Low oil pressure failure and shutdown

Judgment Treatment
Oil pressure sensor is damaged Replace the oil sensor
Lubricating oil is unqualified Replace the Lubricating oil
Oil filter is dirty Replace the oil filter
Oil pump is damaged Replace the oil pump
Lubricating oil is not enough Add lubricating oil
Oil sensor wiring is loose Fix the wiring
Parameter setting error Correct setting
High temperature alarm and
shutdown

Judgment Treatment
Cooling water is not enough Add cooling water
coolant temperature sensor is Replace the coolant temperature
damaged sensor
Thermostat failure Replace the thermostat
Cooling fan failure Replace the cooling fan
Air inlet and outlet is not unobstructed Renovate the generator room
The radiator is dirty
Cleaning the radiator
Fan belt slack
Adjust
Low fuel level alarm

Judgment Treatment
Fuel shortage Add fuel
Fuel level sensor is damaged Replace the fuel level sensor
Charging failure alarm

Judgment Treatment
No excitation output from control Replace the controller
controller
Charging alternator fault Replace the charging alternator
Loose connection Fix the wiring
Generator can not start

Judgment Treatment
Air in fuel system Exclude the air from fuel system
Fuel is not enough Add fuel
Battery capacity is low Charging the battery
Check the battery voltage;Check or
Low start-up speed
replace the starter motor
Air filter is clossed Clean or replace the air filter
Fuel pump failure Repair or replace the fuel pump
Fuel unqualified Replace fuel
Engine temperature is low Preheating
Generator exhaust is white or blue

Judgment Treatment
Lubricating oil is overmuch Reduced to not more than the upper
Lubricating oil is unqualified limit of the dipstick
Cooling water temperature is too low Replace the oil

Fuel injector failure Preheating or replace the thermostat

Fuel injection timing is incorrect Replace the fuel injector


Cylinder pressure is insufficient Adjust
(cylinder, piston ring wear down) Repair or replace
Generator exhaust is black or gray

Judgment Treatment
Fuel is unqualified Replace the fuel
Fuel pump failure Repalce the fuel pump
Fuel injector failure Replace the fuel injector
Air filter is clossed Clean or replace the air filter
Air valve clearance is not correct Adjust
Generator overload Reduce the load
Fuel injection timing is incorrect Adjust
Cylinder pressure is insufficient Repair or replace
(cylinder, piston ring wear down)
Fuel consumption is too high

Judgment Treatment
Fuel is unqualified Replace the fuel
Fuel pump failure Repalce the fuel pump
Fuel injection timing is incorrect Adjust
Fuel injector failure Replace the fuel injector
Air filter is clogged Clean or replace the air filter
Fuel injection timing is incorrect Adjust
Cylinder pressure is insufficient Repair or replace
(cylinder, piston ring wear down)
Oil consumption is too high

Judgment Treatment
Cylinder pressure is insufficient Repair or replace
(cylinder, piston ring wear down) Reduced to not more than the
Lubricating oil is overmuch upper limit of the dipstick
Lubricating oil is unqualified Replace the oil
Lubricating oil system leaks Inspection and fix
Generator no voltage output

Judgment Treatment
AVR wiring loose Check and fixed
No excitation output from AVR Replace the AVR
Diode or varistor of exciter is Replace the diode or varistor
damaged