You are on page 1of 1

What is the answer for below question most the them are saying it is none of the above since

only
calibrated equipment is used for testing kindly advise

Equipment used for testing purpose

a ) New , b) listed, , c) None of the above , d)Both of the above

NFPA – 20
14.2.6* Field Acceptance Test Procedures.
14.2.6.1* Test Equipment.
14.2.6.1.1 Calibrated test equipment shall be provided to
determine net pump pressures, rate of flow through the pump,
volts and amperes, and speed.
14.2.6.1.2 Calibrated test gauges, transducers, and other devices
used for measurements required in 14.2.6.1.1 during the
test shall be used and shall bear a label with the latest date of
calibration.

NFPA – 25
The test equipment should be of high quality and accuracy.
All equipment should have been calibrated within the last
12 months by an approved calibration facility. Where possible,
the calibration facility should provide documentation indicating
the instrument reading against the calibrated reading. Instruments
that pass the calibration test should be labeled by
the calibration facility with the name of the facility and the
date of the test.

NFPA – 20
4.21.2 Meters and Testing Devices.
4.21.2.1* Metering devices or fixed nozzles for pump testing
shall be listed.
4.21.2.2 Metering devices or fixed nozzles shall be capable of
water flow of not less than 175 percent of rated pump capacity

NFPA – 20
Listed. Equipment, materials, or services included in a
list published by an organization that is acceptable to the
authority having jurisdiction and concerned with evaluation of
products or services, that maintains periodic inspection of
production of listed equipment or materials or periodic evaluation
of services, and whose listing states that either the equipment,
material, or service meets appropriate designated
standards or has been tested and found suitable for a specified
purpose.

NFPA – 2001
7.7* Approval of Installations.
7.7.1 General. The completed system shall be reviewed and
tested by qualified personnel to meet the approval of the authority
having jurisdiction. Only listed equipment and devices
shall be used in the systems. To determine that the system has
been properly installed and will function as specified, the following
tests shall be performed.