You are on page 1of 4

Record Plus

Electronic trip units

FK800 - FK1600 Electronic Trip Unit SMR1e, s and g

Non inter changeable electronic Trip Units designed to This easy-to-use trip unit with overload and selective
allow the user to conveniently tailor the protection short-circuit protection is equipped with an overload sig-
device to match individual circuit requirements. The nalling option and has a built-in temperature ­sensor to
available options include adjustable overload pickup prevent the breaker and electrical ­components in its
­values, overload trip time characteristics, short time pick- ­immediate vicinity from ­overheating. The 4 pole units are
up circuit values, short time delay ­circuit trip times and equipped with a switchable neutral protection option,
energy values. The trip unit can be equipped with a allowing the user to set the neutral at 0.50 or 100% of
ground-fault ­protection and provides a flexible solution the phase ratings.
to all ­protection scenarios.

Overload Protection (LT or Long Time) trips the breaker when a short circuit is detected of a value
Trip Units

Designed to meet the newest IEC 60 364 installation regula- exceeding the capabilities of the breaker in which it is installed
tions all variants can trip the breaker with 5 seconds at 8 and initiates a current limiting interruption of the fault.
times the LT setting (Ir). The SMR1e is supplied with this 5
second time band whilst the SMR1s and g variants have 4 This device once combined with unique current limiting pro-
selectable time bands that trip the breaker within 5, 10, 20 peties of the downsteam Record Plus breaker provide a high
or 30 seconds. The device is adjustable from 0.4 to 1 x the level of Selectivity whilst maintaining Current Limitation.
breaker (In) or Ict rating in 9 steps.
Intro All SM1e, s or g trip units have LED's indicating that the Trip
Ground Fault Protection (GF)
Designed for protection under fault conditions the ground
unit has powered up (green) and a second LED that provides fault device measures the vectorial sum of the three phase
information on a imminent tripping event. This LED flashes current and, if procent, that of the neutral conductor if the
A at three times a second when the current reaches 95% of sum of these values exceeds the set current thresholds for
the breaker setting (Ir) and will remain fully lit when 105% of a period of time greater than the set time delay, the
this values is reached. If the temperature in the electronic breaker is tripped.
circuits reaches 75 degrees centigrade both LED's light up The Ground Fault protection option is adjustable from
B simultaneously whilst a trip is initiated once the tempera- 0.2 to 1 x the chosen breaker rating (Ict) in 9 steps. The user
ture exceeds a 90 degree centigrade limit. can also define one of 4 delay time bands (GFD) designed
to allow selectivity between ­different sensor ratings.
C A third LED located in the vicinity of the LT setting knob indi- The groundfault device is available in the SMR1g trip unit type.
cates a breaker trip on an overload event.
Zone Selective Interlock
A device that allows the user to achieve selectivity
D ­combined with the fastest possible fault reaction time. With
connected ZSI the SMR1s and SMR1g trip unit will always
trip the breaker as quickly as possible, ignoring the time
E delays set by means of the STD or GFD devices. However
when a ZSI ­signal is recieved from a downstream breaker
equipped with an SMR1 s, 1g or 2 the STD or GFD of the
upstream device are reset to the previously ignored original
F Timed Short Cicuit Protection (ST or Short Time) GFD and STD timings. The Ground Fault and Short Time Zone
Offering a selective protection against low value short-­ Selective Interlock signals are shared on one in/out put .
circuits the Short Time protection is settable from 1.5 to 10 x The device only works when auxiliary power is ­present and
the adjusted LT protection (Ir). operates up to a distance between breakers of 1 kilometer.
G The SMR1e has a fixed time band of 100 millisecond's. The use of shielded cable is required. A ­maximum of five
A ­setting that allows discrimination with downstream FG SMR 1s, g or SMR2 trip units can be linked in this manner.
devices. (not available in the SMR1e)
X Tthe SMR1s and g variants have a choice of four time
­setting bands (STD), designed to allow ­selectivity between Connection of trip unit
different breaker sizes. Here the STD device can be set to an Each SMR1s and G
'energy curve mode' that changes the reaction of the device Trip Unit has a con-
from a fixed delay and reaction time value when the set nector located on
current level is reached to a reaction time that depends on the right side of the
the energy flowing in the circuit. breaker. This connector is normally hidden behind a break-
away cover and is required to ­connect the following:
HIOSC Tripping Device (If setting) Auxiliary power supply (24V DC), ZSI in and out,
All Record Plus devices are equipped with a HIOSC (hi set long time pre-alarm signal, connection of external CT for
Instantaneous) protection device. This device mechanically 4 pole groundfault on three pole breakers.

B.20
SMR1e, s and g Range

FK800- FK1600 Electronic Trip Units

Trip Units are available in 4 ratings and 3 different In order to verify the correct operation of the breaker an
versions depending on the frame rating and the Trip Unit a PC based software packge is available.
chosen functionality.
FK800 frame size 50/60 Hz 800A We strongly recommend the use of this option.
FK1250 frame size 50/60 Hz 1000 and 1250A
FK1600 frame size at 50/60Hz 1600A

SMR1 - FK frame
FK800, FK1250 and FK1600 breakers - Electronic trip unit overview
FK Frame Electronic trip unit overview
In LT ST Neutral Protection
(A) pick-up band 1.05 - 1.3 Ir pick-up band ± 20% Im Switchable type
Ir setting min (A) max (A) Im setting min (A) max (A) 4P4T 4P 3TN 4P3T
FK800 800 320 800 480 8000 =Ir =Ir/2

protected
FK1250 1000 0.4-1 x In 400 1000 1.5-10 Ir 600 10000 =Ir =Ir/2

Not
SMR 1e N H L
1250 in 9 steps 500 1250 in 9 steps 750 12500 =Ir =Ir/2
FK1600 1600 640 1600 960 16000 =Ir =Ir/2
In LT ST Neutral Protection
(A) pick-up band 1.05 - 1.3 Ir pick-up band ± 20% Im Switchable type
Ir setting min (A) max (A) Im setting min (A) max (A) 4P4T 4P 3TN 4P3T
FK800 800 320 800 480 8000 =Ir =Ir/2
Intro

protected
FK1250 1000 400 1000 1.5-10 Ir 600 10000 =Ir =Ir/2

Not
1250 500 1250 in 9 steps 750 12500 =Ir =Ir/2
FK1600 1600 640 1600 960 16000 =Ir =Ir/2
LTD(1) STD(2)
SMR 1s N H Setting min max Setting min max A
(sec.) (sec.) (sec.) (sec.)
5 4 6 0 0.015 0.05
10 8 12 0.1 0.095 0.17
20
30
16
24
24
36
0.2
0.3
0.175
0.255
0.29
0.41 B
In LT ST Neutral Protection
(A) pick-up band 1.05 - 1.3 Ir pick-up band ± 20% Im Switchable type

FK800 800
Ir setting min (A)
20
max (A) Im setting min (A)
800 480
max (A)
8000
4P4T
=Ir
4P 3TN
=Ir/2
4P3T
C
protected
FK1250 1000 0.4-1 x In 400 1000 1.5-10 Ir 600 10000 =Ir =Ir/2
1250 in 9 steps 500 1250 in 9 steps 750 12500 =Ir =Ir/2 Not
FK1600 1600 640 1600 960 16000 =Ir =Ir/2

Setting
LTD(1)
min max
STD(2)
Setting min max
D
(sec.) (sec.) (sec.) (sec.)
5 4 6 0 0.015 0.05

SMR 1g N H
10
20
8
16
12
24
0.1
0.2
0.095
0.175
0.17
0.29 E
30 24 36 0.3 0.255 0.41
In GF GFD(2)
(A) pick-up band ± 20% Ig Setting min max
Ig setting min (A) max (A) (sec.) (sec.) F
FK800 800 160 800 0 0.015 0.05
FK1250 1000 0.2-1 x In 200 1000 0.1 0.095 0.17
1250 in 9 steps 250 1250 0.2 0.175 0.29
FK1600 1600 320 1600 0.3 0.255 0.41
G
(1) At 7.2 x Ir: Min. is minimum settable delay: Max: Is maximum total tripping time.
(2) At set value: Min. is minimum settable delay: Max: Is maximum total tripping time.

Trip units are available in 4 ratings and 3 X


different versions depending on the frame
rating and the ­chosen functionality.
FK800 frame size
800A, SMR 1e, s or g
FK1250 frame size
1000 and 1250A,SMR 1e, s or g
FK1600 frame size
1600A,SMR 1e, s or g
The trip units are an integral part of the
breaker and are NON interchangeable.

B.21
Record Plus
Time Current Curves
FK800 - FK1600
Trip Units SMR1e, s and g
Breaker FK1600 Ict = 1600A & FK800 Ict = 800A SMR1e Breaker FK1250 Ict = 1250A & FK1250 Ict = 1000A SMR1e
10000 10000
2 hr. 2 hr.
Set at 1 x sensor rating Set at 1 x sensor rating
Ir=800 or 1600A Ir=1000 or 1250A
Ist set a 10 x Ir. Ist set a 10 x Ir.

1000 1000

Set at 0.4 x sensor rating Set at 0.4 x sensor rating


Ir=320 or 640A Ir=400 or 500A
Ist set a 2 x Ir. Ist set a 2 x Ir.

100 100
Trip Units

10 10

1 1

0,1 0,1

Intro 1000A rating

1250A rating

0,01 0,01

A
Seconds (S)
Seconds (S)

0,001 0,001

B 0,1
X sensor rating (Ict=800 or 1600A)
1,0 7.2 10,0 100,0 0,1
X sensor rating (Ict=1000 or 1250A)
1,0 7.2 10,0 100,0

Breaker FK1600 Ict = 1600A & FK800 Ict = 800A SMR1s & g 1/2 Breaker FK1600 Ict = 1600A & FK800 Ict = 800A SMR1s & g 2/2
C 10000
2 hr.
Set at 1 x sensor rating
10000
2 hr.
Set at 1 x sensor rating
Ir=800 or 1600A Ir=800 or 1600A
Ltd=Class 30 Ltd=Class 30
Ist set a 10 x Ir. Ist set a 10 x Ir.
Std=300msec Std=300msec

D 1000 1000

Set at 0.4 x sensor rating Set at 0.4 x sensor rating


Ir=320 or 640A Ir=320 or 640A
Ist set a 2 x Ir. Ist set a 2 x Ir.
Std set at 0 LTD Delay bands Std set at 0.01 LTD Delay bands

E
Class 30 Class 30
100 Class 20 100 Class 20
Class 10 Class 10
Class 5 Class 5

F 10 10

G 1 1

STD bands 0.01, 0.1, 0.2 & 0.3

X 0,1 0,1 I2t ON Ir=320 or 640A

0,01 0,01

STD bands 0.0, 0.1,


Seconds (S)

Seconds (S)

0.2 & 0.3

0,001 0,001
0,1 1,0 7.2 10,0 100,0 0,1 1,0 7.2 10,0 100,0
X sensor rating (Ict=800 or 1600A) X sensor rating (Ict=1000 or 1250A)

B.22
Time Current Curves

Breaker FK1250 Ict = 1250A & FK1250 = Ict = 1000A - SMR1s & g 1/2 Breaker FK1250 Ict = 1250A & FK1250 Ict = 1000A - SMR1s & g 2/2
10000 10000
2 hr. 2 hr.
Set at 1 x sensor rating Set at 1 x sensor rating
Ir=1000 or 1250A Ir=1000 or 1250A
Ltd=Class 30 Ltd=Class 30
Ist set a 10 x Ir. Ist set a 10 x Ir.
Std=300msec Std=300msec

1000 1000

Set at 0.4 x sensor rating Set at 0.4 x sensor rating


Ir=400 or 500A Ir=400 or 500A
Ist set at 2 x Ir. Ist set at 2 x Ir.

SMR1 - FK frame
Std set at 0 LTD Delay bands Std set at 0.01 LTD Delay bands
Class 30 Class 30
100 Class 20 100 Class 20
Class 10 Class 10
Class 5 Class 5

10 10

1 1

STD bands 0.01, 0.1, 0.2 & 0.3


0,1 0,1 I2t ON Ir=400 or 500A

1000A 1000A Intro


1250A 1250A

0,01 0,01

STD bands 0.0, 0.1, 0.2 & 0.3 A


Seconds (S)

Seconds (S)

I2t OFF

0,001 0,001
0,1
X sensor rating (Ict=1000 or 1250A)
1,0 7.2 10,0 100,0 0,1
X sensor rating (Ict=1000 or 1250A)
1,0 7.2 10,0 100,0
B
Breaker FK800 - FK1250 & FK1600 Ground Fault
100 C

GF current value Adjustable


0.2 to 1 x sensor rating
D
Lowest band - Green
GF=0.2 x Ir GFD=100millisec.

10 Highest band - Red


GF=1 x Ir GFD=1000 millisec.

F
1

0,1
X
Seconds (S)

Other GFD bands


Set at: 200 or 500Msec

0,01
0,1 1 10
X Sensor Rating Is

B.23