Professional Documents
Culture Documents
Design and Implementation of An Over-Current Relay For The Power Electronic-Based Converters Protection
Design and Implementation of An Over-Current Relay For The Power Electronic-Based Converters Protection
in Power System
January 8 and 9, 2019
Sharif University of Technology, Tehran
Abstract—In this paper, a new method used in over-current relay current and over-voltage. Variety of current protection, voltage
for power electronic-based converters protection is presented. protection and other issues related to protection have been
Firstly, the proposed method operation is described and proved investigated for three phase diode bridge rectifiers in Siemens
the fact that, without using DFT algorithm, this method can company [7]. Digital relays are able to meet safety requirements
quickly detect the fault current to prevent the damage of power such as reliability, sensitivity and speed; thus digital relays are
electronic components. Further, it is concluded that by applying
the proposed method, the harmonics produced by converters don’t
going to be replaced instead of old relay technologies [8].
affect the over-current relay operation. The simulation studies In this paper, an over-current relay is proposed to protect
performed in PSCAD/EMTDC software compare the main power electronic converters. Typical digital relays use the DFT
harmonic amplitude with the other harmonics amplitude. It is
(Discrete Fourier transform) calculation method for over-
deduced that the harmonic orders more than the main harmonic
have higher amplitudes. Thus, all harmonics amplitude must be
current protection, which only the first harmonic of the current
considered in the current calculation. Finally, the suggested relay signal is achieved and the trip command will be sent to the
is made and tested in a laboratory environment. circuit breaker. On the other hand, in power electronic
converters, due to the existence of different high-amplitude
Keywords- Protection; Power Electronic Converters; Over- harmonics, the calculation of all current harmonics is very
Current Relay; Discrete Fourier Transform; Harmonic important. This matter leads to burning of converter
components. For example, the dominant harmonics in six-pulse
I. INTRODUCTION inverters are 5 and 7 harmonics, which their amplitudes are
The fault is defined as an undesirable condition in a power also high. For this purpose, in this paper, instead of using the
system that requires protection. These unfavorable conditions DFT, a new method is proposed to calculate all effective
are: three-phase short-circuit, single-phase short-circuit to the harmonics.
ground, Internal short circuit, over-current, and so on. The proposed method is applied in an over-current relay to
Nowadays, development of power electronic-based converters measure all current harmonics which can detect the fault and
[1], protection of them is an important issue. Protection systems trip it quickly. By utilizing this method the safety of power
capability of power electronic-based converters are important electronic components that are sensitive to over current will be
for users in terms of economically and reliability. Specifically guaranteed.
for the inverters, a fuse is usually used proportional to their
range of current to protect them precisely. II. REVIEW OF CURRENT MEASUREMENT AND FAULT
DETECTION IN DIGITAL RELAYS
Various methods considering the over-current relays have
been investigated in literature. In [2], the over-current relay is Performance of a digital relay can be summarized in 7
considered by using a neural network method. A sections as follows [9].
multifunctional relay with interoperability in a module by using 1. Current Transformer and isolating Transformer
DSP is introduced in [3]. The innovation of this relay is the
inclusion of different protections in a small relay. The operation 2. Filtering signal conditioning
principle of the simulated numerical relay is based on the IEEE 3. Sampling and holding
Standard Inverse-Time Characteristic Equations of the Over-
current Relays [4]. A unidirectional and double-sided relay is 4. Analog to digital conversion
simulated in [5]. The principle of this simulation is based on the 5. Algorithm for extraction of information from raw
equations specified in IEEE for over-current relays. A multi- samples
purpose relay is described in [6] by using the Atmega328
microcontroller to protect the distribution system against over-
Authorized licensed use limited to: University of the West Indies (UWI). Downloaded on July 14,2020 at 05:20:56 UTC from IEEE Xplore. Restrictions apply.
6. Algorithm for implementation of relay characteristics burden resistance, DC offset resistances which are signed by
or protection scheme Vcc, , R1 and R2, respectively and C1 is to suppress
noise [10].
7. Algorithm for control, automation and monitoring
functions Digital Relay Case
In the first step, the current transformer and the isolating Current Isolation
Transformer Transformer
transformer are as the interface between the power system and
the measuring system. After filtering signal conditioning step,
Current
R
Li ne
sampling and holding step of data are performed [9].Since, the Burd en
current values in a power system are analog and also the digital
relay operation is based on the digital signal processing, first
the analog signals must be converted to the digital signal by
using an analog-to-digital converter. Conversion of the analog Figure 1. Current transformer and isolating transformer
to digital can be implemented by using various techniques
which each technique has its own advantages and Digital Relay Case
disadvantages. By converting the analog signal, we will have n-
Isolation Input Signa l to
bit digital signal. In the next step, the discrete Fourier Transfo rmer Microcontroll er Vcc=3.3V
Transform (DFT) algorithm is performed on the digital signal.
Vin
If the obtained DFT value exceeds the set value, the
R
microcontroller sends the interrupt command to the switch [9]. Vout
Burden R1
50
Authorized licensed use limited to: University of the West Indies (UWI). Downloaded on July 14,2020 at 05:20:56 UTC from IEEE Xplore. Restrictions apply.
The values of DC offset resistances must be exactly equal to controller. The proposed over-current relay in this paper has
the DC offset value . It should be noted that the values of both Definite Time and Inverse Time options. Different modes
2 of inverse time curve defined in IEC60255 standard is given in
these two resistances should be large enough to keep the
Table I. In this work, the type of this curve should be selected
accuracy of the voltage measurement. In this work, each DC
based on the inverter performance; the mentioned curves are
offset resistance value is equal to 10k Ω and the C1 value is
determined by (5) and using Table I:
also 10 .
×( )
C. Filter design = (5)
( ) −1
The input signal of microcontroller requires a suitable filter
to attenuate the noise and high-frequency disturbances and also In (5), I is the load current, t is the operating time, is the
increase the accuracy of measurement [11]. In over-current over-current setting, TMS is the time multiplier setting and α, β
relays, a variety of first or second order filters can be used. First are the constant values.
order filters like RC filters are rarely used due to their high
losses in system. Among the second-order filters, Chebyshev, TABLE I. DIFFERENT TYPES OF RELAY CHARACTERISTICS CURVE
Butterworth filter, LC filters are referred. Second-order low
pass filters are used in high precision relays due to their proper Curve Type α β
slope in cut off frequency and a low voltage drop across the
Normal Inverse 0.02 0.14
passband. In this paper, the Butterworth filter, as a second-order
low pass filter, is used with a cut off frequency of 400 Hz which Very Inverse 1 13.5
is shown in Fig. 4. Extremely Inverse 2 80
Long time Inverse 1 120
start
NO
Sense I
D. The proposed algorithm for Over-current Relay I set < I < 1.2*K*I nom-Motor NO I > 1.2*K*I nom-Motor
51
Authorized licensed use limited to: University of the West Indies (UWI). Downloaded on July 14,2020 at 05:20:56 UTC from IEEE Xplore. Restrictions apply.
IV. SIMULATION RESULTS TABLE II. CURRENT HARMONICS DURING TWO-PHASE FAULT
50
Current (A)
40
29.90
30 22.98
20 15.56
10 3.21 3.00
0.70 2.15
0
1 2 3 4 5 6 7 8
Harmonic Order
0.14
motor side, the measured secondary side current of transformer, 0.12
are given in Table II. The first harmonic values of current are 0.1
obtained by using the DFT method and the sum of the all 0.08
harmonics are achieved by using the proposed method. The 0.06
data listed in this table are the averaged current values in the 0.04
interval of 0.1 seconds after the fault occurrence. In the last 0.02
column, the ratio of all the harmonics to the main harmonic is 0
calculated that are relatively large values. The current
1
137
273
409
545
681
817
953
1089
1225
1361
1497
1633
1769
1905
2041
2177
2313
2449
2585
2721
2857
2993
3129
waveform on the secondary side of power transformer by
applying two-phase short-circuit fault at the motor side with a Main Harmonic Sum of all Harmonics
short-circuit resistance of 1Ω, is depicted in Fig. 7. Figs. 9 and
8 depict the column graphs of current harmonics amplitude Figure 10. Main harmonic and sum of all harmonics during Two-phase fault
considering the described two-phase short-circuit fault and not
TABLE III. CURRENT HARMONICS DURING THREE-PHASE FAULT
considering it, respectively.
Main All
Fault
Harmonic Harmonics
Resistance
Amplitude Amplitude
3.5 (Ω)
3.16 (A) (A)
3 2.77 1531.17 1854.74 1.21
2.46
0.001
2.5 0.1 80.97 109.00 1.35
Current (A)
52
Authorized licensed use limited to: University of the West Indies (UWI). Downloaded on July 14,2020 at 05:20:56 UTC from IEEE Xplore. Restrictions apply.
Comparison of Figs. (8) and (9) shows the fact that when In Fig. 14, a sample of proposed relay is represented by an
two-phase short-circuit fault occurs on the motor side in the ARM microcontroller which is tested in the laboratory
presence of an inverter, the currents including high harmonic environment using the described algorithms in this paper. The
amplitude are achieved. Thus, the significance of calculation of proposed relay is composed of several parts, as shown in Fig.
these harmonics is resulted. In Fig. 10, the main harmonic curve 14 which are followed by:
and the sum of all harmonics are compared.
1. Current Transformer
In the next step, by applying the three-phase short circuit
2. Isolating Transformer
fault at the motor side, the current is measured on the secondary
side of power transformer. As previously described, the 3. Burden resistance, DC offset and filter
measured values are given in Table III. As it is shown in Fig.
11, the current waveform on the secondary side of power 4. Module with ARM microcontroller
transformer is observed after three-phase short circuit fault at 5. LCD
the motor side considering the short-circuit resistance of 1Ω.
Fig. 12 also indicates the column graph of current harmonics 6. Key pad
amplitude of this scenario.
By comparing Figs. 8 and 12, when three-phase short-circuit
fault occurs on the motor side in the presence of inverter, the
high amplitude of current harmonics is obtained. In Fig. 13, the
main harmonic curve and the sum of all harmonics are
compared.
120
100 design and construction of an over-current relay to protect the
80 power electronic-based converters. The proposed method does
60 not require the DFT algorithm to calculate the fault current. It
38.74
40 is noteworthy that this method is not affected by the generated
20 12.88
2.52 2.17 5.04 2.67 1.19 current harmonics of power electronic converters either during
0
1 2 3 4 5 6 7 8 normal operation or during fault operation. The performance
Harmonic Order speed of the introduced method is such that it quickly detects
the fault and prevents the power electronic components to be
Figure 12. Current harmonic values during three-phase fault damaged. The validity of proposed method is confirmed by
considering various types of faults in simulation studies.
0.35
0.3 VI. REFERENCES
CURRENT (KA)
53
Authorized licensed use limited to: University of the West Indies (UWI). Downloaded on July 14,2020 at 05:20:56 UTC from IEEE Xplore. Restrictions apply.
Power Systems Research, vol. 143, 2017, pp. 32–43., supply/rectifier-group/pages/withdrawable-diode
doi:10.1016/j.epsr.2016.10.033. rectifier.aspx.
[4] “IEEE Standard Inverse-Time Characteristic Equations for [8] Goh, Yin Lee, et al. "Evaluation of dsp based numerical
Overcurrent Relays.” doi:10.1109/ieeestd.1997.81576. relay for overcurrent protection." International Journal of
[5] Aman, Muhammad Mohsin, Muhammad Qadeer Ahmed Systems Applications, Engineering and Development 5
Khan, and Saad Ahmed Qazi. "Digital directional and non- (2011): 396-403.
directional over current relays: Modelling and performance [9] Bhide, S. R. Digital Power System Protection. PHI
analysis." NED University Journal of Research 8.2 (2011). Learning Private Limited, 2014.
[6] Ramarao, G., Sateesh K. Telagamsetti, and V. S. Kale. [10] “Archived Forum.” Home | OpenEnergyMonitor,
"Design of microcontroller based multi-functional relay for openenergymonitor.org/forum-archive/node/156.html.
automated protective system." Engineering and Systems
(SCES), 2014 Students Conference on. IEEE, 2014. [11] RAMANATHAN, PRABHU, ET AL. "PERFORMANCE
[7] “Withdrawable Diode Rectifier.” Rail Solutions - Mobility- COMPARISONS OF INTERFACE CIRCUITS FOR MEASURING
Siemens,www.mobility.siemens.com/mobility/global/en/ CAPACITANCES." JOURNAL OF THEORETICAL AND APPLIED
ail-solutions/rail-electrification/dc-traction-power INFORMATION TECHNOLOGY 39.1 (2012): 001-005.
54
Authorized licensed use limited to: University of the West Indies (UWI). Downloaded on July 14,2020 at 05:20:56 UTC from IEEE Xplore. Restrictions apply.