SPH KING 15kVA

3Ph/1Ph PHASE UPS Rev. 1 SPH KING Series

The power protection system can be remotely


monitored via RS232, dry contact or SNMP
interface.

PRINCIPLES OF WORKING
The backup series is composed by: Rectifier,
Inverter, Static Switch, manual by-pass and
Battery.
The Rectifier-Inverter line normally feeds the
users, and the Battery is kept charged by the
Rectifier.
If a black out occurs, the Battery supplies
power energy to users always through the
Inverter. When the blackout is over, the
Rectifier provides for Battery charge.
If a short circuit or an overload occurs to the
users, the Static By-pass switches the load
over the emergency line. When the fault is
over, the Inverter feeds users.

FEATURES

 High efficiency > 93%.


 Filtered, stabilized and regulated sine wave
supply.
 Unity input power factor for energy saving
and low reflected harmonic pollution to the
utility.
The SPH KING series represents the last  Wide input voltage window and input
transformer-less double conversion (VFI) frequency window, the battery usage is
power protection ELIT technology designed to minimized.
protect a wide area of critical applications  Zero transfer time.
including server rooms, networks,  Superior overload capability.
telecommunication system, industrial  Battery monitoring and temperature
processes and medical equipment. Unmatched dependent charging function as option.
reliability, excellent electrical performance,  LCD display for measurements, alarms and
exceptionally compact size and outstanding power history.
cost-efficiency housed in an attractive  Device to avoid a complete battery
enclosure are only some features of this new discharge.
UPS solution.  ON LINE – OFF LINE settable working.
The SPH KING series is available in a variety of  Insulation transformer as option.
models: 7.5-10-15-20-30-40-60 and 80kVA.  Low audible noise, variable load-dependent
SPH KING series is provided in three cabinet DC fan speed.
sizes in order to allow longer battery backup  Customer slot, RS 232 and dry contact
times therefore avoid the use of additional interface as standard, USB, RS485 and
battery cabinets. Monitoring and control data SNPM as option.
are shown on an easy to understand front  Dual input feed as option.
panel display featuring pushbutton controls,  Personalizing 60Hz output converter.
LCD read out for event logs and diagnostics  Emergency Power Off.
and a mimic diagram for system status.
SPH KING 15kVA

3Ph/1Ph PHASE UPS Rev. 1 SPH KING Series

CONTROL PANEL display the voltages, currents, frequencies and


other values.
The user friendly control panel si composed by
three parts:

- Power Management LCD Display (PMD).


INTERFACES
- LED indicators.
- Keys.

The SPH KING is provided with two standard


interfaces:
Power Management Display (PMD)
The 2x20 character LCD simplifies the - Serial RS232.
communication with the UPS and provides the - Dry contacts.
necessary monitoring information about the
UPS.
Serial RS 232
The menu driven LCD enables the access to The smart port is an intelligent RS232 serial
the: port that allows the UPS to a computer. The
- Event register. connector is a standard D-Type, 9 pin, female.
- Monitor the input and output U, I, f, P. The software optionally allows the computer to
- Battery runtime. monitor the mains voltage and the UPS status
- Start up and shutdown of UPS. continuously.
- ON LINE – OFF LINE modality settable
- Diagnosis (Service Mode).
- Adjustments and testing. Dry Port (volt-free contacts)
The dry port may be used for:
- Connection of remote emergency stop
LED indicators facilities.
The mimic diagram serves to indicate the - Connection of remote status panel.
general status of the UPS. The LED indicators - Provision of signals for the automatic and
show the power flow status and in the event of orderly shutdown of servers or IBM AS400
mains failure or load transfer from inverter to
by-pass and vice-versa. The corresponding NO – NC available contacts: mains, common
LED indicators will change colors from green alarm, inverter, battery and EPO.
(normal) to red (warning).
The UPS SPH KING is provided with the
following accessories:
Keys
The keys allow the user to operate the UPS to USB port for remote signaling and automatic
perform settings and adjustments, to start up computer shutdown.
and shut down the UPS, to monitor on the LCD
SPH KING 15kVA

3Ph/1Ph PHASE UPS Rev. 1 SPH KING Series

SNMP card for monitoring and integration in REAR & FRONT PANEL EXPLANATION
network management. The Simple Network
Management Protocol (SNMP) is a worldwide-
standardized communication-protocol. It is
used to monitor any device in the network via
simple control language.

EMERGENCY POWER OFF


The Emergency Power Off facility must use a
normally closed contact, which opens to
operate the emergency stop sequence. The
Emergency Power Off port is located at the
front or at the back of the UPS TPH KING UPS,
according to the model.
In order to allow removal, maintenance or
testing of any remote emergency stop facility
without disturbing the normal operation of the
UPS, it is recommended that a terminal block,
with linking facilities, be installed between the
UPS and the stop button.

1. Use a screened cable with 1 pair (section


of wire 0.5mm2) and maximum length of
100m. - Input/output terminal block.
2. Connect the cable as shown in figure. - Cooling fan.
- Input fuses, emergency line fuses,
battery fuses.
- Maintenance By-pass switch.
- Output switch.
- Dry contact interface.
- RS 232 interface.
- Customer options Slot.
CATALOGO PRODOTTI

THREE/SINGLE PHASE UPS Rev. 3 SPH 10kVA – 20kVA

Model SPH10000 SPH15000 SPH20000 SPH KING15 SPH KING20

Rated power kVA/kW 10/7 15/13.5 20/18 15/12 20/16


INPUT
Nominal Voltage 380/400/415Vac 4w
Voltage tolerance 277 ÷ 485Vac 308 ÷ 460Vac
Power factor Up to 0.99 0.95 at full load 0.98 at full load
Frequency 50/60Hz
Frequency tolerance 45 ÷ 65Hz 35 ÷ 70Hz
Distortione (THiD) < 30% < 25%
OUPUT
Voltage 220/230/240Vac 2w
Frequency 50/60Hz auto sensing
Frequency tolerance ± 0.2% free running; reg. ±1Hz or ±3Hz Static <1%, dynamic ±4%
Waveform Sinusoidal
Distortion (THD) < 3%
Transfer time 0 ms.
Crest factor 3:1
DC start Yes No
Overload 150% for 3’’ 150% for 1’
BATTERY
Type Maintenance free VRLA
Recharge time 4h at 90% 6h at 90% 5h at 90%
Nominal voltage 240Vdc ± 288Vdc
Battery Test Automatic and periodically (adjustable)
EFFICIENCY
ON LINE mode Up to 90% > 91% Up to 94.5%
OFF LINE mode Up to 95% 98%
MISCELLANEOUS
Relative humidity < 90% without condensing
Operating temperature from 0°C to + 40°C
Noise at 1 meter < 50dBA < 52dBA < 53dBA
RS232, contacts & EPO, as
RS232 & EPO, as option:
Interfaces option: RS485, USB and
contacts, 2nd RS232, RS485, USB, SNMP
SNMP
Parallel capability yes no
Heat dissipation < 600W 850W 1150W 750W 960W
Input/output connection Terminals
Ext. battery connection Plug-in & Play Terminals
Dimensions (mm) 290x645x881 2x 290x645x881 340x800x820 450x860x1250
Weight w/o battery(kgs) 45 75 80 85 154
STANDARDS
Safety IEC/EN 62040-1-1, IEC/EN 60950-1
EMC IEC/EN 62040-2, IEC/EN61000-3-2, IEC/EN61000-6-2,
Performance EN 62040-3

ELIT Srl reserves his right to do modifications to his products without notice.