MULTILIN GIII-28-11-2014.489
F:\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3210798
DESCRIPTION: (NONE)
TEXT COLOR
SR489 SETUP
PREFERENCES
Default Message Cycle Time 2.0 s
Default Message Timeout 300 s
Parameter Averages Calc. Period 15 min
Temperature Display Units Celsius
Waveform Trigger Position 25 %
Waveform Memory Buffer 8 x 28 Cycles
MESSAGE SCRATCHPAD
First Scratchpad Message Text 1
Second Scratchpad Message Text 2
Third Scratchpad Message Text 3
Fourth Scratchpad Message Text 4
Fifth Scratchpad Message Text 5
COMMUNICATION
Ethernet Subnet Mask 255.255.255. 0
Slave Address 254
Computer RS485 Baud Rate 9600 baud
Auxiliary RS485 Baud Rate 9600 baud
SYSTEM SETUP
CURRENT SENSING
Phase CT Primary 6000 A
Ground CT 5 A Secondary
Ground CT Ratio 50 :5
VOLTAGE SENSING
VT Connection Type Wye
Transformer Ratio 3.80 :1
Neutral Voltage Connection No
GEN. PARAMETERS
Generator Rated MVA 3.750 MVA
Generator Rated Power Factor 0.80
Generator Voltage Phase-Phase 380 V
Generator Nominal Frequency 50 Hz
Generator Phase Sequence ABC
SERIAL START-STOP
Serial Start/Stop Initiation Off
DIGITAL INPUTS
BREAKER STATUS
Breaker Status Breaker Auxiliary a
GENERAL PURPOSE
GENERAL A
Assign Digital Input (A) Input 1
Input Name (A) S/C DIODE
Asserted Digital Input State (A) Closed
Block Input From Online (A) 0s
General Input A Control Off
Pulsed Control Relay Dwell Time (A) 0.0 s
Control Relay A No Relays
General Input A Control Events Off
General Input A Alarm Latched
Alarm Relays A Relays 2-3-5
General Input A Alarm Delay 0.1 s
General Input A Alarm Events On
General Input A Trip Latched
Trip Relays A Relay 1
General Input A Trip Delay 0.1 s
GENERAL B
Assign Digital Input (B) Input 2
Input Name (B) O/C DIODE
Asserted Digital Input State (B) Closed
Block Input From Online (B) 0s
General Input B Control Off
Pulsed Control Relay Dwell Time (B) 0.0 s
Control Relay B No Relays
General Input B Control Events Off
General Input B Alarm Latched
Alarm Relays B Relay 5
General Input B Alarm Delay 0.1 s
Fri Nov 28 2014 10:59:31 Settings (Enabled Features) PAGE 2
MULTILIN GIII-28-11-2014.489
F:\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3210798
DESCRIPTION: (NONE)
TEXT COLOR
GENERAL C
Assign Digital Input (C) Input 3
Input Name (C) P/S HEALTHY
Asserted Digital Input State (C) Closed
Block Input From Online (C) 0s
General Input C Control Off
Pulsed Control Relay Dwell Time (C) 0.0 s
Control Relay C No Relays
General Input C Control Events Off
General Input C Alarm Latched
Alarm Relays C Relays 2-3-5
General Input C Alarm Delay 0.1 s
General Input C Alarm Events On
General Input C Trip Latched
Trip Relays C Relay 1
General Input C Trip Delay 0.1 s
GENERAL D
Assign Digital Input (D) Input 4
Input Name (D) O/V ALARM
Asserted Digital Input State (D) Closed
Block Input From Online (D) 0s
General Input D Control Off
Pulsed Control Relay Dwell Time (D) 0.0 s
Control Relay D No Relays
General Input D Control Events Off
General Input D Alarm Latched
Alarm Relays D Relays 3-5
General Input D Alarm Delay 0.1 s
General Input D Alarm Events On
General Input D Trip Latched
Trip Relays D Relay 1
General Input D Trip Delay 0.1 s
GENERAL E
Assign Digital Input (E) Input 5
Input Name (E) AVR FAILURE
Asserted Digital Input State (E) Closed
Block Input From Online (E) 0s
General Input E Control Off
Pulsed Control Relay Dwell Time (E) 0.0 s
Control Relay E No Relays
General Input E Control Events Off
General Input E Alarm Latched
Alarm Relays E Relays 2-3-5
General Input E Alarm Delay 0.1 s
General Input E Alarm Events On
General Input E Trip Latched
Trip Relays E Relay 1
General Input E Trip Delay 0.1 s
GENERAL F
Assign Digital Input (F) Input 6
Input Name (F) SPARE
Asserted Digital Input State (F) Closed
Block Input From Online (F) 0s
General Input F Control Off
Pulsed Control Relay Dwell Time (F) 0.0 s
Control Relay F No Relays
General Input F Control Events Off
General Input F Alarm Off
Alarm Relays F Relay 5
General Input F Alarm Delay 5.0 s
General Input F Alarm Events Off
General Input F Trip Off
Trip Relays F Relay 1
General Input F Trip Delay 5.0 s
GENERAL G
Assign Digital Input (G) Input 7
Input Name (G) FAIL TO SYNC
Fri Nov 28 2014 10:59:31 Settings (Enabled Features) PAGE 3
MULTILIN GIII-28-11-2014.489
F:\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3210798
DESCRIPTION: (NONE)
TEXT COLOR
DUAL SETPOINTS
Active Setpoint Group(Dual Setpoints) Group 1
Edit Setpoint Group(Dual Setpoints) Group 1
OUTPUT RELAYS
1 TRIP
R1 Trip All Resets
2 AUXILIARY
R2 Auxiliary All Resets
3 AUXILIARY
R3 Auxiliary All Resets
4 AUXILIARY
R4 Auxiliary All Resets
5 ALARM
R5 Alarm All Resets
6 SERVICE
R6 Service All Resets
MONITORING
TRIP COUNTER
Trip Counter Alarm Off
BREAKER FAILURE
Breaker Failure Alarm Off
CURRENT DEMAND
Current Demand Period 15 min
Current Demand Alarm Off
MW DEMAND
MW Demand Period 15 min
MW Demand Alarm Off
MVAR DEMAND
Mvar Demand Period 15 min
Mvar Demand Alarm Off
MVA DEMAND
MVA Demand Period 15 min
MVA Demand Alarm Off
PULSE OUTPUT
Positive kWh Pulse Output Relays No Relays
Positive kWh Pulse Output Interval 10 kwh
Positive kvarh Pulse Output Relays No Relays
Positive kvarh Pulse Output Interval 10 kvarh
Negative kvarh Pulse Output Relays No Relays
Negative kvarh Pulse Output Interval 10 kvarh
Pulse Width 200 ms
VT FUSE FAILURE
VT Fuse Failure Alarm Latched
VT Fuse Failure Alarm Relays Relay 5
VT Fuse Failure Alarm Events On
Fri Nov 28 2014 10:59:31 Settings (Enabled Features) PAGE 4
MULTILIN GIII-28-11-2014.489
F:\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3210798
DESCRIPTION: (NONE)
TEXT COLOR
PROTECTION
CURRENT ELEMENTS[SETPOINT GROUP 1]
OVERCURRENT ALARM[SETPOINT GROUP 1]
Overcurrent Alarm Off
OVERVOLTAGE[SETPOINT GROUP 1]
Fri Nov 28 2014 10:59:31 Settings (Enabled Features) PAGE 5
MULTILIN GIII-28-11-2014.489
F:\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3210798
DESCRIPTION: (NONE)
TEXT COLOR
VOLTS/HERTZ[SETPOINT GROUP 1]
Volts/Hertz Alarm Latched
Volts/Hertz Alarm Relay Relay 5
Volts/Hertz Alarm Pickup 1.17 X Nominal
Volts/Hertz Alarm Delay 10.0 s
Volts/Hertz Alarm Events Off
Volts/Hertz Trip Latched
Volts/Hertz Trip Relay Relays 1-3
Volts/Hertz Trip Pickup 1.17 X Nominal
Volts/Hertz Trip Delay 30.0 s
Volts/Hertz Trip Reset Rate 1.4
Volts/Hertz Trip Element Definite Time
UNDERFREQUENCY[SETPOINT GROUP 1]
Block Underfrequency from Online 1s
Voltage Level Cutoff 0.50 x Rated
Underfrequency Alarm Latched
Underfrequency Alarm Relay Relay 5
Underfrequency Alarm Level 47.50 Hz
Underfrequency Alarm Delay 5.0 s
Underfrequency Alarm Events Off
Underfrequency Trip Latched
Underfrequency Trip Relay Relays 1-3
Underfrequency Trip Level 1 45.00 Hz
Underfrequency Trip Delay 1 2.0 s
Underfrequency Trip Level 2 45.00 Hz
Underfrequency Trip Delay 2 2.0 s
OVERFREQUENCY[SETPOINT GROUP 1]
Block Overfrequency from Online 1s
Voltage Level Cutoff (overfrequency) 0.50 x Rated
Overfrequency Alarm Latched
Overfrequency Alarm Relay Relay 5
Overfrequency Alarm Level 52.50 Hz
Overfrequency Alarm Delay 5.0 s
Overfrequency Alarm Events Off
Overfrequency Trip Latched
Overfrequency Trip Relay Relays 1-3
Overfrequency Trip Level 1 55.00 Hz
Overfrequency Trip Delay1 2.0 s
Overfrequency Trip Level2 55.00 Hz
Overfrequency Trip Delay2 2.0 s
MULTILIN GIII-28-11-2014.489
F:\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3210798
DESCRIPTION: (NONE)
TEXT COLOR
DISTANCE[SETPOINT GROUP 1]
Step Up Transformer Setup Delta/Wye
Fuse Failure Supervision Off
Zone 1 Trip Off
Zone 2 Trip Off
MULTILIN GIII-28-11-2014.489
F:\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3210798
DESCRIPTION: (NONE)
TEXT COLOR
RTD-ALARMS[SETPOINT GROUP 1]
Open RTD Sensor Alarm Off
RTD Short/Low Temp Alarm Off
MULTILIN GIII-28-11-2014.489
F:\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3210798
DESCRIPTION: (NONE)
TEXT COLOR
OVERVOLTAGE[SETPOINT GROUP 2]
Overvoltage Alarm Off
Overvoltage Trip Off
VOLTS/HERTZ[SETPOINT GROUP 2]
Volts/Hertz Alarm Off
Volts/Hertz Trip Off
UNDERFREQUENCY[SETPOINT GROUP 2]
Block Underfrequency from Online 1s
Voltage Level Cutoff 0.50 x Rated
Underfrequency Alarm Off
Underfrequency Trip Off
OVERFREQUENCY[SETPOINT GROUP 2]
Block Overfrequency from Online 1s
Voltage Level Cutoff (overfrequency) 0.50 x Rated
Overfrequency Alarm Off
Overfrequency Trip Off
DISTANCE[SETPOINT GROUP 2]
Fuse Failure Supervision Off
Zone 1 Trip Off
Zone 2 Trip Off
MULTILIN GIII-28-11-2014.489
F:\
DEVICE DEFINITION
ORDER CODE: 489-P5-LO-A20-E
VERSION: 4.0X
SERIAL NUMBER: B3210798
DESCRIPTION: (NONE)
TEXT COLOR
RTD-ALARMS[SETPOINT GROUP 2]
Open RTD Sensor Alarm Off
RTD Short/Low Temp Alarm Off