Professional Documents
Culture Documents
TABLE OF CONTENTS
1.0 SCOPE
2.0 DEFINITIONS
3.0 GENERAL
5.0 ELECTRICAL
6.0 MECHANICAL
8.0 CEILINGS
10.0 PARTITIONS
11.0 CARPETING
14.0 REFERENCES
1.0 SCOPE
This Standard on fire protection shall apply to all SEC Transmission Communication
Facilities. The requirements in this Standard are in accordance with the Uniform
Building Code (UBC) and National Fire Protection Association (NFPA) Standards.
2.0 DEFINITIONS
2.6 FIRE RESISTANCE RATING - means the time in hours that the material or
construction will withstand the standard fire exposure as determined by a fire
test made in conformity with the "Standard Methods of Fire Test of Building
Construction and Materials" . ASTM E119.
2.10 INTERIOR FINISH - includes material applied to the building structure such
as panelling, wall covering, ceiling tiles, resilient flooring, carpeting, etc.
2.12.3 Class "C" Openings - are in corridor and room partitions. Doors for the
protection of these openings have a fire resistance rating of 3/4 hour.
2.12.4 Class "D" Openings - are in exterior walls which are subject to severe
fire exposure from outside the building. Doors for the protection of
these openings have a fire resistance rating of 1&1/2 hours. Doors with
a fire protection rating of 1&1/2 hours may be employed as shutters for
protection of window opening rated Class "D" when adequately
protected against the weather. No glass shall be used in doors or
shutters for severe exterior exposure locations.
2.12.5 Class "E" Openings - are in exterior walls which are subject to
moderate fire exposure from the outside of the building. Doors for the
protection of these openings have a fire resistance rating of 3/4 hour.
a. Material of which no part will ignite and burn when subjected to fire.
3.0 GENERAL
3.1 Site
3.1.1 To ensure that a fire hydrant with pumper connection should be located within
91.4 m (300 ft).
3.1.2 Water mains at the site should be capable of supplying water at sufficient
volume and residual pressure for fire fighting purposes.
3.2 All outside utility entrance services (electric, water and air conditioning), including all
control valves, meters, etc. to these services, should be secured from tampering.
4.1 The communication building shall be provided with building fire detection and
protection systems which shall consist of the following subsystems:
4.1.1 A passive fire protection subsystem which shall minimize the risk of fire and
fire spreading by appropriate design considerations.
4.1.2 An active fire protection subsystem which shall compromise automatic fire
detection, fire fighting, clean agent type system and portable fire
extinguishers.
4.1.3 A smoke and fume extraction system to rapidly exhaust fire and combustion
products.
4.2 Provide standard exit ways according to building population, and physical arrangement
of the building occupancy layouts in accordance with the provisions of NFPA 1 - Fire
Prevention Code and NFPA 101 – Code for Safety To Life from Fire in Buildings and
Structures.
4.4 Smoking will only be permitted in locations outside of equipment areas such as
lounges, private offices, conference rooms, etc.
4.5 An Evacuation Plan shall be developed for protection of all persons in the event of fire.
Preplanned Fire Response Procedures shall be established to assure prompt notification
of Fire Department and SEC Communication Management personnel.
5.0 ELECTRICAL
5.2 Power and Communication cables should be separated by running them in separate
cable trays. For unavoidable situation, the minimum separation between these two
cable trays will be based on the latest edition of NFPA 70 - National Electrical Code
(NEC), Article 800 requirements.
5.3 Fire system / alarm wirings shall run completely separated from all other wirings. It
shall consist of MICS cabling or RHH, RHW type to NEC Code, flame retardant
armored PVC cable.
5.4 Communication cables entering a building at below grade shall have a ventilated gas
"pre-vent" chamber or a ventilated cable vault Where gas distribution systems are in
the area.
5.5 Two bell alarms shall be provided in each floor and one outside the building.
5.6 The fire alarm system shall be operated as well by push-button alarm.
5.7 A central power control board shall be provided and shall be fed by a battery backed
electrical power supply. From this control board all automatic fire fighting equipment
fire alarms and warnings shall be actuated, and a fire alarm time recorder shall be
included.
6.0 MECHANICAL
6.1 All building air conditioning and heating systems shall be designed and installed in
accordance with accepted fire safety practices (NFPA 90A - Standard for the
Installation of Air-Conditioning and Ventilating Systems). Equipment and controls
shall be Factory Mutual (FM) approved and listed by Underwriters Laboratories, Inc.
(UL) or equivalent.
6.2 All air distribution systems shall be equipped with approved automatic smoke detection
shutdown system including manual reset features.
6.3 Fuel oil riser piping for emergency generators located above the ground floor level
shall be protected against rupture, pinhole leaks, piping flaws, etc.
6.4 Portable fire extinguishers shall be installed in zones with increased fire danger such as
rooms with electrical equipment. The fire extinguisher shall be filled with chemical
powder.
6.5 Means of locking out fire suppression discharge system shall be provided for
maintenance purpose.
7.1 This section outlines standard for interior construction recommnended for restricting
the spread of fire in all Comnunication Rooms.
7.2 Floors
7.2.2 Perforating fire rated floors "poke through" If, to make connections with
underfloor primary electrical and communication wiring systems or other
utilities shall not be permitted.
7.2.3 All openings in floors for ducts, pipes and conduit, etc. shall be suitably fire
stopped.
8.0 CEILINGS
All ceiling construction should have a fire resisting rating of 1&1/2 hours.
9.1 Any series of floor openings providing communication between two or more
successive stories shall be continuously enclosed, to prevent the spread of fire
vertically throughout the building.
9.2 Vertical shafts for power cables, communication cables, piping, air distribution and
ventilation ducts shall be separated from the other areas by one (1) hour fire rated non-
combustible cut-off material.
10.0 PARTITIONS
10.1 Establish one (1) hour retardant rated non-combustible cut-offs for the following areas:
a) Heating Plant
b) Central Type Air Conditioning Equipment
c) Equipment Supply Storage
d) Maintenance Shops
e) Emergency Generator Rooms
f) Lounges
10.2 Telephone power equipment, excluding emergency generators, need not be separated
from other telephone equipment by fire rated non-combustible cut-offs.
10.3 Establish two (2) hours fire retardant rated cut-offs for cable vaults, central type air
conditioning equipment when serving more than two stories.
10.4 Establish three (3) hours fire retardant non-combustible cutoffs for the following:
10.5 Other room partitions for private offices, quarters, conference rooms, etc. may be
constructed of non-combustible material that do not have one (1) hour fire rating,
because the partition itself does not contribute any additional combustibles to the area.
11.0 CARPETING
11.2 If carpeting is provided in the office space of Communication Room, the carpeting
shall have jute backing. Sponge or foam rubber backing is unacceptable because of
generation of dense, pungent smoke under fire conditions.
The table below indicates minimum fire resistance ratings required for all exterior walls for
the Communication Room.
HORIZONTAL
SEPARATION
BETWEEN
OPPOSING WALLS BEARING WALLS NON-BEARING WALLS
13.1 This section outlines the standard for suppressing fire in all critical Communication
Equipment rooms of all SEC offices. The proponent associated with non-critical
communication facilities may determine that protection will be either in accordance
with these standards or with systems specified in the UBC.
13.2 Critical facilities shall be protected with fire protection systems as follows:
13.2.1 Equipment areas shall be protected with clean agent type systems. These
include FM 200 system (HFC-227ea Heptafluoropropane) and Carbon Dioxide
(CO2) system.
13.2.2 System shall be designed and installed in compliance with the applicable
NFPA Standards 12 and 2001, current edition.
13.2.3 Agent supply system shall consist of manifolded cylinders with a 100 per cent
piped in-placed reserve.
13.2.4 Fire extinguishing systems shall be actuated by cross zoned, dual chamber
ionization detection systems. Detection systems shall be designed and installed
in compliance with the latest edition of NFPA 72 – National Fire Alarm Code.
13.2.5 For clean agent extinguishing systems, a pre-discharge alarm and time delay,
sufficient to allow personnel evacuation prior to discharge. Where required,
abort switch can be provided to temporarily hold the specified time delay
(when press/operated), once release the remaining time (countdown) will
continue. Abort switch shall be of a type that requires constant manual
pressure to cause abort. Dry runs shall be made to determine the minimum
time needed for persons to evacuate the hazard area.
13.2.6 CO2 systems shall have a 30-second delay with predischarge alarm.
13.2.7 Back-up power shall be provided to maintain the detection, alarm and
actuation circuits for a minimum twenty four (24) hours duration in the event
of power failure.
13.2.8 Audible and visual alarms shall be installed to signal at constantly attended
location within the communication facilities and at the nearest Fire
Department.
13.2.9 Non-equipment areas such as offices, storage rooms, loading docks shall be
cut-off from equipment areas by minimum two (2) hour fire resistive
construction.
13.2.10 All clean agent systems shall be performance tested upon installation to assure
the design concentration is achieved.
14.0 REFERENCES