Setpoint value card 151489

1/4

Control elements
1 Supply voltage: 24 V DC
2 Supply voltage: 0 V DC
3 Display
4 Turning knob +24V +24V
5 Selector switch
6 Setpoint signal +
1
7 Setpoint signal -
8 External binary input I1
9 LED 3
10 External binary input I2
11 LED I2
12 External binary input I3
4
13 LED I3
6
Design 8 I1

The setpoint value card is housed inside a small


ER unit. The signals and voltages can be
9 I2
accessed via 4 mm jack plugs. +

10 R1 W1 W2
OUT
+
R2 +
Function
0
W3
11 I3 R3 0
0

W4
5
The functions of the setpoint value card are as -

0
R4 -
W5
follows: 12
TIME W6
■ programmable setpoint value generation W7
■ programmable ramp generation
FUNCTION D/E
W8 7
13 OUT
CONTRAST
■ cyclical sequence of setpoint values and ramps
■ Stop watch 0V 0V

Festo Didactic
Setpoint value card 151489
2/4

Menu structure plan

Setpoint values OUT / D/E FUNCTION TIME Ramps R1-R4


W1-W8 CONTRAST

Setting of refer- Setting of Change Setting of


ence values with contrasts with German/ ramp time with
- + - + English
with - +

Display of output
- +
voltage and of
active
setpoint value

Select with - + Dependent on FUNCTION

External Internal Stop watch Measured Setting of


selection of selection of function stop watch switchover
setpoint setpoint values time is time or
values by W1 - Wx Start/Stop displayed advance
activating incorporated is effected switching
inputs in the process via input I1 with
I1, I2, I3 with
- +
- +

Menu structure plan

Storing
The set values are stored by means of further detenting of the selector switch.

Stop watch
The stop watch function is selected via the menu item “FUNCTION”. The measured
time is displayed under the menu item “TIME”. The stop watch is started and stopped
by means of setting at input I1. The maximum measuring time is 100 hours.

Setpoint values
Up to 8 setpoint values can be set between the voltage range of -10 V to +10 V. These
can be activated internally or externally.
Internal activation is effected sequentially within the adjustable reversing time (0.01...50
sec.). The reversing time is identical for all setpoint values. The external control inputs
I1, I2 and I3 are inactive.
With switchover times of less than 0.01 sec. or more than 50.0 sec., the operating
mode “Advance switching setpoint values” is selected, where the internally selected
setpoint values W1...Wx are continually advanced, once the actived setpoint value has
reached its value.

Festo Didactic
Setpoint value card 151489
3/4

Bit table of inputs


I3 I2 I1 Setpoint value
0 0 0 W1
0 0 1 W2
0 1 0 W3
0 1 1 W4
1 0 0 W5
1 0 1 W6
1 1 0 W7
1 1 1 W8 Bit table

External activation is effected in any order according to the bit table via acti-
vation of the inputs I1, I2 and I3. The internal reversing time is inactive.

Ramps
The ramps are set as slope parameters
Setpoint value
(seconds / Volt), i.e.:
■ low ramp value = large slope
■ high ramp value = small slope R1

The ramps in the quadrants of the cartesian R4 Time


R2
coordinate system are defined as follows:
1. Quadrant: positive slope of 0 V
2. Quadrant: negative slope up to 0 V R3
3. Quadrant: negative slope of 0 V
4. Quadrant: positive slope up to 0 V

Supply voltage 24 V DC +/- 10%


Number of setpoint values 8
-10 V...+10 V Tol. ± 5 mV
Output voltage range
(adjustable in steps of 0.1 V)
Number of ramps 4
0...10.0 s / 1V
Ramp times
(adjustable in steps of 50 ms / 1 V)
Activating voltage of inputs min. 15 V
Output rate 1 kHz
Input I1
Stop watch
Measuring time 0...100 hrs.
Connections for 4 mm jack-plug
Subject to change Technical data

Festo Didactic
Setpoint value card 151489
4/4

Example 1
Voltage Settings at setpoint value card:
Function: Internal selection:
Setpoint values 1÷4
Time: Switchover time t = 3.0s
W1 = 3V tR1 = 0.5s/V
R1 R1 Ramp times: tR1 = 0.5s/V
tR2 = 0.0s/V
R2 tR2 = 0.0s/V
tR3 = 1.0s/V
W4 = 0V Time
R3 tR4 = 1.0s/V
tR3 = 1.0s/V
R4 Setpoint values: W1 = 3.0V
W2 = -2V tR4 = 1.0s/V W2 = -2.0V
W3 = -3V W3 = -3.0V
W4 = 0.0V
Switchover time = 3.0s

Example 2
Voltage Settings on the setpoint value card:
Time: Advance switching setpoint values
All other settings identical to example 1.

W1 = 3V tR1 = 0.5s/V
R1 R1 R1
tR2 = 0.0s/V
R2 R2

W4 = 0V Time sec.
0 3 6 9 12
tR3 = 1.0s/V
R3 R4
W2 = -2V tR4 = 1.0s/V
W3 = -3V

Example 3
Voltage
External activation via input I1
Function: Select setpoint values
W1 = 4V tR1 = 0.05s/V with I1, I2, I3
R1 R2
tR2 = 0.30s/V
Ramp times: tR1 = 0.05s/V
tR2 = 0.30s/V
0V Time tR3 = 0.10s/V
R3
tR3 = 0.10s/V
tR4 = 0.30s/V
R4 Setpoint values: W1 = 4.0V
W2 = -4V tR4 = 0.30s/V W2 = -4.0V

I1 W2 W2
ON
W1 W1
OFF Time
0 1 2 3 4 5 6 sec.

Festo Didactic