SAUDI ARAMCO TEST REPORT
Emergency Eyewash/Shower Functional Test Report SATR-B-4001 24-Jul-18 PLUMB
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
TEST PROCEDURE ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

B. TEST EQUIPMENT AND MATERIALS CRITERIA

See SATR-A-2003 (Calibration Test Report-Temperature Gauge)

C. TEST RESULTS

Measured value from the face of the shower head to the


CM
surface on which the user stands

Measured diameter of the spray pattern CM

Measured water temperature °C

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU-24-July-2018 - REV.2018.06.00 (Standards Cutoff - June 30,2018) Rev.2018.06.00 30-Jun-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Emergency Eyewash/Shower Functional Test Report SATR-B-4001 24-Jul-18 PLUMB
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

D. CONCLUSIONS

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
The face of the shower head from the surface on which the user stands is
between 208.3 cm (82 inches) and 243.8 cm (96 inches)
SAES-B-069
D1 (ANSI 4.6.5.3)
Section 7
Note: Applicable to Emergency showers only

With the valve in the " full on" position, measured diameter of the
sprays pattern is a minimum of 50.8 cm (20 inch) at 152.4 cm
SAES-B-069
D2 (60 inch) above the standing surface. The center of the spray shall be at
Section 7
least 40.6 cm (16 inches) from any obstruction. (ANSI 4.6.5.4)
(Applicable to emergency showers only)

SAES-B-069
D3 Measured water temperature shall not exceed 38°C (100°F) at any time.
Para 5.3.1

Test results are acceptable and in accordance with Saudi Aramco


D4 N/A
Engineering Standards and contractural requirements.

REMARKS:

REFERENCE DOCUMENTS:
1-SAES-B-069 -- Emergency Eyewash and Showers, 23 January 2012

2-ANSI Z358.1 -- American National Standard for Emergency and Shower Equipment, 2004

Contractor / Third-Party Saudi Aramco


Technician Performing Test* PMT Representative
Test Performed Successfully and Results are Acceptable: T&I Witnessed QC Record Reviewed Work Verified
Name, Title, Department,
Name, Initials and Date:
Company, Initials and Date:

QC Inspector PID Representative


Witnessed Test Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Implementation of Test and Analysis of Results Y = YES N = NO F = FAILED