You are on page 1of 22

Room air control

5.0
Chapter 5.0

LabSystem
Room air control in laboratories

Table of contents
Section Title Page
1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Laboratory controller LCO500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Group controller GC10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Room control module RAM500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.5 High-speed variable volume flow controllers (VAV) . . . . . . . . . . . . . . 3
1.6 Quick selection LabSystem products . . . . . . . . . . . . . . . . . . . . . . 4

2.1 Room air control in laboratories . . . . . . . . . . . . . . . . . . . . . . . . 5


2.1.1 Rapid changes in volume flow . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1.2 Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 High-speed variable volume flow controller, analogue, VAV-A . . . . . . . . 5
2.3 High-speed variable volume flow controller, LON, VAV-L . . . . . . . . . 5
2.4 High-speed variable volume flow controller, slave, VAV-S . . . . . . . . 6
2.5 Constant volume flow controller (CAV) . . . . . . . . . . . . . . . . . . . . . . 6
2.6 Switchable consumer loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.7 Energy savings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3.1 Room air balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7


3.2 Actual values and setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.3 Conventional wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.4 LON network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.5 Defined room air balance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.6 Negative pressure in the laboratory . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.7 Balancing of several laboratories . . . . . . . . . . . . . . . . . . . 8
3.8 Easy set-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

4.0 Laboratory ventilation examples . . . . . . . . . . . . . . . . . . . . . . . . . . . 9


4.1 Laboratory ventilation without additional extraction units . . . . . . . . . . 9
4.1.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.2 Laboratory ventilation taking into account the room pressure
and the temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 10
4.2.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.3 Laboratory control with a variably operated
fume hood and constant floor extraction . . . . . . . . . . . . . . . . . 11

LabSystem Planning Manual ● Air technology for laboratories 1 


Room air control
Chapter 5.0

Table of contents
Section Title Page
4.3.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.4 Laboratory control, low cost, with several variably
operated fume hoods, analogue and RAM500 . . . . . . . . . . . . . . . 12
4.4.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.5 Complete laboratory control with several variably
operated fume hoods, analogue and GC10 . . . . . . . . . . . . . . . . . 13
4.5.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.5.2 Room air balancing with the group controller . . . . . . . . . . . . . . . . . 14
4.5.3 Suitable for medium-sized to large laboratories . . . . . . . . . . . . . . . . . . . . 14
4.6 Complete laboratory control, LON connected, with
several variably operated fume hoods, analogue and LCO500 . . . . . 15
4.6.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.7 Complete laboratory control, LON connected, with
several variably operated fume hoods, analogue and LCO500 . . . . . 16
4.7.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.7.2 Laboratory controller with field bus connection . . . . . . . . . . . . . . . . . . . . . 17
4.7.3 Advantages of field bus connection . . . . . . . . . . . . . . . . . . . . . . . . 17
4.7.4 Inputs and outputs via the LON network . . . . . . . . . . . . . . . . . 17
4.7.5 Room operating device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.7.6 Room air balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.8 Terminal diagram LCO500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.9 LON connected laboratory control with several variably
operated fume hoods, LON connected . . . . . . . . . . . . . . . . . . . 19
4.9.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.9.2 Room air balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.10 Complete laboratory controll, LON connected, with several
variably operated fume hoods, LON connected . . . . . . . . . . . . . . . 20
4.10.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.10.2 Advantages of the LON network . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.10.3 Router for max. 64 nodes . . . . . . . . . . . . . . . . . . . . . . 21
4.10.4 Free inputs and outputs of the LON controller . . . . . . . . . . . . . . . . . . . . . 21
4.10.5 Room setpoint and room temperature actual value . . . . . . . . . . . . . . . . . . . . 21
4.10.6 Room operating device for daytime/night-time switching and
for switching on the room differential pressure sensor . . . . . . . . . . . . . . . . . . . 21
4.10.7 Room air balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

5.1 Product overview room ventilation controllers . . . . . . . . . . . . . . . . . . . . 22

2 LabSystem Planning Manual ● Air technology for laboratories


Room air control
Chapter 5.0

1.1 Introduction

As a competent partner, SCHNEIDER offers the entire


system solution for room supply air and room exhaust air
control in laboratories from a single source. The advan-
tage for the user is that the entire system functions without
compatibility problems.

The following SCHNEIDER LabSystem products are used


for ventilation control:

 Laboratory controller LCO500


 Group controller GC10
 Foom control module RAM500
 High-speed variable
volume flow controller, LON VAV-L
 High-speed variable
volume flow controller, analogue VAV-A Figure 5.1: Laboratory controller LCO500
 High-speed variable
volumen flow controller, slave VAV-S
 Constant volume flow controller,
mechanical, without auxiliary power CAV-xxx
 Damper for shut-off function,
open/shut DK-xxx 1.5 High-speed variable volume flow
controller (VAV)

The individual area of application determines which pro- Fast-running, variable volume flow controllers are primari-
duct is used, taking into account what gives the best value ly used for controlling room supply air and room exhaust
for money. air in laboratories. SCHNEIDER produces the entire spec-
trum in the usual dimensions in PPs and in galvanised
sheet steel. Depending on the controller model, setpoint
1.2 Laboratory controller actuation is either analogue 0(2)...10V DC or via the LON
network.
The LCO500 laboratory controller is specially developed
for network applications and can be upgraded for BACnet, Three different controllers types are available, which can
LON or Modbus at any time. In addition to room ventilation be used depending on the size of the project.
control, it controls and regulates entire laboratory appli-
cations, including external alarms (gas alarm, fire, etc.). The VAV-A analogue controller (xxx stands for the nomi-
The laboratory controller is ideally suited for connection to nal width NW in mm) is actuated by an analogue setpoint
the building services management (BSM). The integrated 0(2)...10V DC, which is generated by room air balancing
router functionality physically separates the BSM network devices (LCO500 laboratory controller, GC10 group cont-
from the internal room connection of the laboratory fume roller, RAM500 room control module).
hood controllers and thus prevents bus overload.
The LON controller VAV-L automatically calculates the
room air balance by receiving the exhaust air actual va-
1.3 Group controller lues of the extraction units that are to be balanced (fume
hoods, switchable consumer loads, etc.) as a standard
For rapid, demand-related room supply air and room ex- variable type (SNVT) via the LON network. This of course
haust air control together with several variable supply air requires that the entire system is connected via the LON
and exhaust air units and constant loads. The GC10 group network.
controller calculates the room balance and regulates the
laboratory at negative or positive pressure. The optional
LON network offers maximum flexibility and safety.

1.4 Room control module

The RAM500 room control module is attached to an FC500


fume hood controller and offers a cost-efficient alternative
to the group controller, with reduced functionality. A maxi-
mum of 5 analogue inputs as exhaust air actual values can
be balanced and a variable volume flow controller for the
room supply air can be actuated. Network connection via
a field bus is not possible.

LabSystem Planning Manual ● Air technology for laboratories 3 


Room air control
Chapter 5.0

1.6 Quick selection table

Table 5.1 gives a quick overview of the configurations of Technical data sheets, further information and tender
SCHNEIDER's various room ventilation products. specifications for the LCO500, GC10, RAM500, VAV-A,
VAV-L, CAV and DK products are available for download
on the Internet at www.schneider-elektronik.de.
Table 5.1: Quick selection table

LabSystem ● Products
Function Laboratory Group con- Room Variable Variable
controller troller control volume flow volume flow
module controller, controller,
LCO-300 GC10 RAM500 LON analogue
VAV-L VAV-A
Analogue inputs 0(2)...10V DC 10 10 4 + internal 1 1
Extension of analogue inputs through Yes Yes No No No
cascading
Analogue outputs ( 0... 10V DC) 8 4 2 1 1
Digital inputs (switchable consumer loads) 8 8 4 2 2
Relay outputs (potential-free) 8 No No 2 2
Network BACnet
LON LON No LON No
Modbus
Integrated router functionality Yes Yes No No No
Maximum balancing of consumer loads 10 + casca- 10 + casca- 5 - -
with analogue exhaust air actual values ding ding
Maximum balancing of consumer loads 16 16 - 16 -
with LON interface

4 LabSystem Planning Manual ● Air technology for laboratories


Room air control
Chapter 5.0

2.1 Room air control in laboratories 2.2 High-speed variable volume


flow controller, analogue

Laboratories with multiple fume hoods and extraction units The VAV-A variable volume flow controller with analogue
have complex room supply air and room exhaust air con- input 0(2)...10V DC can be used for room supply air and
trol requirements. room exhaust air applications. The setpoint that is to be
regulated is balanced in the LCO500 laboratory controller,
The room air change is defined in DIN 1946, Part 7 and the GC10 group controller or the RAM500 room control
can be calculated with the following rule of thumb: module and is available as an analogue value 0(2)...10V
DC).
25m³ per hour exhaust air volume
25m³ /h x m² flow, multiplied by the laboratory
main floor space in m².

With this formula the prescribed 8 room air changes can


be achieved. During night-time operation the reduced figu-
re of 4 room air changes is sufficient.

In addition to the room air change requirements specified


by DIN 1946, Part 7, air flow balance and maintenance
of protective pressure (negative pressure in laboratories
and positive pressure in clean rooms) as well as comfort
criteria such as temperature, humidity and air movement
must be taken into account.
Figure 5.2: Variable volume flow controller, analogue
0(2)...10V DC, steel,
2.1.1 Rapid changes in volume flow VAV-A-200-S-0-0-MM-0-0

Rapid changes in the volume flow of variable consumer


loads (fume hoods and extraction units) must be recognis-
ed immediately and the necessary room supply/exhaust 2.3 High-speed variable volume
air must be quickly regulated accordingly. When selecting
flow controller, LON
volume flow controllers for room supply air, it is essential to
ensure that the control time of 5 seconds is not exceeded
The VAV-L variable volume flow controller with LON field
(for a 90 degree damper adjustment). At a control speed of
bus module can be used for room supply air and room ex-
> 5 s maintenance of protective pressure in the laboratory
haust air applications. The exhaust air actual values of up
for the various operating states cannot be guaranteed.
to 16 fume hoods can be balanced and automatically re-
gulated. All programming is done via the LON network. As
During the entire system planning, the focus is on protec-
well as room positive pressure or room negative pressure
ting the operating personnel from hazardous substances
control, an additional room exhaust air control can also be
and ensuring their safety.
implemented. Thus a constant room air exchange rate can
be achieved, even for variable exhaust air units.
The SCHNEIDER room control products LCO500, GC10
and RAM500 provide all ventilation functions that are re-
quired to ensure a defined room balance. The room supply
air and room exhaust air control is dependent on the sash
position of the fume hoods and the switchable consumer
loads (demand) and takes place without pressure fluctua-
tions or draughts.

2.1.2 Programming

The system parameters of all SCHNEIDER products can


be configured by users on-site in accordance with their
specific needs using an SVM100 service module or a lap-
top with the PC2500 software. Via a serial interface, va-
lues such as setpoints, actual values, face velocity and
volume flow (even for each individual fume hood) can be
displayed and configured.
Figure 5.3: Variable volume flow controller, LON with
balancing function, PPs,
VAV-L-250-P-0-0-MM-0-0

LabSystem Planning Manual ● Air technology for laboratories 5 


Room air control
Chapter 5.0

2.4 High-speed variable volume flow


controller, slave

The slave variable volume flow controller only works in


connection with a master controller and is a cost-efficient
solution. The master controller can be a VAV-L (LON),
VAV-A (analogue) variable volume flow controller or an
FC500 fume hood controller. The slave controller has only
a static differential pressure transmitter and a fast servo
motor as well as a control body with a measuring system
and damper. Control takes place in the master controller
while the sensors and actuating elements are mounted on
the slave controller.

Figure 5.5: Constant volume flow controller,


mechanical, without auxiliary power,
steel, CAV-160-S

2.6 Switchable consumer loads

Source capture exhaust arms and exhaust chimneys,


which can be switched off and on electrically as needed,
are among the switchable consumer loads.

Constant volume flow controllers (mechanical or electro-


nic), coupled with an OPEN/SHUT damper, are switched
on or off with a motored drive unit and an electric switch.

Figure 5.4: Variable volume flow controller, slave, Connection to the room balance is done via a potential-
rectangular, steel, VAV-S-500-400-S-K-0-0 free contact on the switch as a switched offset value.

The control time for all SCHNEIDER variable volume flow


controllers (VAV) is < 5 seconds over a 90 degree dam-
per adjustment, which ensures that the protective pressu-
re (depending on the case of application, room negative
pressure or room positive pressure) is maintained at all ti-
mes, even for fast extraction units. The control time for the
extraction units (fume hoods, switchable consumer loads,
etc.) is < 3 seconds. Through the selection of different con-
trol times, oscillation can be avoided to a large extent.

2.5 Constant volume flow controller (CAV)

CAV constant volume flow controllers are used in conti- Figure 5.6: Switchable consumer load, with servo
nuous extraction units. Storage cabinets, base extraction motor, PPs, DK-160-P-MM-3
units or floor extraction units must be continuously extrac-
ted with a constant air volume. Mechanical (without auxili-
ary power) and electronic constant volume flow controllers 2.7 Energy savings
regulate a predefined volume flow independent of the duct
pressure. Mechanical constant volume flow controllers Demand-related volume flow control of the required room
are available in two-component finish and PPs. Electronic supply air and exhaust air means a considerable reduction
constant volume flow controllers are available in PPs. in energy consumption and at the same time maximum
safety for the operating personnel.
Connection to the room balance is in the form of a fixed
offset value. European and American standards in which room air ex-
change is defined, e.g. British Standard, DIN, DIN EN,
Norm Francaise, ASHRAE, etc., can easily be implemen-
ted.

6 LabSystem Planning Manual ● Air technology for laboratories


Room air control
Chapter 5.0

By making full use of the diversity factor, smaller dimensio- These setpoints are available as analogue outputs
ning of the entire system is possible without performance 0(2)...10V DC and actuate the corresponding variable vo-
loss. Demand-related system planning achieves a consi- lume flow controllers and/or frequency inverters for room
derable reduction of the operating costs. supply and exhaust air control.

In addition to energy savings, the comfort of the laboratory


personnel is an important factor. When planning a labora- 3.3 Conventional wiring
tory, the following criteria must be taken into account:
The following plan shows conventional room wiring of fume
 Temperatur hood controllers with a GC10 group controller. This type
 Humidity of wiring (star topology) is easy to implement. Compared
 Room flow behaviour to connection via the LON network, conventional wiring is
 Room air flow balance (for supply air and maintenance more cost-intensive and limited in functionality.
of protective pressure)
 Room air exchange (in accordance with national stan-
dards)
FC500 FC500 FC500

The SCHNEIDER LCO500 laboratory controller takes +/-A1 +/-A1 +/-A1

all these measurement data into account and has seve- HOOD #1 HOOD #2 HOOD #3

ral independent control circuits in order to fulfil the above GND2

criteria. In addition to room supply air and room exhaust +/-A1

air control, heating/cooling and humidity control is possib- 1


+/-E3
le. At the same time the room air flow conditions and the +/-E2
+/-E1
room pressure can be recorded and compared with the +/-E4
+/-E5

calculated room balance as redundant values. Supply air VAV GND1 GC10

This also contributes to safety and energy savings.


LAB-
ROOM #1

3.1 Room air balancing FC500 FC500 Connection to Building


+/-A1 +/-A1 management system

The SCHEIDER LCO500, GC10 and RAM500 room con- HOOD #4 HOOD #5
trol products calculate the room balance of the laboratory
depending on the variable, switchable and constant con-
sumer loads (fume hoods, extraction units, etc.) and provi-
de a setpoint as a control variable for the variable volume
flow controller (room supply air). 3.4 LON network
In order to maintain the required minimum room air ex- The room control products LCO500 and GC10 can be
change, a variable volume flow controller (room exhaust connected to the LON network. In addition to processing
air) can also be actuated. exhaust air actual values for room balancing, remote sig-
nals, such as reduced operation (night-time reduction) and
Laboratory specific requirements such as night-time ope- setpoints, can be sent via the LON network. This results in
ration, daytime operation and maximum operation (emer- a considerable increase in flexibility and a reduction of the
gency) can also be integrated. effort required for cabling.

The SCHNEIDER VAV-L variable volume flow controllers


3.2 Actual values and setpoints with LON interface retrieve the data they require directly
and decentrally via the standard variables (SNVT). The
Every FC500 and iCM fume hood controller and every functionality of the entire system is defined in a binding.
variable consumer load has an analogue actual value out-
put 0(2)...10V DC. The room-specific LCO500, GC10 or The LCO500 laboratory controller and the GC10 group
RAM500 group controller is supplied with the individual controller also support heterogenous systems, i.e. the
actual values. measurement values can also be supplied as an analogue
signal. Thus this product is particularly suitable for mixed
Via the software, the group controller adds up the actual systems, i.e. conventional components can be connected
values, as direct reference values for the individual volu- to LON networked products. Retrofitting and connection to
me flow (0...1000 m3/h), and calculates the corresponding existing systems can be easily implemented.
setpoints for the room supply air and room exhaust air,
taking protective pressure maintenance into account.

LabSystem Planning Manual ● Air technology for laboratories 7 


Room air control
Chapter 5.0

With defined room balance control, the focus is on protec-


LON-network ting the operating personnel from the escape of contami-
Connection to Building
management system nants and ensuring their comfort.

The SCHNEIDER product range fulfils these criteria and


FC500

+/-A1
FC500

+/-A1
offers a high level of comfort without draughts and pres-
sure fluctuations. Constant reading and checking of the
HOOD #6 HOOD #7 control variables ensures very fast, stable and demand-
LAB-
related control of the supply air volume flow, taking protec-
Supply air VAV
ROOM #2 tive pressure maintenance into account.
GC10

FC500

+/-A1
FC500

+/-A1
3.7 Balancing of several
laboratories
HOOD #8 HOOD #9

Overall balancing of several laboratories is also possible


with the GC10 and LCO500 products.

The actual value outputs of the individual room group


3.5 Defined room air balance controller 0(2)...10V DC are routed to the corresponding
central group controller. This type of cascading is easy to
The corresponding freely programmable defined room implement with the analogue signals. It is even easier to
balance is automatically calculated by the addition unit calculate the overall balance via the LON network.
(group, laboratory or LON controller). The proportion of
room exhaust air volume flow to room supply air volume The central group controller calculates the required set-
flow can be freely configured with the SVM100 service points for the central supply air and exhaust air motors
module or a laptop with the PC2500 software installed. (building supply air and building exhaust air) and actuates
these via the corresponding frequency inverters.

3.6 Negative pressure in the laboratory Connection to the building services management (BSM) is
guaranteed by standardised interfaces.
To ensure a defined pressure ratio, approx. 10% less sup-
ply air is fed in than exhaust air is extracted. The supply air Connection to the LON network is possible and conside-
value is calculated using the following formula: rably reduces the mounting and installation costs while at
the same time improving system performance.

3.8 Easy set-up


VSUPPLY AIR = VEXHAUST AIR x C
All project-specific control parameters, setpoints and pa-
rameters can easily be displayed, changed and monitored
on-site with the SVM100 service module or a laptop with
the PC2500 software installed.
Example: 10 % difference in pressure
All actual values and setpoints necessary for set-up can
be read off on the service module display. Thus expensi-
C = 0.90 ve and time-consuming measurements are not necessary
and set-up of the system is easy, fast and cost-effective.
Constant Pressure ratio of the laboratory and
All control parameters can also be printed for documenta-
corridor
tion purposes with the PC2500 set-up software.
C<1 The laboratory is in a state of negative
pressure SCHNEIDER offers all the necessary control and moni-
C=1 No difference in pressure toring components for planning your entire system. The
benefits for users: a competent partner for all their needs.
C>1 The laboratory is in a state of positive This also applies to later retrofittings.
pressure

The constant C is freely programmable and determines


the protective pressure maintenance factor.

8 LabSystem Planning Manual ● Air technology for laboratories


Room air control
Chapter 5.0

4.0 Laboratory ventilation examples


The sensor is a static differential pressure transmitter and
The following examples describe various laboratory ven- is thus not susceptible to dirt. The damper is driven by a
tilation concepts. Taking into account the specific require- fast-running constant servo motor (0...10V DC).
ments of the laboratory, the focus is always on the ideal
control strategy. The VAV-A master controller (1) follows the VAV-S slave
controller (2), taking into account the required room pres-
Constant consumer loads can be added at any time, since sure ratios. The analogue input enables seamless control
they are taken into account by the room balancing as con- of the air volumes. Thus it is very easy to implement, for
stant exhaust air volumes. example, reduced operation (night-time reduction).

4.1 Laboratory ventilation without


additional extraction units Control diagram

Supply air 2
Exhaust air

V [m3/h]
p VAV-S
M
VAV-A 800
M p

1
600
Exhaust air volume

400

200

Day operation Night operation


= Room exhaust air volume
= Room supply air volume

LabSystem components
No. Amount Type Description
1 1 VAV-A-200-S Variable volume flow controller, round, analogue input, DN200, galvanised
steel
2 1 VAV-S-200-S Variable volume flow controller, round, slave, DN200, galvanised steel

4.1.1 Functional description

The VAV-A-200-S exhaust air controller (analogue input)


automatically regulates the room exhaust air volume flow
and compensates fluctuations in the duct pressure. The
desired or prescribed room air exchange rate is defined by
the analogue control variable (setpoint).

The room supply air is fed in through a second control


circuit which is also located in the VAV-A exhaust air cont-
roller (1). The VAV-S slave controller (2) only provides the
sensors and actuating elements and is thus a cost-effec-
tive solution.

LabSystem Planning Manual ● Air technology for laboratories 9 


Room air control
Chapter 5.0

4.2 Laboratory ventilation taking into then increases the room supply air volume flow until the
account the room pressure and the room negative pressure has reached the required value
temperature again.

If, for example, the laboratory door is opened, the room


Supply air 2
Exhaust air negative pressure drops, which results in a reduction of
the room supply air volume flow. This ensures that the re-
VAV-A
p
M
VAV-A

quired supply air flows in from the corridor mainly through


M p

1 the laboratory door, with the result that the room negative
pressure is maintained.

The sensors of the controllers are static differential pres-


sure transmitters and are therefore resistant to dust par-
ticles or contaminated air. The dampers are driven by fast-
running servo motors.

If the room pressure differential pressure sensor is not


installed, the room negative pressure can also be ensu-
4 3 red by a master (1) - slave (2) connection (dotted line).
p T The supply air controller then follows dependent on the
+ -
exhaust air controller. Room negative pressure is achie-
ved by supplying only approx. 90% (programmable) of the
room exhaust air as supply air to the laboratory.

LabSystem components
No. Amount Type Description
1 1 VAV-A-200-S Variable volume flow controller, round, analogue input, DN200, galvanised
steel
2 1 VAV-A-200-S Variable volume flow controller, round, analogue input, DN200, galvanised
steel
3 1 RT-PT1000 Room temperature sensor, PT1000, active, 0...10V DC
4 1 RDT±50Pa Room differential pressure sensor, ±50 Pa, 0...10V DC

4.2.1 Functional description


Control diagram
The VAV-A-200-S exhaust air controller (analogue input)
automatically regulates the room exhaust air volume flow
and compensates fluctuations in the duct pressure. The
desired or prescribed room air exchange rate is defined 800
by the setpoint. At the same time the additional analogue
V [m3/h]

command variable of the PT1000 room temperature sen- 600


sor (3) "pushes" the volume flow to such an extent that
the exhaust air volume flow controller (1) opens or closes,
Exhaust air volume

400
within certain limits, in order to regulate the laboratory tem-
perature.
200

The room supply air is regulated by its own, additional


control circuit (2), which, as a command variable, takes the
room negative pressure (4) into account. Thus, for examp- 14 16 18 20 22 24 26 28 30
le, -10 Pascal room negative pressure is automatically fed Roomtemperature [OC]
in, independent of the room exhaust air.
= Room exhaust air volume
= Room supply air volume
If the exhaust air volume flow is increased in order to
maintain a constant room temperature, the room negative
pressure also increases. The room differential pressure
sensor (4) signals this to the supply air controller, which

10 LabSystem Planning Manual ● Air technology for laboratories


Room air control
Chapter 5.0

4.3 Laboratory control with a variably increase in exhaust air volume flow brought about by ope-
operated fume hood and a constant ning the sash and the reduction in exhaust air volume flow
floor extraction unit caused by closing the sash or by external switching to re-
duced operation (night-time reduction or work-free time).

This example is always suitable (e.g. for smaller labora-


tories) when the required minimum level of room air ex-
change is achieved by the the extraction units. The re-
Supply air Exhaust air quired minimum exhaust air volume flow for laboratories
VAV-A
p
stipulated by DIN 1946, Part 7 is 25m³/h x m² in relation to
M
2
M
CAV

3
the main floor space (8 room air changes).
p FC500

1 During reduced operation (night-time reduction), 4 room


air changes are sufficient. In all events the minimum room
air exchange should be defined for the changed operating
Exhaust
conditions, which results in optimal energy considerati-
ons.
Fume hood

Room supply air is compensated based on the room ex-


haust air. Negative room pressure is achieved by supplying
only approx. 90% (programmable) of the room exhaust air
as supply air to the laboratory. Due to the direct actuation
of the supply air volume flow controller VAV-A (2), cost-ef-
ficient implementation is possible.

LabSystem components
No. Amount Type Description
1 1 FC500-V-A Fully variable fume hood controller, analogue output 0...10V DC
1 MD-200-P-MM-1 Maintenance-free measuring device DN200, PPs, socket/socket, servo
motor 3 s
2 1 VAV-A-200-S Variable volume flow controller, round, analogue input, DN200, galvanised
steel
3 1 CAV-80-S Constant volume flow controller, round, DN80, sheet steel, DD finish

4.3.1 Functional description Control diagram

Day operation Night operation


With this version the entire laboratory exhaust air is ex-
tracted via the FC500-V-A variable fume hood controller
V [m3/h]

(1) and the CAV-80 constant floor extraction unit (3). The 800
room supply air is fed in via the VAV-A-200-S volume flow
controller with analogue input (2). Control of the variable
600
Exhaust air volume

exhaust air, the variable supply air and the addition of the
constant exhaust air is taken over completely by the vari-
able fume hood controller (1). 400
Room exhaust air
Room supply air
The variable fume hood controller (1) seamlessly regula- 200
tes the exhaust air volume flow depending on the sash
Additional exhaust air
position. When the sash is shut, the required containment
of the fume hood can be achieved with reduced exhaust shut open

air volume flow, which results in considerable energy and Fume hood (sash)
cost savings. The monitoring system for the ventilation
functions of the fume hood stipulated by DIN EN 14175
is an integral part of the FC500-V-A fume hood controller.
The operating terminal is mounted on the fume hood or The control diagram shows the effect of a closed and open
fitted in the lesene. fume hood sash on the variable exhaust air and the sup-
plied variable supply air during daytime and night-time
High-speed variable exhaust air control (< 3 s) requires operation (reduced operation).
high-speed room supply air control (< 5 s). Due to the
different control times, oscillation is eliminated as far as The constant floor extraction unit is included in the room
possible and at the same time the defined room negative balancing calculation as a constant value (e.g. 80m3/h).
pressure is always guaranteed. This applies both for the

LabSystem Planning Manual ● Air technology for laboratories 11 


Room air control
Chapter 5.0

4.4 Laboratory control, low cost, with several variably operated fume hoods, switchable
bench extraction unit and constant floor extraction unit

Supply air 3
Exhaust air
VAV-A
p

M CAV
1 1 1
4
M M M M
FC500 FC500 FC500 VAV-A 5
p
p 2 p p
RAM

Switchable
canopy exhaust

Exhaust
Fume hood 1 Fume hood 2 Fume hood 3

LabSystem components
No. Amount Type Description
1 3 FC500-V-A Fully variable fume hood controller, analogue output 0...10V DC
3 MD-200-P-MM-1 Maintenance-free measuring device DN200, PPs, socket/socket, servo motor 3 s
2 1 RAM500 Room addition module for max. 5 fume hoods
3 1 VAV-A-315-S Variable volume flow controller, round, analogue input, DN315, galvanised steel
4 1 VAV-A-100-P Switchable volume flow controller, round, analogue output, DN100, PPs
5 1 CAV-80-S Constant volume flow controller, round, DN80, sheet steel, DD finish

4.4.1 Functional description Control diagram

With this version the entire laboratory exhaust air is extrac- Day operation Night operation
ted via three FC500-V-A variable fume hood controllers
(1), a switchable bench extraction unit (4) and a CAV-80
V [m3/h]

constant floor extraction unit (5). The room supply air is 800
fed in via the VAV-A-315-S (2) volume flow controller. The
room balancing is done by the RAM500 room addition mo-
600
Exhaust air volume

dule (2), which calculates the setpoint 0(2)...10V DC for


the supply air controller depending on the variable labora-
tory exhaust air. 400
Room exhaust air
Room supply air

The RAM500 room addition module is an additional cir- 200

cuit board which can be attached to any FC500-V-A fume Additional exhaust air
hood controller. A maximum of 5 variable consumer loads
with 0...10V DC analogue output can be connected. Thus shut open
Fume hood (sash)
smaller laboratories can be cost-effectively equipped with
0...10V DC analogue technology.
The control diagram shows the effect of a closed and open
Control and monitoring of the fume hoods as well as main- fume hood sash on the variable exhaust air and the sup-
tenance of the room pressure correspond to the functional plied variable supply air during daytime operation. During
description 4.3.1 on page 11. night-time operation a minimum room air exchange is re-
gulated.

12 LabSystem Planning Manual ● Air technology for laboratories


Room air control
Chapter 5.0

4.5 Complete laboratory control with several variably operated fume hoods, switchable
bench extraction unit, constant floor extraction unit and additional laboratory exhaust air,
taking into account the room temperature and the redundant room pressure measurement

Supply air 4 Exhaust air


VAV-A
p
Room exhaust air
M
1 1 1 CAV
2
M M M M M
3
FC500 FC500 FC500 VAV-A VAV-A
p p p p p

Switchable
Canopy exhaust

Exhaust
Fume hood 1 Fume hood 2 Fume hood 3

GC10
6
7
8
p
+ - T

LabSystem components
No. Amount Type Description
1 3 FC500-V-A Fully variable fume hood controller, analogue output 0...10V DC
3 MD-200-P-MM-1 Maintenance-free measuring device DN200, PPs, socket/socket, servo motor 3 s
2 1 VAV-A-100-P Switchable volume flow controller, round, analogue output, DN100, PPs
3 1 CAV-80-S Constant volume flow controller, round, DN80, sheet steel, DD finish
4 1 VAV-A-315-S Variable volume flow controller room supply air, round, analogue input, DN315,
sheet steel
5 1 VAV-A-200-P Variable volume flow controller room exhaust air, round, analogue input, DN200,
PPs
6 1 GC10 Group controller for room balancing for n x 10 fume hoods 0...10 VDC and
n x 4 switchable consumer loads (on/off) (n = number of GC10 group controllers)
7 1 RDT±50Pa Room differential pressure sensor, ±50 Pa, 0...10V DC
8 1 RT-PT1000 Room temperature sensor, PT1000, active, 0...10V DC

4.5.1 Functional description

With this version, part of the laboratory exhaust air is ex- The GC10 group controller can balance a maximum of 10
tracted by three FC500-V-A variable fume hood controllers fume hoods (optionally this can be extended) or other va-
(1), a switchable bench extraction unit (2) and a CAV-80 riable consumer loads and in the standard version has 10
constant floor extraction unit (3). In order to ensure con- analogue inputs 0(2)...10V DC. The exhaust air actual va-
stant room air exchange (e.g. 25m³/h x m²) the laboratory lues of the connected consumer loads (m³/h) are provided
exhaust air is also extracted via its own VAV-A-200-P vo- to the group controller as an analogue signal (0...10V DC).
lume flow controller (5). The laboratory supply air is fed in Wiring is done with standard cables (e.g. I(ST)Y 2*2*0.8)
via the VAV-A-315-S volume flow controller with analogue using conventional technology.
output (4).
The group controller also has 4 analogue outputs, which
The entire room balancing for the supply air volume flow serve as setpoints 0(2)...10V DC for volume flow control-
controller (4) and the calculation of the difference for the lers (supply air, exhaust air) and/or as direct actuation for
exhaust air volume flow controller (5) is done by the GC10 frequency inverters. Wiring is also done with standard ca-
group controller (6). bles using conventional technology.

LabSystem Planning Manual ● Air technology for laboratories 13 


Room air control
Chapter 5.0

In addition, a room differential pressure sensor RDT±50Pa 4.5.3 Suitable for medium-sized to large
(7) for redundant room pressure measurement and an RT- laboratories
PT1000 room operating device (8) with room setpoint de-
vice and room sensor (Pt1000) are each connected to an The example described is suitable for medium-sized to
analogue input of the group controller. large laboratories when a specific minimum level of room
air exchange must be maintained, but which cannot be
With the room operating device, the laboratory room tem- fully achieved by the extraction units. An additional volume
perature can be regulated via the volume flow displace- flow controller for room exhaust air (5) always regulates
ment and additional control valves for the static heating the difference between the technically induced exhaust air
elements. The required room air exchange rate is always of the extraction units and the required minimum exhaust
maintained and may not be underrun. air volume flow.

The room differential pressure sensor (7) is used for red- The required minimum exhaust air volume flow for labo-
undant room pressure measurement. The group controller ratories stipulated by DIN 1946, Part 7 is 25m³/h x m² in
(6) compares the calculated value with the measured va- relation to the main floor space (8 room air changes).
lue and can thus recognise and signal any problems that
arise in good time. During reduced operation (night-time reduction), 4 room
air changes are sufficient. In all events the minimum room
If the laboratory door is opened, the room negative pres- air exchange should be defined for the changed operating
sure of the laboratory drops. The group controller registers conditions, which results in optimal energy considerati-
this condition and decreases the supply air volume flow ons.
to a minimum. This ensures that the required supply air
flows in from the corridor mainly through the laboratory Room supply air is compensated based on the room ex-
door, with the result that the room negative pressure is still haust air. Negative room pressure is achieved by supplying
maintained. only approx. 90% (programmable) of the room exhaust air
as supply air to the laboratory.

4.5.2 Room air balancing with the


group controller

The variable fume hood controllers (1) seamlessly regu- Control diagram
ate the exhaust air volume flow depending on the sash
Day operation Night operation
position. When the sash is shut, the required containment
of the fume hood can be achieved with reduced exhaust
air volume flow, which results in considerable energy and
cost savings. Total exhaust air
V [m3/h]

Total supply air

The monitoring system for the ventilation functions of the


fume hood stipulated by DIN EN 14175 is an integral part Exhaust air Labroom
Air volume

of the FC500-V fume hood controller. The operating termi-


nal is mounted on the fume hood or fitted in the lesene. Exhaust air fume hood and
switchable canopy etc.

The switchable bench extraction unit (2) can be operated,


for example, with three switching levels with the settings Additional exhaust air (constant)

Off, I and II, whereby setting I switches on low extraction shut open
and setting II switches on high extraction (freely program- Fume hood (sash)
mable). The individual exhaust air actual values are also
provided to the group controller as an analogue signal.

The constant loads (3) are included in the room balance


calculation as a fixed value (offset).

High-speed variable exhaust air control (< 3 s) requires


high-speed room supply air control (< 5 s). Due to the
different control times, oscillation is eliminated as far as
possible and at the same time the defined room negative
pressure is always guaranteed. This applies both for the
increase in exhaust air volume flow brought about by ope-
ning the sash and the reduction in exhaust air volume flow
caused by closing the sash or by external switching to re-
duced operation (night-time reduction or work-free time).

14 LabSystem Planning Manual ● Air technology for laboratories


Room air control
Chapter 5.0

4.6 Complete laboratory control, LON connected, with several variably operated fume
hoods, switchable bench extraction unit, constant floor extraction unit and additional
laboratory exhaust air, taking into account the room temperature and the redundant room
pressure measurement including recording of the fire dampers (BSK)

9 9

Supply
Exhaust air
air
VAV-A
p
Room
M
exhaust air
4 1 1 1 CAV
2
M M M M M
FC500 FC500 FC500 VAV-A 3 VAV-A
p p p p p

Switchable
Canopy exhaust

Exhaust
Fume hood 1 Fume hood 2 Fume hood 3

LCO500
7

8
p
+ - T

Fieldbus: BACnet, LON or Modbus

LabSystem components
No. Amount Type Description
1 3 FC500-V-A Fully variable fume hood controller, analogue output 0...10V DC
3 MD-200-P-MM-1 Maintenance-free measuring device DN200, PPs, socket/socket, servo motor 3 s
2 1 VAV-A-100-P Switchable volume flow controller, round, analogue output, DN100, PPs
3 1 CAV-80-S Constant volume flow controller, round, DN80, sheet steel, DD finish
4 1 VAV-A-315-S Variable volume flow controller room supply air, round, analogue input, DN315,
sheet steel
5 1 VAV-A-200-P Variable volume flow controller room exhaust air, round, analogue input, DN200,
PPs
6 1 LCO500 Laboratory controller for room balancing of 10 fume hoods (optionally this can
be extended), 8 switchable consumer loads (on/off) via digital inputs and 8 relay
outputs, field bus module, LON, FTT-10A
7 1 RDT±50Pa Room differential pressure sensor, ±50 Pa, 0...10V DC
8 1 RT-PT1000 Room temperature sensor, PT1000, active, 0...10V DC
9 3 BSK Fire damper (BSK) with status notification via contacts (not a SCHNEIDER pro-
duct)

4.6.1 Functional description


The LCO500 laboratory controller (6) can also record the
The example described is suitable for medium-sized to lar- status notifications of fire dampers (BSK) and can be up-
ge laboratories when a specific minimum level of room air graded for connection to a field bus (BACnet, LON or Mod-
exchange must be maintained, but which cannot be fully bus) at any time. Thus status and malfunction notifications
achieved by the extraction units. Control and monitoring of of the fume hoods as well as all exhaust air actual values
the fume hoods as well as maintenance of the room pres- and BSK status notifications are available, for example,
sure and the control diagram correspond to the functional on the LON network as standard variable types (SNVT)
description 4.5.1 on pages 13 and 14. This system is par- and can be included in the overall decentralised functio-
ticularly suitable for mixed systems, i.e. conventional tech- nality. The fume hoods can also be switched to reduced
nology and the LON technology can be used together. operation (night-time reduction or work-free time) via the
LON network.

LabSystem Planning Manual ● Air technology for laboratories 15 


Room air control
Chapter 5.0

4.7 Complete laboratory control, LON connected, with several variably operated fume
hoods and switchable bench extraction unit, analogue, constant floor extraction unit and
additional laboratory exhaust air, taking into account the room temperature and the
redundant room pressure measurement, including recording of the fire dampers (BSK), with
room operating device for daytime/night-time switching and additional inputs and outputs

9 9

Supply
Exhaust air
air
4

VAV-A
p
Room
M
exhaust air
1 1 1 CAV
2
M M M M M
FC500- FC500- FC500- VAV-A 3 VAV-A
p p
p LON p LON p LON

Switchable
canopy exhaust

Exhaust
Fume hood 1 Fume hood 2 Fume hood 3

LCO500 Digital relay output


Light, actuator etc.
10
7 Digital input
Button, relay contact, alarme etc.
8
Day p
Roomcontrol + - T

Fieldbus: BACnet, LON or Modbus

LabSystem components
No. Amount Type Description
1 3 FC500-V-A Fully variable fume hood controller, analogue output 0...10V DC
3 MD-200-P-MM-1 Maintenance-free measuring device DN200, PPs, socket/socket, servo motor 3 s
2 1 VAV-A-100-P Switchable volume flow controller, round, analogue output, DN100, PPs
3 1 CAV-80-S Constant volume flow controller, round, DN80, sheet steel, DD finish
4 1 VAV-A-315-S Variable volume flow controller room supply air, round, analogue input, DN315,
sheet steel
5 1 VAV-A-200-P Variable volume flow controller room exhaust air, round, analogue input, DN200,
PPs
6 1 LCO500 Laboratory controller for room balancing of 10 fume hoods (optionally this can
be extended), 8 switchable consumer loads (on/off) via digital inputs and 8 relay
outputs, field bus module, LON, FTT-10A
7 1 RDT±50Pa Room differential pressure sensor, +-50 Pa, 0...10 VDC
8 1 RT-PT1000 Room temperature sensor, PT1000, active, 0...10V DC
9 3 BSK Fire damper (BSK) with status notification via contacts (not a SCHNEIDER pro-
duct)
10 1 RBG-1T1L Room operating device with daytime/night-time button and daytime/night-time
operating mode display

4.7.1 Functional description

This example shows an entire laboratory control system The control and monitoring of the fume hoods has not
at its maximum configuration with the LCO500 laborato- changed and has already been described in detail in the
ry controller (6) and is suitable for medium-sized to large previous chapters.
laboratories with additional room exhaust air (5). The ad-
ditional room exhaust air (5) is always necessary when
a specific minimum level of room air exchange must be
maintained, which cannot be fully achieved by the extrac-
tion units alone.

16 LabSystem Planning Manual ● Air technology for laboratories


Room air control
Chapter 5.0

The main difference between this and the previous examp- 4.7.5 Room operating device
les is that the LCO500 laboratory controller (6) takes over
the entire control of the laboratory, including all alarms and The example shows an RBG-1T1L room operating device
status notifications (e.g. gas alarm, CO2 measurements, (10) connected to the LCO500 laboratory controller (6).
lighting control, etc.). Reduced operation (night-time operation) can be switched
on and off locally, i.e. within the laboratory, with the Day/
The system described here is ideally suited to mixed sys- night button. Of course, these local functions can be enab-
tems, i.e. conventional technology can be used internally led or disabled via the BSM. It is even possible to enable
in the laboratory and field bus technology (BACnet, LON the functions within a specific time period (e.g. 5 p.m. to
or Modbus) can be used for connection to the building ser- 7 a.m.).
vices management (BSM), which means that the entire
functionality can be implemented cost-effectively. Similarly, night-time operation that has been switched on
by the BSM can be switched off with the room operating
device if, for example, experiments also take place at night
4.7.2 Laboratory controller with field bus in this laboratory. An operating mode display (LED) shows
connection the user the current laboratory status. The BSM is infor-
med of all manual interventions and can thus visualise the
The laboratory controller physically only occupies one current laboratory status.
node on the field bus. In addition to reducing data traffic,
this means that fewer routers are required in large projects.
A laboratory controller monitors, controls and regulates an 4.7.6 Room air balancing
entire laboratory and, for example, a maximum of 64 LON
nodes (laboratory controllers) can be connected to a LON Control and monitoring of the fume hoods as well as main-
network before a router has to be installed. tenance of the room pressure correspond to the functio-
nal description 4.5.1 on pages 13 and 14. Like the GC10
The number of nodes can, of course, be increased at any group controller, the LCO500 laboratory controller works
time using additional routers, whereby here too, a maxi- automatically and decentrally. It balances the required
mum of 64 nodes (LON nodes) can be connected to a room supply air (4) and calculates the difference for the
subnet (e.g. LON network). additional room exhaust air (5) in order to ensure the re-
quired minimum exhaust air volume flow.

4.7.3 Advantages of field bus connection The control diagram has not changed and is the same as
the graphic displayed in the functional description 4.5 on
The key advantage here is that the building services ma- page 14.
nagement (BSM) has full access via the field bus (e.g. LON
network) to all laboratory status notifications and alarms.
Thus all exhaust air actual values of the fume hoods or
other extraction units as well as their status and malfunc- Control diagram
tion notifications are available as standard variable types
(SNVT) and can be included in the overall decentralised Day operation Night operation

functionality. The fume hoods can also be switched to re-


duced operation (night-time reduction) via the field bus.
Total exhaust air
Remote maintenance and diagnostics via the BSM or the
V [m3/h]

Total supply air

Internet are also possible.

Exhaust air Labroom


Air volume

4.7.4 Inputs and outputs via the LON Exhaust air fume hood and
switchable canopy etc.
network
Additional exhaust air (constant)
The LCO500 lab controller (6) has 8 relay outputs and 8
digital inputs, which can be set, reset and read out via the shut open

LON network. Thus, for example, the laboratory lighting Fume hood (sash)
can be switched off via the BSM when the laboratory is not
in use or it can be cooled or heated. All laboratory alarms
and status notifications (e.g. gas alarm) are also available
via the LON network.

The contacts of the fire dampers (BSK) installed in the la-


boratory are also available via the LON network, which
makes it possible to visualise the status of the BSK on the
BSM.

LabSystem Planning Manual ● Air technology for laboratories 17 


LabSystem Planning Manual ● Air technology for laboratories 18
Digital input 5 … 8 X14
Optocoupler inputs.
X101

DIn5 - + DIn5 DIn1 1.1


Non DC-isolation (Jumper = ON) DIn5 DIn1 1.2
-

DIn6 - + DIn6 DIn6


+

Shown with GND intern and DIn7 DIn2 2.1


+ +

DIn7 - + DIn7 2.2


Jumper = ON.

DIn2
-

+24V DC intern. Maximum cable DIn8


JP1

DIn8 3.1
DIn3
66 68 70 72
65 67 69 71

length < 5m. DIn8 - +


+

3.2
Non DC-isolation.

DIn3
-

DC-isolation with corresponding 4.1


JP2 and JP3

JP2
JP3

DIn4
4.2
- PE

DIn5, DIn6, DIn7, DIn8

configuration of JP2 and JP3 (see


+

DC DC DC DC

DIn4
-
24V 24V 24V 24V

terminal picture right).


X10

IOM500

X14
Digital input 5 … 8 DIn5 - + DIn5 DIn5
JP1

Optocoupler inputs. DIn5 +


DIn6 - + DIn6 DIn6
DC-isolation (Jumper = OFF). DIn6 + DIn7 DIn7
DIn7 - +
Max. 8 x 6 W = 48 W

DC-isolation.

DIn8 DIn8
DC-isolated.

External voltage 24VDC/50mA.


24V DC (+) and (-) for
X101 till X108

DIn7 +
Jumper = OFF.
24VDC/50mA.

66 68 70 72
65 67 69 71

Maximum cable length < 1000m DIn8 - +


DIn8 +
voltage supply VAV 1...8
External voltage

JP2
JP3
JP2 and JP3
DIn5, DIn6, DIn7, DIn8

X15
DIn1, DIn2, DIn3, DIn4

28 30 32 34 36 38 40 42 44 46 48 50 52 54
Jumper not connected

Analogue output AOut5 + GND1


29 31 33 35 37 39 41 43 45 47 49 51 53 55

AOut5 GND1
AOut5...AOut8 AOut6 + GND1
AOut6 GND1
GND1
LCO Connector

0(2)...10V DC/10mA AOut7 +


AOut7 GND1
Maximum cable length < 1000m

74 76 78 80
73 75 77 79

DC-isolated! AOut8 + GND1


1 2

AOut8 GND1
AIn1 + GND1
JP4

AIn1 GND1
AIn2 + GND1 Power Connector
Inputs

AIn2 GND1
AIn3 + GND1
AIn3 GND1
connected!

AIn4 + GND1
AIn4 GND1
Input current
JP4

GND1
Voltage range

AIn5 +
AIn5 GND1
AIn6 + GND1
for RS485.

(0 … 10V DC/1mA)

AIn6 GND1
AIn7 + GND1
AIn7 GND1
AIn8 + GND1
AIn8 GND1
1, 2 Jumper = ON.

GND1
Terminal resistor R

AIn9 +
AIn9 GND1
81 83 85 87 89 91 93 95 97 99

AIn10 + GND1
82 84 86 88 90 92 94 96 98100

< 1 mA
Analogue inputs DC-isolated!

AIn10 GND1
X16
POWER

0(2)…+10V DC
SUPPLY

AIn1 GND1 till AIn10 GND1 are internal


230V AC

AIn1+ till AIn10+


POWER

N L

GND
N L

75 W

from fume hood controller and other VAV´s,


Analogue inputs for exhaust air actual value
IN: 230V AC

Analogue input AIn1…AIn10


OUT: 24V DC/

+24V DC
1
X107
X105
X103
X101

ON NO
Relay 1 ON/OFF
+
+
+
+

X4

Relay contact OFF NC


K1
2 3

Max.: 3A / 230VAC
PE

Relay 1

COM
- PE
- PE
- PE
- PE

ON NO
X109

Relay 2 ON/OFF
X5
X108
X106
X104
X102

Relay contact OFF NC


K2
+
+
+
+

Max.: 3A / 230VAC COM


Relay 2

Relay 3 ON/OFF ON NO
- PE
- PE
- PE
- PE

X6

Relay contact OFF NC


K3

Max.: 3A / 230VAC
Relay 3

COM
X110

X1
F2

Relay 4 ON/OFF ON NO
X7

Relay contact OFF NC


K4

Max.: 3A / 230VAC
COM
Relay 4
250V
T1,25 A

Power Connector
Relay 5 ON/OFF ON NO
X8

Relay contact OFF NC


K5

FC500
Max.: 3A / 230VAC
11 12 13 14 15 16 17 18 19 20 21 22 23 24 25

COM
Relay 5
JP6
1
2
3
4
5
6
7
8
9
10
11
12

LON
26 27
Run

LCO Connector

LON A-IN
X9

LON A/B, FTT-10A LON A-OUT


IOM500

LON A-IN with A-OUT and B-IN LON B-IN


X14
with B-OUT internal connected! LON B-OUT DIn5 - + DIn5 DIn5
DIn1 1.1
+24V DC/DIn1 + 1.2 DIn6 - + DIn6 DIn6
Digital input 1 … 4 DIn1 - 2.1 DIn7 DIn7
DIn2 DIn7 - + DIn8 DIn8
Optocoupler inputs. Non DC-isolation. +24V DC/DIn2 + 2.2
JP1
66 68 70 72
65 67 69 71

Shown with GND intern and +24V DC DIn2 - 3.1 DIn8 - +


DIn3
3.2
JP2
JP3

intern. Maximum cable length < 5m. +24V DC/DIn3 + 4.1


Din3 - DIn4
DC-isolation with corresponding 4.2 X15
X20

configuration of JP1 (see terminal +24V DC/Din4 +


AOut5 + GND
Din4 -
picture left top). GND2 AOut6 + GND
1 2 3 4 5

AOut1 AOut7 + GND


Analogue output GND2
74 76 78 80
73 75 77 79

AOut8 + GND
1 2

AOut2
AOut1...AOut4
JP5

GND2
X10

0(2)...10V DC/10mA AOut3


AIn1 + GND
JP4

DC-isolated! GND2
AOut4 AIn2 + GND
GND AIn3 + GND
+24V DC, max. 100mA +24V DC/100mA AIn8
AIn4 + GND
GND
Analogue input A-In 0...10V DC AIn8 AIn5 + GND
RS485-A AIn6 + GND
SERIAL INTERFACE RS485-A AIn7 + GND
RS485-B
28 30 32 34 36 38 40 42 44 46 48 50 52 54

AIn8
X21

AIn8 + GND
29 31 33 35 37 39 41 43 45 47 49 51 53 55

RS485 RS485-B
AIn9 + GND
81 83 85 87 89 91 93 95 97 99

AIn10 + GND
82 84 86 88 90 92 94 96 98100

X16
NO
JP7

Relay 6 ON/OFF ON
1 2 3 4 5

OFF NC
X11
Relay contact
K6

Max.: 3A / 230VAC
Relay 6

COM
JP8

1 2
Relay 7 ON/OFF ON NO

X12
OFF NC

Industriestraße 4
Relay contact
K7

Max.: 3A / 230VAC COM


Relay 7
X 12

Relay 8 ON/OFF ON NO

Tel.: 0049 (0) 6171/884 79-0


OFF

X13
Relay contact NC

61449 Steinbach - Germany


K8
Max.: 3A / 230VAC
COM

56 57 58 59 60 61 62 63 64

SCHNEIDER-Elektronik GmbH
Relay 8

in pairs.

complete
www.schneider-elektronik.de Date: 03. Dec. 2008
Laptop

cable length < 320m.

minimum NYM 3 x 1,52


minimum NYM 3 x 1,52

Lab-Controller
Cable specification:
RS 232

Rev.: 1.1
Cable for analogue in-/outputs:
Cable for LON-network, LON A/B:
*
7
4
1

TERMINAL DIAGRAM
0
8
5
2

LCO500
,
9
6
3

Cable for voltage supply 24V DC/24V AC:


F1 F2 F3

Wires for LON A/B have to be drilled in pairs.


Service module

minimum IY(St)Y 2x2x0,8 Lg. Wires for AIn and


minimum IY(St)Y 2x2x0,8 Lg. Maximum network

Cable for voltage supply VAV 24V DC/24V AC:


GND1 as well as Aout and GND have to be drilled
Terminal diagram LCO500 4.8
Chapter 5.0
Room air control
Room air control
Chapter 5.0

4.9 LON connected laboratory control with several variably operated fume hoods and
switchable extraction unit, LON connected, constant floor extraction unit and additional
laboratory exhaust air including recording of the fire dampers (BSK), with room operating
device for daytime/night-time switching

Supply Exhaust air


4
air
VAV-L
p Room
7
exhaust air
M
1 1 1 CAV
2 7
M M M M M
FC500- FC500- FC500- VAV-L 3 VAV-L
p p
p LON p LON p LON

Switchable
canopy exhaust

Exhaust
Fume hood 1 Fume hood 2 Fume hood 3

LON-network, FTT-10A

Day

Roomcontrol

LabSystem components
No. Amount Type Description
1 3 FC500-V-L Fully variable fume hood controller, LON, FTT-10A
3 MD-200-P-MM-1 Maintenance-free measuring device DN200, PPs, socket/socket, servo motor 3 s
2 1 VAV-L-100-P Switchable volume flow controller, round, LON, FTT-10A, DN100, PPs
3 1 CAV-80-S Constant volume flow controller, round, DN80, sheet steel, DD finish
4 1 VAV-L-315-S Variable volume flow controller, room supply air, round, LON, FTT-10A, DN315,
sheet steel
5 1 VAV-L-200-P Variable volume flow controller, room exhaust air, round, LON, FTT-10A, DN200,
PPs
6 1 RBG-1T1L Room operating device with daytime/night-time button and daytime/night-time
operating mode display
7 3 BSK Fire damper (BSK) with status notification via contacts (not a SCHNEIDER pro-
duct)

4.9.1 Functional description

This example shows a LON networked laboratory control The LON controllers (4) and (5) both have 2 digital inputs
system and is suitable for medium-sized to large labora- and outputs, making it possible to record the status no-
tories with additional room exhaust air (5). The additional tifications of the fire dampers (7) and to connect a room
room exhaust air (5) is always necessary when a specific operating device (6).
minimum level of room air exchange must be maintained,
which cannot be fully achieved by the extraction units alo- All digital inputs and outputs are available as standard va-
ne. riables (SNVT) and enable, for example, access via the
building services management (BSM).

4.9.2 Room air balancing Control and monitoring of the fume hoods as well as main-
tenance of the room pressure and the control diagram cor-
An independent balancing LON controller (4) is used for respond to the functional descriptions 4.5.1 and 4.7.1.
volume flow control of the room supply air. For volume flow
control of the room exhaust air, an independent LON con-
troller (5) is also used, which takes over the calculation of
the difference value for the room exhaust air.

LabSystem Planning Manual ● Air technology for laboratories 19 


Room air control
Chapter 5.0

4.10 Complete laboratory control, LON connected, with several variably operated fume
hood controllers and switchable bench extraction unit, LON connected, constant floor
extraction unit and additional laboratory exhaust air, taking into account the room
temperature and the redundant room pressure measurement including recording of the
fire dampers (BSK), with room operating device for daytime/night-time switching

Supply
Exhaust air
air
4

VAV-L
p
Room
9
M
exhaust air
1 1 1 CAV
2
M M M M M
FC500- FC500- FC500- VAV-L 3 VAV-L
p p
p LON p LON p LON

Switchable
canopy exhaust

Exhaust
Fume hood 1 Fume hood 2 Fume hood 3

LON-network, FTT-10A

7
Day p
Roomcontrol + - T

LabSystem components
No. Amount Type Description
1 3 FC500-V-L Fully variable fume hood controller, LON, FTT-10A
3 MD-200-P-MM-1 Maintenance-free measuring device DN200, PPs, socket/socket, servo motor 3 s
2 1 VAV-L-100-P Switchable volume flow controller, round, LON, FTT-10A, DN100, PPs
3 1 CAV-80-S Constant volume flow controller, round, DN80, sheet steel, DD finish
4 1 VAV-L-315-S Variable volume flow controller room supply air, round, LON, FTT-10A, DN315,
sheet steel
5 1 VAV-L-200-P Variable volume flow controller room exhaust air, round, LON, FTT-10A, DN200,
PPs
6 1 RDT±50Pa Room differential pressure sensor, ±50 Pa, 0...10V DC
7 1 RT-PT1000 Room temperature sensor, PT1000, active, 0...10V DC
8 1 RBG-1T1L Room operating device with daytime/night-time button and daytime/night-time
operating mode display
9 3 BSK Fire damper with status notification via contacts (not a SCHNEIDER product)

4.10.1 Functional description

This example shows a complete LON networked labora- all volume flow controllers are connected end-to-end in the
tory control system at its maximum configuration and is LON network.
suitable for medium-sized to large laboratories with additi-
onal room exhaust air (5). The additional room exhaust air The peripheral devices, such as the RDT±50Pa room dif-
(5) is always necessary when a specific minimum level of ferential pressure sensor (6), the RT-PT1000 room tem-
room air exchange must be maintained, which cannot be perature sensor (7), the RBG-1T1L room operating device
fully achieved by the extraction units alone. (8) and the status notifications of the fire dampers (9) are
connected directly to the individual inputs and outputs of
The control and monitoring of the fume hoods has not the LON room supply air (4) and room exhaust air (5) con-
changed and has already been described in detail in the trollers.
previous chapters.
All digital inputs and outputs are available as standard va-
This example is functionally the same as example 4.7. The riables (SNVT) and enable, for example, access via the
LCO500 laboratory controller is not necessary here, since building services management (BSM).

20 LabSystem Planning Manual ● Air technology for laboratories


Room air control
Chapter 5.0

4.10.2 Advantages of the LON network

All exhaust air actual values of the fume hoods or other 4.10.6 Room operating device for daytime/
extraction units as well as their status and malfunction no- night-time switching and activation of the
tifications are available as standard variable types (SNVT) room differential pressure sensor
and can be included in the overall decentralised functio-
nality. The fume hoods or other LON connected extraction The RBG-1T1L room operating device (8) is connected
units can also be switched to reduced operation (night- to the digital inputs and outputs and the RDT±50Pa red-
time reduction or work-free time) via the LON network. undant room differential pressure sensor (6) is connected
to the analogue output of the LON controller (4) and also
Connection to the BSM is possible without restrictions, provides the room differential pressure and daytime/night-
which enables remote maintenance and diagnostics via time switching as SNVTs on the LON network.
the BSM or the Internet.
Reduced operation (night-time operation) can be switched
The system presented here enables cost-efficient project on and off locally, i.e. within the laboratory, with the Day/
implementation through easy connection of peripheral night button. Of course, these local functions can be enab-
components to the LON controller. led or disabled via the BSM. It is even possible to enable
the functions within a specific time period (e.g. 5 p.m. to
7 a.m.). Similarly, night-time operation that has been swit-
4.10.3 Router for max. 64 nodes ched on by the BSM can be switched off with the room
operating device if, for example, experiments also take
From a maximum of 64 nodes (subscribers) a router is re- place at night in this laboratory. An operating mode display
quired. In practice, each laboratory is physically separated (LED) shows the user the current laboratory status. The
by a router every 20-30 nodes in order to limit data traffic BSM is informed of all manual interventions and can thus
on the LON network and to avoid unnecessary increases visualise the current laboratory status.
in reaction time of the entire system,

The number of nodes can be increased at any time th- 4.10.7 Room air balancing
rough the use of additional routers and/or repeaters.
Control and monitoring of the fume hoods as well as main-
tenance of the room pressure correspond to the functio-
4.10.4 Free inputs and outputs of the LON nal descriptions 4.5.1 and 4.7.1. The LON controller (4)
controller balances the exhaust air actual values of the fume hood
controllers and the switchable bench extraction unit and
The LON controllers (4) and (5) both have 2 digital inputs, automatically regulates the room supply air. Room supply
2 digital outputs, 2 analogue inputs (0...10 VDC) and 1 air is compensated based on the room exhaust air. Nega-
analogue output (0...10 VDC). tive room pressure is achieved by supplying only approx.
90% (programmable) of the entire exhaust air as supply
All inputs and outputs are available via the LON network air to the laboratory.
as standard variable types (SNVT) and can easily be in-
cluded in the overall decentralised functionality. The LON controller (5) calculates the difference for the ad-
ditional room exhaust air and regulates the required mini-
The contacts of the fire dampers (BSK) installed in the la- mum exhaust air volume flow.
boratory are also available via the LON network, which
makes it possible to visualise the status of the BSK on the
BSM. At the same time, it is also possible to specify via Control diagram
the binding that the FC500-V-LON fume hood controllers
in the corresponding laboratory also receive the status in- The control diagram has not changed and is the same as
formation from the fire dampers and automatically close the graphic displayed in the functional description 4.7 on
the exhaust air dampers. This example demonstrates how page 17.
easily extended functionality can be implemented via the
LON network.

4.10.5 Room setpoint and room temperature


actual value

The RT-PT1000 room temperature sensor (7) is connec-


ted to both analogue inputs of the LON controller (5) and
thus provides the room temperature setpoint and the room
temperature actual value as SNVTs on the LON network.
Via the binding the functionality of the volume flow dis-
placement can be used for temperature control. In addi-
tion, LON control valves for regulating the static heating
elements can be connected.

LabSystem Planning Manual ● Air technology for laboratories 21 


Room air control
Chapter 5.0

5.1 Product overview Room ventilation


controllers

The diagram shows an overview of the products that are Technical data sheets, further information and tender
available from SCHNEIDER in the product group Room specifications for the LCO500, GC10, RAM500, VAV and
ventilation controllers. CAV products are available for download on the Internet
at www.schneider-elektronik.de.
See Chapter 1, Section 6.1 for the full LabSystem product
overview.

Product group Product Short description Chapter


Room balancing LCO500 Laboratory controller, 10 x analogue input, 8 x analogue output, 8 x 5.0
digital input, 8 x relay output, optional field bus module, malfunction noti-
fication, actuation of room supply and exhaust air volume flow controllers
GC10 Room group controller, 10 x analogue input, 4 x analogue aoutput, 4 x 5.0
digital input, 3 x relay output, optional field bus module, malfunction noti-
fication, actuation of room supply and exhaust air volume flow controllers
RAM500 Pluggable module for FC500, 4 x analogue input, 1 x analogue output 5.0

High-speed room VAV Volume flow controller for laboratory supply and laboratory exhaust air, 5.0
supply/exhaust air analogue input 0(2)...10V DC for setpoint, optional field bus module,
controller control speed < 3 s

Mechanical auto- CAV Volume flow controller for floor extraction units and safety cabinets, 5.0
matic volume flow mechanical, automatic, without auxiliary power
controller

22 LabSystem Planning Manual ● Air technology for laboratories

You might also like