Cooling Tower Fan#1 Breakdown/Maintenance Report: Site Name: Tata Metaliks Ltd. (1 X 10 MW CPP)
Cooling Tower Fan#1 Breakdown/Maintenance Report: Site Name: Tata Metaliks Ltd. (1 X 10 MW CPP)
Vaccum was not proper > Blade angle was changed to 9.5°
Vaccum was not proper > Blade angle was changed to 11°
> Gear box base bolt got broken > All new blades were removed
> Huge amount of water was filled in all > Old 2 blades were coupled
blades which unbalanced the fan > Base was supported by angles
> Blade angle was maintained 10°
(1 X 10 MW CPP)
Maintenance Report
Date of equipment
taken in service Time to Repair Result
30-Jun-20 10.5 Hrs Fan was working properly, vibration was normal and vaccum
was normal
Remarks