Professional Documents
Culture Documents
Case Studies in Thermal Engineering: Sciencedirect
Case Studies in Thermal Engineering: Sciencedirect
A R T IC LE I N F O ABS TRA CT
Keywords: With high incident solar radiations on the East-West facades under the tropical climate of
Double skin facade Malaysia, the indoor spaces adjacent to the glazed facades will become overheated. The appli-
Adjacent spaces cation of Double skin-facade (DSF) is one of the solar heat gain control techniques in the tropics.
West direct solar radiation This study aims to investigate the effectiveness of the DSF in controlling the heat gain under the
Glazing surface temperature
direct solar radiation of the West orientation in the tropics, Malaysia. Investigation was con-
Indoor/outdoor air temperature
ducted in a certified energy-efficient building with DSF. A general space of the lift lobby ad-
joining the DSF oriented west was investigated. Indoor/Outdoor air-temperatures, surface tem-
peratures, Global/Vertical-west solar radiation and indoor air velocities were measured during
the longest days of the summer solstice from 21st to 30th of June. The results indicated that the
double skin façade DSF is effective in controlling the heat gain occurrence due to the variation of
temperature between outdoor and indoor and the differences in surface temperatures. It is,
however, inadequate to protect indoor from the penetration of the tropical direct solar radiation.
The peak indoor air temperature varies from 26.4 °C to 27.6 °C in the adjacent general space to
the DSF, thus increasing the building cooling requirements.
1. Introduction
The architects and building designers have given more emphasis to the lightness and the transparency of buildings leading to
highly glazed office buildings. This increases the heat gain indoors, which eventually consumes excessive energy for space con-
ditioning and produces a negative impact on the environment due to the associated CO2 emissions.
The application of double-skin facades (DSF) is a notable solution in the tropics for many improvements such as a solar heat gain
control, thermal buffer zone, energy savings and aesthetics [1]. In terms of the role of DSF in reducing solar heat gain in the tropical
countries, it is useful to understand the two means that represent the total heat gain through glazing. The primary mode is the heat
gain due to direct solar radiation, whereas the second is the heat transfer due to the differences in temperature between outdoor and
indoor air temperature and the heat radiation by glazing surfaces [2]. However, preventing direct solar radiation from penetrating
the glazing surfaces is a main solution to be applied to the glazed buildings in the tropics [3].
Hence, a question may be raised as to what extent the double skin façade DSF in the “Security Commission Building” (SCB),
Malaysia, contributes to reducing the total heat gain indoors, under the direct solar radiation of West DSF. To answer the question,
this study aims to investigate the effect of DSF on the reduction of solar heat gain.
a) due to the difference in temperature between ambient and indoor spaces and,
b) due to the exposure of DSF to direct solar radiation that penetrates indoors, in addition to the differences in surface temperatures
https://doi.org/10.1016/j.csite.2019.100419
Received 12 January 2019; Received in revised form 13 February 2019; Accepted 16 February 2019
Available online 21 February 2019
2214-157X/ © 2019 The Author. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license
(http://creativecommons.org/licenses/BY-NC-ND/4.0/).
A.M. Qahtan Case Studies in Thermal Engineering 14 (2019) 100419
of the DSF.
A general space of a lift lobby in a certified Energy Efficient Office Building (EEB), which is “Security Commission Building” (SCB)
in Kuala Lumpur, Malaysia, was the case study chosen to be investigated. The results of the investigation will enhance the efficiency
of the system design for future applications.
Malaysian buildings receive high solar radiation, mainly in the west-façades in the afternoons, causing overheating and large
energy consumption of buildings, so the inclusion of fully glazed facade in buildings is conventionally not recommended [4]. The
application of DSF is an interesting solution for controlling solar heat gain thus enhancing the energy efficient design of the glazed
buildings besides to gain in the aesthetics aspects. However, DSF is a system consisting three elements: the skin construction of two
layers of glazing, the transparency of the bounding surfaces, and the cavity airflow [5].
Many studies on DSF were carried out under different climate regions to examine the appropriateness of the system in enhancing
the indoor environment of the glazed buildings. The study conducted by Ref. [6] involved an experimental and simulation method to
study a DSF on a commercial building in Dublin, Ireland. The DSF was south facing and was extensively observed during winter
months. The study concluded that DSFs are appropriate for passive, low energy architecture in temperate climates. Another study
investigated the energy performance of DSFs in two different climates, temperate and warmer region. A west facing DSFs were
compared. The study concluded that DSFs are more suitable for temperate climates than warmer one. It also found that DSFs are
capable of almost 50% energy savings in temperate and 16% in subtropical climates [7].
Building with DSF showed that the exterior surface temperature of the outer skin was high when the absorptive glazing was
placed outside [8]. A study conducted under a warm climate of Italy by Ref. [9] concluded that in summer, the solar heat is mainly
absorbed by the outer skin of the DSF and there is no significant influence on the inner skin and then on the internal environment,
thus, reducing building cooling requirements. In summary, high temperatures of the glass surface could result in uncomfortable
indoor conditions particularly the spaces near DSF [10].
However, in order to prevent an overheating of inside the cavity of DSF and then inside the building spaces, the protection from
direct solar radiation is recommended. Depending on the type of the glass, an advanced glazing could prevent the heat flow via
glazing surface into indoors [8]. The use of low emissivity (Low-e) glazing as an outer surface of the DSF is suitable. Low-e glass
(external) reflects the infrared wavelengths contributing to a reduction in solar load gain of 40% if glazing transmissivity was set to
55% [11].
With respect to the thermal performance of the cavity, [12] reported that under direct solar radiation of the hot-arid climate, the
temperature in the cavity of the DSF was found to be higher than outside air temperature. The temperature in the cavity remained
high during the night due to the greenhouse effect of the DSF. Another study reported that a temperature of the air in the cavity of
West DSF exposed to high solar radiation, remains higher than outdoor during the whole day. The differences between air tem-
perature in the cavity and the outdoor air temperature fluctuates between 2 °C (night) and 10 °C (day) [13].
Generally, buildings in Malaysia, as in tropics, have two means of heat gain. The first is due to the difference in temperature
between indoor/outdoor. In Malaysia this variation was found reaching to 5 °C peak, [14], which can be controlled effectively by
using low-e glass. This thin film of low-e have a high transmittance in visible range (light) and very high reflectance in long-wave
infrared range (heat) [17]. The second is the direct solar radiation, where Malaysia receives a high solar radiation [2]. The difficulty
of using low-e glazing under the direct solar radiation in the tropics is that the near-infrared radiation (NIR) is still able to transfer
through the glass. This NIR radiation heating up indoor surfaces and re-emitted heat as a long wave IR radiation which cannot
transmit through the low-e glass increasing indoor temperature due to the greenhouse effect [16]. This becomes a disadvantage to the
low-e glass in the tropics, even with extra solution of DSF. This study, as mentioned earlier, concerns on this matter through a field
investigation.
Climate has a significant influence on a building's performance, therefore the climate parameters need to be understood. The
climate of Malaysia has the characteristics of a hot-humid tropical climate. It has been reported by Ref. [14] that Malaysia receives an
annual total radiation of above 4.31kwh/m2, and about 10h of sunshine per a day. This causes a higher indoor temperature, which
needs more energy for artificial cooling in order to succeed in providing thermal comfort in the workspace. The monthly sunshine
duration ranging from 9 to 13 h, with a monthly average of solar radiation according to the data from Subang Jaya station varied
from 4 to 4.6 kWh/m2. The highest monthly average was recorded in February and September with 4.52 and 4.6 kWh/m2 respec-
tively. The lower solar radiation occurs in December to January with 4 to 4.2kWh/m2 respectively. Moreover, with respect to the
solar radiation on the building façade in Malaysia, Ref. [18] has reported that the maximum of solar radiation which faces vertical
walls would vary from 300 Wh/m2 to 250 Wh/m2 throughout the year. This increases the heat gain in indoor spaces particularly the
spaces behind the fully glazed facades.
In general, the climate of Malaysia can be described as typical tropical climate, with no large variations in temperature during the
months of the year. According to the data from the meteorological station of Subang Jaya (10 years), the mean monthly temperature
2
A.M. Qahtan Case Studies in Thermal Engineering 14 (2019) 100419
Table 1
Monthly Dry Bulb temperature °C and Relative Humidity, average 10 years, (source: author based on Subang jaya Station).
Months 1 2 3 4 5 6 7 8 9 10 11 12
Solar Radiation (Kwh-m2) 4.2 4.5 4.5 4.2 4.1 4.3 4.3 4.5 4.6 4.5 4.2 4.0
Temperature (° C) 27.2 27.5 27.9 27.8 28.4 28.0 27.7 27.8 27.5 27.3 27.0 27.1
was found to vary approximately not more than 1.4 °C difference, from the mean 27.0 °C in November to 28.4 °C in May as sum-
marises in Table 1. The variation significantly occurs throughout the day with approximately 7.4 °C difference found between the
daytime and night-time in February and March and approximately 6.5 °C difference between the daytime and night-time in November
and December as summarises in Table 2.
However, designing the energy efficient buildings (non-residential buildings) under the Malaysian climate are required to achieve
an acceptable indoor condition and conform the requirements of the Malaysian Standard, MS 1525: 2007, as summarised in Table 3.
The Securities Commission (SCB), is a mid-rise office building built in 1997. It is located at Bukit Kiara in Kuala Lumpur, Malaysia.
It won the ASEAN Energy Award in 2001 [19]. The building has a gross floor area of 94,288 m2 and comprises 6-level podium (with a
three level below grade car park) and five level office tower Fig. 1. The SCB is constructed with double skin facades that comprises of
two layers of glass with a cavity of 1.2 m Fig. 2. The external skin is (12 mm) thick low-e tinted green glass and the internal one is
(8 mm) thick green glass. Air gap serving as a maintenance walkway and a cool buffer zone. Shading devices, both horizontal louvers
and vertical blinds, are installed within the DSF cavity. The vertical blinds protect the workspace from the direct solar radiation
particularly on the east and west facades and controlled by solar cell. Cooled air from the office space is recycled and exhausted at
ceiling levels into the DSF cavity.
4. Methodology
The study adapts a field investigation in order to make a thermal analysis of a DSF exposed to direct solar radiation in tropical
building during the longest days of the summer solstice, 21st to 30th of June. The study obtained the analysis of these “10” days
including the weekend measurements feedback. The field measurements were carried out in a selected general space of a lift-lobby,
adjoining a west-facing DSF of the SCB. The study collected data using 7 sensors connected to the “Babuc/A” data logger, for indoor
measurements and “Skye” data logger for outdoor measurements. The variables monitored are, indoor/outdoor air temperatures,
outer/inner glazing surface temperatures and global solar radiation (horizontal) and solar radiation on vertical surfaces orientated
west. The indoor sensors were placed on a tripod located at 1.0 m above the floor level and in the centre of the lift lobby space. The
outdoor sensor was located on the rooftop of the building as shown in Fig. 3. The data logger recorded the readings at 5 min intervals
for twenty-four hours duration. Manual readings were recorded from Thermometer's readings and infrared thermometer in order to
minimise errors. The investigation of this case study is an attempt to assess the thermal behaviour of the west double skin facade.
Measurements were taken in summer, June 21st to 30th for a general space adjacent to the DSF that is exposed to west direct solar
radiation. Table 4 summarises the results of 10 days including the weekend. The 26th and 27th presented the weekend with no air-
conditioning, the remaining days are working days with air-conditioning. An average hourly (6am-6pm) of several variables were
plotted to illustrate the findings of the study. These measured variables are the outdoor/indoor air temperatures, indoor air velocity,
surfaces temperatures of the DSF (outer surface and inner surface), together with global solar radiation and direct vertical solar
radiation.
The study started with monitoring the temperature variation between outdoor and indoor in the lift lobby adjacent to the DSF
facing west orientation. The results will be plotted for the daytime from 6am to 6pm. The emphasis of the discussion will be the
afternoon time when the direct solar radiation hits the façade of the investigated space, the lift lobby. Table 4, also, illustrates the
variation between outdoor and indoor air temperature. This table shows that the average hourly outdoor air temperature ranged from
Table 2
Hourly solar radiation (kWh/m2) and Dry Bulb temperature °C, average 3 years, (source: author based on Subang jaya Station).
Hours 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Average, Dry Bulb Tem. (° C) 24.7 24.6 24.9 26.4 28.2 29.6 30.6 31.3 31.6 31.4 30.8 30.0 29.1 28.3 27.5
Average, Solar Rad. (kWh/m2) 0.0 0.0 0.0 1.0 2.7 4.1 5.2 5.6 5.3 4.6 3.4 2.2 1.1 0.2 0.0
3
A.M. Qahtan Case Studies in Thermal Engineering 14 (2019) 100419
Table 3
The recommended indoor condition of MS 1525: 2007.
Recommended dry bulb temperature °C 23 °C - 26 °C
Recommended relative humidity (RH) 55%–70%
Recommended air movement 0.15 m/s to 0.5 m/s
Minimum dry bulb temperature 22 °C
Minimum air movement 0.7 m/s
Fig. 1. 3rd floor Plan showing the investigated lift lobby and perspective view for the SCB (Source: [15]).
Fig. 2. Detailed section (Source: SCB technical report) and View from the cavity walkway, showing vertical and horizontal shading (Source:
Author).
25.6 °C at 8am to 32.7 °C at 1pm. The air velocity fluctuates between 0.0 m/s on weekend to 0.1 m/s average 7 working days.
Fig. 4 shows the average indoor/outdoor air temperature and indoor air velocity during the daytime from 6am to 6pm. The plot
on the left side of Fig. 4 shows the results of the average 6 working days in the lift lobby where the air-conditioner was running, and
air velocity was fluctuating between 0.04 m/s to 0.06 m/s. It shows that indoor air temperature reached 26.4 C at 1:50 p.m. when the
outdoor air temperature was 32.1 °C, with variation of about 5 °C. At about 2:30pm the outdoor temperature dropped to 27.7C,
affected by rain and the changes of the sky condition. It is noticeable, although the outdoor air temperature decreases, the indoor air
temperature did not follow the outdoor air temperature. The indoor air temperature remained the same with a negligible reduction
from 26.4 C to 26.2 °C. The plot on the right side of Fig. 4 shows the results of two off-days (26th and 27th) in the lift lobby, where the
indoor air velocity appears to be almost 0.0 m/s, and the indoor air temperature gradually increased with the increase of outdoor air
4
A.M. Qahtan Case Studies in Thermal Engineering 14 (2019) 100419
Fig. 3. Setting up Data loggers indoor (left), and outdoor (right) (source: Author).
Table 4
Hourly average temperature for Working days and the non-working days of “8” tested days of June.
Date/time Measured parameters Average Hourly-(day time,8 a.m. – 6pm)
8 9 10 11 12 13 14 15 16 17 18
Working days Outdoor Air Temp. °C 25.6 27.1 28.5 30 30.7 31.7 31.1 28.3 28 27.9 27.4
21-25&28–30 June Indoor Air Temp. °C 25.3 25.3 25.5 25.7 26.0 26.2 26.4 26.3 26.2 26.2 26.1
Outer.-G-Surface-Te °C 26.1 28.0 30.5 32.6 34.7 36.2 35.3 32.4 33.7 32.7 29.6
Inner.-G-surface-Te °C 25.5 26.2 27.3 28.4 29.4 30.4 30.5 29.6 29.5 29.5 28.4
West solar Rad. W/m2 67.4 115.6 164.8 196.1 234.3 236.4 220.7 156.2 205.8 125.3 36.7
Ind-Air-Velo,.m/s 0.05 0.03 0.04 0.03 0.03 0.02 0.02 0.03 0.03 0.03 0.02
Off-days Outdoor Air Temp. °C 24.3 26.8 29.6 31.3 32 32.7 31.8 32.2 31.6 30.8 29.9
6&27 June Indoor Air Temp. °C 25.2 25.4 25.6 25.8 25.9 26.2 26.5 26.8 27 27.5 27.5
Outer-G-Surface-Te °C 25.4 27.6 28.6 30 31.6 34.2 35.3 36.5 38.3 41.9 34.6
Inner-G-surface-Te °C 25.1 26.1 26.9 27.6 28.4 29.5 30.4 31 31.9 34 31.9
West solar Rad.,W/m2 67.4 147 151.7 156.7 174.8 225.4 213.2 281.9 236 304.1 73
Ind-Air-Velo., m/s 0.01 0 0 0 0 0 0 0 0 0 0
temperature reaching 26.4 °C at 1:50 p.m. where the outdoor air temperature was 33.1 °C, with variation of about 6.5 °C. At 2pm, the
Outdoor air temperature slightly decreases reaching 31.2 °C at 5:35pm. It is noticeable that on the average two off-days 26th & 27th,
although the outdoor air temperature decreases, the indoor air temperature kept increasing to reach 27.6 °C at 5:10pm where the
vertical west solar radiation was 585 W/m2 and the temperatures of outer-skin, inner skin and outdoor air temperature were 45 °C,
5
A.M. Qahtan Case Studies in Thermal Engineering 14 (2019) 100419
Fig. 5. The average 24 h for all investigated days, including working and weekend days.
5.2. Effect of DSF surfaces temperature on the total solar heat gain indoors
When direct solar radiation hits the DSF a portion of solar energy is absorbed, reflected as well as transmitted indoors. As
mentioned earlier the outer skin of the investigated DSF is a low-e glass with high reflection to inferred energy. However, the study in
this context is to show how the direct solar radiation increases the surfaces temperature of the DSF. Then how the indoor air
temperature varies as a function of the direct solar radiation and surface temperature of the DSF.
Fig. 5 shows the measured variables of 8 different days, including the weekend, of June. These variables are the surfaces tem-
peratures of the DSF (outer surface and inner surface), together with the outdoor/indoor air temperature and the direct vertical solar
radiation. It can be seen from Fig. 5 that the outer low-e glass of the measured west façade of SCB has a high value of surface
temperature compared to the outdoor air temperature. The measurements were conducted in the afternoon time for 8 days, with
maximum variation between outdoor air temperature and outer surface temperature of about 15 °C on 28th and minimum variation
of 5 °C on 23rd of June. The surface temperature of the inner skin (tinted glass), was recorded during the 8 days, also remain high
under the direct solar radiation with a peak of 36 °C at 4pm on 28th of June. However, the changes of the results from day to day is
Fig. 6. The relation between indoor and surface temperature, lift lobby −12pm-7pm.
6
A.M. Qahtan Case Studies in Thermal Engineering 14 (2019) 100419
Fig. 7. The relation between direct vertical solar radiations (west) and indoor air temperature.
7
A.M. Qahtan Case Studies in Thermal Engineering 14 (2019) 100419
outdoor air temperature decreased from 33.7 °C at 12:30 p.m. to 31.0 °C at 3:50 p.m., whereas, indoor air temperature kept gradually
increasing even with the decrease of both global solar radiation and outdoor air temperature.
It should be noted that this study does not give a measure of the condition at the workstations in SCB. It gives an image on the
thermal performance of the DSF and its effect on the general spaces adjoining the DSF of the investigated building. Fig. 8 shows the
behaviour of indoor air temperature in both spaces of the SCB, a general space of a lift-lobby and a workspace. The plot on the left
side of Fig. 8 shows the indoor air temperature in a lift lobby facing west oriented DSF. The indoor air temperature during the
working hours varies between 24 °C and 26.4 °C, when outdoor air temperature reached 32 °C. Whereas, the plot on the right side of
Fig. 8 shows the indoor air temperature in a workspace facing west oriented DSF as well. The indoor air temperature during the
working hours was maintained at 21 °C, when outdoor air temperature reached to 33 °C. This variation in temperature values is due to
the differences in a space volume and the air-conditioning system. However, the average temperature values in the lift-lobby space
remain within the thermal comfort range recommended by the Malaysia standards (MS 1525: 2007.) as given in Table 3. The results,
in general, confirm that the DSF of SCB contributes in reducing the solar heat gain through the west façade under the tropical climate
of Malaysia. Even though the DSF helps protecting indoors from excessive heat, the west orientation of DSF buildings in the tropics
still needs a direct shading to prevent a penetration of the direct solar radiation.
The study adapts a field investigation methodology in order to make a thermal analysis of a DSF exposed to direct solar radiation
in a tropical building during the longest days of the summer solstice, 21st to 30th of June. The study obtained the analysis of these
“10” days including the weekend measurement feedback.
The study started with monitoring an adjacent space to DSF in relation to the temperature variation between outdoor and indoor
in the lift lobby facing west orientation. It is noticeable, although the outdoor air temperature decreases, the indoor air temperature
remained the same and in some cases, indoor air temperature kept increasing despite the reduction of outdoor air temperature.
The study showed that in the tropical climate of Malaysia, the contribution of outdoor air temperature to the heat gain through
DSF is almost non-existent. While the direct solar radiation and consequently the double-glazing surfaces temperature have a clear
impact in increasing the indoor air temperature. In the SCB, DSF in average plays a positive role in reducing heat gain as it integrates
additional strategies such as low-e film placed onto the exterior side of the glass, cooling the cavity, horizontal and vertical shading
devises. In summary, the western façade needs direct shading, so that the SCB incorporated motorized blinds for the workspaces.
It is advisable to introduce an advanced solar control glazing instead of the DSF with a large cavity in such a climate as that of
Malaysia, where the variations between outdoor and indoor air is not very high and the main contribution to the indoor temperature
is the direct solar radiation.
Acknowledgements
This study was supported by the University of Malaya under the project no RP009/2012A and RG 130/11SUS.
References
[1] M.M. Ahmed, A.K. Abel-Rahman, A.H. Ali, a. M. Suzuki, Double skin façade: the state of art on building energy efficiency, J. Clean Energy Technol. 4 (1) (2016)
84–89.
[2] A. Qahtan, N. Keumala, S. Rao, Z. Abdul-Samad, Experimental determination of thermal performance of glazed façades with water film, under direct solar
radiation in the tropics, Build. Environ. 46 (2011) 2238–2246, https://doi.org/10.1016/j.buildenv.2011.05.001.
[3] A.H. Abdullaha, Q. Meng, L. Zhao, F. Wang, Field study on indoor thermal environment in an atrium in tropical climates, Build. Environ. 44 (2) (2009) 431–436.
[4] M.M. Aboulnaga, Towards green buildings: glass as a building element—the use and misuse in the gulf region, Renew. Energy 31 (5) (2006) 631–653.
[5] M.A. Haggag, Building skin and energy efficiency in a hot climate with particular reference to Dubai, UAE, Ecol. Environ. 105 (2007) 1743–3541, https://doi.
8
A.M. Qahtan Case Studies in Thermal Engineering 14 (2019) 100419
org/10.2495/ESUS070291.
[6] O. Kinnane, T. Prendergast, Assessment of the double-skin façade passive thermal buffer effect, 30th International Plea Conference, EPT University, Ahmedabad,
Ahmedabad, 2014, pp. 1–8.
[7] M. Khoshbakht, Z. Gou, K. Dupre, H. Altan2, Thermal environments of an office building with double skin facade, J. Green Build. 12 (3) (2017) 3–22, https://doi.
org/10.3992/1943-4618.12.3.3.
[8] S.K. Lee, H.-J. Chen, K.-S. Fan, H.-C. Hsi, R.S. Horng, Thermal performance and durability properties of the window glazing with exterior film(s), Indoor Built
Environ. 23 (8) (2014) 1163–1176.
[9] G. Baldinelli, Double skin façades for warm climate regions: analysis of a solution with an integrated movable shading system, Build. Environ. (2009)
1107–1118.
[10] Appleton Yagoub, Stevens, Case study of double skin façade in hot climates, Proceedings of Conference: Adapting to Change: New Thinking on Comfort, Network
for Comfort and Energy Use in Buildings, London, 2010.
[11] A. Guardo, M. Coussirat, E. Egusquiza, P. Alavedra, R. Castilla, CFD approach to evaluate the influence of construction and operation parameters on the perfor-
mance of active transparent facades in Mediterranean climates, Energy Build. 41 (2009) 534–542.
[12] N. Hashemi, R. Fayaz, M. Sarshar, Thermal behavior of a ventilated double skinfacade in hot arid climate, Energy Build. 42 (2010) 1823–1832.
[13] S.F. Larsena, L. Rengifob, C. Filippín, Double skin glazed facades in sunny Mediterranean climates, Energy Build. (2015) 18–31.
[14] A.T. Qahtan, N. Keumala, S.P. Rao, Z.A. Samad, Field analysis of thermal comfort in two energy efficient office buildings in Malaysia, Texas A&M University,
Proceedings of the Tenth International Conference for Enhanced Building Operations, Energy Systems Laboratory, Kuwait, 2010, pp. 1–9 Retrieved from http://
esl.tamu.edu http://www.tamu.edu http://oaktrust.library.tamu.edu/handle/1969.1/94096.
[15] ESCI-KSP, Securities Commission Building, (2019, January 11) Retrieved from SB-1.2 Low Energy Building Demonstration Projects: https://esci-ksp.org/project/
securities-commission-building/?task_id=603.
[16] H. Chowdhury, M.B. Cortie, Thermal stresses and cracking in absorptive solar glazing, Constr. Build. Mater. 21 (2) (2007) 464–468.
[17] J. Mohelnikova, Materials for reflective coatings of window glass applications, Constr. Build. Mater. 23 (5) (2009) 1993–1998.
[18] A. Zain-Ahmed, Climate Change, Green Technology and Sustainable Buildings, University Publication Center, UiTM, Kula Lumpour, 2009.
[19] W. Hong, M.S. Chiang, R.A. Shapiro, M.L. Clifford, Building Energy Efficiency, Why Green Buildings Are Key to Asia’s Future, Asia Business Council, Hong Kong,
2007.