GTA8.3
Base Engine Data Sheet D553011CX03
Industrial Market
Number Cylinders: 6 Bore: 4.49 in (114 mm) Revision:
Displacement: 3 Stroke: 5.32 in (135 mm)
505 in (8.3 L) 20-Oct-2015
Aspiration: Turbocharged and Aftercooled
Exhaust System
Maximum allowable static bending moment @ exhaust outlet flange: 10 lb-ft 14 N-m
Exhaust manifold/turbocharger blanketing acceptable: No
Cooling System
Engine cooling circuit:
Coolant system type: 2 Pump-2 Loop
Minimum operating block coolant temperature: 160 deg F 71 deg C
Maximum fill rate: 5 gpm 19 L/min
Minimum water pump inlet pressure with fully deaerating cooling system: 0 in-Hg 0 kPa
Maximum static head of coolant above crankshaft centerline: 60 ft 18 m
Minimum pressure cap rating at sea level: 7 psi 48 kPa
Maximum pressure cap rating at sea level: 15 psi 103 kPa
Minimum coolant expansion space (% of system capacity): 6 %
Maximum deaeration time: 25 min
Acceptable types of deaeration systems: Positive, Non-Positive with Partial Baffle,
Coolant recovery
Minimum drawdown (% total cooling system capacity): 11 %
Maximum allowable accessory coolant flow: 0 gpm 0 L/min
Coolant capacity - engine only: 11.6 quarts 11 L
Maximum recommended external coolant flow restriction in engine circuit: 5 psi 34 kPa
Engine coolant circuit thermostat opening temperature: 180 deg F 82 deg C
Engine coolant circuit thermostat fully open temperature: 190 deg F 88 deg C
Thermostat out coolant flow vs. external restriction for engine system (with open thermostat)
80
300
70
2.2 psi
250
4 psi
60
5 psi
8.2 psi
200
50
40 150
1,500 1,800
Engine Speed (RPM)
System Restriction
Engine 2.2 psi 4 psi 5 psi 8.2 psi
Speed (15.2 kPa) (27.6 kPa) (34.5 kPa) (56.5 kPa)
RPM gpm L/min gpm L/min gpm L/min gpm L/min
1,500 62 235 57 216 54 204 44 167
1,800 77 292 74 280 72 273 65 246
Minimum block coolant pressure at speed (open thermostat without radiator cap)
RPM psi kPa
1,500 4.8 33
1,800 9.5 66
Thermostat out coolant flow vs. external restriction for engine system (with open thermostat)
16
56
2 psi
14 4 psi
51 5 psi
8 psi
13
12 46
1,500 1,800
Engine Speed (RPM)
System Restriction
Engine 2 psi 4 psi 5 psi 8 psi
Speed (13.8 kPa) (27.6 kPa) (34.5 kPa) (55.2 kPa)
RPM gpm L/min gpm L/min gpm L/min gpm L/min
1,500 14 51 13 50 13 49 13 48
1,800 16 60 16 59 15 58 15 56
Lubrication System
Standard Capacity oil pan:
Low oil level: 4 gal 15 L
High oil level: 5 gal 19 L
High Capacity oil pan:
Low oil level: 6 gal 23 L
High oil level: 9 gal 34 L
Electrical System
System voltage: 24 V 12 V
Minimum battery capacity-cold soak at -18 deg C (0 deg F) or above:
Engine only-cold cranking amperes (CCA): 900 CCA 1800 CCA
Engine only-reserve capacity (RC): 320 min 640 min
Maximum starting circuit resistance: 0.002 Ohm 0.00075 Ohm
Fuel System
Minimum gas supply pipe size: 2 in 51 mm
Cummins supplied filter pressure rating: 100 psi 689 kPa
RATING GUIDELINES
1. LOAD RATINGS
1.1 *Continuous rating may be used for constant load applications requiring uninterrupted service at full throttle for extended periods of time for Water Management
applications.
1.2 *WMR (Water Management Rating) may be used for constant load applications requiring uninterrupted service at full throttle for extende periods of time and conforms
with BS 5514 and DIN "A" 6271. Maximum pump size must not exceed WMR net.
1.3 Operating at Elevated Altitude and Temperature. Continuous Turbocharged ratings up to 5000 ft. (1524 m) and 100° F Ambient without derate.For altitudes above
5000 ft, derate 4% / 1000 ft and Ambient temperatures above 100°F,derate 1% per 10°F above 100°F.
2. SPEED RATINGS
2.1 If the application qualifies for the continuous load rating the governor cut-in point shall be set within the limits of the solid line portion of the continuous curve.
2.2 If the application qualifies for the maximum load rating the governor cut-in point shall be set within the limits of the solid line portion of the maximum curve.
3. DEFINITIONS
3.1 Load (Speed) factor is defined as the arithmetic mean of the Load (Speed) profile of the normal duty cycle, not including prolonged periods of idle operation.
The Maximum Rating conforms to ISO 3046 overload power and fuel stop power. The Continuous Rating may be used for continuous service in commercial applications and
it conforms to ISO 3046 continuous power.
Reference standards: BS 5514 and DIN 6271 standards are based on ISO 3046.
End of Report