Professional Documents
Culture Documents
User’s Manual
DIVISION ATD
User's Manual
for
Cycloconverter Power Part
Plant: SOSSEGO
ABB Schweiz AG
Order No.: 1-9 500 497
Issued: 18.07.01 / Frei Change: Off. resp.: ATDE Doc.-type Language Format Page No of
pages
Check. 1: 18.07.01 / Erne A Rec. off.: UM E A4 1 62
Check. 2: - B Der. from:
Released: 25.06.03 / Imboden C Replaces: 3BHS 130 197
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express
authority is strictly forbidden. ABB Schweiz AG
User’s Manual - SOSSSEGO - ABB Schweiz AG Order No. 1-9 500 497
Notice
In case of fire
High voltage!
Toxic Gases!
Overheating!
Content
1. Introduction .......................................................................................................................................6
1.1 Why You Should Read this Manual ....................................................................................................6
1.2 How to Read The ‘User’s Manual’.......................................................................................................7
1.2.1 Safety Instructions ...........................................................................................................................7
1.2.2 Scope...............................................................................................................................................8
1.2.3 User Group of the ‘User’s Manual’...................................................................................................8
1.3 How to Use the ‘User’s Manual’ ..........................................................................................................8
1.3.1 All Information on Operation, Trouble Shooting, Maintenance, Technology, Quality and Safety in
One Manual ..................................................................................................................................................8
1.3.2 Copyright..........................................................................................................................................8
1.4 Quality .................................................................................................................................................9
1.4.1 ABB’s Quality Management Philosophy ..........................................................................................9
1.4.2 ABB Schweiz AG Switzerland Meets ISO 9001 and ISO 14001 Requirements ..............................9
1.4.3 National and International Certificates .............................................................................................9
1.4.4 European and International Standards ..........................................................................................10
1.4.5 International Standards for Design and Construction ....................................................................11
3. Commissioning ...............................................................................................................................22
3.1 Safety Instructions.............................................................................................................................22
3.2 Why You Should Read this Chapter .................................................................................................24
4. Decommissioning ...........................................................................................................................29
4.1 Safety Instructions.............................................................................................................................29
4.2 Why You Should Read this Chapter .................................................................................................29
4.3 Converter Standstill...........................................................................................................................29
4.4 Converter Intermediate Storage........................................................................................................30
4.5 Dismantling the Converter and Separation of Materials....................................................................30
4.6 Disposal and Recycling.....................................................................................................................30
5. Operation .........................................................................................................................................31
5.1 Safety Instructions.............................................................................................................................31
5.2 Operation Instructions .......................................................................................................................31
5.2.1 General Configuration -VERITHYR WXM......................................................................................31
5.2.2 Field of Application and Main Features..........................................................................................32
5.2.3 Operation .......................................................................................................................................34
5.3 Trouble Shooting and Maintenance ..................................................................................................35
5.3.1 Trouble Shooting converter power part and cooling unit in general...............................................35
5.3.2 Trouble Shooting converter power part..........................................................................................36
5.3.3 Trouble Shooting Cooling Unit .......................................................................................................37
5.4 Care and Service ..............................................................................................................................40
5.5 Replacing of components of the converter power part......................................................................40
5.6 Replacement of Cooling Parts ..........................................................................................................41
5.6.1 Changing the Resin Filling in the Deionizing Devices KT001 or KT002 (if available) .....................42
5.6.2 Replacing the level sensor.............................................................................................................42
5.6.3 Replacing the pressure sensor CP001 or CP002 ..........................................................................43
5.6.4 Replacing the conductivity measuring device CD001 or CD002 ...................................................43
5.6.5 Replacing the temperature sensor CT001 or CT002 .....................................................................44
5.6.6 Replacing the flow transmitter ‘Bürkert’ Type 8025, CF001...........................................................44
5.6.7 Replacing and cleaning the strainer KT011 ...................................................................................45
5.6.8 Filling or refilling deionized water circuit ........................................................................................45
5.6.9 Replacing the pump .......................................................................................................................46
5.7 Maintenance Heat Exchanger...........................................................................................................46
5.7.1 Opening the heat exchanger..........................................................................................................46
5.7.2 Taking out the plates .....................................................................................................................47
5.7.3 Cleaning the plates ........................................................................................................................47
5.7.4 Gaskets..........................................................................................................................................48
6. Technology ......................................................................................................................................53
6.1 Technical Facts about the Converter ................................................................................................53
6.1.1 Identification...................................................................................................................................53
6.2 Dimensions and Specifications .........................................................................................................54
6.2.1 Power Converter Section ...............................................................................................................54
6.2.2 Cooling System..............................................................................................................................55
6.2.3 Identification Cooling Unit ..............................................................................................................56
6.3 Description of Essential Components ...............................................................................................57
6.3.1 Thyristors .......................................................................................................................................57
6.3.2 Thyristor Monitoring PCB (Printed-Circuit Board) ..........................................................................57
6.3.3 Pulse Transformers........................................................................................................................57
6.3.4 Snubber Circuit ..............................................................................................................................57
6.3.5 Overvoltage/Surge Protection........................................................................................................57
6.3.6 Base Load......................................................................................................................................58
6.3.7 Short-Circuiter................................................................................................................................58
6.3.8 Current and Potential Transformers...............................................................................................58
6.4 Inspection and Service Program for Converter and Water Cooling Unit ...........................................59
6.4.1 Overview ........................................................................................................................................59
6.4.2 Inspection Program for converter...................................................................................................59
6.4.3 Inspection Program for Cooling Unit ..............................................................................................60
6.4.4 Service Program Cooling Unit........................................................................................................61
6.5 Drawings ...........................................................................................................................................62
1. Introduction
Notice
The safety instructions always appear at the beginning of each chapter, paragraph and/or sub-paragraph.
The safety instructions are divided into five categories and emphasized by the use of the following safety
signs on the left side of the page:
1.2.2 Scope
The 'User's Manual' is considered as an integral part of the delivery of the VERITHYR WXM. The 'User's
Manual' contains all information and instructions required for the safe and correct operation of the
VERITHYR WXM.
The 'User's Manual’ is directed primarily to the converter operator, the maintenance personnel and the
personnel in charge of transport, storage, erection and commissioning. They should have sufficient
electrotechnical or technical knowledge and experience.
This manual provides all information and instructions for properly operating the converter. If you need
further information on a specific aspect, cross-references are given to easily find out the required
information. Always keep this manual at the operator's working place.
1.3.2 Copyright
ABB Schweiz AG reserves all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
1.4 Quality
Customer satisfaction is one of the preconditions for ABB's continuous growth and success. For this
reason ABB's quality management philosophy focuses on fulfilling customer's needs to the highest extent.
ABB's quality management is based on
1.4.2 ABB Schweiz AG Switzerland Meets ISO 9001 and ISO 14001 Requirements
Total quality management, time based management and supply management are the basic elements for
the leading position ABB holds worldwide in quality aspects. Every two years ABB Schweiz AG,
Switzerland has to pass the Quality System Review done by an external group of experts in order to
assure the high quality standards. The quality management of ABB Schweiz AG, Switzerland meets all
requirements of ISO 9001and ISO 14001.
In accordance with ABB's quality management philosophy ABB Schweiz AG has been awarded the
following quality management certificates:
The converter's design corresponds to the relevant common security standards as defined in all member
states of the European community as precondition for exporting the products within the EEC.
- Council Directive of June 1989 on the approximation of the laws of the Member States relating to
machinery (89/392/EEC)
- Council Directive of June 1989 on the approximation of the laws of the Member States relating to
machinery (89/392/EEC) Annex 1: Essential health and safety requirements relating to the design
and construction of machinery
- Council Directive of 19 February 1973 on the harmonization of the laws of Member States
relating to electrical equipment designed for use within certain voltage limits (73/23/EEC)
- Council Directive of 3 May 1989 on the approximation of the laws of the Member States relating to
electromagnetic compatibility (89/336/EEC)
The most important standards for the design, the construction and the test procedures of the ABB
Schweiz AG converters are:
- DIN/EN 60204
Safety of machinery - Electrical equipment of machines;
Part 1: General requirements
- EN 292
Safety of machinery: Basic concepts, general principles for design
- IEC 439
Low voltage switchgear and control gear assemblies
- IEC 694
Common clauses for high-voltage switchgear and controlgear standards
- DIN/VDE 0110
Insulation co-ordination for equipment within low-voltage systems;
Fundamental requirements
- DIN/VDE 40008
Electrical engineering; safety signs; survey
- DIN 55402
Marking for shipping of packages; directive for export packaging
- ISO 780
Packaging - Pictorial marking for handling of goods
2.1 Transport
2.1.1 Safety
!
Do not step on the top side of the converter
Notice
For transport and loading, the converter must always be in an upright position.
The transport conditions are defined on the basis of IEC 721-3-2 'Classification of environmental
conditions; Part 3: Classification of groups of environmental parameters and their severities;
Transportation'.
Pay attention to always fulfill the following environmental conditions inside the converter during transport:
2.1.3 Packing
Packing must be, so that the transport conditions according to IEC 721-3-2 can be conformed with.
For loading and unloading the converter with the help of a lifting gear follow the instructions set out below.
See drawing 3BHS 126 277. Be sure to strictly observe the environmental conditions.
!
Do not step on the top side of the converter
Notice
Always store the converter in an upright position.
The minimum requirements for storage are defined on the basis of IEC 721-3-1 'Classification of
environmental conditions; Part 3: Classification of groups of environmental parameters and their
severities; Storage'.
Pay attention to always fulfill the following environmental conditions during the storage period:
2.2.3 Preservation
Take the following measures, if you want to store the converter module for one year. In case of a longer
storage period contact ABB service organization.
During the storage period you should control the storage conditions and the condition of the converter
every month. For this reason check the condition of the packaging. Pay attention to damages caused by
mechanical forces, water/humidity and heat/fire.
If the packaging is damaged or you find damages caused by water/humidity or heat/fire you have to
unpack the converter and to check its condition outside and inside. Before storing the converter once
again all damages have to be removed. Preserve the converter as described above under paragraph
2.2.3.
2.3 Erection
!
Erection
You could be injured and the converter could be damaged if you try to do Installation work
without knowing enough about it. Be sure you have sufficient knowledge, experience, and the
proper tools before you attempt any converter Installation task.
Note: For defining the exact location of the foundation and the minimum distances refer to the installation
plan 3BHS 126 278.
- non-abrasive
- protected against humidity, dust and entrance of animals
- protected against fire extension
! Important: All openings have to be well covered/sealed to prevent possible fire from extending
into the converter.
! Important: Be sure that all cable and water pipe inlets / outlets are protected against the
entrance of dust, humidity and animals.
1. Place the converter exactly on the prepared foundation and tighten all fixing screws.
3. Mark the location of the cable glands on the bottom shield. Be sure the cable glands diameter exactly
fits the cable diameters.
4. Remove the bottom shield, prepare the cable glands openings and mount the cable glands.
! Important: Be sure that there is no mechanical stress acting on the cables and the cable
terminals.
! Important: Observe the different torques for power cable connections as set out below
(specification of screws: ST-NR A2-70)
! Important: Pay attention to correct power and signal cable placing in order to prevent
interferences.
Notice
Never use blank aluminum cable lugs in combination with copper bars.
This material mix could cause corrosion and damage the converter.
Use nickel-plated aluminum or copper cable lugs.
a) HV and LV cables:
- temperature range from -55°C to +120°C
- halogen-free
- flame retardent
- cable cross section according to the operating current and installation conditions
- shielded cables for signal and control connections
b) Grounding cables/bars:
- cross section min. 2 x 150 sq. millimeters
6. Fix the bottom shield and pull the cables through the cable glands. Tighten the gaskets.
7. Test the insulation (for all power and control cables) and fill out the test report (necessary for
commissioning). The insulation tests have to be performed with the following test voltages (IEC 146-
1-1):
Test Voltage / Low Voltage
UM / √2 Test Voltage
≤ 60 V 500 V
≤ 125 V 1000 V
≤ 250 V 1500 V
≤ 500 V 2000 V
Test Voltage / Medium Voltage
Line Voltage [kV] Impulse Voltage [kV peak] AC Voltage [kV rms]
(1,2 µs / 50 µs) (power frequency)
0,5 < ULN ≤ 1,1 not applicable 1 + 2 UM / √2
1,1 < ULN ≤ 3,6 not applicable 1 + 3 UM / √2
3,6 < ULN ≤ 38 15 + 3 UM / √2 1 + 1,8 UM / √2
8. Connect the power and earthing cables/bars according to diagram 3BHS 126 278.
9. Fix all information plates, safety signs and protection shields according to diagram
3BHS 126 276.
2.6 Mounting the pipe connections
Change Language Sheet Nr.
Customer’s flange facings and bolting provisions must matched to the flange facings of the
Cycloconverter cooling circuit.
Customer’s tubing must not cause any mechanical stress on the Cycloconverter tubing.
Prior to connection to the Cycloconverter cooling circuit, customer’s tubing must be well cleaned and
flushed.
Insertion torques for flange-joint bolts with PN16. Bolt material quality: 4.6.
! Important: Do not hesitate to inform the local ABB service organization about problems and
difficulties during erection work.
3. Commissioning
High Voltage
Danger !
1. High voltage in the high voltage room!
2. Never remove the protecting shields.
3. Before you attempt any converter maintenance task:
- switch off the converter
- disconnect the converter from the main power supply (circuit breaker controlled by customer)
- take steps against unintentional energizing
- check that HV has disappeared
- be sure the converter is disconnected from all machine side power supplies.
4. Be sure there is no high voltage at the incoming bars (transformer side) and at
the outgoing bars (motor side) before you attempt any earth connection.
5. Connect the incoming bars (transformer side) to earth by operating the earthing isolators
according the diagram on the following page.
6. Connect the outgoing bars (motor side) to earth by operating the earthing isolators according the
diagram on the following page.
!
High temperature
Danger of burning
!
Commissioning
Only specially trained ABB personnel is qualified to perform the commissioning work.
Do not try to do commissioning work on the converter. You could be hurt and the converter could
be damaged.
3.3.1 Preconditions
- the raw water circuit of the converter must be connected, checked and commissioned
- deionized water must be available for the converter-internal closed water-circuit (about 300 liters for
each converter)
Preparatory work:
! Important: All auxiliary tools to be used for the filling procedure (e.g. pump, hoses, tank for
the deionized water) must be thoroughly cleaned and rinsed with deionized
water. The water penetrating through openings and venting valves during the
filling procedure must not be used anymore.
a) Make available deionized water of a conductivity of less than 20 µS/cm in an appropriate vessel next
to the converter cubicle (for the quantity refer to the enclosed data sheet).
b) Rinse well the filling accessories - e.g. pump and hoses - with deionized water. Connect the hose to
the filler valve KA101 and prepare the tube connection to the vessel with the de-ionized water as well.
! Important: Proceed with extreme cleanness in order to prevent the deionized-water cooling
system from getting dirty.
Filling Procedure:
c) By means of a pump, slowly fill-in water through the cock until the deionized water penetrates
from the expansion-tank overflow.
Note: If no pump is available, the deionized water can be filled into the cooling system at the vent
plug of the expansion tank.
Note: While filling, repeatedly vent the cooling system carefully by means of all venting devices in the
power converter cooling system (i.e. the screw plugs at the water-distributing resp. water-collecting
tubes) as well as at vent and fill ball valves.
d) Make pump KP001 run shortly (≤ 3 sec) to make the de-ionized-water flow within the cooling
system. Then continue to fill in.
! Important: Prior to the first pump start, the pumps shall be vented at their vent plugs (if
existing)
Repeat this procedure until the liquid level in the expansion tank remains constant and no more
big air bubbles appear (can be heard by the sound the pump makes).
e) Repeat same procedure as d) with pump KP002 (if installed).
f) Make the deionized water circulate for approx. 24 hours, then turn-off the pump and pump out
the first water filling.
Note: The first water-filling procedure serves to clean the cooling system and to remove any dust
deposits within the tubes.
h) Slowly fill-in water a second time. Proceed as described under c), d) and e).
k) Leave this position until there is no more air in the bypass circuit (observe floating-body flow
meters). Fill in more water if necessary.
l) With the pump operating adjust the cock valves KA050 in such a manner that the flow rate
according to the enclosed list of set points is reached.
m) Check the water level in the expansion tank after the air has been completely eliminated (after
approx. 24 hours)., Fill in more water if necessary.
1. Check the condition of the converter with regard to transport or erection damages.
2. Check the external cable connections according the converter installation diagram 3BHS 126 278
and the erection instructions with regard to
- position;
- shielding incl. earthing;
- earthing;
- polarity;
- tightness of water cooling system.
3. Check that all terminals are properly tightened, completely and properly mounted.
4. Check that the space between the cable bundles and the cable glands is well sealed.
The operation check with high voltage applied, has to be performed by ABB Schweiz AG personnel only!
1. Check the condition of the converter with regard to transport or erection damages.
2. Check the external cable connections according the converter installation diagram 3BHS 126 278
and the erection instructions with regard to
- position;
- shielding incl. earthing;
- earthing;
- polarity;
- tightness of water cooling system.
3. Check that all terminals are properly tightened, completely and properly mounted.
4. Check that the space between the cable bundles and the cable glands is well sealed.
Check the motor/converter interface: HV cables and excitation cables connected properly according to the
diagram 3BHS 126 278.
The operation check has to be performed by ABB Schweiz AG, personnel only!
4. Decommissioning
!
Decommissioning
You can be injured if you try to do decommissioning work on the converter without knowing
enough about it. Be sure you have sufficient knowledge, experience, and the proper tools before
you attempt any converter decommissioning task.
2. Protect the converter against dust, humidity, dirt, and other detrimental influences.
4. Do not drain the cooling system. Ensure that the water will be circulated through the pumps every
2 (two) weeks for 2 (two) hours.
! Important: Before removing the external cable connections switch off all power supplies.
5. Operation
High Voltage
Danger
Always close the doors at normal operation!
Excitation
Cooling
M
3
They are mainly used in electric drive technique for supplying variable-speed three-phase motor drives
and, in general, for those plants, which require conversion from a.c. to d.c. current or vice versa within a
certain current/voltage range.
Besides current conversion, with VERITHYR WXM also a.c. power regulators and several other functions
can be realized (with appropriate constructive matching).
One of the main features of VERITHYR WXM series is the possibility of connecting 1 to 6 thyristors in
series per branch. A direct parallel connection of thyristors is not envisaged (for this, the air-cooled ABB-
series THYRIBLOC L is specially suited). However, two or more VERITHYR WXM can be connected in
parallel, if current ratings require.
Another appreciable feature of the VERITHYR WXM series is the application of the ABB high-capacity air
coolers for thyristors, which even for the largest thyristors will ensure sufficient cooling and hence -
compared with conventional coolers available on the market - will effect less temperature rise and thus
higher operational reliability for the same current loading.
This ‘User’s Manual’ deals with the VERITHYR WXM power converter.
Note: The expected lifetime of theVERITHYR WXM is defined as the time during which the converter will
remain suitable for the application for which it was made, provided that it is used, regularly inspected and
serviced in accordance with the manufacturer’s instructions, and provided that lubricants and parts, which
are subject to mechanical wear, are replaced regularly.
The converter is installed in a container cabin for outdoor installation. Access shall only be allowed to
authorized personnel.
Be sure that all converter doors are accessible. Never install anything inside or outside to the converter
block. Never cover it for protection grids.
Pay attention to always fulfill the following environmental conditions for properly operating the converter:
The minimum requirements for stationary use are defined on the basis of IEC 721-3-3 'Classification of
environmental conditions; Part 3: Classification of groups of environmental parameters and their
severities; stationary use at weather protected locations'.
!
Heart Pacemaker
The converter can influence the working of heart pacemakers. Be sure you have installed the
safety sign (part of the delivery) at a minimum distance of 6000 mm / 20 feet!
5.2.3 Operation
Perfect operation of the ABB inverter power section will be guaranteed as long as the data specified on
the rating plate as well as in the data sheet are observed.
! Important: Correct working of control electronics and cooling is a prerequisite for trouble-
free operation.
The powering up and the powering down (switching ON and OFF) procedures as well as various
annunciations, their consequences and the application of the disturbance recording are outlined in the
control system "operation manual".
! Important: Prior to commencing any works on the converter, ensure that the plant is switched
OFF and the converter is grounded.
! Important: 1. The converter power part as well as the cooling unit faults and malfunctions
and the result (T = trip / A = alarm) are indicated at the converter control
display.
2. For more information about dealing with faults and the RESET function and in
case of troubles, refer to the separate operating and trouble shooting manual of
the control electronic.
Drive switch OFF Defective semiconductor. Check of blocking Replace all thyristor of a stack.
caused by an resp. barrier capability For detail ionformation see
overcurrent in the in order to localize sep. manual in the replace
converter. defective thyristor. tool box.
Detailed converter fault finding and trouble shooting,, refer also to the "operation manual" of the control
electronics.
A = Alarm
T = Trip
- Clean dirty components. Do not clean plastic parts with solvents. Remove dust and dirt gathered of
the semiconductor parts by means of a vacuum cleaner.
- Check all faston plug terminals for firm seats (they must be latched).
2. Mark all electrical and mechanical connections before disassembly for proper installation of the
spare part.
4. For replacing a thyristor please use the special tool set (‘User’s Information’ included).
2. Mark all electrical and mechanical connections before disassembly for proper installation of the
spare part.
5.6.1 Changing the Resin Filling in the Deionizing Devices KT001 or KT002 (if available)
Note: The resin filling can be change with the cooling system in operation.
2. Switch out the exhausted deionizer-bottle and switch on the other. Coupling to resin-bottle with
bayonet-coupling, both male and female are close on decoupling.
3. Open the valves KA050 slowly. Control the vent drains. Control the waterlevel in the expansion
tank.
5. Replace the complete bottle or open the exhausted bottle and replace the resin.
Note: Pay attention to the tube joints, so that the input and the output tube joints of the deionizer bottle are
not mixed up.
7. Check after 1 to 3 hours, whether the water conductivity has improved visibly.
With the points 1, 2 and 3 fulfilled, no special procedures are to be considered during the replacement.
Take care that no tools or objects can fall through the sensor opening into the expansion tank.
Disconnect electrical wiring with plug. Close the stop valve KA015 before the pressure sensor. Screw the
pressure sensor off (note: left-hand thread).
Together with the new pressure sensor, a new sealing washer shall be mounted. Grease the thread of the
sensor slightly with silicone grease. When the new pressure sensor is mounted, open the stop valve
slowly and vent the sensor socket.
Disconnect electrical wiring with plug. Close the ball valve KA050 slowly and switch out bayonet-coupling
from resin-bottle KT001 (both male and female are closed on decoupling).
! Important: When transmitter screw out, the water between the pipe parts KA050 resin bottle
flows out.
Replace the conductivity transmitter as follows: Then connect it to the power supply.
For the adjustment of the new conductivity measuring device refer to the supplier’s specific manual.
Disconnect electrical wiring. Remove the temperature sensor from the immersion.
Note: For the replacement of temperature sensors, the water system must not be opened.
Replace the flow transmitter as follows: Then connect it to the power supply.
From bottom, the air in the system will be pressed automatically out.
With the points 1, 2 and 3 fulfilled, close both the ball valves before and behind the pump. Loosen the
flanged joint (note: collect the several litters of draining water in an vessel).
Note: Since a pump weights more than 20 kg, use a lifting device to remove and replace it.
• Installation of a new pump: For the installation of a new pump follow the description.
Check the direction of rotation of the pump by starting the pump shortly. If necessary, change the
electrical connections of the phases S and T. Caution: Disconnect power supply first!
!
The plate edges are sharp!
Use gloves!
If two or more plates have stuck together they must be separated carefully so that the gaskets are kept on
the correct plate.
The plates support each other in pairs. If a plate has been so damaged that it must be taken out and
cannot be repaired or replaced with an identical one, its adjacent plate must also be taken out of the
exchanger.
If the number of plates are changed, so is the thickness of the clamped plate pack, A.
Special plates, such as the first and last plates, and turning plates in multipass heat exchangers, must be
replaced with identical plates.
!
Sodium Hydroxide / Concentrated Nitric Acid
Sodium Hydroxide and concentrated Nitric Acid can seriously harm the skin and mucous
membranes!
The solution must be handled with the greatest care!
Always wear protective goggles and protect hands with rubber gloves!
Fouling of the plate heat exchanger often depends on the flow velocity through the heat exchanger being
too low. Where the possibility exists to increase the flow, this should be tried out if the heat exchanger
shows signs of reduced capacity or increased pressure drop.
However, with products that crystallize of heavily foul the plates or if the heat transfer surfaces have been
scorched, opening and cleaning the heat exchanger is necessary.
5.7.4 Gaskets
A gasket that has come loose, either partly or entirely, must be glued in place. If only a short length has
become detached, glueing can be carried out immediately before clamping, with the plate still sitting in the
frame. If the entire gasket has become detached, the plate should be taken out to the heat exchanger.
Only certain glues may be used for glueing gaskets, namely Bostik 1782, 3M EC 1099. Bond Spray 77 or
Pliobond 20/30 Synthetic glue. Do not use other types of glue, they may contain chlorine or other
substances that attack the plate material. To facilitate application with a brush, The glue should be diluted
with acetone. Maximum dilution 1:1.
Clean the plates from residues of old gaskets. Small patches of glue, hard to remove, that are securely
stuck to the gasket groove may remain there. They provide an excellent foundation for the new gasket.
Wash the gasket groove so that it is completely free of oil and other greasy substances, using a rag and
acetone or other solvent not containing chlorine compounds. Then let the plate dry off.
5.7.10 Assembly
Before the heat exchanger is assembled, inspect all gaskets and surfaces that lie against the gaskets.
Particles that may jeopardize the integrity of the seals or damage the gaskets or sealing surfaces must be
removed. Note that contaminants usually collect at the lower part of the plates.
Plates that have been provided with new gaskets must be checked to make sure that the gaskets are in
the correct gasket groove. The correct gasket groove in used plates usually has a different color from the
rest of the plate due to residues of old glue. Also check the 1/2 thickness gaskets on the fist and last
plates.
Notice
Example:
A plate heat exchanger UFX-12 has a total of 51
plates in the pack. The tightening length of the pack
is: 51 x 3.4=173.4 ± 3 %.
Note:
With large plate packs the A-dimension, due to
tolerance in the plate thickness and depth of
pressing, can deviate somewhat from that given
above ± 3 %. With the correct a-dimension the
plates lie in metallic contact with each other. Check
this by examining the plate edges around the heat
exchanger. Further compression can deform the
plates.
5.7.13 Lubrication
The tighten bolts must be kept lubricated with molybdenum disulfide or its equivalent, particularly on the
sections of thread used for opening and closing the equipment.
6. Technology
Design Data
Technical Data
Cyclo Input
Phases 6 x 3-phase
Apparent Power 6 x 6070 kVA
Voltage (per phase) 1620 V
Current (rms) 2163 A
Frequency 60 Hz
Cyclo Output
Apparent Power 21 005 kVA
Voltage 0…4950…4950 V
Current (rms) 2450 A
Frequency 0 ... 5.574…6.18 Hz
Phases 3-phase
Excitation Input (AC)
Voltage 600 V
Current 441 A
Frequency 60 Hz
The principal element of the converter, the thyristor, is clamped between coolers each. The coolers and
the thyristors are mounted one upon the other in order to form stacks. A spring package mounted topmost
of each stack determines the clamping force exerted on the thyristors within the stack.
The stacks are mounted side by side in the center of the cubicle, dividing it into a front section and a rear
section.
The cooling-water distribution piping: It serves for distributing the cooling water (inflow and return) and for
connecting the deionized cooling-water circuit.
Electro-magnetic pulse transformers as well as are fitted each to the right and left of its corresponding
thyristor.
Components of snubber circuits: A snubber circuit comprises a capacitor and a water-cooled resistor.
The components of the semiconductor overvoltage protection (protection against commutation and
switching-voltage surges) are arranged partly on separate plates.
The power terminals as well as the voltage and current transformers, if applied, are situated in the rear of
the cabinet.
Shielded cables connect the separate terminals of the VERITHYR WXM thyristor-firing system directly
with the corresponding terminals of thyristor control electronics.
The cooling unit serves to remove the heat losses produced in the power section. The heat losses are
dissipated by means of a water-to-water heat exchanger from the deionized-water cooling system to a
raw-water cooling system.
The enclosed cooling diagram shows the deionized-water cooling system of the power converter and
‘Datasheet Cooling Unit’ (see next page) gives the main data about the cooling system. The installed
pump KP001 makes the deionized water circulate in the cooling system.
The deionizer facilities KT001 ensure a constantly low water conductivity of the deionized water. The
water conductivity is measured by the conductivity probes CD001.
The flow-monitoring and -indication devices as well as the temperature-monitoring devices are installed in
the deionized-water system in order to protect the power converter from overheating due to too warm
cooling water or a too low cooling-water flow.
For protection, commissioning and periodical checks of the cooling system the actual valve (water in- and
outlet temperature, water flow main circuit, pressure after pumps, water conductivity and water level in the
expansion tank) are transmitted to the converter control system.
The expansion tank QS001 containing deionized water under atmospheric pressure is located on the
highest point of the cooling system. Any decrease in the water level in the expansion tank QS001 caused
by a leakage or by electrolysis is signaled to the control system by the level monitoring devices which are
installed in the expansion tank. The expansion tank QS001 regulates the heat expansion and the de-
gassing of the deionized water.
To prevent the cooling circuits of the power converter from pollution during commissioning the deionized
cooling circuit is equipped with a strainer, KT011, which is removable for cleaning purpose.
Type C3N212
Cooling Capacity 140 kW
Pressure Drop
Cooler 38.58 kPa 38.36 kPa
Converter - 175 kPa
Pump Data
Motor Power - 5.5 kW
Electrical Data - 3 ∗ 480 V ± 10 %, 60 Hz, 9 A
To ensure optimum utilization of thyristors, the heat-loss power originating from the current through and
the voltage drop across the thyristors must be dissipated.
To achieve a sufficient heat dissipation, disc-type thyristors are clamped with a defined force between two
coolers each.
A thyristor monitoring PCB continuously checks the voltage over a pair of anti-parallel connected
thyristors. As long as a thyristor is able to block the voltage, the thyristor monitoring PCB generates a
signal, which is sent via an opticle-fibre cable to the valve-base electronics, which is located in the control
part.
In the case that one thyristor looses the blocking ability, the monitoring PCB stops signaling, which is
realized and indicated by the valve-base electronics.
The pulse transformers serve for galvanic isolation of the power circuits from the control circuits. The
pulse transformers are connected with the output stages in the control section by shielded cables.
The snubber circuits are RC circuits connected in parallel to each anti-parallel connection of two
thyristors. They damp the overvoltage generated during thyristor turn-off. The resistors of the RC
snubber-circuit are water-cooled.
The overvoltage protection protects the thyristors against overvoltages from the a.c. side (originating from
the hole-storage effect).
The base load consists of a number of capacitors and resistors, which, depending on the rating and the
required capacitance and resistance respectively, are suitably connected in parallel and/or in series.
These elements are mounted in the rear part of the cubicle, partly under the roof and partly to the rear
panel.
The base load ensure thyristor firing during start-up of the synchronous machine and prevents the
thyristors from overvoltages. It consists of a resistor in series with a capacitor, which are connected in
parallel to the load inductance.
6.3.7 Short-Circuiter
The short-circuiter is made of two antiparallel-connected BOD-protected thyristors in series with a resistor
pack. The components of the short-circuiter are mounted to the rear panel of the cubicle.
The short-circuiter is a protection against overvoltages occurring during switch-off of the synchronous
machine under load, at which the machine phases are shorted by means of the voltage-controlled short-
circuited in order to dissipate the magnetic energy of the machine windings into the resistor of the short-
circuiter.
For measuring purposes it is possible to install current transformers and/or potential transformers with
their associated automatic circuit breakers in the VERITHYR WXM.
6.4 Inspection and Service Program for Converter and Water Cooling Unit
6.4.1 Overview
Time interval Visual and Visual and Replacing the Replacing the Replacing the Changing all
mechanical mechanical resin filling of shaft seals of fans tubes in the
check Water check deionizer bottle pump cooling unit
cooling converter
Estimated time Estimated time Estimated time Estimated time Estimated time Estimated time
! Important: The converter is designed for operation under specific environmental conditions. If
the actual environmental conditions differ from the defined conditions contact your
local ABB service organisation.
! Important: Never change the sequence of inspection steps as set out below.
High Voltage
Danger
Follow the safety instructions!
1.1 Remove all dust carefully by the use of a vacuum cleaner. Never Notice
use the vacuum cleaner for PCB’s. Never use hot steam, compressed
Note: PCB's handle with care. Do not touch the printed circuits. Do air or chemical agents! This could
not use a vacuum cleaner. Remove dust with a smooth paint brush. cause a damage to the converter!
1.3 Check the cover grid (bottom and on the roof). If necessary clean it.
1.5 Check
- tightness of all 'Faston' connections
- tightness of all connections of terminal blocks
1.6 Check number and position of all safety instructions/signs mounted Ref. to diagram in the 'User's
inside the converter and outside the converter block; replace the Manual'
missing instructions/signs.
! Important: The converter is designed for operation under specific environmental conditions. If
the actual environmental conditions differ from the defined conditions contact your
local ABB service organisation.
! Important: Never change the sequence of inspection steps as set out below.
! Important : Switch on the low voltage power supply for the High Voltage
mechanical checks. Danger
Follow the safety instructions!
Replace the resin filling of the deionizer bottle according chapter 5.6 in this part of ‘User’ Manual)
Replace the shaft seals when installed a in-line centrifugal pump with shaft seals. Connected motor
pumps are maintenance-free.
6.5 Drawings