Professional Documents
Culture Documents
6.0
Chapter 6.0
LabSystem
Building ventilation systems and
building services management
Table of contents
Section Title Page
1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
6.2 Ventilation system with central supply and exhaust air via individual fans . 8
Chapter 6.0
Table of contents
Section Title Page
8.1 Variable volume flow control . . . . . . . . . . . . . . . . . . . . . . . . . 11
8.1.1 Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
9.1 Ventilation system with speed controlled supply and exhaust air . . . . . . 13
9.2 Ventilation system with speed controlled supply and exhaust air
with bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
9.2.2 Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
11.1 Additional savings potential with a DPO duct pressure optimiser in the
LON network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
11.1.1 Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1.1 Introduction
In addition to the correct dimensioning of the air ducts, this The software runs on WINDOWS® and every SCHNEI-
also includes the correct selection of the supply air and DER product is displayed graphically on the monitor. The
exhaust air fans. actual values, such as the sash position, exhaust air volu-
me flow, face velocity, operating status, etc., are display-
ed.
2.1 Building services management (BSM)
Remote maintenance via the BSM enables cost-efficient,
Building services management forms a considerable part regular maintenance and test functions, which conside-
of building and facility management. Companies such as rably increases the safety of the entire system.
ABB, Siemens/Landis Staefa, Honeywell, Johnson Con-
trols, Sauter, etc. have a leading market position in this In addition, recording of consumption and energy as well
area. as simple accounting (e.g. in relation to the individual labo-
ratories) is possible via the BSM.
With the PAD-3000 management software, SCHNEIDER
offers a product that has been specially developed for con-
trol, regulation and remote maintenance of fume hoods
and fume hood controllers.
2.1.1 PAD-3000
2.2 Duct pressure optimiser with fan load that is least well ventilated.
FI actuation
With weakest point measurement, the duct pressure at
The DPO-L duct pressure optimiser is used primarily in lar- the measuring point is constantly regulated to approx. 130
ge LON networked projects and takes over the optimised Pa (all values stated are only sample values), while at the
actuation of the fan frequency inverter. Via the LON net- measuring point close to the fan the duct pressure is regu-
work the damper positions of all controllers (fume hood, lated to approx. 450 Pa.
room exhaust air, etc.) are automatically checked at regu-
lar intervals and the frequency inverter (FI) for the exhaust In buildings that mainly have laboratories and rooms in a
air fan is regulated downwards until the "weakest" damper state of negative pressure, the exhaust air pressure value
is still at 80° (90° = damper fully open, 0° = damper fully that is to be regulated is always approx. 10 % higher than
shut) and thus is still in the control range. the supply air pressure value that is to be regulated.
The same approach is also valid for the supply air and for
actuation of the supply air fan frequency inverter.
2.3 Duct pressure controller with 2.4 Constant duct pressure controller
fan FI actuation
The CDP constant duct pressure controller regulates a
The DPC duct pressure controller automatically regulates branch duct to a constant, programmable duct pressure
the duct pressure to a constant value in relation to a pre- (e.g. 130 Pa). This means that all consumer loads con-
defined measuring point (e.g. at the weakest point or close nected to this branch duct have the same pressure con-
to the fan). ditions.
The disadvantage of weakest point measurement is the In large buildings or in inappropriately constructed ventila-
higher installation effort required, because in this case a tion networks, it is very important to install constant duct
measurement cable must be laid from the consumer load pressure controllers in appropriate places. For example,
that is least well ventilated to the DPC, which is usually the exhaust air and supply air for each floor should be se-
mounted directly on the ventilator FI. parated from the main ventilation network with constant
duct pressure controllers.
The advantage of weakest point measurement is that
measurement can take place directly on the consumer
This results in considerable advantages with regard to lo- 3.2 Remote maintenance and safety
wer sound levels.
A special feature is the remote maintenance of fume hoods
in networked systems. With the PAD-3000 management
software, the safety functions of every fume hood can be
checked at regular intervals and remote maintenance with
the appropriate documentation (maintenance plan) can be
efficiently and cost-effectively carried out.
In this chapter various examples for building ventilation This means that when the temperature in the fume hood
controllers (supply air and exhaust air) are presented. is increased (within specific limits), the exhaust air volume
flow can also be increased in order to disperse the thermal
loads.
Recognition of the temperature increase via the air flow SCHNEIDER supports the BACnet ® technology and has
sensor is not recommended, as this requires very precise extensive know-how in this area. BACnet® technology is
temperature balancing. becoming increasingly established in building automation
as a manufacturer-independent and licence-free technolo-
Without this necessary temperature compensation the gy. However, the costs for connecting BACnet® at field
airflow sensor would not be suitable for measuring repro- bus level are currently still relatively high.
ducible face velocity values at different laboratory tempe-
ratures (e.g. 19° C to 25° C). In order to technically ensu-
re safe and reproducible fire recognition, we recommend Management level
using a PT 1000 thermoelement.
A similar scenario can also be implemented with the con- Field level
nectable smoke detector.
5.1.1 LON®
5.1.4 INDUSTRIAL ETHERNET®
SCHNEIDER supports the LON® technology and has
extensive know-how in this area. The LON technology is INDUSTRIAL ETHERNET builds on ETHERNET and is
increasingly becoming well established in building auto- increasingly becoming established at field bus level. Ho-
mation. wever, the costs for the field bus subscribers (nodes) are
currently still very high.
LON is a decentral network and thus has a very high level
of safety. Every network or protocol has been developed for a spe-
cific area of application and thus has its own specific ad-
vantages for that area of application. Unfortunately, even
in the near future there will not be only one standardised
network for all areas of application and thus all networks
will continue to have one thing in common: they must un-
derstand one another.
5.1.2 BACnet®
Figure 6.8 shows a ventilation system with central supp- In order to keep flow noise and sound emission to a mi-
ly and exhaust air. This version includes components for nimum, the dimensions of the ventilation ducts must be
heat recovery (integrated circulation system), filters, air selected so that a face velocity of 7 m/sec is not exceeded.
heaters, air coolers and fans that are speed-controlled by Otherwise the required sound levels of max. 52dB(A) in
a frequency inverter. laboratories can only be achieved with very considerable
effort (e.g. sound absorbers).
Heat Filter
exchanger Exhaust fan
FI
Exhaust air
FI
Lab 1
CAV CAV
Supply air
Air volume Air volume
Silencer
control control
Filter Heat
Air heating Air cooling Supply fan Silencer
exchanger
Lab 2
CAV CAV
Lab 3
CAV CAV
Lab 4
CAV CAV
6.1.4 Temperature control, heating Fume hoods that are regulated variably and in accordance
and cooling with the demand require variable volume flow control of
the laboratory supply air and, if necessary, variably regu-
The supply air temperature is regulated to a constant va- lated additional laboratory exhaust air in order to maintain
lue of 19° C and thus is 3K below the setpoint temperature the required room air exchange levels.
of the laboratories (tRA = 22° C). The heating surfaces then
regulate the room temperature to the setpoint. Internal and For unregulated or constantly regulated fume hoods, con-
external thermal loads can thus be taken into account. stant volume flow control of the laboratory supply air and
the laboratory exhaust air is sufficient.
As the outdoor temperature increases (transitional periods
and summer time), first heating of the air by the heater and
then heat recovery is reduced and switched off. The coo- 6.2 Ventilation system with central supply air
ling circuit is then activated so that the room temperature and exhaust air via individual fans
can be regulated to the setpoint for as long as possible.
Figure 6.9 shows a ventilation system with central supply
and exhaust air via individual fans. This version includes
6.1.5 Volume flow control filters, air heaters and coolers and the corresponding fans.
With this version, heat recovery cannot be implemented or
Supply air volume flow is fed into the laboratories, de- can only be implemented with a good deal of effort. The
pending on the laboratory exhaust air either variably or fans work at a one-level or two-level constant speed.
constantly with a volume flow controller. It is advisable to
activate a sound absorber after the supply air volume flow
controllers in order to adhere to the sound emission levels Figure 6.9: Ventilation system with central supply and
required in laboratories of max. 52 dB(A). exhaust air via individual fans
Exhaust air
Exhaust fans
Lab 1
CAV
Supply air
Air volume
Silencer
control
Lab 2
CAV
Air volume
Silencer
control
Lab 3
CAV
Air volume
Silencer
control
Lab 4
CAV
Air volume
Silencer
control
In the following examples various building ventilation con- Figure 6.10 shows constant volume flow control of the la-
cepts are presented. The individual requirements of the boratory supply air and the laboratory exhaust air. Energy
laboratory are taken into account. The supply air is treated savings are not achieved using this control type. The fume
centrally and fed into the laboratories, while the exhaust hoods are not controlled and only have a fume hood mo-
air, depending on the structural conditions, is extracted via nitor (FM100), as stipulated by DIN EN 14175, which mo-
a central exhaust air fan or via individual fans. nitors whether the ventilation functions of the fume hoods
are working correctly.
Exhaust air
Total exhaust
air = 6000m3/h
Exhaust fan
Silencer CAV
VConst. = 600m3/h VConst. = 600m3/h VConst. = 600m3/h VConst. = 600m3/h VConst. = 600m3/h VConst. = 600m3/h CAV
Fume hood 1 Fume hood 2 Fume hood 3 Fume hood 4 Fume hood 5 Fume hood 6
Lab 1
Lab 2
Silencer CAV
Legend:
Total supply air
= 5400m3/h
Manual damper
Supply air
FM100 Fume hood monitor
Air conditioning and fan
The exhaust air volume flow of the fume hoods is measu- 7.1.1 Conclusion
red via the manual dampers and set in accordance with
the type of fume hood. In the example shown, all fume The simplicity of the system design must be weighed up
hoods are restricted to 600m³/h. The constant volume flow against the fact that air requirements may not be ideally
controller for the laboratory supply air and the laboratory accommodated.
exhaust air guarantees the defined room air exchange and
the required negative pressure in the laboratory. The total investment costs for the entire system are only
slightly less than for a fully variably controlled system, but
Table 6.1 shows a summary of the entire building supply the energy costs (for heating and cooling of the supply and
air and exhaust air with the room balances. exhaust air) are very high.
Exhaust air
Total exhaust air
VMAX = 6000m3/h
VMIN = 2000m3/h
Exhaust fan
VMAX = 600m3/h VMAX = 600m3/h VMAX = 600m3/h VMAX = 600m3/h VMAX = 600m3/h VMAX = 600m3/h
VMIN = 200m3/h VMIN = 200m3/h VMIN = 200m3/h VMIN = 200m3/h VMIN = 200m3/h VMIN = 200m3/h
M M M M M M
FC500- FC500- FC500- FC500- FC500- FC500-
p p p p p p
V-L V-L V-L V-L V-L V-L
Fume hood 1 Fume hood 2 Fume hood 3 Fume hood 4 Fume hood 5 Fume hood 6
LON-network, FTT-10A
Room exhaust air
Lab 1 VMAX = 3600m3/h
VMIN = 1200m3/h
Lab 2
Variabler Air Volume
VAV, LON
Room supply air
VMAX = 2160m3/h Silencer VAV-L-315-S
VMIN = 720m3/h
FC500-V-L
Variable fume hood VMIN = 1800m3/h
The exhaust air actual values are available as SNVTs 8.1.1 Conclusion
(Standard Network Variable Type) on the LON network
and are summated in the VAV-L-315-S supply air control- Due to the very high savings potential with regard to the
ler and automatically regulated by this controller. energy costs, this system concept is amortised within a
very short period of time (see Chapter 13.0, economic ef-
The supply air volume flow is reduced by 10% in relation ficiency calculation).
to the exhaust air volume flow. This ensures that negative
pressure is maintained in the laboratory while at the same Compared with example 7.1 only 30% of the required ex-
time preventing contaminated air from flowing into adja- haust air volume flow is necessary when the sashes are
cent rooms. shut. This value is of course theoretical, as it cannot be
assumed that all sashes are always shut.
Table 6.2 shows a summary of the entire building supply
and exhaust air with the room balances. A diversity factor of 50 to 70% can be assumed as a practi-
cal value, whereby the entire central ventilation system for
supply air and exhaust air can also be on a smaller sca-
Table 6.2: le. This advantage considerably reduces the investment
costs for construction.
VMIN in m³/h VMAX in m³/h
Fume hood 1 200 600
Fume hood 2 200 600
Fume hood 3 200 600
Fume hood 4 200 600
Fume hood 5 200 600
Fume hood 6 200 600
Exhaust air 1200 3600
laboratory 1
Supply air 1080 3240
laboratory 1
9.1 Ventilation system with speed 9.2 Ventilation system with speed controlled
controlled central supply air and central supply air and exhaust air
exhaust air with bypass
Figure 6.12 shows a ventilation system with speed cont- The ventilation system shown in Figure 6.13 is very similar
rolled supply and exhaust air. The flow rates of the supply to the design described in Figure 6.12. As in the example
and exhaust air fan are regulated so that the control va- already described, the supply air is regulated by the DPC
riable pressure (∆p) is centrally maintained at a constant duct pressure controller at a constant pressure level via
level. the frequency inverter, while the exhaust air fan is not re-
gulated and runs at a fixed speed. This guarantees that the
The SCHNEIDER DPC duct pressure controller is equip- exit speed of the discharged air, which may be well be over
ped with a PI controller and static differential pressure the required 7m/s for all operating states, remains con-
sensor (∆p) and directly actuates the frequency inverter stant. This safely prevents the contaminated discharge air
of the supply air fan with 0(2)...10V DC. The integrated from being partially drawn in again (e.g. if the inlet vents of
PI controller regulates the constant positive pressure (e.g. the outdoor air are inappropriately located or in inversion
400 Pa) via the supply air fan, the speed of which cont- weather conditions).
rolled by means of the frequency inverter.
Maintenance of constant pressure on the
suction side is achieved by the DPC duct
Figure 6.12: Ventilation system with speed controlled pressure controller actuating a damper with
central supply air and exhaust air a fast running servo motor, which works like
Heat a bypass.
exchanger DPC Filter
FI
p
If only a low exhaust air volume flow is re-
Exhaust air
quired by the connected fume hoods, be-
Exhaust fan cause the sashes are mostly closed, the
bypass is opened accordingly. The exhaust
air fan conveys a constant exhaust air volu-
FI
DPC me and maintains the differential value via
p
the bypass damper as outdoor air.
Supply air
If the maximum exhaust air is required by
Filter Heat
Air heating Air cooling Supply fan Silencer
the fume hoods, the bypass is shut comple-
exchanger
tely and thus ceases to have an effect. The
exhaust air fan now only conveys the con-
taminated exhaust air of the fume hoods.
The exhaust air controller works in the same way as the This version of the exhaust air controller is preferred in
supply air controller. The only difference is in the mainte- Anglo-Saxon countries.
nance of constant pressure on the pressure side (supp-
ly air) and the suction side (exhaust air). The DPC duct
pressure controller regulates the constant negative pres- Figure 6.13: Ventilation system with speed controlled
sure (e.g. 450 pascal) via the exhaust air fan, the speed of central supply and exhaust air with bypass
which is controlled by means of the frequency inverter.
Damper with high
Outside air
The pressure control takes into account the pressure drop speed actuator
(Bypass)
in the system components and in the pipes of the branch
ducts.
DPC Filter
Exhaust fan
p
This control type is fully automatic and regulates
Exhaust air
changing load conditions (variable exhaust air vo-
lume flows) automatically. A building services ma-
nagement (BSM) is not required for central control
of the supply and exhaust air.
FU DPC
The fans are energy-optimised. However, particu- p
larly in the case of low exhaust air volume flows, it Supply air
must be ensured that the exit speed of the dischar-
ged air is not less than 7m/s (see DIN 1946, Part Filter Air heating Air cooling Supply fan Silencer
7). Only in this case is a sufficient emission height
of the discharged air guaranteed, which effectively
prevents partial intake of discharged air.
9.2.2 Conclusion
Figure 6.14 shows variable volume flow control of 4 labo- Sections 9.1 and 9.2 describe in detail the functionality of
ratories with a central exhaust air fan and a central supply central, speed-controlled supply and exhaust air. These
air fan. Both fans are actuated by the SCHNEIDER DPC control circuits are fully automatic and regulate the re-
duct pressure controller and the frequency inverter in such quired total supply air and total exhaust air volume flows
a way that constant negative pressure (exhaust air) and automatically. Changing load conditions (variable exhaust
constant positive pressure (supply air) is regulated. air volume flows) are automatically recognised and regu-
lated. A building services management (BSM) is not re-
quired for central supply and exhaust air control.
Bild 6.14: Variable volume flow control of 4 Each laboratory also functions automatically and the VAV-
laboratories in the LON network L-250-S and VAV-L-315-S supply air volume flow control-
lers with LON interface summate the required laboratory
supply air from the individual laboratory exhaust air values,
Heat
Exchanger DPC Filter
FI
p
- +
Exhaust air
Exhaust fan
Filter Heat
Air heating Air cooling Supply fan Silencer
Exchanger
LON-network LON-network
LON-VAV LON-VAV
VAV-L-250-S VAV-L-315-S
M M M M M
FC500- FC500- FC500- FC500- FC500-
p p p p p
V-L V-L V-L V-L V-L
Lab 1 Lab 2
Router Router
Fume hood 1 Fume hood 2 Fume hood 1 Fume hood 2 Fume hood 3
LON-network
Router Router
LON-network LON-network
LON-VAV LON-VAV
VAV-L-250-S VAV-L-315-S
M M M M M
FC500- FC500- FC500- FC500- FC500-
p p p p p
V-L V-L V-L V-L V-L
Lab 3 Lab 4
Fume hood 1 Fume hood 2 Fume hood 1 Fume hood 2 Fume hood 3
To simplify matters, additional room exhaust air via a LON Figure 6.15: Control room
controller has not been included in this example. The ver-
sion described in detail in section 8.1 can also easily be Remote maintenance and diagnostics are also possible
integrated here. over the intranet and Internet and thus guarantee a high
level of durability and operating safety.
In addition to building and facility management, remote Depending on user behaviour, the entire system can be
maintenance and diagnostics are also possible. Thus, for amortised very quickly (approx. 1 to 2 years) due to the
example, the dampers of the exhaust air and supply air energy cost savings and if the diversity factor approach is
volume flow controllers can be opened or shut in order to used, the construction investment costs can be drastically
test the entire system and the sensors. reduced.
11.1 Additional savings potential with the the exhaust air fan is regulated downwards until the "wea-
DPO duct pressure optimiser in the LON kest" damper is still at 80° (90° = damper fully open, 0° =
network damper fully shut) and thus is still in the control range.
LON-network
DPO-L
Heat
exchanger Filter
FI
Exhaust air
Exhaust fan
LON-network
DPO-L
FU
Supply air
Filter Heat
Air heating Air cooling Supply fan Silencer
exchanger
LON-network LON-network
LON-VAV LON-VAV
VAV-L-250-S VAV-L-315-S
M M M M M
FC500- FC500- FC500- FC500- FC500-
p p p p p
V-L V-L V-L V-L V-L
Lab 1 Lab 2
Router Router
Fume hood 1 Fume hood 2 Fume hood 1 Fume hood 2 Fume hood 3
LON-network
Router Router
LON-network LON-network
LON-VAV LON-VAV
VAV-L-250-S VAV-L-315-S
M M M M M
FC500- FC500- FC500- FC500- FC500-
p p p p p
V-L V-L V-L V-L V-L
Lab 3 Lab 4
Fume hood 1 Fume hood 2 Fume hood 1 Fume hood 2 Fume hood 3
The diagram shows an overview of the products that are Technical data sheets, further information and tender
available from SCHNEIDER in the product group Duct specifications for the duct pressure controllers and duct
pressure controllers and Duct pressure optimisers. pressure optimisers CDP, DPC and DPO are available for
download on the Internet at www.schneider-elektronik.de.
See Chapter 1, Section 6.1 for the full LabSystem product
overview. www.schneider-elektronik.de.
Duct pressure DPO Energy-optimised damper operating point through intelligent damper 6.0
optimiser management with actuation for frequency inverters of the exhaust or
supply air fan.