EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
General Requirements (Issues to be Resolved Prior to Testing to Provide Clear Field Direction)
A Note: Efficiency & Clear Direction exists for Special Construction Processes Before Work
Begins.
Testing location shall be specified by proponent.
SAES-L-108
Field Testing Shops shall be approved by Project Inspection.
A1
*These special process
Para 4.7.1
reqmts are listed in Attachment 1.
Proponent Specifies Valve Testing extent. List is available.
Attachment 1. Line Class List & direction exists for
testing. All new valves designated
for isolation service (as specified by the Proponent) shall be subjected to
SAES-L-108
A2 a high pressure hydrostatic seat test prior to installation in the line.
Para 4.7.2 & 4
Buttweld and socketweld end valves in nominal pipe size (NPS) 2
inches and smaller are exempt from field testing requirements.
VALVE BEING TESTED IS REQUIRED TO HAVE THAT
TEST
Test crews & Inspectors are trained to properly follow testing procedures
SAES-A-004,
to eliminate water after testing and apply preservation measures such as
A5
mfg approved lubricants & other Corrosion Control measures. Procedure
Section 4
shall detail specifics. Attachment 2.
Before employing the pressure testing manifold in the actual system SAES-A-004,
A6 pressure test, it shall be separately pressure tested to at least 1.2 times
the system test pressure. SAIC-A-2009 Safety Checklist. Section 5
Test water Quality meets the requirements of SAES-A-007.
Testing intervals (maximum weekly) are established for test
water. Test water quality shall have a sulfate reducing
bacteria (SRB) count of 10³ per ml or less as determined by RapidChek SAES-A-007,
A7 II Method. Note: Section 4
Water with higher bacteria count may be acceptable if treated with
biocide & retested and approved by Supv. CTU/ME&CCD/CSD
See Attachment 2 & SAIC-A-2007 Lay-
up Checklist.
General Instruction GI-0002.102 "Pressure Testing Safely" shall be SAES-A-004,
A8
followed during pressure testing. Para. 5.1
B
TEST PREPARATION
CRITICAL: INSPECTION (INTERNAL/EXTERNAL) PRECEDES VALVE TESTING (ATTACHMENT 1)
The relief valve of adequate capacity set to relieve at 5% above the
hydrotest pressure shall be installed. The relief valve(s) shall be tested, SAES-A-004,
B1
dated, and tagged within one week prior to the hydrotest for new Para. 5.5.1
construction projects. Relief Valve current logs exist (M&TE).
Page 1 of 6
Pressure gauges and pressure recorders are calibrated before the tests.
SAES-A-004
B2 The calibration interval shall not exceed one (1) month. Stickers shall be
Para 8.1.5.2
applied indicating the latest calibration date.
Page 2 of 6
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
All gages have a range such that the test pressure is within 30 to 80% of SAES-A-004
B3
the full range. Inspectors know the test parameters. Para 8.1.5.3
A minimum of two pressure gages are available for the test system. SAES-A-004
B4
Their accuracy shall be within 5% of one another. Para 8.1.5.4
SATR-A-2014 Water Chemistry Report is available, currently tested in SAES-A-007
B5 accordance with procedure and acceptable (SRB Count, etc) for the
application. Note: Different water requirements apply! (Procedure)
Test Records shall be made for each test by entries on Pressure Test
Report Form 2642-ENG* and the applicable "Safety Instruction Sheet"
per SAES-A-005. *SATR-A-2001V is used. SAES-A-004
B6
Documents uniquely identify valves with Para 9.3
unique ID number. Acceptance markings identify the
valve (per procedure).
C SHELL TESTS (API 598 Tables) Note: Enter Test Results in SATR-A-2001V for each valve.
For shell tests, visually detectable leakage through the pressure
SAES-L-108,
C1 boundary walls and any fixed body joint is not permitted. Criteria!
Para. 4.7.5
(API 598 Para 3.9.1.1)
Shell Test Pressure (API 598 Table 2)
SAES-L-108,
Para. 4.7.5
C2
API 598 Table 2
Notes b-c
SAES-L-108,
C3
Para. 4.7.5
For Class 800 valves, shell test pressure shall be 1½ times pressure
rating* at 100°F (38°C), round up to next higher increment of 25 psi. SAES-L-108,
C4 NOTE: Para. 4.7.5
Check Valve Stamp for pressure rating. For Carbon Steel Valves, API 598 Table 3
1,975 psi is the usual pressure rating. Caution!
SAES-L-108,
C5
Para. 4.7.5
Page 3 of 6
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
D HIGH PRESSURE SEAT CLOSURE TESTS (API 598 Tables) Note: Test Times per Item C5 above
Maximum Allowable Leakage Rates for Closure Tests
SAES-L-108,
Para. 4.7.5 &
API
D1 598
Table 5
Notes A-F
REMARKS:
NOTES: Rejected Valves are dispositioned (repaired & retested) per Attachment 1 Requirements. USE SATR-A-2001V.
ATTACHMENTS: Attachment 1 - Valve Testing Facility Approval, Start-Up & Other Quality Requirements Including Repairs
Attachment 2 - Valve Testing Special Considerations
REFERENCE DOCUMENTS:
1- SAES-L-108 (21 March 2010) Selection of Valves
2- SAES-A-004 (14 December 2009) General Requirements for Pressure Testing
3- API 598 Valve Inspection And Testing
Page 4 of 6
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff -March 2012) Rev 6 31-Mar-12
Page 5 of 6
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff -March 2012) Rev 6 31-Mar-12