You are on page 1of 2

SAUDI ARAMCO ID/PIEU-31-Mar-2019 - Rev. 2019.03.00 (Standards Cutoff - Mar 31,2019) Rev.2019.03.

00 31-Mar-19

SAUDI ARAMCO TEST REPORT SATR NUMBER DATE APPROVED QR NUMBER

Fire Alarm System - Water Flow Switch and Water Valve


SATR-B-6104 10-Jun-19 INST
Position Switch - Pre-Commissioning Test
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
TEST PROCEDURE ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

A Procedure for Commissioning of Different Types of Switches


Documented test procedures shall be submitted to Saudi Aramco for 34-SAMSS-820
A1
approval not less than thirty (30) days before commencement of test. Sec.8

Review Factory Acceptance Test (FAT) documents detailing the set-up 34-SAMSS-820
A2
and procedures for the Functional Test to be provided. Sec.8

Before any testing is performed, verify that the supervisory Initiating


NFPA 72
devices, supervisory are installed per NFPA 72 guidelines and in
A3 Table 14.4.3.2
accordance with the manufacturer’s installation instructions.
Sec.18.
[System Sensor Duct Smoke Technical Bulletin]

The CONTRACTOR shall identify, maintain, control, adjust and calibrate


Schedule Q
A4 all tools, gauges, instruments and other measuring and testing devices
Att. IV Sec. 7.1
used for controlling quality.

Control Valve Switch: Valve shall be operated and signal receipt shall be NFPA 72
A5 verified to be within the fist two revolutions of the hand wheel or within Table 14.4.3.2
one-fifth of the travel distance, or per the manufacturer's specifications. Sec.17(j)(1)

High or Low Air Pressure Switch: Switch shall be operated. Receipt of


NFPA 72
signal obtained where the required pressure is increased or decreased a
A6 Table 14.4.3.2
maximum 70 kPa (10 psi) from the required pressure level shall be
Sec.17(j)(2)
verified.

CONTRACTOR personnel performing test and calibrations shall be Schedule Q


A7
trained per applicable international or manufacturer requirements. Att. IV Sec. 7.3

Room Temperature Switch: Switch shall be operated. Receipt of signal NFPA 72


A8 to indicate the decrease in room temperature to 40°F (4.4°C) and its Table 14.4.3.2
restoration to above 40°F (4.4°C) shall be verified. Sec.17(j)(3)

Water Level Switch: Switch shall be operated. Receipt of signal


indicating the water level raised or lowered a maximum 3 in. (70 mm) from NFPA 72
A9 the required level within a pressure tank, or a maximum 12 in. (300 mm) Table 14.4.3.2
from the required level of a nonpressure tank, shall be verified, as shall its Sec.17(j)(4)
restoral to required level.

Water Temperature Switch: Switch shall be operated. Receipt of signal NFPA 72


A10 to indicate the decrease in water temperature to 40°F (4.4°C) and its Table 14.4.3.2
restoration to above 40°F (4.4°C) shall be verified. Sec.17(j)(5)

Saudi Aramco: Company General Use


Mechanical, Electro Sonic or Pressure-Type Water Flow Device:
Water shall be flowed through an inspector’s test connection indicating
the flow of water equal to that from a single sprinkler of the smallest orifice NFPA 72
A11 size installed in the system for wet-pipe systems, or an alarm test bypass Table 14.4.3.2
connection for dry-pipe, pre-action, or deluge systems in accordance with Sec.14(k)
NFPA 25, Standard for the Inspection, Testing, and Maintenance of
Water-Based Fire Protection Systems.

REMARKS:

REFERENCE DOCUMENTS:
1. Schedule G - Material, Tools and Equipment (Pro Forma MP-IK-LS Contract)
2. Schedule Q - Quality Requirements (Pro Forma Contract),
3. SAES-B-014 - Safety Requirements for Plant and Operations Support Buildings,2 January 2018
4. 34-SAMSS-820 - Instrument Control Cabinets - Indoor, 13 July 2016
5. 34-SAMSS-831 - Instrumentation for Packaged Units,14 May 2018
6. NFPA 70 - National Electrical Code (NEC), 2017 Edition
7. NFPA 72 - National Fire Alarm and Signaling Code, 2013 Edition

ATTACHMENTS:

NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).

3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products or
services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states
that the equipment, material or services either meets appropriate designated standards or has been tested and found suitable for a specified purpose.

4. Labeled - Equipment or materials to which has been attached a label, symbol or other identifying mark of an approved qualified organization
concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the
manufacturer indicates compliance with appropriate standards or performance in a specified manner.
5. Remarks:

Contractor / Third-Party Saudi Aramco


Technician Performing Test* PMT Representative
Test Performed Successfully and Results are Acceptable: T&I Witnessed QC Record Reviewed Work Verified
Name, Title, Department,
Name, Initials and Date:
Company, Initials and Date:

QC Inspector PID Representative


Witnessed Test Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Implementation of Test and Analysis of Results Y = YES N = NO F = FAILED

Saudi Aramco: Company General Use

You might also like