Professional Documents
Culture Documents
Mullion Type
Maximum
Design wind Height of Wall Type of Lintel
(Design length of
S.No. pressure mullions HM thickness Masonry level wall Lw
reference
(kN/m2) (m) (mm) Unit (m)
table of (m)
external wall)
Permissible Longitudinal
Shear Force
τv shear stress Check for MH (kNm) bending
per meter V Hw/Lw α
fs (N/mm2) Shear stress
(kN)
(N/mm2)
Check for
Longitudina Check for Vertical
Self weight tensile
MH l bending flexure in bending stress
H1/Lw α1 Mv at mid- stress in
stress longitudinal (Tension)
height vertical
(N/mm2) direction (N/mm2)
direction
NA NA NA NA NA NA NA NA NA
0.286 0.040 1.411 -0.135 OK 0.706 1.350 -0.062 OK
NA NA NA NA NA NA NA NA NA
0.667 0.066 1.440 -0.138 OK 0.720 2.475 -0.059 OK
0.900 0.079 1.238 -0.119 OK 0.619 3.038 -0.047 OK
NA NA NA NA NA NA NA NA NA
0.364 0.045 0.979 -0.111 OK 0.490 1.242 -0.050 OK
0.964 0.082 1.120 -0.127 OK 0.560 2.795 -0.051 OK
Check for
Vertical Height of Longitudinal Check for
compressive
bending stress panel MH bending flexure in
stress in H2/Lw α2 Mv
(Compression) below stress longitudinal
vertical
(N/mm2) lintel, H2 (N/mm2) direction
direction
NA NA NA NA NA NA NA NA NA
0.073 OK 2.4 0.5714286 0.040 1.411 0.135 OK 0.706
NA NA NA NA NA NA NA NA NA
0.079 OK 2.4 0.7272727 0.040 0.880 0.084 OK 0.440
0.072 OK 2.4 0.8 0.044 0.700 0.067 OK 0.350
NA NA NA NA NA NA NA NA NA
0.061 OK 2.4 0.7272727 0.040 0.880 0.100 OK 0.440
0.076 OK 2.4 0.8571429 0.047619 0.653 0.074 OK 0.327
NA NA NA NA NA
2.700 -0.057 OK 0.079 OK
NA NA NA NA NA
2.700 -0.031 OK 0.053 OK
2.700 -0.023 OK 0.044 OK
NA NA NA NA NA
2.484 -0.039 OK 0.061 OK
2.484 -0.026 OK 0.048 OK
L1 BUILDINGS (HOSPITAL AND LINAC) GF - TF 1 - 3.75 External 250 Type 1 AAC - 2.8 300 250 Y10 Y10 2L-Y8 STPS @150 c/c 12 12 - - - -
L1 BUILDINGS (HOSPITAL AND LINAC) GF - TF 1 - 3.75 External 250 Type 2 AAC 2.4 4 300 250 Y12 Y12 2L-Y8 STPS @150 c/c 12 12 250 250 Y12 2L-Y8 STPS @200 c/c
L1 BUILDINGS (HOSPITAL AND LINAC) GF - TF 3.75 - 4.75 External 250 Type 1 AAC - 2.4 300 250 Y12 Y12 2L-Y8 STPS @150 c/c 12 12 - - - -
L1 BUILDINGS (HOSPITAL AND LINAC) GF - TF 3.75 - 4.75 External 250 Type 2 AAC 2.4 3.3 300 250 Y16 12 2L-Y8 STPS @150 c/c 12 12 250 250 Y12 2L-Y8 STPS @150 c/c
L1 BUILDINGS (HOSPITAL AND LINAC) GF - TF 4.75 - 5.25 External 250 Type 2 AAC 2.4 3 300 250 16 12 2L-Y8 STPS @150 c/c 16 16 250 250 Y12 2L-Y8 STPS @150 c/c
L2 BUILDING (HOSPITAL AND LINAC) GF - 2F 1 - 3.75 External 230 Type 1 Brick - 3.2 300 250 Y10 Y10 2L-Y8 STPS @150 c/c 12 12 - - - -
L2 BUILDING (HOSPITAL AND LINAC) GF - 2F 1 - 3.75 External 230 Type 2 Brick 2.4 4 300 250 Y10 Y12 2L-Y8 STPS @150 c/c 12 12 250 250 Y12 2L-Y8 STPS @200 c/c
L2 BUILDING (HOSPITAL AND LINAC) GF - 5F 1 - 3.75 External 250 Type 1 AAC - 3.2 300 250 Y10 Y10 2L-Y8 STPS @150 c/c 12 12 - - - -
L2 BUILDING (HOSPITAL AND LINAC) GF - 5F 1 - 3.75 External 250 Type 2 AAC 2.4 4 300 250 Y10 Y12 2L-Y8 STPS @150 c/c 12 12 250 250 Y12 2L-Y8 STPS @200 c/c
L2 BUILDING (HOSPITAL AND LINAC) GF - 5F 3.75 - 4.75 External 250 Type 1 AAC - 3 300 250 Y16 Y16 2L-Y8 STPS @200 c/c 12 12 - - - -
L2 BUILDING (HOSPITAL AND LINAC) GF - 5F 3.75 - 4.75 External 250 Type 2 AAC 2.4 3.9 300 250 Y12 Y16 2L-Y8 STPS @150 c/c 12 12 250 250 Y12 2L-Y8 STPS @200 c/c
L2 BUILDING (HOSPITAL AND LINAC) GF - 5F 4.75 - 5.25 External 250 Type 2 AAC 2.4 3.5 300 250 16 12 2L-Y8 STPS @150 c/c 16 16 250 250 Y12 2L-Y8 STPS @150 c/c
L2 BUILDING (HOSPITAL AND LINAC) 6F and Above 1 - 2.85 External 250 Type 1 AAC - 3.2 300 250 Y10 Y10 2L-Y8 STPS @200 c/c 12 12 - - - -
L2 BUILDING (HOSPITAL AND LINAC) GF - 2F 1 - 3.75 External 230 Type 1 Brick - 3.2 300 250 Y10 Y10 2L-Y8 STPS @150 c/c 12 12 - - - -
L2 BUILDING (HOSPITAL AND LINAC) GF - 2F 1 - 3.75 External 230 Type 2 Brick 2.4 4 300 250 Y10 Y12 2L-Y8 STPS @150 c/c 12 12 250 250 Y12 2L-Y8 STPS @200 c/c
L2A BUILDING (HOSPITAL AND LINAC) GF - 5F 1 - 3.75 External 250 Type 1 AAC - 1.6 300 250 Y10 Y6 2L-Y8 STPS @150 c/c 12 12 - - - -
L2A BUILDING (HOSPITAL AND LINAC) GF - 5F 1 - 3.75 External 250 Type 0 AAC 2.4 2.4 300 250 Y10 Y8 2L-Y8 STPS @150 c/c 12 12 250 250 Y11 2L-Y8 STPS @200 c/c
L2A BUILDING (HOSPITAL AND LINAC) GF - 5F 1 - 3.75 External 250 Type 1 AAC - 3.2 300 250 Y10 Y10 2L-Y8 STPS @150 c/c 12 12 - - - -
L2A BUILDING (HOSPITAL AND LINAC) GF - 5F 1 - 3.75 External 250 Type 2 AAC 2.4 4 300 250 Y10 Y12 2L-Y8 STPS @150 c/c 12 12 250 250 Y12 2L-Y8 STPS @200 c/c
L2A BUILDING (HOSPITAL AND LINAC) GF - 5F 3.75 - 4.75 External 250 Type 1 AAC - 3 300 250 Y16 Y16 2L-Y8 STPS @200 c/c 12 12 - - - -
L2A BUILDING (HOSPITAL AND LINAC) GF - 5F 3.75 - 4.75 External 250 Type 2 AAC 2.4 3.9 300 250 Y12 Y16 2L-Y8 STPS @150 c/c 12 12 250 250 Y12 2L-Y8 STPS @200 c/c
L2A BUILDING (HOSPITAL AND LINAC) GF - 5F 4.75 - 5.25 External 250 Type 2 AAC 2.4 3.5 300 250 16 12 2L-Y8 STPS @150 c/c 16 16 250 250 Y12 2L-Y8 STPS @150 c/c
L2A BUILDING (HOSPITAL AND LINAC) 6F and Above 1 - 2.85 External 250 Type 1 AAC - 3.2 300 250 Y10 Y10 2L-Y8 STPS @200 c/c 12 12 - - - -
L3 BUILDINGS (HOSPITAL AND LINAC) GF - TF 1 - 3.75 External 250 Type 1 AAC - 2.8 300 250 Y10 Y10 2L-Y8 STPS @150 c/c 12 12 - - - -
L3 BUILDINGS (HOSPITAL AND LINAC) GF - TF 1 - 3.75 External 250 Type 2 AAC 2.4 4 300 250 Y12 Y12 2L-Y8 STPS @150 c/c 12 12 250 250 Y12 2L-Y8 STPS @200 c/c
L3 BUILDINGS (HOSPITAL AND LINAC) GF - TF 3.75 - 4.75 External 250 Type 1 AAC - 2.4 300 250 Y12 Y12 2L-Y8 STPS @150 c/c 12 12 - - - -
L3 BUILDINGS (HOSPITAL AND LINAC) GF - TF 3.75 - 4.75 External 250 Type 2 AAC 2.4 3.3 300 250 Y16 12 2L-Y8 STPS @150 c/c 12 12 250 250 Y12 2L-Y8 STPS @150 c/c
L3 BUILDINGS (HOSPITAL AND LINAC) GF - TF 4.75 - 5.25 External 250 Type 2 AAC 2.4 3 300 250 16 12 2L-Y8 STPS @150 c/c 16 16 250 250 Y12 2L-Y8 STPS @150 c/c
ALL BUILDINGS ALL STOREY 1 -3.5 Internal 150 Type 1 AAC - 8 200 150 Y10 - Y8 link @ 200 c/c 10 10 - - - -
ALL BUILDINGS ALL STOREY 3.5 - 5 Internal 150 Type 1 AAC - 7.5 200 150 Y10 - Y8 link @ 200 c/c 10 10 - - - -
ALL BUILDINGS ALL STOREY 5-6 Internal 150 Type 1 AAC - 7 200 150 Y10 - Y8 link @ 200 c/c 10 10 - - - -
ALL BUILDINGS ALL STOREY 1 - 4.5 Internal 250 Type 1 AAC - 10 200 250 Y12 - 2L-Y8 STPS @200 c/c 10 10 - - - -
ALL BUILDINGS ALL STOREY 4.5 - 6 Internal 250 Type 1 AAC - 9 200 250 Y12 - 2L-Y8 STPS @200 c/c 10 10 - - - -
ALL BUILDINGS ALL STOREY 1 -3.5 Internal 230 Type 1 Brick - 13.5 200 230 Y12 - 2L-Y8 STPS @200 c/c 10 10 - - - -
ALL BUILDINGS ALL STOREY 3.5 - 5 Internal 230 Type 1 Brick - 13 200 230 Y13 - 2L-Y8 STPS @200 c/c 10 10 - - - -
ALL BUILDINGS ALL STOREY 5-6 Internal 230 Type 1 Brick - 12.5 200 230 Y14 - 2L-Y8 STPS @200 c/c 10 10 - - - -