Professional Documents
Culture Documents
5.0
Chapter 5.0
LabSystem
Room air control in laboratories
Table of contents
Section Title Page
1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Laboratory controller LCO500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Group controller GC10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Room control module RAM500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.5 High-speed variable volume flow controllers (VAV) . . . . . . . . . . . . . . 3
1.6 Quick selection LabSystem products . . . . . . . . . . . . . . . . . . . . . . 4
Table of contents
Section Title Page
4.3.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.4 Laboratory control, low cost, with several variably
operated fume hoods, analogue and RAM500 . . . . . . . . . . . . . . . 12
4.4.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.5 Complete laboratory control with several variably
operated fume hoods, analogue and GC10 . . . . . . . . . . . . . . . . . 13
4.5.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.5.2 Room air balancing with the group controller . . . . . . . . . . . . . . . . . 14
4.5.3 Suitable for medium-sized to large laboratories . . . . . . . . . . . . . . . . . . . . 14
4.6 Complete laboratory control, LON connected, with
several variably operated fume hoods, analogue and LCO500 . . . . . 15
4.6.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.7 Complete laboratory control, LON connected, with
several variably operated fume hoods, analogue and LCO500 . . . . . 16
4.7.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.7.2 Laboratory controller with field bus connection . . . . . . . . . . . . . . . . . . . . . 17
4.7.3 Advantages of field bus connection . . . . . . . . . . . . . . . . . . . . . . . . 17
4.7.4 Inputs and outputs via the LON network . . . . . . . . . . . . . . . . . 17
4.7.5 Room operating device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.7.6 Room air balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.8 Terminal diagram LCO500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.9 LON connected laboratory control with several variably
operated fume hoods, LON connected . . . . . . . . . . . . . . . . . . . 19
4.9.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.9.2 Room air balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.10 Complete laboratory controll, LON connected, with several
variably operated fume hoods, LON connected . . . . . . . . . . . . . . . 20
4.10.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.10.2 Advantages of the LON network . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.10.3 Router for max. 64 nodes . . . . . . . . . . . . . . . . . . . . . . 21
4.10.4 Free inputs and outputs of the LON controller . . . . . . . . . . . . . . . . . . . . . 21
4.10.5 Room setpoint and room temperature actual value . . . . . . . . . . . . . . . . . . . . 21
4.10.6 Room operating device for daytime/night-time switching and
for switching on the room differential pressure sensor . . . . . . . . . . . . . . . . . . . 21
4.10.7 Room air balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1.1 Introduction
Table 5.1 gives a quick overview of the configurations of Technical data sheets, further information and tender
SCHNEIDER's various room ventilation products. specifications for the LCO500, GC10, RAM500, VAV-A,
VAV-L, CAV and DK products are available for download
on the Internet at www.schneider-elektronik.de.
Table 5.1: Quick selection table
LabSystem ● Products
Function Laboratory Group con- Room Variable Variable
controller troller control volume flow volume flow
module controller, controller,
LCO-300 GC10 RAM500 LON analogue
VAV-L VAV-A
Analogue inputs 0(2)...10V DC 10 10 4 + internal 1 1
Extension of analogue inputs through Yes Yes No No No
cascading
Analogue outputs ( 0... 10V DC) 8 4 2 1 1
Digital inputs (switchable consumer loads) 8 8 4 2 2
Relay outputs (potential-free) 8 No No 2 2
Network BACnet
LON LON No LON No
Modbus
Integrated router functionality Yes Yes No No No
Maximum balancing of consumer loads 10 + casca- 10 + casca- 5 - -
with analogue exhaust air actual values ding ding
Maximum balancing of consumer loads 16 16 - 16 -
with LON interface
Laboratories with multiple fume hoods and extraction units The VAV-A variable volume flow controller with analogue
have complex room supply air and room exhaust air con- input 0(2)...10V DC can be used for room supply air and
trol requirements. room exhaust air applications. The setpoint that is to be
regulated is balanced in the LCO500 laboratory controller,
The room air change is defined in DIN 1946, Part 7 and the GC10 group controller or the RAM500 room control
can be calculated with the following rule of thumb: module and is available as an analogue value 0(2)...10V
DC).
25m³ per hour exhaust air volume
25m³ /h x m² flow, multiplied by the laboratory
main floor space in m².
2.1.2 Programming
Figure 5.4: Variable volume flow controller, slave, Connection to the room balance is done via a potential-
rectangular, steel, VAV-S-500-400-S-K-0-0 free contact on the switch as a switched offset value.
CAV constant volume flow controllers are used in conti- Figure 5.6: Switchable consumer load, with servo
nuous extraction units. Storage cabinets, base extraction motor, PPs, DK-160-P-MM-3
units or floor extraction units must be continuously extrac-
ted with a constant air volume. Mechanical (without auxili-
ary power) and electronic constant volume flow controllers 2.7 Energy savings
regulate a predefined volume flow independent of the duct
pressure. Mechanical constant volume flow controllers Demand-related volume flow control of the required room
are available in two-component finish and PPs. Electronic supply air and exhaust air means a considerable reduction
constant volume flow controllers are available in PPs. in energy consumption and at the same time maximum
safety for the operating personnel.
Connection to the room balance is in the form of a fixed
offset value. European and American standards in which room air ex-
change is defined, e.g. British Standard, DIN, DIN EN,
Norm Francaise, ASHRAE, etc., can easily be implemen-
ted.
By making full use of the diversity factor, smaller dimensio- These setpoints are available as analogue outputs
ning of the entire system is possible without performance 0(2)...10V DC and actuate the corresponding variable vo-
loss. Demand-related system planning achieves a consi- lume flow controllers and/or frequency inverters for room
derable reduction of the operating costs. supply and exhaust air control.
all these measurement data into account and has seve- HOOD #1 HOOD #2 HOOD #3
calculated room balance as redundant values. Supply air VAV GND1 GC10
The SCHEIDER LCO500, GC10 and RAM500 room con- HOOD #4 HOOD #5
trol products calculate the room balance of the laboratory
depending on the variable, switchable and constant con-
sumer loads (fume hoods, extraction units, etc.) and provi-
de a setpoint as a control variable for the variable volume
flow controller (room supply air). 3.4 LON network
In order to maintain the required minimum room air ex- The room control products LCO500 and GC10 can be
change, a variable volume flow controller (room exhaust connected to the LON network. In addition to processing
air) can also be actuated. exhaust air actual values for room balancing, remote sig-
nals, such as reduced operation (night-time reduction) and
Laboratory specific requirements such as night-time ope- setpoints, can be sent via the LON network. This results in
ration, daytime operation and maximum operation (emer- a considerable increase in flexibility and a reduction of the
gency) can also be integrated. effort required for cabling.
+/-A1
FC500
+/-A1
offers a high level of comfort without draughts and pres-
sure fluctuations. Constant reading and checking of the
HOOD #6 HOOD #7 control variables ensures very fast, stable and demand-
LAB-
related control of the supply air volume flow, taking protec-
Supply air VAV
ROOM #2 tive pressure maintenance into account.
GC10
FC500
+/-A1
FC500
+/-A1
3.7 Balancing of several
laboratories
HOOD #8 HOOD #9
3.6 Negative pressure in the laboratory Connection to the building services management (BSM) is
guaranteed by standardised interfaces.
To ensure a defined pressure ratio, approx. 10% less sup-
ply air is fed in than exhaust air is extracted. The supply air Connection to the LON network is possible and conside-
value is calculated using the following formula: rably reduces the mounting and installation costs while at
the same time improving system performance.
Supply air 2
Exhaust air
V [m3/h]
p VAV-S
M
VAV-A 800
M p
1
600
Exhaust air volume
400
200
LabSystem components
No. Amount Type Description
1 1 VAV-A-200-S Variable volume flow controller, round, analogue input, DN200, galvanised
steel
2 1 VAV-S-200-S Variable volume flow controller, round, slave, DN200, galvanised steel
4.2 Laboratory ventilation taking into then increases the room supply air volume flow until the
account the room pressure and the room negative pressure has reached the required value
temperature again.
1 the laboratory door, with the result that the room negative
pressure is maintained.
LabSystem components
No. Amount Type Description
1 1 VAV-A-200-S Variable volume flow controller, round, analogue input, DN200, galvanised
steel
2 1 VAV-A-200-S Variable volume flow controller, round, analogue input, DN200, galvanised
steel
3 1 RT-PT1000 Room temperature sensor, PT1000, active, 0...10V DC
4 1 RDT±50Pa Room differential pressure sensor, ±50 Pa, 0...10V DC
400
within certain limits, in order to regulate the laboratory tem-
perature.
200
4.3 Laboratory control with a variably increase in exhaust air volume flow brought about by ope-
operated fume hood and a constant ning the sash and the reduction in exhaust air volume flow
floor extraction unit caused by closing the sash or by external switching to re-
duced operation (night-time reduction or work-free time).
3
the main floor space (8 room air changes).
p FC500
LabSystem components
No. Amount Type Description
1 1 FC500-V-A Fully variable fume hood controller, analogue output 0...10V DC
1 MD-200-P-MM-1 Maintenance-free measuring device DN200, PPs, socket/socket, servo
motor 3 s
2 1 VAV-A-200-S Variable volume flow controller, round, analogue input, DN200, galvanised
steel
3 1 CAV-80-S Constant volume flow controller, round, DN80, sheet steel, DD finish
(1) and the CAV-80 constant floor extraction unit (3). The 800
room supply air is fed in via the VAV-A-200-S volume flow
controller with analogue input (2). Control of the variable
600
Exhaust air volume
exhaust air, the variable supply air and the addition of the
constant exhaust air is taken over completely by the vari-
able fume hood controller (1). 400
Room exhaust air
Room supply air
The variable fume hood controller (1) seamlessly regula- 200
tes the exhaust air volume flow depending on the sash
Additional exhaust air
position. When the sash is shut, the required containment
of the fume hood can be achieved with reduced exhaust shut open
air volume flow, which results in considerable energy and Fume hood (sash)
cost savings. The monitoring system for the ventilation
functions of the fume hood stipulated by DIN EN 14175
is an integral part of the FC500-V-A fume hood controller.
The operating terminal is mounted on the fume hood or The control diagram shows the effect of a closed and open
fitted in the lesene. fume hood sash on the variable exhaust air and the sup-
plied variable supply air during daytime and night-time
High-speed variable exhaust air control (< 3 s) requires operation (reduced operation).
high-speed room supply air control (< 5 s). Due to the
different control times, oscillation is eliminated as far as The constant floor extraction unit is included in the room
possible and at the same time the defined room negative balancing calculation as a constant value (e.g. 80m3/h).
pressure is always guaranteed. This applies both for the
4.4 Laboratory control, low cost, with several variably operated fume hoods, switchable
bench extraction unit and constant floor extraction unit
Supply air 3
Exhaust air
VAV-A
p
M CAV
1 1 1
4
M M M M
FC500 FC500 FC500 VAV-A 5
p
p 2 p p
RAM
Switchable
canopy exhaust
Exhaust
Fume hood 1 Fume hood 2 Fume hood 3
LabSystem components
No. Amount Type Description
1 3 FC500-V-A Fully variable fume hood controller, analogue output 0...10V DC
3 MD-200-P-MM-1 Maintenance-free measuring device DN200, PPs, socket/socket, servo motor 3 s
2 1 RAM500 Room addition module for max. 5 fume hoods
3 1 VAV-A-315-S Variable volume flow controller, round, analogue input, DN315, galvanised steel
4 1 VAV-A-100-P Switchable volume flow controller, round, analogue output, DN100, PPs
5 1 CAV-80-S Constant volume flow controller, round, DN80, sheet steel, DD finish
With this version the entire laboratory exhaust air is extrac- Day operation Night operation
ted via three FC500-V-A variable fume hood controllers
(1), a switchable bench extraction unit (4) and a CAV-80
V [m3/h]
constant floor extraction unit (5). The room supply air is 800
fed in via the VAV-A-315-S (2) volume flow controller. The
room balancing is done by the RAM500 room addition mo-
600
Exhaust air volume
cuit board which can be attached to any FC500-V-A fume Additional exhaust air
hood controller. A maximum of 5 variable consumer loads
with 0...10V DC analogue output can be connected. Thus shut open
Fume hood (sash)
smaller laboratories can be cost-effectively equipped with
0...10V DC analogue technology.
The control diagram shows the effect of a closed and open
Control and monitoring of the fume hoods as well as main- fume hood sash on the variable exhaust air and the sup-
tenance of the room pressure correspond to the functional plied variable supply air during daytime operation. During
description 4.3.1 on page 11. night-time operation a minimum room air exchange is re-
gulated.
4.5 Complete laboratory control with several variably operated fume hoods, switchable
bench extraction unit, constant floor extraction unit and additional laboratory exhaust air,
taking into account the room temperature and the redundant room pressure measurement
Switchable
Canopy exhaust
Exhaust
Fume hood 1 Fume hood 2 Fume hood 3
GC10
6
7
8
p
+ - T
LabSystem components
No. Amount Type Description
1 3 FC500-V-A Fully variable fume hood controller, analogue output 0...10V DC
3 MD-200-P-MM-1 Maintenance-free measuring device DN200, PPs, socket/socket, servo motor 3 s
2 1 VAV-A-100-P Switchable volume flow controller, round, analogue output, DN100, PPs
3 1 CAV-80-S Constant volume flow controller, round, DN80, sheet steel, DD finish
4 1 VAV-A-315-S Variable volume flow controller room supply air, round, analogue input, DN315,
sheet steel
5 1 VAV-A-200-P Variable volume flow controller room exhaust air, round, analogue input, DN200,
PPs
6 1 GC10 Group controller for room balancing for n x 10 fume hoods 0...10 VDC and
n x 4 switchable consumer loads (on/off) (n = number of GC10 group controllers)
7 1 RDT±50Pa Room differential pressure sensor, ±50 Pa, 0...10V DC
8 1 RT-PT1000 Room temperature sensor, PT1000, active, 0...10V DC
With this version, part of the laboratory exhaust air is ex- The GC10 group controller can balance a maximum of 10
tracted by three FC500-V-A variable fume hood controllers fume hoods (optionally this can be extended) or other va-
(1), a switchable bench extraction unit (2) and a CAV-80 riable consumer loads and in the standard version has 10
constant floor extraction unit (3). In order to ensure con- analogue inputs 0(2)...10V DC. The exhaust air actual va-
stant room air exchange (e.g. 25m³/h x m²) the laboratory lues of the connected consumer loads (m³/h) are provided
exhaust air is also extracted via its own VAV-A-200-P vo- to the group controller as an analogue signal (0...10V DC).
lume flow controller (5). The laboratory supply air is fed in Wiring is done with standard cables (e.g. I(ST)Y 2*2*0.8)
via the VAV-A-315-S volume flow controller with analogue using conventional technology.
output (4).
The group controller also has 4 analogue outputs, which
The entire room balancing for the supply air volume flow serve as setpoints 0(2)...10V DC for volume flow control-
controller (4) and the calculation of the difference for the lers (supply air, exhaust air) and/or as direct actuation for
exhaust air volume flow controller (5) is done by the GC10 frequency inverters. Wiring is also done with standard ca-
group controller (6). bles using conventional technology.
In addition, a room differential pressure sensor RDT±50Pa 4.5.3 Suitable for medium-sized to large
(7) for redundant room pressure measurement and an RT- laboratories
PT1000 room operating device (8) with room setpoint de-
vice and room sensor (Pt1000) are each connected to an The example described is suitable for medium-sized to
analogue input of the group controller. large laboratories when a specific minimum level of room
air exchange must be maintained, but which cannot be
With the room operating device, the laboratory room tem- fully achieved by the extraction units. An additional volume
perature can be regulated via the volume flow displace- flow controller for room exhaust air (5) always regulates
ment and additional control valves for the static heating the difference between the technically induced exhaust air
elements. The required room air exchange rate is always of the extraction units and the required minimum exhaust
maintained and may not be underrun. air volume flow.
The room differential pressure sensor (7) is used for red- The required minimum exhaust air volume flow for labo-
undant room pressure measurement. The group controller ratories stipulated by DIN 1946, Part 7 is 25m³/h x m² in
(6) compares the calculated value with the measured va- relation to the main floor space (8 room air changes).
lue and can thus recognise and signal any problems that
arise in good time. During reduced operation (night-time reduction), 4 room
air changes are sufficient. In all events the minimum room
If the laboratory door is opened, the room negative pres- air exchange should be defined for the changed operating
sure of the laboratory drops. The group controller registers conditions, which results in optimal energy considerati-
this condition and decreases the supply air volume flow ons.
to a minimum. This ensures that the required supply air
flows in from the corridor mainly through the laboratory Room supply air is compensated based on the room ex-
door, with the result that the room negative pressure is still haust air. Negative room pressure is achieved by supplying
maintained. only approx. 90% (programmable) of the room exhaust air
as supply air to the laboratory.
The variable fume hood controllers (1) seamlessly regu- Control diagram
ate the exhaust air volume flow depending on the sash
Day operation Night operation
position. When the sash is shut, the required containment
of the fume hood can be achieved with reduced exhaust
air volume flow, which results in considerable energy and
cost savings. Total exhaust air
V [m3/h]
Off, I and II, whereby setting I switches on low extraction shut open
and setting II switches on high extraction (freely program- Fume hood (sash)
mable). The individual exhaust air actual values are also
provided to the group controller as an analogue signal.
4.6 Complete laboratory control, LON connected, with several variably operated fume
hoods, switchable bench extraction unit, constant floor extraction unit and additional
laboratory exhaust air, taking into account the room temperature and the redundant room
pressure measurement including recording of the fire dampers (BSK)
9 9
Supply
Exhaust air
air
VAV-A
p
Room
M
exhaust air
4 1 1 1 CAV
2
M M M M M
FC500 FC500 FC500 VAV-A 3 VAV-A
p p p p p
Switchable
Canopy exhaust
Exhaust
Fume hood 1 Fume hood 2 Fume hood 3
LCO500
7
8
p
+ - T
LabSystem components
No. Amount Type Description
1 3 FC500-V-A Fully variable fume hood controller, analogue output 0...10V DC
3 MD-200-P-MM-1 Maintenance-free measuring device DN200, PPs, socket/socket, servo motor 3 s
2 1 VAV-A-100-P Switchable volume flow controller, round, analogue output, DN100, PPs
3 1 CAV-80-S Constant volume flow controller, round, DN80, sheet steel, DD finish
4 1 VAV-A-315-S Variable volume flow controller room supply air, round, analogue input, DN315,
sheet steel
5 1 VAV-A-200-P Variable volume flow controller room exhaust air, round, analogue input, DN200,
PPs
6 1 LCO500 Laboratory controller for room balancing of 10 fume hoods (optionally this can
be extended), 8 switchable consumer loads (on/off) via digital inputs and 8 relay
outputs, field bus module, LON, FTT-10A
7 1 RDT±50Pa Room differential pressure sensor, ±50 Pa, 0...10V DC
8 1 RT-PT1000 Room temperature sensor, PT1000, active, 0...10V DC
9 3 BSK Fire damper (BSK) with status notification via contacts (not a SCHNEIDER pro-
duct)
4.7 Complete laboratory control, LON connected, with several variably operated fume
hoods and switchable bench extraction unit, analogue, constant floor extraction unit and
additional laboratory exhaust air, taking into account the room temperature and the
redundant room pressure measurement, including recording of the fire dampers (BSK), with
room operating device for daytime/night-time switching and additional inputs and outputs
9 9
Supply
Exhaust air
air
4
VAV-A
p
Room
M
exhaust air
1 1 1 CAV
2
M M M M M
FC500- FC500- FC500- VAV-A 3 VAV-A
p p
p LON p LON p LON
Switchable
canopy exhaust
Exhaust
Fume hood 1 Fume hood 2 Fume hood 3
LabSystem components
No. Amount Type Description
1 3 FC500-V-A Fully variable fume hood controller, analogue output 0...10V DC
3 MD-200-P-MM-1 Maintenance-free measuring device DN200, PPs, socket/socket, servo motor 3 s
2 1 VAV-A-100-P Switchable volume flow controller, round, analogue output, DN100, PPs
3 1 CAV-80-S Constant volume flow controller, round, DN80, sheet steel, DD finish
4 1 VAV-A-315-S Variable volume flow controller room supply air, round, analogue input, DN315,
sheet steel
5 1 VAV-A-200-P Variable volume flow controller room exhaust air, round, analogue input, DN200,
PPs
6 1 LCO500 Laboratory controller for room balancing of 10 fume hoods (optionally this can
be extended), 8 switchable consumer loads (on/off) via digital inputs and 8 relay
outputs, field bus module, LON, FTT-10A
7 1 RDT±50Pa Room differential pressure sensor, +-50 Pa, 0...10 VDC
8 1 RT-PT1000 Room temperature sensor, PT1000, active, 0...10V DC
9 3 BSK Fire damper (BSK) with status notification via contacts (not a SCHNEIDER pro-
duct)
10 1 RBG-1T1L Room operating device with daytime/night-time button and daytime/night-time
operating mode display
This example shows an entire laboratory control system The control and monitoring of the fume hoods has not
at its maximum configuration with the LCO500 laborato- changed and has already been described in detail in the
ry controller (6) and is suitable for medium-sized to large previous chapters.
laboratories with additional room exhaust air (5). The ad-
ditional room exhaust air (5) is always necessary when
a specific minimum level of room air exchange must be
maintained, which cannot be fully achieved by the extrac-
tion units alone.
The main difference between this and the previous examp- 4.7.5 Room operating device
les is that the LCO500 laboratory controller (6) takes over
the entire control of the laboratory, including all alarms and The example shows an RBG-1T1L room operating device
status notifications (e.g. gas alarm, CO2 measurements, (10) connected to the LCO500 laboratory controller (6).
lighting control, etc.). Reduced operation (night-time operation) can be switched
on and off locally, i.e. within the laboratory, with the Day/
The system described here is ideally suited to mixed sys- night button. Of course, these local functions can be enab-
tems, i.e. conventional technology can be used internally led or disabled via the BSM. It is even possible to enable
in the laboratory and field bus technology (BACnet, LON the functions within a specific time period (e.g. 5 p.m. to
or Modbus) can be used for connection to the building ser- 7 a.m.).
vices management (BSM), which means that the entire
functionality can be implemented cost-effectively. Similarly, night-time operation that has been switched on
by the BSM can be switched off with the room operating
device if, for example, experiments also take place at night
4.7.2 Laboratory controller with field bus in this laboratory. An operating mode display (LED) shows
connection the user the current laboratory status. The BSM is infor-
med of all manual interventions and can thus visualise the
The laboratory controller physically only occupies one current laboratory status.
node on the field bus. In addition to reducing data traffic,
this means that fewer routers are required in large projects.
A laboratory controller monitors, controls and regulates an 4.7.6 Room air balancing
entire laboratory and, for example, a maximum of 64 LON
nodes (laboratory controllers) can be connected to a LON Control and monitoring of the fume hoods as well as main-
network before a router has to be installed. tenance of the room pressure correspond to the functio-
nal description 4.5.1 on pages 13 and 14. Like the GC10
The number of nodes can, of course, be increased at any group controller, the LCO500 laboratory controller works
time using additional routers, whereby here too, a maxi- automatically and decentrally. It balances the required
mum of 64 nodes (LON nodes) can be connected to a room supply air (4) and calculates the difference for the
subnet (e.g. LON network). additional room exhaust air (5) in order to ensure the re-
quired minimum exhaust air volume flow.
4.7.3 Advantages of field bus connection The control diagram has not changed and is the same as
the graphic displayed in the functional description 4.5 on
The key advantage here is that the building services ma- page 14.
nagement (BSM) has full access via the field bus (e.g. LON
network) to all laboratory status notifications and alarms.
Thus all exhaust air actual values of the fume hoods or
other extraction units as well as their status and malfunc- Control diagram
tion notifications are available as standard variable types
(SNVT) and can be included in the overall decentralised Day operation Night operation
4.7.4 Inputs and outputs via the LON Exhaust air fume hood and
switchable canopy etc.
network
Additional exhaust air (constant)
The LCO500 lab controller (6) has 8 relay outputs and 8
digital inputs, which can be set, reset and read out via the shut open
LON network. Thus, for example, the laboratory lighting Fume hood (sash)
can be switched off via the BSM when the laboratory is not
in use or it can be cooled or heated. All laboratory alarms
and status notifications (e.g. gas alarm) are also available
via the LON network.
DIn2
-
DIn8 3.1
DIn3
66 68 70 72
65 67 69 71
3.2
Non DC-isolation.
DIn3
-
JP2
JP3
DIn4
4.2
- PE
DC DC DC DC
DIn4
-
24V 24V 24V 24V
IOM500
X14
Digital input 5 … 8 DIn5 - + DIn5 DIn5
JP1
DC-isolation.
DIn8 DIn8
DC-isolated.
DIn7 +
Jumper = OFF.
24VDC/50mA.
66 68 70 72
65 67 69 71
JP2
JP3
JP2 and JP3
DIn5, DIn6, DIn7, DIn8
X15
DIn1, DIn2, DIn3, DIn4
28 30 32 34 36 38 40 42 44 46 48 50 52 54
Jumper not connected
AOut5 GND1
AOut5...AOut8 AOut6 + GND1
AOut6 GND1
GND1
LCO Connector
74 76 78 80
73 75 77 79
AOut8 GND1
AIn1 + GND1
JP4
AIn1 GND1
AIn2 + GND1 Power Connector
Inputs
AIn2 GND1
AIn3 + GND1
AIn3 GND1
connected!
AIn4 + GND1
AIn4 GND1
Input current
JP4
GND1
Voltage range
AIn5 +
AIn5 GND1
AIn6 + GND1
for RS485.
(0 … 10V DC/1mA)
AIn6 GND1
AIn7 + GND1
AIn7 GND1
AIn8 + GND1
AIn8 GND1
1, 2 Jumper = ON.
GND1
Terminal resistor R
AIn9 +
AIn9 GND1
81 83 85 87 89 91 93 95 97 99
AIn10 + GND1
82 84 86 88 90 92 94 96 98100
< 1 mA
Analogue inputs DC-isolated!
AIn10 GND1
X16
POWER
0(2)…+10V DC
SUPPLY
N L
GND
N L
75 W
+24V DC
1
X107
X105
X103
X101
ON NO
Relay 1 ON/OFF
+
+
+
+
X4
Max.: 3A / 230VAC
PE
Relay 1
COM
- PE
- PE
- PE
- PE
ON NO
X109
Relay 2 ON/OFF
X5
X108
X106
X104
X102
Relay 3 ON/OFF ON NO
- PE
- PE
- PE
- PE
X6
Max.: 3A / 230VAC
Relay 3
COM
X110
X1
F2
Relay 4 ON/OFF ON NO
X7
Max.: 3A / 230VAC
COM
Relay 4
250V
T1,25 A
Power Connector
Relay 5 ON/OFF ON NO
X8
FC500
Max.: 3A / 230VAC
11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
COM
Relay 5
JP6
1
2
3
4
5
6
7
8
9
10
11
12
LON
26 27
Run
LCO Connector
LON A-IN
X9
AOut8 + GND
1 2
AOut2
AOut1...AOut4
JP5
GND2
X10
DC-isolated! GND2
AOut4 AIn2 + GND
GND AIn3 + GND
+24V DC, max. 100mA +24V DC/100mA AIn8
AIn4 + GND
GND
Analogue input A-In 0...10V DC AIn8 AIn5 + GND
RS485-A AIn6 + GND
SERIAL INTERFACE RS485-A AIn7 + GND
RS485-B
28 30 32 34 36 38 40 42 44 46 48 50 52 54
AIn8
X21
AIn8 + GND
29 31 33 35 37 39 41 43 45 47 49 51 53 55
RS485 RS485-B
AIn9 + GND
81 83 85 87 89 91 93 95 97 99
AIn10 + GND
82 84 86 88 90 92 94 96 98100
X16
NO
JP7
Relay 6 ON/OFF ON
1 2 3 4 5
OFF NC
X11
Relay contact
K6
Max.: 3A / 230VAC
Relay 6
COM
JP8
1 2
Relay 7 ON/OFF ON NO
X12
OFF NC
Industriestraße 4
Relay contact
K7
Relay 8 ON/OFF ON NO
X13
Relay contact NC
56 57 58 59 60 61 62 63 64
SCHNEIDER-Elektronik GmbH
Relay 8
in pairs.
complete
www.schneider-elektronik.de Date: 03. Dec. 2008
Laptop
Lab-Controller
Cable specification:
RS 232
Rev.: 1.1
Cable for analogue in-/outputs:
Cable for LON-network, LON A/B:
*
7
4
1
TERMINAL DIAGRAM
0
8
5
2
LCO500
,
9
6
3
4.9 LON connected laboratory control with several variably operated fume hoods and
switchable extraction unit, LON connected, constant floor extraction unit and additional
laboratory exhaust air including recording of the fire dampers (BSK), with room operating
device for daytime/night-time switching
Switchable
canopy exhaust
Exhaust
Fume hood 1 Fume hood 2 Fume hood 3
LON-network, FTT-10A
Day
Roomcontrol
LabSystem components
No. Amount Type Description
1 3 FC500-V-L Fully variable fume hood controller, LON, FTT-10A
3 MD-200-P-MM-1 Maintenance-free measuring device DN200, PPs, socket/socket, servo motor 3 s
2 1 VAV-L-100-P Switchable volume flow controller, round, LON, FTT-10A, DN100, PPs
3 1 CAV-80-S Constant volume flow controller, round, DN80, sheet steel, DD finish
4 1 VAV-L-315-S Variable volume flow controller, room supply air, round, LON, FTT-10A, DN315,
sheet steel
5 1 VAV-L-200-P Variable volume flow controller, room exhaust air, round, LON, FTT-10A, DN200,
PPs
6 1 RBG-1T1L Room operating device with daytime/night-time button and daytime/night-time
operating mode display
7 3 BSK Fire damper (BSK) with status notification via contacts (not a SCHNEIDER pro-
duct)
This example shows a LON networked laboratory control The LON controllers (4) and (5) both have 2 digital inputs
system and is suitable for medium-sized to large labora- and outputs, making it possible to record the status no-
tories with additional room exhaust air (5). The additional tifications of the fire dampers (7) and to connect a room
room exhaust air (5) is always necessary when a specific operating device (6).
minimum level of room air exchange must be maintained,
which cannot be fully achieved by the extraction units alo- All digital inputs and outputs are available as standard va-
ne. riables (SNVT) and enable, for example, access via the
building services management (BSM).
4.9.2 Room air balancing Control and monitoring of the fume hoods as well as main-
tenance of the room pressure and the control diagram cor-
An independent balancing LON controller (4) is used for respond to the functional descriptions 4.5.1 and 4.7.1.
volume flow control of the room supply air. For volume flow
control of the room exhaust air, an independent LON con-
troller (5) is also used, which takes over the calculation of
the difference value for the room exhaust air.
4.10 Complete laboratory control, LON connected, with several variably operated fume
hood controllers and switchable bench extraction unit, LON connected, constant floor
extraction unit and additional laboratory exhaust air, taking into account the room
temperature and the redundant room pressure measurement including recording of the
fire dampers (BSK), with room operating device for daytime/night-time switching
Supply
Exhaust air
air
4
VAV-L
p
Room
9
M
exhaust air
1 1 1 CAV
2
M M M M M
FC500- FC500- FC500- VAV-L 3 VAV-L
p p
p LON p LON p LON
Switchable
canopy exhaust
Exhaust
Fume hood 1 Fume hood 2 Fume hood 3
LON-network, FTT-10A
7
Day p
Roomcontrol + - T
LabSystem components
No. Amount Type Description
1 3 FC500-V-L Fully variable fume hood controller, LON, FTT-10A
3 MD-200-P-MM-1 Maintenance-free measuring device DN200, PPs, socket/socket, servo motor 3 s
2 1 VAV-L-100-P Switchable volume flow controller, round, LON, FTT-10A, DN100, PPs
3 1 CAV-80-S Constant volume flow controller, round, DN80, sheet steel, DD finish
4 1 VAV-L-315-S Variable volume flow controller room supply air, round, LON, FTT-10A, DN315,
sheet steel
5 1 VAV-L-200-P Variable volume flow controller room exhaust air, round, LON, FTT-10A, DN200,
PPs
6 1 RDT±50Pa Room differential pressure sensor, ±50 Pa, 0...10V DC
7 1 RT-PT1000 Room temperature sensor, PT1000, active, 0...10V DC
8 1 RBG-1T1L Room operating device with daytime/night-time button and daytime/night-time
operating mode display
9 3 BSK Fire damper with status notification via contacts (not a SCHNEIDER product)
This example shows a complete LON networked labora- all volume flow controllers are connected end-to-end in the
tory control system at its maximum configuration and is LON network.
suitable for medium-sized to large laboratories with additi-
onal room exhaust air (5). The additional room exhaust air The peripheral devices, such as the RDT±50Pa room dif-
(5) is always necessary when a specific minimum level of ferential pressure sensor (6), the RT-PT1000 room tem-
room air exchange must be maintained, which cannot be perature sensor (7), the RBG-1T1L room operating device
fully achieved by the extraction units alone. (8) and the status notifications of the fire dampers (9) are
connected directly to the individual inputs and outputs of
The control and monitoring of the fume hoods has not the LON room supply air (4) and room exhaust air (5) con-
changed and has already been described in detail in the trollers.
previous chapters.
All digital inputs and outputs are available as standard va-
This example is functionally the same as example 4.7. The riables (SNVT) and enable, for example, access via the
LCO500 laboratory controller is not necessary here, since building services management (BSM).
All exhaust air actual values of the fume hoods or other 4.10.6 Room operating device for daytime/
extraction units as well as their status and malfunction no- night-time switching and activation of the
tifications are available as standard variable types (SNVT) room differential pressure sensor
and can be included in the overall decentralised functio-
nality. The fume hoods or other LON connected extraction The RBG-1T1L room operating device (8) is connected
units can also be switched to reduced operation (night- to the digital inputs and outputs and the RDT±50Pa red-
time reduction or work-free time) via the LON network. undant room differential pressure sensor (6) is connected
to the analogue output of the LON controller (4) and also
Connection to the BSM is possible without restrictions, provides the room differential pressure and daytime/night-
which enables remote maintenance and diagnostics via time switching as SNVTs on the LON network.
the BSM or the Internet.
Reduced operation (night-time operation) can be switched
The system presented here enables cost-efficient project on and off locally, i.e. within the laboratory, with the Day/
implementation through easy connection of peripheral night button. Of course, these local functions can be enab-
components to the LON controller. led or disabled via the BSM. It is even possible to enable
the functions within a specific time period (e.g. 5 p.m. to
7 a.m.). Similarly, night-time operation that has been swit-
4.10.3 Router for max. 64 nodes ched on by the BSM can be switched off with the room
operating device if, for example, experiments also take
From a maximum of 64 nodes (subscribers) a router is re- place at night in this laboratory. An operating mode display
quired. In practice, each laboratory is physically separated (LED) shows the user the current laboratory status. The
by a router every 20-30 nodes in order to limit data traffic BSM is informed of all manual interventions and can thus
on the LON network and to avoid unnecessary increases visualise the current laboratory status.
in reaction time of the entire system,
The number of nodes can be increased at any time th- 4.10.7 Room air balancing
rough the use of additional routers and/or repeaters.
Control and monitoring of the fume hoods as well as main-
tenance of the room pressure correspond to the functio-
4.10.4 Free inputs and outputs of the LON nal descriptions 4.5.1 and 4.7.1. The LON controller (4)
controller balances the exhaust air actual values of the fume hood
controllers and the switchable bench extraction unit and
The LON controllers (4) and (5) both have 2 digital inputs, automatically regulates the room supply air. Room supply
2 digital outputs, 2 analogue inputs (0...10 VDC) and 1 air is compensated based on the room exhaust air. Nega-
analogue output (0...10 VDC). tive room pressure is achieved by supplying only approx.
90% (programmable) of the entire exhaust air as supply
All inputs and outputs are available via the LON network air to the laboratory.
as standard variable types (SNVT) and can easily be in-
cluded in the overall decentralised functionality. The LON controller (5) calculates the difference for the ad-
ditional room exhaust air and regulates the required mini-
The contacts of the fire dampers (BSK) installed in the la- mum exhaust air volume flow.
boratory are also available via the LON network, which
makes it possible to visualise the status of the BSK on the
BSM. At the same time, it is also possible to specify via Control diagram
the binding that the FC500-V-LON fume hood controllers
in the corresponding laboratory also receive the status in- The control diagram has not changed and is the same as
formation from the fire dampers and automatically close the graphic displayed in the functional description 4.7 on
the exhaust air dampers. This example demonstrates how page 17.
easily extended functionality can be implemented via the
LON network.
The diagram shows an overview of the products that are Technical data sheets, further information and tender
available from SCHNEIDER in the product group Room specifications for the LCO500, GC10, RAM500, VAV and
ventilation controllers. CAV products are available for download on the Internet
at www.schneider-elektronik.de.
See Chapter 1, Section 6.1 for the full LabSystem product
overview.
High-speed room VAV Volume flow controller for laboratory supply and laboratory exhaust air, 5.0
supply/exhaust air analogue input 0(2)...10V DC for setpoint, optional field bus module,
controller control speed < 3 s
Mechanical auto- CAV Volume flow controller for floor extraction units and safety cabinets, 5.0
matic volume flow mechanical, automatic, without auxiliary power
controller