Professional Documents
Culture Documents
a r t i c l e i n f o a b s t r a c t
Article history: This paper provides a simplified analysis method to estimate the impact of building shape on energy effi-
Received 13 February 2008 ciency of office buildings in Kuwait. The method is based on results obtained from a comprehensive
Accepted 12 September 2008 whole building energy simulation analysis. The analysis takes into account several building shapes and
Available online 17 November 2008
forms including rectangular, L-shape, U-shape, and H-shape as well as building aspect ratios, window-
to-wall ratios, and glazing types. The simplified method is suitable for architects during preliminary
Keywords: design phase to assess the impact of shape on the energy efficiency of office buildings.
Building shape
Ó 2008 Elsevier Ltd. All rights reserved.
Cooling energy use
Heating energy use
Office buildings
Some studies have shown that the building shape can have For the study presented in this paper, a prototypical Kuwaiti of-
a significant impact on the energy costs of heating and cooling fice building is considered. The total office floor area for this proto-
[1–3]. However, no general guidelines are available for architects typical building is 12,500 m2 distributed over 20 floors (625 m2/
and designers on the impact of the form on the energy efficiency floor).
of buildings. Recently, Ourghi et al. [4] have developed a simpli-
fied analysis tool to predict the effect of shape selection on the 2.1. Building shapes
annual energy use for office buildings. In particular, the method
correlates the annual energy use to the relative compactness of Several shapes and floor plans have been developed for the
the building. The relative compactness, a normalized ratio of prototypical office building. The floor plans include: Rectangular-
the volume to the exterior wall area, is commonly used as indi- shape, L-shape, T-shape, Cross-shape, H-shape, U-shape and
cator of shape in buildings. The method of Ourghi et al. has been Cut-shape shape. For an easier comparative analysis, the energy
developed for limited building shapes (rectangular and L-shapes) simulation results are normalized using the results obtained from
[4]. a reference shape, which has a square floor plan with the same
In this paper, the work of Ourghi et al. is extended to include floor area (625 m2) and number of floors (20 floors) as the proto-
several building shapes, window areas, glazing types. Using the re- typical office building. In addition to the reference square floor
sults of a comprehensive parametric analysis, a correlation is plan, a ‘‘bounding rectangle” is defined for each floor plan. This
developed to predict the impact of building shape on energy effi- bounding rectangle is defined by its width W, and depth D as
ciency for various window areas and glazing types. First, the basic shown in Table 1 for each shape. The floor area is kept constant
settings for the parametric analysis, conducted using a detailed for all shapes. To ensure that the conditioned building volume re-
building energy simulation tool, are described. Then, selected re- mains constant, the total height is kept the same for all building
sults of the parametric analysis are presented. Finally, the simpli- configurations throughout the study.
fied calculation method is developed to correlate annual energy Table 1 lists the geometric dimensions including the perimeter
use to building shape and window-to-wall ratio as well as glazing (P) and the relative compactness (RC) of the floor plans for all the
type. building configurations used in this study.
* Corresponding author. Tel.: +1 303 492 3389; fax: +1 303 492 7317. The relative compactness (RC) is used in this study as an indica-
E-mail address: krarti@colorado.edu (M. Krarti). tor of building shape to help the comparative analysis when
0196-8904/$ - see front matter Ó 2008 Elsevier Ltd. All rights reserved.
doi:10.1016/j.enconman.2008.09.033
A. AlAnzi et al. / Energy Conversion and Management 50 (2009) 822–828 823
Table 1
Geometric dimensions for building floor plans with L, cross, T and H shapes
No. Bound rectangle L-shape Cross-shape T-shape H-Shape
W (m) D (m) t (m) P (m) RC t (m) P (m) RC t (m) P (m) RC t (m) P (m) RC
1 19.00 294.00 2.00 626.00 0.16 2.00 626.00 0.16 2.00 626.00 0.16 1.03 1211.94 0.08
2 20.00 231.30 2.50 502.60 0.20 2.50 502.60 0.20 2.50 502.60 0.20 1.30 962.61 0.10
3 22.00 188.33 3.00 420.67 0.24 3.00 420.67 0.24 3.00 420.67 0.24 1.57 794.19 0.13
4 22.50 158.71 3.50 362.43 0.28 3.50 362.43 0.28 3.50 362.43 0.28 1.85 676.16 0.15
5 24.00 135.50 4.00 319.00 0.31 4.00 319.00 0.31 4.00 319.00 0.31 2.14 585.72 0.17
6 25.00 104.40 5.00 258.80 0.39 5.00 258.80 0.39 5.00 258.80 0.39 2.72 462.15 0.22
7 26.00 83.67 6.00 219.33 0.45 6.00 219.33 0.45 6.00 219.33 0.45 3.33 380.00 0.26
8 27.00 68.86 7.00 191.71 0.52 7.00 191.71 0.52 7.00 191.71 0.52 3.97 321.49 0.31
9 28.00 57.75 8.00 171.50 0.58 8.00 171.50 0.58 8.00 171.50 0.58 4.63 277.73 0.36
10 29.00 49.11 9.00 156.22 0.64 9.00 156.22 0.64 9.00 156.22 0.64 5.34 243.77 0.41
11 30.00 42.20 10.00 144.40 0.69 10.00 144.40 0.69 10.00 144.40 0.69 6.08 216.63 0.46
12 31.00 36.55 11.00 135.09 0.74 11.00 135.09 0.74 11.00 135.09 0.74 6.89 194.41 0.51
13 27.00 36.83 12.00 127.67 0.78 12.00 127.67 0.78 12.00 127.67 0.78 7.21 186.91 0.53
14 28.00 32.85 13.00 121.69 0.82 13.00 121.69 0.82 13.00 121.69 0.82 8.01 171.37 0.58
15 29.20 29.23 14.00 116.86 0.85 14.00 116.86 0.85 14.00 116.86 0.85 8.91 157.50 0.63
assessing the impact of shape and geometric dimensions on the ðV=As Þbuilding
RC ¼ ð1Þ
building energy performance. It is described mathematically as ðV=As ÞRef
follow:
Table 3
Types of glazing and window-to-wall ratios considered in the simulation analysis
Table 2
Office building model basic features Glazing Label SHGC WWR
Lighting power density (LPD) 12.3 W/m2 Single clear 6 mm SVC 0.815 0–0.75
Equipment power density (EPD) 2.6 W/m2 Double green DGR 0.419 0–0.75
Average occupancy density (m2/person) 26 m2/person Double bronze DBR 0.492 0–0.75
Glazing distribution Uniform glazing distribution Double clear DCL 0.762 0–0.75
HVAC system Water-cooled chiller HVAC system Double clear low e DCLE 0.643 0–0.75
with electric resistance heating Single bronze reflective tint L SBR 0.252 0–0.75
824 A. AlAnzi et al. / Energy Conversion and Management 50 (2009) 822–828
where (V/As)building is the compactness of a specific shape, and dow to wall ratio was set to vary from 0 (no opening) to 0.75. Sev-
(V/As)ref is the compactness of the reference building (which has a eral glazing types with varying solar heat gain coefficient (SHGC)
square floor plan in this study). Note that V and As refer, respec- were analyzed and used. Table 3 summarizes the glazing types
tively, to the conditioned volume and envelope surface area ex- characterized by the solar heat gain coefficient (SHGC) and the
posed to the outdoor air (i.e., exposed exterior wall area). As range of window-to-wall ratios (WWRs) used in the analysis.
indicated by Eq. (1), the relative compactness (RC) has no dimen- For all the building models, the roof is made up of 100-mm hea-
sions. Since the floor area and total height of any building configu- vy weight concrete and 75-mm extruded polystyrene insulation
ration are identical, the building volume is constant for buildings and build-up roofing while the walls are made up of 200-mm hea-
including the reference building. Eq. (1) can be rewritten as vy weight concrete and 25-mm extruded polystyrene insulation
and 25-mm stucco. The roof and wall constructions meet the
RC ¼ ðAs Þref =ðAs Þbuilding ð2Þ
Kuwaiti Ministry of Energy (MOE) code of practice [6]. The overall
Table 1 shows the geometric characteristics for various building U-values are 0.40 W/m2 K and 0.54 W/m2 K for, respectively, the
shapes used in the study. These geometric characteristics include: roof and the walls.
the dimensions of the bounding rectangle, W and D, the perimeter Fig. 1 shows 3-D rendering for selected building models with
(P) and the relative compactness (RC). An interesting observation various shapes considered in the simulation analysis.
from Table 1 is that the perimeter values of the L-, T- and cross-
shaped buildings are identical for the similar bounding rectangle
dimensions (W and D). In fact, these perimeters’ values indicate 3. Discussion of results
the same degree of surface exposure to the ambient conditions.
In addition, the values shown in Table 1 indicate that higher rela- The total annual energy use, Et, for any building configuration is
tive compactness (RC) is associated with lower perimeter. normalized relative to the annual energy use, Eref obtained for the
reference building (with a square floor plan) to facilitate the com-
2.3. Building models parative analysis. A similar normalization is performed for the an-
nual cooling energy use.
Models for office buildings with various shapes have been In this section selected results of the parametric analysis are
developed using DOE-2 simulation program [5]. For all models, presented.
typical office space occupancy patterns and schedules suitable for
Kuwait are utilized. In particular, these office space occupancy pat- 3.1. Impact of relative compactness
terns are listed in Table 2.
Several parameters are varied to estimate the annual electricity Fig. 2 illustrates the impact of the relative compactness (RC) on
use for several building configurations with different building both annual cooling energy use and annual total building energy
shapes and relative compactness values. The analysis is carried use for a building with no windows (WWR = 0) for all building
out for various window sizes and glazing types. In particular, win- shapes considered in the analysis. The results of Fig. 2 indicate that
the energy use decreases as the relative compactness increases. In-
deed, as the relative compactness (RC) increases, the exterior wall
area exposed to ambient conditions decreases and consequently
the building cooling load decreases.
The same results shown in Fig. 2 are rearranged and presented
in Fig. 3 using 1/RC in the x-axis. It is clear that when there is no
window (WWR = 0), the energy use in the building is proportional
to 1/RC. Referring to Eq. (2), this result is expected since 1/RC is
simply related to the building exterior wall area.
2.10
2.00 L T + H Cut Rc U
1.90
1.80
1.70
1.50
1.40
1.30
1.20
1.10
1.00
0.90
0.05 0.15 0.25 0.35 0.45 0.55 0.65 0.75 0.85 0.95 1.05
RC
(a) Total Energy
2.20
2.10
L T + H Cut Rc U
2.00
1.90
1.80
1.50
1.40
1.30
1.20
1.10
1.00
0.90
0.05 0.15 0.25 0.35 0.45 0.55 0.65 0.75 0.85 0.95 1.05
RC
(b) Cooling Energy Use
Fig. 2. Normalized annual building (a) total energy use and (b) cooling energy use for L, T, H, cut, rectangular and U building shapes (WWR = 0) as a function of RC.
4. Development of a simplified analysis method type. Thus, three parameters are considered to correlate the nor-
malized building energy use to the building shape. These parame-
Based on the results of the parametric analysis, it is determined ters include: the relative compactness (RC), the window-to-wall
that the impact of the building shape on the building energy per- ratio (WWR), and glazing type defined by its solar heat gain coef-
formance depends primarily on the window area and the glazing ficient (SHGC). Several correlation equations are tested. Table 4
826 A. AlAnzi et al. / Energy Conversion and Management 50 (2009) 822–828
2.10
2.00 L T + H Cut Rc U
1.90
1.80
1.70
1.60
Et/Eref
1.50
1.40
1.30
1.20
1.10
Ratio of Total Energy Use with 0% Glazing
1.00
0.90
1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00 10.00 11.00 12.00 13.00
1/RC
(a) Total Energy
2.40
2.30 L T + H Cut Rc U
2.20
2.10
2.00
1.90
Et/Eref
1.80
1.70
1.60
1.50
1.40
1.30
1.20
1.10
1.00
Ratio of Cooling Energy Use with 0% Glazin g
0.90
1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00 10.00 11.00 12.00 13.00
1/RC
(b) Cooling Energy Use
Fig. 3. Normalized annual building (a) total energy use and (b) cooling energy use for L, T, H, Cut, rectangular and U building shapes (WWR = 0) as a function of 1/RC.
A. AlAnzi et al. / Energy Conversion and Management 50 (2009) 822–828 827
14.00
13.00 L T + H U Rc Cut
12.00
11.00
10.00
9.00
8.00
Single Clear Glazing (WWR = 50%)
Et/Eref
7.00
6.00
5.00
4.00
3.00
2.00
1.00
0.00
0.05 0.15 0.25 0.35 0.45 0.55 0.65 0.75 0.85 0.95 1.05
RC
Fig. 4. Normalized annual building total energy use for L, T, H, cut, rectangular and U building shapes with clear glass and 50% WWR.
RC = 0.16, 25%G
7
6
5
E/Er
4
3
2
1
0
0 45 90 135 180 225 270 315
Azimuth Angle
U H L + T Rectangle
RC = 0.16/0.17, 50%G
9
8
7
6
E/Er
5
4
3
2
1
0
0 45 90 135 180 225 270 315
Azimuth Angle
U H L + T Rectangle
Table 4
Regression results for recommended correlation equations
15
y = 0.9259x + 0.2244
transmission) to heating and cooling building loads. For buildings
R2 = 0.9259 with small windows (or no windows as the case of the results
12
Et/Etr (Calc) shown in Fig. 2), the term 1/RC is dominant.
Based on simplicity and accuracy, the total building energy use
9
from any building shape can be obtained from the following corre-
6
lation (Equation T-8):
Et ¼ Eref fA þ B ðWWR SHGC 1=RCÞ 2
3
þ C ðWWR SHGC 1=RCÞ þ D 1=RCg ð3Þ
0
0 5 10 15 where
Et/Etr (Act)
(a) Correlation T-1 Eref is the total building energy use for a square building (refer-
ence building) with the same floor area and volume of the actual
15
y = 0.9455x + 0.1643 building;
R2 = 0.9456 A, B, C, and D are regression coefficients with A = 0.4525;
12
B = 0.223; C = 1.755; and D = 0.848.
Et/Etr (Calc)
6 5. Summary
3
The results of a detailed parametric analysis indicate that the
effect of building shape on total building energy use depends on
0
0 5 10 15 primarily three factors, the relative compactness, RC, the win-
Et/Etr (Act) dow-to-wall ratio, WWR and glazing type defined by it solar heat
(b) Correlation T-2 gain coefficient, SHGC. For buildings with low window-to-wall
15
ratios, it is found that the total energy use is inversely proportional
y = 0.9464x + 0.1623 to the building relative compactness independent of its form.
R2 = 0.9464
12 Based on regression analysis, a correlation is found to provide a
good curve fit between the annual total building energy use and
Et/Etr (Calc)
0
Acknowledgement
0 5 10 15
Et/Etr (Act) The authors would like to acknowledge the financial support
(c) Correlation T-3 from the Kuwait University Research Administration.
Fig. 6. Prediction accuracy for three correlation equations T-1, T-2, and T-3.
References