,
plans, aa similar
similar temperature
temperature riserise inclination
inclination remained.
remained.However,
However,with withthe
theapplication
applicationofofan anSCSCand
anda
arise
riseininits
itsheight,
height,the
thetemperature
temperaturein inthe
theSCSC zone
zone remained
remained almost
almost same
same asas the
the temperature in the
temperature in the
TOP
TOP with
with no no temperature
temperature rise. In the
rise. In the ALT
ALT 33 thatthat implemented
implemented thermal
thermal effect,
effect, the
the air
air temperature
temperature
somewhat
somewhatincreased
increasedininthetheSCSCzone,
zone, butbut
its its
temperature
temperature riserise
waswas smaller thanthan
smaller that in thein1F–TOP
that zone.
the 1F–TOP
The overall temperature distribution was lower than that at the time when solar
zone. The overall temperature distribution was lower than that at the time when solar irradiance was irradiance was at the
high
at theandhigh middle levels.levels.
and middle In terms of cavity
In terms air temperature,
of cavity the application
air temperature, of an SC
the application and
of an SCa and
rise ainrise
its
height and thermal effect were not influential. In all the alternative plans, a small
in its height and thermal effect were not influential. In all the alternative plans, a small and similar and similar pressure
rise inclination
pressure remained remained
rise inclination in each vertical
in each zone. As the
vertical temperature
zone. difference difference
As the temperature and air density
and airdifference
density
in the vertical
difference direction
in the verticalofdirection
the double-skin facade became
of the double-skin smaller,
facade the smaller,
became pressurethewaspressure
lower than wasthat
lowerat
the time when solar irradiance was at the high and middle
than that at the time when solar irradiance was at the high and middle levels. levels.
Sustainability 2019, 11, x FOR PEER REVIEW 19 of 24
Figure 17. Air temperature and pressure distribution with low solar irradiance.
Figure 18 illustrates the temperature difference and pressure difference on the top and bottom
in each alternative plan on the basis of the average cavity air temperature and pressure in the daytime
Figure 17. Air temperature and pressure distribution with low solar irradiance.
(11:00–16:00) on analysis
Figure 17. Air days when solar
temperature irradiance
and pressure was at the
distribution withhigh,
low solarmiddle, and low levels. A
irradiance.
temperatureFiguredifference is the
18 illustrates thereference
temperaturetodifference
judge the available
and pressure heat of
difference thetop
on the double-skin
and bottom facade,
Figure
presenting 18 illustrates
the
in each difference
alternative the temperature
between
plan difference
the oftop
on the basis averageand
the temperature pressure
cavity and difference
outdoor
air temperature air on
and the top
temperature
pressure in and
the inbottom
each
in each alternative
daytime
alternative plan on the
(11:00–16:00)
plan. A pressure on basis of the
analysis
difference days average
means when cavity airbetween
solar irradiance
the difference temperature
was at the andpressure
high,
the top pressureand
middle, in the
and thedaytime
low bottom
levels.
(11:00–16:00) A temperature
oneach analysis difference
days when is the reference to judge the available heat of the double-skin facade,
(1F) pressure in alternative plan. solar
With irradiance
a rise in thewas solar at irradiance
the high, middle, and low levels.
of the double-skin A
facade,
presenting the difference between the top temperature and outdoor air temperature in each alternative
temperature
the temperature difference
and pressureis the differences
reference tobetween judge the the available
top and bottom heat of in theeachdouble-skin
alternativefacade,
plan
plan. A pressure difference means the difference between the top pressure and the bottom (1F) pressure
presenting
increased. Inthe
in each difference
particular,
alternative the between
plan. ALT
With a3 rise
thatthethetop
solartemperature
inimplemented irradiance of theand
thermal effectoutdoor
showed
double-skin air
facade, the temperature
thelargest in each
temperature
temperature
alternative
and and plan.
pressure pressure A pressure
differencesdifferences difference
by available
between the airmeans
and the
volumes,
top bottomdifference
showing between
the highest
in each alternative the top pressure
possibility
plan increased. of andproduction.
heat the bottom
In particular,
(1F) pressure
When the ALT
solar in3 that
each
irradiance alternative
implemented
was at the plan.
thermal With
loweffect aallrise
showed
level, inlargest
the the solar
alternative irradiance
temperature
plans ofsimilar
and pressure
showed the differences
double-skin by facade,
temperature and
available
the temperature air volumes,
andsopressure showing the highest
differences possibility
between of heat
the use production.
top ofand When
bottom solar
in eachirradiance was
alternative plan
pressure differences, that energy production with the solar heat was not different in each
at the low level, all alternative plans showed similar temperature and pressure differences, so that
increased. In
alternative particular, the ALT 3 that implemented thermal effect showed the largest temperature
plan.
energy production with the use of solar heat was not different in each alternative plan.
and pressure differences by available air volumes, showing the highest possibility of heat production.
When solar irradiance was at the low level, all alternative plans showed similar temperature and
pressure differences, so that energy production with the use of solar heat was not different in each
alternative plan.
heating air conditioning time when the original OA-based air volume was applied to the double-skin
facade used in this study. The lower the solar irradiance was, the higher the OA-based air volume was
and the greater the heating air conditioning time was. So, the baseline model had the smallest heating
air conditioning time overall. Based on the ALT1 with the greatest heating air conditioning time,
Sustainability
the average 2019, 11, x FOR
outdoor PEER REVIEW of heating air conditioning time in each one of the high, middle,
air temperature 20 of 24
and low levels of solar irradiance was calculated. As a result, the outdoor air temperature was highest
temperature was highest in the order of low level (3.44 ℃) > middle level (0.65 ℃) > high level (−3.54
in the order of low level (3.44 ◦ C) > middle level (0.65 ◦ C) > high level (−3.54 ◦ C) of solar irradiance.
℃) of solar irradiance.
Table 6. Air conditioning time (h) by ALT and AHC.
Table 6. Air conditioning time (h) by ALT and AHC.
Category BASE(O) 1) AHC Baseline ALT1 ALT2 ALT3
Category BASE(O)1) AHC Baseline ALT1 ALT2 ALT3
0.7 153 156 157 157
0.7 153 156 157 157
High High 148 148 1.0
1.0 156
156 158 158 163 163
158 158
1.3
1.3 159
159 162 162 166 166164 164
0.7
0.7 182
182 187 187 185 185
187 187
Middle Middle 176 176 1.0
1.0 185
185 191 191 196 196
190 190
1.3
1.3 190
190 193 193 198 195
198 195
Low Low 398 398 0.7
0.7 398
398 420 420 403 403
403 403
0.7
0.7 733
733 763 763 745 747
745 747
Total Total 722 722 1.0
1.0 739
739 769 769 762 751
762 751
1.3
1.3 747
747 775 775 767 762
767 762
1)1)ACH (OAairflow
ACH 0.4 (OA airflow9600
9600 CMH)
CMH).
Figure
Figure19 19shows
showsthe theannual
annual indoor
indoor heating
heating load
load in each alternative plan according
alternative plan according to to solar
solar
irradiance. Compared to the BASE (O) model, all alternative plans had relatively higher
irradiance. Compared to the BASE (O) model, all alternative plans had relatively higher heating heating loads.
Figure
loads.20 presents
Figure the total the
20 presents heating
totalload (including
heating indoor heating
load (including indoorload) according
heating to solar irradiance.
load) according to solar
As shown inAs
irradiance. theshown
figure,inwith the application
the figure, of an SC and
with the application a rise
of an in its
SC and height,
a rise in itsand also and
height, an increase
also an
inincrease
OA-based air volume,
in OA-based the load the
air volume, wasload
high overall.
was However,
high overall. the ALT3
However, the that
ALT3applied thermal
that applied effect
thermal
toeffect to had
the SC the SC had a somewhat
a somewhat lower
lower load load
than than Therefore,
ALT2. ALT2. Therefore,
ALT2 had ALT2thehad the highest
highest annualannual
indoor
indoor load.
heating heating load.
Figure2019,
Sustainability 23 11,
shows
x FORthe heating
PEER REVIEWenergy use rate of each alternative plan for the BASE (O) model in
22 of 24
Sustainability 2019, 11, 6238
terms of the original OA-based air volume of the double-skin facade. With the application of an SC 22 of 24
and Figure
a rise 23in shows the heating
its height, energycapacity
the available use rate of each alternative
the solar plan for
irradiance of the BASE (O) model
double-skin in
facade
terms of the original OA-based air volume of the double-skin facade. With
increased, and thereby the use rate of heating energy increased. With a rise in the OA-based airthe application of an SC
Figure 23 shows the heating energy use rate of each alternative plan for the BASE (O) model
and a rise
volume in itsalternative
in each height, the available
plan, the usecapacity
rate alsoof the solarThe
increased. irradiance
ALT3 that of applied
the double-skin facade
thermal effect to
in terms of the original OA-based air volume of the double-skin facade. With the application of an
increased,
the SC hadand the thereby
highest the use energy
heating rate of use
heating
rate.energy
When ACHincreased. With
was 1.3, a rise
it was in the to
possible OA-based air
use heating
SC and a rise in its height, the available capacity of the solar irradiance of the double-skin facade
volume in each
energy about 7.6alternative
times higherplan, thethe
than useBASE(O)
rate alsomodel.
increased.
FigureThe24ALT3 thatthe
presents applied thermal
annual heatingeffect
energyto
increased, and thereby the use rate of heating energy increased. With a rise in the OA-based air
the SC had the
production highest
capacity of heating energy use
the double-skin rate. in
facade When
eachACH was 1.3,
alternative it was
plan possibletotoOA-based
according use heating air
volume in each alternative plan, the use rate also increased. The ALT3 that applied thermal effect to
energy
volume. about
The 7.6 timesenergy
heating higherproduction
than the BASE(O)
capacitymodel.
of theFigure 24 presents
double-skin facade the annual the
presents heating energy
heating loss
the SC had the highest heating energy use rate. When ACH was 1.3, it was possible to use heating
production
load ratio incapacity of the double-skin
the installation facade in each
side of the double-skin alternative
facade plan
for the net according
solar to OA-based
heat-based air
energy of the
energy about 7.6 times higher than the BASE(O) model. Figure 24 presents the annual heating energy
volume. The facade
double-skin heatingofenergy production
the building, whichcapacity
uses theof cavity
the double-skin facade presents
as the preheating path of the heating loss
air conditioning
production capacity of the double-skin facade in each alternative plan according to OA-based air
load
OA. ratio in the installation side of the double-skin facade for the net solar heat-based energy of the
volume. The heating energy production capacity of the double-skin facade presents the heating loss
double-skin facade of the building, which uses the cavity as the preheating path of air conditioning
load ratio in the installation side of the double-skin facade for the net solar heat-based energy of the
OA.
double-skin facade of the building, which uses the cavity as the preheating path of air conditioning OA.
double-skin facade. Nevertheless, when the capacity exceeds ‘1’ at least, it is judged that the heating
energy generated by the double-skin facade has productivity. According to the analysis, the BASE(O)
model with the original OA-based air volume of the double-skin facade used in this study had a
heating energy production capacity of 1.23. With the application of an SC and a rise in its height,
the heating energy production capacity increased. With an increase in OA-based air volume in each
alternative plan, the heat production capacity also went up. In the ALT3 that applied thermal effect to
the SC, when the ACH was 1.3, the heating energy production capacity was the highest, at 2.74.
In the winter evaluation, the indoor load according to the OA-based air volume and the OA
based-heat through the double-skin facade was analyzed in each SC-based alternative plan proposed
to improve the heat performance of the double-skin facade. The higher the OA-based air volume
was, the higher the double-skin facade-based heat was. The range that began to make the increase in
double-skin facade-based heat remain constant was chosen as the appropriate OA-based air volume
range (the high and middle levels of solar irradiance: 26,000 CMH or less, the low level of solar
irradiance: 15,000 CMH or less). In the chosen OA-based air volume range, as solar irradiance increased,
the temperature difference and pressure of the cavity in the upper and lower sides of the double-skin
facade increased, and thereby the available heat through the double-skin facade went up. In addition,
with the application of an SC and a rise in its height, the available capacity of the solar irradiance of
the double-skin facade rose and the heating energy use rate increased. Among the alternative plans,
the ALT3 that applied thermal effect had the highest heating energy use rate. In ALT3, when the ACH
was 1.3, it was possible to use heating energy about 7.6 times higher than the original performance of
the double-skin facade operated with ACH 0.4. Therefore, the heating energy production capacity in
ALT3 was the highest, at 2.74. According to the winter evaluation, with the application of an SC and a
rise in its height, the heating energy saving was excellent. When thermal effect was applied to the SC,
the heating energy utilization effect of solar irradiance of the double-skin facade was large.
5. Conclusions
In order to propose an improved operation plan for a double-skin facade for reducing the indoor
load in winter, this study analyzed the thermal phenomenon through the field measurement of the
double-skin facade of a real building. In addition, with the use of an energy analysis tool, it verified
the effect of the improvement plan. This study came to the following conclusions:
(1) To find the actual state of operation of a double-skin facade in winter, this study measured the
target building. As a result, if an appropriate air volume control strategy is applied to reduce the
outer skin load and outdoor air load, in terms of the OA use of the preheated air through the
double-skin facade, it is possible to save a great deal of energy. Accordingly, this study proposed
a solar chimney-based double-skin facade as a passive alternative plan to improve ventilation
and energy performance across the seasons.
(2) The solar chimney-based double-skin facade was analyzed in winter. As a result, with the
application of a solar chimney and a rise in its height, the available capacity of relatively larger
solar heat increased, and therefore the proposed plan had excellent performance in terms of
heating energy saving. When thermal effect was applied to the solar chimney, the heating energy
use effect of solar irradiance of the double-skin facade was larger. When thermal effect was
applied to the three-floor solar chimney, the heating energy use increased to about 7.6 times
higher than that of the original performance of the double-skin facade.
Author Contributions: U.-J.S. managed the project and wrote the manuscript. S.-H.K. wrote and edited
the manuscript.
Funding: This work was supported by the Korea Institute of Energy Technology Evaluation and Planning (KETEP)
and the Ministry of Trade, Industry & Energy (MOTIE) of the Republic of Korea (No. 20162010104270).
Sustainability 2019, 11, 6238 24 of 24
Acknowledgments: This work was supported by the Korea Institute of Energy Technology Evaluation
and Planning (KETEP) and the Ministry of Trade, Industry & Energy (MOTIE) of the Republic of Korea
(No. 20162010104270).
Conflicts of Interest: The authors declare no conflict of interest.
References
1. Pomponi, F.; Piroozfar, P.A.E.; Southall, R.; Ashton, P.; Farr, E.R.P. Energy performance of Double-Skin
Facades in temperate climates: A systematic review and meta-analysis. Renew. Sustain. Energy Rev. 2016, 54,
1525–1536. [CrossRef]
2. Kassai, M. Effectiveness and humidification capacity investigation of liquid-to-air membrane energy
exchanger under low heat capacity ratios at winter air conditions. J. Therm. Sci. 2015, 24, 391–397. [CrossRef]
3. Stec, W.J.; Van Paassen, A.H.C.; Maziarz, A. Modelling the double skin facade with plants. Energy Build.
2005, 37, 419–427. [CrossRef]
4. Stec, W.J.; Van Paassen, A.H.C. Symbiosis of the double skin facade with the HVAC system. Energy Build.
2005, 37, 461–469. [CrossRef]
5. Chou, S.K.; Chua, K.J. A study on the effects of double skin facades on the energy management in buildings.
Energy Convers. Manag. 2009, 50, 2275–2281. [CrossRef]
6. Xu, L.; Ojima, T. Field experiments on natural energy utilization in a residential house with a double skin
facade system. Build. Environ. 2007, 42, 2014–2023. [CrossRef]
7. Gratia, E.; De Herde, A. Is day natural ventilation still possible in office buildings with a double-skin facade?
Build. Environ. 2004, 39, 399–409. [CrossRef]
8. Gratia, E.; De Herde, A. Natural cooling strategies efficiency in an office building with a double-skin façade.
Energy Build. 2004, 36, 1139–1152. [CrossRef]
9. Gratia, E.; De Herde, A. Natural ventilation in a double-skin façade. Energy Build. 2004, 36, 137–146.
[CrossRef]
10. Gratia, E.; De Herde, A. Are energy consumptions decreased with the addition of a double-skin? Energy Build.
2004, 39, 605–619. [CrossRef]
11. Gratia, E.; De Herde, A. Greenhouse effect in double-skin façade. Energy Build. 2004, 39, 199–211. [CrossRef]
12. Gratia, E.; De Herde, A. Guidelines for improving natural daytime ventilation in an office building with a
double-skin façade. Sol. Energy 2004, 81, 435–448. [CrossRef]
13. Gratia, E.; De Herde, A. The most efficient position of shading devices in a double-skin façade. Energy Build.
2007, 39, 364–373. [CrossRef]
14. Andelkovic, A.S.; Mujan, I.; Dakic, S. Experimental validation of a EnergyPlus model: Alication of a
multi-storey naturally ventilated double skin facade. Energy Build. 2016, 118, 27–36. [CrossRef]
15. Kassai, M. Experimental investigation on the effectiveness of sorption energy recovery wheel in ventilation
system. Exp. Heat Transf. 2018, 31, 106–120. [CrossRef]
© 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).