You are on page 1of 3

 

Stress Model Consistency Documentation REV.1: 
Coordinate System: 

 ‐X = North 
 +Y = Up 
 ‐Z = East 

Coordinates noted on isometric drawings as north or East should be put in as negative in the Caesar 
global coordinate system consistency. Likewise, coordinates noted on isometric drawings as South 
or West should be put in as positives. 

Standard Loads and Load cases: 

Loads: 

LOADS  DEFINITION 
W  WEIGHT 
T1  OPERATING TEMPERATURE 
T2  HOT DESIGN TEMPERATURE 
T3  COLD DESIGN / CRITICAL EXPOSURE TEMPERATURE 
(MIN. OF LOW TEMPERATURE ON LINE LIST OR CRITICAL EXPOSURE TEMP = 9°F) 
P1  DESIGN PRESSURE 
WIN1  WIND IN +X DIRECTION 
WIN2  WIND IN ‐X DIRECTION 
WIN3  WIND IN +Z DIRECTION 
WIN4  WIND IN ‐Z DIRECTION 
HP  HYDROTEST PRESSURE 
WW  HYDROTEST WEIGHT (WATER WEIGHT) 
 
Note: 

1. Hargrove’s standard practice is to take a conservative approach and apply max design pressure 
to all of the thermal load cases and only apply the operating pressure if this practice causes a 
piping overstress. 
2. Project wind parameters should be set per ASCE 7 – 10 using the following values: 

a. Wind shape factor: 0.7 
b. Basis Wind Speed: 202.4 ft/sec 
c. Wind Exposure: Exposure C 
d. Structure Damping Coeff.: 0.030 
e. Structure Natural Frequency: 0.000 
f. Risk Category III 
 

   
 
Combinations: 

THREE (3) THERMAL LOADS AND NO HANGER LOAD CASES 
COMBINATION 

STRESS 
DEFINITION  NAME  TYPE 
L1  WW+HP  HYDRO TEST CASE  HYD 
L2  W+T1+P1  OPERATING CASE CONDITION 1  OPE 
L3  W+P1  ALTERNATE SUSTAINED STRESS BASED ON OPERATING CASE 1  SUS 
L4  W+T2+P1  OPERATING CASE CONDITION 2  OPE 
L5  W+P1  ALTERNATE SUSTAINED STRESS BASED ON OPERATING CASE 2  SUS 
L6  W+T3+P1  OPERATING CASE CONDITION 3  OPE 
L7  W+P1  ALTERNATE SUSTAINED STRESS BASED ON OPERATING CASE 3  SUS 
L8  W+P1  SUSTAINED CASE CONDITION 1  SUS 
L9  W+T1+P1+WIN1  OPERATING CASE CONDITION 1 PLUS WIND IN +X  OPE 
L10  W+T1+P1+WIN2  OPERATING CASE CONDITION 1 PLUS WIND IN ‐X  OPE 
L11  W+T1+P1+WIN3  OPERATING CASE CONDITION 1 PLUS WIND IN +Z  OPE 
L12  W+T1+P1+WIN4  OPERATING CASE CONDITION 1 PLUS WIND IN ‐Z  OPE 
L13  L9‐L2  WIND IN +X  OCC 
L14  L10‐L2  WIND IN ‐X  OCC 
L15  L11‐L2  WIND IN +Z  OCC 
L16  L12‐L2  WIND IN ‐Z  OCC 
L17  L13+L8  SUSTAINED CASE CONDITION 1 PLUS WIND IN +X  OCC 
L18  L14+L8  SUSTAINED CASE CONDITION 1 PLUS WIND IN ‐X  OCC 
L19  L15+L8  SUSTAINED CASE CONDITION 1 PLUS WIND IN +Z  OCC 
L20  L16+L8  SUSTAINED CASE CONDITION 1 PLUS WIND IN ‐Z  OCC 
L21  L2‐L8  EXPANSION CASES CONDITION 1  EXP 
L22  L4‐L8  EXPANSION CASES CONDITION 2  EXP 
L23  L6‐L8  EXPANSION CASES CONDITION 3  EXP 
L24  L4‐L6  THERMAL RANGE  EXP 
Notes: 

1. Additional thermal loads may be necessary and should follow the format used in the table 
above. 
2. Any deviation in the standard loads or load cases should be noted in stress documentation. 

   
 
 

THREE (3) THERMAL LOADS AND WITH HANGER LOAD CASES 
COMBINATION 

STRESS 
DEFINITION  NAME  TYPE 
L1  W  WEIGHT FOR HANGER SIZE  HGR 
L2  W+T1+P1  OPERATING CASE CONDITION 1 FOR HANGER TRAVEL  HGR 
L3  WW+HP  HYDRO TEST CASE  HYD 
L4  W+T1+P1+H  OPERATING CASE CONDITION 1  OPE 
L5  W+P1+H  ALTERNATE SUSTAINED STRESS BASED ON OPERATING CASE 1  SUS 
L6  W+T2+P1+H  OPERATING CASE CONDITION 2  OPE 
L7  W+P1+H  ALTERNATE SUSTAINED STRESS BASED ON OPERATING CASE 2  SUS 
L8  W+T3+P1+H  OPERATING CASE CONDITION 3  OPE 
L9  W+P1+H  ALTERNATE SUSTAINED STRESS BASED ON OPERATING CASE 3  SUS 
L10  W+P1+H  SUSTAINED CASE CONDITION 1  SUS 
L11  W+T1+P1+WIN1+H  OPERATING CASE CONDITION 1 PLUS WIND IN +X  OPE 
L12  W+T1+P1+WIN2+H  OPERATING CASE CONDITION 1 PLUS WIND IN ‐X  OPE 
L13  W+T1+P1+WIN3+H  OPERATING CASE CONDITION 1 PLUS WIND IN +Z  OPE 
L14  W+T1+P1+WIN4+H  OPERATING CASE CONDITION 1 PLUS WIND IN ‐Z  OPE 
L15  L11‐L4  WIND IN +X  OCC 
L16  L12‐L4  WIND IN ‐X  OCC 
L17  L13‐L4  WIND IN +Z  OCC 
L18  L14‐L4  WIND IN ‐Z  OCC 
L19  L15+L10  SUSTAINED CASE CONDITION 1 PLUS WIND IN +X  OCC 
L20  L16+L10  SUSTAINED CASE CONDITION 1 PLUS WIND IN ‐X  OCC 
L21  L17+L10  SUSTAINED CASE CONDITION 1 PLUS WIND IN +Z  OCC 
L22  L18+L10  SUSTAINED CASE CONDITION 1 PLUS WIND IN ‐Z  OCC 
L23  L4‐L10  EXPANSION CASES CONDITION 1  EXP 
L24  L6‐L10  EXPANSION CASES CONDITION 2  EXP 
L25  L8‐L10  EXPANSION CASES CONDITION 3  EXP 
L26  L6‐L8  THERMAL RANGE  EXP 
 

1. See hanger combinations highlighted in yellow above. 
2. Additional thermal loads may be necessary and should follow the format used in the table 
above. 
3. Any deviation in the standard loads or load cases should be noted in stress documentation. 

You might also like