3AH5 Vacuum Circuit-Breakers

Medium-Voltage Equipment
Selection and Ordering Data

Catalog HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers

R-HG11-172.tif

2 Siemens HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers Contents

Contents Page

3AH5 Vacuum Description 5


Circuit-Breakers General
Construction and mode of operation, standards
6
7
1
Ambient conditions, current carrying capacity
Medium-Voltage Equipment
and dielectric strength 9
Catalog HG 11.05 · 2007 Product range overview and basic equipment 10

Invalid:
Catalog HG 11.11 · 1999, Part 4 and
Catalog HG 11.12 · 2005, Part 4 Equipment Selection 11
Ordering data and configuration example
Selection of basic types, circuit-breakers
12
13
2
Selection of secondary equipment 15
Additional equipment 20
Accessories and spare parts 21

Technical Data 25
Electrical data, dimensions and weights
Operating times, short-circuit protection
26
3
of motors, consumption data of releases 31
Circuit diagrams 32

Annex 33
Inquiry form
Configuration instructions
34
35 4
Configuration aid Foldout page

© Siemens AG 2007

Siemens HG 11.05 · 2007 3


3AH5 Vacuum Circuit-Breakers

R-HG11-173.tif

4 Siemens HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers Description
Contents

Contents Page

Description 5
General 6 1
Construction and mode of operation:
Pole assemblies 7
Operating mechanism box 7
Operating mechanism 7
Trip-free mechanism 7
Releases 8
Closing 8
Interlocking 8

Standards 8
Ambient conditions 9
R-HG11-174.tif

Current carrying capacity 9


Dielectric strength 9
Industrial application: Refinery
Product range overview and basic equipment 10

Siemens HG 11.05 · 2007 5


Description 3AH5 Vacuum Circuit-Breakers
General

3AH5 vacuum circuit-breaker from 12 to 36 kV – The Economical

3AH5 vacuum circuit-breakers control all switching duties tors, capacitors, filter circuits, motors and reactors.
in medium-voltage systems. They are applicable for oper- Here, small short-circuit ratings in distribution systems

1 ation of e.g. overhead lines, cables, transformers, genera- face high breaking currents in industrial systems.

3AH5 – the universal circuit-breaker in the product range R-HG11-201.eps

R-HG11-185.eps

The 3AH5 vacuum circuit-breaker is a real all-round device in rents as well as various pole-center distances for voltage
its field of application. With its compact dimensions, it fits in levels from 12 kV to 36 kV enables its universal application
all customary switchgear types. The comprehensive variety for all medium-voltage requirements.
of types with different normal currents and short-circuit cur-

6 Siemens HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers Description
Construction and mode of operation

The 3AH5 vacuum circuit-breaker consists of the pole as-


semblies (1) and the operating mechanism box (2). The pole
assemblies are fixed to the operating mechanism box via 3 6
post insulators (3). The switching movement is transferred
by means of operating rods (4) and levers. 1

Pole assemblies
The pole assemblies consist of the vacuum interrupters (5)
2
5
1
and the interrupter supports. The vacuum interrupters are 8

air-insulated and freely accessible. This makes it possible to


7
clean the insulating parts easily in adverse ambient condi-

HG11-2543 eps
4
tions. The vacuum interrupter is rigidly fixed to the upper
interrupter support (6). The lower part of the interrupter is
guided in the lower interrupter support (7), allowing axial Circuit-breaker structure
movement. The braces (8) absorb the external forces result-
ing from switching operations and the contact pressure. 1 Pole assembly 5 Vacuum interrupter
2 Operating mechanism box 6 Upper interrupter support
Operating mechanism box 3 Post insulator 7 Lower interrupter support
4 Operating rod 8 Brace
The whole operating mechanism with releases, auxiliary
switches, indicators and actuating devices is accommodated
in the operating mechanism box.
The extent of the secondary equipment depends on the
case of application and offers a multiple variety of options
in order to meet almost every requirement.

Operating mechanism
For circuit-breaker operation, both spring-operated and
stored-energy mechanisms are available. With manual
spring-operated mechanisms, the closing process takes place
automatically after manual charging of the closing spring.
The opening or contact springs are charged simultaneously
R-HG11-186.tif

during the closing operation, which means that a stored-


energy mechanism is available for the opening operation.
With motor or manual operating stored-energy mechanisms, Front view
the closing spring is either charged electrically or manually.
It latches tight at the end of the charging process and serves
as an energy store.
To close the breaker, the closing spring can be unlatched
either mechanically by means of the local “ON” pushbutton
or electrically by remote control. The closing spring charges
the opening or contact pressure springs as the breaker closes.
The now discharged closing spring will be charged again
automatically by the mechanism motor or manually. Then
the operating sequence OPEN-CLOSE-OPEN is stored in the
springs.

Trip-free mechanism
R-HG11-187.tif

3AH5 vacuum circuit-breakers have a trip-free mechanism ac-


cording to IEC 62271-100. In the event of an opening com-
mand being given after a closing operation has been initiated,
Open operating mechanism box
the moving contacts return to the open position and remain
there even if the closing command is sustained. This means
that the contacts of the vacuum circuit-breakers are momen-
tarily in the closed position, which is permissible according to
IEC 62271-100.

Siemens HG 11.05 · 2007 7


Description 3AH5 Vacuum Circuit-Breakers
Construction and mode of operation, standards

Releases An electrical closing lock-out prevents unpermissible closing


A release is a device which transfers commands from an of the circuit-breaker. The closing lock-out releases the
external source, such as a control room, to the latching operation of the circuit-breaker when auxiliary voltage is
mechanism of the vacuum circuit-breaker so that it can be available, and blocks both local manual closing and remote
opened or closed. The maximum possible equipment is one electrical closing mechanically when there is no auxiliary

1 shunt release and another release to be selected at will.


For release combinations, refer to page 15.
• The closing solenoid unlatches the charged closing spring
voltage available.
The operating voltage of the electrical closing lock-out is the
same as that of the 1st release. If constant CLOSE and OPEN
of the vacuum circuit-breaker, closing it by electrical means. commands are present at the vacuum circuit-breaker at the
same time, the vacuum circuit-breaker will return to the
• Shunt releases are used for automatic tripping of vacuum
open position after closing. It remains in this position until
circuit-breakers by suitable protection relays and for deliber-
a new CLOSE command is given. In this manner, continuous
ate tripping by electrical means. They are intended for con-
closing and opening (= “pumping”) is prevented.
nection to an external power supply (DC or AC voltage) but,
in special cases, may also be connected to a voltage trans-
former for manual operation. Interlocking
• Current-transformer operated releases comprise a stored- Mechanical interlocking for stored-energy mechanisms
energy mechanism, an unlatching mechanism and an elec- To interlock circuit-breaker trucks, withdrawable parts or
tromagnetic system. They are used when there is no exter- disconnectors according to the switch position, the stored-
nal source of auxiliary power (e.g. a battery). Tripping is energy mechanisms of 3AH5 circuit-breakers can be
effected by means of a protection relay (e.g. overcurrent- equipped with a mechanical interlocking. A sensor at the
time protection) acting on the current-transformer operated switchgear checks the position of the circuit-breaker and
release. prevents the open circuit-breaker in a reliable way from
• Undervoltage releases comprise a stored-energy mecha- being closed mechanically and electrically.
nism, an unlatching mechanism and an electromagnetic Electrical interlocking
system which is permanently connected to the secondary or The vacuum circuit-breakers can be integrated in electro-
auxiliary voltage while the vacuum circuit-breaker is closed. magnetic feeder or switchgear interlocks. In case of elec-
If the voltage falls below a predetermined value, unlatching trical interlocking, the disconnector or its operating mecha-
of the release is enabled and the circuit-breaker is opened nism is equipped with a magnetic lock-out mechanism.
via the stored-energy mechanism. The deliberate tripping This mechanism is controlled by an auxiliary contact of the
of the undervoltage release generally takes place via an NC circuit-breaker, so that the disconnector can only be oper-
contact in the tripping circuit or via an NO contact by short- ated when the circuit-breaker is open. On the other hand,
circuiting the magnet coil. With this type of tripping, the the vacuum circuit-breaker is also controlled by the discon-
short-circuit current is limited by the built-in resistors. nector or its operating mechanism, so that it can only be
Undervoltage releases can also be connected to voltage closed when the disconnector is in an end position. For this
transformers. When the operating voltage drops to im- purpose, the circuit-breaker operating mechanism must be
permissibly low levels, the circuit-breaker is tripped auto- equipped with a closing lock-out (see “Closing”).
matically.
For delayed tripping, the undervoltage release can be Standards
combined with energy stores. The vacuum circuit-breakers conform to the following
standards:
Closing • IEC 62271-100 (former IEC 60056)
In the standard version of the stored-energy mechanisms, • IEC 60694 (in future IEC 62271-1)
3AH5 vacuum circuit-breakers can be remote-closed elec- • VDE 0671 (former VDE 0670 Part 100
trically. They can also be closed locally by mechanical un- and VDE 0670 Part 1000)
latching of the closing spring via pushbutton. With spring- All 3AH5 vacuum circuit-breakers fulfil the endurance
operated mechanisms, closing takes place after the charging classes E2, M2 and C2 according to IEC 62271-100.
process.

8 Siemens HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers Description
Ambient conditions, current carrying capacity and dielectric strength

Ambient conditions
The vacuum circuit-breakers are designed for the normal
operating conditions defined in IEC 62271-100.
Condensation can occasionally occur under the ambient
conditions shown opposite. 3AH5 vacuum circuit-breakers
are suitable for use in the following climatic classes accord-
ing to IEC 60721, Part 3-3:
40°C
1
Climatic ambient conditions: Class 3K4 1)
max. 95% per day
Biological ambient conditions: Class 3B1 max. 90% per month
-5°C
Mechanical ambient conditions: Class 3M2
Chemically-active substances: Class 3C2 2)

HG11-2515a_en eps
Mechanically-active substances: Class 3S2 3)
1) Low temperature limit: – 5 °C
2) Without icing and wind-driven precipitation
3) Restriction: Clean insulation parts

Current carrying capacity


The rated normal currents specified in the opposite diagram 3400
have been defined according to IEC 62271-100 for an am- A
3000
Rated normal current

bient temperature of + 40 °C and apply to open switchgear.


For enclosed switchgear the data of the switchgear manufac- 2600
turer applies.
4
At ambient temperatures below + 40 °C, higher normal 2200
currents can be carried (see diagram): 3
1800
Characteristics curve 1 = Rated normal current 800 A
Characteristics curve 2 = Rated normal current 1250 A 1400

HG11-2545c_en eps
2
Characteristics curve 3 = Rated normal current 2000 A
1000
Characteristics curve 4 = Rated normal current 2500 A 1

600
Dielectric strength 10 20 30 40 50 60 °C 70
Ambient temperature
The dielectric strength of air insulation decreases with
increasing altitude due to low air density. According to
IEC 60694, the rated lightning impulse withstand voltage
values specified in the chapter “Technical Data” apply to a
site altitude of 1000 m above sea level. For an altitude
above 1000 m, the insulation level must be corrected 1.50
according to the opposite diagram.
Altitude correction factor

The characteristic shown applies to the rated short-duration 1.40


power-frequency withstand voltage and the rated lightning
impulse withstand voltage. 1.30
To select the devices, the following applies:
U W U0 x Ka 1.20
U Rated withstand voltage under standard reference atmosphere
HG11-2517c_en eps

U0 Rated withstand voltage requested for the place of installation


1.10
Ka Altitude correction factor according to the opposite diagram

Example 1.00
1000 1500 2000 2500 3000 3500 m 4000
For a requested rated lightning impulse withstand voltage Site altitude
of 75 kV at an altitude of 2500 m, an insulation level of
90 kV under standard reference atmosphere is required as
a minimum:
90 kV W 75 kV x 1.2

Siemens HG 11.05 · 2007 9


Description 3AH5 Vacuum Circuit-Breakers
Product range overview and basic equipment

Product range overview


circuit breaking

Rated normal current (A)


Rated voltage

Rated short-

800 1250 2000 2500


current

Pole-center distance (in mm)

1 kV
12
kA
13.1
160
n
210
n
275 160 210 275 350 210 275 350 210 275

16 n n n n
20 n n n n n
25 n n n n n
31.5 n n n
17.5 25 n n n n n
31.5 n n n
24 16 n n n n
20 n n n n n n
25 n n n n
36 16 n n
25 n n n

Basic equipment

Features Minimum equipment Alternative equipment Remarks

Operating mechanism Manual spring-operated Manual operating stored-energy mechanism Manual operating mechanism
mechanism Motor operating stored-energy mechanism always with hand crank
Closing Manual closing Closing solenoid Closing solenoid only with
stored-energy mechanisms
1st release Shunt release – –
2nd release Without Shunt release, –
undervoltage release,
c.t.-operated release
Varistor circuit Installed for W 60 V DC – For limiting switching overvoltages
Auxiliary switch 2 NO + 2 NC 6 NO + 6 NC 12 NO + 12 NC
12 NO + 12 NC Only with 64-pole plug
Plug connector Without 24-pole terminal strip 24-pole plug
24-pole plug Not with 12 NO + 12 NC
64-pole plug
Anti-pumping – For motor operating stored-energy mechanism –
Circuit-breaker Without Possible –
tripping signal
Operating cycle counter Available – –
Electrical closing Without Possible Prevents unpermissible closing
lock-out of the circuit-breaker
Interlocking Without Mechanical interlocking –

10 Siemens HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers Equipment Selection
Contents

Contents Page

Equipment Selection 11
Ordering data and configuration example 12

Selection of basic types, circuit-breakers:


Voltage level 12 kV 13
Voltage level 17.5 kV 13
Voltage level 24 kV 14
Voltage level 36 kV 14

Selection of secondary equipment:


Equipment features
Tripping combination
15
15
2
Operating voltage, closing solenoid 16
Operating voltage, 1st shunt release 16
R-HG11-184.tif

Operating voltage, 2nd release 17


Counter and circuit-breaker tripping signal 18
3AH5 135-6 vacuum circuit-breaker
Operating voltage for operating mechanism/
mechanism type 18
Auxiliary switch, secondary connection,
interlocking 19
Languages and frequency 19
Additional equipment 20

Accessories and spare parts 21


R-HG11-188.eps

3AH5 204-1 vacuum circuit-breaker

Siemens HG 11.05 · 2007 11


Equipment Selection 3AH5 Vacuum Circuit-Breakers
Ordering data and configuration example

Order number structure Special versions ( ) «


The 3AH5 vacuum circuit-breakers consist of a primary and In case of special versions, “-Z” is added to the order number
a secondary part. The relevant data make up the 16-digit and a descriptive order code follows. If several special versions
order number. The primary part covers the main electrical are required, the suffix “-Z” is listed only once. If a requested
data of the circuit-breaker poles. The secondary part covers special version is not in the catalog and can therefore not be
the auxiliary devices which are necessary for operating and ordered via order code, it has to be identified with Y 9 9 after
controlling the vacuum circuit-breaker. consultation. The agreement hereto is made between your
Order codes responsible sales partner and the order processing depart-
ment (PTD M C S) in our Switchgear Factory in Berlin.
Individual equipment versions, marked with 9 or Z in the
9th or 16th position, are explained more in detail by a 3-digit
order code. Several order codes can be added to the order
number in succession and in any sequence.

2 Position:
Order No.:
a: alphabetical
1 2
3 A H 5
3 4 5
n
n: numerical
6
n
7
n


8
n
9
a
10 11 12 –
a n n –
13 14 15 16
n a a n –
Order codes
« n n n
Primary part
1st position Superior group
Switching devices

2nd position Main group


Circuit-breaker

3rd position Subgroup


Circuit-breaker type series

4th to 8th position Basic equipment


Design and ratings
primary part

Secondary part
9th to 16th position Secondary equipment
Operating mechanism, releases, operating
voltages and further auxiliary equipment

Order codes
Group of 3 after the Order No.
Format: a n a

Special versions ( )«
Initiated with “-Z”
Group of 3 after the Order No.
Format: a n n

Configuration example
In order to simplify the selection of the correct order number
for the requested circuit-breaker type, you will find a con-
figuration example on each side of the chapter “Equipment
Selection”. For the selection of the secondary part, always the
last example of the primary part was taken over and continued, On the foldout page we offer a configuring aid.
so that at the end of the equipment selection (page 20) a Here you can fill in the order number you have deter-
completely configured circuit-breaker results as an example. mined for your circuit-breaker.

Example for Order No.: 3 A H 5 1 2 2 – 1 n n n n – n n n n


Order codes:

12 Siemens HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers Equipment Selection
Selection of basic types, circuit-breakers

12 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A H 5 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % DC component

Rated normal current


Rated short-duration

Pole-center distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

power-frequency

breaking current

making current
Rated voltage

(at 50/60 Hz)

See page 15
See page 16
See page 16
See page 17

See page 18
See page 18
See page 19
See page 19

See page 20
Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm A
12 75 28 13.1 33/34 160 800 3 A H 5 1 2 1 – 1
210 800 3 A H 5 1 3 1 – 1
16 40/42 160 800 3 A H 5 1 2 2 – 1
1250 3 A H 5 1 2 2 – 2
210 800 3 A H 5 1 3 2 – 1

2
1250 3 A H 5 1 3 2 – 2
20 50/52 160 800 3 A H 5 1 2 3 – 1
1250 3 A H 5 1 2 3 – 2
210 800 3 A H 5 1 3 3 – 1
1250 3 A H 5 1 3 3 – 2
2000 3 A H 5 1 3 3 – 4
25 63/65 160 800 3 A H 5 1 2 4 – 1
1250 3 A H 5 1 2 4 – 2
210 800 3 A H 5 1 3 4 – 1
1250 3 A H 5 1 3 4 – 2
2500 3 A H 5 1 3 4 – 6
31.5 80/82 160 1250 3 A H 5 1 2 5 – 2
210 1250 3 A H 5 1 3 5 – 2
2500 3 A H 5 1 3 5 – 6

17.5 kV
50/60 Hz
Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm A
17.5 95 38 25 63/65 160 800 3 A H 5 2 0 4 – 1
1250 3 A H 5 2 0 4 – 2
210 800 3 A H 5 2 1 4 – 1
1250 3 A H 5 2 1 4 – 2
2500 3 A H 5 2 1 4 – 6
31.5 80/82 160 1250 3 A H 5 2 0 5 – 2
210 1250 3 A H 5 2 1 5 – 2
2500 3 A H 5 2 1 5 – 6
Special version (available for all 17.5 kV circuit-breakers)
Ud = 42 kV – Z E 1 3

Configuration example
3AH5 vacuum circuit-breaker 3 A H 5
Rated voltage Ur = 17.5 kV
Rated short-circuit breaking current Isc = 25 kA
Rated normal current Ir = 2500 A
Pole-center distance = 210 mm 2 1 4 – 6
Special version Ud = 42 kV – Z E 1 3

Example for Order No.: 3 A H 5 2 1 4 – 6 n n n n – n n n n – Z


Order codes: E 1 3

Siemens HG 11.05 · 2007 13


Equipment Selection 3AH5 Vacuum Circuit-Breakers
Selection of basic types, circuit-breakers

24 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A E 1 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % DC component

Rated normal current


Rated short-duration

Pole-center distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

power-frequency

breaking current

making current
Rated voltage

(at 50/60 Hz)

See page 15
See page 16
See page 16
See page 17

See page 18
See page 18
See page 19
See page 19

See page 20
Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm A
24 125 50 16 40/42 210 800 3 A H 5 2 7 2 – 1
1250 3 A H 5 2 7 2 – 2
275 800 3 A H 5 2 8 2 – 1
1250 3 A H 5 2 8 2 – 2
20 50/52 210 1250 3 A H 5 2 7 3 – 2

2
2000 3 A H 5 2 7 3 – 4
2500 3 A H 5 2 7 3 – 6
275 1250 3 A H 5 2 8 3 – 2
2000 3 A H 5 2 8 3 – 4
2500 3 A H 5 2 8 3 – 6
25 63/65 210 1250 3 A H 5 2 7 4 – 2
2500 3 A H 5 2 7 4 – 6
275 1250 3 A H 5 2 8 4 – 2
2500 3 A H 5 2 8 4 – 6

36 kV
50/60 Hz
Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm A
36 170 70 16 40/42 275 1250 3 A H 5 3 2 2 – 2
350 1250 3 A H 5 3 1 2 – 2
25 63/65 275 1250 3 A H 5 3 2 4 – 2
350 1250 3 A H 5 3 1 4 – 2
2000 3 A H 5 3 1 4 – 4

Configuration example
3AH5 vacuum circuit-breaker 3 A H 5
Rated voltage Ur = 36 kV
Rated short-circuit breaking current Isc = 25 kA
Rated normal current Ir = 2000 A
Pole-center distance = 350 mm 3 1 4 – 4

Example for Order No.: 3 A H 5 3 1 4 – 4 n n n n – n n n n


Order codes:

14 Siemens HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers Equipment Selection
Selection of secondary equipment

Equipment features for the different types of operating mechanisms


Type of operating

1st shunt release


Closing solenoid

plug connection

plug connection
Auxiliary switch

Auxiliary switch

Auxiliary switch
12 NO + 12 NC
Circuit-breaker
tripping signal

terminal strip

terminal strip
2 NO + 2 NC

6 NO + 6 NC

interlocking
mechanism

Mechanical
2nd release

Counter

Without

24-pole

24-pole

64-pole
Manual spring-
operated mechanism – n n Ð Ð – Ð Ð Ð –

Manual operating
stored-energy mechanism n n Ð Ð – Ð Ð Ð –

Motor operating
stored-energy mechanism n n n – Ð Ð – Ð Ð Ð

n Basic equipment Ð Optionally selectable basic equipment Selectable additional equipment – Not available

9th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


n n n n n n n n n n n n « n n n
Release combination Order No.: 3 A H 5 – – –
2
Undervoltage release

C.t.-operated release

C.t.-operated release

C.t.-operated release

C.t.-operated release
with tripping pulse

with tripping pulse


2nd shunt release
1st shunt release

W 0.1 Ws (10 O)

W 0.1 Ws (20 O)

See page 16
See page 16
See page 17

See page 18
See page 18
See page 19
See page 19

See page 20
0.5 A

1.0 A

n M
n n N
n n R
n n U
n n U – Z A 4 6
n n V
n n V – Z A 4 5

Configuration example
3AH5 vacuum circuit-breaker 3 A H 5
(Ur = 36 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 350 mm) 3 1 4 – 4
1st shunt release; c.t.-operated release with 1.0 A U – Z A 4 6

Example for Order No.: 3 A H 5 3 1 4 – 4 U n n n – n n n n – Z


Order codes: A 4 6

Siemens HG 11.05 · 2007 15


Equipment Selection 3AH5 Vacuum Circuit-Breakers
Selection of secondary equipment

10th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Operating voltage of the closing solenoid Order No.: 3 A H 5 n n n – n n n n n – n n n n – « n n n

See page 17

See page 18
See page 18
See page 19
See page 19

See page 20
Standard voltages Special voltages

To be observed for selection!


• Manual spring-operat. mechan. generally without closing solenoid (A)
• Man. operat. stored-energy mechan. option. with closing solenoid (A – Z)
• Motor op. stored-energy mech. generally with closing solenoid (B – Z)

Without closing solenoid A


24 V DC B
48 V DC C
60 V DC D
110 V DC E
220 V DC F
100 V AC 50/60 Hz 1) H

2 110 V AC
230 V AC
50/60 Hz 1)
50/60 Hz 1)
30 V DC
J
K
Z With order code K 1 A
32 V DC Z With order code K 1 B
120 V DC Z With order code K 1 C
125 V DC Z With order code K 1 D
127 V DC Z With order code K 1 E
240 V DC Z With order code K 1 F
120 V AC 50/60 Hz 1) Z With order code K 1 K
125 V AC 50/60 Hz 1) Z With order code K 1 L
240 V AC 50/60 Hz 1) Z With order code K 1 M

11th position
Operating voltage of the 1st shunt release

Standard voltages Special voltages

24 V DC 1
48 V DC 2
60 V DC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6
110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 V DC 9 With order code L 1 A
32 V DC 9 With order code L 1 B
120 V DC 9 With order code L 1 C
125 V DC 9 With order code L 1 D
127 V DC 9 With order code L 1 E
240 V DC 9 With order code L 1 F
120 V AC 50/60 Hz 1) 9 With order code L 1 K
125 V AC 50/60 Hz 1) 9 With order code L 1 L
240 V AC 50/60 Hz 1) 9 With order code L 1 M
1) The AC frequency 50 or 60 Hz is selected at the 16th position
of the order number together with the language (see page 19)

Configuration example
3AH5 vacuum circuit-breaker 3 A H 5
(Ur = 36 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 350 mm) 3 1 4 – 4 U
Operating voltage of the closing solenoid 48 V DC (manual operating stored-energy mechanism) C
Operating voltage of the 1st shunt release 48 V DC 2

Example for Order No.: 3 A H 5 3 1 4 – 4 U C 2 n – n n n n – Z


Order codes: A 4 6

16 Siemens HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers Equipment Selection
Selection of secondary equipment

12th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Operating voltage of the 2nd release Order No.: 3 A H 5 n n n – n n n n n – n n n n – « n n n

See page 18
See page 18
See page 19
See page 19

See page 20
Standard voltages Special voltages

Without, or c.t.-operated release 0


24 V DC 1
48 V DC 2
60 V DC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6
110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 V DC 9 With order code M 1 A
32 V DC 9 With order code M 1 B
120 V DC 9 With order code M 1 C
125 V DC
127 V DC
240 V DC
9
9
9
With order code
With order code
With order code
M
M
M
1 D
1 E
1 F
2
120 V AC 50/60 Hz 1) 9 With order code M 1 K
125 V AC 50/60 Hz 1) 9 With order code M 1 L
240 V AC 50/60 Hz 1) 9 With order code M 1 M
Special version
To operate the 2nd release as an undervoltage release on an
energy store type AN1902- (for DC) or AN1902-2 (for AC),
both make Bender, the operating voltage must be defined –
and whether the energy store will be provided by the customer
or included in the scope of supply.

Energy store
Type In the scope of delivery
60 V DC AN1902- no 9 With order code M 2 D
110 V DC AN1902- no 9 With order code M 2 E
220 V DC AN1902- no 9 With order code M 2 F
100/110/230 V AC AN1901-2 no 9 With order code M 2 G
60 V DC AN1902- yes 9 With order code M 3 D
110 V DC AN1902- yes 9 With order code M 3 E
220 V DC AN1902- yes 9 With order code M 3 F
100/110/230 V AC AN1901-2 yes 9 With order code M 3 G

1) The AC frequency 50 or 60 Hz is selected at the 16th position


of the order number together with the language (see page 19)

Configuration example
3AH5 vacuum circuit-breaker 3 A H 5
(Ur = 36 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 350 mm) 3 1 4 – 4 U C 2
2nd release as c.t.-operated release with 1.0 A 0

Example for Order No.: 3 A H 5 3 1 4 – 4 U C 2 0 – n n n n – Z


Order codes: A 4 6

Siemens HG 11.05 · 2007 17


Equipment Selection 3AH5 Vacuum Circuit-Breakers
Selection of secondary equipment

13th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Counter and circuit-breaker tripping signal Order No.: 3 A H 5 n n n – n n n n n – n n n n – « n n n
Attention! The selection of the counter and the circuit-breaker tripping
signal depends on the selection of the secondary connection.
Without terminal

24-pole terminal

15th position n
Circuit-breaker
tripping signal

(see page 19)


64-pole plug

See page 19
See page 19

See page 20
Definition
strip/plug

strip/plug
Counter

n ¡ A, B 1 n
n 1) ¡ 1) E, F, G
and H 1 n
n n ¡ E, F, G
and H 2 n
n 1) n 1) ¡ 1) J, K, L
and M 5 n
n Equipment to be selected ¡ Dependent equipment
1) Equipment only possible in combination with motor operating stored-

2 energy mechanism

14th position
Operating voltage of the operating mechanism/
type of operating mechanism

Standard voltages Special voltages

Manual operat. stored-energy mechan. (hand crank incl. in the scope of supply) A
Manual spring-operated mechan. (hand crank incl. in the scope of supply) X

Motor operating stored-energy mechan. (selection of an operating voltage)


24 V DC B
48 V DC C
60 V DC D
110 V DC E
220 V DC F
100 V AC 50/60 Hz 2) H
110 V AC 50/60 Hz 2) J
230 V AC 50/60 Hz 2) K
30 V DC Z With order code P 1 A
32 V DC Z With order code P 1 B
120 V DC Z With order code P 1 C
125 V DC Z With order code P 1 D
127 V DC Z With order code P 1 E
240 V DC Z With order code P 1 F
120 V AC 50/60 Hz 2) Z With order code P 1 K
125 V AC 50/60 Hz 2) Z With order code P 1 L
240 V AC 50/60 Hz 2) Z With order code P 1 M

2) The AC frequency 50 or 60 Hz is selected at the 16th position


of the order number together with the language, see page 19

Configuration example
3AH5 vacuum circuit-breaker 3 A H 5
(Ur = 36 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 350 mm) 3 1 4 – 4 U C 2 0 –
With counter and circuit-breaker tripping signal 2
Manual operating stored-energy mechanism A

Example for Order No.: 3 A H 5 3 1 4 – 4 U C 2 0 – 2 A n n – Z


Order codes: A 4 6

18 Siemens HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers Equipment Selection
Selection of secondary equipment

15th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Auxiliary switch, secondary connection, interlocking Order No.: 3 A H 5 n n n – n n n n n – n n n n – « n n n
Attention! The selection of these options depends on the already
selected counter and circuit-breaker tripping signal
(13th position)
12 NO + 12 NC 2)
Auxiliary switch

Auxiliary switch

Auxiliary switch

terminal strip 1)
13th position n

2 NO + 2 NC 1)
(see page 18)

terminal strip

See page 18

See page 20
6 NO + 6 NC

interlocking
Mechanical
Definition

Without

24-pole

24-pole

64-pole
plug 2)
plug

1 n n n A
1 n n n n B
1 2) or 2 n n n E3)
1 2) or 2 n n n n F3)
1 2) or 2 n n n G3)
1 2) or 2 n n n n H3)
5 n n n J4)
5 n n n n K4)
n n n
5
5 n
Special versions gold-plated contacts and pins
n n n
L4)
M4) 2
Auxiliary switch 6 NO + 6 NC and 64-pole plug connector (J or K) – Z A 2 0
Auxiliary switch 12 NO + 12 NC and 64-pole plug connector (L or M) – Z A 2 1

1) Not possible with motor operating stored-energy mechanism


2) Only possible with motor operating stored-energy mechanism
3) Electrical components are wired to the lower part of the plug.
The free auxiliary switch connections are not wired
4) Electrical components are wired to the lower part of the plug.
The auxiliary switches are wired to the lower part of the plug according
to the circuit diagrams

16th position
AC frequency of operating voltages
Languages of operating instructions and rating plate

Language Frequency

German 50 Hz or DC 0
60 Hz 1
English 50 Hz or DC 2
60 Hz 3
French 50 Hz or DC 4
60 Hz 5
Spanish 50 Hz or DC 6
60 Hz 7
Other languages on request
Special versions
Additional information on the rating plate (only after consultation
with Dept. PTD M C S, Berlin). Information in clear text. – Z Y 1 2

Configuration example
3AH5 vacuum circuit-breaker 3 A H 5
(Ur = 36 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 350 mm) 3 1 4 – 4 U C 2 0 – 2 A
Auxiliary switch 6 NO + 6 NC, 24-pole plug and mechanical interlocking H
Frequency 50 Hz or DC, operating instructions and rating plate in English 2

Example for Order No.: 3 A H 5 3 1 4 – 4 U C 2 0 – 2 A H 2 – Z


Order codes: A 4 6

Siemens HG 11.05 · 2007 19


Equipment Selection 3AH5 Vacuum Circuit-Breakers
Additional equipment

Additional equipment Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Order No.: 3 A H 5 n n n – n n n n n – n n n n – « n n n

Options

Wiring cables, halogen-free and flame-retardant – Z A 1 0


Condensation protection, heating for 230 V AC, 50 W – Z A 3 0
Silicone-free design – Z A 3 1
With electrical closing lock-out 1) (not for 3AH512, 3AH520) – Z A 4 7
Additional rating plate, loose delivery – Z B 0 0
Routine test certificate enclosed – Z F 2 0
Hand crank (also with motor operating mechanism)
for manual charging of the closing spring – Z F 3 0
Further non-listed special versions (only after consultation
with Dept. PTD M C S, Berlin). Information additionally in clear text – Z Y 9 9
1) The operating voltage of the closing lock-out is the same
as that of the 1st shunt release.

Configuration example
3AH5 vacuum circuit-breaker 3 A H 5
Rated voltage Ur = 36 kV
Rated short-circuit breaking current Isc = 25 kA
Rated normal current Ir = 2000 A
Pole-center distance = 350 mm 3 1 4 – 4
1st shunt release, c.t.-operated release with 1.0 A U – Z A 4 6
Operating voltage of the closing solenoid 48 V DC C
Operating voltage of the 1st shunt release 48 V DC 2
2nd release as c.t.-operated release with 1.0 A 0 –
With counter and breaker tripping signal 2
Manual operating stored-energy mechanism A
Auxiliary switch 6 NO + 6 NC, 24-pole plug and mechanical interlocking H
Frequency 50 Hz or DC, operating instructions and rating plate in English 2
With electrical closing lock-out (not for 3AH512, 3AH520) – Z A 4 7
Routine test certificate enclosed – Z F 2 0

Example for Order No.: 3 A H 5 3 1 4 – 4 U C 2 0 – 2 A H 2 – Z


Order codes: A 4 6 + A 4 7 + F 2 0

20 Siemens HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers Equipment Selection
Accessories and spare parts

Retrofitting Accessories for the plug connector


When releases/solenoids are retrofitted, the order num- Included in the scope of supply of the basic equipment for
bers of the built-on parts must also be specified. For other 3AH5 vacuum circuit-breakers:
additional equipment, the required mounting parts are For 24-pole plug connector
included in the delivery.
– Lower part of plug
– Crimp sockets acc. to number of contacts
Spare parts – Upper part of plug with screw contacts
When releases/solenoids are required as spare parts, the (no crimp sockets required)
order number and the type of construction of the associated For 64-pole plug connector
circuit-breaker type must also be specified.
– Lower part of plug
– Upper part of plug
Remark for orders – Crimp sockets according to number of contacts
The order numbers are applicable to circuit-breakers of cur-
rent manufacture. When mounting parts or spare parts are
Vacuum interrupters and other spare parts must only be
being ordered for an existing vacuum circuit-breaker, always
replaced by instructed personnel.
quote the type designation, serial number, design code and
the year of manufacture of the circuit-breaker to be sure to
get the correct delivery.
2

Designation Remarks Operating voltage Order No.

Hand crank 3AX15 30-2B


Lubricant (for special application conditions)
180 g Klüber-Isoflex Topas L32N 3AX11 33-3H
1 kg Klüber-Isoflex Topas L32N 3AX11 33-3E
1 kg Shell Tellus oil 32 (special oil) 3AX11 33-2D
Operating solenoid
Used as closing solenoid or 24 V DC 3AY15 10-5B
1st shunt release 30/32 V DC 3AY15 10-5M
48 V DC 3AY15 10-5C
Including varistor 60 V DC 3AY15 10-5D
100/120 V DC 3AY15 10-5E
125/127 V DC 3AY15 10-5N
220/240 V DC 3AY15 10-5F
Including rectifier 100 – 125 V AC, 50/60 Hz 3AY15 10-5E
230/240 V AC, 50/60 Hz 3AY15 10-5F
2nd shunt release
Without varistor, without rectifier 24/32 V DC 3AX11 01-2B
Including varistor 48/60 V DC 3AX11 01-2C
110/127 V DC 3AX11 01-2E
220/240 V DC 3AX11 01-2F
Including rectifier 100/125 V AC, 50 Hz 3AX11 01-2G
230/240 V AC, 50 Hz 3AX11 01-2J
100/125 V AC, 60 Hz 3AX11 01-3G
230/240 V AC, 60 Hz 3AX11 01-3J
Mounting parts (for retrofitting) With one existing shunt release 3AX16 11-2A
Current-transformer
operated release For rated normal current 0.5 A, including varistor and rectifier 3AX11 02-2A
For rated normal current 1.0 A, including varistor and rectifier 3AX11 02-2B
For tripping pulse W 0.1 WS, for protection system 7SJ451 (10 O) 3AX11 04-0B
For tripping pulse W 0.1 WS, for protection relay 7SJ45 and SEG WIP 1 (20 O) 3AX11 04-2B
Mounting parts (for retrofitting) With one existing shunt release 3AX16 11-2A

Siemens HG 11.05 · 2007 21


Equipment Selection 3AH5 Vacuum Circuit-Breakers
Accessories and spare parts

Designation Remarks Operating voltage Order No.

Undervoltage release
Without varistor, without rectifier 24 V DC 3AX11 03-2B
48 V DC 3AX11 03-2C
Including varistor 60 V DC 3AX11 03-2D
110 V DC 3AX11 03-2E
120 – 127 V DC 3AX11 03-2N
220 V DC 3AX11 03-2F
240 V DC 3AX11 03-2P
Including rectifier and varistor 100 V AC, 50 Hz 3AX11 03-2G
110 – 125 V AC, 50 Hz 3AX11 03-2H
230 V AC, 50 Hz 3AX11 03-2J
100 V AC, 60 Hz 3AX11 03-3G
110 – 125 V AC, 60 Hz 3AX11 03-3H
230 V AC, 60 Hz 3AX11 03-3J
Mounting parts (for retrofitting) With one existing shunt release 3AX16 13-2A

2 Undervoltage release
In combination with energy store AN1902-
(make Bender), specified voltage corresponds to the
60 V DC
110 V DC
3AX11 03-2D
3AX11 03-2E
input voltage of the energy store 220 V DC 3AX11 03-2F
In combination with energy store AN1901-2 100 V AC, 50/60 Hz 3AX11 03-3K
(make Bender), specified voltage corresponds to the 110 V AC, 50/60 Hz 3AX11 03-3K
input voltage of the energy store 230 V AC, 50/60 Hz 3AX11 03-3K
Energy store (for delayed tripping of undervoltage release)
Make Bender Type AN1901-2B, with dropout delay Input voltage 3AX11 35-0A
of approx. 1/1.8/2.5 s 100/110/230 V AC, 50/60 Hz,
Output voltage 220 V DC
Type AN1902-1B, with dropout delay Input and output voltage 3AX11 35-0B
of approx. 0.5/0.9/1.5 s 220 V DC
Type AN1902-2B, with dropout delay Input and output voltage 3AX11 35-0C
of approx. 0.8/0.9/1.5 s 110 V DC
Type AN1902-3B, with dropout delay Input and output voltage 3AX11 35-0D
of approx. 0.5/0.9/1.5 s 60 V DC
Digital, c.t.-operated
overcurrent-time relay As release, make SEG, type WIP 1 For overcurrent 3AX11 35-1A
For earth fault 3AX11 35-1B
Drive motor
No retrofitting for manual spring-operated mechanism 24/30/32 V DC 3AY17 11-2B
48 V DC 3AY17 11-2C
Including varistor 60 V DC 3AY17 11-2D
Required for AC rectifier 100/110/126 V DC/AC 3AY17 11-2E
220 V DC/230 V AC 3AY17 11-2F
Rectifier component
100/250 V AC 3AY15 25-1F
Auxiliary contactor
(type 3TH20 22-7) For anti-pumping 24/30/32 V DC SWB: 48683
48 V DC SWB: 48687
60 V DC SWB: 48684
110/120 V DC SWB: 48685
125 V DC SWB: 47730
220 V – 240 V DC SWB: 48686
100 V – 125 V AC, 50 Hz SWB: 48680
230 V – 240 V AC, 50 Hz SWB: 49906
100 V – 125 V AC, 60 Hz SWB: 48679
230 V – 240 V AC, 60 Hz SWB: 49907

22 Siemens HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers Equipment Selection
Accessories and spare parts

Designation Remarks Operating voltage Order No.

Electrical closing lock-out


24 V DC 3AX16 05-5B
48 V DC 3AX16 05-5C
60 V DC 3AX16 05-5D
110 V DC 3AX16 05-5E
220 V DC 3AX16 05-5F
100 V AC, 50/60 Hz 3AX16 05-5G
110 V AC, 50/60 Hz 3AX16 05-5H
230 V AC, 50/60 Hz 3AX16 05-5J
Mounting parts (for retrofitting) 3AX16 15-2A
Position switch Type 3SE4 (as spare part), without installation accessories
Used for: Nos. SWB: 46677
– Electrical anti-pumping (-S3) 1
– Motor control (-S21, -S22) 2
– Closing spring charged (-S4) 1

Auxiliary switch (-S1)


– Circuit-breaker tripping signal (-S6, -S7)
– Electrical closing lock-out (-S5)
2
1 2
2 NO + 2 NC 3SV92 23-2AA0
6 NO + 6 NC 3SV92 73-2AA0
12 NO + 12 NC 3SV92 74-2AA0
Switch position sensor For manual spring-operated mechanism 3AX16 20-2C
Mechanical interlocking For stored-energy mechanism
– for normal panel, pole-center distance 210 mm, 3AX16 20-2A
275 mm and 350 mm
– for small panel, pole-center distance 160 mm 3AX16 20-2B
Varistor module With 2 varistors 3AX15 26-0F
Wire bundle With 10 wires for auxiliary switch connection to
– 64-pole plug connector 3AX11 34-4F
– 24-pole plug connector 3AX11 34-2B
– 24-pole terminal strip 3AX11 34-2C
Accessories for plug connector (for wire cross-section 1.5 mm2)
Crimp pins for lower part of plug 24-pole 3AX11 34-3A
64-pole 3AX11 34-4B
Crimp sockets for upper part of plug 64-pole 3AX11 34-4C
Crimping pliers 3AX11 34-4D
Disassembly tool 3AX11 34-4G

Siemens HG 11.05 · 2007 23


Equipment Selection 3AH5 Vacuum Circuit-Breakers
Accessories and spare parts

Designation Remarks Design code Order No.

Spare pole assemblies (complete)


For circuit breakers: 3AH5 121-1, 3AH5 131-1 1A 3AY17 14-6A
3AH5 122-1, 3AH5 123-1, 3AH5 124-1 1A 3AY17 14-6B
3AH5 132-1, 3AH5 133-1, 3AH5 134-1 1A 3AY17 14-6B
3AH5 122-2, 3AH5 123-2, 3AH5 124-2 1A 3AY17 14-6C
3AH5 132-2, 3AH5 133-2, 3AH5 134-2 1A 3AY17 14-6C
3AH5 135-2, 3AH5 125-2 1A 3AY17 14-6D
3AH5 135-6, 3AH5 133-4, 3AH5 134-6 1A 3AY17 14-6E
3AH5 204-1, 3AH5 214-1 3D 3AY17 14-3D
3AH5 204-2, 3AH5 214-2 3D 3AY17 14-4D
3AH5 214-6, 3AH5 215-6 1A 3AY17 14-6F
3AH5 215-2, 3AH5 205-2 1A 3AY17 14-6G
3AH5 272-1, 3AH5 282-1 3A 3AY17 14-8H
3AH5 272-2, 3AH5 282-2 3A 3AY17 14-8J
3AH5 273-4, 3AH5 273-6, 3AH5 274-6 2A 3AY17 14-7K

2 3AH5 283-4, 3AH5 283-6, 3AH5 284-6


3AH5 273-2, 3AH5 283-2, 3AH5 284-2, 3AH5 274-2
3AH5 322-2, 3AH5 324-2
2A
3A
1A
3AY17 14-7K
3AY17 14-8L
3AY17 14-3N
3AH5 312-2, 3AH5 314-2 3N 3AY17 14-3N
3AH5 314-4 1A 3AY17 14-6M

As spare parts, the vacuum interrupters are always supplied


as a complete pole including post insulator.
To select the correct spare interrupter, please specify
the type designation, serial number, design code and
year of manufacture of the circuit-breaker. All data is
given on the rating plate. Vacuum interrupters and
other spare parts must only be replaced by instructed
personnel.

Data on the rating plate


Note:
For any query regarding spare parts,
subsequent deliveries, etc. the following
four details are necessary:
– Type designation
– Serial No.
– Design code
– Year of manufacture
HG11-2587_en eps

24 Siemens HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers Technical Data
Contents

Contents Page

Technical Data 25
Electrical data, dimensions and weights:
Voltage level 12 kV 26
Voltage level 17.5 kV 28
Voltage level 24 kV 28
Voltage level 36 kV 30

Operating times 31
Short-circuit protection of motors 31
Consumption data of releases 31
Circuit diagrams 32
R-HG11-202.tif

Motor operating mechanism with energy store and


closing solenoid

3
R-HG11-203.tif

Upper pole support with conductor bar connection

Siemens HG 11.05 · 2007 25


Technical Data 3AH5 Vacuum Circuit-Breakers
Electrical data, dimensions and weights

Catalog dimension drawing No. (see page 27)


Operating cycle diagram No. (see page 27)
Rated lightning impulse withstand voltage
of the rated short-circuit breaking current
12 kV

Voltage drop ΔU between connections


Rated short-duration power-frequency

(according to IEC 60694 at DC 100 A)


Rated short-circuit breaking current
50/60 Hz

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,
DC component in %

(has to be ordered)
withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weights
Ir tk Isc Ima Up Ud

A mm s kA % kA kA kV kV mV mm mm mm mm kg

3AH5 121-1 ... 800 160 n 3 13.1 36 14.7 33/


34
75 28 6.0 90 135 88 95 35 3M 441 00641 1 1.1

3AH5 122-1 ... 800 160 n 3 16 36 17.9 40/


42
75 28 3.4 120 135 71 95 40 3M 441 00643 2 1.3

3AH5 122-2 ... 1250 160 n 3 16 36 17.9 40/


42
75 28 3.4 120 135 71 95 40 3M 441 00643 2 1.3

3AH5 123-1 ... 800 160 n 3 20 36 22.4 50/


52
75 28 3.4 120 135 71 95 40 3M 441 00643 3 1.3

3AH5 123-2 ... 1250 160 n 3 20 36 22.4 50/


52
75 28 3.4 120 135 71 95 40 3M 441 00643 3 1.3

3AH5 124-1 ... 800 160 n 3 25 36 28 63/


65
75 28 3.4 120 135 71 95 40 3M 441 00643 4 1.3

3AH5 124-2 ... 1250 160 n 3 25 36 28 63/


65
75 28 3.4 120 135 71 95 40 3M 441 00643 4 1.3

3AH5 125-2 ... 1250 160 n 3 31.5 36 35.4 80/


82
75 28 2.7 129 135 58 95 40 3M 441 00651 5 1.7

3 3AH5 131-1 ...

3AH5 132-1 ...


800

800
210

210
n
n
3

3
13.1

16
36

36
14.7

17.9
33/
34
40/
42
75

75
28

28
6.0

3.4
90

120 135 121


135 138 95

95
35

40
3M 441 00642

3M 441 00644
1

2
1.2

1.4

3AH5 132-2 ... 1250 210 n 3 16 36 17.9 40/


42
75 28 3.4 120 135 121 95 40 3M 441 00644 2 1.4

3AH5 133-1 ... 800 210 n 3 20 36 22.4 50/


52
75 28 3.4 120 135 121 95 40 3M 441 00644 3 1.4

3AH5 133-2 ... 1250 210 n 3 20 36 22.4 50/


52
75 28 3.4 120 135 121 95 40 3M 441 00644 3 1.4

3AH5 133-4 ... 2000 210 n 3 20 36 22.4 50/


52
75 28 1.6 129 135 91 95 55 3M 441 00646 3 1.6

3AH5 134-1 ... 800 210 n 3 25 36 28 63/


65
75 28 3.4 120 135 121 95 40 3M 441 00644 4 1.4

3AH5 134-2 ... 1250 210 n 3 25 36 28 63/


65
75 28 3.4 120 135 121 95 40 3M 441 00644 4 1.4

3AH5 134-6 ... 2500 210 n 3 25 36 28 63/


65
75 28 1.6 129 135 91 95 55 3M 441 00646 4 1.6

3AH5 135-2 ... 1250 210 n 3 31.5 36 35.4 80/


82
75 28 2.7 129 135 109 95 45 3M 441 00645 5 1.5

3AH5 135-6 ... 2500 210 n 3 31.5 36 35.4 80/


82
75 28 1.6 129 135 91 95 55 3M 441 00646 5 1.6

n Standard according to IEC 62271-100 Possible

26 Siemens HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers Technical Data
Electrical data, dimensions and weights

Operating cycle diagrams and dimension drawings 12 kV

Operating cycles n The permissible number of Operating cycles n


20 000 20 000
electrical operating cycles
10 000 is shown as a function 10 000
of the breaking current
5 000 5 000
(r.m.s. value). All vacuum
2 000 circuit-breakers fulfil the 2 000
endurance classes E2,
1 000 1 000
M2 and C2 according
500 to IEC 62271-100. The 500
curve shape beyond the
200 200
parameters defined in
100 IEC 62271-100 is based on 100
80
average experience data.
50 50
HG11-2546a_en eps

HG11-2547a_en eps
The number of operating
25 cycles that can actually be 25
20 20
2 3 4 reached can be different 1 5
10 depending on the respec- 10
0.5 1 2 5 10 16 20 25 kA 50 0.5 1 2 5 kA 10 13.1 20 31.5 50
tive application.

b
456 a a Dimension a b c
drawing mm mm mm

3
90

1.1 160 390 490


1.2 210 490 592
170 1.3 160 405 490
482 (558)
435

1.4 210 505 592


1.5 210 510 592
HG11-2548 eps

1.6 210 534 592


44

1.7 160 410 490


Value in brackets for 2500 A c

Siemens HG 11.05 · 2007 27


Technical Data 3AH5 Vacuum Circuit-Breakers
Electrical data, dimensions and weights

Catalog dimension drawing No. (see page 29)


Operating cycle diagram No. (see page 29)
Rated lightning impulse withstand voltage
of the rated short-circuit breaking current
17.5 kV

Voltage drop ΔU between connections


Rated short-duration power-frequency

(according to IEC 60694 at DC 100 A)


Rated short-circuit breaking current
50/60 Hz

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,
DC component in %

(has to be ordered)
withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weights
Ir tk Isc Ima Up Ud

A mm s kA % kA kA kV kV mV mm mm mm mm kg

3AH5 204-1… 800 160 n 3 25 36 28 63/


65
95 38 3.4 129 170 176 130 40 3M 441 00705 1 2.1

3AH5 204-2… 1250 160 n 3 25 36 28 63/


65
95 38 3.4 129 170 176 130 40 3M 441 00705 1 2.1

3AH5 205-2… 1250 160 n 3 31.5 36 35.4 80/


82
95 38 2.7 129 170 140 130 40 3M 441 00652 2 2.1

3AH5 214-1… 800 210 n 3 25 36 28 63/


65
95 38 3.4 129 170 108 130 45 3M 441 00706 1 2.2

3AH5 214-2… 1250 210 n 3 25 36 28 63/


65
95 38 3.4 129 170 108 130 45 3M 441 00706 1 2.2

3AH5 214-6… 2500 210 n 3 25 36 28 63/


65
95 38 1.6 129 170 163 130 55 3M 441 00649 1 2.3

3AH5 215-2… 1250 210 n 3 31.5 36 35.4 80/


82
95 38 2.7 129 170 108 130 45 3M 441 00648 2 2.2

3AH5 215-6… 2500 210 n 3 31.5 36 35.4 80/


82
95 38 1.6 129 170 163 130 55 3M 441 00649 2 2.3

3
24 kV Ir tk Isc Ima Up Ud
50/60 Hz
A mm s kA % kA kA kV kV mV mm mm mm mm kg

3AH5 272-1… 800 210 n 3 16 36 17.9 40/


42
125 50 3.8 200 190 215 175 55 3M 441 00660 4 3.1

3AH5 272-2… 1250 210 n 3 16 36 17.9 40/


42
125 50 3.8 200 190 215 175 55 3M 441 00660 4 3.1

3AH5 273-2… 1250 210 n 3 20 36 22.4 50/


52
125 50 3.8 200 190 215 175 55 3M 441 00662 5 3.1

3AH5 273-4… 2000 210 n 3 20 36 22.4 50/


52
125 50 2.2 200 190 227 175 80 3M 441 00663 5 3.1

3AH5 273-6… 2500 210 n 3 20 36 22.4 50/


52
125 50 2.2 200 190 227 175 80 3M 441 00663 5 3.1

3AH5 274-2… 1250 210 n 3 25 36 28 63/


65
125 50 3.8 200 190 260 175 55 3M 441 00662 7 3.1

3AH5 274-6… 2500 210 n 3 25 36 28 63/


65
125 50 2.2 200 190 227 175 80 3M 441 00663 7 3.1

3AH5 282-1… 800 275 n 3 16 36 17.9 40/


42
125 50 3.8 200 190 180 175 55 3M 441 00661 4 3.2

3AH5 282-2… 1250 275 n 3 16 36 17.9 40/


42
125 50 3.8 200 190 180 175 55 3M 441 00661 4 3.2

3AH5 283-2… 1250 275 n 3 20 36 22.4 50/


52
125 50 3.8 200 190 165 175 55 3M 441 00664 5 3.2

3AH5 283-4… 2000 275 n 3 20 36 22.4 50/


52
125 50 2.2 200 190 135 175 80 3M 441 00668 5 3.3

3AH5 283-6… 2500 275 n 3 20 36 22.4 50/


52
125 50 2.2 200 190 135 175 80 3M 441 00668 5 3.3

3AH5 284-2… 1250 275 n 3 25 36 28 63/


65
125 50 3.8 200 190 165 175 50 3M 441 00664 7 3.2

3AH5 284-6… 2500 275 n 3 25 36 28 63/


65
125 50 2.2 200 190 135 175 80 3M 441 00668 7 3.34

n Standard according to IEC 62271-100 Possible

28 Siemens HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers Technical Data
Electrical data, dimensions and weights

Operating cycle diagram and dimension drawings 17.5 kV

Operating cycles n 629 b


20 000 491 a a
10 000

90
5 000
170

482 (558)
2 000

630
435
1 000

HG11-2550 eps
500

86
Value in brackets for 2500 A c
200
Barrier for pole-center distance
100 of 160 mm
80
50
HG11-2549a_en eps

Dimension a b c
1 drawing mm mm mm
20
2 2.1 160 412 490
10
0.5 1 2 5 10 kA 20 25 31.5 50 2.2 210 514 592
2.3 210 534 592

Operating cycle diagram and dimension drawings 24 kV

Operating cycles n 670 b


20 000 537 a a

10 000

5 000
3
90

568 (572)

170
2 000
700
435

1 000

500
HG11-2553 eps
123

200
Value in brackets for 2500 A c
100 Barrier for pole-center distance
of 210 mm
50
HG11-2551_en eps

35
25 5 Dimension a b c
20 drawing mm mm mm
4 7
10 3.1 210 534 592
0.5 1 2 5 10 16 20 25 kA 50
3.2 275 650 708
3.3 275 690 708
The permissible number of electrical operating cycles is
shown as a function of the breaking current (r.m.s. value).
All vacuum circuit-breakers fulfil the endurance classes E2,
M2 and C2 according to IEC 62271-100. The curve shape
beyond the parameters defined in IEC 62271-100 is based
on average experience data. The number of operating cycles
that can actually be reached can be different depending on
the respective application.

Siemens HG 11.05 · 2007 29


Technical Data 3AH5 Vacuum Circuit-Breakers
Electrical data, dimensions and weights

Catalog dimension drawing No. (see below)


Rated lightning impulse withstand voltage
of the rated short-circuit breaking current

Operating cycle diagram No. (see below)


36 kV

Voltage drop ΔU between connections


Rated short-duration power-frequency

(according to IEC 60694 at DC 100 A)


Rated short-circuit breaking current
50/60 Hz

Rated short-circuit making current


Asymmetrical breaking current

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated short-circuit duration
Rated operating sequence:
O - 3 min - CO - 3 min - CO
O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-center distance

Minimum clearance,

Minimum clearance,
DC component in %

(has to be ordered)
withstand voltage

phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weights
Ir tk Isc Ima Up Ud

A mm s kA % kA kA kV kV mV mm mm mm mm kg

3AH5 312-2… 1250 350 n 3 16 36 28 40/


42
170 70 3.0 240 310 256 300 85 3M 441 00910 3 4.2

3AH5 314-2… 1250 350 n 3 25 36 28 63/


65
170 70 3.0 240 310 256 300 85 3M 441 00910 1 4.2

3AH5 314-4… 2000 350 n 3 25 36 28 63/


65
170 70 2.5 240 310 256 300 110 3M 441 00676 1 4.3

3AH5 322-2… 1250 275 n 3 16 36 28 40/


42
170 70 3.0 240 310 256 300 75 3M 441 00990 3 4.1

3AH5 324-2… 1250 275 n 3 25 36 28 63/


65
170 70 3.0 240 310 256 300 75 3M 441 00990 1 4.1

n Standard according to IEC 62271-100 Possible

3 Operating cycle diagram and dimension drawings 36 kV

Operating cycles n 785 b


20 000 673 a a

10 000

5 000
90

2 000
170
607 (682)

1 000
973
435

500

200
214

HG11-2554 eps

100
80
50 c
HG11-2552_en eps

Value in brackets for 2000 A


25
20
3 1
10
0.5 1 2 5 10 16 20 25 kA 50 Dimension a b c
drawing mm mm mm

4.1 275 650 708


The permissible number of electrical operating cycles is
4.2 350 810 868
shown as a function of the breaking current (r.m.s. value).
4.3 350 844 868
All vacuum circuit-breakers fulfil the endurance classes E2,
M2 and C2 according to IEC 62271-100. The curve shape
beyond the parameters defined in IEC 62271-100 is based
on average experience data. The number of operating cycles
that can actually be reached can be different depending on
the respective application.

30 Siemens HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers Technical Data
Operating times, short-circuit protection of motors and consumption data of releases

Operating times

Operating times at rated voltage of the secondary circuit Equipment of circuit-breaker Operating time
of circuit-breaker

Closing time < 75 ms 1)


Opening time 1st shunt release < 65 ms 1)
2nd release < 50 ms
Arcing time < 15 ms
Opening time 1st shunt release < 80 ms
2nd release < 65 ms
Dead time 300 ms
CLOSE/OPEN contact time 1st shunt release < 75 ms
2nd release < 60 ms
Minimum command duration Closing solenoid 45 ms
1st shunt release 40 ms
2nd release 20 ms
Pulse time for circuit-breaker tripping signal 1st shunt release > 15 ms
2nd release > 10 ms
Charging time for electrical operation < 15 s
Synchronism error between the poles ⱕ 2 ms

1) Shorter operating times on request

Short-circuit protection of motors (fuse protection of drive motors)

Rated voltage Operating voltage Power consumption Smallest possible


of the motor of the motor rated current 2) of the m.c.b.
(miniature circuit-breaker)
with C-characteristic

V
DC 24
max. V
26
min. V
20
W (at DC)
350
VA (at AC)

A
8
3
DC 48 53 41 350 – 6
DC 60 66 51 350 – 4
DC 110 121 93 350 – 2
DC 220 242 187 350 – 1.6
AC 110 121 93 – 400 2
AC 230 244 187 – 400 1.6

2) The current inrush in the drive motor can be neglected due to its very short presence

Consumption data of releases

Release Power consumption Tripping ranges

Operation at Tripping voltage Tripping voltage


or tripping current
DC AC 50/60 Hz at DC at AC 50/60 Hz
approx. W approx. VA
Closing solenoid 3AY15 10 140 140 85 bis 110 % U 85 bis 110 % U
1st shunt release 140 140 70 bis 110 % U 85 bis 110 % U
(without energy store) 3AY15 10
2nd shunt release 70 50 70 bis 110 % U 85 bis 110 % U
(without energy store) 3AY11 01
Undervoltage release 3AY11 03 20 20 35 bis 0 % U 35 bis 0 % U
Current-transformer operated release 3AX11 02 – 10 3) – 90 bis 110 % Ia
(rated current 0.5 or 1 A)
Current-transformer operated release 3AX11 04 – – – –
(tripping pulse W 0.1 Ws)

3) Consumption at pickup current (90 % of the rated current) and open armature

Siemens HG 11.05 · 2007 31


Technical Data 3AH5 Vacuum Circuit-Breakers
Circuit diagrams

Basic equipment
Manual closing Manual opening
without wiring

-Y9
HE

-S21 -S22 -S3 -S4


11 13 21 23
-S1
-M1 M P
12 14 22 24

-S7 -S6
2 NO + 2 NC contacts
HA available for customer

HG11-2405a eps -Y1

Additional equipment

-X0 -X0 -X0 -X0 -X0 -X0 -X0

22
21 -S3 21
-S21 21
-S7
13 21
22 -K1 22
22 14
A1 31
-M1 M -K1 -S4 13 21 -Y1 A1 -Y7 D1 -Y6 A1
-S6 13
D2 32 U<
14 22 A2 D2 A2

3 -S22
22

21
-Y9 A1
A2
-K1 A1
A2
14

-R1
1
HG11-2266a eps
HG11-2270a eps

HG11-2268a eps
HG11-2267a eps
HG11-2264a eps

HG11-2269a eps
HG11-2265b eps

-X0 -X0 -X0 -X0 -X0 -X0 -X0


Motor operating Closing and Circuit-breaker Signal “closing 1st shunt Undervoltage Low-energy
mechanism 1) anti-pumping 1) tripping signal 1) spring charged” 1) release 1) release 1) release 1)

1) Only upon order, for combination possibilities see


“Selection of secondary equipment”

Legend
HA Manual opening S21, Position switch S4 Position switch X0 Lower part of plug
HE Manual closing S22 (to de-energize the motor (indicates the charging state) Y6 Low-energy current-
K1 Contactor (anti-pumping) operating mechanism S6 Circuit-breaker tripping transformer operated release
M1 Motor operating mechanism after charging) signal Y7 Undervoltage release
P Energy store S3 Position switch S7 Cutout switch for circuit- Y9 Closing solenoid
R1 Resistance (opens when closing spring breaker tripping signal
S1 Auxiliary switch is charged)

32 Siemens HG 11.05 · 2007


3AH5 Vacuum Circuit-Breakers Annex
Contents

Contents Page

Annex 33

Inquiry form 34

Configuration instructions 35
Configuration aid Foldout page

R-HG11-181.tif

Brandenburger Tor, Berlin, Germany

4
R-HG11-180.eps

Switchgear Factory in Berlin, Germany

Siemens HG 11.05 · 2007 33


Annex 3AH5 Vacuum Circuit-Breakers
Inquiry form

Please copy and return to your Siemens partner


or you can use our prompted online configurator
under www.siemens.com/energy

Inquiry concerning
Technical data Other values

o 3AH5 circuit-breaker Rated voltage o 12 kV


o 24 kV
o 17.5 kV
o 36 kV o _ _ _ kV
Rated lightning impulse o 75 kV o 95 kV
withstand voltage o 125 kV o 170 kV o _ _ _ kV
Rated short-duration o 28 kV o 38 kV o 42 kV
Please power-frequency withstand voltage o 50 kV o 70 kV o _ _ _ kV
o 13.1 kA o 16 kA o 20 kA
o Submit an offer
Rated short-circuit
o 25 kA o 31.5 kA o _ _ _ kA
o Call us
breaking current

o Visit us Rated normal current o 800 A


o 2000 A
o 1250 A
o 2500 A o ___A
Pole-center distance o 160 mm o 210 mm o 275 mm o 350 mm

Your address Secondary equipment


For possible combinations see pages 15 to 20
Company o Manual spring-operated mechanism
Circuit-breaker equipment o Manual operating stored-energy mechanism
Dept. o Motor operating stored-energy mechanism
Motor operating mechanism o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz
Name
Closing solenoid o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz

Street 1st shunt release o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz

2nd shunt release o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz


Postal code/city
Current-transformer operated release o 0.5 A o 1A o W 0.1 Ws 10 c o W 0.1 Ws 20 c
Phone Undervoltage release o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz

Fax
Auxiliary switch o 2 NO + 2 NC o 6 NO + 6 NC o 12 NO + 12 NC
Low-voltage connection o without o 24-pole o 24-pole plug o 64-pole plug
E-mail terminal strip

o Mechanical interlocking

4 Siemens AG
o Counter
o Circuit-breaker tripping signal
o Electrical closing lock-out
Dept.
Operating instructions o English o German o French o Spanish
Name

Application and other requirements


Street

Postal code/city

Fax

o Please check off _ _ _ Please fill in

34 Siemens HG 11.05 · 2007


You prefer to configure your 3AH5 vacuum circuit-breaker on your own? For configuration of your
Please follow the steps for configuration and enter the order number in the configuration aid. 3AH5 vacuum circuit-breaker
Alternatively you can also use our prompted online configurator under www.siemens.com/energy

1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16
3 A H 5 n n n – n n n n n – n n n n – Z
Instruction for configuration of the 3AH5 vacuum circuit-breaker

1st step: Definition of the primary part (see pages 13 and 14)

See page 13

See page 15
See page 16
See page 16
See page 17

See page 18
See page 18
See page 19
See page 19

See page 20
Page 14
Please specify the following ratings: Possible options:

and
Rated voltage (Ur) Ur: 12 kV, 17.5 kV, 24 kV, 36 kV
Rated lightning impulse withstand voltage (Up) Up: 75 kV, 95 kV, 125 kV, 170 kV
Rated short-duration power-frequency withstand voltage (Ud) Ud: 28 kV, 38 kV, 42 kV, 50 kV, 70 kV
Rated short-circuit breaking current (Isc) Isc: 13.1 kA, 16 kA, 20 kA, 25 kA, 31.5 kA 3 A H 5 – –
Pole-center distance 160 mm, 210 mm, 275 mm, 350 mm
Rated normal current (Ir) Ir: 800 A, 1250 A, 2000 A, 2500 A + + + +

These ratings define the positions 5 to 8 of the order number + + + +

3 A H 5 – –

+ + + +
2nd step: Definition of the secondary equipment (see pages 15 to 19)
+ + + +

Please specify the following equipment features: Possible options: 3 A H 5 – –

+ + + +
Release combination Shunt release, current-transformer operated release
(position 9) and undervoltage release
Closing solenoid Operating voltages from 24 V DC to 240 V AC + + + +
(position 10)
Operating voltage of the releases Operating voltages from 24 V DC to 240 V AC 3 A H 5 – –
(positions 11/12)
Equipment with circuit-breaker tripping signal Equipment depends on the selection of the + + + +
(position 13) secondary connection
Type of operating mechanism and operating voltage of a motor, Manual spring-operated mechanism,
if available (position 14) manual operating stored-energy mechanism, + + + +
motor operating stored-energy mechanism
with operating voltages from 24 V DC to 240 V AC
3 A H 5 – –
Number of auxiliary contacts 2 NO + 2 NC, 6 NO + 6 NC, 12 NO + 12 NC
(position 15)
Design of the secondary connection 24-pole terminal strip, 24-pole plug connector, + + + +
(position 15) 64-pole plug connector, without connection system
Language of the documentation English, German, French, Spanish + + + +
(position 16)
Frequency of the operating voltage of the 50 Hz/60 Hz
secondary equipment at AC (position 16) 3 A H 5 – –

These equipment features define the positions 9 to 16 of the order number + + + +

+ + + +

3 A H 5 – –
3rd step: Do you have any further requirements concerning the equipment? (Please refer to page 20)
+ + + +
Should you still need more options than the possible special equipment like halogen-free and
+ + + +
flame-retardant or silicone-free version, condensate protection or an additional rating plate, etc.,
please contact your responsible sales partner.
3 A H 5 – –

+ + + +

+ + + +

3 A H 5 – –

+ + + +

+ + + +
Siemens HG 11.05 · 2007 35
If not stated otherwise on the individual pages of this catalog, Siemens AG For questions concerning Subject to change without notice
we reserve the right to include modifications, especially regarding Power Transmission and Distribution Power Transmission and Distribution: Order No. E50001-K1511-A051-A1-7600
Printed in Germany
the stated values, dimensions and weights. Medium Voltage Division You can contact our Customer Support Dispo 31601
Drawings are not binding. All product designations used are Nonnendammallee 104 Center 24 hours a day, 365 days a year. KG 02.07 7.0 32 En
trademarks or product names of Siemens AG or other suppliers. 13623 Berlin Tel.: +49 180/524 70 00 102303 6101/C6137
If not stated otherwise, all dimensions in this catalog are given Deutschland Fax: +49 180/524 24 71
in mm. (Calls charged: e.g. 12 Ct/min)
www.siemens.com/energy E-Mail: support.energy@siemens.com
www.siemens.com/energy-support
Responsible for
Technical contents: General editing:
Siemens AG, Dept. PTD M C PPM Siemens AG, Dept. PTD CC M
Berlin Erlangen The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases.
The required features should therefore be specified in each individual case at the time of closing the contract.