Professional Documents
Culture Documents
Regulators 95B PDF
Regulators 95B PDF
1:95B
W7512
¶ Compact ¶ Robust
TYPE 95BH
y
a lit ¶
e ci s Ve
e
Sp a s rs
¶ G at
ile
W7520
TYPE 95BL
D102682X012
06/99
Bulletin 71.1:95B
Introduction
The 95B Series bronze, direct-operated, pressure reducing regulators are designed to meet the needs of a variety
of specialty and demanding applications. These compact, large-capacity regulators are available in 1/2, 3/4, 1,
1-1/2, and 2-inch sizes (DN 15, 20, 25, 40, and 50) with NPT screwed end connections. They are designed to
handle pressures up to 350 psig (24,1 bar) and temperatures from -325° to 350°F (-198° to 176°C).
• Direct-Operated—The design
A6616
maximizes speed of response and
INLET PRESSURE minimizes maintenance requirements.
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
2
Bulletin 71.1:95B
• P1 = P2—Inlet pressure
rating equals outlet pressure
rating in Type 95BH up to 350
psig (24,1 bar).
A6554
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
Principle of Operation
The 95B Series (refer to figures 2 and 3) are direct- down and the disk away from the seat. This allows flow
operated, pressure reducing regulators. During normal through the body to the downstream system. Spring
operation, downstream pressure is registered internally force is used to regulate outlet pressure.
through the body to the underside of the diaphragm.
When the downstream pressure is at or above the set As the downstream pressure nears the set pressure,
pressure, the disk is held against the seat and there is the downstream pressure begins to overcome the
no flow through the regulator. spring force and pushes the disk towards the seat.
When pressure rises slightly above the setpoint, the
When demand increases, downstream pressure drops downstream pressure overcomes the spring force and
slightly allowing the spring to extend, moving the stem pushes the disk against the seat to stop flow.
3
Bulletin 71.1:95B
Specifications
Available Configurations Regulator Temperature Capabilities(1)
Type 95BL: Low-pressure regulator for 2 to 30 psig Nitrile (NBR) Parts: -40° to 180°F (-40° to 82°C)
(0,1 to 2,0 bar) outlet pressures Neoprene (CR) Parts: -40° to 180°F (-40° to 82°C)
Type 95BH: High-pressure regulator for 5 to 150 psig Fluoroelastomer (FKM) Parts:
(0,34 to 10 bar) outlet pressures 0° to 300°F (-18° to 149°C)
Body Sizes and End Connection Style(1) Teflon (PTFE) Parts: -325° to 350°F (-198° to 177°C)
Cast Iron Parts: -40° to 350°F (-40° to177°C)
Type 95BL: 1/2-inch (DN 15) body) NPT screwed 300 Series Stainless Steel Parts:
end connections -325° to 350°F (-198° to 177°C)
Type 95BH:1/2-inch (DN 15), 3/4-inch (DN 20), 400 Series Stainless Steel Parts:
1-inch (DN 25), 1-1/2-inch (DN 40), and 2-inch -40° to 350°F (-40° to 177°C)
(DN 50) NPT screwed end connections Bronze and Brass Parts: -325° to 350°F
Orifice Sizes (-198° to 177°C)
Type Y602-12 Vent: up to 180°F (up to 82°C)
1/2-inch body: 3/8-inch (9,5 mm)
3/4 and 1-inch bodies: 9/16-inch (14,3 mm) Construction Materials
1-1/2 and 2-inch bodies: 1-1/16-inch (27 mm) Body: Bronze (ASTM B61 Grade C92200)
Spring Case: Cast iron (A126 Class B) or Bronze
Maximum Inlet (Casing) Pressure(1) (ASTM B61 Grade C92200)
Type 95BL: 250 psig (17,2 bar) Diaphragm: Neoprene (CR), Fluoroelastomer
Type 95BH: 350 psig (24,1 bar) (FKM), S30200 Stainless steel, or Monel
Valve Plug (Metal Seat): Brass, S31600 Stainless
Maximum Allowable Operating Inlet Pressure(1)
steel, or S41600 Stainless steel
Type 95BL: 250 psig (17,2 bar) Valve Plug Guide: Brass
Type 95BH: 300 psig (20,7 bar) Disk (Elastomer Seat): Fluoroelastomer (FKM) or
Maximum Allowable Outlet Pressures(1) Neoprene (CR)
Disk Holder (Elastomer Seat): S31600 Stainless
Type 95BL steel or Brass
Bronze: 125 psig (8,6 bar) Orifice: Brass, S41600 Stainless steel or S31600
Cast Iron: 50 psig (3,4 bar) Stainless steel
Type 95BH: Stem Assembly and Pusher Post : Brass
Bronze: 350 psig (24,1 bar) Spring: Zinc-plated steel, Inconel or Stainless
Cast Iron: 250 psig (17,2 bar) steel (depending on spring range and/or application)
Outlet Pressure Ranges(1) Diaphragm Head Assembly: Aluminum or
S31600 Stainless steel
See tables 1 and 2 Spring Seat: Aluminum or S31600 Stainless steel
Flow Coefficients Adjusting Screws: Steel, or 18-8 Stainless steel
Bushings: Brass
See table 3
Gaskets: Composition, or Grafoil (Optional)
Regulating Capacities Valve Spring: S30200 Stainless steel
Air: See tables 4, 5 and 6 Bolting: Bronze Spring Case: Stainless steel
Water: See tables 7, 8 and 9 Cast Iron Spring Case: Grade 5 zinc-plated steel
Shutoff Classification Per ANSI/FCI 70-2-1975 R1990 Approximate Weight
Metal Seats: Class IV (standard) Type 95BL:
Elastomer Seats: Class VI or better 1/2-inch (DN 15) body: 18 lb (8,1 kg)
Teflon (PTFE): Class V Type 95BH:
1/2-inch (DN 15) body: 10 lb (4,5 kg)
Spring Case Connection 3/4 and 1-inch (DN 20 and 25) bodies: 20 lb (9,1 kg)
Cast Iron: 1/8-inch drilled hole 1-1/2 and 2-inch (DN 40 and 50) bodies:
Bronze: 1/4-inch NPT with Y602-12 vent 73 lb (33,1 kg)
1. The pressure/temperature limits in this bulletin and any applicable standard or code limitation should not be exceeded.
4
Bulletin 71.1:95B
Table 1. Outlet Pressure Ranges(1)
SPRING WIRE SPRING FREE
BODY SIZE, OUTLET PRESSURE RANGE,
TYPE SPRING COLOR SPRING PART NUMBER DIAMETER, LENGTH,
INCHES (DN) PSIG (bar)
INCHES (mm) INCHES (mm)
2 to 6 (0,14 to 0,41) Yellow 1E395627022 0.207 (5,26) 2.50 (63,5)
95BL 1/2 (15) 5 to 15 (0,34 to 1,0) Green 1D745527142 0.234 (5,94) 2.62 (66,5)
13 to 30 (0,90 to 2,1) Red 1E395727192 0.281 (7,13) 2.44 (62,0)
15 to 30 (1,0 to 2,1) Yellow 1E395627022 0.207 (5,26) 2.50 (63,5)
1/2 (15) 25 to 75 (1,7 to 5,2) Green 1E745527142 0.234 (5,94) 2.62 (66,5)
70 to 150 (4,8 to 10,3) Red 1E395727192 0.281 (7,13) 2.44 (62,0)
3/4 (20) 15 to 30 (1,0 to 2,1) Yellow 1E398927022 0.306 (7,77) 4.09 (104)
and 25 to 75 (1,7 to 5,2) Green 1E399027142 0.343 (8.71) 4.09 (104)
95BH
1 (25) 70 to 150 (4,8 to 10,3) Red 1E395727192 0.281 (7,13) 2.44 (62,0)
5 to 80 (0,34 to 5,5) Light blue 1E795327082 0.531 (13,5) 6.50 (166)
1-1/2 (40)
60 to 120 (4,1 to 8,3) Light gray 1E795427082 0.562 (14,3) 6.50 (166)
and
100 to 140 (6,9 to 9,7) Yellow 1E793327082 0.593 (15,1) 6.50 (166)
2 (50)
120 to 150 (8,3 to 10,3) Black 1P788827082 0.656 (16,7) 6.50 (166)
1. All springs can be backed off to 0 psig (0 bar).
Table 2. Special Control Spring Part Numbers for Corrosive and Other Severe Applications(1)
SPRING FREE
BODY SIZE, OUTLET PRESSURE RANGE, SPRING WIRE DIAMETER,
TYPE SPRING PART NUMBER LENGTH
INCHES (DN) PSIG (bar) INCHES (mm)
INCHES (mm)
2 to 6 (0,14 to 0,41) 1E3956X0012 0.207 (5,26) 2.50 (63,5)
95BL 1/2 (15) 5 to 15 (0,34 to 1,0) 1N642838992 0.243 (6,17) 2.50 (63,5)
13 to 30 (0,90 to 2,1) 17B2495X012 0.294 (7,47) 2.55 (64,7)
15 to 30 (1,0 to 2,1) 1E3956X0012 0.207 (5,26) 2.50 (63,5)
1/2 (15) 25 to 75 (1,7 to 5,2) 1N642838992 0.243 (6,17) 2.50 (63,5)
70 to 150 (4,8 to 10,3) 17B2495X012 0.294 (7,47) 2.55 (64,7)
3/4 (20) 15 to 30 (1,0 to 2,1) 1E3989X0012 0.306 (7,77) 4.00 (102)
and 25 to 75 (1,7 to 5,2) 1K762537022 0.375 (9,53) 3.88 (98.5)
95BH 1 (25) 70 to 150 (4,8 to 10,3) 11A8269X012 0.437 (11,1) 4.00 (102)
5 to 80 (0,34 to 5,5) 14B1802X012 0.531 (13,5) 6.50 (166)
1-1/2 (40) 60 to 120 (4,1 to 8,3) --- --- ---
and
2 (50) 100 to 140 (6,9 to 9,7) --- --- ---
120 to 150 (8,3 to 10,3) --- --- ---
1. All springs can be backed off to 0 psig (0 bar).
Capacity Data
The capacity information in tables 4 through 9 is based settings not given. To maintain accuracy, it is impor-
on two offset factors,10 and 20 percent. Offset (droop) tant when interpolating to stay within a spring range if
is the deviation from the setpoint of the regulator, and is possible. The following is a procedure for interpolating
usually stated in percentage of setpoint value. The the data to calculate flow:
setpoint is obtained at same minimum flow condition.
1. Determine which spring is to be used.
For highest capacity and the most accurate control,
use the lowest range spring that can be adjusted to the 2. Find the two outlet settings (P2a and P2b) that
desired setpoint. (See table 1 or 2 for part numbers of bracket the actual outlet pressure P2.
appropriate springs for each body size.) 3. For a given body size and inlet pressure, find the
If closer control is necessary, a regulator of larger ca- capacity Qa for P2a and Qb for P2b.
pacity or different design should be selected, so that 4. Use the following formula to determine the interpo-
the necessary flow can be obtained with a smaller lated capacity (Q).
offset factor.
Qb − Qa Qb − Q
Sometimes it may be necessary to interpolate the =
capacity table data to determine capacity for outlet P2b − P2a P2b − P2
5
Bulletin 71.1:95B
Table 3. Flow Coefficients For Non-Critical Pressure Drops
WIDE-OPEN
COEFFICIENTS
For pressure drops lower than critical (absolute outlet
BODY SIZE,
INCHES (DN) (FOR RELIEF SIZING) C1 Km pressure greater than one-half of absolute inlet pres-
Cg Cv sure), use the following formula:
1/2 (15) 67 1.9 35 0.71
520 3417 ∆P
3/4 (20), 1 (25) 156 4.4 35 0.67 Q= CgP1SIN DEG
1-1/2 (40), 2 (50) 475 12.5 38 0.82
GT C1 P1
where,
Q = gas flow rate, scfh
Note
G = specific gravity of the gas
The same interpolation procedure can be T = absolute temperature of gas at inlet, °Rankine
used for different inlet pressures. Cg = gas sizing coefficient
P1 = absolute inlet pressure, psia
An alternative method for interpolating capacities is to C1 = flow coeficient
back calculate the Cv provided in table 3. Contact your ∆P = pressure drop across the regulator, psi
nearest Fisher Sales Representative or Sales Office if
you have any questions about selecting the proper Then, if capacity is desired in normal cubic meters per
regulator. hour at 0°C and 1,01325 bar, multiply scfh by 0.0268.
Air Capacities
Regulating capacities at selected pressures and outlet
pressure flows are given in scfh (at 60°F and 14.7 psia)
and m3/h(n) (at 0°C and 1,01325 bar) of air. To deter- Table 4. Capacities in Air for Type 95BL 1/2-Inch (DN 15) Body
mine the equivalent capacities for other gases, multiply with Elastomer Diaphragm
the table capacities by the following appropriate
OUTLET OUTLET CAPACITIES IN SCFH
conversion factors: 1.29 for 0.6 specific gravity natural PRESSURE PRESSURE
INLET
PRESSURE, (m³/h(n)) OF AIR
gas, 0.810 for propane, 0.707 for butane, or 1.018 for RANGE, SETTING,
PSIG (bar) 10% Offset 20% Offset
nitrogen. For gases of other specific gravities, divide by PSIG (bar) PSIG (bar)
the square root of the appropriate specific gravity. 20 (1,4) 500 (13,4) 750 (20,1)
50 (3,4) 600 (16,1) 850 (22,8)
2 to 6
Capacities in tables 4, 5, and 6, are for regulators 5 (0,34) 100 (6,9) 700 (18,8) 900 (24,1)
(0,14 to 0,4)
200 (13,8) 700 (18,8) 900 (24,1)
using elastomer diaphragms. Depending on regulator 250 (17,2) 700 (18,8) 900 (24,1)
construction, a multiplier must be used to convert to 20 (1,4) 750 (20,1) 1100 (29,5)
capacities for regulators using metal diaphragms. 50 (3,4) 1000 (26,8) 1400 (37,5)
10 (0,69) 100 (6,9) 1000 (26,8) 1400 (37,5)
To determine wide-open flow capacity for relief valve 200 (13,8) 1000 (26,8) 1400 (37,5)
5 to 15 250 (17,2) 1000 (26,8) 1400 (37,5)
sizing, use one of the following equations:
(0,34 to 1,0) 20 (1,4) 800 (21,4) 1200 (32,2)
50 (3,4) 1300 (34,8) 1600 (32,9)
For Critical Pressure Drops 15 (1,0) 100 (6,9) 1400 (37,5) 1800 (48,2)
200 (13,8) 1400 (37,5) 1800 (48,2)
Use this equation for critical pressure drops (absolute 250 (17,2) 1400 (37,5) 1800 (48,2)
outlet pressure equal to one-half or less than one-half 30 (2,1) 1100 (29,5) 1500 (40,2)
50 (3,4) 1400 (37,5) 1800 (48,2)
the absolute inlet pressure). 20 (1,4) 100 (6,9) 1600 (42,9) 2100 (56,3)
200 (13,8) 1600 (42,9) 2100 (56,3)
13 to 30 250 (17,2) 1600 (42,9) 2100 (56,3)
Q = P1(abs)Cg (0,9 to 2,1)
50 (3,4) 2000 (53,6) 2700 (72,4)
where, 100 (6,9) 2400 (64,3) 3600 (96,5)
30 (2,1)
Q = gas flow rate, scfh 200 (13,8) 2500 (67) 3600 (96,5)
250 (17,2) 2500 (67) 3600 (96,5)
Cg = gas sizing coefficient
1. To obtain capacities for regulators using metal diaphragms, multiply the table values
P 1 = absolute inlet pressure, psia by 0.8.
6
Bulletin 71.1:95B
Table 5. Capacities in Air for Type 95BH 1/2 , 3/4 and 1-Inch (DN 15 , 20 and 25) Bodies with Elastomer Diaphragm
OUTLET OUTLET CAPACITIES IN SCFH (m³/h(n)) OF AIR
INLET
PRESSURE PRESSURE
PRESSURE, 1/2-Inch (DN 15) Body 3/4-Inch (DN 20) Body 1-Inch (DN 25) Body
RANGE, SETTING,
PSIG (bar)
PSIG (bar) PSIG (bar) 10% Offset 20% Offset 10% Offset 20% Offset 10% Offset 20% Offset
30 (2,1) 900 (24,1) 1400 (37,5) 2200 (59,0) 3100 (83,1) 2200 (59,0) 3300 (88,4)
50 (3,4) 900 (24,1) 1500 (40,2) 2900 (77,7) 4300 (115) 3400 (91,1) 5400 (145)
15 (1,0) 100 (6,9) 1400 (37,5) 2100 (56,3) 4000 (107) 6000 (161) 5400 (145) 8000 (214)
15 to 30 200 (13,8) 2200 (59,0) 2800 (75,0) 6000 (161) 8000 (214) 8700 (233) 11,700 (314)
(1,0 to 2,1) 300 (20,7) 2700 (72,4) 3300 (88,4) 7400 (198) 9600 (257) 10,000 (268) 14,000 (375)
50 (3,4) 1300 (34,8) 2100 (56,3) 4000 (107) 6000 (161) 4000 (107) 6600 (177)
100 (6,9) 2000 (53,6) 3000 (80,4) 6300 (169) 9800 (263) 7400 (198) 11,000 (295)
30 (2,1)
200 (13,8) 3100 (83,1) 4300 (115) 9200 (247) 12,000 (322) 12,000 (322) 18,000 (482)
300 (20,7) 4000 (107) 4900 (131) 10,000 (268) 14,000 (375) 15,000 (402) 21,000 (563)
75 (5,2) 1400 (37,5) 2300 (61,6) 6000 (161) 8600 (231) 6300 (169) 9600 (257)
100 (6,9) 2100 (56,3) 2900 (77,7) 7400 (198) 11,000 (295) 7000 (188) 13,000 (348)
50 (3,4)
25 to 75 200 (13,8) 3100 (83,1) 4600 (123) 11,000 (295) 17,000 (456) 15,000 (402) 24,000 (643)
(1,7 to 5,2) 300 (20,7) 3500 (93,8) 5100 (137) 12,000 (322) 18,000 (482) 19,000 (509) 27,000 (724)
100 (6,9) 2300 (61,6) 3700 (99,2) 8000 (214) 12,000 (322) 8700 (233) 13,000 (348)
75 (5,2) 200 (13,8) 3700 (99,2) 5500 (147) 14,000 (375) 21,000 (563) 17,000 (456) 28,000 (750)
300 (20,7) 4700 (126) 7100 (190) 16,000 (429) 25,000 (670) 23,000 (616) 35,000 (938)
125 (8,6) 3400 (91,1) 5800 (155) 8500 (228) 14,000 (375) 11,000 (295) 16,000 (429)
150 (10,3) 4000 (107) 6800 (182) 12,000 (322) 18,000 (482) 14,000 (375) 20,000 (536)
100 (6,9)
70 to 150 200 (13,8) 5200 (139) 8200 (220) 15,000 (402) 23,000 (616) 16,000 (429) 27,000 (724)
(4,8 to 10,3) 300 (20,7) 8000 (214) 11,000 (295) 19,000 (509) 29,000 (777) 26,000 (697) 38,000 (1018)
175 (12,1) 5600 (150) 9500 (255) 14,000 (375) 20,000 (536) 16,000 (429) 22,000 (590)
150 (10,3) 200 (13,8) 6500 (174) 11,000 (295) 16,000 (429) 24,000 (643) 20,000 (536) 26,000 (697)
300 (20,7) 8700 (233) 15,000 (402) 23,000 (616) 37,000 (992) 31,000 (831) 44,000 (1179)
1. To obtain capacities for regulators using metal diaphragms, multiply the table values by 0.6.
Table 6. Capacities in Air for Type 95BH 1-1/2 and 2-Inch (DN 40 and 50) Bodies with Elastomer or Metal Diaphragm
OUTLET CAPACITIES IN SCFH (m³/h(n)) OF AIR
OUTLET PRESSURE
PRESSURE INLET PRESSURE,
RANGE, 1-1/2-Inch (DN 40) Body 2-Inch (DN 50) Body
SETTING, PSIG (bar)
PSIG (bar)
PSIG (bar) 10% Offset 20% Offset 10% Offset 20% Offset
10 (0,69) 950 (25,5) 1000 (36,8) 1000 (26,8) 1100 (29,5)
50 (3,4) 3500 (93,8) 4000 (107) 4000 (107) 5500 (147)
5 (0,34) 100 (6,9) 6500 (174) 8000 (214) 9000 (241) 12,000 (322)
200 (13,8) 12,000 (322) 14,000 (375) 16,000 (429) 19,000 (509)
300 (20,7) 18,000 (482) 20,000 (536) 19,000 (509) 21,000 (563)
40 (2,8) 3400 (91,1) 6100 (163) 4500 (121) 6200 (166)
50 (3,4) 4500 (121) 9000 (241) 8000 (214) 10,000 (268)
30 (2,1) 100 (6,9) 8000 (214) 15,000 (402) 24,000 (643) 30,000 (804)
5 to 80 200 (13,8) 20,000 (536) 31,000 (831) 48,000 (1286) 55,000 (1474)
(0,34 to 5,5) 300 (20,7) 29,000 (777) 38,000 (1018) 53,000 (1420) 59,000 (1581)
75 (5,2) 9000 (241) 14,000 (375) 12,000 (322) 20,000 (536)
100 (6,9) 10,000 (268) 19,000 (509) 20,000 (536) 40,000 (1072)
50 (3,4)
200 (13,8) 21,000 (563) 36,000 (965) 43,000 (1152) 75,000 (2010)
300 (20,7) 39,000 (1045) 51,000 (1367) 65,000 (1742) 84,000 (2251)
100 (6,9) 14,000 (375) 22,000 (590) 15,000 (402) 28,000 (750)
75 (5,2) 200 (13,8) 23,000 (616) 49,000 (1313) 50,000 (1340) 90,000 (2412)
300 (20,7) 43,000 (1152) 65,000 (1742) 90,000 (2412) 120,000 (3216)
125 (8,6) 11,000 (295) 29,000 (777) 12,000 (322) 30,000 (804)
60 to 120
100 (6,9) 225 (15,5) 28,000 (750) 62,000 (1662) 28,000 (750) 62,000 (1662)
(4,1 to 8,3)
300 (20,7) 40,000 (1072) 88,000 (2358) 55,000 (1474) 80,000 (2144)
100 to 140 150 (10,3) 21,000 (563) 40,000 (1072) 22,000 (590) 40,000 (1072)
(6,9 to 9,7) 125 (8,6) 200 (13,8) 28,000 (750) 54,000 (1447) 39,000 (1045) 70,000 (1876)
300 (20,7) 42,000 (1126) 85,000 (2278) 86,000 (2305) 150,000 (4020)
175 (12,1) 19,000 (509) 32,000 (858) 20,000 (536) 33,000 (884)
120 to 150
150 (10,3) 200 (13,8) 23,000 (616) 44,000 (1179) 24,000 (643) 45,000 (1206)
(8,3 to 10,3)
300 (20,7) 45,000 (1206) 90,000 (2412) 86,000 (2305) 140,000 (3752)
7
Bulletin 71.1:95B
Water Capacities Table 7. Capacities in Water for Type 95BL 1/2-Inch (DN 15) Body
with Elastomer Diaphragm
All water capacities in tables 7, 8, and 9 are in gallons CAPACITIES IN
OUTLET OUTLET
per minute and liters per minute. Depending on regulator PRESSURE PRESSURE
INLET GALLONS (LITERS) PER
PRESSURE,
size, a multiplier, given in these tables, must be used to RANGE, SETTING,
PSIG (bar)
MINUTE OF WATER
convert to capacities for regulators using metal dia- PSIG (bar) PSIG (bar) 10% Droop 20% Droop
phragms. To determine flow capacity for liquid relief 20 (1,4) 2.8 (10,6) 4.0 (15,1)
valve sizing, use the following equation: 50 (3,4) 3.7 (14,0) 4.8 (18,2)
2 to 6
5 (0,34) 100 (6,9) 3.7 (14,0) 4.8 (18,2)
(0,1 to 0,4)
200 (13,8) 3.7 (14,0) 4.8 (18,2)
250 (17,2) 3.7 (14,0) 4.8 (18,2)
∆P
Q = Cv 20 (1,4) 3.7 (14,0) 5.0 (18,9)
G 50 (3,4) 4.2 (15,9) 5.3 (20,1)
10 (0,69) 100 (6,9) 4.2 (15,9) 5.3 (20,1)
where, 200 (13,8) 4.2 (15,9) 5.3 (20,1)
5 to 15 250 (17,2) 4.2 (15,9) 5.3 (20,1)
Q = liquid flow rate, gpm (0,34 to 1,0) 20 (1,4) 3.5 (13,2) 5.0 (18,9)
Cv = liquid sizing coefficient 50 (3,4) 4.8 (18,2) 6.2 (23,5)
∆P = pressure drop across the regulator, psi 15 (1,0) 100 (6,9) 5.0 (18,9) 6.3 (23,8)
200 (13,8) 5.0 (18,9) 6.3 (23,8)
G = specific gravity (specific gravity of water is 1) 250 (17,2) 5.0 (18,9) 6.3 (23,8)
30 (2,1) 4.3 (16,3) 5.8 (22,0)
Then, if capacity is desired in liters per minute, multiply 50 (3,4) 5.5 (20,8) 7.2 (27,3)
gallons per minute by 3.785. Use the Km values to 20 (1,4) 100 (6,9) 5.5 (20,8) 7.2 (27,3)
200 (13,8) 5.5 (20,8) 7.2 (27,3)
predict choked flow on liquid service. 13 to 30 250 (17,2) 5.5 (20,8) 7.2 (27,3)
(0,9 to 2,1)
50 (3,4) 6.5 (24,6) 8.3 (31,4)
100 (6,9) 6.7 (25,4) 9.2 (34,8)
30 (2,1)
200 (13,8) 6.7 (25,4) 9.2 (34,8)
250 (17,2) 6.7 (25,4) 9.2 (34,8)
1. To obtain capacities for regulators with metal diaphragms, multiply the table values
by 0.8.
Table 8. Capacities in Water for Type 95BH 1/2, 3/4, and 1-Inch (DN 15, 20, and 25) Bodies with Elastomer Diaphragm
OUTLET OUTLET CAPACITIES IN GALLONS (LITERS) PER MINUTE OF WATER
INLET
PRESSURE PRESSURE
PRESSURE, 1/2-Inch Body 3/4-Inch Body 1-Inch Body
RANGE, SETTING,
PSIG (bar)
PSIG (bar) PSIG (bar) 10% Droop 20% Droop 10% Droop 20% Droop 10% Droop 20% Droop
30 (2,1) 2.0 (7,57) 3.2 (12,1) 7.0 (26,5) 10 (37,9) 8.0 (30,3) 11 (41,6)
50 (3,4) 4.0 (15,1) 5.5 (20,8) 9.0 (34,1) 14 (53,0) 8.5 (32,2) 15 (56,8)
15 (1,0) 100 (6,9) 5.0 (18,9) 6.5 (24,6) 13 (49,2) 19 (71,9) 19 (71,9) 26 (98,4)
200 (13,8) 5.1 (19,3) 6.5 (24,6) 19 (71,9) 25 (94,6) 32 (121) 37 (140)
15 to 30 300 (20,7) 5.2 (19,7) 6.6 (25,0) 20 (75,7) 28 (106) 34 (129) 38 (144)
(1,0 to 2,1)
50 (3,4) 3.5 (13,2) 5.7 (21,6) 11 (41,6) 16 (60,6) 11 (41,6) 18 (68,1)
100 (6,9) 5.0 (18,9) 6.1 (23,1) 17 (64,4) 24 (90,9) 19 (71,9) 31 (117)
30 (2,1)
200 (13,8) 6.5 (24,6) 6.9 (26,1) 24 (90,9) 31 (117) 35 (132) 48 (182)
300 (20,7) 7.0 (26,5) 7.5 (28,4) 26 (98,4) 36 (136) 37 (140) 54 (204)
75 (5,2) 5.0 (18,9) 8.6 (32,6) 12 (45,4) 20 (75,7) 14 (53,0) 21 (79,5)
100 (6,9) 5.5 (20,8) 9.0 (34,1) 15 (56,8) 24 (90,9) 16 (60,6) 26 (98,4)
50 (3,4)
200 (13,8) 6.5 (24,6) 10 (37,9) 24 (90,9) 34 (129) 30 (114) 42 (159)
25 to 75 300 (20,7) 7.3 (27,6) 11 (41,6) 25 (94,6) 40 (151) 40 (151) 55 (208)
(1,7 to 5,2)
100 (6,9) 9.5 (36,0) 12 (45,4) 16 (60,6) 23 (87,1) 16 (60,6) 24 (90,9)
75 (5,2) 200 (13,8) 11 (41,6) 15 (56,8) 28 (106) 41 (155) 29 (110) 46 (174)
300 (20,7) 11 (41,6) 15 (56,8) 33 (125) 49 (185) 39 (148) 56 (212)
125 (8,7) 7.0 (26,5) 11 (41,6) 15 (56,8) 24 (90,9) 30 (114) 24 (90,9)
150 (10,3) 8.0 (30,3) 14 (53,0) 17 (64,4) 27 (102) 35 (132) 30 (114)
100 (6,9)
200 (13,8) 9.5 (36,0) 15 (56,8) 25 (94,6) 37 (140) 45 (170) 41 (155)
70 to 150 300 (20,7) 11 (41,6) 16 (60,6) 33 (125) 48 (182) 57 (216) 43 (163)
(4,8 to 10,3)
175 (12,0) 8.7 (32,9) 14 (53,0) 21 (79,5) 28 (106) 34 (129) 26 (98,4)
150 (10,3) 200 (13,8) 10 (37,9) 17 (64,4) 24 (90,9) 33 (125) 40 (151) 34 (129)
300 (20,7) 13 (49,2) 20 (75,7) 35 (132) 49 (185) 55 (208) 53 (201)
1. To obtain capacities for regulators with metal diaphragms, multiply the table values by 0.6.
8
Bulletin 71.1:95B
Table 9. Capacities in Water for Type 95BH 1-1/2 and 2-Inch (DN 40 and 50) Bodies with Elastomer or Metal Diaphragm
OUTLET OUTLET CAPACITIES IN GALLONS (LITERS) PER MINUTE OF WATER
INLET
PRESSURE PRESSURE
PRESSURE, 1-1/2-Inch Body 2-Inch Body
RANGE, SETTING,
PSIG (bar)
PSIG (bar) PSIG (bar) 10% Droop 20% Droop 10% Droop 20% Droop
10 (0,69) 4.8 (18,2) 5.2 (19,7) 4.8 (18,2) 5.2 (19,7)
50 (3,4) 9.5 (36,0) 10 (37,9) 10 (37,9) 12 (45,4)
5 (0,34) 100 (6,9) 14 (53,0) 15 (56,8) 14 (53,0) 15 (56,8)
200 (13,8) 18 (68,1) 20 (75,7) 18 (68,1) 21 (79,5)
300 (20,7) 20 (75,7) 24 (90,9) 33 (125) 40 (151)
30 (2,1) 8.0 (30,3) 9.0 (34,1) 7.0 (26,5) 10 (37,9)
50 (3,4) 12 (45,4) 13 (49,2) 11 (41,6) 15 (56,8)
15 (1,0) 100 (6,9) 17 (64,4) 21 (79,5) 18 (68,1) 22 (83,3)
5 to 80 200 (13,8) 23 (87,1) 32 (121) 24 (90,9) 31 (117)
(0,34 to 5,5) 300 (20,7) 25 (94,6) 35 (132) 32 (121) 50 (189)
75 (5,2) 20 (75,7) 33 (125) 19 (71,9) 32 (121)
100 (6,9) 25 (94,6) 40 (151) 24 (90,9) 38 (144)
50 (3,4)
200 (13,8) 42 (159) 61 (231) 42 (159) 62 (235)
300 (20,7) 56 (212) 82 (310) 55 (208) 83 (314)
100 (6,9) 19 (71,9) 30 (114) 20 (75,7) 30 (114)
75 (5,2) 200 (13,8) 52 (197) 74 (280) 45 (170) 71 (269)
300 (20,7) 65 (246) 95 (360) 68 (257) 100 (379)
125 (8,7) 23 (87,1) 30 (114) 24 (90,9) 32 (121)
60 to 120
100 (6,9) 225 (15,5) 52 (197) 83 (314) 54 (204) 84 (318)
(4,1 to 8,3)
300 (20,7) 70 (265) 100 (379) 100 (378) 130 (492)
150 (10,3) 28 (106) 51 (193) 29 (110) 52 (197)
100 to 140
125 (8,7) 200 (13,8) 30 (114) 64 (242) 33 (125) 71 (269)
(6,9 to 9,7)
300 (20,7) 39 (148) 82 (310) 69 (261) 120 (454)
175 (12,0) 29 (110) 52 (197) 33 (125) 54 (204)
120 to 150
150 (10,3) 200 (13,8) 32 (121) 55 (208) 34 (129) 58 (220)
(8,3 to 10,3)
300 (20,7) 55 (208) 94 (356) 55 (208) 95 (360)
9
Bulletin 71.1:95B
BODY SIZE, DIMENSIONS, INCHES (mm)
TYPE
INCHES (DN) A B C D
95BL 1/2 (15) 3.88 (99) 1.81 (46) 6.12 (155) 7.00 (178)
1/2 (15) 3.88 (99) 1.81 (46) 6.00 (152) 4.25 (108)
95BH 3/4 (20), 1 (25) 4.88 (124) 2.25 (57) 9.00 (229) 6.06 (154)
1-1/2 (40), 2 (50) 7.25 (184) 2.56 (65) 14.44 (367) 8.19 (208)
1/8-INCH VENT ( CAST IRON BODY) 1/8-INCH VENT ( CAST IRON BODY)
OR OR
1/4-INCH VENT (BRONZE BODY) 1/4-INCH VENT (BRONZE BODY)
C
C (MAXIMUM)
(MAXIMUM)
BODY
SIZE
BODY
B SIZE B
NPT
A TYPE 95BH
TYPE 95BL
Figure 4. Dimensions
10
Bulletin 71.1:95B
Order Guide Seat Material
11
Bulletin 71.1:95B
Fisher, Fisher-Rosemount, and Managing The Process Better are marks owned by Fisher Controls International, Inc. or Fisher-Rosemount Systems, Inc.
All other marks are the property of their respective owners.
Printed in U.S.A.