PLC
General Structure
MILL DRIVE
Subsystems DEVICES
SENSOR 1
Devices
SENSOR 2
PUMP 1
PUMP 2
etc.
HEATER 1
etc. etc.
SWITCH 1
etc.
BREAKE SYSTEM
etc.
© ABB Industries - 3
RINGMOTOR
etc.
etc.
PLC
Control / interlocks
Signals are physically inputs/ outputs of the Drive Controller/ PLC as
well as internal calculated values or Boolean values as a result of logical
conjunctions.
Signals will be described in control/ interlocks of the particular
subsystems
Physical inputs/ outputs can be find in the I/O list of the referring mill
All significant Boolean and analogue values will be sent to the DCS
system. They can be find in the DCS list.
Interlocks are defined as an input/ output signal or a PLC/ DCS internal
logic condition that automatically prevents the operation of an individual
device/ auxiliary. Interlocks are listed in the interlock list.
© ABB Industries - 4
PLC
Different types of interlocks
Safety interlocks
Process interlocks
CYCLONE
UNDERFLOW
LAUNER
BALL MILL
BALL MILL
LUBRICATION
SYSTEM
BALL MILL
BRAKING
SYSTEM
CYCLONE
© ABB Industries - 7
Controller
General
Time critical tasks
All time critical tasks will be processed in the drive control system
(PSR)
Functionality
Functionalities
Brake control logic
Cyloconverter cooling pump control logic
Ringmotor air gap detection
© ABB Industries - 10
PLC System
Mode control
Communication from / to DCS system
Communication from / to PRS
Control lubrication system
Control ringmotor auxiliary system
Supervising and I/O control of cycloconverter cooling pumps
Supervising and I/O control of brake system
Alarm/ Fault handling of auxiliary drives/ devices
© ABB Industries - 11
General overview
DCS
see DCS Signal List
VMS Ethernet
OperatelT Profibus
RSView ControlNet
Modbus
serial communication
DF1(Allen Bradley) or
Modbus
PLC PSR
Ethernet
OPC
PLC specific
Serialbus
I/O
see I/O Signal List
© ABB Industries - 12
Overview of signal flow
23kV / 50Hz / 3ph -15/+5% Legend
380V / 3ph / 50Hz
1. MCC LV Power Supply
Client Proxy Server 2. Synchronisation Transformer HV Supply
125VDC
MCC-supplied
Air condition UPS 24. Main Breaker Control and Supervision
redundant 40 System
Supply 25. Stator Transformer 1 Supervision
+F14
40
26. Stator Transformer 2 Supervision
MCC +CA +CB +CC
27. Stator Transformer 3 Supervision
+F05...+F08 PSR +F02 PLC Video Monitoring 28. Serial Interface PSR to PLC (RS 232 / DH+)
30
Control & Regulation +F03 System +F04 29. Motor Winding temperature Supervision
Water inlet / outlet temp. supervision by PT100
Cyclo-Converter 12-Pulse 30. Cycloconverter control & supervision
16 Excitation 31. Cycloconverter Recooling System
+F01 Cycloconv.Recooling Supervision
19 redundant 31 28 32. Mill Lubrication system Supervision
+F15 VMS Tower Data Logger
33. Excitation converter control
33 34. Air Gap Supervision
35. Air temp., water flow/ leakage, filter superv., dust
sealing
14 15 36. Interconnection MLCB to PLC
21 E-House
37 Arcnet Interface MLCB to PSR
42 38. Interface PLC to DCS
39. Serial Interace VMS to PLC
Knife switches 39a.Serial Interace VMS to Monitor in DCS
34 37 40. UPS Power Supply (PSR,PLC, VMS)
17 36 41. Mill Brake Control & Supervision
2 x Make up Fan
V
Ringmotor W
water leakage
U MLCB
dust sealing
PT100
Y
9x Probe
exchanger
Excitation
Box
M 44. Transformer Differential Protection
Heater
air gap
35
DF1(Allen Bradley) or Modbus
32
20
Mill Lubrication System Hardwired connections
© ABB Industries - 13
41
(scope of mill supplier) Mill Brake Ethernet, Profibus, ControlNet, Modbus
System
(scope of mill supplier)
Ethernet
18 Phoneline
© ABB Industries - 14
I/O interface
Fieldbus Module,
Profibus-DP
AC 800F (Master)
HUB CCR
Ethernet
Communication
Module
LOCAL HUB
Fieldbus Module,
Profibus-DP
Fieldbus Module,
Modbus Serial
VMS
PLC
PSR DRIVE
CONTROLLER
PSR
SAG MILL
AC 800F
Fieldbus Module,
DCS
VMS
Profibus-DP
BALL MILL 1
Ethernet
Communication
Module
BALL MILL 2
Fieldbus Module,
Printer
Profibus-DP
I/O interface
OPTION
I/O interface
Network PLC physical connection
ABB
I/O interface
ABB
ABB
DCS SYSTEM
CLIENT
© ABB Industries - 15
RS232
RS485
PSR Controller
ABB E- House Panel +F02 (PRS)
Bus
PLC specific
17 5 6 - P A 7 2
Rack 0
17 56 -L5 5M 14
Rack 5
Rack 4
Rack 3
Rack 2
R ESER VE
1756-IR6I 1756-IA16 1756-IA16 1756-MVI
R ESER VE
1756-IR6I 1756-IA16
R ESE RVE
R ESE RVE
Ana lo g Outp ut
17 56 -L5 5M 14
Option
17 5 7-S R M
Local PLC physical connection
Rack 1
Ethernet
VMS
LOCAL HUB
ABB E- House
to DCS system
ABB TOOL
Commissioning notebook
Ethernet
ETHERNET
LEVEL 2 DATA LAYER CSMA/CD
ETHERNET, CONTROLNET,…
LEVEL 1 PHYSICAL LAYER
© ABB Industries - 16
Modbus
Port 1 Channel A
RS232 RS232
Port 2
RS485
RS485
Channel B
Port 3
© ABB Industries - 17
Modbus
PSR PLC
Slave
Device Nr 6
MODBUS MODULE MCM.P2Cmd[1].IntAddress =0
Master
MCM.P2Cmd[1].Device = 6
MCM.P2Cmd[1].Func = 16
300H aaaa 0 MCM.ModDef.WriteStartReg 0 aaaa
00
MCM.ModDef.WriteRegCnt = 600
un ce = s = 6
s
6
d[0 Dev dre
3
C m d [ 0 ] . I n t Ad
c=
i
M. 2Cm [0].
].F
MC M.P Cmd
WRITE
2
MC M.P
P2
MC
MCM.P2Cmd[0].Count = 100
MCM.P2Cmd[1].Count = 100
598
599
600 MCM.ModDef.ReadStartReg 47
601 48 AAAA
602 49 BBBB
50 CCCC
MCM.ModDef.ReadRegCnt = 600
51
READ
© ABB Industries - 18
32FH gghh 96
Program overview
Systems
Lubrication system (supplied by mill supplier)
Brake system (supplied by mill supplier)
MV (Medium Voltage) system
Excitation system
Cycloconverter system
Ringmotor system
E-House
Reference documents
Cat. 1 - SAG Mill Drive Operation Manual
- BALL Mill Drive Operation Manual
State
State
Alarm, Command, Control, Fault, High, Indication, Low, Normal,
Release, Selected, Value
Type
DI, DO, AIT, AIV, AIP, DIP, AOP, DOP, DIC, AIC
© ABB Industries - 23
Lubrication system
Subsystem
General lube system
Oil reservoir system
Low pressure pump system
High pressure pump system
Emergency accumulator system
© ABB Industries - 24
Lubrication System
DISCHARGING
FEED END
END
FLOW
DIVIDER
OIL
FILTER
INDIVIDUAL
NITROGEN
FLOW
CHARGING
DIVIDER
COOLING
WATER FLOW
DIVIDER
HEAT
EXCHANGER FLOW
DIVIDER
COOLING
WATER
FLOW
DIVIDER
LOW PRESSURE
PUMPS
RELIEF
RELIEF VALVE FLOW FLOW
VALVE DIVIDER
RELIEF DIVIDER
FLOW
VALVE
DIVIDER
HIGH PRESSURE
PUMPS
OPERATING OPERATING STANDBY
FLOW UNLOAD EMERGENCY
CONTROL RELIEF LUBRICATION
VALVE VALVE CIRCUIT
HEATERS
HEATER
ACCUMULATOR
© ABB Industries - 25
CHARGE/ RUNDOWN
SETTLING RETURN CONDITIONED
PUMP
COMPARTMENT COMPARTMENT COMPARTMENT
Brake system
Subsystem
Hydraulic system brake
Reservoir system brake
Caliper system brake
© ABB Industries - 26
MV (Medium Voltage) system
Subsystem
Disconnect system stator
Main circuit breaker stator (controlled by PSR)
Stator transformer 1
Stator transformer 2
Stator transformer 3
© ABB Industries - 27
MV (Medium Voltage) system
23kV / 50Hz / 3ph -15/+5% Legend
380V / 3ph / 50Hz
1. MCC LV Power Supply
Client Proxy Server 2. Synchronisation Transformer HV Supply
125VDC
MCC-supplied
Air condition UPS 24. Main Breaker Control and Supervision
redundant 40 System
Supply 25. Stator Transformer 1 Supervision
+F14
40
26. Stator Transformer 2 Supervision
MCC +CA +CB +CC
27. Stator Transformer 3 Supervision
+F05...+F08 PSR +F02 PLC Video Monitoring 28. Serial Interface PSR to PLC (RS 232 / DH+)
30
Control & Regulation +F03 System +F04 29. Motor Winding temperature Supervision
Water inlet / outlet temp. supervision by PT100
Cyclo-Converter 12-Pulse 30. Cycloconverter control & supervision
16 Excitation 31. Cycloconverter Recooling System
+F01 Cycloconv.Recooling Supervision
19 redundant 31 28 32. Mill Lubrication system Supervision
+F15 VMS Tower Data Logger
33. Excitation converter control
33 34. Air Gap Supervision
35. Air temp., water flow/ leakage, filter superv., dust
sealing
14 15 36. Interconnection MLCB to PLC
21 E-House
37 Arcnet Interface MLCB to PSR
42 38. Interface PLC to DCS
39. Serial Interace VMS to PLC
Knife switches 39a.Serial Interace VMS to Monitor in DCS
34 37 40. UPS Power Supply (PSR,PLC, VMS)
17 36 41. Mill Brake Control & Supervision
2 x Make up Fan
V
Ringmotor W
water leakage
U MLCB
dust sealing
Y
PT100
9x Probe
exchanger
Excitation
Box
M 44. Transformer Differential Protection
Heater
air gap
35
DF1(Allen Bradley) or Modbus
32
20
© ABB Industries - 28
Subsystem
Disconnect system rotor
Excitation transformer
Excitation control
© ABB Industries - 29
Cycloconverter System
Subsystem
Power part
Recooling unit
Control & supervision
© ABB Industries - 30
Ringmotor system
Subsystem
Knife switches
Motor space heater
Overpressure air fans
Main motor fans
Motor winding temperature
Air gap monitoring
Motor local control box
© ABB Industries - 31
E- House
Subsystem
Air condition system
Fire fighting system
UPS system
MCC system
Lighting system
© ABB Industries - 32
System Operation
General
Main circuit breaker stator
Disconnect switch rotor
Cycloconverter power part
Cycloconverter cooling system
Knife switch stator
Knife switch rotor
Lubrication system
Brake system
Ringmotor auxiliary system
Ringmotor
© ABB Industries - 33
Modes
Remote Mode
Normal mode of operation for SAG/ BALL mills.
Mill will be controlled by clients DCS.
E- House Mode
This mode will be provided mainly for commissioning or in case
of adjusting of regulation parameter/ measuring values for
optimizing the system.
MLCB Mode
This mode will be provided for local operation. Mill will be
controlled by the control unit in front of the respective mill.
All local operation like: Mill Inching, Mill creeping, Mill manual
lowering etc will be executed in this mode
© ABB Industries - 34
Mode
PRIORITY 1: PRIORITY 2:
CONTROL DCS CONTROL MLCB
REMOTE = 0
REMOTE
?
RE S ER VE
DCS
DCS/ E-
MLCB HOUSE
1 7 5 6 -L 5 5 M 1 4
1 7 5 6 -P A 7 2
1756-ENET
MLCB
I/O Boards
1756-MVI
E-
HOUSE
PLC I/O INTERFACE
NO PRIORITY:
CONTROL E- HOUSE
CONTROL E- HOUSE
ABB ARCNET
1756-ENET
I/O Boards
1756-MVI
PSR Controller
Physical Connections
© ABB Industries - 35
Signal Flow
Start-up sequence
Start auxiliary drives
Step 1.1 Start cycloconverter cooling system
Step 1.2 Start lubrication system
Step 1.3 Activate brake system
Step 1.4 Start ringmotor auxiliary system
During operation the motor will get the reference value from
selected control location. The drive will follow the reference
speed value as best as possible. Under extreme high load
condition's the regulation principle of the drive permits an
permanent offset between actual and reference speed. The drive
keeps running until reaching the overload current setting.
All systems will be supervised by the drive Controller/PLC
controller to act in case of any Alarms/ Faults
© ABB Industries - 37
Shutdown sequences
Normal stop sequence
Ringmotor
Lubrication system
Ringmotor auxiliary drives