Professional Documents
Culture Documents
Thermia Atria
Installation instructions
9680-56538001
Rev. 2
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 1/62
8/9/2019 Atria_Optimum_Install_EN.pdf
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 2/62
8/9/2019 Atria_Optimum_Install_EN.pdf
List of contents
1 Important information ................. 4 9.2.1 Heat pump (compressor) ................... 31 10.3 Control System
2 Positioning and removal 9.2.2 Auxiliary heating .............................. 31 - Possible Operating Modes ........... 46
of packaging ............................... 5 9.3 Conditions for stop of heating mode 31 10.4 Heating System .............................. 47
2.1 Preparations before installing heat pump ... 6 9.3.1 Heat pump (compressor) ................... 31 10.4.1 Adjustment of ”ROOM”-value ............. 47
2.2 Removal of packaging and positioning 9.3.2 Auxiliary heating .............................. 31 10.4.2 How to change the ”ROOM”-value ..... 47
1 Introductory Remarks
Installation may only be carried out by a qualified installation contractor in compliance with current rules and
regulations and the instructions in this manual.
Do not install the heat pump in rooms that may be exposed to frost!
Ensure that the floor and substructure are capable of sustaining the weight of the unit! Remember that the
weight of the unit should include the water-filled water heater (see Technical Specifications).
The outdoor unit must be positioned on, and secured to, a stable base.
5
2
5
300 mm
(with support
600 mm feet at high-
est level)
690 mm
600 mm
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 9/62
8/9/2019 Atria_Optimum_Install_EN.pdf
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 10/62
8/9/2019 Atria_Optimum_Install_EN.pdf
mm
300
m in
m in 3
00 m
m
m in 3
00 mm
m
0 m
150
m in
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 11/62
8/9/2019 Atria_Optimum_Install_EN.pdf
9
3 7 0
4
8 1
Legend:
5 6
596 0
0
4
0
1
1
40
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 12/62
8/9/2019 Atria_Optimum_Install_EN.pdf
NOTE! Connect the expansion vessel and safety valve to the heat pump according to relevant regulations. The
connecting pipe to the safety valve must rise continuously; i.e. it must at no single point be angled below an
imaginary horizontal line.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 13/62
8/9/2019 Atria_Optimum_Install_EN.pdf
Outgoing
(= incoming coolant must
coolant be installed
to the on the lower terminal of the outdoor unit
heat pump).
• Use 2 suitable flexible hoses on the outdoor unit’s connection pipe and then 28 mm
pipe to the heat pump.
• Pull the entering chilled water hose (marked “Brine return”) through the rubber grommet
(located on the side of the heat pump).
• Install a strainer in the line to protect the heat pump system from foreign particles.
• Install the brine return line with all the necessary components.
• Pull the leaving chilled water hose through the corresponding rubber grommet in the
side panel.
• Install the leaving chilled water line with all the necessary components.
• Insulate both lines with watertight thermal insulation all the way from the heat pump to
the outdoor unit.
• The coolant pipes that run outside the house to the outdoor unit can be buried in the
ground but must be well insulated.
• The heat pump is equipped with an expansion outlet for the coolant side. The outlet is
located in the rear, right-hand corner (internal 25 mm thread). In instances where the
roof height is sufficient, the expansion tank can be mounted on this outlet. Where there
is insufficient roof height, the expansion tank is mounted on the pipe for incoming cool-
ant, also see chapter 4.6 Connection diagram.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 14/62
8/9/2019 Atria_Optimum_Install_EN.pdf
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 15/62
8/9/2019 Atria_Optimum_Install_EN.pdf
Pos Name 57
1 Heat pump
35 Shutoff valve 87
47 Non-return valve 78 77 80
50 Outdoor air sensor CW
57 Strainer
59 Venting and expansion tank (heat
transfer fluid) 96
86 HW
77 Non-return valve
78 Vacuum valve 59
80 Shutoff valve
86 Safety valve (1,5bar)
87 Safety valve (9bar) 1
96 Flexible hose
Brine out
80 86
Brine
59 in
80 57 80
Fig.6 Piping diagram
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 16/62
8/9/2019 Atria_Optimum_Install_EN.pdf
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 17/62
8/9/2019 Atria_Optimum_Install_EN.pdf
Outdoor sensor
UTEGIVARE
200 035
Conduit
embeddedforsensors
Room sensor (optional) Outdoor sensor
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 18/62
8/9/2019 Atria_Optimum_Install_EN.pdf
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 19/62
8/9/2019 Atria_Optimum_Install_EN.pdf
7 Electric installation
Connections
All electrical wiring must be carried out according to existing
local and national codes and regulations under the supervision
of a certified electrician. The connection of the heatpump to the
mains supply shall be a hardwired connection, and a multi-pole
switch (safety switch) with a minimum contact opening of 3 mm
must be installed in the power supply line to the unit.
(Max load for external units is 2 A.)
Electric Current!
Power is supplied to the connecting devices and may cause
electric shock. Therefore disconnect the power supply before
starting the electrical installation! The heat pump is factory
wired internally. Therefore the electric installation is mainly
limited to the following:
Connecting the mains supply
• Remove the front panel to get access to the terminal blocks.
• Pass the mains lead to the terminal blocks through the bushing
provided in the top plate.
• Connect the mains lead to the terminal block (see fig. 8)
ATTENTION: The mains lead may only be connected to the
terminal block that is provided for this purpose. No other
terminal blocks may be used.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 20/62
8/9/2019 Atria_Optimum_Install_EN.pdf
7 6
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 21/62
8/9/2019 Atria_Optimum_Install_EN.pdf
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 22/62
8/9/2019 Atria_Optimum_Install_EN.pdf
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 23/62
8/9/2019 Atria_Optimum_Install_EN.pdf
NOTE!
Never reconnect the heat pump for higher temperatures if the
heating or warm water system does not require it.
Higher temperatures put greater loads on the heat pump.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 24/62
8 Filling the chilled water system
8/9/2019 Atria_Optimum_Install_EN.pdf
When you fill the chilled water circuit, the chilled water pump must be running. Therefore, the electrical installation must have been carried out
before filling.
Ethylene glycol or ethanol with anti-corrosion protection additives of 45 percent volume must be used as anti-freeze, which corresponds to
freeze protection to minimum -32°C. This mixture withstands temperatures of a minimum of -50°C before risk of cracking. It is very important
that only ethylene glycol is used, other types of anti-freezes are too viscous at coolant temperatures of -10°C and below. We recommend that
the coolant is mixed and that it can withstand temperatures of at least -32°C and is checked before filling the system.
The volumes of the coolant system are as follows:
Heat pump (exchanger, pipe and outer jacket) approximately 47 litres
Expansion tank approximately 3 litres
External section approximately 7 litres
28 mm pipe (between HP & outdoor unit) approximately 0.5 litres per metre of pipe
Note that it is important for the installation’s function and reliability that the coolant side is completely bled in connection with operation.
Remember to also bleed the outdoor unit several times during operation.
Remove the right side panel from the outdoor unit, there is a bleed nipple at the top on both collection pipes for bleeding the outdoor unit.
– Select operating mode Off (see p. 45).
– Mix the correct proportions of water and anti-freeze liquid in a container (66) (e.g. plastic tub).
ATTENTION! Each filling must be well mixed. Then fill the system with the chilled water mixture from the tub (66) with the help of an external
pump (67) strong enough to vent the chilled water loop. (See diagram on the following page.)
Remove the venting vessel and connect the discharge side of the pump to the charging connection at the shut-off valve (62).
– Close shut-off valve (57).
– Open shut-off valve (62) and (64).
– Open shut-off valve (61) and connect a hose between the valve and the chilled water tub.
– Start the external pump (67) to fill the chilled water loop. Then start the chilled water pump (29) manually from the
display menu ”Manual Test”
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 25/62
8/9/2019 Atria_Optimum_Install_EN.pdf
WARNING
!
Ethylene
the glycol on
instructions must
thebe handled !in accordance with
package
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 26/62
8/9/2019 Atria_Optimum_Install_EN.pdf
Run the chilled water pump and the external pump in series until the liquid coming out of the return hose from
shut-off valve (61) is free of air.
• Stop the chilled water pump (29) from the display menu ”Manual Test” but let the external pump go on running.
To eliminate air between the valves (61) and (62), open valve (57) (external pump still running).
• Close valve (61) and pressurize the system by means of the external pump. ATTENTION: No more than max.
300kPa (3 bar).
• Close valve (62).
• Stop the external pump (67) and disconnect the filling arrangement.
If there is any chilled water mixture left, keep this available in a suitable plastic container to be used for later filling of the system
(to be left with the customer).
• Start the chilled water pump (29) manually and check that the level in the expansion/venting vessel stabilizes.
ATTENTION! If the system has to be refilled, the chilled water pump (29) must run. To refill the system, remove the safety valve (60)
and fill the vessel through the safety valve connection to about 2/3 of the vessel. Then reconnect the safety valve.
• Keep the chilled water pump (29) running until all the air contained in the system has assembled in the expansion/venting
vessel. During this procedure, the water level in the vessel will sink and more chilled water must be added. (See above.)
• Open the safety valve (60) to discharge positive pressure, if any. The water level should not be less than 2/3 of the
vessel. Check that valve (61) is closed.
• Provided the heating system has been filled with water, change operating mode from ” ” to the desired position.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 27/62
8/9/2019 Atria_Optimum_Install_EN.pdf
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 28/62
8/9/2019 Atria_Optimum_Install_EN.pdf
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 29/62
8/9/2019 9.2 Conditions for start of heating modeAtria_Optimum_Install_EN.pdf
9.2.1 Heat pump (compressor)
• The integral value is lower than the value selected for “Integral HP” and
• more than 5 minutes have elapsed since the heat pump was stopped and
• the re-starting delay as set in “Hpinterval” has expired and
• the regulating pressure switch is closed (=1) and
• the outdoor temperature is below the value selected for heating stop.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 30/62
8/9/2019
9.4 Conditions for start of warm water production
Atria_Optimum_Install_EN.pdf
9.4.1 Heat pump (compressor)
• The warm water temperature is equal to or lower than the value selected for start of warm water production (WH.start) or
• the warm water temperature exceeds the setpoint value for WH start by no more than 2° when heating mode is stopped (referred
to as Top-Up)
9.4.2 Auxiliary heating
• The compressor stops automatically when the outside temperature is -21°C or colder, warm water is then produced
by the additional heater.
Normally, auxiliary heating (ADD) will not be used for warm water production except in the following cases when the VL system was
selected:
1. ADD is already running at the start of WH mode.
2. TOPHEAT mode (legionella function): ADD is added 2 minutes after start of WH mode.
3. Operating mode ADD was selected .
9.5.2 Auxiliary
In the case heating
of the VL system, WH mode is stopped:
• when the set value for TOPHEATstop has been reached, or
• when operating mode ADD was selected and the temperature is equal to the preset value for WH ADD.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 31/62
8/9/2019 Atria_Optimum_Install_EN.pdf
10 Control Panel
The Atria control panel features a display unit, four control buttons,
and an alarm indicator. Next to the control panel you will find a
Display unit
User’s Manual, short instructions for temperature adjustment, and a
label with name and telephone mumber of Thermia’s retail dealer.
Control buttons
Alarm indicator
10.1 Functions
The control computer is operated with a user friendly menu sys-
tem. The menus are shown in the display unit. The menu system
is divided into four sub menus accessible via the main menu. ROOM 20°C
Detailed information about all the menus will be given further NO DEMAND HEAT
down in a separate section. OPERATE AUTO
Display unit
To access a particlar menu to view or change a set value,
use either of the four control buttons:
• One plus button pointing upwards
• One minus button pointing downwards
• One button pointing to the right
• One button pointing to the left Control buttons
An alarm indicating light at the bottom of the control panel will
tell you whether the heat pump is running properly (fixed light)
or if something is amiss and an alarm has been activated (blink-
ing light). You will always be able to see the indicating light even Alarm indicator
if the upper front panel is closed.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 32/62
8/9/2019 Atria_Optimum_Install_EN.pdf
Message Meaning
ROOM Displays desired (setpoint) room temp. If room sensor, setpoint and actual
temp. displayed.
PHASE ORDER Reversed phase order to compressor. Only displayed the first 10 minutes.
HIGH RETURN Heat pump (HP) operation not allowed due to high return temperature .
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 33/62
8/9/2019
Messages and Adjustments - Normal (contd.) Atria_Optimum_Install_EN.pdf
Message Meaning
SYMBOL HP Displayed when compressor is in operation. An ”F” indicates that flow switch is installed. An
”0” indicates that regulating pressure switch has cut out.
SYMBOL LIGHTNING Indicates that ADD is ”on”. A figure indicates the number of capacity steps.
SYMBOL COOLING Indicates that cooling is ”on”. An ”A” is for active cooling.
SYMBOL CLOCK Indicates that the function for temperature reduction is active.
SYMBOL TANK Indicates warm water production. The tank will be filled according to warm water tempera-
ture. Empty tank signifies starting temp.setpoint (normally 51 C at start). Full tank signifies
temp. at end of warm water production. Max. temp is 54° C and min. 49° C. If ADD selec-
ted, this is setpoint value for production stop. When warm water is produced, tank fills up.
Filling starts at actual temperature. Lightning next to tank symbol indicates topheat
SYMBOL FAN Displayed when fan is active L=Low speed och H=High speed.
H
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 34/62
8/9/2019 Atria_Optimum_Install_EN.pdf
10.2.2 Alarm
Alarm messages are displayed when a fault occurs. Reset of first five alarms: operation mode ”off” or power cut .
Message Meaning
HIGHPRESS ERROR High pressure switch cut-out. Stop of compressor. No warm water production.
LOWPRESS ERROR Low pressure switch cut-out. Stop of compressor. No warm water production.
MOTOR P ERROR Motor protection cut-out. Stop of compressor. No warm water production.
LOW BRINE FLOW Flow switch not active at the latest start. Stop of compressor. No warm water production.
ADD HEAT ERROR Overheating protection cut-out.
SENSOR OUT Outside air sensor fault. 0 degrees will be used for calculation of feed line setpoint temp.
SENSOR SUPPLYLINE Feed line sensor fault. Everything, except radiator pump, will be stopped.
SENSOR RETURNLINE Return line sensor fault. Return temp. = return line -5 will be used. Calc. feedline max 45°C.
SENSOR WARMWATER Warm water sensor fault. No warm water producition.
BRINEIN Control shifts to a safety mode and controls defrost using time instead, 90 minutes between defrosts
and with completely open shunt.
BRINE OUT Control shifts to a safety mode and controls defrost using time instead, 90 minutes between defrosts
and with completely open shunt.
This menu is only available in Thermia Atria Optimum
CIRC. PUMP The circulation pump’s integrated alarm has deployed
BRINE PUMP The brine pump’s integrated alarm has deployed. Both these alarms are reset by holding the red
button on the respective pump depressed for at least 1 second.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 35/62
8/9/2019 Atria_Optimum_Install_EN.pdf
10.2.3 INFORMATION for the User
This is the main menu. Here the user can change operating mode and adjust the heat curve as well as obtain use-
ful information about installation, such as actual temperatures, operating times etc. To reach ”Information” from
”Normal”, press right or left button .
10.2.3.1 Operation
Adjustment of heat source
Message Explanation
OFF Heat pump operation is off. Alarms are reset.
AUTO Heat pump and auxiliary heater allowed. Is also displayed when ADD operation is blocked.
HEATPUMP Heat pump operation allowed.
ADD.HEAT Auxiliary heater allowed.
WARMWATER Only warm water production with heat pump. Auxiliary heater added for topheat.
MANUAL TEST Manual control of output ports. No adjustments possible
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 36/62
8/9/2019
10.2.3.2 Heat Curve Atria_Optimum_Install_EN.pdf
Message Explanation
REDUCTION
ROOM FACTOR Reduction
Factor of room
multiplied by setpoint temperature.
room temperature fault,Active
which when EVUthe
influences contacts closed
feed line temp.with 10 kohm.
Displayed provided room sensor is connected. .
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 37/62
8/9/2019 Atria_Optimum_Install_EN.pdf
10.2.3.4 Temperature
Display of actual temperatures, history, and setpoint/calculated values. Historical data will be shown at set intervals (see right-hand
margin). In case of alarm, logging of data will be stopped for a week or until alarm is reset (operating mode = Off).
ROOM 20°C
SUPPLYLINE 41(40)°C Feed-line temperature (desired temperature to radiators). Use right-hand button for history.
RETURNLINE 34(48)°C Return-line temperature (setpoint temp. for heatstop). Use right-hand button for history.
WARMWATER 44°C Warm water temperature. Use right-hand button for history.
INTEGRAL -40 Calculated integral value. Use right-hand button for history.
BRINE OUT -3°C Leaving brine temperature. Use right-hand button for history.
BRINE IN 0°C Entering brine temperature. Use right-hand button for history.
COOLING 15(16)°C X card. Temperature Shunt Cooling (setpoint temperature). Optional
SHUNTGROUP 33(35)°C X card. Temperature Shunt Shunt Group (desired temperature). Optional
CURRENT 17(20)A X card. Amps (main fuse). Optional
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 38/62
10.2.3.5 OPERATING TIME
8/9/2019 Atria_Optimum_Install_EN.pdf
HEATPUMP Operating time, compressor.
ADD.HEAT 1 Operating time, auxiliary heater at full capacity 3 kW in 400V version 1,5 kW in 230V
version (VL).
ADD.HEAT 2 Operating time, auxiliary heater at full capacity 6 kW (400V) / 3 kW (230V) (VL).
ADD.HEAT 3 Operating time, auxiliary heater at full capacity 9 kW (400V) / 4,5 kW (230V) (VL).
ADD.HEAT 4 Only for 400V version, operating time, auxiliary heater at full capacity 12 kW (VL).
ADD.HEAT 5 Only for 400V version, Operating time, auxiliary heater at full capacity 15 kW (VL).
WARMWATER Operating time, warm water production with compressor.
COOLING Total operating time, cooling (active and passive).
Displayed provided sensor connected.
COOLING ACTIVE Operating time, active cooling. Displayed if sensor is connected and NODE >19.
10.2.3.6 DEFROST
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 39/62
8/9/2019 Atria_Optimum_Install_EN.pdf
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 40/62
8/9/2019 Atria_Optimum_Install_EN.pdf
10.2.4.3 Auxiliary Heater 400V version
INTEGRAL A2 Integral starting value +A1 for ADD (and 2°C subnormal temperature).
HYSTERESIS Forced start of auxiliary heating. Integral = A1+A2 .
MAXSTEP Maximum number of capacity steps. 0=no / ADD 1=3 kW / 2=6 kW / 3=9 kW / 4=12 kW / 5=15 kW
MAX CURRENT Main fuse amps. Only applicable if card with overload cut-out is connected.
SHUNTTIME Shunt motor running periods. Applicable to all shunt groups connected. The time value
indicates the shortest interval between shunt signals.
WARMWATER STOP Temp. at which warm water production is stopped when operating mode ADD(VL) is selected.
INTEGRAL A2 Integral starting value +A1 for ADD (and 2°C subnormal temperature).
HYSTERESIS Forced start of auxiliary heating. Integral = A1+A2 .
MAX STEP Maximum number of capacity steps. 0 = no / ADD 1=1,5 kW / 2=3 kW / 3=4,5 kW / 4=N.A / 5=N.A
MAX CURRENT Main fuse amps. Only applicable if card with overload cut-out is connected.
SHUNTTIME Shunt motor running periods. Applicable to all shunt groups connected. The time value
indicates the shortest interval between shunt signals.
WARMWATER STOP Temp. at which warm water production is stopped when operating mode ADD(VL) is selected.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 41/62
10.2.4.4 Manual test
8/9/2019 Test of output ports . Atria_Optimum_Install_EN.pdf
Meddelande Betydelse
MANUAL TEST 0 0 = display of output ports, 1 = activation manual, 2 = manual for temperature checks.
HEATPUMP Start of heat pump. Also starts brine pump. Pump can’t be started when alarm is activated.
BRINE PUMP Output port, brine pump.
CIRC.PUMP Output port, radiator pump.
VXV WARMWATER Output port, reversing valve warm water.
ADD.HEAT 3 Output port, electric heating element 3kW (400V) / 1,5kW (230V) (VL) .
ADD.HEAT6 Output port, electric heating element 6kW (400V) / 3kW (230V) (VL) .
ADD.HEAT6.2 Output port, electric heating element 6 kW (400V) (VL), only available for 400V version .
SHUNT DEFR Output port, defrost shunt .
FAN L Output port, fan low speed .
FAN H Output port, fan high speed .
ADD.HEAT Output port, oil (D).
SHUNT 1 Output port, shunt (D).
TOPH. WARMWATER Output port, topheat (D).
ALARM Output port, external alarm (X-card).
SHUNT COOLING Output port, shunt cooling (X-card).
SHUNT GROUP Output port, shunt group (X-card).
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 42/62
8/9/2019 10.2.4.5 Installation 1A Atria_Optimum_Install_EN.pdf
Settings to be made at installation. Control card version no. = 1. Display version no. = A .
Message Explanation
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 43/62
10.2.4.6 Defrost
8/9/2019 Atria_Optimum_Install_EN.pdf
Possible settings for adjustments in defrostfunction.
Message Explanation
DEFR CURVE 0 Here, the angle of the defrost curve can be changed using the right-hand arrow and by either
pressing + or – (change the start temperature for defrost).
DEFR CURVE -20 Here, the angle of the defrost curve can be changed using the right-hand arrow and by either
pressing + or – (change the start temperature for defrost).
DEFR TEMPERATURE The temperature shunted to the outdoor unit during a defrost.
STOP DEFR The temperature that must be reached in the Brine In sensor to complete a defrost.
FAN DELAY COMP The time in minutes that the fan continues to run after the compressor has stopped
(self defrosting using air circulation). Function only active from +2°C to + 5°C for
outdoor temperature.
BELOW 0°C DEFR Safety defrosting occurs when the outdoor temperature has been below 0° for a set number
of days, shunts +20°C for 10 minutes.
This menu is only available in Atria Optimum
CIRC: DIFF Setting the desired temperature difference in the heat transfer system.
BRINE. DIFF Setting the desired temperature difference in the coolant system.
FLOW RAD AUTO = Automatic adjustment of the temperature difference in the heat transfer system.
3 - 10 = manually set speed.
FLOW BRINE AUTO = Automatic adjustment of the temperature difference in the coolant system.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 44/62
8/9/2019 10.3 Control System - Possible Operating Modes
Atria_Optimum_Install_EN.pdf
The menu ”OPERATE” - displayed on the control panel - allows you to choose between the following five operating modes:
• OPERATION OFF: Heat pump is off. Under OPERATION, the display shows the symbol “ “
If this operating mode is selected in winter for extended periods of time, please note that the heating system must
be emptied of water to avoid any damage caused by temperatures below zero.
• OPERATION AUTO: In this mode, operation of heat pump and auxiliary heater is regulated automatically by the
control computer. On the control panel, the message ”AUTO” will be displayed under the heading OPERATION.
• OPERATION HEATPUMP: In this mode, the heat pump unit (the compressor) only is allowed to operate. On the
control panel, the message ”HEATPUMP” will be displayed under the heading OPERATION.
• OPERATION ADD: In this mode, the auxiliary heater only is allowed to operate. This mode may be useful when in a
new heat pump installation the chilled water system is not yet filled and ready to take into service.
On the control panel, the message ”ADD” will be displayed under OPERATION only. No heat will be sent to the
heating system. On the control panel, the message ”WARMWATER” will be displayed under OPERATION.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 45/62
8/9/2019 10.4 Heating System Atria_Optimum_Install_EN.pdf
56
2 Increase or reduce the ROOM value to the
desired temperature, using the plus (up) or
40
minus (down) button. Wait for 10 seconds
or press the left-hand button once to return
to the main menu. 24
20 0 -20 °C
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 46/62
8/9/2019 10.5 Adjustment of Heat Curve Atria_Optimum_Install_EN.pdf
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 47/62
8/9/2019 10.6 Maximum Return Line Temperature for the Heating System
Atria_Optimum_Install_EN.pdf
Factory setting of the maximum return line temperature is 48°C. This value must be adapted to each indi-
vidual installation. For a new value to be entered, the heat pump must be in heating mode and operating in
a stable manner.
The value of the maximum return line temperature will be adjusted in the ”Service” menu under
”HEATPUMP”.
• Establish the difference between the is-values of feed line and return lines,
in this case 36 – 30 = 6.
• Deduct this value from 55°C (maximum feed line temperature), i.e. 55 – 6 = 49.
• Enter the new value 49° in the ”Service” menu under ”HEATPUMP”.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 48/62
8/9/2019 10.8 Hot Water Production Atria_Optimum_Install_EN.pdf
The temperature of the warm water to the water heater is controlled by the regulating pressure
switch and cannot be adjusted.
The values displayed after ”WARMWATER” represent the actual warm water temperature and in
brackets the temperature at which warm water production is allowed to start.
When the temperature falls below the starting value, warm water production will be resumed.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 49/62
8/9/2019 Atria_Optimum_Install_EN.pdf
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 50/62
8/9/2019 Atria_Optimum_Install_EN.pdf
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 51/62
Troubleshooting - Alarm (contd.)
8/9/2019 Atria_Optimum_Install_EN.pdf
LOWPRESS
ERROR Low pressureiscut-out.
Compressor stopped. Incorrect
mixture. anti-freeze or incorrect Check
and thatthat
theethylene
mixture glycol has beena used
can withstand mini-
No warm water production. mum temperature of -30°C.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 52/62
8/9/2019 Atria_Optimum_Install_EN.pdf
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 53/62
Troubleshooting - Alarm (contd.)
8/9/2019 Atria_Optimum_Install_EN.pdf
Feedline sensor: The control computer will be set to OFF, while heating system pump goes on running.
Room sensor: Actual room temp. will not be displayed. 20° will be used for calculation of feed line
setpoint temp.
Brine Out: Safety defrost activated.
Brine In: Safety defrost activated.
ALARM RESET Alarms are reset by either switching off the safety switch or setting the control computer in the
OFF/Standby position.
In case of an alarm condition, the graphic display of system temperatures will be blocked in order to
facilitate troubleshooting. When the ”OFF/Standby” position is selected, the display of temperautres
will resume.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 54/62
8/9/2019
12 Control System Default Settings
Atria_Optimum_Install_EN.pdf
HEATCURVE
CURVE 40°C (floor=30) 22 56
MIN 10°C 10 50
MAX 55°C (floor=45) 40 70
CURVE 5 0°C -5 5
CURVE 0 0°C -5 5
CURVE -5 0°C -5 5
HEATSTOP 17°C 0 40, OFF
REDUCTION 3°C 1 10
ROOMFACTOR 2 0 4
HEAT CURVE 2
Only if expansion card is
connected
CURVE2 40°C 22 56
MIN2 10°C 10 40
MAX2 55°C 30 70
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 55/62
Control System Default Settings (contd.)
8/9/2019 Atria_Optimum_Install_EN.pdf
Parameter Factory Setting Min. Max
WARMWATER
START 38°C 30 46
TIME WARMWATER Atria6/8 40M - Atria10/12 20M 5 40
TIME HEATING 20M 5 40
TOPHEAT INTERVAL 14 D OFF, 1 90
TOPHEAT STOP 60°C 50 65
HEATPUMP
INTEGRAL (A1) 60 5 99
HYSTERESIS 12°C 1 15
MAX RETURN 55°C 30 70
START INTERVAL 20M 1 30
ALARM BRINE OFF OFF, -14 10
PRESSURE 120 100 120
OUTDOOR STOP -20 -20 0
SHUNT COOLING 16°C 0 30
ADD.HEAT
INTEGRAL (A2) 600 50 990
HYSTERESIS 20°C 5 30
MAX STEP 2 OFF, 1 5 (400V) / 3 (230V)
MAX CURRENT (230V) – – –
MAX CURRENT
SHUNT TIME (400V) 20A
60s 3016 9935
WARMWATER STOP 65°C 50 65
CALIBRATION SENSORS
OUTDOOR 0°C -5 5
SUPPLYLINE 0°C -5 5
RETURNLINE 0°C -5 5
WARMWATER 0°C -5 5
BRINE OUT 0°C -5 5
BRINE IN 0°C -5 5
EXTERNAL FACTORS 5 0 20
SYSTEM VL
LOGTIME 1M 1 60
NODE 5 0 30
BRINETIME ON 30 S 10 600
BRINETIME OFF 30 S 10 600
TOPPH. TIME OFF OFF ON
TOPPH. TIME D 1H 1 10
DEFROST
DEFR CURVE O -10°C --10°C -4°C
DEFR CURVE -20 -24°C --28°C -21°C
DEFR TEMPERATURE 15°C 10°C 20°C
STOP DEFR 9°C 7°C 15°C
FAN DELAY COMP 1 15,
BELOW O°C DEFR 7 1 14,
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 57/62
13 Refrigerant
8/9/2019 Atria_Optimum_Install_EN.pdf
The compressor (refrigerant) circuit of the heat pump is charged with the refrigerant R404A.
Service and repair work on the refrigerant circuit must be carried out by certified refrigeration personnel only.
Flammability
R404A is neither flammable nor explosive.
Toxicity
Under normal circumstances, and used correctly, the refrigerant has a low level of toxicity. In spite of this, it may cause injury (even danger to
life) under abnormal conditions or if deliberately misused.
Refrigerant gases are many times heavier than air. If there is a leak of refrigerant in a small and badly ventilated room, strong concentrations
of refrigerant gas might form with resulting lack of oxygen and risk of suffocation. Therefore, the heat pump should always be placed in a
room with good ventilation.
In connection with open flame the refrigerant forms phosgene, a pungent gas that is easily recognizable by its smell already in
concentrations well below the allowed limit. In this case, evacuate the premises and air well.
Any person showing symptoms of intoxication must be moved into the fresh air immediately.
Scrapping
Before scrapping the heat pump, the refrigerant must be destroyed according to local and national health and environment regulations.
14 Technical specifications
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf ATTENTION: R404A is an environmentally sound, non-chloric refrigerant that
does not affect the ozone layer. Nevertheless all service work involving the
58/62
refrigerant circuit must be carried out by a qualified technician.
8/9/2019 Heat pump, model: Atria_Optimum_Install_EN.pdf
Atria 6 Atria 8 Atria 10 Atria 12
Refrigerant: – type R404A R404A R404A R404A
– quantity kg 0,95 1,45 1,4 1,6
– test pressure MPa 3,2 3,2 3,2 3,2
– design pressure Mpa 2,9 2,9 2,9 2,9
Compressor – type Scroll Scroll Scroll Scroll
– type of oil Ester Ester Ester Ester
El.data Mains voltage volt 400V 3-N 400V 3-N 400V 3-N 400V 3-N
Ratedpower comp. kW 2 2,3 3,6 4,4
Rartedpower + Aux. kW 5,02)/8,0 3)/11,0 4) 5,3 2)/8,3 3)/11,3 4) 6,6 2)/9,6 3)/12,6 4) 7,4 2)/10,4 3)/13,4 4)
Auxiliary heater kW 3/6/9/12/15 3/6/9/12/15 3/6/9/12/15 3/6/9/12/15
Starting amps LRA A 14 25 29 32
Fuse size A 10 2)/16 3)/20 4)/20 5)/25 6) 16 2)/16 3)/20 4)/20 5)/25 6) 16 2)/16 3)/20 4)/20 5)/25 6) 16 2)/20 3)/25 4)/25 5)/25 6)
1) Tested at outdoor temperature/heating medium out: 7/35°C and 7/50°C 5) 12 kW auxiliary heater (cannot be used in combination with compressor)
(excluding circulationpumps and fan). 6) 12 kW auxiliary heater (cannot be used in combination with compressor)
2) Heat pump with 3kW auxiliary heater. 7) Pressure drop that must not be exceeded outside the heat pumps without
3) Heat pump with 6kW auxiliary heater. the nominal flow being reduced.
4) Heat pump with 9kW auxiliary heater.
14 Technical specifications
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf
ATTENTION: R404A is an environmentally sound, non-chloric refrigerant that
does not affect the ozone layer. Nevertheless all service work involving the
59/62
refrigerant circuit must be carried out by a qualified technician.
8/9/2019 Heat pump, model: Atria 6Atria_Optimum_Install_EN.pdf
ES Atria 8 ES Atria 10 ES Atria 12 ES
Refrigerant: – type R404A R404A R404A R404A
– quantity kg 0,95 1,45 1,5 1,6
– test pressure MPa 3,2 3,2 3,2 3,2
– design pressure Mpa 2,9 2,9 2,9 2,9
Compressor – type Scroll Scroll Scroll Scroll
– type of oil Ester Ester Ester Ester
El.data Mains voltage volt 230V 1-N 230V 1-N 230V 1-N 230V 1-N
Ratedpower comp. kW 3,3 4,2 5,4 5,7
Rartedpower + Aux. kW 4,8 2)/6,3 )/7,8 4) 5,7 2)/7,2 3)/8,7 4) 6,9 2)/8,4 3)/9,9 4) 7,2 2)/8,7 3)/10,2 4)
Auxiliary heater kW 1,5/3/4,5 1,5/3/4,5 1,5/3/4,5 1,5/3/4,5
Starting amps LRA A 58 76 97 108
Fuse size A 45 2)/45 3)/45 4) 45 2)/45 3)/45 4) 45 2)/45 3)/63 4 45 2)/45 3)/63 4)
1) Tested at outdoor temperature/heating medium out: 7/35°C and 7/50°C 4) Heat pump with 9kW auxiliary heater.
(excluding circulationpumps and fan). 5) Pressure drop that must not be exceeded outside the heat pumps without
2) Heat pump with 3kW auxiliary heater. the nominal flow being reduced.
3) Heat pump with 6kW auxiliary heater.
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 60/62
Installation and commissioning carried out by:
8/9/2019 As a user you should ensure that the installation contractors in charge enter the information required in this form.
Atria_Optimum_Install_EN.pdf
ELECTRICAL INSTALLATION
SYSTEM ADJUSTMENT
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 61/62
8/9/2019 Atria_Optimum_Install_EN.pdf
http://slidepdf.com/reader/full/atriaoptimuminstallenpdf 62/62