Professional Documents
Culture Documents
Description Supplier
1. PROXIMITY SWITCHES
1.2 Proximity Sensor XSAV11801 (Speed Monitor) Telemecanique X X X X X X X X
1.4 Proximity Sensor XSAV11373EX (Speed Monitor) Telemecanique X
1.8 Inductive Proximity Sensor IQ40 Sick X X X X X X X X X
2. SWITCHES
2.1 Limit Switches TD 250 Schmersal X X X X X X X X X
2.3 Reed Proximity Switches BN20 Schmersal X X X X X X X X
2.5 Wire Emergency Stop Telemecanique / Kiepe X X X X X
2.17 Limit Switch i110 Sick X X X X X X X
2.18 Ultimate bypass switch Schneider Electric X X X X X X X
4. POWER SUPPLY
4.4 Powersupply 24 VDC Phoenix X X X X X X X X X
4.5 Powersupply PS307 Siemens X X X X X X X X
4.9 Transformer Noratel Noratel X X X X X X X X X
5. MOTOR STARTERS
5.10 ACS 800 Frequency Converter - Hardware Manual ABB X X X X X X
5.11 ACS 800 Frequency Converter - Firmware Manual ABB X X X X X X X X X
5.12 ACS 800 Frequency Converter - Encoder module RTAC-01 ABB X X X X X
5.13 ACS 800-11 Frequency Converter - Hardware Manual ABB X X X
5.14 ACS 800 Frequency Converter - Profibus module RPBA-01 ABB X X X X X X X X X
5.21 Soft Starter PST30 - PSTB1050 ABB X X X X X
6. TRANSMITTERS
6.3 Level probe, Capacitiv, FTC53 + FTC325 Endress and Hauser X
6.9 Ethernet Equipment Hirschmann/phoenix/Weidmuller X X X X X X X X
6.27 Crane overload protection OL3000A Nord Tech/Vetec X X X X
6.31 Warning equipment Banner X X X X X X X X X
6.33 Transmitter 4-20 mA Gemac X X X
6.49 Level sensors Sick X X X X
6.50 FO Converters Phoenix X X X X X X X X
6.51 Fiber Patchbox EFB Nordic X X X X X X X
6.53 Level switch, FTI55 + FTI56 (Solicap M) Endress and Hauser X
7. Lamp
7.3 LED Lighting LED-TEK X X X X X X X X X
8. ENCODER
8.5 Encoder POSITAL POSITAL X X X X X X X
9 SPARE
11. Spare
12. Spare
13. Spare
17. CABIN
17.4 El-cabinet partlist Rittal Rittal X X X X
17.5 Cabinet Seals, Twinseal Power Flex X X X X X X X X X
17.9 Maintenance and Torques Lögstrup Lögstrup X X X X X X X X X
18. MOTOR
18.1 Data sheet for three-phase Motors
18.2 Data sheet for three-phase Motors with brake
18.3 Data sheet for three-phase Motors for variable speed
Main
Range of product OsiSense XS
Series name Application
Sensor type Inductive proximity sensor
Device application Rotation monitoring
Sensor name XSA
Sensor design Cylindrical M30
Size 81 mm
Body type Fixed
Detector flush mounting Flush mountable
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
acceptance
Material Metal
Enclosure material Nickel plated brass
Type of output signal Discrete
Wiring technique 2-wire
[Sn] nominal sensing 10 mm
distance
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Discrete output function 1 NC
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Output circuit type AC/DC
Electrical connection Cable
Cable length 2m
[Us] rated supply volt- 24...240 V AC 50/60 Hz
age 24...210 V DC
Switching capacity in 5...350 mA AC
mA 5...200 mA DC
IP degree of protection IP67 conforming to IEC 60529
Complementary
Thread type M30 x 1.5
Detection face Frontal
Front material PPS
Adjustable frequency range 6...150 cyc/mn
Operating zone 0...8 mm
Differential travel 3...15% of Fr
Repeat accuracy 3% of Sr
Cable composition 2 x 0.34 mm²
Wire insulation material PvR
Status LED 1 LED red for output state
Supply voltage limits 20...264 V AC/DC
Residual current <= 1.5 mA for open state
Switching frequency <= 100 Hz
Voltage drop <= 5.7 V at closed state
Run up delay at power up 9 s standard
Marking CE
Threaded length 57 mm
Height 30 mm
Environment
Product certifications CCC
CSA
UL
Ambient air temperature for operation -25...70 °C
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW)
Compliant - since 0825 - Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Product environmental profile Available Download Product Environmental
Product end of life instructions Available Download End Of Life Manual
2
Product data sheet XSAV11373EX
Characteristics inductive sensor XSAV - M30 - Sn10mm -
6..150c/mn - 12..48VDC - cable 2m
Main
Range of product OsiSense XS ATEX D
Series name Application
Sensor type Inductive proximity sensor
Device application Rotation monitoring ATEX dust
Sensor name XSA
Sensor design Cylindrical M30
Size 81 mm
Body type Fixed
Detector flush mounting Flush mountable
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
acceptance
Material Metal
Enclosure material Nickel plated brass
[Sn] nominal sensing 10 mm
distance
Type of output signal Discrete
Wiring technique 3-wire
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Discrete output function 1 NC
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Output circuit type DC
Discrete output type PNP
Electrical connection Cable
Cable length 2m
[Us] rated supply volt- 12...48 V DC with reverse polarity protection
age
Switching capacity in <= 200 mA with overload and short-circuit protection
mA
IP degree of protection IP67 conforming to IEC 60529
Complementary
Thread type M30 x 1.5
Detection face Frontal
Front material PPS
Adjustable frequency range 6...150 cyc/mn
Operating zone 0...8 mm
Differential travel 3...15% of Fr
Repeat accuracy 3% of Sr
Cable composition 3 x 0.34 mm²
Wire insulation material PvR
Status LED 1 LED red (output state)
Supply voltage limits 10...58 V DC
Switching frequency <= 100 Hz
Voltage drop <= 1.8 V, closed state contact(s)
Current consumption 0...15 mA, no-load
Run up delay at power up 9 s standard
Marking II2 D-Ex tb IIIC T90°C Db IP67
Threaded length 57 mm
Environment
Standards Directive ATEX 94/9/EC
EN/IEC 60079-0
EN/IEC 60079-31
Product certifications CCC
INERIS 04ATEX0022X
Ambient air temperature for operation -20...60 °C
Dust zone Zone 21 - 22
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW)
Compliant - since 0945 - Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Product environmental profile Available Download Product Environmental
Product end of life instructions Available Download End Of Life Manual
2
2.
SWITCHES
Datasheet - BN 20-10Z - 101172882 - eclass 27270104 27-27-01-04 Side 1 af 8
08.07.2013 - 11:39:55h
Datasheet - BN 20-10Z
Magnetic reed switch / BN 20
Preferred typ
• Non-contact principle
• With pre-wired cable
• 1 Reed contakts
• Long life
• 104 mm x 52 mm x 47 mm
• Aluminium enlosure
• Actuating distance up to 50 mm depending on
actuating magnet and version
• Screw connection
• Highly resistant to vibration
• Available for actuation from front or side
Ordering details
Approval
Approval -
Global Properties
Product name BN 20
Standards -
Compliance with the Directives (Y/N) Yes
suitable for elevators (Y/N) No
Active principle Magnetic drive
Materials
- Material of the housings Aluminium
- Material of the active surface Metal film
Housing construction form rectangular
Weight 285 g
Recommended actuator 2 x BP 10, 2 x BP 15/2, BP 20, BP 31, BP 11, BP 12,
BP 21 N, BE 20
http://www.schmersal.net/datenblatt?lang=en&produkt=4co734745nkmzt8ekjj42004... 08-07-2013
Datasheet - BN 20-10Z - 101172882 - eclass 27270104 27-27-01-04 Side 2 af 8
Mechanical data
Ambient conditions
Ambient temperature
- Min. environmental temperature −25 °C
- Max. environmental temperature +90 °C
Protection class IP67
Electrical data
Outputs
ATEX
http://www.schmersal.net/datenblatt?lang=en&produkt=4co734745nkmzt8ekjj42004... 08-07-2013
Datasheet - BN 20-10Z - 101172882 - eclass 27270104 27-27-01-04 Side 3 af 8
Dimensions
notice
The opening and closing functions depend on the direction of actuation, the actuating magnets and the polarity of the
actuating magnets.
When the switches and actuators come together, the colours must coincide: Red (S) to red (S) and green (N) to green
(N).
Included in delivery
Diagram
Note Diagram
positive break NC contact
active
no active
Normally-open contact
Normally-closed contact
Documents
http://www.schmersal.net/datenblatt?lang=en&produkt=4co734745nkmzt8ekjj42004... 08-07-2013
Datasheet - BN 20-10Z - 101172882 - eclass 27270104 27-27-01-04 Side 4 af 8
Images
Characteristic curve
System components
Actuator
101059927 - BP 2x21 S
• Al-metal housing
• S-pole marked red
• Suitable for mounting on ferrous material
http://www.schmersal.net/datenblatt?lang=en&produkt=4co734745nkmzt8ekjj42004... 08-07-2013
Datasheet - BN 20-10Z - 101172882 - eclass 27270104 27-27-01-04 Side 5 af 8
101059928 - BP 2x21 N
• Al-metal housing
• N-pole marked green
• Suitable for mounting on ferrous material
101057534 - BP 21 S
• Al-metal housing
• S-pole marked red
• Suitable for mounting on ferrous material
101057536 - BP 21 N
• Al-metal housing
• N-pole marked green
• Suitable for mounting on ferrous material
101059921 - BP 21
• Al-metal housing
• S-pole marked red
• N-pole marked green
• Suitable for mounting on ferrous material
101059926 - BP 2x12 S
• Al-metal housing
• S-pole marked red
• Suitable for mounting on ferrous material
101059925 - BP 2x12 N
• Al-metal housing
• N-pole marked green
• Suitable for mounting on ferrous material
101059917 - BP 12 N
• Al-metal housing
• N-pole marked green
• Suitable for mounting on ferrous material
101059916 - BP 12
• Al-metal housing
• S-pole marked red
• N-pole marked green
• Suitable for mounting on ferrous material
http://www.schmersal.net/datenblatt?lang=en&produkt=4co734745nkmzt8ekjj42004... 08-07-2013
Datasheet - BN 20-10Z - 101172882 - eclass 27270104 27-27-01-04 Side 6 af 8
101059930 - BP 2x11 S
• Al-metal housing
• S-pole marked red
• Suitable for mounting on ferrous material
101059929 - BP 2x11 N
• Al-metal housing
• N-pole marked green
• Suitable for mounting on ferrous material
101057533 - BP 11 S
• Al-metal housing
• S-pole marked red
• Suitable for mounting on ferrous material
101059923 - BP 11 N
• Al-metal housing
• N-pole marked green
• Suitable for mounting on ferrous material
101059922 - BP 11
• Al-metal housing
• S-pole marked red
• N-pole marked green
• Suitable for mounting on ferrous material
101057521 - BP 31 S
• thermoplastic enclosure
• S-pole marked red
• Suitable for mounting on ferrous material with a
distance of 20 mm
101057520 - BP 31 N
• thermoplastic enclosure
• N-pole marked green
• Suitable for mounting on ferrous material with a
distance of 20 mm
101057530 - BP 31
• thermoplastic enclosure
• S-pole marked red
• N-pole marked green
http://www.schmersal.net/datenblatt?lang=en&produkt=4co734745nkmzt8ekjj42004... 08-07-2013
Datasheet - BN 20-10Z - 101172882 - eclass 27270104 27-27-01-04 Side 7 af 8
101057541 - BP 20 S
• Al-metal housing
• S-pole marked red
• Suitable for mounting on ferrous material with a
distance of 20 mm
101057538 - BP 20 N
• Al-metal housing
• N-pole marked green
• Suitable for mounting on ferrous material with a
distance of 20 mm
101057549 - BP 20
• Al-metal housing
• S-pole marked red
• N-pole marked green
• Suitable for mounting on ferrous material with a
distance of 20 mm
101057553 - BP 34
• thermoplastic enclosure
• S-pole marked red
• N-pole marked green
• Suitable for mounting on ferrous material with a
distance of 25 mm
101060165 - BP 15/2
• Unenclosed
• Polarity stamped in
• Suitable for mounting on ferrous material with a
distance of 18 mm
101060163 - BP 15
• thermoplastic enclosure
• N-pole marked green
• S-pole marked red
• Suitable for mounting on ferrous material with a
distance of 18 mm
101057531 - BP 10
• Unenclosed
• Colour coding of poles by lables
http://www.schmersal.net/datenblatt?lang=en&produkt=4co734745nkmzt8ekjj42004... 08-07-2013
Datasheet - BN 20-10Z - 101172882 - eclass 27270104 27-27-01-04 Side 8 af 8
K.A. Schmersal GmbH & Co. KG, Möddinghofe 30, D-42279 Wuppertal
The data and values have been checked throroughly. Technical modifications and errors excepted.
Generiert am 08.07.2013 - 11:40:00h Kasbase 2.2.17.F DBI
http://www.schmersal.net/datenblatt?lang=en&produkt=4co734745nkmzt8ekjj42004... 08-07-2013
belt conveyor - pull rope Switch
hEn
Function
The pull-rope emergency stop switch is actuated by a pull rope 1 The emergency stop signal is performed with positive-making
connected on both sides of the red release lever. The contacts are normally closed (NC) contacts in accordance with the closed circuit
actuated by a spring supported cam disc (snap action function). principle.
At the same time, up to three NC and NO contacts are actuated After the emergency stop function is triggered, the switching
simultaneously and a cross comparison of the contacts can be mechanism is locked in the shut-off position "0". When the blue
performed with an external control unit. reset lever is actuated in switch position "1", the switching con-
tacts are reactivated and the conveyor belt is prepared for being
turned back on again.
Resetting the pull-rope emergency stop switch must not cause the
conveyor system to start up.
Te c h n i c a l da t a
Designation Pull-rope emergency stop switch type HEN – emergency stop device with latching function
Type of actuation Bidirectional; spring-loaded ("snap action")
Complies with DIN EN ISO 13850; DIN EN 60204-1; DIN EN 60947-5-5;
DIN EN 60947-5-1; EN 620; BGI 710
Suited for Control units and systems in accordance with DIN EN 60204
Mechanics
Enclosure Aluminum GK-AISi 12
Finish DD-paint
Enclosure – yellow (RAL 1004), release lever – red (RAL 3000), reset lever – blue (RAL 5010)
Mounting 2 slotted holes for M8 screws
Installation position Horizontal, tilt angle up to about 15°
Pull-rope length Up to approx. 100 m
Actuation force 30 N ± 10 N
Weight 1.7 kg
Electrical system
Switching system Up to 3 NC and NO contacts; cam operated positive-making switches
Cable entry Threaded holes 2x M25 x 1.5 with each
1x screwed cable gland: sealing area Ø 11 mm to Ø 16 mm; 1x dummy screw
Utilization category AC-15: 230 V; 6 A
DC-13: 110 V; 1.1 A
Connection cross section 1 mm2 to 2.5 mm2
Protective conductor connection In the casing; M4
Rated insulation voltage Ui 400 V
Rated impulse withstand voltage Uimp 2.5 kV, degree of pollution III
Conventional thermal current Ith 16 A
Contact reliability 1 2 million switching operations
Ambient conditions in accordance with DIN EN 60947-5-5
Permissible ambient temperature –25 °C …+70 °C
Extended ambient temperature range –40 °C …+70 °C (type HEN 7xx)
Protection rating IP 67 in accordance with EN 60529
Safety data in accordance with DIN EN ISO 13849 and EN 61062
Safety functions Emergency stop incl. latching
Manual reset
Usable in accordance with Up to PLe (depending on customer application)
DIN EN ISO 13849-1
B10d value 24,000 actuations
S e l e c t i o n ta b l e
Switch type Contact configuration Integrated Temperature range Ventilation Order number
NO NC signal lamp –40 °C …+70 °C membran
Equipment options:
Gold-plated contacts
Ventilation membran
Reset with square instead of lever
Signal lamps for 230 V, 110 V, or 24 V
LED signal lamps in AC/DC version for 230 V or 24 V
Devices for two-wire bus line
Mounting
Pull-rope emergency stop switches of types HEN are each fas- as well as the protective conductor connection. The pull-rope 1 is
tened to the substructure in installation position with 2 M8 screws, tensioned by tension springs 2 between the anchor hooks 3 and
centered between the anchor hook 3 of the pull-rope system (see fastened at the red release lever.
the mounting diagram).
After the tension springs 2 have been adjusted, the actuation
Electrical connection is performed with the device open using the force and path for triggering the switch must be tested to ensure
screwed cable gland included in the delivery, directly on the screw compliance with specified requirements.
joints of the switching elements and the lamp fitting (option)
M o u n t i n g d i a g r am
3 2 5 8 7 1 6 7 4
D i me n s i o n s
15° 15°
80
119.5
123
X1 X2
43
31
16
7
192
176
162
15
8.5
13.25
80.5
54
22
81
119
Main
Range of product Harmony XB4
Product or component Head for key selector switch
type
Device short name ZB4
Bezel material Chromium plated metal
Mounting diameter 22 mm
Sale per indivisible 1
quantity
Shape of signaling unit Round
head
Operator profile Black key switch
Operator position infor- 2 positions 90°
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
mation
Type of keylock Ronis 455
Key withdrawal position Left
Complementary
CAD overall width 29 mm
CAD overall height 29 mm
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
CAD overall depth 72 mm
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Product weight 0.098 kg
Resistance to high pressure washer 7000000 Pa at 55 °C,distance: 0.1 m
Mechanical durability 1000000 cycles
Electrical composition code C15 for 1 contacts using single blocks in front mounting
C11 for <= 3 contacts using single blocks in front mounting
C8 for <= 4 contacts using single and double blocks in front mounting
C7 for <= 4 contacts using single blocks in front mounting
C6 for <= 5 contacts using single and double blocks in front mounting
C5 for <= 5 contacts using single blocks in front mounting
C4 for <= 6 contacts using single and double blocks in front mounting
C3 for <= 6 contacts using single blocks in front mounting
Environment
Protective treatment TH
Ambient air temperature for storage -40...70 °C
Ambient air temperature for operation -25...70 °C
Class of protection against electric shock Class I conforming to IEC 60536
IP degree of protection IP69K conforming to IEC 60529
NEMA degree of protection NEMA 4X
NEMA 13
IK degree of protection IK06 conforming to IEC 50102
Standards EN/IEC 60947-1
EN/IEC 60947-5-1
EN/IEC 60947-5-4
EN/IEC 60947-5-5
UL 508
GB 14048.5
CSA C22.2 No 14
2
Product data sheet ZB4BG2
Dimensions Drawings
Dimensions
3
Product data sheet ZB4BG2
Mounting and Clearance
Panel Cut-out for Pushbuttons, Switches and Pilot Lights (Finished Holes, Ready for Installation)
Pushbuttons, Switches and Pilot Lights for Printed Circuit Board Connection
4
Printed Circuit Board Cut-outs (Viewed from Electrical Block Side)
Dimensions in mm
A: 30 mm min.
B: 40 mm min.
Dimensions in in.
A: 1.18 in. min.
B: 1.57 in. min.
Installation Precautions
● Minimum thickness of circuit board: 1.6 mm / 0.06 in.
● Cut-out diameter: 22.4 mm ± 0.1 / 0.88 in. ± 0.004
● Orientation of body/fixing collar ZB4 BZ009: ± 2°30’ (excluding cut-outs marked a and b).
● Tightening torque of screws ZBZ 006: 0.6 N.m (5.3 lbf.in) max.
● Allow for one ZB4 BZ079 fixing collar/pillar and its fixing screws:
○ every 90 mm / 3.54 in. horizontally (X), and 120 mm / 4.72 in. vertically (Y).
○ with each selector switch head (ZB4 BD•, ZB4 BJ•, ZB4 BG•).
The fixing centers marked a and b are diagonally opposed and must align with those marked 4 and 5.
5
(1) Panel
(2) Printed circuit board
Dimensions An + 18.1 relate to the Ø 2.4 mm ± 0.05 / 0.09 in. ± 0.002 holes for centring adapter ZBZ 01•.
6
Product data sheet ZB4BG2
Technical Description
7
Electrical Composition Corresponding to Code C8
1 N/O
1 N/C
Legend
Single contact
Double contact
Light block
Possible location
8
Sequence of Contacts Fitted to 2-position Selector Switch Body
Position 315°
Bottom
State 0 0 0
Position 45°
Bottom
State 1 1 1
9
3.
EMERGENCY STOP RELAY
PNOZ s2
Safety relays
Operating Manual-21394-EN-08
Preface
This document is a translation of the original document.
All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made
for internal purposes. Suggestions and comments for improving this documentation will be
gratefully received.
Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®,
SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks
of Pilz GmbH & Co. KG in some countries.
Introduction 5
Validity of documentation 5
Using the documentation 5
Definition of symbols 5
Safety 6
Intended use 6
Safety regulations 6
Safety assessment 6
Use of qualified personnel 6
Warranty and liability 7
Disposal 7
For your safety 7
Unit features 8
Safety features 8
Function description 9
Timing diagram 10
Installation 10
Wiring 11
Operation 13
Status indicators 14
Error indicators 15
Faults - malfunctions 15
Dimensions in mm 16
Technical Details 16
Safety characteristic data 21
Supplementary data 21
Service life graph 22
Order reference 23
EC declaration of conformity 23
Introduction
Validity of documentation
This documentation is valid for the product PNOZ s2. It is valid until new documentation is
published.
This operating manual explains the function and operation, describes the installation and
provides guidelines on how to connect the product.
Definition of symbols
Information that is particularly important is identified as follows:
DANGER!
This warning must be heeded! It warns of a hazardous situation that poses
an immediate threat of serious injury and death and indicates preventive
measures that can be taken.
WARNING!
This warning must be heeded! It warns of a hazardous situation that could
lead to serious injury and death and indicates preventive measures that can
be taken.
CAUTION!
This refers to a hazard that can lead to a less serious or minor injury plus
material damage, and also provides information on preventive measures
that can be taken.
NOTICE
This describes a situation in which the product or devices could be dam-
aged and also provides information on preventive measures that can be
taken. It also highlights areas within the text that are of particular import-
ance.
INFORMATION
This gives advice on applications and provides information on special fea-
tures.
Safety
Intended use
The safety relay provides a safety-related interruption of a safety circuit.
The safety relay meets the requirements of EN 60947-5-1, EN 60204-1 and VDE 0113-1
and may be used in applications with
} E-STOP pushbuttons
} Safety gates
The following is deemed improper use in particular:
} Any component, technical or electrical modification to the product
} Use of the product outside the areas described in this manual
} Use of the product outside the technical details (see Technical details [ 16]).
NOTICE
EMC-compliant electrical installation
The product is designed for use in an industrial environment. The product
may cause interference if installed in other environments. If installed in other
environments, measures should be taken to comply with the applicable
standards and directives for the respective installation site with regard to in-
terference.
Safety regulations
Safety assessment
Before using a unit it is necessary to perform a safety assessment in accordance with the
Machinery Directive.
Functional safety is guaranteed for the product as a single component. However, this does
not guarantee the functional safety of the overall plant/machine. In order to achieve the re-
quired safety level for the overall plant/machine, define the safety requirements for the
plant/machine and then define how these must be implemented from a technical and organ-
isational standpoint.
A competent person is someone who, because of their training, experience and current pro-
fessional activity, has the specialist knowledge required to test, assess and operate the
work equipment, devices, systems, plant and machinery in accordance with the general
standards and guidelines for safety technology.
It is the company’s responsibility only to employ personnel who:
} Are familiar with the basic regulations concerning health and safety / accident preven-
tion
} Have read and understood the information provided in this description under "Safety"
} And have a good knowledge of the generic and specialist standards applicable to the
specific application.
Disposal
} In safety-related applications, please comply with the mission time TM in the safety-re-
lated characteristic data.
} When decommissioning, please comply with local regulations regarding the disposal of
electronic devices (e.g. Electrical and Electronic Equipment Act).
Unit features
} Positive-guided relay outputs:
– 3 safety contacts (N/O), instantaneous
– 1 auxiliary contact (N/C), instantaneous
} Protective separation of safety contacts from all other circuits
} 1 semiconductor output
} Connection options for:
– E-STOP pushbutton
– Safety gate limit switch
– Start button
} A connector can be used to connect 1 PNOZsigma contact expansion module
} Operating modes can be set via rotary switch
} LED indicator for:
– Supply voltage
– Input status, channel 1
– Input status, channel 2
– Switch status of the safety contacts
– Start circuit
– Errors
} Plug-in connection terminals (either spring-loaded terminal or screw terminal)
} See order reference for unit types
Safety features
The relay meets the following safety requirements:
} The circuit is internally redundant with built-in self-monitoring.
} The safety function remains effective in the case of a component failure.
} The correct opening and closing of the safety function relays is tested automatically in
each on-off cycle.
expansion
Interface
module
Fig.: Centre: Front view with cover, right: Front view without cover
*Safe separation from non-marked area in accordance with EN 60947-1, 6 kV, basic insula-
tion between all safety contacts.
Function description
} Single-channel operation: No redundancy in the input circuit, earth faults in the start
and input circuit are detected.
} Automatic start: Unit is active once the input circuit has been closed.
} Manual start Unit is active once the input circuit and the start circuit are closed.
} Monitored start with falling edge: Unit is active once
– the input circuit is closed and then the start circuit is closed and opened again.
– the start circuit is closed and then opened again once the input circuit is closed.
} Monitored start with rising edge: Unit is active once the input circuit is closed and
once the start circuit is closed after the waiting period has elapsed (see technical de-
tails).
} Increase in the number of available instantaneous safety contacts by connecting con-
tact expander modules or external contactors/relays;
A connector can be used to connect 1 PNOZsigma contact expander module.
Timing diagram
Legend
} Power: Supply voltage
} Start: Start circuit
} Input: Input circuits
} Output safe: Safety contacts
} Output aux: Auxiliary contacts
} Out semi: Semiconductor output
} [1]: Automatic start
} [2]: Manual start
} [3]: Monitored start with rising edge
} [4]: Monitored start with falling edge
} a: Input circuit closes before start circuit
} b: Start circuit closes before input circuit
} t1: Switch-on delay
} t2: Delay-on de-energisation
} t3: Waiting period
} t4: Min. start pulse duration with a monitored start
Installation
Install base unit without contact expansion module:
} Ensure that the plug terminator is inserted at the side of the unit.
Connect base unit and PNOZsigma contact expansion module:
} Remove the plug terminator at the side of the base unit and at the contact expansion
module.
} Connect the base unit and the contact expansion module to the supplied connector be-
fore mounting the units to the DIN rail.
Wiring
Please note:
} Information given in the "Technical details [ 16]" must be followed.
} Outputs 13-14, 23-24, 33-34 are safety contacts; output 41-42 is an auxiliary contact
(e.g. for display).
} Auxiliary contact 41-42 and semiconductor output Y32 should not be used for safety
circuits!
} To prevent contact welding, a fuse should be connected before the output contacts (see
Technical details [ 16]).
} Calculation of the max. cable runs lmax in the input circuit:
Rlmax
Imax =
Rl / km
Operating modes
The operating mode is set via the rotary switch on the unit. You can do this by opening the
cover on the front of the unit.
NOTICE
Do not adjust the rotary switch during operation, otherwise an error mes-
sage will appear, the safety contacts will open and the unit will not be ready
for operation until the supply voltage has been switched off and then on
again.
Operating mode se- Automatic/manual Monitored start rising Monitored start fall-
lector switch "mode" start edge ing edge
without detection of
shorts across con-
tacts
Connection
Supply voltage AC DC
S1
A1 L+
A2 L-
Safety gate
without detection of shorts
across contacts S1
A1 L+
NOTICE
In the event of an automatic start or manual start with a bridged start con-
tact (fault case)
The unit starts up automatically when the safeguard is reset, e.g. when the
E-STOP pushbutton is released. Use external circuit measures to prevent
an unexpected restart.
Semiconductor output
INFORMATION
If a base unit and a contact expansion module from the PNOZsigma range
are connected via the connector, no additional wiring is necessary.
Operation
NOTICE
The safety function should be checked after initial commissioning and each
time the plant/machine is changed. The safety functions may only be
checked by qualified personnel.
The unit is ready for operation when the Power LED is permanently lit.
LEDs indicate the status and errors during operation:
LED on
LED flashes
INFORMATION
Status indicators and error indicators may occur independently. In the case
of an error display, the "Fault" LED will light or flash (exception: "Supply
voltage too low"). An LED that is also flashing indicates the potential cause
of the error. An LED that is lit and is static indicates a normal operating
status. Several status indicators and error indicators may occur simultan-
eously.
Status indicators
POWER, IN1, IN2
Input circuit is closed.
OUT
Safety contacts are closed and semiconductor output Y32 carries a high signal.
RESET
24 VDC is present at S34.
Error indicators
FAULT
Diagnostics: Plug terminator not connected
} Remedy: Insert plug terminator, switch supply voltage off and then on
again.
FAULT
Diagnostics: Internal error, unit defective
} Remedy: Switch supply voltage off and then on again, change unit if neces-
sary.
POWER
Diagnostics: Supply voltage too low
} Remedy: Check supply voltage and increase if necessary.
RESET FAULT
Diagnostics: Position of rotary switch is not permitted or rotary switch was ad-
justed during operation.
} Remedy: Switch supply voltage off and then on again.
Faults - malfunctions
} Contact malfunctions: If the contacts have welded, reactivation will not be possible after
the input circuit has opened.
Dimensions in mm
*with spring-loaded terminals
120 (4.72")
98 (3.86")
17,5
* 100 (3,94") (0.69")
Technical Details
Where standards are undated, the 2014-07 latest editions shall apply.
NOTICE
You must comply with the safety-related characteristic data in order to
achieve the required safety level for your plant/machine.
Operating EN ISO EN ISO EN 62061 EN 62061 IEC 61511 IEC 61511 EN ISO
mode 13849-1: 13849-1: SIL CL PFHD [1/h] SIL PFD 13849-1:
2008 2008 2008
PL Category TM [year]
Safety con-
tacts, in-
stantaneous PL e Cat. 4 SIL CL 3 2,50E-09 SIL 3 2,13E-05 20
All the units used within a safety function must be considered when calculating the safety
characteristic data.
INFORMATION
A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.
Supplementary data
CAUTION!
It is essential to consider the relay's service life graphs. The relay outputs'
safety-related characteristic data is only valid if the values in the service life
graphs are met.
The PFH value depends on the switching frequency and the load on the relay output.
If the service life graphs are not accessible, the stated PFH value can be used irrespective
of the switching frequency and the load, as the PFH value already considers the relay's
B10d value as well as the failure rates of the other components.
Cycles x 1000
Example
} Inductive load: 0.2 A
} Utilisation category: AC15
} Contact service life: 2 000 000 cycles
Provided the application to be implemented requires fewer than 2 000 000 cycles, the PFH
value (see Technical details [ 16]) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With DC con-
tactors, use flywheel diodes for spark suppression.
Order reference
Product type Features Connection type Order No.
PNOZ s2 24 V DC Screw terminals 750 102
PNOZ s2 C 24 V DC Spring-loaded terminals 751 102
EC declaration of conformity
This product/these products meet the requirements of the directive 2006/42/EC for ma-
chinery of the European Parliament and of the Council. The complete EC Declaration of
Conformity is available on the Internet at www.pilz.com/downloads.
Representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix-Wankel-Str. 2, 73760 Ost-
fildern, Germany
Printed in Germany
Support
21394-EN-08, 2015-09100XXXX-DE-0X
in Germany
© Pilz GmbH & Co. KG, 2015
KG, 2015
& Co.Printed
Technical support is available from Pilz round the clock.
2015-00
Americas Australia Scandinavia
© Pilz GmbH
0-0-1-3-000,
Brazil +61 3 95446300 +45 74436332
+55 11 97569-2804 Spain
Canada Europe +34 938497433
+1 888-315-PILZ (315-7459) Austria Switzerland
SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks of Pilz GmbH & Co. KG in some countries. We would point out that product features may vary
Mexico +43 1 7986263-0 +41 62 88979-30
CMSE®, InduraNET p®, PAS4000®, PAScal®, PASconfig®, Pilz®, PIT®, PLID®, PMCprimo®, PMCprotego®, PMCtendo®, PMD®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®,
+52 55 5572 1300 Belgium, Luxembourg The Netherlands
USA (toll-free) +32 9 3217575 +31 347 320477
from the details stated in this document, depending on the status at the time of publication and the scope of the equipment. We accept no responsibility for the validity, accuracy
+1 877-PILZUSA (745-9872) France Turkey
+33 3 88104000 +90 216 5775552
Asia Germany United Kingdom
China +49 711 3409-444 +44 1536 462203
+86 21 60880878-216 Ireland
Japan +353 21 4804983 You can reach our
+81 45 471-2281 Italy international hotline on:
South Korea +39 0362 1826711 +49 711 3409-444
+82 31 450 0680 support@pilz.com
and entirety of the text and graphics presented in this information. Please contact our Technical Support if you have any questions.
Pilz develops environmentally-friendly products using
ecological materials and energy-saving technologies.
Offices and production facilities are ecologically designed,
environmentally-aware and energy-saving. So Pilz offers
sustainability, plus the security of using energy-efficient
products and environmentally-friendly solutions.
Partner of:
The Best of
German
Engineering
} Safety relays
Introduction 5
Validity of documentation 5
Using the documentation 5
Definition of symbols 5
Safety 6
Intended use 6
Safety regulations 7
Safety assessment 7
Use of qualified personnel 7
Warranty and liability 7
Disposal 7
For your safety 8
Unit features 8
Safety features 8
Function description 10
Timing diagram 11
Installation 11
Wiring 12
Operation 16
Status indicators 16
Error indicators 17
Faults - malfunctions 18
Dimensions in mm 18
Technical details 19
Safety characteristic data 30
Supplementary data 31
Service life graph 31
Order reference 34
EC declaration of conformity 35
Introduction
Validity of documentation
This documentation is valid for the product PNOZ s4. It is valid until new documentation is
published.
This operating manual explains the function and operation, describes the installation and
provides guidelines on how to connect the product.
Definition of symbols
Information that is particularly important is identified as follows:
DANGER!
This warning must be heeded! It warns of a hazardous situation that poses
an immediate threat of serious injury and death and indicates preventive
measures that can be taken.
WARNING!
This warning must be heeded! It warns of a hazardous situation that could
lead to serious injury and death and indicates preventive measures that can
be taken.
CAUTION!
This refers to a hazard that can lead to a less serious or minor injury plus
material damage, and also provides information on preventive measures
that can be taken.
NOTICE
This describes a situation in which the product or devices could be dam-
aged and also provides information on preventive measures that can be
taken. It also highlights areas within the text that are of particular import-
ance.
INFORMATION
This gives advice on applications and provides information on special fea-
tures.
Safety
Intended use
The safety relay provides a safety-related interruption of a safety circuit.
The safety relay meets the requirements of EN 60947-5-1, EN 60204-1 and VDE 0113‑1
and may be used in applications with
} E-STOP pushbuttons
} Safety gates
} Light grids and safety switches with detection of shorts across contacts
Units with the following order numbers can be used as a safety component for lifts in ac-
cordance with Annex IV of the directive 95/16/EC and EN 81-1:
} 750 104
} 751 104
} 750 134
} 751 134
The following is deemed improper use in particular:
} Any component, technical or electrical modification to the product
} Use of the product outside the areas described in this manual
} Use of the product outside the technical details (see Technical details [ 19]).
NOTICE
EMC-compliant electrical installation
The product is designed for use in an industrial environment. The product
may cause interference if installed in other environments. If installed in other
environments, measures should be taken to comply with the applicable
standards and directives for the respective installation site with regard to in-
terference.
Safety regulations
Safety assessment
Before using a unit it is necessary to perform a safety assessment in accordance with the
Machinery Directive.
Functional safety is guaranteed for the product as a single component. However, this does
not guarantee the functional safety of the overall plant/machine. In order to achieve the re-
quired safety level for the overall plant/machine, define the safety requirements for the
plant/machine and then define how these must be implemented from a technical and organ-
isational standpoint.
Disposal
} In safety-related applications, please comply with the mission time TM in the safety-re-
lated characteristic data.
} When decommissioning, please comply with local regulations regarding the disposal of
electronic devices (e.g. Electrical and Electronic Equipment Act).
Unit features
} Positive-guided relay outputs:
– 3 safety contacts (N/O), instantaneous
– 1 auxiliary contact (N/C), instantaneous
} 1 semiconductor output
} Connection options for:
– E-STOP pushbuttons
– Safety gate limit switches
– Start buttons
– Light grids and safety switches with detection of shorts across contacts
} A connector can be used to connect 1 PNOZsigma contact expansion module
} Operating modes can be set via rotary switch
} LED indicator for:
– Supply voltage
– Input status, channel 1
– Input status, channel 2
– Switch status of the safety contacts
– Start circuit
– Errors
} Plug-in connection terminals (either spring-loaded terminal or screw terminal)
} See order reference for unit types
Safety features
The relay meets the following safety requirements:
} The circuit is redundant with built-in self-monitoring.
} The safety function remains effective in the case of a component failure.
} The correct opening and closing of the safety function relays is tested automatically in
each on-off cycle.
expansion
Interface
module
Fig.: Centre: Front view with cover, right: Front view without cover
*Insulation between the non-marked area and the relay contacts: Basic insulation (over-
voltage category III), Protective separation (overvoltage category II)
Fig.: Centre: Front view with cover, right: Front view without cover
*Insulation between the non-marked area and the relay contacts: Basic insulation (over-
voltage category III), Protective separation (overvoltage category II)
Function description
In2+
} Single-channel operation: no redundancy in the input circuit, earth faults in the start
circuit and input circuit are detected.
} Dual-channel operation without detection of shorts across contacts: redundant input cir-
cuit, detects
– earth faults in the start and input circuit,
– short circuits in the input circuit and, with a monitored start, in the start circuit too.
In2-
} Dual-channel operation with detection of shorts across contacts: redundant input cir-
cuit, detects
– earth faults in the start and input circuit,
– short circuits in the input circuit and, with a monitored start, in the start circuit too,
– shorts between contacts in the input circuit.
} Automatic start: Unit is active once the input circuit has been closed.
} Manual start Unit is active once the input circuit and the start circuit are closed.
} Monitored start with falling edge: Unit is active once
– the input circuit is closed and then the start circuit is closed and opened again.
– the start circuit is closed and then opened again once the input circuit is closed.
} Monitored start with rising edge: Unit is active once the input circuit is closed and
once the start circuit is closed after the waiting period has elapsed (see technical de-
tails).
} Start with start-up test: The unit checks whether safety gates that are closed are
opened and then closed again when supply voltage is applied.
} Increase in the number of available instantaneous safety contacts by connecting con-
tact expander modules or external contactors/relays;
A connector can be used to connect 1 PNOZsigma contact expander module.
Timing diagram
Legend
} POWER: Supply voltage
} Start: Start circuit
} Input: Input circuits
} Output safe: Safety contacts
} Output aux: Auxiliary contacts
} Out semi: Semiconductor output
} [1]: Automatic start
} [2]: Manual start
} [3]: Monitored start with rising edge
} [4]: Monitored start with falling edge
} a: Input circuit closes before start circuit
} b: Start circuit closes before input circuit
} t1: Switch-on delay
} t2: Delay-on de-energisation
} t3: Waiting period with a monitored start
} t4: Min. start pulse duration with a monitored start
Installation
Install base unit without contact expansion module:
} Ensure that the plug terminator is inserted at the side of the unit.
Connect base unit and PNOZsigma contact expansion module:
} Remove the plug terminator at the side of the base unit and at the contact expansion
module.
} Connect the base unit and the contact expansion module to the supplied connector be-
fore mounting the units to the DIN rail.
Installation in control cabinet
} The safety relay should be installed in a control cabinet with a protection type of at least
IP54.
} Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).
} When installed vertically: Secure the unit by using a fixing element (e.g. retaining
bracket or end angle).
} Push the device upwards or downwards before lifting it from the DIN rail.
Wiring
Please note:
} Information given in the "Technical details [ 19]" must be followed.
} Outputs 13-14, 23-24, 33-34 are safety contacts; output 41-42 is an auxiliary contact
(e.g. for display).
} Auxiliary contact 41-42 and semiconductor output Y32 should not be used for safety
circuits!
} To prevent contact welding, a fuse should be connected before the output contacts (see
Technical details [ 19]).
} Calculation of the max. cable runs lmax in the input circuit:
Rlmax
Imax =
Rl / km
NOTICE
If you connect contact expansion modules to a base unit with a universal
power supply, you will need to limit the conventional thermal current at the
contact expansion modules' safety contacts to 70 % of the stated current
(see technical details for contact expansion module).
Operating modes
The operating mode is set via the rotary switch on the unit. You can do this by opening the
cover on the front of the unit.
NOTICE
Do not adjust the rotary switch during operation, otherwise an error mes-
sage will appear, the safety contacts will open and the unit will not be ready
for operation until the supply voltage has been switched off and then on
again.
tion of shorts
across contacts
With detection of In2+ In2- In2+ In2- In2+ In2- In2+ In2-
shorts across
contacts
Connection
A2 L-
E-Stop S1
S11
with detection of shorts S21
across contacts S22
S12
Safety gate
without detection of shorts
S1
across contacts S11 S11
S1
S12 S2
S22 S12
S22
Safety gate
with detection of shorts
across contacts S11
S1
S12 S2
S21
S22
GND
NOTICE
When operated with a light grid or sensor
– It must not be possible to switch off the supply voltage for the PNOZ-
sigma separately from the supply voltage for the light grid or safety
switch.
– The operating mode selector switch must be set to "Without detection
of shorts across contacts", as shorts across contacts are detected by
the ESPE.
NOTICE
When used as a safety component in accordance with EN 81-1:
– The switch that is used must be designed as a safety switch in ac-
cordance with 14.1.2.2 of EN 81-1, so that a failure to open when en-
ergised is excluded.
– The supply lines to the safety switch must be laid in accordance with
13.5 of EN 81-1 so that short circuits that would bridge the contacts
in the switch can be excluded.
NOTICE
In the event of an automatic start or manual start with bridged start contact
(fault)
The unit starts up automatically when the safeguard is reset, e.g. when the
E-STOP pushbutton is released. Use external circuit measures to prevent
an unexpected restart.
Legend
} S1/S2: E-STOP/safety gate switch
} S3: Reset button
} : Switch operated
} : Gate open
} : Gate closed
Operation
NOTICE
The safety function should be checked after initial commissioning and each
time the plant/machine is changed. The safety functions may only be
checked by qualified personnel.
The unit is ready for operation when the Power LED is permanently lit.
LEDs indicate the status and errors during operation:
LED on
LED flashes
LED off
INFORMATION
Status indicators and error indicators may occur independently. In the case
of an error display, the "Fault" LED will light or flash (exception: "Supply
voltage too low"). An LED that is also flashing indicates the potential cause
of the error. An LED that is lit and is static indicates a normal operating
status. Several status indicators and error indicators may occur simultan-
eously.
Status indicators
POWER
Supply voltage is present.
IN1
Input circuit at S12 is closed.
IN2
Input circuit at S22 is closed.
OUT
Safety contacts are closed and semiconductor output Y32 carries a high signal.
RESET
24 VDC is present at S34.
Error indicators
All LEDs off
Diagnostics: Short across contacts/earth fault; unit switched off
} Remedy: Rectify short across contacts/earth fault, switch off supply voltage
for 1 min.
FAULT
Diagnostics: Plug terminator not connected
} Remedy: Insert plug terminator, switch supply voltage off and then on
again.
FAULT
Diagnostics: Internal error, unit defective
} Remedy: Switch supply voltage off and then on again, change unit if neces-
sary.
POWER
Diagnostics: Supply voltage too low
} Remedy: Check supply voltage and increase if necessary.
IN1 FAULT
Diagnostics: Power-up blocked due to short-term interruption at S12; input cir-
cuits not operated simultaneously
} Remedy: Open both input circuits, S12 and S22, simultaneously and then
close again.
IN2 FAULT
Diagnostics: Power-up blocked due to short-term interruption at S22; input cir-
cuits not operated simultaneously
} Remedy: Open both input circuits, S12 and S22, simultaneously and then
close again.
RESET FAULT
Diagnostics: Position of rotary switch is not permitted or rotary switch was ad-
justed during operation.
} Remedy: Switch supply voltage off and then on again.
Faults - malfunctions
} Contact malfunctions: If the contacts have welded, reactivation will not be possible after
the input circuit has opened.
Dimensions in mm
*with spring-loaded terminals
Technical details
NOTICE
You must comply with the safety-related characteristic data in order to
achieve the required safety level for your plant/machine.
Operating EN ISO EN ISO EN 62061 EN 62061 IEC 61511 IEC 61511 EN ISO
mode 13849-1: 13849-1: SIL CL PFHD [1/h] SIL PFD 13849-1:
2008 2008 2008
PL Category TM [year]
Safety con-
tacts, in-
stantaneous PL e Cat. 4 SIL CL 3 2,31E-09 SIL 3 2,03E-06 20
All the units used within a safety function must be considered when calculating the safety
characteristic data.
INFORMATION
A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.
Supplementary data
CAUTION!
It is essential to consider the relay's service life graphs. The relay outputs'
safety-related characteristic data is only valid if the values in the service life
graphs are met.
The PFH value depends on the switching frequency and the load on the relay output.
If the service life graphs are not accessible, the stated PFH value can be used irrespective
of the switching frequency and the load, as the PFH value already considers the relay's
B10d value as well as the failure rates of the other components.
Cycles x 1000
Example
} Inductive load: 0.2 A
} Utilisation category: AC15
} Contact service life: 2 000 000 cycles
Provided the application to be implemented requires fewer than 2 000 000 cycles, the PFH
value (see Technical details [ 19]) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With DC con-
tactors, use flywheel diodes for spark suppression.
Cycles x 1000
Example
} Inductive load: 0.2 A
} Utilisation category: AC15
} Contact service life: 1 000 000 cycles
Provided the application to be implemented requires fewer than 1 000 000 cycles, the PFH
value (see Technical details [ 19]) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all relay con-
tacts. With capacitive loads, any power surges that occur must be noted. With DC contact-
ors, use flywheel diodes for spark suppression.
Order reference
Product type Features Connection type Order No.
PNOZ s4 24 VDC Screw terminals 750 104
PNOZ s4 48 – 240 VAC/DC Screw terminals 750 134
PNOZ s4 C 24 VDC Spring-loaded terminals 751 104
PNOZ s4 C 48 – 240 VAC/DC Spring-loaded terminals 751 134
EC declaration of conformity
This product/these products meet the requirements of the directive 2006/42/EC for ma-
chinery of the European Parliament and of the Council. The complete EC Declaration of
Conformity is available on the Internet at www.pilz.com/downloads.
Representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix-Wankel-Str. 2, 73760 Ost-
fildern, Germany
Printed in Germany
Support
21396-EN-14, 2015-09100XXXX-DE-0X
in Germany
© Pilz GmbH & Co. KG, 2015
KG, 2015
& Co.Printed
Technical support is available from Pilz round the clock.
2015-00
Americas Australia Scandinavia
© Pilz GmbH
0-0-1-3-000,
Brazil +61 3 95446300 +45 74436332
+55 11 97569-2804 Spain
Canada Europe +34 938497433
+1 888-315-PILZ (315-7459) Austria Switzerland
SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks of Pilz GmbH & Co. KG in some countries. We would point out that product features may vary
Mexico +43 1 7986263-0 +41 62 88979-30
CMSE®, InduraNET p®, PAS4000®, PAScal®, PASconfig®, Pilz®, PIT®, PLID®, PMCprimo®, PMCprotego®, PMCtendo®, PMD®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®,
+52 55 5572 1300 Belgium, Luxembourg The Netherlands
USA (toll-free) +32 9 3217575 +31 347 320477
from the details stated in this document, depending on the status at the time of publication and the scope of the equipment. We accept no responsibility for the validity, accuracy
+1 877-PILZUSA (745-9872) France Turkey
+33 3 88104000 +90 216 5775552
Asia Germany United Kingdom
China +49 711 3409-444 +44 1536 462203
+86 21 60880878-216 Ireland
Japan +353 21 4804983 You can reach our
+81 45 471-2281 Italy international hotline on:
South Korea +39 0362 1826711 +49 711 3409-444
+82 31 450 0680 support@pilz.com
and entirety of the text and graphics presented in this information. Please contact our Technical Support if you have any questions.
Pilz develops environmentally-friendly products using
ecological materials and energy-saving technologies.
Offices and production facilities are ecologically designed,
environmentally-aware and energy-saving. So Pilz offers
sustainability, plus the security of using energy-efficient
products and environmentally-friendly solutions.
Partner of:
The Best of
German
Engineering
} Safety relays
Introduction 5
Validity of documentation 5
Using the documentation 5
Definition of symbols 5
Safety 6
Intended use 6
Safety regulations 7
Safety assessment 7
Use of qualified personnel 7
Warranty and liability 7
Disposal 8
For your safety 8
Unit features 8
Safety features 8
Function description 9
Timing diagrams 10
Delay-on de-energisation, not retriggerable 10
Delay-on de-energisation, retriggerable 11
Pulse on switching on 12
Delay-on energisation 13
Installation 13
Wiring 14
Operation 17
Status indicators 18
Fault indicators 18
Faults - malfunctions 19
Dimensions in mm 19
Technical details 19
Safety characteristic data 24
Supplementary data 25
Service life graph 25
Order reference 27
EC declaration of conformity 27
Introduction
Validity of documentation
This documentation is valid for the product PNOZ s9. It is valid until new documentation is
published.
This operating manual explains the function and operation, describes the installation and
provides guidelines on how to connect the product.
Definition of symbols
Information that is particularly important is identified as follows:
DANGER!
This warning must be heeded! It warns of a hazardous situation that poses
an immediate threat of serious injury and death and indicates preventive
measures that can be taken.
WARNING!
This warning must be heeded! It warns of a hazardous situation that could
lead to serious injury and death and indicates preventive measures that can
be taken.
CAUTION!
This refers to a hazard that can lead to a less serious or minor injury plus
material damage, and also provides information on preventive measures
that can be taken.
NOTICE
This describes a situation in which the product or devices could be dam-
aged and also provides information on preventive measures that can be
taken. It also highlights areas within the text that are of particular import-
ance.
INFORMATION
This gives advice on applications and provides information on special fea-
tures.
Safety
Intended use
The unit meets the requirements of EN 60947-5-1, EN 60204-1 and VDE0113-1. In con-
junction with a base unit the unit is used as a
} Contact expansion module to increase the number of contacts available on a base unit.
Base units are all safety relays with feedback loop monitoring.
} Pulse relay
– In accordance with EN ISO 12100 (inching circuit for limited movement of hazard-
ous machine components during installation, set up and positioning)
– In safety circuits in accordance with VDE 0113 and EN 60204-1 (e.g. on movable
guards)
} Safe timer, delay-on energisation
– In accordance with EN ISO 14119 (release with delay through timer)
– In safety circuits in accordance with VDE 0113-1 and EN 60204-1 (e.g. on movable
guards)
} Safe timer, delay-on de-energisation
– In safety circuits in accordance with VDE 0113-1 and EN 60204-1 (e.g. on movable
guards)
The max. achievable safety level depends on the base unit. The expansion module may not
exceed this. The safety-related characteristic values stated under Safety-related character-
istic data [ 25] can only be achieved if the base unit also exhibits these values.
} The unit can also be used without a base unit as a pulse relay or safe timer.
The unit is designed for use with
} Safety relays in the series PNOZsigma, PNOZ X, PNOZelog, PNOZmulti
} Safety gate monitors from the PST series
} Two-hand relays from the PNOZsigma, P2HZ series
The following is deemed improper use in particular:
} Any component, technical or electrical modification to the product
} Use of the product outside the areas described in this manual
} Use of the product outside the technical details (see Technical details [ 19]).
NOTICE
EMC-compliant electrical installation
The product is designed for use in an industrial environment. The product
may cause interference if installed in other environments. If installed in other
environments, measures should be taken to comply with the applicable
standards and directives for the respective installation site with regard to in-
terference.
Safety regulations
Safety assessment
Before using a unit it is necessary to perform a safety assessment in accordance with the
Machinery Directive.
Functional safety is guaranteed for the product as a single component. However, this does
not guarantee the functional safety of the overall plant/machine. In order to achieve the re-
quired safety level for the overall plant/machine, define the safety requirements for the
plant/machine and then define how these must be implemented from a technical and organ-
isational standpoint.
Disposal
} In safety-related applications, please comply with the mission time TM in the safety-re-
lated characteristic data.
} When decommissioning, please comply with local regulations regarding the disposal of
electronic devices (e.g. Electrical and Electronic Equipment Act).
Unit features
} Positive-guided relay outputs, either instantaneous, delay-on de-energisation
(also retriggerable), pulsing or delay-on energisation:
– 3 safety contacts
– 1 auxiliary contact
} Switch-on time, pulse time or delay-on de-energisation selectable with rotary switches
} LED indicator for:
– Supply voltage
– Input status, channel 1
– Input status, channel 2
– Switch status channel 1/2
– Start circuit
– Error
} Plug-in connection terminals (either spring-loaded terminal or screw terminal)
} See order reference for unit types
Safety features
The unit meets the following safety requirements:
} The unit monitors its own output contacts.
} The safety function remains effective in the case of a component failure.
} Earth fault in the feedback loop is detected.
} Earth fault in the input circuit:
The output relays de-energise and the safety contacts open.
Fig.: Centre: Front view with cover, right: Front view without cover
*Safe separation from non-marked area in accordance with EN 60947-1, 6 kV, basic insula-
tion between all safety contacts.
Function description
} Delay-on de-energisation, not retriggerable
If the supply voltage at the input circuit is interrupted, the safety contacts will open once
the set release time has elapsed, even if the safety function is cancelled during the
delay time. The unit cannot be reactivated until the delay time has elapsed.
} Delay-on de-energisation, retriggerable
(only possible as a standalone application or with the PNOZsigma base unit!)
If the supply voltage at the input circuit is interrupted, the safety contacts will open once
the set release time has elapsed.
If the safety function is cancelled during the delay time (e.g. safety gate closed), the unit
will remain active.
} Pulse on switching on
The safety contacts close when supply voltage is applied, the feedback loop is closed
and finally the input circuit is closed. The safety contacts are reopened once the pulse
time has elapsed.
If the input circuit is opened for more than 10 ms during the pulse time, the safety con-
tacts will open immediately and the auxiliary contact will be closed.
} Delay-on energisation
The set delay time is started when supply voltage is applied, the feedback loop is
closed and finally the input circuit is closed.
If the input circuit and feedback loop are closed once the delay time has elapsed, the
safety contacts will close and the auxiliary contact will be opened.
If the input circuit is opened for more than 10 ms, the safety contacts will open immedi-
ately and the auxiliary contact will be closed.
with PNOZsigma base unit:
} Dual-channel operation via PNOZsigma connector
with other base units or without base unit:
} Single-channel operation: one input circuit affects the output relays
Timing diagrams
[1] [2]
POWER
Input
Reset
Output safe
Output aux.
Legend
} POWER: Supply voltage
} Input: Input circuit
} Output safe: Safety contacts
} Output aux: Auxiliary contact
} Reset: Feedback loop input
} t1: Switch-on delay
} tv: Delay time
} [1]: Delay-on de-energisation with the time tv
} [2]: No retriggering in the time tv
NOTICE
At the latest the safety contacts open after the set delay time + 20 ms +
15% of the set value, even in the case of a component failure.
[1] [2]
POWER
Input
Reset
Output safe
Output aux.
Legend
} POWER: Supply voltage
} Input: Input circuit
} Output safe: Safety contacts
} Output aux: Auxiliary contact
} Reset: Feedback loop input
} t1: Switch-on delay
} tv: Delay time
} tges: Overall delay time
} [1]: Delay-on de-energisation with the time tv
} [2]: Retriggering in the time tv for overall delay-on de-energisation tges
NOTICE
At the latest the safety contacts open after the set delay time + 20 ms +
15% of the set value, even in the case of a component failure.
Pulse on switching on
Input
Reset
Output safe
Output aux.
Legend
} POWER: Supply voltage
} Input: Input circuit
} Output safe: Safety contacts
} Output aux: Auxiliary contact
} Reset: Feedback loop input
} t1: Switch-on delay
} t2: Delay-on de-energisation
} tv: Delay time (pulse time)
} [1]: Normal operating cycle
} [2]: Fault: Input circuit opened too early
} [3]: Fault: Feedback loop closed too late
} [4]: Normal operating cycle with supply interruption < 10 ms
NOTICE
At the latest the safety contacts open after the set delay time + 20 ms +
15% of the set value, even in the case of a component failure.
Delay-on energisation
Input
Reset
Output safe
Output aux.
Legend
} POWER: Supply voltage
} Input: Input circuit
} Output safe: Safety contacts
} Output aux: Auxiliary contact
} Reset: Feedback loop input
} t2: Delay-on de-energisation
} tv: Delay time
} [1]: Normal operating cycle
} [2]: Fault: Input circuit opened too early, before tv expired
} [3]: Fault: Feedback loop closed too late after tv elapsed
} [4]: Normal operating cycle with supply interruption < 10 ms
NOTICE
At the earliest the safety contacts close after the set delay time - 20 ms -
15% of the set value, even in the case of a component failure.
Installation
Install contact expansion module without base unit:
} Ensure that the plug terminator is inserted at the side of the unit.
Connect base unit and PNOZsigma contact expansion module:
} Remove the plug terminator at the side of the base unit and at the contact expander
module
} Connect the base unit and the contact expansion module using the connector supplied,
before mounting the units to the DIN rail.
Control cabinet installation
} The safety relay should be installed in a control cabinet with a protection type of at least
IP54.
} Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).
} When installed vertically: Secure the unit by using a fixing element (e.g. retaining
bracket or end angle).
} Push the unit upwards or downwards before lifting it from the DIN rail.
Wiring
Please note:
} Information given in the "Technical details [ 19]" must be followed.
} Outputs 17-18, 27-28, 37-38 are safety contacts; output 45-46 is an auxiliary contact
(e.g. for display).
} Auxiliary contact 45-46 should not be used for safety circuits!
} To prevent contact welding, a fuse should be connected before the output contacts (see
Technical details [ 19]).
} Calculation of the max. cable runs lmax in the input circuit:
Rlmax
Imax =
Rl / km
NOTICE
Do not adjust the rotary switch during operation, otherwise an error mes-
sage will appear, the safety contacts will open and the unit will not be ready
for operation until the supply voltage has been switched off and then on
again.
operating mode delay-on de-en- delay-on de-en- delay-on ener- pulse on switch-
selector switch ergisation, not ergisation, ret- gisation ing on
"mode" retriggerable riggerable
Connection
} Supply voltage
Supply voltage AC DC
A1 L+
A2 L-
INFORMATION
The supply voltage may only be connected as shown in the examples listed
below!
Base unit: 24 V DC 24 V DC
Base unit: 24 V DC 24 V DC
INFORMATION
Feedback loop
The inputs that evaluate the feedback loop will depend on the base unit and
application.
S34
Interface
PNOZ s3
connector.
PNOZsigma
PNOZ s4
Interface
PNOZ s5 PNOZ s1
PNOZ s2
PNOZsigma
Interface
Interface
connector.
PNOZ s6 PNOZ s6.1
INFORMATION
If a base unit and a contact expansion module from the PNOZsigma range
are linked via the connector, no additional wiring is necessary.
Do not connect S32 on the contact expansion module!
} Application
Legend
} S3: Start button
Operation
NOTICE
The safety function should be checked after initial commissioning and each
time the plant/machine is changed. The safety functions may only be
checked by qualified personnel.
The unit is ready for operation when the Power LED is permanently lit.
LEDs indicate the status and errors during operation:
LED on
LED flashes
INFORMATION
Status indicators and error indicators may occur independently. In the case
of an error display, the "Fault" LED will light or flash (exception: "Supply
voltage too low"). An LED that is also flashing indicates the potential cause
of the error. An LED that is lit and is static indicates a normal operating
status. Several status indicators and error indicators may occur simultan-
eously.
Status indicators
POWER
Supply voltage is present.
IN1
Input circuit at S32 is closed.
IN2
Input circuit at S32 is closed.
OUT
Safety contacts are closed.
RESET
24 VDC is present at S34.
OUT
Set delay time is running.
Fault indicators
FAULT
Diagnostics: Plug terminator not connected
} Remedy: Insert plug terminator, switch supply voltage off and then on
again.
With base unit PNOZsigma:
Diagnostics: Input circuit S32 is closed without authorisation
FAULT
Diagnostics: Internal error, unit defective
} Remedy: Switch supply voltage off and then on again, change unit if neces-
sary.
POWER
Diagnostics: Supply voltage too low
} Remedy: Check supply voltage and increase if necessary.
RESET FAULT
Diagnostics: Position of rotary switch is not permitted or rotary switch was ad-
justed during operation.
} Remedy: Switch supply voltage off and then on again.
Faults - malfunctions
} Contact malfunctions: If the contacts have welded, reactivation will not be possible after
the input circuit has opened.
} In the case of an error, the delay-on de-energisation contacts may open before the
delay time has elapsed.
Dimensions in mm
*with spring-loaded terminals
120 (4.72")
98 (3.86")
17,5
* 100 (3,94") (0.69")
Technical details
NOTICE
You must comply with the safety-related characteristic data in order to
achieve the required safety level for your plant/machine.
Operating EN ISO EN ISO EN 62061 EN 62061 IEC 61511 IEC 61511 EN ISO
mode 13849-1: 13849-1: SIL CL PFHD [1/h] SIL PFD 13849-1:
2008 2008 2008
PL Category TM [year]
Safety con-
tacts,
delayed PL e Cat. 4 SIL CL 3 2,34E-09 SIL 3 2,75E-05 20
All the units used within a safety function must be considered when calculating the safety
characteristic data.
INFORMATION
A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.
Supplementary data
CAUTION!
It is essential to consider the relay's service life graphs. The relay outputs'
safety-related characteristic data is only valid if the values in the service life
graphs are met.
The PFH value depends on the switching frequency and the load on the relay output.
If the service life graphs are not accessible, the stated PFH value can be used irrespective
of the switching frequency and the load, as the PFH value already considers the relay's
B10d value as well as the failure rates of the other components.
Cycles x 1000
Example
} Inductive load: 0.2 A
} Utilisation category: AC15
} Contact service life: 2 000 000 cycles
Provided the application to be implemented requires fewer than 2 000 000 cycles, the PFH
value (see Technical details [ 19]) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With DC con-
tactors, use flywheel diodes for spark suppression.
Order reference
Product type Features Connection type Order No.
PNOZ s9 24 VDC Screw terminals 750 109
PNOZ s9 C 24 VDC Spring-loaded terminals 751 109
PNOZ s9 C 24 VDC Spring-loaded terminals 751 189
(coated version)
PNOZ s9 C 24 VDC; 10 pieces Spring-loaded terminals 751 909
EC declaration of conformity
This product/these products meet the requirements of the directive 2006/42/EC for ma-
chinery of the European Parliament and of the Council. The complete EC Declaration of
Conformity is available on the Internet at www.pilz.com/downloads.
Representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix-Wankel-Str. 2, 73760 Ost-
fildern, Germany
Printed in Germany
Support
21401-EN-09, 2015-09100XXXX-DE-0X
in Germany
© Pilz GmbH & Co. KG, 2015
KG, 2015
& Co.Printed
Technical support is available from Pilz round the clock.
2015-00
Americas Australia Scandinavia
© Pilz GmbH
0-0-1-3-000,
Brazil +61 3 95446300 +45 74436332
+55 11 97569-2804 Spain
Canada Europe +34 938497433
+1 888-315-PILZ (315-7459) Austria Switzerland
SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks of Pilz GmbH & Co. KG in some countries. We would point out that product features may vary
Mexico +43 1 7986263-0 +41 62 88979-30
CMSE®, InduraNET p®, PAS4000®, PAScal®, PASconfig®, Pilz®, PIT®, PLID®, PMCprimo®, PMCprotego®, PMCtendo®, PMD®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®,
+52 55 5572 1300 Belgium, Luxembourg The Netherlands
USA (toll-free) +32 9 3217575 +31 347 320477
from the details stated in this document, depending on the status at the time of publication and the scope of the equipment. We accept no responsibility for the validity, accuracy
+1 877-PILZUSA (745-9872) France Turkey
+33 3 88104000 +90 216 5775552
Asia Germany United Kingdom
China +49 711 3409-444 +44 1536 462203
+86 21 60880878-216 Ireland
Japan +353 21 4804983 You can reach our
+81 45 471-2281 Italy international hotline on:
South Korea +39 0362 1826711 +49 711 3409-444
+82 31 450 0680 support@pilz.com
and entirety of the text and graphics presented in this information. Please contact our Technical Support if you have any questions.
Pilz develops environmentally-friendly products using
ecological materials and energy-saving technologies.
Offices and production facilities are ecologically designed,
environmentally-aware and energy-saving. So Pilz offers
sustainability, plus the security of using energy-efficient
products and environmentally-friendly solutions.
Partner of:
The Best of
German
Engineering
Main
Range of product Harmony XB4
Harmony XB5
Product or component Contact block
type
Device short name ZBE
Sale per indivisible 5
quantity
IP degree of protection IP20 conforming to IEC 60529
Contacts type and com- 1 NC
position
Contacts operation Slow-break
Contact block type Single
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Contacts usage Standard contacts
Connections - terminals Screw clamp terminals : >= 1 x 0.22 mm² without ca-
ble end conforming to EN 60947-1
Screw clamp terminals : <= 2 x 1.5 mm² with cable
end conforming to EN 60947-1
Complementary
Terminals description ISO n°1 (11-12)NC
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Product weight 0.011 kg
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Positive opening With positive opening conforming to EN/IEC 60947-5-1 appendix K
Operating travel 4.3 mm (total travel)
1.5 mm (NC changing electrical state)
Operating force 2 N (NC changing electrical state)
Mechanical durability 5000000 cycles
Tightening torque 0.8...1.2 N.m conforming to EN 60947-1
Shape of screw head Slotted head compatible with flat Ø 5.5 mm screwdriver
Slotted head compatible with flat Ø 4 mm screwdriver
Cross head compatible with pozidriv No 1 screwdriver
Cross head compatible with Philips no 1 screwdriver
Contacts material Silver alloy (Ag/Ni)
Short circuit protection 10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
[Ith] conventional free air thermal current 10 A conforming to EN/IEC 60947-5-1
[Ui] rated insulation voltage 600 V (degree of pollution: 3) conforming to EN 60947-1
[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-1
[Ie] rated operational current 1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
Electrical durability 1000000 cycles, DC-13, 0.5 A at 24 V, operating rate: 3600 cyc/h, load factor: 0.5
conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.2 A at 110 V, operating rate: 3600 cyc/h, load factor:
0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 4 A at 24 V, operating rate: 3600 cyc/h, load factor: 0.5
conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 120 V, operating rate: 3600 cyc/h, load factor: 0.5
conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 2 A at 230 V, operating rate: 3600 cyc/h, load factor: 0.5
conforming to EN/IEC 60947-5-1 appendix C
Electrical reliability IEC 60947-5-4 Λ < 10exp(-8) at 17 V, 5 mA in clean environment conforming to EN/IEC
60947-5-4
Λ < 10exp(-7) at 5 V, 1 mA in clean environment conforming to EN/IEC
60947-5-4
Environment
Protective treatment TH
Ambient air temperature for storage -40...70 °C
Ambient air temperature for operation -25...70 °C
Standards EN/IEC 60947-1
EN/IEC 60947-5-1
EN/IEC 60947-5-4
JIS C 4520
UL 508
CSA C22.2 No 14
Product certifications BV
CCC
CSA
DNV
GL
GOST
LROS (Lloyds register of shipping)
RINA
UL
Vibration resistance 5 gn (f = 2...500 Hz) conforming to IEC 60068-2-6
Shock resistance 50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC
60068-2-27
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC
60068-2-27
2
Product data sheet ZBE102
Dimensions Drawings
Dimensions
3
Product data sheet ZB4BS844
Characteristics red Ø40 Emergency stop,switching off head
Ø22 trigger and latching turn release
Main
Range of product Harmony XB4
Product or component Head for emergency switching off push-button
type
Device short name ZB4
Bezel material Chromium plated metal
Mounting diameter 22 mm
Sale per indivisible 1
quantity
Shape of signaling unit Round
head
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Type of operator Trigger action and mechanical latching
Reset Turn to release
Operator profile Red mushroom Ø 40 mm unmarked
Complementary
CAD overall width 40 mm
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
CAD overall height 40 mm
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
CAD overall depth 57 mm
Product weight 0.073 kg
Mechanical durability 300000 cycles
Electrical composition code C10 for <= 4 contacts using single and double blocks in front mounting
C15 for 1 contacts using single blocks in front mounting
C11 for <= 3 contacts using single blocks in front mounting
C8 for <= 4 contacts using single and double blocks in front mounting
C7 for <= 4 contacts using single blocks in front mounting
Environment
Protective treatment TH
Ambient air temperature for storage -40...70 °C
Ambient air temperature for operation -25...70 °C
Class of protection against electric shock Class I conforming to IEC 61140
IP degree of protection IP66 conforming to IEC 60529
NEMA degree of protection NEMA 12
NEMA 4
NEMA 4X
NEMA 13
IK degree of protection IK03 conforming to IEC 50102
Standards EN/IEC 60204-1
EN/IEC 60947-1
EN/IEC 60947-5-1
EN/IEC 60947-5-4
EN/IEC 60947-5-5
EN/ISO 13850
IEC 60364-5-53
JIS C 4520
UL 508
GB 14048.5
CSA C22.2 No 14
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW)
Compliant - since 0810 - Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Product environmental profile Available Download Product Environmental
Product end of life instructions Need no specific recycling operations
2
Product data sheet ZB4BS844
Dimensions Drawings
Dimensions
3
Product data sheet ZB4BS844
Mounting and Clearance
Panel Cut-out for Pushbuttons, Switches and Pilot Lights (Finished Holes, Ready for Installation)
Pushbuttons, Switches and Pilot Lights for Printed Circuit Board Connection
4
Printed Circuit Board Cut-outs (Viewed from Electrical Block Side)
Dimensions in mm
A: 30 mm min.
B: 40 mm min.
Dimensions in in.
A: 1.18 in. min.
B: 1.57 in. min.
Installation Precautions
● Minimum thickness of circuit board: 1.6 mm / 0.06 in.
● Cut-out diameter: 22.4 mm ± 0.1 / 0.88 in. ± 0.004
● Orientation of body/fixing collar ZB4 BZ009: ± 2°30’ (excluding cut-outs marked a and b).
● Tightening torque of screws ZBZ 006: 0.6 N.m (5.3 lbf.in) max.
● Allow for one ZB4 BZ079 fixing collar/pillar and its fixing screws:
○ every 90 mm / 3.54 in. horizontally (X), and 120 mm / 4.72 in. vertically (Y).
○ with each selector switch head (ZB4 BD•, ZB4 BJ•, ZB4 BG•).
The fixing centers marked a and b are diagonally opposed and must align with those marked 4 and 5.
5
(1) Panel
(2) Printed circuit board
Dimensions An + 18.1 relate to the Ø 2.4 mm ± 0.05 / 0.09 in. ± 0.002 holes for centring adapter ZBZ 01•.
6
Product data sheet ZB4BS844
Technical Description
1 N/O
1 N/C
7
Legend
Single contact
Double contact
Light block
Possible location
8
Product data sheet ZB4BZ103
Characteristics single contact block with body/fixing collar 2NO
screw clamp terminal
Main
Range of product Harmony XB4
Product or component Complete body/contact assembly
type
Device short name ZB4
Fixing collar material Zamak
Sale per indivisible 1
quantity
Contacts type and com- 2 NO
position
Contacts operation Slow-break
Contact block type Single
Additional information With body/fixing collar
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Connections - terminals Screw clamp terminals : >= 1 x 0.22 mm² without ca-
ble end conforming to EN 60947-1
Screw clamp terminals : <= 2 x 1.5 mm² with cable
end conforming to EN 60947-1
Complementary
CAD overall width 30 mm
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
CAD overall height 47 mm
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
CAD overall depth 37 mm
Terminals description ISO n°1 (13-14)NO
Product weight 0.062 kg
Contacts usage Standard contacts
Positive opening Without positive opening
Operating travel 4.3 mm (total travel)
2.6 mm (NO changing electrical state)
Operating torque 0.05 N.m (NO changing electrical state)
Mechanical durability 5000000 cycles
Tightening torque 0.8...1.2 N.m conforming to EN 60947-1
Shape of screw head Slotted head compatible with flat Ø 5.5 mm screwdriver
Slotted head compatible with flat Ø 4 mm screwdriver
Cross head compatible with pozidriv No 1 screwdriver
Cross head compatible with Philips no 1 screwdriver
Contacts material Silver alloy (Ag/Ni)
Short circuit protection 10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
[Ith] conventional free air thermal current 10 A conforming to EN/IEC 60947-5-1
[Ui] rated insulation voltage 600 V (degree of pollution: 3) conforming to EN 60947-1
[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-1
[Ie] rated operational current 1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
Environment
Protective treatment TH
Ambient air temperature for storage -40...70 °C
Ambient air temperature for operation -25...70 °C
IP degree of protection IP20 conforming to IEC 60529
Standards EN/IEC 60947-1
EN/IEC 60947-5-1
EN/IEC 60947-5-4
EN/IEC 60947-5-5
JIS C 4520
UL 508
CSA C22.2 No 14
Product certifications BV
CSA
DNV
GL
LROS (Lloyds register of shipping)
RINA
UL
Vibration resistance 5 gn (f = 2...500 Hz) conforming to IEC 60068-2-6
Shock resistance 50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC
60068-2-27
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC
60068-2-27
2
Product data sheet ZB4BZ103
Dimensions Drawings
Dimensions
3
Product data sheet ZB4BZ103
Mounting and Clearance
Panel Cut-out for Pushbuttons, Switches and Pilot Lights (Finished Holes, Ready for Installation)
4
Product data sheet ZB4BZ104
Characteristics single contact block with body/fixing collar 2NC
screw clamp terminal
Main
Range of product Harmony XB4
Product or component Complete body/contact assembly
type
Device short name ZB4
Fixing collar material Zamak
Sale per indivisible 1
quantity
Contacts type and com- 2 NC
position
Contacts operation Slow-break
Contact block type Single
Additional information With body/fixing collar
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Connections - terminals Screw clamp terminals : >= 1 x 0.22 mm² without ca-
ble end conforming to EN 60947-1
Screw clamp terminals : <= 2 x 1.5 mm² with cable
end conforming to EN 60947-1
Complementary
CAD overall width 30 mm
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
CAD overall height 47 mm
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
CAD overall depth 37 mm
Terminals description ISO n°1 (11-12)NC
Product weight 0.062 kg
Contacts usage Standard contacts
Positive opening With positive opening conforming to EN/IEC 60947-5-1 appendix K
Operating travel 4.3 mm (total travel)
1.5 mm (NC changing electrical state)
Mechanical durability 5000000 cycles
Tightening torque 0.8...1.2 N.m conforming to EN 60947-1
Shape of screw head Slotted head compatible with flat Ø 5.5 mm screwdriver
Slotted head compatible with flat Ø 4 mm screwdriver
Cross head compatible with pozidriv No 1 screwdriver
Cross head compatible with Philips no 1 screwdriver
Contacts material Silver alloy (Ag/Ni)
Short circuit protection 10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
[Ith] conventional free air thermal current 10 A conforming to EN/IEC 60947-5-1
[Ui] rated insulation voltage 600 V (degree of pollution: 3) conforming to EN 60947-1
[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-1
[Ie] rated operational current 1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
Environment
Protective treatment TH
Ambient air temperature for storage -40...70 °C
Ambient air temperature for operation -25...70 °C
IP degree of protection IP20 conforming to IEC 60529
Standards EN/IEC 60947-1
EN/IEC 60947-5-1
EN/IEC 60947-5-4
EN/IEC 60947-5-5
JIS C 4520
UL 508
CSA C22.2 No 14
Product certifications BV
CSA
DNV
GL
LROS (Lloyds register of shipping)
RINA
UL
Vibration resistance 5 gn (f = 2...500 Hz) conforming to IEC 60068-2-6
Shock resistance 50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC
60068-2-27
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC
60068-2-27
2
Product data sheet ZB4BZ104
Dimensions Drawings
Dimensions
3
Product data sheet ZB4BZ104
Mounting and Clearance
Panel Cut-out for Pushbuttons, Switches and Pilot Lights (Finished Holes, Ready for Installation)
4
https://www.phoenixcontact.com/us/products/2985688
Safety-related digital input module, IP20 protection, for the SafetyBridge, INTERBUS-Safety, and PROFIsafe
system. The module has 4 safe digital inputs for two-channel assignment or 8 safe digital inputs for single-
channel assignment.
Product Description
The safety module is an input module from the Inline product range, designed for use in a SafetyBridge, INTERBUS-Safety or PROFIsafe system.
The safety module can be used as part of an Inline station at any point within a SafetyBridge, INTERBUS-Safety or PROFIsafe Inline system. The
transmission speed of the safety module can be set to 500 kbaud or 2 Mbaud using a switch. Only one transmission speed must be used uniformly
within a station. The module has four safe digital inputs for two-channel assignment or eight safe digital inputs for single-channel assignment. The inputs
can be parameterized according to the application and enable the integration of sensors in the safe SafetyBridge, INTERBUS (INTERBUS-Safety), and
PROFIsafe system. Depending on the installation and parameterization, in these systems the safety module can achieve the following safety integrity:
– Up to category 4 according to standard EN 954-1
– Up to SIL 3 according to standards EN 61508 and EN 62061
– Up to PL e according to standard EN ISO 13849-1
Product Features
■ SIL 3 according to IEC 61508/EN 61508
Technical data
Note
EMC: class A product, see manufacturer's declaration in the download
Utilization restriction
area
Dimensions
Width 48.8 mm
Height 119.8 mm
Depth 71.5 mm
Note on dimensions Housing dimensions
05/26/2016 Page 1 / 5
https://www.phoenixcontact.com/us/products/2985688
Interfaces
Fieldbus system INTERBUS
Designation Inline local bus
Connection method Inline data jumper
Transmission speed 500 kBit/s 2MBit/s (can be switched)
Digital inputs
Input name Digital inputs
Connection method Spring-cage connection
2, 3, 4-wire
Number of inputs 4 (with two-channel assignment)
8 (for single-channel assignment)
Typical response time See technical data
Input characteristic curve IEC 61131-2 type 3
Input voltage 24 V DC (via clock outputs UT1 and UT2 or external supply)
Input voltage range "0" signal -3 V DC ... 5 V DC
Input voltage range "1" signal 11 V DC ... 30 V DC
Input voltage range -3 V DC ... 30 V DC
Typical input current per channel 4.2 mA (at 24 V)
General
Mounting type DIN rail
Net weight 349.4 g
Note on weight specifications with connectors
05/26/2016 Page 2 / 5
https://www.phoenixcontact.com/us/products/2985688
Classifications
eCl@ss
05/26/2016 Page 3 / 5
https://www.phoenixcontact.com/us/products/2985688
ETIM
UNSPSC
Approvals
Approvals
Approvals
Ex Approvals
Approvals submitted
Approval details
UL Listed
cUL Listed
05/26/2016 Page 4 / 5
https://www.phoenixcontact.com/us/products/2985688
Functional Safety
PROFIsafe
cULus Listed
05/26/2016 Page 5 / 5
https://www.phoenixcontact.com/in/products/2700606
Safety-related digital output module, IP20 protection, for the SafetyBridge system. The module has four safe
digital outputs with two-channel occupancy or 8 safe digital outputs with single-channel occupancy
Product Description
The safety module is an output module from the Inline product range, designed for use in a SafetyBridge technology system. The safety module
®
can be used as part of an Inline station at any point within an INTERBUS, DeviceNet™, CANopen , EtherNet/IP™, Sercos, Modbus, PROFINET
or PROFIBUS system. The transmission speed of the safety module can be set to 500 kbaud or 2 Mbaud using a switch. One transmission speed
must be used consistently within a station. The module has four safe digital outputs for two-channel assignment or eight safe digital outputs for
single-channel assignment. Depending on the installation and parameterization, in the SafetyBridge system the safety module can achieve the
following safety integrity:
- Up to SIL 3 according to standard EN 61508
- Up to SIL CL 3 according to standard EN 62061
- Up to Cat. 4/PL e according to standard EN ISO 13849-1
Product Features
■ Generation and monitoring of the SafetyBridge protocol
GTIN
Technical data
Note
EMC: class A product, see manufacturer's declaration in the download
Utilization restriction
area
Dimensions
Width 48.8 mm
Height 119.8 mm
Depth 71.5 mm
Note on dimensions Housing dimensions
Ambient conditions
Ambient temperature (operation) -25 °C ... 55 °C
05/23/2016 Page 1 / 7
https://www.phoenixcontact.com/in/products/2700606
Interfaces
Fieldbus system INTERBUS
Designation Inline local bus
Connection method Inline data jumper
Transmission speed 500 kBit/s / 2MBit/s (can be switched)
Digital outputs
Output name Digital outputs
Connection method Spring-cage connection
2, 3, 4-wire
Number of outputs 4 (with two-channel assignment)
8
Protective circuit Overload protection, short-circuit protection of outputs
Output voltage 24 V DC (US - 1 V)
Nominal output voltage 24 V DC
Output current max. 6 A (Total current of all outputs, -25 °C ... 50 °C)
max. 4 A (Total current of all outputs, >50 °C ... 55 °C)
Maximum output current per channel 2A
Maximum output current per group 3A
Nominal load, inductive see safety data
Nominal load, lamp see safety data
Nominal load, ohmic see safety data
General
Mounting type DIN rail
Net weight 353.1 g
Note on weight specifications with connectors
Short-circuit / overload of the digital outputs Error message in
Diagnostics messages
diagnostics code (bus) and display by means of the LED on the motor
05/23/2016 Page 2 / 7
https://www.phoenixcontact.com/in/products/2700606
SafetyBridge properties
Connection to I/O modules max. 5 (safe digital I/O modules)
Logic memory 24 kByte
Classifications
eCl@ss
UNSPSC
Approvals
Approvals
Approvals
Ex Approvals
Approvals submitted
Approval details
UL Listed
cUL Listed
Functional Safety
cULus Listed
05/23/2016 Page 4 / 7
https://www.phoenixcontact.com/in/products/2700606
Documentation
Terminal block for filtering test pulses from safe semiconductor outputs with adjustable filter values (20 µF/86 µF), as
well as for EMC filtering of 24 V signals up to an amperage of 2 A.
05/23/2016 Page 5 / 7
https://www.phoenixcontact.com/in/products/2700606
Terminal block for filtering test pulses from safe semiconductor outputs with adjustable filter values (1.5 µF/11.5 µF),
as well as for EMC filtering of 24 V signals up to an amperage of 2 A.
Labeling panel
Parameterization memory
Program and configuration memory, plug-in, 2 GB, with license key and application program for easy web-based
configuration and startup of a SafetyBridge solution.
Program and configuration memory, plug-in, 2 GB, with license key and application program for easy web-based
configuration and startup of a SafetyBridge solution including communication via Modbus/TCP, PROFINET, and e-
mail.
Terminal marking
05/23/2016 Page 6 / 7
https://www.phoenixcontact.com/in/products/2700606
Insert strip, Sheet, white, unlabeled, can be labeled with: Office printing systems, Plotter: Laser printer, Mounting
type: Insert, Lettering field: 62 x 10 mm
Insert strip, Sheet, white, unlabeled, can be labeled with: Office printing systems, Plotter: Laser printer, Mounting
type: Insert, Lettering field: 62 x 46 mm
05/23/2016 Page 7 / 7
https://www.phoenixcontact.com/us/products/2700973
The Inline controller offers the option of communicating via PROFINET and Modbus/TCP. Programming is carried
out using PC Worx Express or PC Worx (IEC 61131-3).
Product Description
The ILC 131 ETH modular small-scale controller for the Inline I/O system is at the heart of Easy Automation. The ILC 1X1 series is characterized by its
support for the Modbus/TCP and PROFINET Ethernet-based protocols. A new feature is the support for an optional SD card.
Product Features
■ PROFINET-Device
■ Modbus/TCP-Client
■ Numerous protocols supported such as: http, https, FTP, SNTP, SNMP, SMTP, SQL, MySQL, DCP, etc.
■ Modbus/TCP server
■ HTML 5
Technical data
Note
05/26/2016 Page 1 / 5
https://www.phoenixcontact.com/us/products/2700973
Dimensions
Width 80 mm
Height 119.8 mm
Depth 71.5 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above mean sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above mean sea level)
Shock 25g, Criterion 1, according to IEC 60068-2-27
Vibration (operation) 5g
Control system
Programming tool PC WORX / PC WORX EXPRESS
Diagnostics tool DIAG+
Configuration tool Config+ Version 1.01 or later
Mechanical design
Weight 285 g
Diagnostics display No
Controller redundancy No
Data interfaces
Interface INTERBUS local bus (master)
Connection method Inline data jumper
Transmission speed 500 kBaud / 2 MBaud (can be switched)
Interface Parameterization/operation/diagnostics
Connection method RS-232-C, 6-pos. MINI-DIN socket (PS/2), Ethernet 10/100 (RJ45)
Transmission speed max. 115,2 kBit/s
Interface Ethernet 10Base-T/100Base-TX
Connection method RJ45 socket
Transmission speed 10/100 MBit/s
PROFINET
05/26/2016 Page 2 / 5
https://www.phoenixcontact.com/us/products/2700973
Power supply
Typical current consumption 210 mA
Max. current consumption 870 mA (370 mA communications power + 500 mA analog voltage supply)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC
Residual ripple ±5%
Power dissipation max. 5 W
Fieldbus function
Amount of process data max. 2048 Bit (INTERBUS)
max. 8192 Bit (internal Modbus /TCP client)
Number of supported devices max. 63
Number of local bus devices that can be connected max. 63 (observe current consumption)
Number of devices with parameter channel max. 8
Direct I/Os
Input name Digital inputs
Number of inputs 8
Connection method Inline potential distributor
Description of the input EN 61131-2 type 1 NPN/PNP
Output name Digital outputs
Number of outputs 4
Connection method 2, 3, 4-wire
Maximum output current per channel 500 mA
Without analog input yes
Without analog output yes
Without pulse direction output yes
Without counter input yes
General data
05/26/2016 Page 3 / 5
https://www.phoenixcontact.com/us/products/2700973
Classifications
eCl@ss
ETIM
UNSPSC
Approvals
Approvals
Approvals
UL Listed / cUL Listed / RINA / BSH / LR / BV / ABS / EAC / EAC / cULus Listed
05/26/2016 Page 4 / 5
https://www.phoenixcontact.com/us/products/2700973
Ex Approvals
Approvals submitted
Approval details
UL Listed
cUL Listed
RINA
BSH
LR
BV
ABS
EAC
EAC
cULus Listed
05/26/2016 Page 5 / 5
https://www.phoenixcontact.com/us/products/2988162
Similar figure
Product Description
Program and configuration memory to save the application programs and other files in the file system of the PLC.
Alternatively, a program and configuration memory with integrated license is available to disconnect various function blocks.
Product Features
■ Program and configuration memory, plug-in, 2 Gbytes
■ For storing application programs and other files in the file system of the PLC
Technical data
Classifications
eCl@ss
05/26/2016 Page 1 / 2
https://www.phoenixcontact.com/us/products/2988162
UNSPSC
05/26/2016 Page 2 / 2
4.
POWER SUPPLY
https://www.phoenixcontact.com/us/products/2866417
Energy storage - MINI-BAT/24DC/1.3AH - 2866417
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Energy storage device, lead AGM, VRLA technology, 24 V DC, 1.3 Ah.
Technical data
Dimensions
Width 52 mm
Height 130 mm
Depth 110 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) 0 °C ... 40 °C
Ambient temperature (storage/transport) 0 °C ... 40 °C
Max. permissible relative humidity (operation) 95 %
Input data
Nominal input voltage 24 V DC
Buffer period 20 min. (2 A)
5 min. (5 A)
Output data
Nominal output voltage 24 V DC
Output current Imax 15 A
06/15/2016 Page 1 / 4
https://www.phoenixcontact.com/us/products/2866417
Energy storage - MINI-BAT/24DC/1.3AH - 2866417
Technical data
Output data
Connection in parallel 5
Connection in series No
Output fuse 1x 15 A
General
IQ technology No
Used batteries must not be thrown away with household waste, they
should instead be disposed of in accordance with applicable national
Disposal
regulations. They can also be returned to Phoenix Contact or the
manufacturer.
Net weight 1.7 kg
Protection class III
Classifications
eCl@ss
ETIM
UNSPSC
06/15/2016 Page 2 / 4
https://www.phoenixcontact.com/us/products/2866417
Energy storage - MINI-BAT/24DC/1.3AH - 2866417
Approvals
Approvals
Approvals
EAC / EAC
Ex Approvals
Approvals submitted
Approval details
EAC
EAC
Accessories
Accessories
Assembly adapter
Assembly adapters - QUINT-PS-ADAPTERS7/1 - 2938196
Fuse
06/15/2016 Page 3 / 4
https://www.phoenixcontact.com/us/products/2866417
Energy storage - MINI-BAT/24DC/1.3AH - 2866417
Accessories
Flat-type plug-in fuse, type C, color code: light blue, nominal current: 15 A
Drawings
Block diagram
06/15/2016 Page 4 / 4
https://www.phoenixcontact.com/us/products/2866446
Primary-switched MINI POWER power supply for DIN rail mounting, input: 1-phase, output: 24 V DC/1.3 A
Product Description
MINI POWER power supplies for MCR technology
In measurement and control technology (MCR), modular electronics housing has become the industry standard. MINI POWER is the power supply unit
to go with it. The devices are flexible, thanks to special voltages and special versions.
Product Features
■ Easy-maintenance connection technology thanks to keyed COMBICON connectors
Technical data
Dimensions
Width 22.5 mm
Height 99 mm
Depth 107 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
05/08/2016 Page 1 / 7
https://www.phoenixcontact.com/us/products/2866446
Input data
Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 85 V AC ... 264 V AC
90 V DC ... 350 V DC
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Current consumption 0.55 A (100 V AC)
0.23 A (240 V AC)
Inrush surge current < 15 A (< 0.6 A s)
2
Output data
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 22.5 V DC ... 28.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 1.3 A (-25 °C ... 60 °C)
POWER BOOST (IBoost) 1.6 A (-25°C ... 40°C permanent )
Derating 60 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series Yes
Starting delay with capacitive load Unrestricted
Max. capacitive load Unlimited
Active current limitation Approx. 5 A (for short-circuit)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 3 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 20 mVPP (20 MHz)
Output power 31.2 W
Typical response time <1s
Peak switching voltages nominal load < 50 mVPP (20 MHz)
Maximum power dissipation in no-load condition 1.4 W
Power loss nominal load max. 4.5 W
05/08/2016 Page 2 / 7
https://www.phoenixcontact.com/us/products/2866446
05/08/2016 Page 3 / 7
https://www.phoenixcontact.com/us/products/2866446
Classifications
eCl@ss
05/08/2016 Page 4 / 7
https://www.phoenixcontact.com/us/products/2866446
UNSPSC
Approvals
Approvals
Approvals
UL Listed / cUL Listed / UL Recognized / cUL Recognized / EAC / EAC / UL Listed / cUL Listed / cULus Recognized / cULus Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
cUL Listed
05/08/2016 Page 5 / 7
https://www.phoenixcontact.com/us/products/2866446
UL Recognized
cUL Recognized
EAC
EAC
UL Listed
cUL Listed
cULus Recognized
cULus Listed
Drawings
L (+)
NC
NC DC OK
N (-)
99
05/08/2016 Page 6 / 7
https://www.phoenixcontact.com/us/products/2866446
05/08/2016 Page 7 / 7
https://www.phoenixcontact.com/us/products/2866705
Primary-switched QUINT POWER power supply for DIN rail mounting with SFB (Selective Fuse Breaking)
Technology, input: 3-phase, output: 24 V DC/10 A
Product Description
QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective system
protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states
before errors occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 5 V
DC ... 56 V DC are covered.
Product Features
■ High level of system availability even in the event of permanent phase failure
Technical data
Dimensions
Width 60 mm
Height 130 mm
Depth 125 mm
Width with alternative assembly 122 mm
Height with alternative assembly 130 mm
Depth with alternative assembly 63 mm
05/26/2016 Page 1 / 8
https://www.phoenixcontact.com/us/products/2866705
Input data
Nominal input voltage range 3x 400 V AC ... 500 V AC
Input voltage range 3x 320 V AC ... 575 V AC
2x 360 V AC ... 575 V AC
450 V DC ... 800 V DC
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Discharge current to PE < 3.5 mA
Current consumption 3x 1.2 A (400 V AC)
3x 1 A (500 V AC)
0.4 A (600 V DC)
Inrush surge current < 15 A (typical)
Power failure bypass > 30 ms (400 V AC)
> 46 ms (500 V AC)
Choice of suitable circuit breakers 6 A ... 16 A (AC: Characteristics B, C, D, K)
Type of protection Transient surge protection
Protective circuit/component Varistor, gas-filled surge arrester
Output data
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 10 A (-25°C ... 60°C, UOUT = 24 V DC)
POWER BOOST (IBoost) 15 A (-25°C ... 40°C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB) 60 A (12 ms)
Derating 60 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series Yes
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 3 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 20 mVPP (with nominal values)
05/26/2016 Page 2 / 8
https://www.phoenixcontact.com/us/products/2866705
General
Net weight 1.1 kg
Operating voltage display Green LED
Efficiency > 93 % (at 400 V AC and nominal values)
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Protection class I
MTBF (IEC 61709, SN 29500) > 1100000 h (25 °C)
> 630000 h (40°C)
> 280000 s (60°C)
Mounting position horizontal DIN rail NS 35, EN 60715
Alignable: 5 mm horizontally, 15 mm next to active components, 50 mm
Assembly instructions
vertically
05/26/2016 Page 3 / 8
https://www.phoenixcontact.com/us/products/2866705
05/26/2016 Page 4 / 8
https://www.phoenixcontact.com/us/products/2866705
Classifications
eCl@ss
ETIM
UNSPSC
Approvals
Approvals
Approvals
CSA / UL Recognized / UL Listed / cUL Recognized / LR / GL / BV / DNV / ABS / NK / RINA / BSH / IECEE CB Scheme / SEMI F47 / IECEE CB
Scheme / EAC / EAC / GL / BV / ABS / NK / RINA / BSH / SEMI F47 / cULus Recognized
05/26/2016 Page 5 / 8
https://www.phoenixcontact.com/us/products/2866705
Ex Approvals
Approvals submitted
Approval details
CSA
UL Recognized
UL Listed
cUL Recognized
LR
GL
BV
DNV
ABS
NK
RINA
05/26/2016 Page 6 / 8
https://www.phoenixcontact.com/us/products/2866705
BSH
IECEE CB Scheme
SEMI F47
IECEE CB Scheme
EAC
EAC
GL
BV
ABS
NK
RINA
BSH
SEMI F47
cULus Recognized
Drawings
05/26/2016 Page 7 / 8
https://www.phoenixcontact.com/us/products/2866705
L1 (+)
L2
L3 (-)
DC OK
I < IN
13
14
05/26/2016 Page 8 / 8
https://www.phoenixcontact.com/us/products/2866611
Uninterruptible power supply with integrated power supply unit, 5A, in combination with MINI-BAT/24/DC/1.3 AH,
QUINT-BAT/24DC 3,4AH, 7,2AH or 12 AH
Technical data
Dimensions
Width 60 mm
Height 130 mm
Depth 118 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport) -40 °C ... 80 °C
Max. permissible relative humidity (operation) 95 % (at 25 °C, non-condensing)
Noise immunity EN 61000-6-2:2005
Input data
Nominal input voltage range 100 V AC ... 240 V AC
AC input voltage range 85 V AC ... 264 V AC (Derating < 90 V AC: 2.5%V)
Input voltage range DC 100 V DC ... 350 V DC (UL508: 100 ... 250 V)
adjustable: 0.5 min; 1 min; 2 min; 3 min; 5 min; 10 min; 15 min; 20 min;
Buffer time
PC-Mode
Current consumption 1.1 A (230 V AC, maximum)
06/15/2016 Page 1 / 11
https://www.phoenixcontact.com/us/products/2866611
Output data
Nominal output voltage 24 V DC
22.5 V DC ... 29.5 V DC (Network operation; in the buffer mode, dependent
Setting range of the output voltage (USet)
on the battery voltage of 27.9 V DC ... 19.2 V DC)
Nominal output current (IN) 5 A (-25°C ... 55°C)
Derating 55 °C ... 70 °C (2.5%/K)
Output current limit max. 6 A (Mains operation)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Efficiency > 88 % (230 V AC, network operation)
> 86 % (120 V AC, network operation)
> 86 % (Battery operation)
Residual ripple < 10 mVPP
Peak switching voltages nominal load < 25 mVPP
Connection in parallel Yes, 2
Surge protection against internal surge voltages Yes, < 35 V DC
Feedback resistance 35 V DC
General
IQ technology No
Net weight 1.1 kg
Memory medium External, battery 1.3 Ah / 3.4 Ah / 7.2 Ah / 12 Ah
Operating mode
Insulation voltage input/output 4 kV (type test)
2 kV (Routine test)
Protection class I
> 596000 h (40°C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions Can be aligned: Horizontally 0 mm, vertically 50 mm
Charging process
Charge characteristic curve I/U characteristic curve
Battery presence check/time interval 60 s
Charge current 0.2 A ... 1.5 A (Default 1.0 A)
End-of-charge voltage 25 V DC ... 30 V DC (Default 27.6 V DC)
Temperature compensation 0 mV/K ... 200 mV/K (42 mV/K by default)
Quality check of battery 4 h ... 200 h (Default 12 h)
Deep discharge protection 18 V DC ... 21 V DC (Default 19.2 V DC)
Alarm signaling threshold 18 V DC ... 30 V DC (Default 20.4 V DC)
06/15/2016 Page 3 / 11
https://www.phoenixcontact.com/us/products/2866611
Classifications
eCl@ss
ETIM
UNSPSC
Approvals
Approvals
Approvals
UL Recognized / UL Listed / cUL Recognized / cUL Listed / EAC / EAC / cULus Recognized / cULus Listed
Ex Approvals
Approvals submitted
Approval details
UL Recognized
UL Listed
06/15/2016 Page 5 / 11
https://www.phoenixcontact.com/us/products/2866611
cUL Recognized
cUL Listed
EAC
EAC
cULus Recognized
cULus Listed
Accessories
Accessories
Assembly adapter
Assembly adapters - QUINT-PS-ADAPTERS7/2 - 2938206
06/15/2016 Page 6 / 11
https://www.phoenixcontact.com/us/products/2866611
Energy storage - MINI-BAT/24DC/1.3AH - 2866417
Energy storage device, lead AGM, VRLA technology, 24 V DC, 1.3 Ah.
Energy storage device, lead AGM, VRLA technology, 24 V DC, 3.4 Ah. Connection via pin cable lug, 14 mm.
Energy storage device, lead AGM, VRLA technology, 24 V DC, 7.2 Ah. Connection via pin cable lug, 14 mm.
Energy storage - QUINT-BAT/24DC/12AH - 2866365
Energy storage device, lead AGM, VRLA technology, 24 V DC, 12 Ah. Connection via pin cable lug, 14 mm.
Energy storage - UPS-BAT/VRLA/24DC/1.3AH - 2320296
Energy storage device, lead AGM, VRLA technology, 24 V DC, 1.3 Ah, tool-free battery replacement, automatic
detection, and communication with QUINT UPS-IQ
06/15/2016 Page 7 / 11
https://www.phoenixcontact.com/us/products/2866611
Energy storage - UPS-BAT/VRLA/24DC/3.4AH - 2320306
Energy storage device, lead AGM, VRLA technology, 24 V DC, 3.4 Ah, tool-free battery replacement, automatic
detection, and communication with QUINT UPS-IQ
Energy storage - UPS-BAT/VRLA/24DC/7.2AH - 2320319
Energy storage device, lead AGM, VRLA technology, 24 V DC, 7.2 Ah, tool-free battery replacement, automatic
detection, and communication with QUINT UPS-IQ
Energy storage - UPS-BAT/VRLA/24DC/12AH - 2320322
Energy storage device, lead AGM, VRLA technology, 24 V DC, 12 Ah, tool-free battery replacement, automatic detection,
and communication with QUINT UPS-IQ
Fuse
Flat-type plug-in fuse, type C, color code: light blue, nominal current: 15 A
06/15/2016 Page 8 / 11
https://www.phoenixcontact.com/us/products/2866611
Memory block - IFS-CONFSTICK - 2986122
Multi-functional memory block for the INTERFACE systemf for easy storage and backup of the configuration.
Programming adapter
Programming adapter - IFS-USB-PROG-ADAPTER - 2811271
Programming adapter with USB interface, for programming with software. The USB driver is included in the software
solutions for the products to be programmed, such as measuring transducers or motor managers.
Drawings
10
2x 12V
Battery R1 Remote
On/Off
R2
Alarm
1
Bat.-Mode 60 3
Bat.-Charge
1
Time [min]
L (+) 2
Output DC 10
PS
N (-) 24 V 5 A 1 = 1,3Ah
2 = 3,4Ah
3 = 7,2Ah
4 = 12Ah
1
0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5
Current [A]
06/15/2016 Page 9 / 11
https://www.phoenixcontact.com/us/products/2866611
06/15/2016 Page 10 / 11
https://www.phoenixcontact.com/us/products/2866611
06/15/2016 Page 11 / 11
Data sheet 6ES7307-1EA01-0AA0
POWER SUPPLY PS307 24 V/5 A
SIMATIC S7-300 STABILIZED POWER SUPPLY PS307 INPUT:
120/230 V AC OUTPUT: DC 24 V DC/5 A
Input
Input 1-phase AC
Supply voltage
● 1 at AC Rated value 120 V
● 2 at AC Rated value 230 V
● Note Automatic range selection
Input voltage
● 1 at AC 85 ... 132 V
● 2 at AC 170 ... 264 V
Wide-range input No
Overvoltage resistance 2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min. 20 ms; at Vin = 93/187 V
Rated line frequency 1 50 Hz
Rated line frequency 2 60 Hz
Rated line range 47 ... 63 Hz
Input current
● at rated input voltage 120 V 2.3 A
● at rated input voltage 230 V 1.2 A
Switch-on current limiting (+25 °C), max. 20 A
Output
Output Controlled, isolated DC voltage
Rated voltage Vout DC 24 V
Total tolerance, static ± 3 %
Static mains compensation, approx. 0.1 %
Static load balancing, approx. 0.5 %
Residual ripple peak-peak, max. 50 mV
Residual ripple peak-peak, typ. 10 mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 150 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz) 20 mV
Product function Output voltage adjustable No
Output voltage setting -
Status display Green LED for 24 V OK
On/off behavior No overshoot of Vout (soft start)
Startup delay, max. 2 s
Voltage rise, typ. 10 ms
Rated current value Iout rated 5 A
Current range 0 ... 5 A
Supplied active power typical 120 W
Short-term overload current
● on short-circuiting during the start-up typical 20 A
● at short-circuit during operation typical 20 A
Duration of overloading capability for excess current
● on short-circuiting during the start-up 100 ms
● at short-circuit during operation 100 ms
Parallel switching for enhanced performance Yes
Efficiency
Efficiency at Vout rated, Iout rated, approx. 87 %
Power loss at Vout rated, Iout rated, approx. 18 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), 0.1 %
max.
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± 1 %
typ.
Load step setting time 50 to 100%, typ. 0.3 ms
Load step setting time 100 to 50%, typ. 0.3 ms
Safety
Primary/secondary isolation Yes
Galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN
50178
Protection class Class I
Leakage current
● maximum 3.5 mA
● typical 0.5 mA
CE mark Yes
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289
Explosion protection ATEX (EX) II 3G Ex nA II T4; cULus (ISA 12.12.01, CSA C22.2
No.213) Class I, Div. 2, Group ABCD, T4, File E330455
FM approval Class I, Div. 2, Group ABCD, T4
CB approval No
Marine approval In S7-300 system
Degree of protection (EN 60529) IP20
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation EN 61000-3-2
Noise immunity EN 61000-6-2
Operating data
Ambient temperature
● during operation 0 ... 60 °C
— Note with natural convection
● during transport -40 ... +85 °C
● during storage -40 ... +85 °C
Humidity class according to EN 60721 Climate class 3K3, no condensation
Mechanics
Connection technology screw-type terminals
Connections
● Supply input L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-
core/finely stranded
● Output L+, M: 3 screw terminals each for 0.5 ... 2.5 mm²
● Auxiliary -
Width of the enclosure 60 mm
Height of the enclosure 125 mm
Type SUL
Open single-phase isolating-/control-transformer
with separate insulated windings and protected
against dust, humidity and corrosion through
complete impregnation in heat tempered varnish.
UL-approved and produced according to DNV,
Lloyds register of shipping and Bureau Veritas
regulations which include 45°C ambient tempe-
rature. Compact design, fixed installation, easy
mounting in cabinets or switchboards.
Applications:
Industrial isolating-/control-transformer suitable
for installation which require protective separa-
tion between input and output. SUL84A, SUL84B,
SUL96C & SUL96C can be mounted on 35mm
DIN-rail. The transformer must be protected
against overload and short circuit in the installation.
Dimensions (mm) Wt
Type
A B C D E F G (Kg)
SUL84A 86 84 97 60 64 65 4,5x8 1,4
SUL84B 86 84 97 74 64 65 4,5x8 1,9
SUL96B 102 96 105 80 84 87 5,5x9 2,8
SUL96C 102 96 105 94 84 87 5,5x9 3,5
SUL120A 86 120 120 88 90 69 6x11 4,2
SUL120B 98 120 120 100 90 81 6x11 5,1
SUL120C 117 120 120 120 90 101 6x11 6,6
SUL150A 106 150 145 108 122 85 7x13 8,1
SUL150B 122 150 145 124 122 103 7x13 9,9
SUL150C 147 150 145 150 122 128 7x13 13,3
SUL192C 156 192 180 154 150 126 10x18 22,5
SUL192D 177 192 188 175 150 148 10x18 27,3
SUL192E 184 192 188 184 150 154 10x18 28,7
3-24 www.noratel.com
Technical specifications Voltage Current Power (VA)
Type Art. no.
■
Input voltage: 230-400±15 V Sec. (V) Sec. (A) IEC / UL
400-460±20 V 230-400±15V/2x115V
SUL84A-234230 2x115 2x0,27 63 / 63 4-065-084230
550-575±25 V
SUL84B-234230 2x115 2x0,43 100 / 100 4-065-084231
■
Frequency: 47-63 Hz SUL96B-234230 2x115 2x0,7 160 / 160 4-065-096232
SUL96C-234230 2x115 2x1,09 250 / 200 4-065-096233
■
Output voltage: 2x115 V
SUL120A-234230 2x115 2x1,39 320 / 250 4-065-120234
■
According to: EN61558, UL506, SUL120B-234230 2x115 2x1,74 400 / 320 4-065-120235
UL file no. E305755 SUL120C-234230 2x115 2x2,17 500 / 400 4-065-120236
SUL150A-234230 2x115 2x2,74 630 / 500 4-065-150237
■
Test/insulating voltage: 4,5 kV AC RMS SUL150B-234230 2x115 2x3,48 800 / 630 4-065-150238
■
Construction class: I SUL150C-234230 2x115 2x4,35 1000 / 800 4-065-150239
SUL192C-234230 2x115 2x6,96 1600 / 1000 4-065-192240
■
Insulation class: IEC - B (130°C)
SUL192D-234230 2x115 2x8,7 2000 / 1600 4-065-192241
UL - class A (105°C) SUL192E-234230 2x115 2x10,87 2500 / 2000 4-065-192242
■
Ambient temp. (ta): 45°C 400-460±20V/2x115V
SUL84A-460230 2x115 2x0,27 63 / 63 8-065-084063
■
Degree of protection: IP00
SUL84B-460230 2x115 2x0,43 100 / 100 8-065-084100
SUL96B-460230 2x115 2x0,7 160 / 160 8-065-096160
■
The SUL 234 transformer series is designed for connecting to
SUL96C-460230 2x115 2x1,09 250 / 200 8-065-096250
a wide range of primary voltages. Connect neutral conductor
(N) and phase conductor (P) according to the table: SUL120A-460230 2x115 2x1,39 320 / 250 8-065-120320
SUL120B-460230 2x115 2x1,74 400 / 320 8-065-120400
Terminal SUL120C-460230 2x115 2x2,17 500 / 400 8-065-120500
Primary
SUL150A-460230 2x115 2x2,74 630 / 500 8-065-150630
voltage +15 0 15 230 400
SUL150B-460230 2x115 2x3,48 800 / 630 8-065-150800
215 V N P
SUL150C-460230 2x115 2x4,35 1000 / 800 8-065-150000
230 V N P
SUL192C-460230 2x115 2x6,96 1600 / 1000 8-065-192160
245 V N P
SUL192D-460230 2x115 2x8,7 2000 / 1600 8-065-192200
385 V N P
SUL192E-460230 2x115 2x10,87 2500 / 2000 8-065-192250
400 V N P
500-575±25V/2x115V
415 V N P
SUL84A-500230 2x115 2x0,27 63 / 63 8-065-084230
SUL84B-500230 2x115 2x0,43 100 / 100 8-065-084231
Primary Terminal SUL96B-500230 2x115 2x0,7 160 / 160 8-065-096232
voltage +20 0 20 400 460 SUL96C-500230 2x115 2x1,09 250 / 200 8-065-096233
SUL120A-500230 2x115 2x1,39 320 / 250 8-065-120234
380 V N P
SUL120B-500230 2x115 2x1,74 400 / 320 8-065-120235
400 V N P
SUL120C-500230 2x115 2x2,17 500 / 400 8-065-120236
420 V N P
SUL150A-500230 2x115 2x2,74 630 / 500 8-065-150237
440 V N P
SUL150B-500230 2x115 2x3,48 800 / 630 8-065-150238
460 V N P
SUL150C-500230 2x115 2x4,35 1000 / 800 8-065-150239
480 V N P
115**
Primary Terminal
P
P
475 V N P
500 V N P
0**
N
-
525 V N P
550 V N P
0*
N
N
575 V N P
115V
230V
Sec.
600 V N P
www.noratel.com 3-25
5.
MOTOR STARTERS
ACS800
Hardware Manual
ACS800-01 Drives (0.55 to 200 kW)
ACS800-U1 Drives (0.75 to 200 hp)
List of related manuals
Drive hardware manuals and guides Code (English)
ACS800-01/U1 Drives Hardware Manual (0.55 to 200 kW, 0.75 to 3AFE64382101
200 hp)
Converter module capacitor reforming instructions 3BFE64059629
ACS800-01, -U1, -04 frames R2-R6 EMC filter disconnection 3AXD00000168163
You can find manuals and other product documents in PDF format on the Internet. See section
Document library on the Internet on the inside of the back cover. For manuals not available in the
Document library, contact your local ABB representative.
ACS800-01/U1 manuals
ACS800-01 Drives
0.55 to 200 kW
ACS800-U1 Drives
0.75 to 200 hp
Hardware Manual
3AFE64382101 Rev K
EN
EFFECTIVE: 2013-06-27
Safety instructions
Hot surface warning warns of hot surfaces which can cause physical
injury.
Safety instructions
6
WARNING! Ignoring the following instructions can cause physical injury or death, or
damage to the equipment:
• Only qualified electricians are allowed to install and maintain the drive.
• Never work on the drive, motor cable or motor when main power is applied.
After disconnecting the input power, always wait for 5 min to let the intermediate
circuit capacitors discharge before you start working on the drive, motor or
motor cable.
Always ensure by measuring with a multimeter (impedance at least 1 Mohm)
that:
1. voltage between drive input phases U1, V1 and W1 and the frame is close to
0 V.
2. voltage between terminals UDC+ and UDC- and the frame is close to 0 V.
• Do not work on the control cables when power is applied to the drive or to the
external control circuits. Externally supplied control circuits may cause
dangerous voltages inside the drive even when the main power on the drive is
switched off.
• Do not make any insulation or voltage withstand tests on the drive or drive
modules.
• When reconnecting the motor cable, always check that the phase order is
correct.
• Do not change the electrical installations of the drive except for the essential
control and power connections. Changes may affect the safety performance or
operation of the drive unexpectedly. All customer-made changes are on the
customer's responsibility.
Note:
• The motor cable terminals on the drive are at a dangerously high voltage when
the input power is on, regardless of whether the motor is running or not.
Safety instructions
7
• The Safe torque off function (option +Q967) does not remove the voltage from
the main and auxiliary circuits.
• At installation sites above 2000 m (6562 ft), the terminals of the RMIO board
and option modules attached to the board do not fulfil the Protective Extra Low
Voltage (PELV) requirements stated in EN 50178.
Grounding
These instructions are intended for all who are responsible for the grounding of the
drive.
WARNING! Ignoring the following instructions can cause physical injury, death,
increased electromagnetic interference and equipment malfunction:
• Ground the drive, motor and adjoining equipment to ensure personnel safety in
all circumstances, and to reduce electromagnetic emission and interference.
• Do not install a drive with EMC filter option +E202 or +E200 on an ungrounded
power system or a high-resistance-grounded (over 30 ohms) power system.
Note:
• Power cable shields are suitable for equipment grounding conductors only
when adequately sized to meet safety regulations.
Safety instructions
8
WARNING! Ignoring the following instructions can cause physical injury or death,
or damage to the equipment:
• The drive is heavy. Do not lift it alone. Do not lift the unit by the front cover.
Place the unit only on its back.
• Beware of hot surfaces. Some parts, such as heatsinks of power
semiconductors, remain hot for a while after disconnection of the electrical
supply.
• Make sure that dust from borings and grindings does not enter the drive when
installing. Electrically conductive dust inside the unit may cause damage or
malfunctioning.
WARNING! Ignoring the following instructions can cause damage to the printed
circuit boards:
• Handle the fibre optic cables with care. When unplugging optic cables, always
grab the connector, not the cable itself. Do not touch the ends of the fibres with
bare hands as the fibre is extremely sensitive to dirt. The minimum allowed
bend radius is 35 mm (1.4 in.).
Safety instructions
9
Operation
These warnings are intended for all who plan the operation of the drive or operate
the drive.
WARNING! Ignoring the following instructions can cause physical injury or death,
or damage to the equipment:
• Before adjusting the drive and putting it into service, make sure that the motor
and all driven equipment are suitable for operation throughout the speed range
provided by the drive. The drive can be adjusted to operate the motor at
speeds above and below the speed provided by connecting the motor directly
to the power line.
• Do not activate automatic fault reset functions of the Standard Control Program
if dangerous situations can occur. When activated, these functions will reset
the drive and resume operation after a fault.
• Do not control the motor with the disconnecting device; instead, use the control
panel keys and , or commands via the I/O board of the drive. The
maximum allowed number of charging cycles of the DC capacitors (i.e. power-
ups by applying power) is five in ten minutes.
Note:
• If an external source for start command is selected and it is ON, the drive (with
Standard Control Program) will start immediately after fault reset unless the
drive is configured for 3-wire (a pulse) start/stop.
• When the control location is not set to Local (L not shown in the status row of
the display), the stop key on the control panel will not stop the drive. To stop
the drive using the control panel, press the LOC/REM key and then the stop
key .
Safety instructions
10
WARNING! Do not work on the drive when the permanent magnet motor is rotating.
Also, when the supply power is switched off and the inverter is stopped, a rotating
permanent magnet motor feeds power to the intermediate circuit of the drive and the
supply connections become live.
Before installation and maintenance work on the drive:
• Stop the motor.
• Ensure that the motor cannot rotate during work. Prevent the start-up of any
drives in the same mechanical group by opening the Prevention of unexpected
start switch (option +Q950) or the Safe torque off switch (option +Q967) and
padlocking it. Make sure that no other system, like hydraulic crawling drives, are
able to rotate the motor directly or through any mechanical connection like felt,
nip, rope, etc.
• Ensure that there is no voltage on the drive power terminals:
Alternative 1) Disconnect the motor from the drive with a safety switch or by other
means. Measure that there is no voltage present on the drive input, output or DC
terminals (U1, V1, W1, U2, V2, W2, UDC+, UDC-).
Alternative 2) Measure that there is no voltage present on the drive input, output
or DC terminals (U1, V1, W1, U2, V2, W2, UDC+, UDC-). Ground the drive output
terminals temporarily by connecting them together as well as to the PE.
Alternative 3) If possible, both of the above.
WARNING! Do not run the motor over the rated speed. Motor overspeed leads to
overvoltage which can damage the capacitors in the intermediate circuit of the drive.
Safety instructions
11
Table of contents
Safety instructions
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Use of warnings and notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Mechanical installation and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Printed circuit boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Fibre optic cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Permanent magnet motor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Start-up and operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table of contents
Mechanical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Unpacking the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Example 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Example 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table of contents
12
Table of contents
13
Electrical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Checking the insulation of the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Supply cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Motor and motor cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
IT (ungrounded) systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Connecting the power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Conductor stripping lengths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Allowed wire sizes, tightening torques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Wall installed units (European version) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Power cable installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Wall installed units (US version) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Warning sticker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Cabinet installation (IP21, UL type 1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Frame size R5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Frame size R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Connecting the control cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
360 degrees grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Connecting the shield wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Cabling of I/O and fieldbus modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Pulse encoder module cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Fastening the control cables and covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Installation of option modules and PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Fibre optic link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Table of contents
14
Installation checklist
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Maintenance
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Maintenance intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Heatsink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Fan replacement (R2, R3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Fan replacement (R4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Fan replacement (R5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Fan replacement (R6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Table of contents
15
Technical data
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
IEC data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Temperature derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Altitude derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Frame sizes R2 to R4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Frame sizes R5 and R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Calculation example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Fuse tables for frame sizes R5 and R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Standard gG fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Ultrarapid (aR) fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Quick guide for selecting between gG and aR fuses . . . . . . . . . . . . . . . . . . . . . . . . . 114
Cable types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Cable entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Dimensions, weights and noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Package dimensions and weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
NEMA data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Cable types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Cable Entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Dimensions, weights and noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Package dimensions and weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Input power connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Motor connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Degree of protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
AGPS-11C (option +Q950) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
ASTO-11C (option +Q967). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Materials. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Applicable standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Table of contents
16
CE marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Compliance with the European Low Voltage Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Compliance with the European EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Compliance with the European Machinery Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Compliance with EN 61800-3:2004. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
First environment (drive of category C2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Second environment (drive of category C3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Second environment (drive of category C4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
“C-tick” marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Marine type approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
UL/CSA markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
UL checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Dimensional drawings
Frame size R2 (IP21, UL type 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Frame size R2 (IP55, UL type 12). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Frame size R3 (IP21, UL type 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Frame size R3 (IP55, UL type 12). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Frame size R4 (IP21, UL type 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Frame size R4 (IP55, UL type 12). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Frame size R5 (IP21, UL type 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Frame size R5 (IP55, UL type 12). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Frame size R6 (IP21, UL type 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Frame size R6 (IP21, UL type 1), -205-3 and -255-5 units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Frame size R6 (IP55, UL type 12). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Frame size R6 (IP55, UL type 12) -0205-3 and -0255-5 units . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Dimensional drawings (USA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Frame size R2 (UL type 1, IP21) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Frame size R2 (UL type 12, IP55) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Frame size R3 (UL type 1, IP21) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Frame size R3 (UL type 12, IP55) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Frame size R4 (UL type 1, IP21) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Frame size R4 (UL type 12, IP55) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Frame size R5 (UL type 1, IP21) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Frame size R5 (UL type 12, IP55) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Frame size R6 (UL type 1, IP21) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Frame size R6 (UL type 1, IP21) -0205-3 and -0255-5 units . . . . . . . . . . . . . . . . . . . . . . . 154
Frame size R6 (UL type 12, IP55) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Frame size R6 (UL type 12, IP55) -0205-3 and -0255-5 units . . . . . . . . . . . . . . . . . . . . . . 156
AGPS board (option +Q950) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
ASTO board with enclosure (option +Q967) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Resistor braking
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Availability of brake choppers and resistors for the ACS800 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Selecting the correct drive/chopper/resistor combination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Table of contents
17
External +24 V DC power supply for the RMIO board via terminal X34
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Parameter settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Connecting +24 V DC external power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Further information
Product and service inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Product training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Providing feedback on ABB Drives manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Document library on the Internet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Table of contents
18
Table of contents
19
Intended audience
This manual is intended for people who plan the installation, install, commission, use
and service the drive. Read the manual before working on the drive. The reader is
expected to know the fundamentals of electricity, wiring, electrical components and
electrical schematic symbols.
This manual is written for readers worldwide. Both SI and imperial units are shown.
Special US instructions for installations within the United States that must be
installed per the National Electrical Code and local codes are marked with (US).
Contents
The chapters of this manual are briefly described below.
Safety instructions give safety instructions for the installation, commissioning,
operation and maintenance of the drive.
Introduction to this manual lists the steps in checking the delivery and installing and
commissioning the drive and refers to chapters/sections in this manual and other
manuals for particular tasks.
Operation principle and hardware description describes the drive.
Mechanical installation instructs how to place and mount the drive.
Planning the electrical installation instructs on the motor and cable selection,
protections and cable routing.
Electrical installation shows how to wire the drive.
Installation of the AGPS board (Prevention of unexpected start-up, +Q950) contains
electrical installation instructions of the optional Prevention of unexpected start-up
function (+Q950) of the drive, and gives instructions for starting up, validating and
using the function.
Installation of the ASTO board (Safe torque off, +Q967) describes the electrical
installation of the optional Safe torque off function (+Q967).
Motor control and I/O board (RMIO) shows the external control connections to the
I/O board.
Installation checklist contains a list for checking the mechanical and electrical
installation of the drive.
Start-up and use describes the start-up procedure and use of the drive.
Maintenance contains preventive maintenance instructions.
Technical data contains the technical specifications of the drive, e.g. the ratings,
sizes and technical requirements, provisions for fulfilling the requirements for CE
and other markings and warranty policy.
Dimensional drawings contains the dimensional drawings of the drive.
Resistor braking describes how to select, protect and wire brake choppers and
resistors. The chapter also contains the technical data.
External +24 V DC power supply for the RMIO board via terminal X34 describes how
to connect an external +24 V DC power supply for the RMIO board using terminal
X34.
Task See
Identify the frame size of your drive: R2, R3, R4, R5 Technical data: IEC data or NEMA data
or R6.
Unpack and check the units. Mechanical installation: Unpacking the unit.
Check that all necessary option modules and If the converter has been non-operational for
equipment are present and correct. more than one year, the converter DC link
Only intact units may be started up. capacitors need to be reformed. See Converter
module capacitor reforming instructions
(3BFE64059629 [English]).
Task See
Check the insulation of the motor and the motor Electrical installation: Checking the insulation of
cable. the installation
Connect the control and the auxiliary control cables. Electrical installation, Motor control and I/O
board (RMIO), and the option module manual
delivered with the module.
Product overview
The ACS800-01/U1 is a wall mountable drive for controlling AC motors.
Front cover
Connection box
Type code
The type code contains information on the specifications and configuration of the
drive. The first digits from left express the basic configuration (for example,
ACS800-01-0006-5). The optional selections are given thereafter, separated by +
signs (for example, +E202). The main selections are described below. Not all
selections are available for all types. For more information, refer to ACS800
Ordering Information (EN code: 3AFY64556568, available on request).
Selection Alternatives
Product series ACS800 product series
Type 01 Wall mounted. When no options are selected: IP21, control panel CDP 312R,
no EMC filter, Standard Control Program, cable connection box (cabling from
below), brake chopper in frame sizes R2 and R3 (230/400/500 V units) and in
frame size R4 (690 V units), boards without coating, one set of English
manuals.
U1 Wall mounted (USA). When no options are selected: UL type 1, control panel
CDP 312R, no EMC filter, US version of the Standard Control Program (three-
wire start/stop as default setting), US gland/conduit box, brake chopper in
frame sizes R2 and R3 (230/400/500 V units) and in frame size R4 (690 V
units), boards without coating, one set of English manuals.
Size Refer to Technical data: IEC data or NEMA data.
Voltage range 2 208/220/230/240 V AC
(nominal rating in bold) 3 380/400/415 V AC
5 380/400/415/440/460/480/500 V AC
7 525/575/600/690 V AC
Option codes (+ codes)
Degree of protection B056 IP55 / UL type 12
Construction C131 Vibration dampers
C132 Marine type approved unit (coated boards included, +C131 required for frame
sizes R4 to R6 in wall installations, +C131 not required in cabinet installations)
Resistor braking D150 Brake chopper
Filter E200 EMC/RFI filter for second environment TN (grounded) system, drive category
C3 (frame sizes R2…R5)
E202 EMC/RFI filter for first environment TN (grounded) system, drive category C2
E210 EMC/RFI filter for second environment TN/IT (grounded/ungrounded) system,
drive category C3 (frame size R6 only)
Cabling H358 US/UK gland/conduit box
Control panel 0J400 No control panel
Fieldbus K... Refer to ACS800 Ordering Information (EN code: 3AFY64556568).
I/O L...
Control program N...
Manual language R...
Safety features Q950 Prevention of unexpected start-up: AGPS board and 3 m connection cable
(not to be used with option +Q967)
Q967 Safe torque off (STO) function without safety relay: ASTO board and 3 m
connection cable (not to be used with option +Q950)
Specialities P901 Coated boards
P904 Extended warranty
Diagram
This diagram shows the control interfaces and the main circuit of the drive.
Drive
Motor
control and Option module 1: RMBA, RAIO, RDIO,
I/O board RDNA, RLON, RIBA, RPBA, RCAN,
(RMIO) RCNA, RMBP, RETA, RECA, REPL, RRIA
or RTAC
R- UDC+ UDC-
R+
Operation
This table describes the operation of the main circuit in short.
Component Description
capacitor bank energy storage which stabilizes the intermediate circuit DC voltage
IGBT inverter converts the DC voltage to AC voltage and vice versa. The motor
operation is controlled by switching the IGBTs.
Motor control
The motor control is based on the Direct Torque Control (DTC) method. Two phase
currents and DC link voltage are measured and used for the control. The third phase
current is measured for earth fault protection.
Mechanical installation
Mechanical installation
30
Example 1
1. To cut the box into two pieces, pull from the spots marked with arrows.
2. Remove the upper part of the box.
3. Remove the unit and other contents from the box.
1 2
Pull
Mechanical installation
31
Example 2
1. Cut the straps.
2. Remove the outer box and sleeve.
3. Remove the locking sheet and the screws that attach the unit to the bottom pallet.
Mechanical installation
32
Before installation
The drive must be installed in an upright position with the cooling section facing a
wall. Check the installation site according to the requirements below. Refer to
Dimensional drawings for frame details.
Mechanical installation
33
50 [2.0]
200 [7.9]
300 [12]
50 [2.0]
Mechanical installation
34
UL 12 units
Install the hood delivered with the drive 50 mm (2.0 in.) above the top of unit.
Mechanical installation
35
Cabinet installation
For better cooling, it is recommended to remove the front cover if the unit is installed
into a cabinet. The required distance between parallel units is five millimetres
(0.2 in.) in installations without the front cover. The cooling air entering the unit must
not exceed +40 °C (+104 °F).
HOT
Main air flow out AREA
COOL AREA
Mechanical installation
36
Mechanical installation
37
Example 1: When the supply voltage is 440 V and a drive with a diode supply is
operating in motor mode only, the maximum peak voltage in the motor terminals
can be approximated as follows: 440 V · 1.35 · 2 = 1190 V. Check that the motor
insulation system withstands this voltage.
Requirements table
The following table shows how to select the motor insulation system and when an
optional ABB du/dt filter, insulated N-end (non-driven end) motor bearings and ABB
common mode filters are required. Ignoring the requirements or improper installation
may shorten motor life or damage the motor bearings and voids the warranty.
3.0 5.5
ÛLL/UN 5.0
2.5 du/dt
------------- (1/s)
4.5 UN
2.0 4.0
3.5
1.5
3.0
ÛLL/UN
1.0 2.5
du/dt
------------- (1/s)
UN 2.0
0.5
1.5
0.0 1.0
100 200 300 100 200 300
Note 9: Sine filters protect the motor insulation system. Therefore, du/dt filter can be
replaced with a sine filter. The peak phase-to-phase voltage with the sine filter is
approximately 1.5 × UN.
Note 10: Common mode filter is available as a separate option.
Supply connection
Disconnecting device
Install a hand-operated input disconnecting device between the AC power source
and the drive. The disconnecting device must be of a type that can be locked to the
open position for installation and maintenance work.
EU
To meet the European Union Directives, according to standard EN 60204-1, Safety
of Machinery, the disconnecting device must be one of the following types:
• switch-disconnector of utilization category AC-23B (EN 60947-3)
• disconnector that has an auxiliary contact that in all cases causes switching
devices to break the load circuit before the opening of the main contacts of the
disconnector (EN 60947-3)
• circuit breaker suitable for isolation in accordance with EN 60947-2.
US
The disconnecting device must conform to the applicable safety regulations.
Fuses
See section Thermal overload and short-circuit protection.
Main contactor
If used, dimension the contactor according to the nominal voltage and current of the
drive. The utilization category (IEC 947-4) is AC-1.
Thermal overload protection of the drive and the input and motor cables
The drive protects itself and the input and motor cables against thermal overload
when the cables are dimensioned according to the nominal current of the drive. No
additional thermal protection devices are needed.
Fuses
~ M
~ 3~
Circuit
breaker
~ M
I>
~ 3~
Fuses
Size the fuses according to instructions given in chapter Technical data. The fuses
will protect the input cable in short-circuit situations, restrict drive damage and
prevent damage to adjoining equipment in case of a short-circuit inside the
drive.Circuit breakers which have been tested by ABB with the ACS800 can be
used. Fuses must be used with other circuit breakers. Contact your local ABB
representative for the approved breaker types and supply network characteristics.
Circuit breaker
The protective characteristics of circuit breakers depend on the type, construction
and settings of the breakers. There are also limitations pertaining to the short-circuit
capacity of the supply network.
Note: Circuit breakers must not be used without fuses in the USA.
WARNING! The Prevention of unexpected start-up function does not disconnect the
voltage of the main and auxiliary circuits from the drive. Therefore maintenance work
on electrical parts of the drive or the motor can only be carried out after isolating the
drive system from the main supply.
Note: The Prevention of unexpected start-up function is not intended for stopping
the drive. If the Prevention of unexpected start-up function is activated when the
drive is running, the control voltage of the power semiconductors is cut off and the
motor coasts to a stop.
For detailed instructions for installation, start-up, use and maintenance of the
function, see chapter Installation of the AGPS board (Prevention of unexpected
start-up, +Q950).
WARNING! The Safe torque off function does not disconnect the voltage of the main
and auxiliary circuits from the drive. Therefore maintenance work on electrical parts
of the drive or the motor can only be carried out after isolating the drive system from
the main supply.
Note: The Safe torque off function can be used for stopping the drive in emergency
stop situations. In the normal operating mode, use the Stop command instead. If the
Safe torque off function is activated when the drive is running, the control voltage of
the power semiconductors is cut off and the motor coasts to a stop. If this is not
acceptable, e.g. causes danger, the drive and machinery must be stopped using the
appropriate stopping mode before using this function.
Note concerning permanent magnet motor drives in case of a multiple IGBT
power semiconductor failure: In spite of the activation of the Safe torque off
function, the drive system can produce an alignment torque which maximally rotates
the motor shaft by 180/p degrees. p denotes the pole pair number.
For more information on the installation of the Safe torque off function, see chapter
Installation of the ASTO board (Safe torque off, +Q967).
For more information on the Safe torque off function and the relevant safety data,
see ACS800-01/04/11/31/104/104LC Safe torque off function (+Q967), Application
guide (3AUA0000063373 [English]).
An example circuit diagram is shown below.
3AUA0000072271
General rules
Dimension the mains (input power) and motor cables according to local
regulations:
• The cable must be able to carry the drive load current. See chapter Technical
data for the rated currents.
• The cable must be rated for at least 70 °C (158 °F) maximum permissible
temperature of conductor in continuous use. For US, see Additional US
requirements.
• The inductance and impedance of the PE conductor/cable (grounding wire) must
be rated according to permissible touch voltage appearing under fault conditions
(so that the fault point voltage will not rise excessively when a ground fault
occurs).
• 600 V AC cable is accepted for up to 500 V AC. 750 V AC cable is accepted for
up to 600 V AC. For 690 V AC rated equipment, the rated voltage between the
conductors of the cable should be at least 1 kV.
For drive frame size R5 and larger, or motors larger than 30 kW (40 hp), symmetrical
shielded motor cable must be used (figure below). A four-conductor system can be
used up to frame size R4 with up to 30 kW (40 hp) motors, but shielded symmetrical
motor cable is always recommended. The shield(s) of motor cable(s) must have
360° bonding at both ends.
Note: When continuous metal conduit is employed, shielded cable is not required.
The conduit must have bonding at both ends as with cable shield.
A four-conductor system is allowed for input cabling, but shielded symmetrical cable
is recommended. To operate as a protective conductor, the shield conductivity must
be as follows when the protective conductor is made of the same metal as the phase
conductors:
Cross-sectional area of the phase Minimum cross-sectional area of the
conductors corresponding protective conductor
S (mm2) Sp (mm2)
S < 16 S
16 < S < 35 16
35 < S S/2
Recommended
Symmetrical shielded cable: three phase conductors A separate PE conductor is required if the conductivity
and a concentric or otherwise symmetrically of the cable shield is < 50% of the conductivity of the
constructed PE conductor, and a shield phase conductor.
PE conductor Shield
and shield Shield
PE
PE
PE Shield
A four-conductor system:
three phase conductors
and a protective
conductor
Not allowed for motor cables Not allowed for motor cables with phase
conductor cross section larger than 10 mm2
[motors > 30 kW (40 hp)].
Cable core
Additional US requirements
Type MC continuous corrugated aluminum armor cable with symmetrical grounds or
shielded power cable must be used for the motor cables if metallic conduit is not
used. For the North American market, 600 V AC cable is accepted for up to
500 V AC. 1000 V AC cable is required above 500 V AC (below 600 V AC). For
drives rated over 100 amperes, the power cables must be rated for 75 °C (167 °F).
Conduit
Separate parts of a conduit must be coupled together, bridge the joints with a ground
conductor bonded to the conduit on each side of the joint. Bond the conduits also to
the drive enclosure and motor frame. Use separate conduits for input power, motor,
brake resistor, and control wiring. When conduit is employed, type MC continuous
corrugated aluminium armor cable or shielded cable is not required. A dedicated
ground cable is always required.
Note: Do not run motor wiring from more than one drive in the same conduit.
Armored cable / shielded power cable
Six conductor (3 phases and 3 ground) type MC continuous corrugated aluminum
armor cable with symmetrical grounds is available from the following suppliers (trade
names in parentheses):
• Anixter Wire & Cable (Philsheath)
• BICC General Corp (Philsheath)
• Rockbestos Co. (Gardex)
• Oaknite (CLX).
Shielded power cables are available from Belden, LAPPKABEL (ÖLFLEX) and
Pirelli.
If there are power factor compensation capacitors in parallel with the three phase
input of the drive:
1. Do not connect a high-power capacitor to the power line while the drive is
connected. The connection will cause voltage transients that may trip or even
damage the drive.
2. If capacitor load is increased/decreased step by step when the AC drive is
connected to the power line: Ensure that the connection steps are low enough not
to cause voltage transients that would trip the drive.
3. Check that the power factor compensation unit is suitable for use in systems with
AC drives i.e. harmonic generating loads. In such systems, the compensation unit
should typically be equipped with a blocking reactor or harmonic filter.
WARNING! Never connect the supply power to the drive output terminals U2, V2
and W2. If frequent bypassing is required, employ mechanically connected switches
or contactors. Mains (line) voltage applied to the output can result in permanent
damage to the unit.
WARNING! When the DTC motor control mode is in use, never open the output
contactor while the drive controls the motor. The DTC motor control operates
extremely fast, much faster than it takes for the contactor to open its contacts. When
the contactor starts opening while the drive controls the motor, the DTC control will
try to maintain the load current by immediately increasing the drive output voltage to
the maximum. This will damage, or even burn the contactor completely.
RMIO
Relay outputs
Varistor X25
1 RO1
2 RO1
230 V AC
3 RO1
RC filter X26
1 RO2
2 RO2
230 V AC
3 RO2
Diode X27
1 RO3
2 RO3
24 V DC
3 RO3
a b
A double-shielded twisted A single-shielded twisted
pair cable pair cable
Relay cable
The cable type with braided metallic screen (e.g. ÖLFLEX by LAPPKABEL,
Germany) has been tested and approved by ABB.
WARNING! IEC 60664 requires double or reinforced insulation between live parts
and the surface of accessible parts of electrical equipment which are either non-
conductive or conductive but not connected to the protective earth.
To fulfil this requirement, the connection of a thermistor (and other similar
components) to the digital inputs of the drive can be implemented in three alternate
ways:
1. There is double or reinforced insulation between the thermistor and live parts of
the motor.
2. Circuits connected to all digital and analogue inputs of the drive are protected
against contact and insulated with basic insulation (the same voltage level as the
drive main circuit) from other low voltage circuits.
3. An external thermistor relay is used. The insulation of the relay must be rated for
the same voltage level as the main circuit of the drive. For connection, see the
firmware manual.
WARNING! Protect against direct contact when installing, operating and servicing
the RMIO board wiring and option modules attached to the board. The Protective
Extra Low Voltage (PELV) requirements stated in EN 50178 are not fulfilled at
altitudes above 2000 m (6562 ft).
Motor cable
Drive
min 300 mm (12 in.)
Power cable
Control cables
230 V 230 V
24 V (120 V) 24 V (120 V)
Not allowed unless the 24 V cable is Lead 24 V and 230 V (120 V) control
insulated for 230 V (120 V) or insulated cables in separate ducts inside the
with an insulation sleeving for 230 V cabinet.
(120 V).
Electrical installation
WARNING! The work described in this chapter may only be carried out by a qualified
electrician. Follow the Safety instructions on the first pages of this manual. Ignoring
the safety instructions can cause injury or death.
Make sure that the drive is disconnected from the mains (input power) during
installation. If the drive is already connected to the mains, wait for 5 min after
disconnecting mains power.
Drive
Do not make any voltage tolerance or insulation resistance tests on any part of the
drive as testing can damage the drive. Every drive has been tested for insulation
between the main circuit and the chassis at the factory. Also, there are voltage-
limiting circuits inside the drive which cut down the testing voltage automatically.
Supply cable
Check the insulation of the supply (input) cable according to local regulations before
connecting to the drive.
Electrical installation
62
U1
M
V1
3~
ohm W1
PE
IT (ungrounded) systems
In units with EMC filter options (+E202 or +E200 in the type code), disconnect the
filter capacitors before connecting the drive to an ungrounded system. For detailed
instructions, see ACS800-01, -U1, -04 frames R2-R6 EMC filter disconnection
(3AXD00000168163 [English]).
Electrical installation
63
Diagram
Drive
INPUT UDC+ UDC- OUTPUT
PE U1 V1 W1 R- R+ U2 V2 W2
1) 2)
3) 4) 4)
(PE) PE (PE)
5)
V1 W1
U1
External brake
For alternatives, see
Planning the electrical
resistor 3 ~
installation: Motor
Disconnecting device
L1 L2 L3
b > 1/5 · a
5) Use a separate grounding cable if the conductivity of
the cable shield is < 50% of the conductivity of the b
a
phase conductor and there is no symmetrically
constructed grounding conductor in the cable (see
Planning the electrical installation: Selecting the
power cables).
Note:
If there is a symmetrically constructed grounding
conductor in the motor cable in addition to the
conductive shield, connect the grounding conductor to
the grounding terminal at the drive and motor ends.
Do not use an asymmetrically constructed motor cable
for motors > 30 kW (40 hp). Connecting its fourth
conductor at the motor end increases bearing currents
and causes extra wear.
Electrical installation
64
Electrical installation
65
1 8
Bottom plate
Fasten the
control
cables
between
these plates
with cable
Cover
ties
Frame sizes R2 to R4
U1 V1 W1 UDC+
U2 V2 W2
R- R+ UDC-
PE
6 6
5 5
Electrical installation
66
Frame size R5
UDC+
U1 V1 W1 R- R+ UDC- U2 V2 W2 6
3 3
6 6
8 8
5
5
Electrical installation
67
Frame size R6: Cable lug installation [16 to 70 mm2 (6 to 2/0 AWG) cables]
3 3
5 5
Frame size R6: Cable terminal installation [95 to 240 mm2 (3/0 to 500 MCM) cables]
PE 6
a
a. Connect the cable to the terminal.
Electrical installation
68
Frame sizes R2 to R4
UDC+
U1 V1 W1 R- R+ UDC- U2 V2 W2
4 4
PE
3 3
5. Lead the cables through the glands to the inside of the gland box.
6. Connect the PE conductors of the input and motor cables to the grounding
terminal. Note: cable lugs are needed in frame sizes R2 and R3. Connect the
separate PE conductor (if used) to the grounding terminal.
7. Connect the phase conductors of the input cable to the U1, V1 and W1 terminals
and the phase conductors of the motor cable to the U2, V2 and W2 terminals.
For frame size R6, see Wall installed units (European version) / figures for frame
size R6. In case of a cable lug installation, use UL listed cable lugs and tools
given below or corresponding to meet UL requirements.
Electrical installation
69
Warning sticker
There are warning stickers in different languages inside the packing box of the drive.
Attach a warning sticker in the language of your choice onto the plastic skeleton
above the power cable terminals.
Electrical installation
70
1 2
Electrical installation
71
Frame size R6
Cover the power cable terminals as follows:
1. Cut holes for the installed cables into the clear plastic shroud in cable lug
installations.
2. Press the shroud onto the terminals.
Removal of the shroud by lifting up with a screw driver from the corner:
Electrical installation
72
Terminals
Frame sizes R2 to R4
The control cable connection terminals are
exposed when the control panel mounting platform
is turned aside by pulling this knob. Be careful, do Detachable connection terminals (pull up)
not use excess force when pulling.
X39 for control panel cable
X41
Option module 2
Electrical installation
73
Control panel
Option module 2
Electrical installation
74
Insulation
4
3
2
1
When the outer surface of the shield is covered with non-conductive material:
• Strip the cable carefully (do not cut the grounding wire and the shield)
• Turn the shield inside out to expose the conductive surface.
• Wrap the grounding wire around the conductive surface.
• Slide a conductive clamp onto the conductive part.
• Fasten the clamp to the grounding plate with a screw as close as possible to the
terminals where the wires are about to be connected.
Electrical installation
75
Module
As short as possible
Shield
4
3
2
1
As short as
possible
Note 1: If the encoder is of
1
2 unisolated type, ground the encoder
3
4 cable at the drive end only. If the
encoder is galvanically isolated
from the motor shaft and the stator
frame, ground the encoder cable
Shield
Electrical installation
76
US cover
Electrical installation
77
WARNING! Dangerous voltages can be present on the AGPS board even when the
115...230 V AC supply is switched off. Follow the Safety instructions on the first
pages of this manual and the instruction in this chapter when working on the AGPS
board.
Make sure that the drive is disconnected from the mains (input power) and the
115...230 V AC source for the AGPS board is switched off during installation
and maintenance. If the drive is already connected to the mains, wait for 5 min
after disconnecting mains power.
WARNING! The supply voltage for the AGPS board is 230 V AC. If the board is
supplied with 24 V DC, the board is damaged and it needs to be replaced.
The following figure shows how the external AGPS board is connected to the drive.
The cable (length 3 m [10 ft]) is delivered with the AGPS board.
X2
3 m (10 ft)
X41
See
• page 72 for location of terminal X41 of the drive
• page 80 for the circuit diagram
• page 157 for the dimensions of the AGPS board
• page 124 for the technical data of the AGPS-11C board.
WARNING! Use only the AGPS cable delivered with the kit. Using another cable or
modifying the cable may cause a malfunction of the drive.
• Connect a cable between connector X1 of the AGPS board (3) and the
115...230 V AC source.
• Fasten the enclosure cover back with screws.
X2
X1
115...230 V AC
3
Circuit diagram
This circuit diagram shows how the AGPS-11 kit is installed.
3AFE00374994
Ensure that the drive can be run and stopped freely during the start-up.
Stop the drive (if running), switch the input power off and isolate the drive from the power line by a
disconnector.
Check the Prevention of unexpected start-up circuit connections against the circuit diagram.
Test the operation of the Prevention of unexpected start-up function when the motor is stopped:
• Give a stop command for the drive (if running) and wait until the motor shaft is at standstill.
• Activate the Prevention of unexpected start-up function and give a start command for the drive.
• Ensure that the drive does not start and the motor stays at standstill.
• Deactivate the Prevention of unexpected start-up function.
Use
Activate the function as follows:
• Stop the drive. Use the stop key of the panel (local mode) or give the stop
command through the I/O or fieldbus interface.
• Open the switch activating the Prevention of unexpected start-up function of the
drive. -> The indication lamp (if installed) is lit.
• Lock the switch to the open position.
• Before starting the work on the machinery, ensure that the motor shaft is at
standstill (not freely rotating).
Inactivate the function in reverse order.
Maintenance
After the operation of the circuit is validated at start-up, it does not need any
maintenance. However, it is a good practice to check the operation of the function
when other maintenance routines of the machinery are carried out.
Dimensional drawing
See page 157.
WARNING! Dangerous voltages can be present at the ASTO board even when the
24 V DC supply is switched off. Follow the Safety instructions on the first pages of
this manual and the instruction in this chapter when working on the ASTO board.
Make sure that the drive is disconnected from the mains (input power) and the
24 V DC source for the ASTO board is switched off during installation and
maintenance. If the drive is already connected to the mains, wait for 5 min after
disconnecting mains power.
WARNING! The supply voltage for the ASTO-11C board is 24 V DC. If the board is
supplied with 230 V AC, the board is damaged and it needs to be replaced.
The following figure shows how the external ASTO board is connected the drive. The
cable (length 3 m [10 ft]) is delivered with the ASTO board.
X2
3 m (10 ft)
X41
See
• page 72 for location of terminal X41 of the drive
• page 86 for the circuit diagram
• page 158 for the dimensions of the ASTO-11C board
• page 124 for the technical data of the ASTO-11C board.
WARNING! Use only the ASTO cable delivered with the kit. Using another cable or
modifying the cable may cause a malfunction of the drive.
• Connect a cable between connector X1 of the ASTO board (3) and the 24 V DC
source.
• Fasten the cover of the ASTO unit back with screws.
X2
X1
Note! 24 V DC
3
Circuit diagram
The diagram below shows the connection between the ASTO board and the drive
when it is ready. For an example diagram of a complete Safe torque off circuit, see
page 50.
3AUA0000072542
Dimensional drawing
See page 158.
WARNING! If the RMIO board is supplied from an external power source via
terminal X34, the loose end of the cable removed from the RMIO board terminal
must be secured mechanically to a location where it cannot come into contact with
electrical parts. If the screw terminal plug of the cable is removed, the wire ends
must be individually insulated.
Parameter settings
In Standard Control Program, set parameter 16.9 CTRL BOARD SUPPLY to
EXTERNAL 24V if the RMIO board is powered from an external supply.
Analogue outputs
Two programmable current outputs: 0 (4) to 20 mA, RL < 700 ohm
Resolution 0.1% (10 bit)
Inaccuracy ±1% (Full Scale Range) at 25 °C (77 °F). Temperature coefficient: ±200 ppm/°C
(±111 ppm/°F) max.
Digital inputs
Six programmable digital inputs (common ground: 24 V DC, -15% to +20%) and a
start interlock input. Group isolated, can be divided in two isolated groups (see
Isolation and grounding diagram below).
Thermistor input: 5 mA, < 1.5 kohm “1” (normal temperature), > 4 kohm “0”
(high temperature), open circuit “0” (high temperature).
Internal supply for digital inputs (+24 V DC): short-circuit proof. An external 24 V DC
supply can be used instead of the internal supply.
Insulation test voltage 500 V AC, 1 min
Logical thresholds < 8 V DC “0”, > 12 V DC “1”
Input current DI1 to DI 5: 10 mA, DI6: 5 mA
Filtering time constant 1 ms
Relay outputs
Three programmable relay outputs
Switching capacity 8 A at 24 V DC or 250 V AC, 0.4 A at 120 V DC
Minimum continuous current 5 mA rms at 24 V DC
Maximum continuous current 2 A rms
Insulation test voltage 4 kV AC, 1 minute
The terminals on the RMIO board as well as on the option modules attachable to the board fulfil the Protective Extra Low
Voltage (PELV) requirements stated in EN 50178 provided that the external circuits connected to the terminals also fulfil
the requirements and the installation site is below 2000 m (6562 ft). Above 2000 m (6562 ft), see page 58.
9 AO1+
10 AO1-
11 AO2+
12 AO2-
X22
1 DI1
2 DI2
3 DI3
4 DI4
Jumper J1 settings:
9 DGND1
Installation checklist
Checklist
Check the mechanical and electrical installation of the drive before start-up. Go
through the checklist below together with another person.
WARNING! Only qualified electricians are allowed to commission the drive. Read
and follow the Safety instructions on the first pages of this manual. Ignoring the
safety instructions can cause injury or death.
Check that...
MECHANICAL INSTALLATION
The ambient operating conditions are allowed. (See Mechanical installation, Technical data:
IEC data or NEMA data, Ambient conditions.)
The unit is fixed properly on a vertical non-flammable wall. (See Mechanical installation.)
The cooling air will flow freely.
The motor and the driven equipment are ready for start. (See Planning the electrical
installation: Motor selection and compatibility, Technical data: Motor connection.)
ELECTRICAL INSTALLATION (See Planning the electrical installation, Electrical installation.)
The +E202 and +E200 EMC filter capacitors are disconnected if the drive is connected to an
IT (ungrounded) system.
The capacitors are reformed if stored over one year, refer to Converter modules with
electrolytic DC capacitors in the DC link, Capacitor reforming instructions (3BFE64059629
[English]).
The drive is grounded properly.
The mains (input power) voltage matches the drive nominal input voltage.
The mains (input power) connections at U1, V1 and W1 and their tightening torques are OK.
Appropriate mains (input power) fuses and disconnector are installed.
The motor connections at U2, V2 and W2 and their tightening torques are OK.
The motor cable is routed away from other cables.
Installation checklist
94
Check that...
There are no power factor compensation capacitors in the motor cable.
The external control connections inside the drive are OK.
There are no tools, foreign objects or dust from drilling inside the drive.
Mains (input power) voltage cannot be applied to the output of the drive (with bypass
connection).
Drive, motor connection box and other covers are in place.
Installation checklist
95
Startup procedure
1. Ensure that the installation of the drive has been checked according to the
checklist in chapter Installation checklist, and that the motor and driven
equipment are ready for start.
2. Switch the power on and set-up the drive control program according to the start-
up instructions given in the drive firmware manual.
3. Validate the Prevention of unexpected start-up function (option +Q950) according
to the instructions given in chapter Installation of the AGPS board (Prevention of
unexpected start-up, +Q950).
4. Validate the Safe torque off function (option +Q967) according to the instructions
given in ACS800-01/04/11/31/104/104LC Safe torque off function (+Q967),
Application guide (3AUA0000063373 [English]).
Control panel
The user interface of the drive is the control panel (type CDP 312R). For more
information on using the control panel, see the firmware manual delivered with the
drive.
Maintenance
Safety
WARNING! Read the Safety instructions on the first pages of this manual before
performing any maintenance on the equipment. Ignoring the safety instructions can
cause injury or death.
Maintenance intervals
If installed in an appropriate environment, the drive requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB.
Consult your local ABB Service representative for more details on the maintenance.
On the Internet, go to http://www.abb.com/drives.
Maintenance
98
Heatsink
The heatsink fins pick up dust from the cooling air. The drive runs into
overtemperature warnings and faults if the heatsink is not clean. In a “normal”
environment (not dusty, not clean) the heatsink should be checked annually, in a
dusty environment more often.
Clean the heatsink as follows (when necessary):
1. Remove the cooling fan (see section Fan).
2. Blow clean compressed air (not humid) from bottom to top and simultaneously
use a vacuum cleaner at the air outlet to trap the dust. Note: If there is a risk of
the dust entering adjoining equipment, perform the cleaning in another room.
3. Refit the cooling fan.
Fan
The lifespan of the cooling fan depends on the drive usage and ambient
temperature. See the appropriate ACS800 firmware manual for an actual signal
which indicates the hours of usage of the fan. For resetting the running time signal
after a fan replacement, refer to the firmware manual.
Fan failure can be predicted by the increasing noise from fan bearings and the
gradual rise in the heatsink temperature in spite of heatsink cleaning. If the drive is
operated in a critical part of a process, fan replacement is recommended once these
symptoms start appearing. Replacement fans are available from ABB. Do not use
other than ABB specified spare parts.
Bottom view
Maintenance
99
1 1 Bottom view
2
3
View from above fan
plate pulled out
4 4
4 4
Maintenance
100
Maintenance
101
3. Take off the casing and replace the fan onto the casing’s pins.
3
Maintenance
102
Additional fan
There is an additional cooling fan in all IP55 units and most IP21 units. However,
there is no additional fan in the following IP21 units: -0003-3, -0004-3, -0005-3,
-0004-5, -0005-5 and -0006-5. The following IP55 units have two additional fans:
-0205-3 and -0255-5.
Replacement (R6)
Remove the top cover by lifting it by the rear edge. To remove the fan, release the
retaining clips by pulling the back edge (1) of the fan upwards. Disconnect the cable
(2, detachable terminal). Install the new fan in reverse order.
Rotation direction
Maintenance
103
Capacitors
The drive intermediate circuit employs several electrolytic capacitors. The lifespan
depends on drive loading and ambient temperature. Capacitor life can be prolonged
by lowering the ambient temperature.
It is not possible to predict a capacitor failure. Capacitor failure is usually followed by
a mains fuse failure or a fault trip. Contact ABB if capacitor failure is suspected.
Replacements for frame size R4 and up are available from ABB. Do not use other
than ABB specified spare parts.
Reforming
Reform (re-age) spare part capacitors once a year according to Converter modules
with electrolytic DC capacitors in the DC link, Capacitor reforming instructions
(3BFE64059629 [English]).
LEDs
This table describes LEDs of the drive.
Maintenance
104
Maintenance
105
Technical data
IEC data
Ratings
The IEC ratings for the ACS800-01 with 50 Hz and 60 Hz supplies are given below.
The symbols are described below the table.
ACS800-01 size Nominal No- Light-overload Heavy-duty use Frame Air flow Heat
overload
ratings use
use size dissipation
Icont.max Imax Pcont.max I2N PN I2hd Phd
A A
kW
A kW A kW m3/h W
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0001-2 5.1 6.5 1.1 4.7 0.75 3.4 0.55 R2 35 100
-0002-2 6.5 8.2 1.5 6.0 1.1 4.3 0.75 R2 35 100
-0003-2 8.5 10.8 1.5 7.7 1.5 5.7 1.1 R2 35 100
-0004-2 10.9 13.8 2.2 10.2 2.2 7.5 1.5 R2 35 120
-0005-2 13.9 17.6 3 12.7 3 9.3 2.2 R2 35 140
-0006-2 19 24 4 18 4 14 3 R3 69 160
-0009-2 25 32 5.5 24 5,5 19 4 R3 69 200
-0011-2 34 46 7.5 31 7.5 23 5.5 R3 69 250
-0016-2 44 62 11 42 11 32 7.5 R4 103 340
-0020-2 55 72 15 50 11 37 7.5 R4 103 440
-0025-2 72 86 18.5 69 18.5 49 11 R5 250 530
-0030-2 86 112 22 80 22 60 15 R5 250 610
-0040-2 103 138 30 94 22 69 18.5 R5 250 810
-0050-2 141 164 37 132 37 97 30 R6 405 1190
-0060-2 166 202 45 155 45 115 30 R6 405 1190
-0070-2 202 282 55 184 55 141 37 R6 405 1440
Technical data
106
ACS800-01 size Nominal No- Light-overload Heavy-duty use Frame Air flow Heat
overload
ratings use
use size dissipation
Icont.max Imax Pcont.max I2N PN I2hd Phd
A A
kW
A kW A kW m3/h W
Three-phase supply voltage 380 V, 400 V or 415 V
-0003-3 5.1 6.5 1.5 4.7 1.5 3.4 1.1 R2 35 100
-0004-3 6.5 8.2 2.2 5.9 2.2 4.3 1.5 R2 35 120
-0005-3 8.5 10.8 3 7.7 3 5.7 2.2 R2 35 140
-0006-3 10.9 13.8 4 10.2 4 7.5 3 R2 35 160
-0009-3 13.9 17.6 5.5 12.7 5.5 9.3 4 R2 35 200
-0011-3 19 24 7.5 18 7.5 14 5.5 R3 69 250
-0016-3 25 32 11 24 11 19 7.5 R3 69 340
-0020-3 34 46 15 31 15 23 11 R3 69 440
-0025-3 44 62 22 41 18.5 32 15 R4 103 530
-0030-3 55 72 30 50 22 37 18.5 R4 103 610
-0040-3 72 86 37 69 30 49 22 R5 250 810
-0050-3 86 112 45 80 37 60 30 R5 250 990
-0060-3 103 138 55 94 45 69 37 R5 250 1190
-0075-3 145 170 75 141 75 100 45 R5 405 1440
-0070-3 * 141 164 75 132 55 97 45 R6 405 1440
-0100-3 166 202 90 155 75 115 55 R6 405 1940
-0120-3 202 282 110 184 90 141 75 R6 405 2310
-0135-3 225 326 110 220 110 163 90 R6 405 2810
-0165-3 260 326 132 254 132 215 110 R6 405 3260
-0205-3 290 351 160 285 160 234 132 R6 405 4200
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0004-5 4.9 6.5 2.2 4.5 2.2 3.4 1.5 R2 35 120
-0005-5 6.2 8.2 3 5.6 3 4.2 2.2 R2 35 140
-0006-5 8.1 10.8 4 7.7 4 5.6 3 R2 35 160
-0009-5 10.5 13.8 5.5 10 5.5 7.5 4 R2 35 200
-0011-5 13.2 17.6 7.5 12 7.5 9.2 5.5 R2 35 250
-0016-5 19 24 11 18 11 13 7.5 R3 69 340
-0020-5 25 32 15 23 15 18 11 R3 69 440
-0025-5 34 46 18.5 31 18.5 23 15 R3 69 530
-0030-5 42 62 22 39 22 32 18.5 R4 103 610
-0040-5 48 72 30 44 30 36 22 R4 103 810
-0050-5 65 86 37 61 37 50 30 R5 250 990
-0060-5 79 112 45 75 45 60 37 R5 250 1190
-0070-5 96 138 55 88 55 69 45 R5 250 1440
-0105-5 145 170 90 141 90 100 55 R5 405 2150
-0100-5 * 124 164 75 115 75 88 55 R6 405 1940
-0120-5 157 202 90 145 90 113 75 R6 405 2310
-0140-5 180 282 110 163 110 141 90 R6 405 2810
-0165-5 225 326 132 220 132 163 110 R6 405 3260
-0205-5 260 326 160 254 160 215 132 R6 405 3800
-0255-5 290 351 200 285 200 234 160 R6 405 4500
* Type not available any more
Technical data
107
ACS800-01 size Nominal No- Light-overload Heavy-duty use Frame Air flow Heat
overload
ratings use
use size dissipation
Icont.max Imax Pcont.max I2N PN I2hd Phd
A A
kW
A kW A kW m3/h W
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0011-7 13 14 11 11.5 7.5 8.5 5.5 R4 103 300
-0016-7 17 19 15 15 11 11 7.5 R4 103 340
-0020-7 22 28 18.5 20 15 15 11 R4 103 440
-0025-7 25 38 22 23 18.5 19 15 R4 103 530
-0030-7 33 44 30 30 22 22 18.5 R4 103 610
-0040-7 36 54 30 34 30 27 22 R4 103 690
-0050-7 51 68 45 46 37 34 30 R5 250 840
-0060-7 57 84 55 52 45 42 37 R5 250 1010
-0070-7 79 104 75 73 55 54 45 R6 405 1220
-0100-7 93 124 90 86 75 62 55 R6 405 1650
-0120-7 113 172 110 108 90 86 75 R6 405 1960
-0145-7 134 190 132 125 110 95 90 R6 405 2660
-0175-7 166 245 160 155 132 131 110 R6 405 3470
-0205-7 190 245 160 180 160 147 132 R6 405 4180
0009693
Symbols
Nominal ratings
Icont.max continuous rms output current. No overload capability at 40 °C (104 °F).
Imax maximum output current. Available for 10 s at start, otherwise as long as allowed by drive
temperature.
Typical ratings:
No-overload use
Pcont.max typical motor power. The power ratings apply to most IEC 60034 motors at the nominal
voltage, 230 V, 400 V, 500 V or 690 V.
Light-overload use (10% overload capability)
I2N continuous rms current. 10% overload is allowed for one minute every 5 minutes.
PN typical motor power. The power ratings apply to most IEC 60034 motors at the nominal
voltage, 230 V, 400 V, 500 V or 690 V.
Heavy-duty use (50% overload capability)
I2hd continuous rms current. 50% overload is allowed for one minute every 5 minutes.
Phd typical motor power. The power ratings apply to most IEC 60034 motors at the nominal
voltage, 230 V, 400 V, 500 V or 690 V.
Sizing
The current ratings are the same regardless of the supply voltage within one voltage
range. To achieve the rated motor power given in the table, the rated current of the
drive must be higher than or equal to the rated motor current.
Note 1: The maximum allowed motor shaft power is limited to 1.5 · Phd, 1.1 · PN or
Pcont.max (whichever value is greatest). If the limit is exceeded, motor torque and
current are automatically restricted. The function protects the input bridge of the
drive against overload. If the condition exists for 5 minutes, the limit is set to
Pcont.max.
Note 2: The ratings apply at an ambient temperature of 40 °C (104 °F). At lower
temperatures the ratings are higher (except Imax).
Technical data
108
Note 3: Use the DriveSize PC tool for a more accurate dimensioning if the ambient
temperature is below 40 °C (104 °F) or the drive is loaded cyclically.
Derating
The load capacity (current and power) decreases if the installation site altitude
exceeds 1000 metres (3300 ft), or if the ambient temperature exceeds 40 °C
(104 °F).
Temperature derating
In the temperature range +40 °C (+104 °F) to +50 °C (+122 °F) the rated output
current is decreased 1% for every additional 1 °C (1.8 °F). The output current is
calculated by multiplying the current given in the rating table by the derating factor.
Example If the ambient temperature is 50 °C (+122 °F), the derating factor is 100% -
1 % · 10 °C = 90% or 0.90. The output current is then 0.90 · I2N or 0.90 · I2hd.
°C
Altitude derating
In altitudes from 1000 to 4000 m (3300 to 13123 ft) above sea level, the derating is
1% for every 100 m (328 ft). For a more accurate derating, use the DriveSize PC
tool. See Installation sites above 2000 metres (6562 feet) on page 58.
Fuses
gG and aR fuses for protection against short-circuit in the input power cable or drive
are listed below. Either fuse type may be used if it operates rapidly enough.
Frame sizes R2 to R4
Check from the fuse time-current curve that the operating time of the fuse is
below 0.5 seconds. The operating time depends on the supply network impedance
and the cross-sectional area and length of the supply cable. The short-circuit current
can be calculated as shown below in section Frame sizes R5 and R6.
Note 1: See also Planning the electrical installation: Thermal overload and short-circuit protection. For
UL recognized fuses, see NEMA data on page 118.
Note 2: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Larger fuses than the recommended ones must not be used.
Note 4: Fuses from other manufacturers can be used if they meet the ratings and the melting curve of
the fuse does not exceed the melting curve of the fuse mentioned in the table.
Technical data
109
Technical data
110
U
Ik2-ph =
2· Rc2 + (Zk + Xc)2
where
Ik2-ph = short-circuit current in symmetrical two-phase short-circuit
U = network line-to-line voltage (U)
Rc = cable resistance (ohm)
Zk = zk · UN2/SN = transformer impedance (ohm)
zk = transformer impedance (%)
UN = transformer rated voltage (V)
SN = nominal apparent power of the transformer (kVA)
Xc = cable reactance (ohm).
Calculation example
Drive:
• ACS800-01-0075-3
• supply voltage
Transformer:
• rated power SN = 600 kVA
• rated voltage (drive supply voltage) UN = 430 V
• transformer impedance zk = 7.2%.
Supply cable:
• length = 170 m
• resistance/length = 0.398 ohm/km
• reactance/length = 0.082 ohm/km.
ohm
Rc = 170 m · 0.398 km = 67.66 mohm
ohm
Xc = 170 m · 0.082 = 13.94 mohm
km
Technical data
111
410 V
Ik2-ph = = 2.7 kA
2· (67.66 mohm)2 + (22.19 mohm + 13.94 mohm)2
The calculated short-circuit current 2.7 kA is higher than the minimum short-circuit
current of the drive gG fuse type OFAF00H160 (2400 A). -> The 500 V gG fuse (ABB
Control OFAF00H160) can be used.
Standard gG fuses
ACS800-01 size Input Min. Fuse
current short-
circuit
current 1)
A A A2s * V Manufacturer Type IEC size
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0025-2 67 1050 80 34500 500 ABB Control OFAF000H80 000
-0030-2 81 1480 100 63600 500 ABB Control OFAF000H100 000
-0040-2 101 1940 125 103000 500 ABB Control OFAF00H125 00
-0050-2 138 2400 160 200000 500 ABB Control OFAF00H160 00
-0060-2 163 2850 200 350000 500 ABB Control OFAF1H200 1
-0070-2 202 3300 224 420000 500 ABB Control OFAF1H224 1
Three-phase supply voltage 380 V, 400 V or 415 V
-0040-3 69 1050 80 34500 500 ABB Control OFAF000H80 000
-0050-3 83 1480 100 63600 500 ABB Control OFAF000H100 000
-0060-3 100 1940 125 103000 500 ABB Control OFAF00H125 00
-0075-3 142 2400 160 200000 500 ABB Control OFAF00H160 00
-0070-3 ** 138 2400 160 200000 500 ABB Control OFAF00H160 00
-0100-3 163 2850 200 350000 500 ABB Control OFAF1H200 1
-0120-3 198 3300 224 420000 500 ABB Control OFAF1H224 1
-0135-3 221 3820 250 550000 500 ABB Control OFAF1H250 1
-0165-3 254 4510 315 1100000 500 ABB Control OFAF2H315 2
-0205-3 286 4510 315 1100000 500 ABB Control OFAF2H315 2
Technical data
112
Standard gG fuses
ACS800-01 size Input Min. Fuse
current short-
circuit
current 1)
A A A2s * V Manufacturer Type IEC size
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0050-5 64 1050 80 34500 500 ABB Control OFAF000H80 000
-0060-5 78 1480 100 63600 500 ABB Control OFAF000H100 000
-0070-5 95 1940 125 103000 500 ABB Control OFAF00H125 00
-0105-5 142 2400 160 200000 500 ABB Control OFAF00H160 00
-0100-5 ** 121 2400 160 200000 500 ABB Control OFAF00H160 00
-0120-5 155 2850 200 350000 500 ABB Control OFAF1H200 1
-0140-5 180 2850 200 350000 500 ABB Control OFAF1H200 1
-0165-5 222 3820 250 550000 500 ABB Control OFAF1H250 1
-0205-5 256 4510 315 1100000 500 ABB Control OFAF2H315 2
-0255-5 286 4510 315 1100000 500 ABB Control OFAF2H315 2
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0050-7 52 740 63 28600 690 ABB Control OFAA0GG63 0
-0060-7 58 740 63 28600 690 ABB Control OFAA0GG63 0
-0070-7 79 1050 80 52200 690 ABB Control OFAA0GG80 0
-0100-7 91 1480 100 93000 690 ABB Control OFAA1GG100 1
-0120-7 112 1940 125 126000 690 ABB Control OFAA1GG125 1
-0145-7 131 2400 160 220000 690 ABB Control OFAA1GG160 1
-0175-7 162 2850 200 350000 690 ABB Control OFAA1GG200 1
-0205-7 186 3820 250 700000 690 ABB Control OFAA2GG250 2
* maximum total I2t value for 550 V or 690 V
** Type not available any more.
1)
minimum short-circuit current of the installation
Note 1: See also Planning the electrical installation: Thermal overload and short-circuit protection. For UL recognized
fuses, see NEMA data on page 118.
Note 2: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Larger fuses than the recommended ones must not be used.
Note 4: Fuses from other manufacturers can be used if they meet the ratings and the melting curve of the fuse does not
exceed the melting curve of the fuse mentioned in the table.
00096931, 00556489
Technical data
113
Technical data
114
Dimensional drawings).
4) This cable type cannot be used in the drive because the cable lug is not designed for multiple wires.
Technical data
115
ACS800-01 size Cable type Supply transformer minimum apparent power SN (kVA)
Copper Aluminium Max. cable length with gG fuses Max. cable length with aR fuses
10 m 50 m 100 m 10 m 100 m 200 m
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0050-7 3×16 Cu 3×25 Al 65 67 70 63 63 63
-0060-7 3×16 Cu 3×25 Al 70 70 70 70 70 70
-0070-7 3×25 Cu 3×50 Al 95 95 99 95 95 95
-0100-7 3×35 Cu 3×50 Al 130 140 150 110 110 110
-0120-7 3×50 Cu 3×70 Al 180 180 190 140 140 140
-0145-7 3×70 Cu 3×95 Al 220 220 240 160 160 160
-0175-7 3×95 Cu 3×120 Al 260 260 280 200 200 200
-0205-7 3×95 Cu 3×150 Al 340 360 390 230 230 230
Note 1: The supply transformer minimum power in kVA is calculated with a zk value of 6% and frequency 50 Hz.
Note 2: This table is not intended for transformer selection - that must be done separately.
The following parameters may effect on the correct operation of the protection:
• cable length, i.e. the longer the cable the weaker the fuse protection, as the long
cable limits the fault current
• cable size, i.e. the smaller the cable the weaker the fuse protection, as the small
cable size limits the fault current
• transformer size, i.e the smaller the transformer the weaker the fuse protection,
as the small transformer limits the fault current
• transformer impedance, i.e. the higher the zk the weaker the fuse protection as
high impedance limits the fault current.
The protection can be improved by installing a larger supply transformer and/or
bigger cables, and in most cases by selecting aR fuses instead of gG fuses.
Selection of smaller fuses improves the protection, but may also affect the fuse life
time and lead to unnecessary operation of the fuses.
In case of any uncertainty regarding the drive protection, please contact your local
ABB.
Technical data
116
Cable types
The table below gives copper and aluminium cable types for different load currents.
Cable sizing is based on max. 9 cables laid on a cable ladder side by side, ambient
temperature 30 °C (86 °F), PVC insulation, surface temperature 70 °C (158 °F)
(EN 60204-1 and IEC 60364-5-52:2001). For other conditions, size the cables
according to local safety regulations, appropriate input voltage and the load current
of the drive.
Copper cables with Aluminium cables with
concentric copper shield concentric copper shield
Max. load Cable type Max. load Cable type
current current
A mm2 A mm2
13 3×1.5 61 3×25
18 3×2.5 69 3×35
24 3×4 83 3×50
30 3×6 107 3×70
42 3×10 130 3×95
56 3×16 151 3×120
71 3×25 174 3×150
88 3×35 199 3×185
107 3×50 235 3×240
137 3×70 274 3 × (3×50) *
167 3×95 260 2 × (3×95) *
193 3×120
223 3×150
255 3×185
301 3×240
3BFA 01051905
* This cable type cannot be used in this drive because the cable lug
is not designed for multiple wires.
Technical data
117
Cable entries
Brake resistor, mains and motor cable terminal sizes (per phase), accepted cable
diameters and tightening torques are given below.
Frame U1, V1, W1, U2, V2, W2, R+, R- Earthing PE
size Wire size Max. cable Ø Cable Ø Tightening Wire size Tightening
IP21 IP55 torque torque
mm2 mm mm Nm mm2 Nm
R2 up to 16* 21 14...20 1.2...1.5 up to 10 1.5
R3 up to 16* 21 14...20 1.2...1.5 up to 10 1.5
R4 up to 25 29 23...35 2…4 up to 16 3.0
R5 6...70 35 23...35 15 6...70 15
R6 95...240 **† 53 † 30...45 † 20...40 95 8
Technical data
118
NEMA data
Ratings
The NEMA ratings for the ACS800-U1 with 60 Hz supplies are given below. The
symbols are described below the table. For sizing, derating and 50 Hz supplies, see
IEC data on page 105.
ACS800-U1 size Imax Normal use Heavy-duty use Frame Air flow Heat
size dissipation
I2N PN I2hd Phd
A A hp A hp ft3/min BTU/Hr
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0002-2 8.2 6.6 1.5 4.6 1 R2 21 350
-0003-2 10.8 8.1 2 6.6 1.5 R2 21 350
-0004-2 13.8 11 3 7.5 2 R2 21 410
-0006-2 24 21 5 13 3 R3 41 550
-0009-2 32 27 7.5 17 5 R3 41 680
-0011-2 46 34 10 25 7.5 R3 41 850
-0016-2 62 42 15 31 10 R4 61 1150
-0020-2 72 54 20 1) 42 15 2) R4 61 1490
-0025-2 86 69 25 54 20 2) R5 147 1790
-0030-2 112 80 30 68 25 2) R5 147 2090
-0040-2 138 104 40 1) 80 30 2) R5 147 2770
-0050-2 164 132 50 104 40 R6 238 3370
-0060-2 202 157 60 130 50 2) R6 238 4050
-0070-2 282 192 75 154 60 2) R6 238 4910
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V or 480 V
-0004-5 6.5 4.9 3 3.4 2 R2 21 410
-0005-5 8.2 6.2 3 4.2 2 R2 21 480
-0006-5 10.8 8.1 5 5.6 3 R2 21 550
-0009-5 13.8 11 7.5 8.1 5 R2 21 690
-0011-5 17.6 14 10 11 7.5 R2 21 860
-0016-5 24 21 15 15 10 R3 41 1150
-0020-5 32 27 20 21 15 R3 41 1490
-0025-5 46 34 25 27 20 R3 41 1790
-0030-5 62 42 30 34 25 R4 61 2090
-0040-5 72 52 40 37 30 3) R4 61 2770
-0050-5 86 65 50 52 40 R5 147 3370
-0060-5 112 79 60 65 50 R5 147 4050
-0070-5 138 96 75 77 60 R5 147 4910
-0105-5 170 141 100 100 75 R5 238 7340
-0100-5 5) 164 124 100 96 75 R6 238 6610
-0120-5 202 157 125 124 100 R6 238 7890
-0140-5 282 180 150 156 125 R6 238 9600
-0205-5 326 245 200 215 150 R6 238 12980
Technical data
119
ACS800-U1 size Imax Normal use Heavy-duty use Frame Air flow Heat
size dissipation
I2N PN I2hd Phd
A A hp A hp ft3/min BTU/Hr
Three-phase supply voltage 525 V, 575 V, 600 V
-0011-7 14 11.5 10 8.5 7.5 R4 61 1050
-0016-7 19 15 10 11 10 R4 61 1200
-0020-7 28 20 15/20 4) 15 152) R4 61 1550
-0025-7 38 23 20 20 202) R4 61 1850
-0030-7 44 30 25/30 4) 25 252) R4 61 2100
-0040-7 54 34 30 30 302) R4 61 2400
-0050-7 68 46 40 40 402) R5 147 2900
-0060-7 84 52 50 42 40 R5 147 3450
-0070-7 104 73 60 54 50 R6 238 4200
-0100-7 124 86 75 62 60 R6 238 5650
-0120-7 172 108 100 86 75 R6 238 6700
-0145-7 190 125 125 99 100 R6 238 9100
-0175-7 245 155 150 131 125 R6 238 11850
-0205-7 245 192 200 147 150 R6 238 14300
00096931
1) Overload may be limited to 5% at high speeds (> 90% speed) by the internal power limit of the drive.
The limitation also depends on motor characteristics and network voltage.
2)
Overload may be limited to 40% at high speeds (> 90% speed) by the internal power limit of the
drive. The limitation also depends on motor characteristics and network voltage.
3) Special 4-pole high-efficiency NEMA motor
4) Higher rating is available with special 4-pole high-efficiency NEMA motor
5) Type not available any more.
Symbols
Nominal ratings
Imax maximum output current. Available for 10 s at start, otherwise as long as allowed by drive
temperature.
Normal use (10% overload capability)
I2N continuous rms current. 10% overload is typically allowed for one minute every 5 minutes.
PN typical motor power. The power ratings apply to most 4-pole NEMA rated motors (230 V,
460 V or 575 V).
Heavy-duty use (50% overload capability)
I2hd continuous rms current. 50% overload is typically allowed for one minute every 5 minutes.
Phd typical motor power. The power ratings apply to most 4-pole NEMA rated motors (230 V,
460 V or 575 V).
Note 1: The ratings apply at an ambient temperature of 40 °C (104 °F). In lower temperatures the
ratings are higher (except Imax).
Sizing
See page 107.
Derating
See page 108.
Technical data
120
Fuses
UL class T fuses for branch circuit protection are listed below. Fast acting class T or
faster fuses are recommended in the USA.
Check from the fuse time-current curve that the operating time of the fuse is
below 0.5 seconds for units of frame sizes R2 to R4 and 0.1 seconds for units
of frame sizes R5 and R6. The operating time depends on the supply network
impedance and the cross-sectional area and length of the supply cable. The short-
circuit current can be calculated as shown in section Frame sizes R5 and R6 on
page 110.
Note 1: See also Planning the electrical installation: Thermal overload and short-circuit protection.
Note 2: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Larger fuses must not be used.
Note 4: Fuses from other manufacturers can be used if they meet the ratings and the melting curve of
the fuse does not exceed the melting curve of the fuse mentioned in the table.
ACS800-U1 type Frame size Input Fuse
current
A A V Manufacturer Type UL class
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0002-2 R2 5.2 10 600 Bussmann JJS-10 T
-0003-2 R2 6.5 10 600 Bussmann JJS-10 T
-0004-2 R2 9.2 15 600 Bussmann JJS-15 T
-0006-2 R3 18 25 600 Bussmann JJS-25 T
-0009-2 R3 24 30 600 Bussmann JJS-30 T
-0011-2 R3 31 40 600 Bussmann JJS-40 T
-0016-2 R4 38 50 600 Bussmann JJS-50 T
-0020-2 R4 49 70 600 Bussmann JJS-70 T
-0025-2 R5 64 90 600 Bussmann JJS-90 T
-0030-2 R5 75 100 600 Bussmann JJS-100 T
-0040-2 R5 102 125 600 Bussmann JJS-125 T
-0050-2 R6 126 175 600 Bussmann JJS-175 T
-0060-2 R6 153 200 600 Bussmann JJS-200 T
-0070-2 R6 190 250 600 Bussmann JJS-250 T
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V or 480 V
-0004-5 R2 4.1 10 600 Bussmann JJS-10 T
-0005-5 R2 5.4 10 600 Bussmann JJS-10 T
-0006-5 R2 6.9 10 600 Bussmann JJS-10 T
-0009-5 R2 9.8 15 600 Bussmann JJS-15 T
-0011-5 R2 13 20 600 Bussmann JJS-20 T
-0016-5 R3 18 25 600 Bussmann JJS-25 T
-0020-5 R3 24 35 600 Bussmann JJS-35 T
-0025-5 R3 31 40 600 Bussmann JJS-40 T
-0030-5 R4 40 50 600 Bussmann JJS-50 T
-0040-5 R4 52 70 600 Bussmann JJS-70 T
-0050-5 R5 63 80 600 Bussmann JJS-80 T
-0060-5 R5 77 100 600 Bussmann JJS-100 T
-0070-5 R5 94 125 600 Bussmann JJS-125 T
-0105-5 R5 138 150 600 Bussmann JJS-150 T
-0100-5 * R6 121 150 600 Bussmann JJS-150 T
-0120-5 R6 155 200 600 Bussmann JJS-200 T
-0140-5 R6 179 225 600 Bussmann JJS-225 T
-0205-5 R6 243 350 600 Bussmann JJS-350 T
Technical data
121
Cable types
Cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire
insulation at 40 °C (104 °F) ambient temperature. Not more than three current-
carrying conductors in raceway or cable or earth (directly buried). For other
conditions, dimension the cables according to local safety regulations, appropriate
input voltage and the load current of the drive.
Copper cables with concentric copper
shield
Max. load Cable type
current
A AWG/MCM
18 14
22 12
31 10
44 8
57 6
75 4
88 3
101 2
114 1
132 1/0
154 2/0
176 3/0
202 4/0
224 250 MCM or 2 × 1
251 300 MCM or 2 × 1/0
00096931
Technical data
122
Cable Entries
Brake resistor, input and motor cable (per phase) terminal sizes, accepted cable
diameters and tightening torques are given below.
Frame U1, V1, W1, U2, V2, W2, R+, R- Earthing PE
size Wire size Knock-out hole Ø Tightening Wire size Tightening
(UL type 1) torque torque
AWG in. lbf ft AWG lbf ft
R2 up to 6* 1.10 0.9…1.1 up to 8 1.1
R3 up to 6* 1.14 0.9...1.1 up to 8 1.1
R4 up to 4 1.38 1.5…3.0 up to 5 2.2
R5 10…2/0 1.97 11.1 10...2/0 11.1
R6 3/0…500 MCM** † 2.40 † 14.8...29.5 4/0 5.9
* In -0205-3 and -0255-5 units, H1 is 38.46 in. and weight is 150 lb.
Technical data
123
Motor connection
Voltage (U2) 0 to U1, 3-phase symmetrical, Umax at the field weakening point
Frequency DTC mode: 0 to 3.2 · fFWP. Maximum frequency 300 Hz.
UNmains
fFWP = · fNmotor
UNmotor
fFWP: frequency at field weakening point; UNmains: mains (input power) voltage;
UNmotor: rated motor voltage; fNmotor: rated motor frequency
Frequency resolution 0.01 Hz
Current See section IEC data.
Power limit 1.5 · Phd, 1.1 · PN or Pcont.max (whichever value is greatest)
Field weakening point 8 to 300 Hz
Switching frequency 3 kHz (average). In 690 V units 2 kHz (average).
Maximum recommended Sizing method Max. motor cable length
motor cable length DTC control Scalar control
according to I2N and I2hd R2 to R3: 100 m (328 ft) R2: 150 m (492 ft)
according to Icont.max at R4 to R6: 300 m (984 ft) R3 to R6: 300 m (984 ft)
ambient temperatures below
30 °C (86 °F)
according to Icont.max at R2: 50 m (164 ft) Note: This applies to units with EMC filter
ambient temperatures above also.
30 °C (86 °F) R3 and R4: 100 m (328 ft)
R5 and R6: 150 m (492 ft)
Note: With cables longer than 100 m (328 ft), the EMC Directive requirements may not be
fulfilled. See section CE marking.
Efficiency
Approximately 98% at nominal power level
Technical data
124
Cooling
Method Internal fan, flow direction from bottom to top.
Free space around the unit See chapter Mechanical installation.
Degree of protection
IP21 (UL type 1) and IP55 (UL type 12). Without the connection box and front cover, the
unit must be protected against contact according to IP2x [see chapter Electrical
installation: Cabinet installation (IP21, UL type 1)].
Technical data
125
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Operation Storage Transportation
installed for stationary use in the protective package in the protective package
Installation site altitude 0 to 4000 m (13123 ft) above - -
sea level [above 1000 m
(3281 ft), see section
Derating]
Drives with option +Q967:
0 to 2000 (6562 ft)
Air temperature -15 to +50 °C (5 to 122 °F). -40 to +70 °C -40 to +70 °C
No frost allowed. See section (-40 to +158 °F) (-40 to +158 °F)
Derating.
Relative humidity 5 to 95% Max. 95% Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
corrosive gases.
Contamination levels No conductive dust allowed.
(IEC 60721-3-3, IEC 60721-3- Boards without coating: Boards without coating: Boards without coating:
2, IEC 60721-3-1) Chemical gases: Class 3C1 Chemical gases: Class 1C2 Chemical gases: Class 2C2
Solid particles: Class 3S2 Solid particles: Class 1S3 Solid particles: Class 2S2
Boards with coating: Boards with coating: Boards with coating:
Chemical gases: Class 3C2 Chemical gases: Class 1C2 Chemical gases: Class 2C2
Solid particles: Class 3S2 Solid particles: Class 1S3 Solid particles: Class 2S2
Atmospheric pressure 70 to 106 kPa 70 to 106 kPa 60 to 106 kPa
0.7 to 1.05 atmospheres 0.7 to 1.05 atmospheres 0.6 to 1.05 atmospheres
Vibration (IEC 60068-2) Max. 1 mm (0.04 in.) Max. 1 mm (0.04 in.) Max. 3.5 mm (0.14 in.)
(5 to 13.2 Hz), (5 to 13.2 Hz), (2 to 9 Hz),
max. 7 m/s2 (23 ft/s2) max. 7 m/s2 (23 ft/s2) max. 15 m/s2 (49 ft/s2)
(13.2 to 100 Hz) sinusoidal (13.2 to 100 Hz) sinusoidal (9 to 200 Hz) sinusoidal
Shock (IEC 60068-2-27) Not allowed Max. 100 m/s2 (330 ft./s2), Max. 100 m/s2 (330 ft./s2),
11 ms 11 ms
Free fall Not allowed 250 mm (10 in.) for weight 250 mm (10 in.) for weight
under 100 kg (220 lb) under 100 kg (220 lb)
100 mm (4 in.) for weight 100 mm (4 in.) for weight
over 100 kg (220 lb) over 100 kg (220 lb)
Technical data
126
Materials
Drive enclosure • PC/ABS 2.5 mm, colour NCS 1502-Y (RAL 9002 / PMS 420 C)
• hot-dip zinc coated steel sheet 1.5 to 2 mm, thickness of coating 100 micrometres
• cast aluminium AlSi (R2 and R3)
• extruded aluminium AlSi (R4 to R6)
Package Depends on the frame size and selected options: cardboard, heavy duty cardboard or
plywood, EPS cushions (expanded polystyrene), wooden pallet
Plastic covering of the package: PE-LD, bands PP or steel.
Disposal The main parts of the drive can be recycled to preserve natural resources and energy.
Product parts and materials should be dismantled and separated.
Generally all metals, such as steel, aluminum, copper and its alloys, and precious metals
can be recycled as material. Plastics, rubber, cardboard and other packaging material can
be used in energy recovery. Printed circuit boards and DC capacitors (C1-1 to C1-x) need
selective treatment according to IEC 62635 guidelines. To aid recycling, plastic parts are
marked with an appropriate identification code.
Contact your local ABB distributor for further information on environmental aspects and
recycling instructions for professional recyclers. End of life treatment must follow
international and local regulations.
Applicable standards
• EN 50178:1997 Electronic equipment for use in power installations
• EN 60204-1:2006 +A1:2009 Safety of machinery. Electrical equipment of machines. Part 1: General requirements.
Provisions for compliance: The final assembler of the machine is responsible for installing
- an emergency-stop device
- a supply disconnecting device.
• EN 60529:1991 Degrees of protection provided by enclosures (IP code)
+ corrigendum May 1993
+ A1:2000
• IEC 60664-1:2007 Insulation coordination for equipment within low-voltage systems. Part 1: Principles,
requirements and tests.
• EN 61800-3:2004 Adjustable speed electrical power drive systems. Part 3: EMC requirements and specific
test methods
• UL 508C (2002) UL Standard for Safety, Power Conversion Equipment, second edition
• NEMA 250 (2003) Enclosures for Electrical Equipment (1000 Volts Maximum)
• CSA C22.2 No. 14-05 Industrial control equipment
(2005)
Technical data
127
CE marking
A CE mark is attached to the drive to verify that the unit follows the provisions of the
European Low Voltage and EMC Directives. The CE marking also verifies that the
drive, in regard to its safety functions (such as Safe torque off), conforms with the
Machinery Directive as a safety component.
Definitions
EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic
equipment to operate without problems within an electromagnetic environment.
Likewise, the equipment must not disturb or interfere with any other product or
system within its locality.
First environment includes establishments connected to a low-voltage network which
supplies buildings used for domestic purposes.
Second environment includes establishments connected to a network not supplying
domestic premises.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be
installed and commissioned only by a professional when used in the first
environment. Note: A professional is a person or organisation having necessary
skills in installing and/or commissioning power drive systems, including their EMC
aspects.
Drive of category C3: drive of rated voltage less than 1000 V and intended for use in
the second environment and not intended for use in the first environment.
Technical data
128
Drive of category C4: drive of rated voltage equal to or above 1000 V, or rated
current equal to or above 400 A, or intended for use in complex systems in the
second environment.
First environment (drive of category C2)
The drive complies with the standard with the following provisions:
1. The drive is equipped with EMC filter +E202.
2. The motor and control cables are selected as specified in the hardware manual.
3. The drive is installed according to the instructions given in the hardware manual.
4. Maximum cable length is 100 metres.
WARNING! The drive may cause radio interference if used in a residential or
domestic environment. The user is required to take measures to prevent
interference, in addition to the requirements for CE compliance listed above, if
necessary.
Note: It is not allowed to install a drive equipped with EMC filter +E202 on IT
(ungrounded) systems. The supply network becomes connected to ground potential
through the EMC filter capacitors which may cause danger or damage the unit.
Second environment (drive of category C3)
The drive complies with the standard with the following provisions:
1. Frame sizes R2…R5: The drive is equipped with EMC filter +E200. The filter is
suitable for TN (earthed) systems only.
Frame size R6: The drive is equipped with EMC filter +E210. The filter is suitable
for TN (grounded) and IT (ungrounded) systems.
2. The motor and control cables are selected as specified in the hardware manual.
3. The drive is installed according to the instructions given in the hardware manual.
4. Maximum cable length is 100 metres.
WARNING! A drive of category C3 is not intended to be used on a low-voltage public
network which supplies domestic premises. Radio frequency interference is
expected if the drive is used on such a network.
Technical data
129
Neighbouring network
Static screen
Point of measurement
Equipment Equipment
“C-tick” marking
A “C-tick” mark is attached to each drive in order to verify compliance with the EMC
product standard (EN 61800-3:2004), required under the Trans-Tasman
Electromagnetic Compatibility Scheme for levels 1, 2 and 3 in Australia and New
Zealand. See section Compliance with EN 61800-3:2004.
Technical data
130
UL/CSA markings
The ACS800-01 and ACS800-U1 units of UL type 1 are cULus listed and CSA
marked.
UL checklist
• The drive is to be used in a heated, indoor controlled environment. The drive must
be installed in clean air according to enclosure classification. Cooling air must be
clean, free from corrosive materials and electrically conductive dust. See section
Ambient conditions for specific limits.
• The maximum ambient air temperature is 40 °C (104 °F) at rated current. The
current is derated for 40 to 50 °C (104 to 122 °F).
• The drive is suitable for use on a circuit capable of delivering not more than 100
kA rms symmetrical amperes at the drive nominal voltage (600 V maximum for
690 V units) when protected by fuses given in the NEMA data fuse table. The
ampere rating is based on tests done according to UL 508C.
• The cables located within the motor circuit must be rated for at least 75 °C
(167 °F) in UL-compliant installations.
• The input cable must be protected with fuses. Circuit breakers must not be used
without fuses in the USA. Suitable IEC (class aR) fuses and UL (class T) fuses
are listed in this hardware manual.
• For installation in the United States, branch circuit protection must be provided in
accordance with the National Electrical Code (NEC) and any applicable local
codes. To fulfil this requirement, use the UL classified fuses.
• For installation in Canada, branch circuit protection must be provided in
accordance with the Canadian Electrical Code and any applicable provincial
codes. To fulfil this requirement, use the UL classified fuses.
• The drive provides overload protection in accordance with the National Electrical
Code (NEC). See the firmware manual for setting. Default setting is off, must be
activated at start-up.
• Brake chopper - ABB has brake choppers that, when applied with appropriately
sized brake resistors, will allow the drive to dissipate regenerative energy
(normally associated with quickly decelerating a motor). Proper application of the
brake chopper is defined in chapter Resistor braking.
Disclaimer
The manufacturer shall have no obligation with respect to any product which (i) has
been improperly repaired or altered; (ii) has been subjected to misuse, negligence or
accident; (iii) has been used in a manner contrary to the manufacturer's instructions;
or (iv) has failed as a result of ordinary wear and tear.
Technical data
131
Dimensional drawings
Dimensional drawings of the ACS800-01 are shown below. The dimensions are
given in millimetres and [inches].
Dimensional drawings
132
64646117-B
Dimensional drawings
133
64646150-B
Dimensional drawings
134
64646192-B
Dimensional drawings
135
64646206-C
Dimensional drawings
136
64646214-B
Dimensional drawings
137
64647130-B
Dimensional drawings
138
64646222-B
Dimensional drawings
139
64647156-B
Dimensional drawings
140
64646231-B
Dimensional drawings
141
3AUA0000045356
Dimensional drawings
142
64684957-C
Dimensional drawings
143
3AUA0000057578
Dimensional drawings
144
Dimensional drawings
145
64741829-A
Dimensional drawings
146
64788051-A
Dimensional drawings
147
64741811-A
Dimensional drawings
148
64788078-A
Dimensional drawings
149
64741802-A
Dimensional drawings
150
64788086-A
Dimensional drawings
151
64741748-A
Dimensional drawings
152
64788094-A
Dimensional drawings
153
64739361-A
Dimensional drawings
154
3AUA0000045584
Dimensional drawings
155
64788108-A
Dimensional drawings
156
Frame size R6 (UL type 12, IP55) -0205-3 and -0255-5 units
3AUA0000057583
Dimensional drawings
157
3AFE68293898
Dimensional drawings
158
3AUA0000068698
Dimensional drawings
159
Resistor braking
where
Pbr denotes Pbr5, Pbr10, Pbr30, Pbr60, or Pbrcont depending on the duty cycle.
3. Check the resistor selection. The energy generated by the motor during a 400-
second period must not exceed the resistor heat dissipation capacity ER.
If the ER value is not sufficient, it is possible to use a four-resistor assembly in which two standard
resistors are connected in parallel, two in series. The ER value of the four-resistor assembly is four
times the value specified for the standard resistor.
Resistor braking
160
Note: A resistor other than the standard resistor can be used provided that:
• its resistance is not lower than the resistance of the standard resistor.
WARNING! Never use a brake resistor with a resistance below the value specified
for the particular drive / brake chopper / resistor combination. The drive and the
chopper are not able to handle the overcurrent caused by the low resistance.
• the resistance does not restrict the braking capacity needed, that is,
2
UDC
Pmax <
R
where
Pmax maximum power generated by the motor during braking
UDC voltage over the resistor during braking, e.g.,
1.35 · 1.2 · 415 V DC (when supply voltage is 380 to 415 V AC),
1.35 · 1.2 · 500 V DC. (when supply voltage is 440 to 500 V AC) or
1.35 · 1.2 · 690 V DC (when supply voltage is 525 to 690 V AC).
R resistor resistance (ohm)
• the heat dissipation capacity (ER) is sufficient for the application (see step 3
above).
Resistor braking
161
Resistor braking
162
Pbrcont The drive and the chopper will withstand this continuous braking power. The braking is considered continuous if the
braking time exceeds 30 s.
Note: Check that the braking energy transmitted to the specified resistor(s) in 400 seconds does not exceed ER.
R Resistance value for the listed resistor assembly. Note: This is also the minimum allowed resistance for the brake
resistor.
ER Short energy pulse that the resistor assembly withstands every 400 seconds. This energy will heat the resistor
element from 40 °C (104 °F) to the maximum allowable temperature.
PRcont Continuous power (heat) dissipation of the resistor when placed correctly. Energy ER dissipates in 400 seconds.
1)
22 kW with standard 22 ohm resistor and 33 kW with 32…37 ohm resistor
All brake resistors must be installed outside the drive. The SACE brake resistors are built in an IP21 metal housing.
The SAFUR brake resistors are built in an IP00 metal frame. Note: The SACE and SAFUR resistors are not UL
listed.
WARNING! The materials near the brake resistor must be non-flammable. The
surface temperature of the resistor is high. Air flowing from the resistor is of
hundreds of degrees Celsius. Protect the resistor against contact.
Use the cable type used for drive input cabling (refer to chapter Technical data) to
ensure the input fuses will also protect the resistor cable. Alternatively, two-
conductor shielded cable with the same cross-sectional area can be used. The
maximum length of the resistor cable(s) is 10 m (33 ft). For the connections, see the
power connection diagram of the drive.
Resistor braking
163
L1 L2 L3
OFF
Fuses 2
1 3 5 13 3
ON
2 4 6 14 4
ACS800
U1 V1 W1
Thermal switch
(standard in ABB
K1
resistors)
Resistor braking
164
With Standard Control Program, wire the thermal switch as shown below. By default,
the drive will stop by coasting when the switch opens.
For other control programs, the thermal switch may be wired to a different digital
input. Programming of the input to trip the drive by “EXTERNAL FAULT” may be
needed. See the appropriate firmware manual.
WARNING! If the drive is equipped with a brake chopper but the chopper is not
enabled by parameter setting, the brake resistor must be disconnected because the
protection against resistor overheating is then not in use.
For settings of other control programs, see the appropriate firmware manual.
Note: Some brake resistors are coated with oil film for protection. At the start-up, the
coating burns off and produces a little bit of smoke. Ensure proper ventilation at the
start-up.
Resistor braking
165
Parameter settings
In Standard Control Program, set parameter 16.09 CTRL BOARD SUPPLY to
EXTERNAL 24V if the RMIO board is powered from an external supply.
External +24 V DC power supply for the RMIO board via terminal X34
166
4
4
3
X34
External +24 V DC power supply for the RMIO board via terminal X34
167
5 6 7
External +24 V DC power supply for the RMIO board via terminal X34
168
External +24 V DC power supply for the RMIO board via terminal X34
169
Overview
The RDCO-0x DDCS Communication options are add-on modules for the
• RMIO Motor Control and I/O board (also part of RDCU control units)
• BCU control units.
RDCO modules are available factory-installed as well as retrofit kits.
The RDCO module includes the connectors for fiber optic DDCS channels CH0,
CH1, CH2 and CH3. The usage of these channels is determined by the application
program; see the Firmware Manual of the drive. However, the channels are normally
assigned as follows:
CH0 – overriding system (eg. fieldbus adapter)
CH1 – I/O options and supply unit
CH2 – Master/Follower link
CH3 – PC tool (ACS800 only).
There are several types of the RDCO. The difference between the types is the
optical components. In addition, each type is available with a coated circuit board,
this being indicated by a “C” suffix, eg. RDCO-03C.
Optical component type
Module type
CH0 CH1 CH2 CH3
The optical components at both ends of a fiber optic link must be of the same type
for the light intensity and receiver sensitivity levels to match. Plastic optical fiber
(POF) cables can be used with both 5 MBd and 10 MBd optical components. 10
MBd components also enable the use of Hard Clad Silica (HCS) cables, which allow
longer connection distances thanks to their lower attenuation.
Note: The optical component type does not reflect the actual communication speed.
Delivery check
The option package contains:
• RDCO-0x module
• Two screws (M3×8)
• This document.
Module layout
CH 0
GND
CH 1
CHGND CH 3
Installation
WARNING! All electrical installation and maintenance work on the drive should be
carried out by qualified electricians only.
The drive and adjoining equipment must be properly earthed.
Do not work on a powered drive. Before installation, switch off the mains and other
dangerous voltages (eg. from external control circuits) to the drive. After switching off
the mains, always allow the intermediate circuit capacitors 5 minutes to discharge
before starting work on the frequency converter. It is a good practice to check (with a
voltage indicating instrument) that the drive is in fact discharged before beginning
work.
There may be dangerous voltages inside the drive from external control circuits even
when the drive mains power is shut off. Exercise appropriate care when working on
the unit. Neglecting these instructions may cause physical injury or death.
WARNING! The component boards of the drive contain integrated circuits that are
extremely sensitive to electrostatic discharge (ESD). Wear an earthing wrist band
when handling component boards. Do not touch the boards unnecessarily. Do not
remove any board from its antistatic packaging until required.
WARNING! Handle the fiber optic cables with care. The maximum long term tensile
load is 1 N; the minimum short term bend radius is 35 mm. Do not touch the ends of
the fibers with bare hands as the fiber is extremely sensitive to dirt.
Use rubber grommets at cable entries to protect the cables.
The RDCO-0x module is to be inserted into the position marked “DDCS” on the
drive. On installation, the signal and power connection to the drive is automatically
made through a 20-pin connector.
The module is held in place with plastic retaining clips and two screws. The screws
also provide the earthing of module, and interconnect the GND signals of the module
and the control board.
Installation procedure
1. Access the optional module slots on the drive. Whenever necessary, refer to the
Hardware Manual of the drive for instructions on removing any covers.
2. Insert the module carefully into the slot marked with “DDCS” (BCU control unit
slot 4) on the control board until the retaining clips lock the module into position.
3. Fasten the screws included in the package. Note that correct installation of the
screws is essential for fulfilling the EMC requirements and for proper operation of
the module.
4. Lead the fiber optic cables from the external device to the appropriate channel(s)
of the RDCO. Inside the drive, route the cables as shown in its Hardware Manual.
Make sure the cables are not kinked or laid against sharp edges. Observe colour
coding so that transmitters are connected to receivers and vice versa. In case
multiple devices are to be connected to one channel, they must be connected in a
ring.
Technical data
Module types: RDCO-01(C), RDCO-02(C), RDCO-03(C), RDCO-04(C)
Degree of protection: IP20
Ambient conditions: The applicable ambient conditions specified for the drive in its
Hardware Manual are in effect.
Connectors:
• 20-pin pinheader
• 4 transmitter/receiver connector pairs for fiber optic cable. Type: Agilent
Technologies Versatile Link. Communication speed: 1, 2 or 4 Mbit/s
Operating voltage: +5 V DC ±10%, supplied by the control unit of the drive.
Current consumption: 200 mA max.
Electromagnetic immunity: IEC 1000-4-2 (limits: industrial, second environment);
IEC 1000-4-3; IEC 1000-4-4; IEC 1000-4-6
30 34
95
20
Product training
For information on ABB product training, navigate to www.abb.com/drives and select
Training courses.
www.abb.com/drives
www.abb.com/drivespartners
Firmware Manual
ACS800 Standard Control Program 7.x
ACS800 Standard Control Program 7.x
Firmware Manual
3AFE64527592 REV L
EN
EFFECTIVE: 2011-08-25
Table of contents
Table of contents
Control panel
Chapter overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Overview of the panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Panel operation mode keys and displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Status row . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Drive control with the panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
How to start, stop and change direction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
How to set speed reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Actual signal display mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
How to select actual signals to the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
How to display the full name of the actual signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
How to view and reset the fault history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
How to display and reset an active fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
About the fault history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Parameter mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
How to select a parameter and change the value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
How to adjust a source selection (pointer) parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Function mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
How to enter an assistant, browse and exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
How to upload data from a drive to the panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table of contents
6
Program features
Chapter overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Start-up Assistant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
The default order of the tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
List of tasks and the relevant drive parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Contents of the assistant displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Local control vs. external control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Local control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
External control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Block diagram: start, stop, direction source for EXT1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Block diagram: reference source for EXT1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Reference types and processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Reference trimming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Programmable analogue inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Update cycles in the Standard Control Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Programmable analogue outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Update cycles in the Standard Control Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Programmable digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Update cycles in the Standard Control Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Programmable relay outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Update cycles in the Standard Control Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Actual signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Motor identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Power loss ride-through . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Automatic Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Table of contents
7
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Safe torque off (STO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Prevention of unexpected start-up (POUS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Safely-limited speed (SLS) (AS7R firmware version only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Diagnostics and control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
DC Magnetising . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
DC Hold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Flux Braking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Flux Optimisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Acceleration and deceleration ramps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Critical speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Constant speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Speed controller tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Speed control performance figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Torque control performance figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Scalar control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
IR compensation for a scalar controlled drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Hexagonal motor flux . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Programmable protection functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
AI<Min . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Panel Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
External Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Motor Thermal Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Motor temperature thermal model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Use of the motor thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Stall Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Underload Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Motor Phase Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Earth Fault Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Table of contents
8
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Communication Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Supervision of optional IO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Preprogrammed faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Overcurrent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
DC overvoltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
DC undervoltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Drive temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Enhanced drive temperature monitoring for ACS800, frame sizes R7 and R8 . . . . . . . . . . . . . 67
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Short circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Input phase loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Control board temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Overfrequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Internal fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Operation limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Power limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Automatic resets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Supervisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Parameter lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Process PID control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Block diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Sleep function for the process PID control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Motor temperature measurement through the standard I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Motor temperature measurement through an analogue I/O extension . . . . . . . . . . . . . . . . . . . . . . 75
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Adaptive Programming using the function blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
DriveAP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Control of a mechanical brake . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Operation time scheme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
State shifts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Table of contents
9
Application macros
Chapter overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Overview of macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Note on external power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Parameter settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Factory macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Default control connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Hand/Auto macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Default control connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
PID Control macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Connection example, 24 VDC / 4…20 mA two-wire sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Default control connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Torque Control macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Default control connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Sequential Control macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Operation diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Default control connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
User macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Table of contents
10
22 ACCEL/DECEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
23 SPEED CTRL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
24 TORQUE CTRL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
25 CRITICAL SPEEDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
26 MOTOR CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
27 BRAKE CHOPPER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
30 FAULT FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
31 AUTOMATIC RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
32 SUPERVISION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
33 INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
34 PROCESS VARIABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
35 MOT TEMP MEAS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
40 PID CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
42 BRAKE CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
45 ENERGY OPT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
50 ENCODER MODULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
51 COMM MODULE DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
52 STANDARD MODBUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
60 MASTER/FOLLOWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
70 DDCS CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
72 USER LOAD CURVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
83 ADAPT PROG CTRL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
84 ADAPTIVE PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
85 USER CONSTANTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
90 D SET REC ADDR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
92 D SET TR ADDR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
95 HARDWARE SPECIF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
96 EXTERNAL AO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
98 OPTION MODULES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
99 START-UP DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
Fieldbus control
Chapter overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
System overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Redundant fieldbus control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
Setting up communication through a fieldbus adapter module . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Setting up communication through the Standard Modbus Link . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Modbus addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
Setting up communication through Advant controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Drive control parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
The fieldbus control interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
The Control Word and the Status Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Fieldbus reference selection and correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Reference handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
Actual Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Block diagram: Control data input from fieldbus when a type Rxxx fieldbus adapter is used . 206
Block diagram: Actual value selection for fieldbus when a type Rxxx fieldbus adapter is used 207
Block diagram: Control data input from fieldbus when a type Nxxx fieldbus adapter is used . 208
Table of contents
11
Block Diagram: Actual value selection for fieldbus when a type Nxxx fieldbus adapter is used 209
Communication profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
ABB Drives communication profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
03.01 MAIN CONTROL WORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
03.02 MAIN STATUS WORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Fieldbus reference scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Generic Drive communication profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Drive commands supported by the Generic Drive communication profile . . . . . . . . . . . . . . 216
Fieldbus reference scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
CSA 2.8/3.0 communication profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
CONTROL WORD for the CSA 2.8/3.0 communication profile . . . . . . . . . . . . . . . . . . . . . . 218
STATUS WORD for the CSA 2.8/3.0 communication profile . . . . . . . . . . . . . . . . . . . . . . . . 218
Diverse status, fault, alarm and limit words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
03.03 AUXILIARY STATUS WORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
03.04 LIMIT WORD 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
03.05 FAULT WORD 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
03.06 FAULT WORD 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
03.07 SYSTEM FAULT WORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
03.08 ALARM WORD 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
03.09 ALARM WORD 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
03.13 AUXILIARY STATUS WORD 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
03.14 AUXILIARY STATUS WORD 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
03.15 FAULT WORD 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
03.16 ALARM WORD 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
03.17 FAULT WORD 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
03.18 ALARM WORD 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
03.19 INT INIT FAULT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
03.30 LIMIT WORD INV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
03.31 ALARM WORD 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
03.32 EXT IO STATUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
03.33 FAULT WORD 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
04.01 FAULTED INT INFO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
04.02 INT SC INFO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
Fault tracing
Chapter overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Warning and fault indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
How to reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Fault history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Warning messages generated by the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Warning messages generated by the control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
Fault messages generated by the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
Table of contents
12
Index
Table of contents
13
Chapter overview
The chapter includes a description of the contents of the manual. In addition it
contains information about the compatibility, safety and intended audience.
Compatibility
The manual is compatible with Standard Control Program versions ASXR7360 and
AS7R7363. See parameter 33.01 SOFTWARE VERSION.
Safety instructions
Follow all safety instructions delivered with the drive.
• Read the complete safety instructions before you install, commission, or use
the drive. The complete safety instructions are given at the beginning of the
Hardware Manual.
• Read the software function specific warnings and notes before changing the
default settings of the function. For each function, the warnings and notes are
given in this manual in the section describing the related user-adjustable
parameters.
Reader
The reader of the manual is expected to know the standard electrical wiring
practices, electronic components, and electrical schematic symbols.
Contents
The manual consists of the following chapters:
• Start-up and control through the I/O instructs in setting up the application
program, and how to start, stop and regulate the speed of the drive.
• Control panel gives instructions for using the panel.
• Program features contains the feature descriptions and the reference lists of the
user settings and diagnostic signals.
• Application macros contains a short description of each macro together with a
connection diagram.
• Actual signals and parameters describes the actual signals and parameters of the
drive.
• Fieldbus control describes the communication through the serial communication
links.
• Fault tracing lists the warning and fault messages with the possible causes and
remedies.
• Analogue Extension Module, describes the communication between the drive and
the analogue I/O extension (optional).
• Additional data: actual signals and parameters contains more information on the
actual signals and parameters.
• Control block diagrams contains block diagrams concerning reference control
chains and handling of Start, Stop, Run Enable and Start Interlock.
Product training
For information on ABB product training, navigate to www.abb.com/drives and select
Training courses.
Chapter overview
The chapter instructs how to:
• do the start-up
• start, stop, change the direction of rotation, and adjust the speed of the motor
through the I/O interface
• perform an Identification Run for the drive.
SAFETY
The start-up may only be carried out by a qualified electrician.
The safety instructions must be followed during the start-up procedure. See the
appropriate hardware manual for safety instructions.
Check the installation. See the installation checklist in the appropriate hardware/installation
manual.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if:
- there is a risk of damage in case of incorrect direction of rotation, or
- a Standard ID Run needs to be performed during the drive start-up. (ID Run is essential only
in applications which require the ultimate in motor control accuracy.)
POWER-UP
Apply the main power. The control panel first shows the panel CDP312 PANEL Vx.xx
identification data … .......
…after which the display suggests starting the Language Selection. 1 -> 0.0 rpm O
*** INFORMATION ***
(If no key is pressed for a few seconds, the display starts to alternate between the
Press FUNC to start
Actual Signal Display and the suggestion on selecting the language.)
Language Selection
The drive is now ready for the start-up.
SELECTING THE LANGUAGE
Press the FUNC key. Language Selection 1/1
LANGUAGE ?
[ENGLISH]
ENTER:OK ACT:EXIT
Scroll to the desired language by the arrow keys ( or ) and 1 -> 0.0 rpm O
press ENTER to accept. *** INFORMATION ***
Press FUNC to start
(The drive loads the selected language into use, shifts back to the Actual Signal guided Motor Setup
Display and starts to alternate between the Actual Signal Display and the
suggestion on starting the guided motor set-up.)
How to perform the limited start-up (covers only the basic settings)
Before you start, ensure you have the motor nameplate data at your hand.
SAFETY
The start-up may only be carried out by a qualified electrician.
The safety instructions must be followed during the start-up procedure. See the
appropriate hardware manual for safety instructions.
Check the installation. See the installation checklist in the appropriate hardware/installation
manual.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if:
- there is a risk of damage in case of incorrect direction of rotation, or
- a Standard ID Run needs to be performed during the drive start-up. (ID Run is essential
only in applications which require the ultimate in motor control accuracy.)
POWER-UP
Apply the main power. The control panel first shows the panel CDP312 PANEL Vx.xx
identification data … .......
…after which the display suggests starting the Language Selection. 1 -> 0.0 rpm O
*** INFORMATION ***
(If no key is pressed for a few seconds, the display starts to alternate between the
Press FUNC to start
Actual Signal Display and the suggestion on starting the Language Selection.)
Language Selection
Press ACT to remove the suggestion on starting the language 1 -> 0.0 rpm O
selection. FREQ 0.00 Hz
CURRENT 0.00 A
The drive is now ready for the limited start-up. POWER 0.00 %
Select the Application Macro. The general parameter setting 1 -> 0.0 rpm O
procedure is given above. 99 START-UP DATA
02 APPLICATION MACRO
The default value FACTORY is suitable in most cases. [ ]
Select the motor control mode. The general parameter setting 1 -> 0.0 rpm O
procedure is given above. 99 START-UP DATA
04 MOTOR CTRL MODE
DTC is suitable in most cases. The SCALAR control mode is recommended [DTC]
- for multimotor drives when the number of the motors connected to the drive is
variable
- when the nominal current of the motor is less than 1/6 of the nominal current of
the inverter
- when the inverter is used for test purposes with no motor connected.
Enter the motor data from the motor nameplate: Note: Set the motor data to
exactly the same value as
on the motor nameplate.
ABB Motors For example, if the motor
3 motor M2AA 200 MLA 4
nominal speed is 1440 rpm
IEC 200 M/L 55
No on the nameplate, setting
Ins.cl. F IP 55 the value of parameter
V Hz kW r/min A cos IA/IN t E/s 99.08 MOTOR NOM
690 Y 50 30 1475 32.5 0.83
400 D 50 30 1475 56 0.83 SPEED to 1500 rpm
660 Y 50 30 1470 34 0.83 380 V results in the wrong
380 D 50 30 1470 59 0.83 input operation of the drive.
415 D 50 30 1475 54 0.83
440 D 35 1770 59 0.83
voltage
60
Cat. no 3GAA 202 001 - ADA
When the motor data has been entered, two displays (warning and 1 -> 0.0 rpm O
information) start to alternate. Move to next step without pressing ACS800
** WARNING **
any key.
ID MAGN REQ
Note: If you select STANDARD ID Run, the brake is opened when
the Start command is given from the control panel and the brake 1 -> 0.0 rpm I
remains open until the STANDARD ID Run is completed. If you *** Information ***
Press green button
select ID MAGN, the brake is kept closed during the ID Run
to start ID MAGN
sequence.
PRELIMINARY SETTINGS
Ensure the Factory macro is active. See parameter 99.02.
Ensure the drive is in external control mode. Press the LOC/REM key to In External control, there is
change between external and local control. no L visible on the first row
of the panel display.
Regulate the speed by adjusting the voltage of analogue input AI1. 1 -> 500.0 rpm I
FREQ 16.66 Hz
CURRENT 12.66 A
POWER 8.33 %
Reverse direction: Switch digital input DI2 on. 1 <- 500.0 rpm I
FREQ 16.66 Hz
CURRENT 12.66 A
POWER 8.33 %
Note: If you select STANDARD ID Run, the brake is opened when the Start
command is given from the control panel and the brake remains open until the
STANDARD ID Run is completed. If you select ID MAGN, the brake is kept closed
during the ID Run sequence.
ID Run Procedure
Note: If parameter values (Group 10 to 98) are changed before the ID Run, check
that the new settings meet the following conditions:
• 20.01 MINIMUM SPEED < 0 rpm
• 20.02 MAXIMUM SPEED > 80% of motor rated speed
• 20.03 MAXIMUM CURRENT > 100% · Ihd
• 20.04 MAXIMUM TORQUE > 50%
• Ensure that the panel is in the local control mode (L displayed on the status row).
Press the LOC/REM key to switch between modes.
• Change the ID Run selection to STANDARD or REDUCED.
1 L ->1242.0 rpm O
99 START-UP DATA
10 MOTOR ID RUN
[STANDARD]
1 L ->1242.0 rpm O
ACS800
**WARNING**
ID RUN SEL
• To start the ID Run, press the key. The Start Interlock (digital input DI_IL) and
Run Enable signals (parameter 16.01 RUN ENABLE) must be active.
Warning when the ID Run is Warning during the ID Run Warning after a successfully
started completed ID Run
In general it is recommended not to press any control panel keys during the ID run.
However:
• The Motor ID Run can be stopped at any time by pressing the control panel stop
key ( ).
• After the ID Run is started with the start key ( ), it is possible to monitor the
actual values by first pressing the ACT key and then a double-arrow key ( ).
Control panel
Chapter overview
The chapter describes how to use the control panel CDP 312R.
The same control panel is used with all ACS800 series drives, so the instructions
given apply to all ACS800 types. The display examples shown are based on the
Standard Control Program; displays produced by other application programs may
differ slightly.
No. Use
1 Start
ENTER
2 Stop
Control panel
26
Parameter Mode
Function Mode
Status row
The figure below describes the status row digits.
Control panel
27
Control panel
28
Control panel
29
2. To select a row (a blinking cursor indicates the selected 1 L -> 1242.0 rpm I
row). FREQ 45.00 Hz
CURRENT 80.00 A
POWER 75.00 %
5.a To accept the selection and to return to the Actual Signal 1 L -> 1242.0 rpm I
ENTER
Display Mode. FREQ 45.00 Hz
TORQUE 70.00 %
POWER 75.00 %
5.b To cancel the selection and keep the original selection. 1 L -> 1242.0 rpm I
ACT PAR
FREQ 45.00 Hz
CURRENT 80.00 A
The selected keypad mode is entered.
FUNC DRIVE
POWER 75.00 %
Control panel
30
1. To display the full name of the three actual signals. Hold 1 L -> 1242.0 rpm I
FREQUENCY
ACT CURRENT
POWER
2. To return to the Actual Signal Display Mode. Release 1 L -> 1242.0 rpm I
FREQ 45.00 Hz
ACT CURRENT 80.00 A
POWER 75.00 %
Note: The fault history cannot be reset if there are active faults or warnings.
3. To select the previous (UP) or the next fault/warning 1 L -> 1242.0 rpm I
(DOWN). 2 LAST FAULT
+OVERVOLTAGE
1121 H 1 MIN 23 S
Control panel
31
WARNING! If an external source for start command is selected and it is ON, the
drive will start immediately after fault reset. If the cause of the fault has not been
removed, the drive will trip again.
Control panel
32
Parameter mode
In the Parameter Mode, the user can:
• view the parameter values
• change the parameter settings.
The panel enters the Parameter Mode when the user presses the PAR key.
6b. To cancel the new setting and keep the original value, 1 L -> 1242.0 rpm O
ACT PAR
press any of the mode selection keys. 11 REFERENCE SELECT
The selected mode is entered. 03 EXT REF1 SELECT
FUNC DRIVE
AI1
Control panel
33
ENTER
2. To scroll between the inversion, group, index and bit 1 L ->1242.0 rpm O
fields.1) 84 ADAPTIVE PROGRAM
06 INPUT1
[±000.000.00]
1)
Control panel
34
Function mode
In the Function Mode, the user can:
• start a guided procedure for adjusting the drive settings (assistants)
• upload the drive parameter values and motor data from the drive to the panel.
• download group 1 to 97 parameter values from the panel to the drive. 1)
• adjust the contrast of the display.
The panel enters the Function Mode when the user presses the FUNC key.
1)
The parameter groups 98, 99 and the results of the motor identification are not included by default. The restriction
prevents downloading of unfit motor data. In special cases it is, however, possible to download all. For more information,
please contact your local ABB representative.
Control panel
35
2. To select a task or function from the list (a flashing cursor 1 L -> 1242.0 rpm O
indicates the selection). Motor Setup
Double arrows: To change page to see more assistants/ Application Macro
functions. Speed Control EXT 1
( )
motor nameplate.
and return to the task).
FUNC, ACT
b. To cancel the setting and take one step back. RESET Motor Setup 3/10
MOTOR NOM VOLTAGE?
[415 V]
ENTER:Ok RESET:back
Control panel
36
Note:
• Upload before downloading.
• Ensure the firmware of the destination drive is the same (e.g. standard firmware).
• Before removing the panel from a drive, ensure the panel is in remote operating
mode (change with the LOC/REM key).
• Stop the drive before downloading.
2. Enter the page that contains the upload, download and 1 L -> 1242.0 rpm O
contrast functions. UPLOAD <=<=
DOWNLOAD =>=>
CONTRAST 4
3. Select the upload function (a flashing cursor indicates the 1 L -> 1242.0 rpm O
selected function). UPLOAD <=<=
DOWNLOAD =>=>
CONTRAST 4
Control panel
37
2. Ensure the drive is in local control (L shown on the first row 1 L -> 1242.0 rpm I
LOC
of the display). If necessary, press the LOC/REM key to FREQ 45.00 Hz
REM
change to local control. CURRENT 80.00 A
POWER 75.00 %
4. Enter the page that contains the upload, download and 1 L -> 1242.0 rpm O
contrast functions. UPLOAD <=<=
DOWNLOAD =>=>
CONTRAST 4
5. Select the download function (a flashing cursor indicates 1 L -> 1242.0 rpm O
the selected function). UPLOAD <=<=
DOWNLOAD =>=>
CONTRAST 4
Control panel
38
2. Enter the page that contains the upload, download and 1 L -> 1242.0 rpm O
contrast functions. UPLOAD <=<=
DOWNLOAD =>=>
CONTRAST 4
3. Select a function (a flashing cursor indicates the selected 1 L -> 1242.0 rpm O
function). UPLOAD <=<=
DOWNLOAD =>=>
CONTRAST 4
6.b Cancel the new setting and retain the original value by 1 L -> 1242.0 rpm I
pressing any of the mode selection keys. ACT PAR FREQ 45.00 Hz
CURRENT 80.00 A
POWER 75.00 %
The selected mode is entered. FUNC DRIVE
Control panel
39
Note: The default ID number setting of the drive should not be changed unless the
drive is to be connected to the panel link with other drives on-line.
ASAAA5000 xxxxxx
ID NUMBER 1
3. To connect to the last displayed drive and to enter another 1 L -> 1242.0 rpm I
mode, press one of the mode selection keys. ACT PAR FREQ 45.00 Hz
CURRENT 80.00 A
FUNC
POWER 75.00 %
The selected mode is entered.
Control panel
40
Bit 15 Bit 0
Control panel
41
Program features
Chapter overview
The chapter describes program features. For each feature, there is a list of related
user settings, actual signals, and fault and warning messages.
Start-up Assistant
Introduction
The assistant guides the user through the start-up procedure, helping the user to
feed the requested data (parameter values) to the drive. The assistant also check
that the entered values are valid, i.e. within the allowed range. At the first start, the
drive suggests entering the first task of the assistant, Language Select,
automatically.
The Start-up Assistant is divided into tasks. The user may activate the tasks either
one after the other as the Start-up Assistant suggests, or independently. The user
may also adjust the drive parameters in the conventional way without using the
assistant at all.
See chapter Control panel on how to start the assistant, browse and exit.
Note: Option modules assistant is not supported from firmware version AS7R7363
onwards.
Program features
42
Program features
43
Standard I/O
Advant controller
(e.g. AC 80, AC 800M)
Program features
44
Local control
The control commands are given from the control panel keypad when the drive is in
local control. L indicates local control on the panel display.
1 L ->1242 rpm I
The control panel always overrides the external control signal sources when used in
local mode.
External control
When the drive is in external control, the commands are given through the standard
I/O terminals (digital and analogue inputs), optional I/O extension modules and/or
the fieldbus interface. In addition, it is also possible to set the control panel as the
source for the external control.
External control is indicated by a blank on the panel display or with an R in those
special cases when the panel is defined as a source for external control.
The user can connect the control signals to two external control locations, EXT1 or
EXT2. Depending on the user selection, either one is active at a time. This function
operates on a 12 ms time level.
Settings
Panel key Additional information
LOC/REM Selection between local and external control
Parameter
11.02 Selection between EXT1 and EXT2
10.01 Start, stop, direction source for EXT1
11.03 Reference source for EXT1
10.02 Start, stop, direction source for EXT2
11.06 Reference source for EXT2
Group 98 OPTION Activation of the optional I/O and serial communication
MODULES
Diagnostics
Actual signals Additional information
01.11, 01.12 EXT1 reference, EXT2 reference
03.02 EXT1/EXT2 selection bit in a packed boolean word
Program features
45
Select
DI1 / Std IO DI1
DI6 EXT1
DI6 / Std IO Start/stop/
DI7 to DI9 direction
DI1 / DIO ext 1 10.01
I/O Extensions
DI2 / DIO ext 1
See group 98
DI1 / DIO ext 2 OPTION
DI2 / DIO ext 2 MODULES.
Fb. selection
Fieldbus adapter slot 1 See chapter COMM.
CH0 / RDCO board Fieldbus control. CW
Standard Modbus® Link
KEYPAD
Control panel
DI1 / Std IO = Digital input DI1 on the standard I/O terminal block
DI1 / DIO ext 1 = Digital input DI1 on the digital I/O extension module 1
AI1 / Std IO = Analogue input AI1 on the standard I/O terminal block
AI1 / AIO ext = Analogue input AI1 on the analogue I/O extension module
Program features
46
Settings
Parameter Additional information
Group 11 REFERENCE External reference source, type and scaling
SELECT
Group 20 LIMITS Operating limits
Group 22 ACCEL/DECEL Speed reference acceleration and deceleration ramps
Group 24 TORQUE CTRL Torque reference ramp times
Group 32 SUPERVISION Reference supervision
Diagnostics
Actual signal Additional information
01.11, 01.12 Values of external references
Group 02 ACTUAL SIGNALS The reference values in different stages of the reference processing
chain.
Parameter
Group 14 RELAY OUTPUTS Active reference / reference loss through a relay output
Group 15 ANALOGUE Reference value
OUTPUTS
Program features
47
Reference trimming
In reference trimming, the external %-reference (External reference REF2) is
corrected depending on the measured value of a secondary application variable.
The block diagram below illustrates the function.
Switch Select
max.freq
Select
DIRECT (3)
max.speed max.torque
%ref PROPOR. (2)
Select 99.04 (DTC) 40.18
1 OFF (1)
AI1 Add
AI2 40.14 %ref
... Mul. %ref’
40.16
PID Mul.
40.15 40.17
tref
40.01 k
Actual Values 40.02 ti
40.03 td
40.05 .
. i
. Filter 40.04 dFiltT
40.07 40.05 errVInv
AI1 40.13 rInt
AI2 PIDmax oh1
AI3 PIDmin ol1
AI5
AI6 40.19
IMOT
Settings
Parameter Additional information
40.14…40.18 Trimming function settings
40.01…40.13, 40.19 PID control block settings
Group 20 LIMITS Drive operation limits
Program features
48
Example
The drive runs a conveyor line. It is speed-controlled but the line tension also needs
to be taken into account: If the measured tension exceeds the tension setpoint, the
speed will be slightly decreased, and vice versa.
To accomplish the desired speed correction, the user:
• activates the trimming function and connects the tension setpoint and the
measured tension to it
• tunes the trimming to a suitable level.
Tension
setpoint
Program features
49
Settings
Parameter Additional information
Group 11 REFERENCE AI as a reference source
SELECT
Group 13 ANALOGUE Processing of the standard inputs
INPUTS
30.01 Supervision of AI loss
Group 40 PID AI as a PID process control reference or actual values
CONTROL
35.01 AI in a motor temperature measurement
40.15 AI in a drive reference trimming
42.07 AI in a mechanical brake control function
98.06 Activation of optional analogue inputs
98.13 Optional AI signal type definition (bipolar or unipolar)
98.14 Optional AI signal type definition (bipolar or unipolar)
Diagnostics
Actual value Additional information
01.18, 01.19, 01.20 Values of standard inputs
01.38, 01.39 Value of optional inputs
Group 09 ACTUAL Scaled analogue input values (integer values for function block
SIGNALS programming)
Program features
50
Settings
Parameter Additional information
Group 15 ANALOGUE AO value selection and processing (standard outputs)
OUTPUTS
30.20 Operation of an externally controlled AO in a communication break
30.22 Supervision of the use of optional AO
Group 35 MOT TEMP AO in motor temperature measurement
MEAS
Group 96 EXTERNAL Optional AO value selection and processing
AO
Group 98 OPTION Activation of optional I/O
MODULES
Diagnostics
Actual value Additional information
01.22, 01.23 Values of the standard outputs
01.28, 01.29 Values of the optional outputs
Warning
IO CONFIG (FF8B) Improper use of optional I/O
Program features
51
Settings
Parameter Additional information
Group 10 START/STOP/ DI as start, stop, direction
DIR
Group 11 REFERENCE DI in reference selection, or reference source
SELECT
Group 12 CONSTANT DI in constant speed selection
SPEEDS
Group 16 SYST CTRL DI as external Run Enable, fault reset or user macro change signal
INPUTS
22.01 DI as acceleration and deceleration ramp selection signal
30.03 DI as external fault source
30.05 DI in motor overtemperature supervision function
30.22 Supervision of optional I/O use
40.20 DI as sleep function activation signal (in PID process control)
42.02 DI as mechanical brake acknowledgement signal
98.03…96.05 Activation of the optional digital I/O extension modules
98.09…98.11 Naming of the optional digital inputs in the application program
Diagnostics
Actual value Additional information
01.17 Values of the standard digital inputs
01.40 Values of the optional digital inputs
Warning
IO CONFIG (FF8B) Improper use of optional I/O
Fault
I/O COMM ERR (7000) Communication loss to I/O
Program features
52
Settings
Parameter Additional information
Group 14 RELAY RO value selections and operation times
OUTPUTS
30.20 Operation of an externally controlled relay output on a communication break
Group 42 BRAKE RO in a mechanical brake control
CONTROL
Group 98 OPTION Activation of optional relay outputs
MODULES
Diagnostics
Actual value Additional information
01.21 Standard relay output states
01.41 Optional relays output states
Program features
53
Actual signals
Several actual signals are available:
• Drive output frequency, current, voltage and power
• Motor speed and torque
• Supply voltage and intermediate circuit DC voltage
• Active control location (Local, EXT1 or EXT2)
• Reference values
• Drive temperature
• Operating time counter (h), kWh counter
• Digital I/O and Analogue I/O status
• PID controller actual values (if the PID Control macro is selected)
Three signals can be shown simultaneously on the control panel display. It is also
possible to read the values through the serial communication link or through the
analogue outputs.
Settings
Parameter Additional information
Group 15 ANALOGUE Selection of an actual signal to an analogue output
OUTPUTS
Group 92 D SET TR Selection of an actual signal to a data set (serial communication)
ADDR
Diagnostics
Actual value Additional information
Group 01 ACTUAL Lists of actual signals
SIGNALS … 09
ACTUAL SIGNALS
Motor identification
The performance of Direct Torque Control is based on an accurate motor model
determined during the motor start-up.
A motor Identification Magnetisation is automatically done the first time the start
command is given. During this first start-up, the motor is magnetised at zero speed
for several seconds to allow the motor model to be created. This identification
method is suitable for most applications.
In demanding applications a separate Identification Run can be performed.
Settings
Parameter 99.10.
Program features
54
Uin
TM fout UDC
(Nm) (Hz) (V d.c.) UDC
160 80 520
120 60 390
fout
80 40 260
TM
40 20 130
t(s)
1.6 4.8 8 11.2 14.4
UDC= Intermediate circuit voltage of the drive, fout = output frequency of the drive,
TM = Motor torque
Loss of supply voltage at nominal load (fout = 40 Hz). The intermediate circuit DC voltage drops to the
minimum limit. The controller keeps the voltage steady as long as the supply voltage is switched off.
The drive runs the motor in generator mode. The motor speed falls but the drive is operational as long
as the motor has enough kinetic energy.
Note: Cabinet assembled units equipped with main contactor option have a “hold
circuit” that keeps the contactor control circuit closed during a short supply break.
The allowed duration of the break is adjustable. The factory setting is five seconds.
Automatic Start
Since the drive can detect the state of the motor within a few milliseconds, the
starting is immediate under all conditions. There is no restart delay. E.g. the starting
of turbining pumps or windmilling fans is easy.
Settings
Parameter 21.01.
Program features
55
WARNING! The Safe torque off function does not disconnect the voltage of the main
and auxiliary circuits from the drive. Therefore, maintenance work on electrical parts
may only be carried out after disconnecting the drive system from the input power
line.
Diagnostics
Actual value Additional information
03.03 AUX STATUS WORD, bit 8 Safe torque off function activation status
03.08 ALARM WORD 1, bit 0 / Safe torque off function alarm/fault
03.03 AUX STATUS WORD, bit 8
Program features
56
Actual speed
SLS activated
Settings
Parameter Additional information
10.09 SLS ACTIVE Selection of DI source
20.22 SLS SPEED LIMIT Safely-limited speed limit
22.10 SLS ACCELER TIME Time required for speed limit to ramp up from SLS to normal
22.11 SLS DECELER TIME Time required for speed limit to ramp down from current actual
speed to SLS
See also Safe speed functions for ACS800 cabinet-installed drives (+Q965/+Q966)
Application guide [3AUA0000090742 (English)].
Note: When SLS function is active, critical speed settings in parameter group 25 are
not in effect.
Program features
57
DC Magnetising
When DC Magnetising is activated, the drive automatically magnetises the motor
before starting. This feature guarantees the highest possible breakaway torque, up
to 200% of motor nominal torque. By adjusting the premagnetising time, it is possible
to synchronise the motor start and e.g. a mechanical brake release. The Automatic
Start feature and DC Magnetising cannot be activated at the same time.
Settings
Parameters 21.01 and 21.02.
DC Hold
By activating the motor DC Hold feature it is possible to Motor
Speed
lock the rotor at zero speed. When both the reference DC Hold
and the motor speed fall below the preset DC hold
speed, the drive stops the motor and starts to inject DC DC hold
speed
into the motor. When the reference speed again exceeds t
the DC hold speed, the normal drive operation resumes. Speed
Reference
Settings
DC hold
Parameters 21.04, 21.05, and 21.06. speed
t
Flux Braking
The drive can provide greater deceleration by raising the level of magnetisation in
the motor. By increasing the motor flux, the energy generated by the motor during
braking can be converted to motor thermal energy. This feature is useful in motor
power ranges below 15 kW.
Motor TBr
Speed TN (%)
TBr = Braking Torque
No Flux Braking 60 TN = 100 Nm
40
Flux Braking
20
Flux Braking No Flux Braking
t (s) f (Hz)
50 HZ / 60 Hz
Program features
58
2
40 3
4
5
0 f (Hz)
5 10 20 30 40 50
The drive monitors the motor status continuously, also during the Flux Braking.
Therefore, Flux Braking can be used both for stopping the motor and for changing
the speed. The other benefits of Flux Braking are:
• The braking starts immediately after a stop command is given. The function does
not need to wait for the flux reduction before it can start the braking.
• The cooling of the motor is efficient. The stator current of the motor increases
during the Flux Braking, not the rotor current. The stator cools much more
efficiently than the rotor.
Settings
Parameter 26.02.
Flux Optimisation
Flux Optimisation reduces the total energy consumption and motor noise level when
the drive operates below the nominal load. The total efficiency (motor and the drive)
can be improved by 1% to 10%, depending on the load torque and speed.
Settings
Parameter 26.01.
Program features
59
Settings 2 t (s)
Critical speeds
A Critical Speeds function is available for applications where it is necessary to avoid
certain motor speeds or speed bands because of e.g. mechanical resonance
problems.
Settings
Parameter group 25 CRITICAL SPEEDS.
Constant speeds
It is possible to predefine 15 constant speeds. Constant speeds are selected with
digital inputs. Constant speed activation overrides the external speed reference.
This function operates on a 6 ms time level.
Settings
Parameter group 12 CONSTANT SPEEDS.
Program features
60
A B C D
A: Undercompensated t
B: Normally tuned (autotuning)
C: Normally tuned (manually). Better dynamic performance than with B
D: Overcompensated speed controller
The figure below is a simplified block diagram of the speed controller. The controller
output is the reference for the torque controller.
Derivative
acceleration
compensation
Proportional,
integral + Torque
Speed + Error +
reference - value + reference
Derivative
Actual speed
Settings
Parameter group 23 SPEED CTRL and 20 LIMITS.
Diagnostics
Actual signal 01.02.
Program features
61
10
< 5 ms t(s)
TN = rated motor torque
Tref = torque reference
Tact = actual torque
Program features
62
Scalar control
It is possible to select Scalar Control as the motor control method instead of Direct
Torque Control (DTC). In the Scalar Control mode, the drive is controlled with a
frequency reference. The outstanding performance of the default motor control
method, Direct Torque Control, is not achieved in Scalar Control.
It is recommended to activate the Scalar Control mode in the following special
applications:
• In multimotor drives: 1) if the load is not equally shared between the motors, 2) if
the motors are of different sizes, or 3) if the motors are going to be changed after
the motor identification
• If the nominal current of the motor is less than 1/6 of the nominal output current of
the drive
• If the drive is used without a motor connected (e.g. for test purposes)
• The drive runs a medium voltage motor via a step-up transformer.
In the Scalar Control mode, some standard features are not available.
Settings
Parameter 99.04.
Settings
Parameter 26.03.
Program features
63
Settings
Parameter 26.05.
AI<Min
AI<Min function defines the drive operation if an analogue input signal falls below the
preset minimum limit.
Settings
Parameter 30.01.
Panel Loss
Panel Loss function defines the operation of the drive if the control panel selected as
control location for the drive stops communicating.
Settings
Parameter 30.02.
External Fault
External Faults can be supervised by defining one digital input as a source for an
external fault indication signal.
Settings
Parameter 30.03.
Program features
64
50
Temp. t Zero speed load
Rise
Speed
100%
63%
t
Motor thermal time
Note: It is also possible to use the motor temperature measurement function. See
sections Motor temperature measurement through the standard I/O on page 73 and
Motor temperature measurement through an analogue I/O extension on page 75.
Program features
65
Stall Protection
The drive protects the motor in a stall situation. It is possible to adjust the supervision
limits (torque, frequency, time) and choose how the drive reacts to a motor stall
condition (warning indication / fault indication & stop the drive / no reaction).
The torque and current limits, which define the stall limit, must be set according to
the maximum load of the used application. Note: Stall limit is restricted by internal
current limit 03.04 TORQ_INV_CUR_LIM.
When the application reaches the stall limit and the output frequency of the drive is
below the stall frequency: Fault is activated after the stall time delay.
Settings
Parameters 30.10 to 30.12.
Parameters 20.03, 20.13 and 20.14 (Define the stall limit.)
Underload Protection
Loss of motor load may indicate a process malfunction. The drive provides an
underload function to protect the machinery and process in such a serious fault
condition. Supervision limits - underload curve and underload time - can be chosen
as well as the action taken by the drive upon the underload condition (warning
indication / fault indication & stop the drive / no reaction).
Settings
Parameters 30.13 to 30.15.
Program features
66
Communication Fault
The Communication Fault function supervises the communication between the drive
and an external control device (e.g. a fieldbus adapter module).
Settings
Parameters 30.18 to 30.21.
Supervision of optional IO
The function supervises the use of the optional analogue and digital inputs and
outputs in the application program, and warns if the communication to the input/
output is not operational.
Settings
Parameter 30.22.
Preprogrammed faults
Overcurrent
The overcurrent trip limit for the drive is 1.65 to 2.17 · Imax depending on the drive
type.
DC overvoltage
The DC overvoltage trip limit is 1.3 × 1.35 × U1max, where U1max is the maximum
value of the supply voltage range. For 400 V units, U1max is 415 V. For 500 V units,
U1max is 500 V. For 690 V units, U1max is 690 V. The actual voltage in the
intermediate circuit corresponding to the supply voltage trip level is 728 V DC for
400 V units, 877 V DC for 500 V units, and 1210 V DC for 690 V units.
Program features
67
DC undervoltage
The DC undervoltage trip limit is 0.6 × 1.35 × U1min, where U1min is the minimum
value of the supply voltage range. For 400 V and 500 V units, U1min is 380 V. For
690 V units, U1min is 525 V. The actual voltage in the intermediate circuit
corresponding to the supply voltage trip level is 307 V DC for 400 V and 500 V units,
and 425 V DC for 690 V units.
Drive temperature
The drive supervises the inverter module temperature. There are two supervision
limits: warning limit and fault trip limit.
Note: The monitoring is available for ACS800-02, -04 and -07, frame sizes R7 and
R8 with Standard Control Program version ASXR7360 (and later versions). For
ACS800-U2, -U4 and -U7, frame sizes R7 and R8, the monitoring is available with
Standard Control Program version ASXR730U (and later versions).
Program features
68
-0440-3/5/7
-0490-3/5/7
-0550-5/7
-0610-5/7
Settings
Parameter Additional information
95.10 TEMP INV AMBIENT Ambient temperature
Diagnostics
Warning/Fault Additional information
INV OVERTEMP Excessive converter module temperature
Short circuit
There are separate protection circuits for supervising the motor cable and the
inverter short circuits. If a short circuit occurs, the drive will not start and a fault
indication is given.
Overfrequency
If the drive output frequency exceeds the preset level, the drive is stopped and a
fault indication is given. The preset level is 50 Hz over the operating range absolute
maximum speed limit (Direct Torque Control mode active) or frequency limit (Scalar
Control active).
Internal fault
If the drive detects an internal fault, the drive is stopped and a fault indication is
given.
Operation limits
ACS800 has adjustable limits for speed, current (maximum), torque (maximum) and
DC voltage.
Settings
Parameter group 20 LIMITS.
Program features
69
Power limit
Power limitation is used to protect the input bridge and the DC intermediate circuit.
If the maximum allowed power is exceeded, the drive torque is automatically limited.
Maximum overload and continuous power limits depend on the drive hardware.
For specific values refer to the appropriate hardware manual.
Automatic resets
The drive can automatically reset itself after overcurrent, overvoltage, undervoltage
and “analogue input below a minimum” faults. The Automatic Resets must be
activated by the user.
Settings
Parameter group 31 AUTOMATIC RESET.
Supervisions
The drive monitors whether certain user selectable variables are within the user-
defined limits. The user may set limits for speed, current etc.
The supervision functions operate on a 100 ms time level.
Settings
Parameter group 32 SUPERVISION.
Diagnostics
Actual Signals Additional information
03.02 Supervision limit indicating bits in a packed boolean word
03.04 Supervision limit indicating bits in a packed boolean word
03.14 Supervision limit indicating bits in a packed boolean word
Group 14 RELAY Supervision limit indication through a relay output
OUTPUTS
Parameter lock
The user can prevent parameter adjustment by activating the parameter lock.
Settings
Parameters 16.02 and 16.03.
Program features
70
Block diagrams
The block diagram below right illustrates the process PID control.
The figure on the left shows an application example: The controller adjusts the
speed of a pressure boost pump according to the measured pressure and the set
pressure reference.
40.03 td
40.06 .
E N T E R
reference
L O C R E S E T R E F
i
R E M
.. 40.04 dFiltT
3
40.12 Filter
AI1
40.05 errVInv Speed
40.13 rInt
2 0 ...1 0 b a r AI2 PIDmax
reference
4 ...2 0 m A oh1
AI3 PIDmin ol1 99.04 = 0
AI5
(DTC)
AI6 40.19
3
IMOT
Program features
71
Settings
Parameter Purpose
99.02 Process PID control activation
40.01...40.13, 40.19, The settings of the process PID controller
40.25...40.27
32.13...32.18 The supervision limits for the process reference REF2 and the variables
ACT1 and ACT2
Diagnostics
Actual Signals Purpose
01.12, 01.24, 01.25, PID process controller reference, actual values and error value
01.26 and 01.34
Group 14 RELAY Supervision limit exceeded indication through a relay output
OUTPUTS
Group 15 ANALOGUE PID process controller values through standard analogue outputs
OUTPUTS
Group 96 EXTERNAL PID process controller values through optional analogue outputs
AO
Compare
Mot.speed 1 Select
0
Delay
And
1<2 INTERNAL Set/Reset
DI1 t S
40.21 2 ..
.
%refActive
PIDCtrlActive & 1)
40.20 modulating
40.22
S/R
R
Or
03.02 (B1)
1)
<1 Or 1 = Activate
03.02 (B2)
sleeping
Compare
StartRq
<1 0 = Deactivate
01.34
sleeping
1 Select Delay
0
1<2 INTERNAL t
DI1
40.23 2 ..
.
40.20 40.24
Program features
72
Example
The time scheme below visualises the operation of the sleep function.
Motor Speed
Sleep level
Par. 40.21 Text on display
SLEEP MODE
Time
Actual Value STOP START
twd
Wake-up level
Parameter 42.23
Time
twd = Wake-up delay, parameter 40.24
Actual Value
Inverted, i.e. par. 40.05 is YES.
Parameter 42.23
Wake-up level
twd
Time
Sleep function for a PID controlled pressure boost pump: The water consumption
falls at night. As a consequence, the PID process controller decreases the motor
speed. However, due to natural losses in the pipes and the low efficiency of the
centrifugal pump at low speeds, the motor does not stop but keeps rotating. The
sleep function detects the slow rotation, and stops the unnecessary pumping after
the sleep delay has passed. The drive shifts into sleep mode, still monitoring the
pressure. The pumping restarts when the pressure falls under the allowed minimum
level and the wake-up delay has passed.
Settings
Parameter Additional information
99.02 Process PID control activation
40.05 Inversion
40.20...40.24 Sleep function settings
Diagnostics
Warning SLEEP MODE on the panel display.
Program features
73
RMIO board
One sensor
AI1+
Motor
AI1-
T
AO1+
AO1-
10 nF The minimum voltage
(> 630 VAC) of the capacitor must
be 630 VAC.
Three sensors RMIO board
AI1+
Motor AI1-
T T T
AO1+
AO1-
10 nF
(> 630 VAC)
WARNING! According to IEC 664, the connection of the motor temperature sensor
to the RMIO board, requires double or reinforced insulation between motor live parts
and the sensor. Reinforced insulation entails a clearance and creepage distance of
8 mm (400 / 500 VAC equipment). If the assembly does not fulfil the requirement:
• The RMIO board terminals must be protected against contact and they may not
be connected to other equipment.
Or
• The temperature sensor must be isolated from the RMIO board terminals.
Program features
74
Settings
Parameter Additional information
15.01 Analogue output in a motor 1 temperature measurement. Set to M1 TEMP
MEAS.
35.01…35.03 Settings of motor 1 temperature measurement
Other
Parameters 13.01 to 13.05 (AI1 processing) and 15.02 to 15.05 (AO1 processing) are not effective.
At the motor end the cable shield should be earthed through a 10 nF capacitor. If this is not possible,
the shield is to be left unconnected.
Diagnostics
Actual values Additional information
01.35 Temperature value
Warnings
MOTOR 1 TEMP (4312) Measured motor temperature has exceeded the set alarm limit.
T MEAS ALM (FF91) Motor temperature measurement is out of acceptable range.
Faults
MOTOR 1 TEMP (4312) Measured motor temperature has exceeded the set fault limit.
Program features
75
RAIO module
One sensor
AI1+
Motor
AI1-
T
AO1+
AO1-
10 nF
(> 630 VAC)
SHLD
T T T
AO1+
AO1-
10 nF
(> 630 VAC)
SHLD
WARNING! According to IEC 664, the connection of the motor temperature sensor
to the RAIO module, requires double or reinforced insulation between motor live
parts and the sensor. Reinforced insulation entails a clearance and creepage
distance of 8 mm (400 / 500 VAC equipment). If the assembly does not fulfil the
requirement:
• The RAIO module terminals must be protected against contact and they may not
be connected to other equipment.
Or
• The temperature sensor must be isolated from the RAIO module terminals.
Program features
76
Settings
Parameter Additional information
35.01 … 35.03 Settings of motor 1 temperature measurement
98.12 Activation of optional analogue I/O for motor temperature measurement
Other
Parameters 13.16 to 13.20 (AI1 processing) and 96.01 to 96.05 (AO1 signal selection and processing)
are not effective.
At the motor end the cable shield should be earthed through a 10 nF capacitor. If this is not possible,
the shield is to be left unconnected.
Diagnostics
Actual values Additional information
01.35 Temperature value
Warnings
MOTOR 1 TEMP (4312) Measured motor temperature has exceeded the set alarm limit
T MEAS ALM (FF91) Motor temperature measurement is out of acceptable range.
Faults
MOTOR 1 TEMP (4312) Measured motor temperature has exceeded the set fault limit
DriveAP
DriveAP is a Windows based tool for Adaptive Programming. With DriveAP it is
possible to upload the Adaptive Program from the drive and edit it with PC.
For more information, see the DriveAP User’s Manual [3AFE64540998 (English)].
Program features
77
Example
The figure below shows a brake control application example.
WARNING! Make sure that the machinery into which the drive with brake control
function is integrated fulfils the personnel safety regulations. Note that the frequency
converter (a Complete Drive Module or a Basic Drive Module, as defined in IEC
61800-2), is not considered as a safety device mentioned in the European
Machinery Directive and related harmonised standards. Thus, the personnel safety
of the complete machinery must not be based on a specific frequency converter
feature (such as the brake control function), but it has to be implemented as defined
in the application specific regulations.
7 +24 V
Program features
78
1 5
Start command
External speed
reference
Inverter modulating 7
2
Motor magnetised tmd
tcd
Open brake
command
4
Internal speed
reference (actual tod 3 6
motor speed) ncs
Torque reference
Ts
time
Program features
79
State shifts
From any state
1) (rising edge)
NO
MODULATION 0/0/1
2)
OPEN
BRAKE 1/1/1
3)
A
5)
RELEASE RFG
INPUT 1/1/0
4)
RFG INPUT
TO ZERO 1/1/1
7)
10)
6)
11) CLOSE
BRAKE 0/1/1
RFG = Ramp Function 12)
A
Generator in the speed 13)
control loop (reference 8) 9)
handling).
BRAKE
ACK FAULT 0/0/1
State (Symbol NN )
X/Y/Z
- NN: State name
- X/Y/Z: State outputs/operations
X=1 Open the brake. The relay output set to brake on/off control energises.
Y=1 Forced start. The function keeps the internal Start on until the brake is closed in spite of the
status of the external Start signal.
Z=1 Ramp in zero. Forces the used speed reference (internal) to zero along a ramp.
Program features
80
Settings
Parameter Additional information
14.01 Relay output for the brake control (set to BRAKE CTRL)
Group 42 BRAKE CONTROL Brake function settings
Diagnostics
Actual value Additional information
03.01 Ramp in zero bit
03.13 The state of bit “brake open/close command”
Warnings
BRAKE ACKN (FF74) Unexpected state of brake acknowledge signal
Faults
BRAKE ACKN (FF74) Unexpected state of brake acknowledge signal
External control
External control
signals
signals
n 3 n 3
Supply Supply
3 3
Master/
Follower fault 2 2 Follower Link Follower fault 2 2 Master/Follower
supervision supervision Link
3 3
Supply Supply
3 3
Program features
81
Jogging
The jogging function is typically used to control a cyclical movement of a machine
section. One push button controls the drive through the whole cycle: When it is on,
the drive starts, accelerates to a preset speed at a preset rate. When it is off, the
drive decelerates to zero speed at a preset rate.
The figure and table below describe the operation of the drive. They also represent
how the drive shifts to normal operation (= jogging inactive) when the drive start
command is switched on. Jog cmd = State of the jogging input, Start cmd = State of
the drive start command.
The function operates on a 100 ms time level.
Speed
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Time
Program features
82
Settings
Parameter Additional information
10.06 Input for the on/off control of the jogging.
12.15 Jogging speed
21.10 Switch off delay for the inverter IGBT control. A delay keeps the inverter
modulation live over a short standstill period enabling a smooth restart.
22.04, 22.05 Acceleration and deceleration times used during the jogging.
22.06 Acceleration and deceleration ramp shape time: Set to zero during the
jogging.
Settings
Parameter Additional information
95.03 INT CONFIG Number of existing parallel connected inverters
USER
Diagnostics
Actual value Additional information
04.01 INT board fault
Faults
INT CONFIG Number of inverter modules is not equal to original number of inverters.
Program features
83
T/Tn
Normal motor load capacity
0 Hz 50 Hz 100 Hz
Overload
Overload supervision can be applied to the user load curve by setting parameters
72.18 LOAD CURRENT LIMIT... 72.20 COOLING TIME according to the overload
values defined by the motor manufacturer.
The supervision is based on an integrator, ∫I2dt. Whenever the drive output current
exceeds the user load curve, the integrator is started. When the integrator has
reached the overload limit defined by parameters 72.18 and 72.19, the drive reacts
as defined by parameter 72.01 OVERLOAD FUNC. The output of the integrator is
set to zero if the current stays continuously below the user load curve for the cooling
time defined by parameter 72.20 COOLING TIME.
If the overload time 72.19 LOAD THERMAL TIME is set to zero, the drive output
current is limited to the user load curve.
Current
72.20
COOLING TIME
Ioutput
Frequency / Time
Program features
84
Settings
Parameter Additional information
Group 72 USER LOAD User load curve
CURVE
Diagnostics
Actual value Additional information
02.20 Measured motor current in percent of the user load curve current
Warnings
USER L CURVE Integrated motor current has exceeded load curve.
Faults
USER L CURVE Integrated motor current has exceeded load curve.
Program features
85
Application macros
Chapter overview
This chapter describes the intended use, operation and the default control
connections of the standard application macros. It also describes how to save a user
macro, and how to recall it.
Overview of macros
Application macros are preprogrammed parameter sets. While starting up the drive,
the user typically selects one of the macros - the one that is best suited to his needs
- by parameter 99.02, makes the essential changes and saves the result as a user
macro.
There are five standard macros and two user macros. The table below contains a
summary of the macros and describes suitable applications.
Factory Ordinary speed control applications where no, one, two or three constant speeds
are used:
- Conveyors
- Speed-controlled pumps and fans
- Test benches with predefined constant speeds
Hand/Auto Speed control applications. Switching between two external control devices is
possible.
PID Control Process control applications e.g. different closed loop control systems such as
pressure control, level control, and flow control. For example:
- pressure boost pumps of municipal water supply systems
- level controlling pumps of water reservoirs
- pressure boost pumps of district heating systems
- material flow control on a conveyor line.
It is also possible to switch between process and speed control.
Torque Torque control applications. Switching between torque and speed control is
Control possible.
Sequential Speed control applications in which speed reference, seven constant speeds and
Control two acceleration and deceleration ramps can be used.
User The user can save the customised standard macro i.e. the parameter settings
including group 99, and the results of the motor identification into the permanent
memory, and recall the data at a later time. Two user macros are essential when
switching between two different motors is required
Application macros
86
WARNING! If the RMIO board is supplied from an external power source via
terminal X34, the loose end of the cable removed from the RMIO board terminal
must be secured mechanically to a location where it cannot come into contact with
electrical parts. If the screw terminal plug of the cable is removed, the wire ends
must be individually insulated.
Parameter settings
In Standard Control Program, set parameter 16.09 CTRL BOARD SUPPLY to
EXTERNAL 24V if the RMIO board is powered from an external supply.
Application macros
87
Factory macro
All drive commands and reference settings can be given from the control panel or
from an external control location. The active control location is selected with the
LOC/REM key of the panel. The drive is speed-controlled.
In external control, the control location is EXT1. The reference signal is connected to
analogue input AI1 and Start/Stop and Direction signals are connected to digital
inputs DI1 and DI2. By default, the direction is fixed to FORWARD (parameter
10.03). DI2 does not control the direction of rotation unless parameter 10.03 is
changed to REQUEST.
Three constant speeds are selected by digital inputs DI5 and DI6. Two acceleration/
deceleration ramps are preset. The acceleration and deceleration ramps are used
according to the state of digital input DI4.
Two analogue signals (speed and current) and three relay output signals (ready,
running and inverted fault) are available.
The default signals on the display of the control panel are FREQUENCY, CURRENT
and POWER.
Application macros
88
1)
Effective only if parameter 10.03 is X20
switched to REQUEST by the user. 1 VREF Reference voltage -10 VDC
2 GND 1 kohm < RL < 10 kohm
2)
The US default settings differ as X21
follows: 1 VREF Reference voltage 10 VDC
2 GND 1 kohm < RL < 10 kohm
DI1 Start (Pulse: 0->1)
3 AI1+ Speed reference 0(2) … 10 V, Rin > 200 kohm
DI2 Stop (Pulse: 1->0) 4 AI1-
DI3 Forward/Reverse 5 AI2+ By default, not in use. 0(4) … 20 mA, Rin =
6 AI2- 100 ohm
3) 7 AI3+ By default, not in use. 0(4) … 20 mA, Rin =
0 = ramp times according to par.
8 AI3- 100 ohm
22.02 and 22.03. 1 = ramp times
according to par. 22.04 and 22.05. rpm 9 AO1+ Motor speed 0(4) … 20 mA = 0 … motor nom.
10 AO1- speed, RL < 700 ohm
A 11 AO2+ Output current 0(4) … 20 mA = 0 … motor
4)
See parameter group 12 12 AO2- nom. current, RL < 700 ohm
CONSTANT SPEEDS: X22
DI5 DI6 Operation 1 DI1 Stop/Start 2)
0 0 Set speed through AI1 2 DI2 Forward/reverse 1, 2)
1 0 Speed 1 3 DI3 By default, not in use. 2)
0 1 Speed 2 4 DI4 Acceleration & deceleration select 3)
5 DI5 Constant speed select 4)
1 1 Speed 3
6 DI6 Constant speed select 4)
7 +24 V +24 VDC, max. 100 mA
5)
See parameter 21.09. 8 +24 V
9 DGND1 Digital ground
6) 10 DGND2 Digital ground
Total maximum current shared
11 DI IL Start interlock (0 = stop) 5)
between this output and optional
X23
modules installed on the board.
1 +24 V Auxiliary voltage output and input, non-
2 GND isolated, 24 V DC 250 mA 6)
X25
1 RO11 Relay output 1
2 RO12 Ready
3 RO13
X26
1 RO21 Relay output 2
2 RO22 Running
3 RO23
X27
1 R031 Relay output 3
Fault 2 R032 Inverted fault
3 R033
Application macros
89
Hand/Auto macro
Start/Stop and Direction commands and reference settings can be given from one of
two external control locations, EXT1 (Hand) or EXT2 (Auto). The Start/Stop/Direction
commands of EXT1 (Hand) are connected to digital inputs DI1 and DI2, and the
reference signal is connected to analogue input AI1. The Start/Stop/Direction
commands of EXT2 (Auto) are connected to digital inputs DI5 and DI6, and the
reference signal is connected to analogue input AI2. The selection between EXT1
and EXT2 is dependent on the status of digital input DI3. The drive is speed
controlled. Speed reference and Start/Stop and Direction commands can be given
from the control panel keypad also. One constant speed can be selected through
digital input DI4.
Speed reference in Auto Control (EXT2) is given as a percentage of the maximum
speed of the drive.
Two analogue and three relay output signals are available on terminal blocks. The
default signals on the display of the control panel are FREQUENCY, CURRENT and
CTRL LOC.
Application macros
90
1)
Selection between two external X20
control locations, EXT1 and EXT2. 1 VREF Reference voltage -10 VDC
2 GND 1 kohm < RL < 10 kohm
2)
See parameter 21.09. X21
1 VREF Reference voltage 10 VDC, kohm < RL <
3) 2 GND 10 kohm
Total maximum current shared
3 AI1+ Speed reference (Hand control). 0(2) … 10 V,
between this output and optional
4 AI1- Rin > 200 kohm
modules installed on the board.
5 AI2+ Speed reference (Auto control). 0(4) …
6 AI2- 20 mA, Rin = 100 ohm
7 AI3+ By default, not in use. 0(4) … 20 mA,
8 AI3- Rin = 100 ohm.
rpm 9 AO1+ Motor speed 0(4) … 20 mA = 0 … motor nom.
10 AO1- speed, RL < 700 ohm
A 11 AO2+ Output current 0(4) … 20 mA = 0 … motor
12 AO2- nom. current, RL < 700 ohm
X22
1 DI1 Stop/Start (Hand control)
2 DI2 Forward/Reverse (Hand control)
3 DI3 Hand/Auto control select 1)
4 DI4 Constant speed 4: Par. 12.05
5 DI5 Forward/Reverse (Auto control)
6 DI6 Stop/Start (Auto control)
7 +24 V +24 VDC, max. 100 mA
8 +24 V
9 DGND1 Digital ground
10 DGND2 Digital ground
11 DI IL Start interlock (0 = stop) 2)
X23
1 +24 V Auxiliary voltage output and input, non-
2 GND isolated, 24 V DC 250 mA 3)
X25
1 RO11 Relay output 1
2 RO12 Ready
3 RO13
X26
1 RO21 Relay output 2
2 RO22 Running
3 RO23
X27
1 R031 Relay output 3
Fault 2 R032 Inverted fault
3 R033
Application macros
91
Note: The sensor is supplied through its current output. Thus the output signal must
be 4…20 mA, not 0…20 mA.
Application macros
92
1)
Selection between two external X20
control locations, EXT1 and EXT2 1 VREF Reference voltage -10 VDC
2 GND 1 kohm < RL < 10 kohm
2)
In use only when the speed control X21
is active (DI3 = 0) 1 VREF Reference voltage 10 VDC
2 GND 1 kohm < RL < 10 kohm
3) 3 AI1+ Speed ref. (speed cntrl) or process ref.
Off = Run Enable off. Drive will not
4 AI1- (process cntrl). 0(2) … 10 V, Rin > 200 kohm
start or stops. On = Run Enable on.
Normal operation. PT
5 AI2+ Process actual value measurement. 0(4) …
6 AI2- 20 mA, Rin = 100 ohm
5)
4)
7 AI3+ By default, not in use. 0(4) … 20 mA, Rin =
See parameter 21.09. 8 AI3- 100 ohm.
rpm 9 AO1+ Motor speed 0(4) … 20 mA =
5) 10 AO1- 0 … motor nom. speed, RL < 700 ohm
The sensor needs to be powered.
See the manufacturer’s instructions. A 11 AO2+ Output current 0(4) … 20 mA =
A connection example of a two-wire 12 AO2- 0 … motor nom. current, RL < 700 ohm
24 VDC / 4…20 mA sensor is shown X22
on previous page. 1 DI1 Stop/Start (speed control)
2 DI2 By default, not in use.
6)Total maximum current shared 3 DI3 Speed / process control select 1)
between this output and optional 4 DI4 Constant speed 4: Par. 12.05 2)
modules installed on the board. 5 DI5 Run Enable. 3)
6 DI6 Stop/Start (process control)
7 +24 V +24 VDC, max. 100 mA
8 +24 V
9 DGND1 Digital ground
10 DGND2 Digital ground
11 DI IL Start interlock (0 = stop) 4)
X23
1 +24 V Auxiliary voltage output and input, non-
2 GND isolated, 24 V DC 250 mA 6)
X25
1 RO11 Relay output 1
2 RO12 Ready
3 RO13
X26
1 RO21 Relay output 2
2 RO22 Running
3 RO23
X27
1 R031 Relay output 3
Fault 2 R032 Inverted fault
3 R033
Application macros
93
Application macros
94
Application macros
95
Operation diagram
The figure below shows an example of the use of the macro.
Speed
Speed 3
Stop with
Speed 2 deceleration
ramp
Speed 1
Time
Accel1 Accel1 Accel2 Decel2
Start/Stop
Accel1/Decel1
Speed 1
Speed 2
Accel2/Decel2
Speed 3
Application macros
96
1) Off =
Ramp times according to par. X20
22.02 and 22.03. On = Ramp times 1 VREF Reference voltage -10 VDC
according to par. 22.04 and 22.05. 2 GND 1 kohm < RL < 10 kohm
X21
2) 1 VREF Reference voltage 10 VDC
See parameter group 12
CONSTANT SPEEDS: 2 GND 1 kohm < RL < 10 kohm
3 AI1+ External speed reference 0(2) … 10 V, Rin >
DI4 DI5 DI6 Operation
4 AI1- 200 kohm
0 0 0 Set speed through AI1
5 AI2+ By default, not in use. 0(4) … 20 mA, Rin =
1 0 0 Speed 1 6 AI2- 100 ohm
0 1 0 Speed 2 7 AI3+ By default, not in use. 0(4) … 20 mA, Rin =
1 1 0 Speed 3 8 AI3- 100 ohm
0 0 1 Speed 4 rpm 9 AO1+ Motor speed 0(4) … 20 mA = 0 … motor nom.
1 0 1 Speed 5 10 AO1- speed, RL < 700 ohm
0 1 1 Speed 6 A 11 AO2+ Output current 0(4) … 20 mA = 0 … motor
1 1 1 Speed 7 12 AO2- nom. current, RL < 700 ohm
X22
1 DI1 Stop/Start
3)
See parameter 21.09. 2 DI2 Forward/Reverse
3 DI3 Acceleration & deceleration selection 1)
4)
Total maximum current shared 4 DI4 Constant speed select 2)
between this output and optional 5 DI5 Constant speed select 2)
modules installed on the board. 6 DI6 Constant speed select 2)
7 +24 V +24 VDC, max. 100 mA
8 +24 V
9 DGND1 Digital ground
10 DGND2 Digital ground
11 DI IL Start interlock (0 = stop) 3)
X23
1 +24 V Auxiliary voltage output and input, non-
2 GND isolated, 24 V DC 250 mA 4)
X25
1 RO11 Relay output 1
2 RO12 Ready
3 RO13
X26
1 RO21 Relay output 2
2 RO22 Running
3 RO23
X27
1 R031 Relay output 3
Fault 2 R032 Inverted fault
3 R033
Application macros
97
User macros
In addition to the standard application macros, it is possible to create two user
macros. The user macro allows the user to save the parameter settings including
Group 99, and the results of the motor identification into the permanent memory, and
recall the data at a later time. The panel reference is also saved, if the macro is
saved and loaded in Local control mode. Remote control location setting is saved
into the user macro, but Local control location setting is not.
To create User Macro 1:
• Adjust the parameters. Perform the motor identification if not performed yet.
• Save the parameter settings and the results of the motor identification by
changing parameter 99.02 to USER 1 SAVE (press ENTER). The storing takes 20
s to 1 min.
Note: If user macro save function is executed several times, drive memory fills up
and file compression starts. File compression can last up to 10 minutes. Macro
saving will be completed after the file compression. (Operation is indicated on the
last row of the control panel display by blinking dots).
To recall the user macro:
• Change parameter 99.02 to USER 1 LOAD.
• Press ENTER to load.
The user macro can also be switched via digital inputs (see parameter 16.05).
Note: User macro load restores also the motor settings in group 99 START-UP
DATA and the results of the motor identification. Check that the settings correspond
to the motor used.
Example: The user can switch the drive between two motors without having to
adjust the motor parameters and to repeat the motor identification every time the
motor is changed. The user needs only to adjust the settings and perform the motor
identification once for both motors and then to save the data as two user macros.
When the motor is changed, only the corresponding User macro needs to be loaded,
and the drive is ready to operate.
Application macros
98
Application macros
99
Chapter overview
The chapter describes the actual signals and parameters and gives the fieldbus
equivalent values for each signal/parameter. More data is given in chapter Additional
data: actual signals and parameters.
Absolute Maximum Value of 20.08, or 20.07 if the absolute value of the minimum limit is
Frequency greater than the maximum limit.
Absolute Maximum Value of parameter 20.02, or 20.01 if the absolute value of the minimum
Speed limit is higher than the maximum limit.
Actual signal Signal measured or calculated by the drive. Can be monitored by the
user. No user setting possible.
FbEq Fieldbus equivalent: The scaling between the value shown on the panel
and the integer used in serial communication.
DI1,2 Start and stop through digital input DI1. 0 = stop, 1 = start. Direction through 3
digital input DI2. 0 = forward, 1 = reverse. To control direction, parameter 10.03
DIRECTION must be REQUEST.
WARNING! After a fault reset, the drive will start if the start signal is
on.
DI1P,2P Pulse start through digital input DI1. 0 -> 1: Start. Pulse stop through digital 4
input DI2. 1 -> 0: Stop. Direction of rotation is fixed according to parameter
10.03 DIRECTION.
DI1P,2P,3 Pulse start through digital input DI1. 0 -> 1: Start. Pulse stop through digital 5
input DI2. 1 -> 0: Stop. Direction through digital input DI3. 0 = forward, 1 =
reverse. To control direction, parameter 10.03 DIRECTION must be
REQUEST.
DI1P,2P,3P Pulse start forward through digital input DI1. 0 -> 1: Start forward. Pulse start 6
reverse through digital input DI2. 0 -> 1: Start reverse. Pulse stop through
digital input DI3. 1 -> ”0”: stop. To control the direction, parameter 10.03
DIRECTION must be REQUEST.
DI6 See selection DI1. 7
DI6,5 See selection DI1,2. DI6: Start/stop, DI5: direction. 8
KEYPAD Control panel. To control the direction, parameter 10.03 DIRECTION must be 9
REQUEST.
COMM.CW Fieldbus Control Word. 10
DI7 See selection DI1. 11
DI7,8 See selection DI1,2. DI7: start/stop, DI8: direction. 12
DI7P,8P See selection DI1P,2P. 13
DI7P,8P,9 See selection DI1P,2P,3. 14
DI7P,8P,9P See selection DI1P,2P,3P. 15
PARAM 10.04 Source selected by 10.04. 16
DI1 F, DI2 R Start, stop and direction commands through digital inputs DI1 and DI2. 17
11.01 KEYPAD REF SEL Selects the type of the reference given from panel.
REF1 (rpm) Speed reference in rpm. (Frequency reference (Hz) if parameter 99.04 is 1
SCALAR.)
REF2 (%) %-reference. The use of REF2 vary depending on the application macro. For 2
example, if the Torque Control macro is selected, REF2 is the torque
reference.
11.02 EXT1/EXT2 SELECT Defines the source from which the drive reads the signal that selects between
the two external control locations, EXT1 or EXT2.
DI1 Digital input DI1. 0 = EXT1, 1 = EXT2. 1
DI2 See selection DI1. 2
11.05
11.04
0
AI1
-11.04
-11.05
2 6 10
Par. 13.01 = 2 V, Par 13.02 = 10 V
Note: If the signal is bipolar (±10 VDC), use the selection AI1 BIPOLAR. The
selection AI1/JOYST ignores the negative signal range.
AI2/JOYST See selection AI1/JOYST. 6
AI1+AI3 Summation of analogue input AI1 and AI3 7
AI2+AI3 Summation of analogue input AI2 and AI3 8
AI1-AI3 Subtraction of analogue input AI1 and AI3 9
AI2-AI3 Subtraction of analogue input AI2 and AI3 10
AI1*AI3 Multiplication of analogue input AI1 and AI3 11
AI2*AI3 Multiplication of analogue input AI2 and AI3 12
MIN(AI1,AI3) Minimum of analogue input AI1 and AI3 13
MIN(AI2,AI3) Minimum of analogue input AI2 and AI3 14
MAX(AI1,AI3) Maximum of analogue input AI1 and AI3 15
MAX(AI2,AI3) Maximum of analogue input AI2 and AI3 16
DI3U,4D(R) Digital input 3: Reference increase. Digital input DI4: Reference decrease. 17
Stop command or power switch off resets the reference to zero. Parameter
22.04 defines the rate of the reference change.
DI3U,4D Digital input 3: Reference increase. Digital input DI4: Reference decrease. The 18
program stores the active speed reference (not reset by a stop command or
power switch-off). Parameter 22.04 defines the rate of the reference change.
DI5U,6D See selection DI3U,4D. 19
COMM. REF Fieldbus reference REF1 20
COM.REF1+AI1 Summation of fieldbus reference REF1 and analogue input AI1 21
COM.REF1*AI1 Multiplication of fieldbus reference REF1 and analogue input AI1 22
10.03 DIRECTION =
FORWARD or
REQUEST
Speed Reference
minREF1
-minREF1
10.03 DIRECTION =
REVERSE or
REQUEST
-scaled
maxREF1
-maxAI1 -minAI1 minAI1 maxAI1
Analogue Input Signal
11.04 EXT REF1 MINIMUM Defines the minimum value for external reference REF1 (absolute value).
Corresponds to the minimum setting of the source signal used.
0 … 18000 rpm Setting range in rpm. (Hz if parameter 99.04 is SCALAR.) 1 … 18000
Example: Analogue input AI1 is selected as the reference source (value of
parameter 11.03 is AI1). The reference minimum and maximum correspond
the AI minimum and maximum settings as follows:
EXT REF1 Range
2’
1 parameter 13.01
2 parameter 13.02
1’ parameter 11.04
2’ parameter 11.05
1’
AI1 Range
1 2
Note: If the reference is given through fieldbus, the scaling differs from that of
an analogue signal. See chapter Fieldbus control for more information.
DI7(SPEED1) Speed defined by parameter 12.02 is activated through digital input DI7. 15
1 = active, 0 = inactive.
DI8(SPEED2) Speed defined by parameter 12.03 is activated through digital input DI8. 16
1 = active, 0 = inactive.
60% 90 rpm
690 rpm
40% 600 rpm
0V 0 mA 0 rpm
%
Unfiltered Signal O = I · (1 - e-t/T)
100
I = filter input (step)
63 O = filter output
Filtered Signal
t = time
T = filter time constant
t
T
Note: The signal is also filtered due to the signal interface hardware (10 ms
time constant). This cannot be changed by any parameter.
0.00 … 10.00 s Filter time constant 0 … 1000
13.05 INVERT AI1 Activates/deactivates the inversion of analogue input AI1.
NO No inversion 0
YES Inversion active. The maximum value of the analogue input signal corresponds 65535
to the minimum reference and vice versa.
13.06 MINIMUM AI2 See parameter 13.01.
0 mA See parameter 13.01. 1
4 mA See parameter 13.01. 2
TUNED VALUE See parameter 13.01. 3
TUNE See parameter 13.01. 4
13.07 MAXIMUM AI2 See parameter 13.02.
20 mA See parameter 13.02. 1
TUNED VALUE See parameter 13.02. 2
TUNE See parameter 13.02. 3
1
Drive status
0
1
RO1 status
0
time
tOn tOff tOn tOff
tOn 14.04
tOff 14.05
14.05 RO1 TOFF DELAY Defines the release delay for relay output RO1.
0.0 … 3600.0 s See parameter 14.04. 0 … 36000
14.06 RO2 TON DELAY Defines the operation delay for relay output RO2.
0.0 … 3600.0 s See parameter 14.04. 0 … 36000
14.07 RO2 TOFF DELAY Defines the release delay for relay output RO2.
0.0 … 3600.0 s See parameter 14.04. 0 … 36000
14.08 RO3 TON DELAY Defines the operation delay for relay output RO3.
0.0 … 3600.0 s See parameter 14.04. 0 … 36000
14.09 RO3 TOFF DELAY Defines the release delay of relay output RO3.
0.0 … 3600.0 s See parameter 14.04. 0 … 36000
%
Unfiltered Signal O = I · (1 - e-t/T)
100
I = filter input (step)
63 O = filter output
Filtered Signal
t = time
T = filter time constant
t
T
Note: Even if you select 0 s as the minimum value, the signal is still filtered
with a time constant of 10 ms due to the signal interface hardware. This cannot
be changed by any parameters.
15.05 SCALE AO1 Scales the analogue output AO1 signal.
10 … 1000% Scaling factor. If the value is 100%, the reference value of the drive signal 100 …
corresponds to 20 mA. 10000
Example: The nominal motor current is 7.5 A and the measured maximum
current at maximum load 5 A. The motor current 0 to 5 A needs to be read as 0
to 20 mA analogue signal through AO1. The required settings are:
1. AO1 is set to CURRENT by parameter 15.01.
2. AO1 minimum is set to 0 mA by parameter 15.03.
3. The measured maximum motor current is scaled to correspond to 20 mA
analogue output signal by setting the scaling factor (k) to 150%. The value is
defined as follows: The reference value of the output signal CURRENT is the
motor nominal current i.e. 7.5 A (see parameter 15.01). To make the measured
maximum motor current correspond to 20 mA, it should be scaled equal to the
reference value before it is converted to an analogue output signal. Equation:
k · 5 A = 7.5 A => k = 1.5 = 150%
15.06 ANALOGUE See parameter 15.01.
OUTPUT2
NOT USED See parameter 15.01. 1
P SPEED See parameter 15.01. 2
SPEED See parameter 15.01. 3
FREQUENCY See parameter 15.01. 4
CURRENT See parameter 15.01. 5
TORQUE See parameter 15.01. 6
POWER See parameter 15.01. 7
DC BUS VOLT See parameter 15.01. 8
OUTPUT VOLT See parameter 15.01. 9
APPL OUTPUT See parameter 15.01. 10
REFERENCE See parameter 15.01. 11
CONTROL DEV See parameter 15.01. 12
ACTUAL 1 See parameter 15.01. 13
20.04 TORQ MAX LIM1 Defines the maximum torque limit 1 for the drive.
0.0 … 600.0% Value of limit in percent of motor nominal torque. 0 … 60000
20.05 OVERVOLTAGE Activates or deactivates the overvoltage control of the intermediate DC link.
CTRL Fast braking of a high inertia load causes the voltage to rise to the overvoltage
control limit. To prevent the DC voltage from exceeding the limit, the
overvoltage controller automatically decreases the braking torque.
Note: If a brake chopper and resistor are connected to the drive, the controller
must be off (selection NO) to allow chopper operation.
OFF Overvoltage control deactivated. 0
ON Overvoltage control activated. 65535
20.06 UNDERVOLTAGE Activates or deactivates the undervoltage control of the intermediate DC link.
CTRL If the DC voltage drops due to input power cut off, the undervoltage controller
will automatically decrease the motor speed in order to keep the voltage above
the lower limit. By decreasing the motor speed, the inertia of the load will cause
regeneration back into the drive, keeping the DC link charged and preventing
an undervoltage trip until the motor coasts to stop. This will act as a power-loss
ride-through functionality in systems with a high inertia, such as a centrifuge or
a fan.
OFF Undervoltage control deactivated. 0
ON Undervoltage control activated. 65535
20.07 MINIMUM FREQ Defines the minimum limit for the drive output frequency. The limit can be set
only parameter 99.04 = SCALAR.
-300.00 … 50 Hz Minimum frequency limit. -30000 …
Note: If the value is positive, the motor cannot be run in the reverse direction. 5000
20.08 MAXIMUM FREQ Defines the maximum limit for the drive output frequency. The limit can be set
only if parameter 99.04 = SCALAR
-50 … 300.00 Hz Maximum frequency limit -5000 …
30000
13.01 13.02
Analogue signal
0.0 … 600.0% %-value that corresponds to the minimum setting of the analogue input. 100 = 1%
20.21 MAX AI SCALE See parameter 20.20.
0.0 … 600.0% %-value that corresponds to the maximum setting of the analogue input. 100 = 1%
20.22 SLS SPEED LIMIT Defines the safely-limited speed limit (SLS). When the SLS function is 20000 =
activated the speed limits are ramped to 20.22 SLS SPEED LIMIT. The speed 1500 rpm
of the deceleration to SLS is defined by parameter 22.11 and acceleration from
SLS to the original speed is defined by parameter 22.10.
Note: This parameter is available in AS7R firmware version only.
0…9000 rpm (0…4
times sync speed)
21 START/STOP Start and stop modes of the motor.
21.01 START FUNCTION Selects the motor starting method. See also section Automatic Start on page
54.
SPEEDmotor
DC Hold
Ref. t
DC HOLD SPEED
t
Note: DC Hold has no effect if the start signal is switched off.
Note: Injecting DC current into the motor causes the motor to heat up. In
applications where long DC hold times are required, externally ventilated
motors should be used. If the DC hold period is long, the DC hold cannot
prevent the motor shaft from rotating if a constant load is applied to the motor.
See section DC Hold on page 57.
NO Inactive 0
YES Active 65535
21.05 DC HOLD SPEED Defines the DC Hold speed. See parameter 21.04.
0 … 3000 rpm Speed in rpm 0 … 3000
21.06 DC HOLD CURR Defines the DC hold current. See parameter 21.04.
0 … 100% Current in percent of the motor nominal current 0 … 100
21.07 RUN ENABLE FUNC Selects the stop mode applied when the Run Enable signal is switched off. The
Run Enable signal is put into use by parameter 16.01.
Note: The setting overrides the normal stop mode setting (parameter 21.03)
when the Run Enable signal is switched off.
WARNING! The drive will restart after the Run Enable signal restores
(if the start signal is on).
RAMP STOP The application program stops the drive along the deceleration ramp defined in 1
group 22 ACCEL/DECEL.
COAST STOP The application program stops the drive by cutting off the motor power supply 2
(the inverter IGBTs are blocked). The motor rotates freely to zero speed.
WARNING! If the brake control function is on, the application program
uses ramp stop in spite of the selection COAST STOP (see parameter
group 42 BRAKE CONTROL).
OFF2 STOP The application program stops the drive by cutting off the motor power supply 3
(the inverter IGBTs are blocked). The motor rotates freely to zero speed. The
drive will restart only when the Run Enable signal is on and the start signal is
switched on (the program receives the rising edge of the start signal).
S-curve ramp:
Par. 22.06 > 0 s
time
Par. 22.02 Par. 22.06
22.07 EM STOP RAMP Defines the time inside which the drive is stopped if
TIME - the drive receives an emergency stop command or
- the Run Enable signal is switched off and the Run Enable function has value
OFF3 (see parameter 21.07).
The emergency stop command can be given through a fieldbus or an
Emergency Stop module (optional). Consult the local ABB representative for
more information on the optional module and the related settings of the
Standard Control Program.
0.00 … 2000.00 s Deceleration time 0 … 200000
22.08 ACC PTR Defines the source or constant for value PAR 22.08&09 of parameter 22.01.
-255.255.31 … Parameter index or a constant value. See parameter 10.04 for information on 100 = 1 s
+255.255.31 / C.- the difference.
32768 … C.32767
22.09 DEC PTR Defines the source or constant for value PAR 22.08&09 of parameter 22.01
-255.255.31 … Parameter index or a constant value. See parameter 10.04 for information on 100 = 1 s
+255.255.31 / C.- the difference.
32768 … C.32767
22.10 SLS ACCELER TIME Defines the time required for the speed limits to ramp up from the safely-limited 100 = 1 s
speed defined by parameter 20.22 to the speed limits defined by parameters
20.01 MINIMUM SPEED and 20.02 MAXIMUM SPEED when the SLS function
is deactivated.
Note: This parameter is available in AS7R firmware version only.
0…1800 s Speed ramp time.
%
Gain = Kp = 1
TI = Integration time = 0
TD= Derivation time = 0
Error Value
Controller Output
Controller e = Error value
output = Kp · e
t
0.0 … 250.0 Gain 0 … 25000
23.02 INTEGRATION TIME Defines an integration time for the speed controller. The integration time
defines the rate at which the controller output changes when the error value is
constant. The shorter the integration time, the faster the continuous error value
is corrected. Too short an integration time makes the control unstable.
The figure below shows the speed controller output after an error step when
the error remains constant.
%
Controller Output
Gain = Kp = 1
TI = Integration time > 0
Kp · e TD= Derivation time = 0
Kp · e e = Error value
t
TI
0.01 … 999.97 s Integration time 10 …
999970
Controller Output
Δe
Kp · TD ·
Ts Kp · e
Error Value
Kp · e e = Error value
t
TI
0.0 … 9999.8 ms Derivation time value. 1 = 1 ms
23.04 ACC Defines the derivation time for acceleration/(deceleration) compensation. In
COMPENSATION order to compensate inertia during acceleration a derivative of the reference is
added to the output of the speed controller. The principle of a derivative action
is described for parameter 23.03.
Note: As a general rule, set this parameter to the value between 50 and 100%
of the sum of the mechanical time constants of the motor and the driven
machine. (The speed controller Autotune Run does this automatically, see
parameter 23.06.)
The figure below shows the speed responses when a high inertia load is
accelerated along a ramp.
% % Speed reference
Actual speed
t t
0.00 … 999.98 s Derivation time 0 … 9999
23.07 SP ACT FILT TIME Defines the time constant of the actual speed filter, i.e. time within the actual
speed has reached 63% of the nominal speed.
0...1000000 ms Time constant 1 = 1 ms
24 TORQUE CTRL Torque control variables.
Visible only if parameter 99.02 = T CNTRL and parameter 99.04 = DTC.
24.01 TORQ RAMP UP Defines the torque reference ramp up time.
0.00 … 120.00 s Time for the reference to increase from zero to the nominal motor torque. 0 … 12000
24.02 TORQ RAMP DOWN Defines the torque reference ramp down time.
0.00 … 120.00 s Time for the reference to decrease from the nominal motor torque to zero. 0 … 12000
25 CRITICAL SPEEDS Speed bands within which the drive is not allowed to operate. See section
Critical speeds on page 59.
25.01 CRIT SPEED Activates/deactivates the critical speeds function.
SELECT Example: A fan has vibrations in the range of 540 to 690 rpm and 1380 to
1560 rpm. To make the drive to jump over the vibration speed ranges:
- activate the critical speeds function,
- set the critical speed ranges as in the figure below.
Motor speed
(rpm) 1 Par. 25.02 = 540 rpm
2 Par. 25.03 = 690 rpm
1560
3 Par. 25.04 = 1380 rpm
1380
690 4 Par. 25.05 = 1590 rpm
540
Note: If parameter 99.02 = PID CTRL, the critical speeds are not in use.
OFF Inactive 0
ON Active. 65535
100%
f (Hz)
Field weakening point
0 … 30% Voltage boost at zero speed in percent of the motor nominal voltage 0 … 3000
U / UN
(%)
100%
26.03 IR
COMPENSATION
f (Hz)
For more information, see the Sine Filters User’s Manual for ACS800 Drives
[3AFE68389178 (English)].
0...50 Hz Frequency
26.05 HEX FIELD WEAKEN Selects whether motor flux is controlled along a circular or a hexagonal pattern
in the field weakening area of the frequency range (above 50/60 Hz). See
section Hexagonal motor flux on page 63.
OFF The rotating flux vector follows a circular pattern. Optimal selection in most 0
applications: Minimal losses at constant load. Maximal instantaneous torque is
not available in the field weakening range of the speed.
ON Motor flux follows a circular pattern below the field weakening point (typically 65535
50 or 60 Hz) and a hexagonal pattern in the field weakening range. Optimal
selection in the applications that require maximal instantaneous torque in the
field weakening range of the speed. The losses at constant operation are
higher than with the selection NO.
26.06 FLUX REF PTR Selects the source for the flux reference, or sets the flux reference value.
-255.255.31 … Parameter index or a constant value. See parameter 10.04 for information on 100 = 1%
+255.255.31 / C.- the difference. The range of the flux is 25 … 140%. With constant value
32768 … C.32767 settings 100% = C.10000. Typically there is no need to change this value.
26.07 FLYSTART CUR REF Defines the current reference used with flying start (start to a rotating motor) 1 = 1%
[%] when no pulse encoder is used.
If flying start fails (i.e. drive is unable to detect motor speed 01.02 SPEED):
Monitor signals 01.02 SPEED and 01.04 CURRENT with DriveWindow PC tool
and increase the reference in steps of 5% until the flying start function is
successfully performed (i.e. drive is able to detect 01.02 SPEED).
See also parameter 26.08 FLYSTART INIT DLY.
0…100% Value in percent
LAST SPEED The drive generates a warning AI < MIN FUNC (8110) and freezes the speed 4
to the level the drive was operating at. The speed is determined by the average
speed over the previous 10 seconds.
WARNING! Make sure that it is safe to continue operation in case the
analogue input signal is lost.
30.02 PANEL LOSS Selects how the drive reacts to a control panel communication break.
FAULT Drive trips on a fault and the motor coasts to a stop. 1
CONST SP 15 The drive generates a warning and sets the speed to the speed defined by 2
parameter 12.16.
WARNING! Make sure that it is safe to continue operation in case of a
panel communication break.
LAST SPEED The drive generates a warning and freezes the speed to the level the drive was 3
operating at. The speed is determined by the average speed over the previous
10 seconds.
WARNING! Make sure that it is safe to continue operation in case of a
panel communication break.
30.03 EXTERNAL FAULT Selects an interface for an external fault signal. See section External Fault on
page 63.
NOT SEL Inactive 1
DI1 External fault indication is given through digital input DI1. 0: Fault trip. Motor 2
coasts to stop. 1: No external fault.
DI2 See selection DI1. 3
DI3 See selection DI1. 4
DI4 See selection DI1. 5
DI5 See selection DI1. 6
DI6 See selection DI1. 7
DI7 See selection DI1. 8
DI8 See selection DI1. 9
DI9 See selection DI1. 10
DI10 See selection DI1. 11
DI11 See selection DI1. 12
DI12 See selection DI1. 13
USER MODE The protection is based on the user-defined motor thermal model and the 2
following basic assumptions:
- The motor is at the estimated temperature (value of 01.37 MOTOR
TEMP EST saved at power switch off) when the power is switched on. With the
first power switch on, the motor is at the ambient temperature (30°C).
- The motor temperature increases if it operates in the region above the motor
load curve.
- The motor temperature decreases if it operates in the region below the curve.
This applies only if the motor is overheated.
The user-defined thermal model uses the motor thermal time constant
(parameter 30.06) and the motor load curve (parameters 30.07, 30.08 and
30.09). User tuning is typically needed only if the ambient temperature differs
from the normal operating temperature specified for the motor.
WARNING! The model does not protect the motor if it does not cool
properly due to dust and dirt.
6 DI6
7 +24 VDC
T
Motor
6 DI6
7 +24 VDC
T 10 nF
Motor
Note: If the motor nominal current is above 800 A, the user defined motor
thermal model is used instead of the calculated model and the user must
define parameters 30.06, 30.07, 30.08 and 30.09.
Motor
Load
100%
Temperature
t
100%
63%
t
Motor thermal time constant
256.0 … 9999.8 s Time constant 256 … 9999
30.07 MOTOR LOAD Defines the load curve together by parameters 30.08 and 30.09. The load
CURVE curve is used in the user-defined thermal model (see the selection USER
MODE of parameter 30.05).
30.07
100
50
30.08
50.0 … 150.0% Allowed continuous motor load in percent of the nominal motor current. 50 … 150
30.08 ZERO SPEED LOAD Defines the load curve together with parameters 30.07 and 30.09.
25.0 … 150.0% Allowed continuous motor load at zero speed in percent of the nominal motor 25 … 150
current
30.09 BREAK POINT Defines the load curve together with parameters 30.07 and 30.08.
1.0 … 300.0 Hz Drive output frequency at 100% load 100 …
30000
80 3
70%
60 2
50%
40 1 5
30%
20
4
0
ƒN 2.4 * ƒN
LAST SPEED Protection is active. The drive generates a warning and freezes the speed to 4
the level the drive was operating at. The speed is determined by the average
speed over the previous 10 seconds.
WARNING! Make sure that it is safe to continue operation in case of a
communication break.
30.19 MAIN REF DS T-OUT Defines the time delay for the Main Reference data set supervision. See
parameter 30.18.
0.1 … 60.0 s Time delay 10 … 6000
30.20 COMM FLT RO/AO Selects the operation of the fieldbus controlled relay output and analogue
output in a communication break. See groups 14 RELAY OUTPUTS and 15
ANALOGUE OUTPUTS and chapter Fieldbus control. The delay for the
supervision function is given by parameter 30.21.
ZERO Relay output is de-energised. Analogue output is set to zero. 0
LAST VALUE The relay output keeps the last state before the communication loss. The 65535
analogue output gives the last value before the communication loss.
WARNING! After the communication recovers, the update of the relay
and the analogue outputs starts immediately without fault message
resetting.
30.21 AUX DS T-OUT Defines the delay time for the Auxiliary Reference data set supervision. See
parameter 30.18. The drive automatically activates the supervision 60 seconds
after power switch-on if the value is other than zero.
Note: The delay also applies for the function defined by parameter 30.20.
0.0 … 60.0 s Time delay. 0.0 s = The function is inactive. 0 … 6000
32.02 SPEED1 LIMIT Defines the speed supervision limit. See parameter 32.01.
- 18000 … 18000 rpm Value of the limit - 18000 …
18000
32.03 SPEED2 FUNCTION See parameter 32.01.
NO See parameter 32.01. 1
LOW LIMIT See parameter 32.01. 2
HIGH LIMIT See parameter 32.01. 3
ABS LOW LIMIT See parameter 32.01. 4
32.04 SPEED2 LIMIT See parameter 32.01.
- 18000 … 18000 rpm See parameter 32.01. - 18000 …
18000
32.05 CURRENT Activates/deactivates the motor current supervision function and selects the
FUNCTION type of the supervision limit.
NO See parameter 32.01. 1
LOW LIMIT See parameter 32.01. 2
HIGH LIMIT See parameter 32.01. 3
32.06 CURRENT LIMIT Defines the limit for the motor current supervision (see parameter 32.05).
0 … 1000 A Value of the limit 0 … 1000
32.07 TORQUE 1 Activates/deactivates the motor torque supervision function and selects the
FUNCTION type of the supervision limit.
NO See parameter 32.01. 1
LOW LIMIT See parameter 32.01. 2
33.02 APPL SW VERSION Displays the type and the version of the application program.
Note: Parameter setting cannot be changed by the user.
Decoding key:
ASAxxxyx
Product Series
A = ACS800
Product
S = ACS800 Standard
Firmware Type
A = Application Program
Firmware Version
7xyx = Version 7.xyx
PARAMETER
TABLE
Select
00.00
•••
99.99
34.03 Mul.
34.01 01.01
Select
NO
Unit for actual
FPM signal 01.01
34.02
%
Unfiltered Signal O = I · (1 - e-t/T)
100
I = filter input (step)
63 O = filter output
Filtered Signal
t = time
T = filter time constant
t
T
34.05 TORQ ACT FILT TIM Defines a filter time for the actual signal torque (actual signal 01.05). Affects
also on the torque supervision (parameters 32.07 and 32.09) and the torque
read through an analogue output.
0 … 20000 ms Filter time constant 0 … 20000
%
Unfiltered Signal O = I · (1 - e-t/T)
100
I = filter input (step)
63 O = filter output
Filtered Signal
t = time
T = filter time constant
t
T
34.06 RESET RUN TIME Resets the motor running time counter (actual signal 01.43).
NO No reset. 0
YES Reset. The counter restarts from zero. 65535
35 MOT TEMP MEAS Motor temperature measurement. For the function description see sections
Motor temperature measurement through the standard I/O on page 73 and
Motor temperature measurement through an analogue I/O extension on page
75.
35.01 MOT 1 TEMP AI1 SEL Activates the motor 1 temperature measurement function and selects the
sensor type.
Note: If an optional analogue I/O extension module RAIO is used for the
temperature measurement and 35.01 MOT 1 TEMP AI1 SEL and/or 35.04
MOT 2 TEMP AI2 SEL are set to 1xPT100, analogue extension module input
signal range must be set to 0...2 V (instead of 0...10 V) with DIP switches.
NOT IN USE The function is inactive. 1
1xPT100 The function is active. The temperature is measured with one Pt 100 sensor. 2
Analogue output AO1 feeds constant current through the sensor. The sensor
resistance increases as the motor temperature rises, as does the voltage over
the sensor. The temperature measurement function reads the voltage through
analogue input AI1 and converts it to degrees centigrade.
2XPT100 The function is active. Temperature is measured using two Pt 100 sensors. 3
See selection 1xPT100.
3XPT100 The function is active. Temperature is measured using three Pt 100 sensors. 4
See selection 1xPT100.
100
T
35.02 MOT 1 TEMP ALM L Defines the alarm limit for motor 1 temperature measurement. The alarm
indication is given when the limit is exceeded.
-10 … 5000 ohm/°C Limit in °C or ohms. °C: parameter 35.01 is 1xPT100, 2XPT100, 3XPT100. -10 … 5000
(PTC/Pt100) Ohm: parameter 35.01 is 1...3 PTC.
35.03 MOT 1 TEMP FLT L Defines the fault trip limit for motor 1 temperature measurement. The fault
indication is given when the limit is exceeded.
-10 … 5000 ohm/°C Limit in °C or ohms. °C: parameter 35.01 is 1xPT100, 2XPT100, 3XPT100. -10 … 5000
(PTC/Pt100) Ohm: parameter 35.01 is 1...3 PTC.
35.04 MOT 2 TEMP AI2 SEL Activates the motor 2 temperature measurement function and selects the
sensor type. Two motors can be protected only by using an optional analogue
extension module. Parameter 98.12 needs to be activated.
Note: If 98.12 is activated, the analogue I/O extension is also used for motor 1
temperature measurement (the standard I/O terminals are not in use).
Note: If an optional analogue I/O extension module RAIO is used for the
temperature measurement and 35.01 MOT 1 TEMP AI1 SEL and/or 35.04
MOT 2 TEMP AI2 SEL are set to 1xPT100, analogue extension module input
signal range must be set to 0...2 V (instead of 0...10 V) with DIP switches.
NOT IN USE See 35.01. 1
1xPT100 See 35.01. 2
2XPT100 See 35.01. 3
3XPT100 See 35.01. 4
1...3 PTC See 35.01. 5
35.05 MOT 2 TEMP ALM L Defines the alarm limit for the motor 2 temperature measurement function. The
alarm indication is given when the limit is exceeded.
-10 … 5000 ohm/°C See 35.02. -10 … 5000
(PTC/Pt100)
40.02 PID INTEG TIME Defines the integration time for the process PID controller.
Error/Controller output
O I = controller input (error)
I
O = controller output
G·I G = gain
t = time
G·I Ti = integration time
time
Ti
0.02 … 320.00 s Integration time 2 … 32000
%
Unfiltered Signal O = I · (1 - e-t/T)
100
I = filter input (step)
63 O = filter output
Filtered Signal
t = time
T = filter time constant
t
T
40.05 ERROR VALUE INV Inverts the error at the process PID controller input (error = process reference -
process actual value).
NO No inversion 0
YES Inversion. 65535
With sleep function, the drive operation is as follows:
The drive enters the sleep mode when the motor speed is below the sleep
level (02.02 < 40.21) and when the process PID control actual value is smaller
than the wake-up level (01.34 < 40.23).
The drive wakes up when the process PID actual value is greater than the
wake-up level (01.34 > 40.23).
See also section Sleep function for the process PID control on page 71.
40.06 ACTUAL VALUE SEL Selects the process actual value for the process PID controller: The sources
for the variable ACT1 and ACT2 are further defined by parameters 40.07 and
40.08.
ACT1 ACT1 1
ACT1-ACT2 Subtraction of ACT1 and ACT 2. 2
ACT1+ACT2 Addition of ACT1 and ACT2 3
ACT1*ACT2 Multiplication of ACT1 and ACT2 4
ACT1/ACT2 Division of ACT1 and ACT2 5
MIN(A1,A2) Selects the smaller of ACT1 and ACT2 6
MAX(A1,A2) Selects the higher of ACT1 and ACT2 7
sqrt(A1-A2) Square root of the subtraction of ACT1 and ACT2 8
sqA1+sqA2 Addition of the square root of ACT1 and the square root of ACT2 9
40.07 ACTUAL1 INPUT SEL Selects the source for the variable ACT1. See parameter 40.06.
AI1 Analogue input AI1 1
AI2 Analogue input AI2 2
AI3 Analogue input AI3 3
AI5 Analogue input AI5 4
AI1min - 13.01
ACT1 MINIMUM = · 100%
13.02 - 13.01
AI1min The voltage value received from the measuring device when
the measured process actual value is at the desired minimum
level.
13.01 AI1 minimum (parameter setting)
13.02 AI1 maximum (parameter setting)
40.10 ACT1 MAXIMUM Defines the maximum value for the variable ACT1 if an analogue input is
selected as a source for ACT1. See parameter 40.07. The minimum (40.09)
and maximum settings of ACT1 define how the voltage/current signal received
from the measuring device is converted to a percentage value used by the
process PID controller.
-1000 … 1000% Maximum value in percent of the set analogue input signal range. The -10000 …
equation below instructs how to calculate the value when analogue input AI1 is 10000
used as a variable ACT1.
AI1max - 13.01
ACT1 MAXIMUM = · 100%
13.02 - 13.01
AI1max The voltage value received from the measuring device when
the measured process actual value is at the desired maximum
level.
13.01 AI1 minimum (parameter setting)
13.02 AI1 maximum (parameter setting)
-sclAI5
-maxAI5 -minAI5 minAI5 maxAI5
Start/Stop
Motor magnetised
Actual speed
1 = brake close speed
2 = brake close delay
3 = extended run time
1
t
2 3
42.10 LOW REF BRK HOLD Activates a brake hold function and defines the hold delay for it. The function
stabilises the operation of the brake control application when the motor
operates near zero speed and there is no measured speed feedback available
(pulse encoder).
0.0 … 60.0 s 0.0 s = inactive. 100 = 1 s
0.1 s … 60.0 s = active. When the absolute value of the motor speed reference
falls below the brake close speed:
- The brake hold delay counter starts.
- The brake is closed according to normal stop routine of the brake control
function.
During the delay, the function keeps the brake closed despite of the speed
reference value and the value of start command. When the set delay has
passed, the normal operation resumes.
45 ENERGY OPT Energy optimization settings
45.02 ENERGY TARIFF1 Price of energy per kWh. Used for reference when savings are calculated. See
parameters 01.46 SAVED KWH, 01.48 SAVED AMOUNT and 01.50 SAVED
CO2.
0.0000…1024.0000 Price of energy per kWh. 1 = 0.001
45.06 E TARIFF UNIT Specifies the currency used for the savings calculation.
LOCAL The currency is determined by the setting of parameter 99.01 Language. 0
EUR Euro 1
USD US dollar 2
45.08 PUMP REF POWER Pump power when connected directly to supply. Used for reference when
energy savings are calculated. See parameters 01.46 SAVED KWH, 01.48
SAVED AMOUNT and 01.50 SAVED CO2.
No Drooping
100% } Par. 60.06 DROOP RATE
Drooping
where Ioverload is the motor overload and Iuser curve is the current defined by the
user load curve at the nominal frequency. User load curve is defined by
parameters 72.02...72.17.
Example: Motor overload capacity is 150% of the nominal current for
10 s / 10 min and the continuous load capacity is 80% at the nominal
frequency:
2 2 2
72.18 LOAD CURRENT LIMIT = 150 – 80 + 100 = 162%
100...800% Value in percent of the nominal motor current (99.06 MOTOR NOM 10 = 1%
CURRENT)
84.02 FAULTED PAR Points out the faulted parameter in the Adaptive Program. -
84.05 BLOCK1 Selects the function block for Block Parameter Set 1. See the Adaptive
Program Application Guide [3AFE64527274 (English)].
ABS 11
ADD 10
AND 2
BITWISE 26
COMPARE 16
COUNT 21
DPOT 23
EVENT 20
S
P P Q
cos ( 30 ) = ---- = ------------------------
S 2 2 30°
P +Q
P
Positive reference 30° denotes capacitive load.
Negative reference 30° denotes inductive load.
P = signal 01.09 POWER value
Parameter 24.03 values are converter to degrees by the line-side converter
application program: -3000...30000 = -30°...30°. Value -10000/10000 equals to
-30°/30°, since the range is limited to -3000/3000.
-10000...10000 Reference value. See par.
description.
95.07 LCU DC REF Defines the intermediate circuit DC voltage reference for the line-side
converter (i.e. IGBT supply unit). This reference is written into line-side
converter parameter 23.01 DC VOLT REF. For more information, see IGBT
Supply Control Program 7.x Firmware manual [3AFE68315735 (English)].
0...1100 V Voltage 1=1V
95.08 LCU PAR1 SEL Selects the line-side converter address from which the actual signal 09.12 LCU
ACT SIGNAL1 is read from.
0…9999 Line-side converter parameter index. Default value 106 = line-side converter 0…9999
parameter 01.06 LINE CURRENT. For more information, see IGBT Supply
Control Program 7.x Firmware manual [3AFE68315735 (English)].
95.09 LCU PAR2 SEL Selects the line-side converter address from which the actual signal 09.13 LCU
ACT SIGNAL2 is read from.
0…9999 Line-side converter parameter index. Default value 110 = line side converter 0…9999
parameter 01.10 DC VOLTAGE. For more information, see IGBT Supply
Control Program 7.x Firmware manual [3AFE68315735 (English)].
95.10 TEMP INV AMBIENT Defines the ambient temperature for the Enhanced drive temperature
monitoring function. See Enhanced drive temperature monitoring for ACS800,
frame sizes R7 and R8 on page 67.
Note: If ambient temperature exceeds 40°C, the drive load capacity
decreases. See the derating instructions in the appropriate hardware manual.
20...50°C Temperature 10 = 1°C
AI3
Dataset 121 (CH1) Dataset 121 (CH0)
MCW (fixed) PERCENT +
MCW PARAM 24.02
kVAr
95.06 LCU Q PW REF Q-REF(fixed) 24.02 +
PHI
95.07 LCU DC REF DC REF(fixed) COSPHI
AI2 23.01
MCW = Main Control Word
MSW = Main Status Word AI3
FIELDBUS
95.12 LCU RUN PTR Selection of run command for line-side converter. When 95.11 SUPPLY CTRL
MODE is set to LINE CONV, starting of modulation can be assigned freely to a
parameter or signal using bit pointer.
Note: This parameter is available in AS7R firmware version only.
-255.255.31… Parameter index or a constant value: -
+255.255.31 / C.- - Parameter pointer: Inversion, group, index and bit fields. The bit number is
32768…C.32767 effective only for blocks handling boolean inputs.
- Constant value: Inversion and constant fields. Inversion field must have value
C to enable the constant setting.
96 EXTERNAL AO Output signal selection and processing for the analogue extension module
(optional).
The parameters are visible only when the module is installed and activated by
parameter 98.06.
96.01 EXT AO1 Selects the signal connected to analogue output AO1 of the analogue I/O
extension module.
NOT USED See parameter 15.01. 1
P SPEED See parameter 15.01. 2
SPEED See parameter 15.01. 3
FREQUENCY See parameter 15.01. 4
CURRENT See parameter 15.01. 5
TORQUE See parameter 15.01. 6
Before setting the drive parameters, ensure the module hardware settings are
appropriate for the motor temperature measurement:
1. The module node number is 9.
2. The input signal type selections are the following:
- for one Pt 100 sensor measurement, set the range to 0 … 2 V.
- for two to three Pt 100 sensors or one to three PTC sensors, set the range to
0 … 10 V.
3. The operation mode selection is unipolar.
NAIO Communication active. Module type: NAIO. Connection interface: Fibre optic 1
DDCS link.
Note: Make the module hardware settings as described above. For
instructions, see the NTAC-0x/NDIO-0x/NAIO-0x Module Installation and Start-
up Guide [3AFY58919730 (English)].
NO Inactive 2
RAIO-SLOT1 Communication active. Module type: RAIO. Connection interface: Option slot 1 3
of the drive.
Note: Make the module hardware settings as described above. The node
number is not required. For directions, see the RAIO Module User’s Manual
[3AFE64484567 (English)].
RAIO-SLOT2 Communication active. Module type: RAIO. Connection interface: Option slot 2 4
of the drive.
Note: Make the module hardware settings as described above. The node
number is not required. For directions, see the RAIO Module User’s Manual
[3AFE64484567 (English)].
Fieldbus control
Chapter overview
The chapter describes how the drive can be controlled by external devices over
a communication network.
System overview
The drive can be connected to an external control system – usually a fieldbus
controller – via an adapter module. The drive can be set to receive all of its control
information through the external control interface, or the control can be distributed
between the external control interface and other available sources, for example
digital and analogue inputs. The following diagram shows the control interfaces and
I/O connections of the drive.
Fieldbus
controller
Fieldbus
(* (*
ACS800 Other
devices
Advant
Fieldbus adapter Controller controller
Rxxx (e.g. AC 800M,
Modbus AC 80)
Slot 1
RMIO board
(*
RMBA-01 adapter
std. Modbus link
Slot 1 or 2 I/O adapter
RTAC/RDIO/RAIO
CH1
RDCO comm. AIMA-01 I/O
module (DDCS) adapter module
or
Data Flow
Control Word (CW)
References
Process I/O (cyclic)
Status Word (SW)
Actual values
(*
Either an Rxxx or Nxxx, and an RMBA-01 adapter can be connected to the drive simultaneously.
Fieldbus control
192
ACS800
RMIO board
RPBA-01 adapter
PROFIBUS-DP link
Slot 1
RMBA-01 adapter
std. Modbus link
Slot 2
The control (i.e. the Main Reference data set, see section The fieldbus control
interface on page 202) is activated by setting parameter 98.02 to FIELDBUS or
STD MODBUS.
In case there is a communication problem with one fieldbus, the control can be
switched to the other fieldbus. Switching between the buses can be controlled
e.g. with adaptive programming. Parameters and signals can be read by both
fieldbuses, but simultaneous cyclical writing to the same parameter is forbidden.
Fieldbus control
193
COMMUNICATION INITIALISATION
98.07 ABB DRIVES ABB DRIVES Selects the communication profile used by the
GENERIC GENERIC or drive. See section Communication profiles on page
CSA 2.8/3.0 CSA 2.8/3.0 210.
51.02 (FIELDBUS These parameters are adapter module-specific. For more information, see the module manual.
PARAMETER 2) Note that not all of these parameters are necessarily visible.
•••
51.26 (FIELDBUS
PARAMETER 26)
51.27 FBA PAR (0) DONE – Validates any changed adapter module
REFRESH* (1) REFRESH configuration parameter settings. After refreshing,
the value reverts automatically to DONE.
51.28 FILE CPI xyz (binary coded – Displays the required CPI firmware revision of the
FW REV* decimal fieldbus adapter as defined in the configuration file
stored in the memory of the drive. The CPI firmware
version of the fieldbus adapter (refer to par. 51.32)
must contain the same or a later CPI version to be
compatible. x = major revision number; y = minor
revision number; z = correction number. Example:
107 = revision 1.07.
Fieldbus control
194
51.29 FILE xyz (binary coded – Displays the fieldbus adapter module configuration
CONFIG ID* decimal) file identification stored in the memory of the drive.
This information is drive application program-
dependent.
51.30 FILE xyz (binary coded – Displays the fieldbus adapter module configuration
CONFIG REV* decimal) file revision stored in the memory of the drive.
x = major revision number; y = minor revision
number; z = correction number. Example: 1 =
revision 0.01.
51.31 FBA (0) IDLE – Displays the status of the adapter module.
STATUS* (1) EXEC. INIT IDLE = Adapter not configured.
(2) TIME OUT
EXEC. INIT = Adapter initialising.
(3) CONFIG
ERROR TIME OUT = A timeout has occurred in the
(4) OFF-LINE communication between the adapter and the drive.
(5) ON-LINE CONFIG ERROR = Adapter configuration error.
(6) RESET The major or minor revision code of the CPI
program revision in the drive is not the revision
required by the module (refer to par. 51.32) or
configuration file upload has failed more than five
times.
OFF-LINE = Adapter is off-line.
ON-LINE = Adapter is on-line.
RESET = Adapter performing a hardware reset.
51.32 FBA CPI FW – – Displays the CPI program revision of the module
REV* inserted in slot 1. x = major revision number;
y = minor revision number; z = correction number.
Example: 107 = revision 1.07.
*Parameters 51.27 to 51.33 are only visible when type Rxxx fieldbus adapter is installed.
After the module configuration parameters in group 51 have been set, the drive
control parameters (section Drive control parameters on page 199) must be checked
and adjusted where necessary.
The new settings will take effect when the drive is next powered up, or when
parameter 51.27 is activated.
Fieldbus control
195
COMMUNICATION INITIALISATION
98.07 ABB DRIVES ABB DRIVES Selects the communication profile used by the
GENERIC drive. See section Communication profiles on
CSA 2.8/3.0 page 210.
COMMUNICATION PARAMETERS
After the communication parameters in group 52 have been set, the drive control
parameters (section Drive control parameters on page 199) must be checked and
adjusted where necessary.
Fieldbus control
196
Modbus addressing
In the Modbus controller memory, the Control Word, the Status Word, the
references, and the actual values are mapped as follows:
Data from fieldbus controller to drive Data from drive to fieldbus controller
Fieldbus control
197
TB811 × ×
TB810 ×
If branching unit NDBU-85/95 is used with CI810A, TB810 Optical ModuleBus Port
Interface must be used.
Fieldbus control
198
The following table lists the parameters which need to be defined when setting up
communication between the drive and Advant controller.
Parameter Alternative settings Setting for control through Function/Information
CH0
COMMUNICATION INITIALISATION
98.07 ABB DRIVES ABB DRIVES Selects the communication profile used by
GENERIC the drive. See section Communication
CSA 2.8/3.0 profiles on page 210.
70.01 0-254 AC 800M ModuleBus 1...125 Defines the node address for DDCS
AC 80 ModuleBus 17-125 channel CH0.
FCI (CI810A) 17-125
After the communication initialisation parameters have been set, the drive control
parameters (section Drive control parameters on page 199) must be checked and
adjusted where necessary.
In an Optical ModuleBus connection, channel 0 address (parameter 70.01) is
calculated from the value of the POSITION terminal in the appropriate database
element (for the AC 80, DRISTD) as follows:
1. Multiply the hundreds of the value of POSITION by 16.
2. Add the tens and ones of the value of POSITION to the result.
For example, if the POSITION terminal of the DRISTD database element has the
value of 110 (the tenth drive on the Optical ModuleBus ring), parameter 70.01 must
be set to 16 × 1 + 10 = 26.
Fieldbus control
199
10.01 COMM.CW Enables the fieldbus Control Word (except 03.01 Main Control Word bit 11)
when EXT1 is selected as the active control location. See also par. 10.07.
10.02 COMM.CW Enables the fieldbus Control Word (except 03.01 Main Control Word bit 11)
when EXT2 is selected as the active control location.
10.03 FORWARD Enables rotation direction control as defined by parameters 10.01 and
REVERSE or 10.02. The direction control is explained in section Reference handling on
REQUEST page 204.
10.07 0 or 1 Setting the value to 1 overrides the setting of par. 10.01 so that the fieldbus
Control Word (except 03.01 Main Control Word bit 11) is enabled when
EXT1 is selected as the active control location.
Note 1: Only visible with the Generic Drive communication profile selected
(see par. 98.07).
Note 2: Setting not saved into permanent memory.
10.08 0 or 1 Setting the value to 1 overrides the setting of par. 11.03 so that Fieldbus
reference REF1 is used when EXT1 is selected as the active control
location.
Note 1: Only visible with the Generic Drive communication profile selected
(see par. 98.07).
Note 2: Setting not saved into permanent memory.
11.02 COMM.CW Enables EXT1/EXT2 selection by fieldbus Control Word bit 11 EXT CTRL
LOC.
11.03 COMM.REF1 Fieldbus reference REF1 is used when EXT1 is selected as the active
FAST COMM control location. See section References on page 203 for information on
COM.REF1+AI1 the alternative settings.
COM.REF1+AI5
COM.REF1*AI1 or
COM.REF1*AI5
11.06 COMM.REF2 Fieldbus reference REF2 is used when EXT2 is selected as the active
FAST COMM control location. See section References on page 203 for information on
COM.REF2+AI1 the alternative settings.
COM.REF2+AI5
COM.REF2*AI1 or
COM.REF2*AI5
Fieldbus control
200
14.01 COM.REF3 Enables relay output RO1 control by fieldbus reference REF3 bit 13.
14.02 COM.REF3 Enables relay output RO2 control by fieldbus reference REF3 bit 14.
14.03 COM.REF3 Enables relay output RO3 control by fieldbus reference REF3 bit 15.
15.01 COMM.REF4 Directs the contents of fieldbus reference REF4 to analogue output AO1.
Scaling: 20000 = 20 mA
15.06 COMM.REF5 Directs the contents of fieldbus reference REF5 to analogue output AO2.
Scaling: 20000 = 20 mA.
16.01 COMM.CW Enables the control of the Run Enable signal through fieldbus 03.01 Main
Control Word bit 3.
Note: Must be set to YES when the Generic Drive communication profile is
selected (see par. 98.07).
16.04 COMM.CW Enables fault reset through fieldbus 03.01 Main Control Word bit 7.
Note: Reset through fieldbus Control Word (03.01 bit 7) is enabled
automatically and it is independent of parameter 16.04 setting if parameter
10.01 or 10.02 is set to COMM.CW.
16.07 DONE; SAVE Saves parameter value changes (including those made through fieldbus
control) to permanent memory.
30.19 0.1 … 60.0 s Defines the time between Main Reference data set loss detection and the
action selected with parameter 30.18.
30.20 ZERO Determines the state in which relay outputs RO1 to RO3 and analogue
LAST VALUE outputs AO1 and AO2 are left upon loss of the Auxiliary Reference data set.
30.21 0.0 … 60.0 s Defines the time between Auxiliary Reference data set loss detection and
the action selected with parameter 30.18.
Note: This supervision function is disabled if this parameter, or parameters
90.01, 90.02 and 90.03 are set to 0.
90.01 0 … 8999 Defines the drive parameter into which the value of fieldbus reference
REF3 is written.
Format: xxyy, where xx = parameter group (10 to 89), yy = parameter
Index. E.g. 3001 = parameter 30.01.
Fieldbus control
201
90.02 0 … 8999 Defines the drive parameter into which the value of fieldbus reference
REF4 is written.
Format: see parameter 90.01.
90.03 0 … 8999 Defines the drive parameter into which the value of fieldbus reference
REF5 is written.
Format: see parameter 90.01.
90.04 1 (Fieldbus Control) or If 98.02 is set to CUSTOMISED, this parameter selects the source from
81 (Standard Modbus which the drive reads the Main Reference data set (comprising the fieldbus
Control) Control Word, fieldbus reference REF1, and fieldbus reference REF2).
90.05 3 (Fieldbus Control) or If 98.02 is set to CUSTOMISED, this parameter selects the source from
83 (Standard Modbus which the drive reads the Auxiliary Reference data set (comprising fieldbus
Control) references REF3, REF4 and REF5).
92.01 302 (Fixed) The Status Word is transmitted to as the first word of the Main Actual Signal
data set.
92.02 0 … 9999 Selects the Actual signal or parameter value to be transmitted as the
second word (ACT1) of the Main Actual Signal data set.
Format: (x)xyy, where (x)x = actual signal group or parameter group, yy =
actual signal or parameter index. E.g. 103 = actual signal 1.03
FREQUENCY; 2202 = parameter 22.02 ACCEL TIME 1.
Note: With the Generic Drive communication profile active (par. 98.07 =
GENERIC), this parameter is fixed to 102 (actual signal 1.02 SPEED – in
DTC motor control mode) or 103 (1.03 FREQUENCY – in Scalar mode).
92.03 0 … 9999 Selects the actual signal or parameter value to be transmitted as the third
word (ACT2) of the Main Actual Signal data set.
Format: see parameter 92.02.
92.04 0 … 9999 Selects the actual signal or parameter value to be transmitted as the first
word (ACT3) of the Auxiliary Actual Signal data set.
Format: see parameter 92.02.
92.05 0 … 9999 Selects the actual signal or parameter value to be transmitted as the
second word (ACT4) of the Auxiliary Actual Signal data set.
Format: see parameter 92.02.
92.06 0 … 9999 Selects the actual signal or parameter value to be transmitted as the third
word (ACT5) of the Auxiliary Actual Signal data set.
Format: see parameter 92.02.
92.07 -255.255.31…+255.255.31 Selects the address from which the 03.02 Main Status Word bit 10 is read
/ C.-32768 … C.32767 from.
92.08 -255.255.31…+255.255.31 Selects the address from which the 03.02 Main Status Word bit 13 is read
/ C.-32768 … C.32767 from.
92.09 -255.255.31…+255.255.31 Selects the address from which the 03.02 Main Status Word bit 14 is read
/ C.-32768 … C.32767 from.
Fieldbus control
202
*Index Main Reference data set DS1 *Index Main Actual Signal data set DS2
1 1st word Control Word (Fixed) 4 1st word Status Word (Fixed)
*Index Auxiliary Reference data set DS3 *Index Aux. Actual Signal data set DS4
7 1st word Reference 3 Par. 90.01 10 1st word Actual 3 Par. 92.04
8 2nd word Reference 4 Par. 90.02 11 2nd word Actual 4 Par. 92.05
9 3rd word Reference 5 Par. 90.03 12 3rd word Actual 5 Par. 92.06
*The index number is required when data word allocation to process data is defined
via the fieldbus parameters at group 51. This function is dependent on the type of the
fieldbus adapter.
**With the Generic Drive communication profile active, Actual 1 is fixed to actual
signal 01.02 SPEED (in DTC motor control mode) or 01.03 FREQUENCY (in Scalar
mode).
The update time for the Main Reference and Main Actual Signal data sets is 6
milliseconds; for the Auxiliary Reference and Auxiliary Actual Signal data sets, it is
100 milliseconds.
Fieldbus control
203
References
References (REF) are 16-bit signed integers. A negative reference (indicating
reversed direction of rotation) is formed by calculating the two’s complement from
the corresponding positive reference value.
Fieldbus reference selection and correction
Fieldbus reference (called COM.REF in signal selection contexts) is selected by
setting a Reference selection parameter – 11.03 or 11.06 – to COMM.REFx, FAST
COMM, COM.REFx+AI1, COM.REFx+AI5, COM.REFx*AI1 or COM.REFx*AI5.
(With Generic Drive communication profile, fieldbus reference is also selected when
par. 10.08 is set to 1.) The latter four selections enable correction of the fieldbus
reference using analogue inputs as shown below. (An optional RAIO-01 Analogue
I/O Extension Module is required for use of Analogue input AI5).
COMM.REF1 (in 11.03) or COMM.REF2 (in 11.06)
The fieldbus reference is forwarded as such without correction.
FAST COMM
The fieldbus reference is forwarded as such without correction. The reference is
read every 2 milliseconds if either of the following conditions is met:
• Control location is EXT1, par. 99.04 MOTOR CTRL MODE is DTC, and par. 40.14
TRIM MODE is OFF
• Control location is EXT2, par. 99.04 MOTOR CTRL MODE is DTC, par. 40.14
TRIM MODE is OFF, and a torque reference is used.
In any other event, the fieldbus reference is read every 6 milliseconds.
Note: The FAST COMM selection disables the critical speed function.
Fieldbus control
204
COM.REFx+AI1
Fieldbus Reference
COM.REFx+AI5 Correction Coefficient
100%
COM.REFx*AI1
COM.REFx*AI5 Fieldbus Reference
Correction Coefficient
100%
50%
0%
0 5V 10 V AI1/AI5 Input
Voltage
Reference handling
The control of rotation direction is configured for each control location (EXT1 and
EXT2) using the parameters in group 10. Fieldbus references are bipolar, i.e. they
can be negative or positive. The following diagrams illustrate how group 10
parameters and the sign of the fieldbus reference interact to produce the reference
REF1/REF2.
Notes:
• With the ABB Drives communication profile, 100% reference is defined by
parameters 11.05 (REF1) and 11.08 (REF2).
• With the Generic Drive communication profile, 100% reference is defined by
parameter 99.08 in DTC motor control mode (REF1), or 99.07 in scalar control
mode (REF1), and by parameter 11.08 (REF2).
• External reference scaling parameters 11.04 and 11.07 are also in effect.
For information on the scaling of the fieldbus reference, see section Fieldbus
reference scaling on page 214 (for ABB Drives profile) or Fieldbus reference scaling
on page 217 (for Generic Drive profile).
Fieldbus control
205
Fieldbus Fieldbus
Ref. 1/2 Ref. 1/2
-100% 100% -100% 100%
-163% 163% -163% 163%
–[Max.Ref.] –[Max.Ref.]
–[Max.Ref.] –[Max.Ref.]
Max.Ref. Max.Ref.
-163%
Fieldbus -100% Fieldbus
Ref. 1/2 Ref. 1/2
100% -100% 100%
163% -163% 163%
–[Max.Ref.] –[Max.Ref.]
Direction Command:
REVERSE
Actual Values
Actual Values (ACT) are 16-bit words containing information on selected operations
of the drive. The functions to be monitored are selected with the parameters in group
92. The scaling of the integers sent to the master as Actual Values depends on the
selected function; please refer to chapter Actual signals and parameters.
Fieldbus control
Block diagram: Control data input from fieldbus when a type Rxxx
206
fieldbus adapter is used DI1 11.02
•
•
COMM.CW •
10.01 03.01
DI1 MAIN CW
Fieldbus control
30.18 COMM FAULT FUNC
DATA •
Fieldbus Words 1 … n ** 30.19 MAIN REF DS T-OUT •
SET COMM.CW •
Adapter TABLE
Slot1 10.02
Word 1 NO MAIN
1 AI1
(Control word) DS 1 FIELD- REFERENCE
2 •
Word 2 BUS DATA SET • 01.11
3 COMM.REF •
(Speed/freq ref.*) 4 ADVANT EXT REF1
DS CW
Word 3 5 DS 2 STD 11.03
PAR 6 MODBUS REF1
3 AI1
… 7 CUSTOM- REF2 •
8 DS 3 ISED • 01.12
DS COMM.REF •
Word n 9 EXT REF2
PAR 10 98.02 11.06
n
11 DS 4
12
13
14 DS 5 PARAMETER
15 Bits
13…15 90.01 TABLE
90.03 •••
30.18 COMM FAULT FUNC
30.20 COMM FLT RO/AO Analogue Output
30.21 AUX REF DS T-OUT AO2 (see 15.06)
•••
DATA SET
TABLE
•••
10.01 92.04 Fieldbus specific selectors
in Group 51 ***
••• AUXILIARY Addresses for words 3 … n in
ACTUAL SIGNAL format xxyy
DATA SET xx Address
••• 92.05 00 yy = word no. in data set
ACT3
table
ACT4
01 … xx = par. group
ACT5
••• 99 yy = par. index
in parameter table
99.99 92.06
* Fixed to 03.02 MAIN STATUS WORD (bits 10, 13 and 14 are programmable).
** Fixed to 01.02 SPEED (DTC control) or 01.03 FREQUENCY (Scalar control) when Generic communication profile is used.
*** See the fieldbus adapter user’s manual for more information.
Fieldbus control
207
Block diagram: Control data input from fieldbus when a type Nxxx
208
fieldbus adapter is used
DI1 11.02
•
DATA 30.18 COMM FAULT FUNC •
COMM.CW •
Fieldbus control
SET 30.19 MAIN REF DS T-OUT
TABLE 10.01 03.01
NO DI1 MAIN CW
3 words FIELD- MAIN •
DS 1 •
Fieldbus (6 bytes) BUS REFERENCE COMM.CW •
Adapter ADVANT DATA SET
10.02
(CH0) DS 2 STD
MODBUS
CW AI1
1 REF1 •
• CUSTOM- • 01.11
3 words DS 3 • ISED COMM.REF •
• REF2 EXT REF1
(6 bytes)
255 11.03
90.04 98.02
DS 4 AI1
•
• 01.12
COMM.REF •
Modbus EXT REF2
•••
Controller 11.06
40001 3 words
40002 DS 81
(6 bytes)
40003 Standard NO
Modbus FIELD-
DS 82 Bits PARAMETER
Link BUS
13…15 90.01 TABLE
(RMBA) ADVANT
40007 (Slot 1/2) AUXILIARY Relay Outputs
3 words STD
40008 DS 83 REFERENCE (see 14.01…14.03) 10.01
(6 bytes) MODBUS
40009 DATA SET
1 CUSTOM-
•
DS 84 • ISED REF3
• 10.02
255
98.02 REF4
90.05
••• REF5
90.02 •••
Analogue Output
AO1 (see 15.01) 89.99
30.18 COMM FAULT FUNC
30.20 COMM FLT RO/AO
30.21 AUX REF DS T-OUT
•••
90.03
Analogue Output
AO2 (see 15.06)
Block Diagram: Actual value selection for fieldbus when a type Nxxx
fieldbus adapter is used
DATA SET
TABLE
ACTUAL SIGNAL/
PARAMETER 92.01* DS 1
TABLE
MAIN 3 words
DS 2
1.01 (6 bytes) Fieldbus
ACTUAL SIGNAL
DATA SET Adapter
92.02 STATUS WORD* DS 3 (CH0)
1.02
ACT1**
ACT2 3 words
DS 4
••• (6 bytes)
92.03 •••
3.99
Modbus
DS 81 Controller
•••
40004
3 words
DS 82 40005
10.01 (6 bytes) Standard
92.04 40006
Modbus
DS 83 Link
••• AUXILIARY
ACTUAL SIGNAL 40010
DATA SET 3 words
DS 84 40011
99.99 (6 bytes)
92.05 40012
ACT3
ACT4
•••
ACT5
92.06
* Fixed to 03.02 MAIN STATUS WORD (bits 10, 13 and 14 are programmable).
** Fixed to 01.02 SPEED (DTC motor control) or 0103 FREQUENCY (Scalar control) when Generic communication profile is used.
Fieldbus control
209
210
Communication profiles
The ACS800 supports three communication profiles:
• ABB Drives communication profile
• Generic Drive communication profile.
• CSA 2.8/3.0 communication profile.
The ABB Drives communication profile should be selected with type Nxxx fieldbus
adapter modules, and when the manufacturer-specific mode is selected (via the
PLC) with type Rxxx fieldbus adapter modules.
The Generic Drive profile is supported by type Rxxx fieldbus adapter modules only.
The CSA 2.8/3.0 communication profile can be selected for backward compatibility
with Application Program versions 2.8 and 3.0. This eliminates the need for
reprogramming the PLC when drives with the above-mentioned program versions
are replaced.
Fieldbus control
211
Fieldbus control
212
Fieldbus control
213
SWITCH-ON
MAINS OFF INHIBITED (SW Bit6=1)
ABB Drives
Power ON (CW Bit0=0)
Communication
NOT READY Profile
TO SWITCH ON (SW Bit0=0)
A B C D
CW = Control Word
SW = Status Word
n = Speed
(CW=xxxx x1xx xxxx x110)
I = Input Current
(CW Bit3=0)
RFG = Ramp Function Generator
READY TO f = Frequency
OPERATION SWITCH ON (SW Bit0=1)
INHIBITED (SW Bit2=0)
from any state
operation
(CW=xxxx x1xx xxxx x111)
inhibited
Fault
READY TO
FAULT
OPERATE (SW Bit1=1) (SW Bit3=1)
n(f)=0 / I=0
(CW Bit4=0)
OPERATION
C D
ENABLED (SW Bit2=1)
A
(CW Bit5=0) (CW=xxxx x1xx xxx1 1111)
D RFG: OUTPUT
ENABLED
B
(CW Bit6=0) (CW=xxxx x1xx xx11 1111)
RFG: ACCELERATOR
ENABLED
C
(CW=xxxx x1xx x111 1111)
OPERATING
(SW Bit8=1)
D
Fieldbus control
214
REF1 (any) -32768 ... Speed or Frequency -20000 = -[par. 11.05] Final reference limited by
32767 (not with -1 = -[par. 11.04] 20.01/20.02 [speed] or
FAST COMM) 20.07/20.08 [frequency].
0 = [par. 11.04]
20000 = [par. 11.05]
REF2 FACTORY, -32768 ... Speed or Freq. (not -20000 = -[par. 11.08] Final reference limited by
HAND/AUTO, 32767 with FAST COMM) -1 = -[par. 11.07] 20.01/20.02 [speed] or
or SEQ CTRL 0 = [par. 11.07] 20.07/20.08 [frequency].
20000 = [par. 11.08]
T CTRL or -32768 ... Torque (not with -10000 = -[par. 11.08] Final reference limited by
M/F (optional) 32767 FAST COMM) -1 = -[par. 11.07] par. 20.04.
0 = [par. 11.07]
10000 = [par. 11.08]
Fieldbus control
215
Fieldbus control
216
Fieldbus control
217
REF2 FACTORY, -32768... Speed or Freq. -20000 = -[par. 11.08] 0=0 Final reference
HAND/AUT 32767 (not with -1 = -[par. 11.07] 20000 = [par. limited by
or SEQ FAST COMM) 0 = [par. 11.07] 99.08 (DTC) / 20.01/20.02
CTRL 20000 = [par. 11.08] 99.07 (scalar)]** [speed] or
20.07/20.08
[frequency]
* With DTC the filter time of the actual speed value can be adjusted using parameter 34.04.
** Note: The maximum reference value is 163% (i.e. 163% = 1.63 · value of parameter 99.08/99.07 value).
Fieldbus control
218
The reference and actual scaling is equal to that of the ABB Drives profile.
Fieldbus control
219
0 Reserved
1 OUT OF WINDOW Speed difference is out of the window (in speed control)*.
2 Reserved
4 Reserved
6 1 START NOT Drive has not been started after changing the motor
DONE parameters in group 99.
9 LIMITING Control at a limit. See actual signal 3.04 LIMIT WORD 1 below.
11 ZERO SPEED Absolute value of motor actual speed is below zero speed limit
(4% of synchronous speed).
14 … 15 Reserved
Fieldbus control
220
0 SHORT CIRC For the possible causes and remedies, see chapter Fault
tracing.
1 OVERCURRENT
2 DC OVERVOLT
3 ACS800 TEMP
4 EARTH FAULT
5 THERMISTOR
6 MOTOR TEMP
8 UNDERLOAD For the possible causes and remedies, see chapter Fault
tracing.
9 OVERFREQ
10 … 15 Reserved
Fieldbus control
221
0 SUPPLY PHASE For the possible causes and remedies, see chapter Fault
tracing.
1 NO MOT DATA
2 DC UNDERVOLT
3 Reserved
4 RUN ENABLE For the possible causes and remedies, see chapter Fault
tracing.
5 ENCODER ERR
6 I/O COMM
7 CTRL B TEMP
8 EXTERNAL FLT
9 OVER SWFREQ
11 PPCC LINK
12 COMM MODULE
13 PANEL LOSS
14 MOTOR STALL
15 MOTOR PHASE
Fieldbus control
222
15 Reserved
0 START INHIBIT For the possible causes and remedies, see chapter Fault
tracing.
1 Reserved
2 THERMISTOR For the possible causes and remedies, see chapter Fault
tracing.
3 MOTOR TEMP
4 ACS800 TEMP
5 ENCODER ERR
6 T MEAS ALM
7 … 11 Reserved
12 COMM MODULE For the possible causes and remedies, see chapter Fault
tracing.
13 Reserved
14 EARTH FAULT For the possible causes and remedies, see chapter Fault
tracing.
15 Reserved
Fieldbus control
223
0 Reserved
1 UNDERLOAD For the possible causes and remedies, see chapter Fault
tracing.
2, 3 Reserved
4 ENCODER For the possible causes and remedies, see chapter Fault
tracing.
5, 6 Reserved
9 MOTOR STALL For the possible causes and remedies, see chapter Fault
tracing.
10 AI < MIN FUNC
11, 12 Reserved
13 PANEL LOSS For the possible causes and remedies, see chapter Fault
tracing.
14, 15 Reserved
6 OPEN BRAKE The Open Brake command is ON. See group 42 BRAKE
CONTROL.
8 STOP DI STATUS The state of the interlock input on the RMIO board.
12…15 Reserved
Fieldbus control
224
2 CURRENT LIM Motor current has exceeded or fallen below the set
supervision limit. See group 32 SUPERVISION.
5 TORQUE 1 LIM The motor torque has exceeded or fallen below the
TORQUE1 supervision limit. See group 32
SUPERVISION.
6 TORQUE 2 LIM The motor torque has exceeded or fallen below the
TORQUE2 supervision limit. See group 32
SUPERVISION.
7 ACT 1 LIM PID controller actual value 1 has exceeded or fallen below
the set supervision limit. See group 32 SUPERVISION.
8 ACT 2 LIM PID controller actual value 2 has exceeded or fallen below
the set supervision limit. See group 32 SUPERVISION.
10 … Reserved
15
1 MOTOR 1 TEMP For the possible causes and remedies, see chapter Fault
tracing.
2 MOTOR 2 TEMP
3 BRAKE ACKN
4 … 15 Reserved
Fieldbus control
225
1 MOTOR 1 TEMP For the possible causes and remedies, see chapter Fault
tracing.
2 MOTOR 2 TEMP
3 BRAKE ACKN
4 SLEEP MODE
6 … 15 Reserved
0 BR BROKEN For the possible causes and remedies, see chapter Fault
tracing.
1 BR WIRING
2 BC SHORT CIR
3 BR OVERHEAT
4 BC OVERHEAT
5 IN CHOKE TEMP
6 PP OVERLOAD
7 INV DISABLED
8 TEMP DIF
10 INT CONFIG
11 USER L CURVE
12 Reserved
13 INV OVERTEMP For the possible causes and remedies, see chapter Fault
tracing.
14...15 Reserved
Fieldbus control
226
0 REPLACE FAN For the possible causes and remedies, see chapter Fault
tracing.
1 SYNCRO SPEED
2 BR OVERHEAT
3 BC OVERHEAT
4 IN CHOKE TEMP
5 PP OVERLOAD
6 INV DISABLED
7 CUR UNBAL
9 DC BUS LIM
13 USER L CURVE
14 Reserved
15 BATT FAILURE For the possible causes and remedies, see chapter Fault
tracing.
5 … 15 Reserved
Fieldbus control
227
2 INT LOW FREQ Current limit at high IGBT temperature with low output
frequency (<10 Hz). Temperature model is not active.*
8 OVERLOAD CUR Maximum inverter overload current limit. See par. 20.03.
11...15 Reserved
0 INV OVERTEMP For the possible causes and remedies, see chapter Fault
tracing.
1...2 Reserved
3 ENC CABLE For the possible causes and remedies, see chapter Fault
tracing.
4…15 Reserved
Fieldbus control
228
1 EMSTOP OFF2 CMD DI1 of emergency stop module. See 03.01 MAIN
CONTROL WORD bit1 OFF2 CONTROL.
2 EMSTOP OFF3 CMD DI2 of emergency stop module. See 03.01 MAIN
CONTROL WORD bit2 OFF3 CONTROL.
4 EMSTOP OFF3 STATUS RO1 of emergency stop module. See 03.02 MAIN STATUS
WORD bit5 OFF_3_STA. Bit inverted.
5 EMSTOP TRIP STATUS RO2 of emergency stop module. See 03.02 MAIN STATUS
WORD bit3 TRIPPED.
7 STEPUP CHOKE FLT DI1 of Step-Up module. For the possible causes and
CMD remedies, see chapter Fault tracing: CHOKE OTEMP
(FF82).
8 STEPUP FAN ALM CMD DI2 of Step-Up module. For possible causes and remedies,
see chapter Fault tracing: FAN OTEMP (FF83).
11 STEPUP TRIP STATUS RO2 of Step-Up module. See 03.02 MAIN STATUS WORD
bit3 TRIPPED.
12-15 Reserved
0…1 Reserved
2 ENC CABLE For possible causes and remedies, see chapter Fault
tracing.
3…15 Reserved
Fieldbus control
229
12...14 Reserved
Fieldbus control
230
U V W
1 2 3
INT INT INT
U V W U V W U V W ...
6...15 Reserved
Fieldbus control
231
Fault tracing
Chapter overview
The chapter lists all warning and fault messages including the possible cause and
corrective actions.
Safety
WARNING! Only qualified electricians are allowed to maintain the drive. The Safety
Instructions on the first pages of the appropriate hardware manual must be read
before you start working with the drive.
How to reset
The drive can be reset either by pressing the keypad RESET key, by digital input or
fieldbus, or switching the supply voltage off for a while. When the fault has been
removed, the motor can be restarted.
Fault history
When a fault is detected, it is stored in the Fault History. The latest faults and
warnings are stored together with the time stamp at which the event was detected.
The fault logger collects 64 of the latest faults. When the drive power is switched off,
16 of the latest faults are stored.
See chapter Control panel for more information.
Fault tracing
232
ACS800 TEMP Drive IGBT temperature is excessive. Fault trip Check ambient conditions.
(4210) limit is 100%. Check air flow and fan operation.
3.08 AW 1 bit 4 Check heatsink fins for dust pick-up.
Check motor power against unit power.
AI < MIN FUNC Analogue control signal is below minimum Check for proper analogue control signal
(8110) allowed value due to incorrect signal level or levels.
3.09 AW 2 bit 10 failure in control wiring. Check control wiring.
(programmable Check Fault Function parameters.
Fault Function
30.01)
AD [message] Message generated by an EVENT block in the Consult the documentation or author of the
Adaptive Program. Adaptive Program.
BACKUP USED PC stored backup of drive parameters is Wait until download is completed.
(FFA3) downloaded into use.
BATT FAILURE APBU branching unit memory backup battery With parallel connected inverters, enable
(5581) error caused by backup battery by setting actuator 6 of switch
- incorrect APBU switch S3 setting S3 to ON.
3.18 AW 5 bit 15
- too low battery voltage. Replace backup battery.
BC OVERHEAT Brake chopper overload Stop drive. Let chopper cool down.
(7114) Check parameter settings of resistor overload
3.18 AW 5 bit 3 protection function (see parameter group 27
BRAKE CHOPPER).
Check that braking cycle meets allowed limits.
Check that drive supply AC voltage is not
excessive.
BRAKE ACKN Unexpected state of brake acknowledge signal See parameter group 42 BRAKE CONTROL.
(FF74) Check connection of brake acknowledgement
3.16 AW 4 bit 3 signal.
BR OVERHEAT Brake resistor overload Stop drive. Let resistor cool down.
(7112) Check parameter settings of resistor overload
3.18 AW 5 bit 2 protection function (see parameter group 27
BRAKE CHOPPER).
Check that braking cycle meets allowed limits.
CALIBRA REQ Calibration of output current transformers is Calibration starts automatically. Wait for a
(FF36) required. Displayed at start if drive is in scalar while.
control (parameter 99.04) and scalar fly start
feature is on (parameter 21.08).
Fault tracing
233
COMM MODULE Cyclical communication between drive and Check status of fieldbus communication. See
(7510) master is lost. chapter Fieldbus control, or appropriate
3.08 AW 1 bit 12 fieldbus adapter manual.
(programmable Check parameter settings:
Fault Function - group 51 COMM MODULE DATA (for fieldbus
30.18, 30.19) adapter)
- group 52 STANDARD MODBUS (for
Standard Modbus Link).
Check Fault Function parameters.
Check cable connections.
Check if master can communicate.
DC BUS LIM Drive limits torque due to too high or too low Informative alarm
(3211) intermediate circuit DC voltage. Check Fault Function parameters.
3.18 AW5 bit 9
(programmable
Fault Function
30.23)
EARTH FAULT Drive has detected load unbalance typically Check there are no power factor correction
(2330) due to earth fault in motor or motor cable. capacitors or surge absorbers in motor cable.
3.08 AW 1 bit 14 Check that there is no earth fault in motor or
(programmable motor cables:
Fault Function - measure insulation resistances of motor and
30.17) motor cable.
If no earth fault can be detected, contact your
local ABB representative.
ENC CABLE Pulse encoder phase signal is missing. Check pulse encoder and its wiring.
(7310) Check pulse encoder interface module and its
3.31 AW 6 bit 3 wiring.
(programmable
Fault Function
50.07)
ENCODER A<>B Pulse encoder phasing is wrong: Phase A is Interchange connection of pulse encoder
(7302) connected to terminal of phase B and vice phases A and B.
3.09 AW 2 bit 4 versa.
ENCODER ERR Communication fault between pulse encoder Check pulse encoder and its wiring, pulse
(7301) and pulse encoder interface module and encoder interface module and its wiring,
3.08 AW 1 bit 5 between module and drive parameter group 50 ENCODER MODULE
settings.
FAN OTEMP Excessive temperature of drive output filter fan. Stop drive. Let it cool down.
(FF83) Supervision is in use in step-up drives. Check ambient temperature.
3.16 AW 4 bit 0 Check fan rotates in correct direction and air
flows freely.
HW RECONF RQ Inverter type (e.g. sr0025_3) has been Wait until alarm POWEROFF! activates and
(FF38) changed. Inverter type is usually changed at switch control board power off to validate
factory or during drive implementation. inverter type change.
Fault tracing
234
ID MAGN Motor identification magnetisation is on. This Wait until drive indicates that motor
(FF31) warning belongs to normal start-up procedure. identification is completed.
ID MAGN REQ Motor identification is required. This warning Start Identification Magnetisation by pressing
(FF30) belongs to normal start-up procedure. Drive Start key, or select ID Run and start (see
expects user to select how motor identification parameter 99.10).
should be performed: By Identification
Magnetisation or by ID Run.
ID N CHANGED Drive ID number has been changed from 1. Change ID number back to 1. See chapter
(FF68) Control panel.
ID RUN Motor identification Run is on. Wait until drive indicates that motor
(FF35) identification Run is completed.
ID RUN SEL Motor Identification Run is selected, and drive Press Start key to start Identification Run.
(FF33) is ready to start ID Run. This warning belongs
to ID Run procedure.
IN CHOKE TEMP Excessive input choke temperature Stop drive. Let it cool down.
(FF81) Check ambient temperature.
3.18 AW 5 bit 4 Check that fan rotates in correct direction and
air flows freely.
INV CUR LIM Internal inverter current or power limit has Reduce load or increase ramp time.
(2212) been exceeded. Limit inverter actual power or decrease line-
3.18 AW 5 bit 8 side converter reactive power generation
(programmable reference value (parameter 95.06 LCU Q PW
Fault Function REF).
30.23) Check Fault Function parameters.
INV DISABLED Optional DC switch has opened while unit was Close DC switch.
(3200) stopped. Check AFSC-0x Fuse Switch Controller unit.
3.18 AW 5 bit 6
Fault tracing
235
INV OVERTEMP Converter module temperature is excessive. Check ambient temperature. If it exceeds
(4290) 40°C, ensure that load current does not
exceed derated load capacity of drive. See
3.31 AW 6 bit 0
appropriate hardware manual.
Check that ambient temperature setting is
correct (parameter 95.10).
Check converter module cooling air flow and
fan operation.
Cabinet installation: Check cabinet air inlet
filters. Change when necessary. See
appropriate hardware manual.
Modules installed in cabinet by user: Check
that cooling air circulation in cabinet has been
prevented with air baffles. See module
installation instructions.
Check inside of cabinet and heatsink of
converter module for dust pick-up. Clean when
necessary.
IO CONFIG Input or output of optional I/O extension or Check Fault Function parameters.
(FF8B) fieldbus module has been selected as signal Check parameter group 98 OPTION
(programmable interface in application program but MODULES.
Fault Function communication to appropriate I/O extension
30.22) module has not been set accordingly.
MACRO CHANGE Macro is restoring or User macro is being Wait until drive has finished task.
(FF69) saved.
MOD CHOKE T Overtemperature in choke of liquid cooled R8i Check inverter fan.
(FF89) inverter module. Check ambient temperature.
09.11 AW 3 bit 13 Check liquid cooling system.
MOT CUR LIM Drive limits motor current according to current Reduce load or increase ramp time.
(2300) limit defined by parameter 20.03 MAXIMUM Increase parameter 20.03 MAXIMUM
CURRENT. CURRENT value.
3.18 AW 5 bit 10
(programmable Check Fault Function parameters.
Fault Function
30.23)
MOTOR STALL Motor is operating in stall region due to e.g. Check motor load and drive ratings.
(7121) excessive load or insufficient motor power. Check Fault Function parameters.
3.09 AW 2 bit 9
(programmable
Fault Function
30.10)
MOTOR STARTS Motor Identification Run starts. This warning Wait until drive indicates that motor
(FF34) belongs to ID Run procedure. identification is completed.
Fault tracing
236
MOTOR TEMP Motor temperature is too high (or appears to be Check motor ratings, load and cooling.
(4310) too high) due to excessive load, insufficient Check start-up data.
3.08 AW 1 bit 3 motor power, inadequate cooling or incorrect
Check Fault Function parameters.
(programmable start-up data.
Fault Function
30.04…30.09)
MOTOR 1 TEMP Measured motor temperature has exceeded Check value of alarm limit.
(4312) alarm limit set by parameter 35.02. Check that actual number of sensors
3.16 AW 4 bit 1 corresponds to value set by parameter.
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
MOTOR 2 TEMP Measured motor temperature has exceeded Check value of alarm limit.
(4313) alarm limit set by parameter 35.05. Check that actual number of sensors
3.16 AW 4 bit 2 corresponds to value set by parameter.
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
MOT POW LIM Drive limits motor power according to limits Informative alarm
(FF86) defined by parameters 20.11 and 20.12. Check parameter 20.11 P MOTORING LIM
3.18 AW 5 bit 12 and 20.12 P GENERATING LIM settings.
(programmable Check Fault Function parameters.
Fault Function
30.23)
MOT TORQ LIM Drive limits motor torque according to Informative alarm
(FF85) calculated motor pull-out torque limit and Check parameter 20.13 MIN TORQ SEL and
minimum and maximum torque limits defined 20.14 MAX TORQ SEL settings.
3.18 AW 5 bit 11
by parameters 20.13 and 20.14.
(programmable Check Fault Function parameters.
Fault Function If LIMIT WORD 1 bit 0 TORQ MOTOR LIM
30.23) is 1,
- check motor parameter settings (parameter
group 99 START-UP DATA)
- ensure that ID run has been completed
successfully.
PANEL LOSS Control panel selected as active control Check panel connection (see appropriate
(5300) location for drive has ceased communicating. hardware manual).
3.09 AW 2 bit 13 Check control panel connector.
(programmable Replace control panel in mounting platform.
Fault Function Check Fault Function parameters.
30.02)
POINTER ERROR Source selection (pointer) parameter points to Check source selection (pointer) parameter
(FFD0) non existing parameter index. settings.
->POWEROFF! Inverter type (e.g. sr0025_3) has been Switch control board power off to validate
(FF39) changed. Inverter type is usually changed at inverter type change.
factory or during drive implementation.
Fault tracing
237
PPCC LINK Fibre optic link to INT board is faulty. Check fibre optic cables or galvanic link. With
(5210) frame sizes R2-R6 link is galvanic.
3.06 FW 2 bit 11 If RMIO is powered from external supply,
ensure that supply is on. See parameter 16.09
CTRL BOARD SUPPLY.
Check signal 03.19. Contact ABB
representative if any of faults in signal 3.19 are
active.
PPCC LINK xx INT board fibre optic connection fault in Check connection from inverter module Main
(5210) inverter unit of several parallel connected Circuit Interface Board, INT to PPCC
inverter modules. xx refers to inverter module Branching Unit, PBU. (Inverter module 1 is
3.06 FW 2 bit 11 and
4.01
number. connected to PBU INT1 etc.)
Check signal 03.19. Contact ABB
representative if any of faults in signal 3.19 are
active.
REPLACE FAN Running time of inverter cooling fan has Replace fan.
(4280) exceeded its estimated life time. Reset fan run time counter 01.44.
3.18 AW 5 bit 0
RUN ENABLE No Run enable signal received. Check setting of parameter 16.01. Switch on
(FF8E) signal or check wiring of selected source.
3.06 FW 2 bit 4
SLEEP MODE Sleep function has entered sleeping mode. See parameter group 40 PID CONTROL.
(FF8C)
3.16 AW 4 bit 4
START INHIBI Safe torque off function has been activated Close Safe torque off function switch. If switch
(FF7A) while drive was stopped. is closed and warning is still active, check
Or: Optional start inhibit hardware logic is power supply at ASTO board input terminals.
AW 1 bit 0
activated. Replace ASTO board.
Or: Check start inhibit circuit (AGPS board).
START INTERL No Start Interlock signal received. Check circuit connected to Start Interlock input
(FF8D) on RMIO board.
SYNCRO SPEED Value of motor nominal speed set to parameter Check nominal speed from motor rating plate
(FF87) 99.08 is not correct: Value is too near and set parameter 99.08 exactly accordingly.
synchronous speed of motor. Tolerance is
3.18 AW 5 bit 1
0.1%. This warning is active only in DTC mode.
Fault tracing
238
THERMISTOR Motor temperature is excessive. Motor thermal Check motor ratings and load.
(4311) protection mode selection is TEMP SENSOR. Check start-up data.
3.08 AW 1 bit 2 Check thermistor connections to digital input
(programmable DI6.
Fault Function
30.04…30.05)
T MEAS ALM Motor temperature measurement is out of Check connections of motor temperature
(FF91) acceptable range. measurement circuit. See chapter Program
3.08 AW 1 bit 6 features for circuit diagram.
UNDERLOAD Motor load is too low due to e.g. release Check for problem in driven equipment.
(FF6A) mechanism in driven equipment. Check Fault Function parameters.
3.09 AW 2 bit 1
(programmable
Fault Function
30.13)
USER L CURVE Integrated motor current has exceeded load Check parameter group 72 USER LOAD
(2312) curve defined by parameters in group 72 CURVE settings.
USER LOAD CURVE. Reduce load.
3.18 AW 5 bit 13
Fault tracing
239
DOWNLOADING Download function of panel has failed. No data Make sure panel is in local mode.
FAILED has been copied from panel to drive. Retry (there might be interference on link).
Contact ABB representative.
DRIVE IS Downloading is not possible while motor is Stop motor. Perform downloading.
RUNNING running.
DOWNLOADING
NOT POSSIBLE
(4) = Panel type not compatible with drive Check panel type and drive application
application program version program version. Panel type is printed on
panel cover. Application program version is
stored in parameter 33.02.
NO FREE ID Panel Link already includes 31 stations. Disconnect another station from link to free ID
NUMBERS ID number.
NUMBER
SETTING NOT
POSSIBLE
NOT UPLOADED No upload function has been performed. Perform upload function before downloading.
DOWNLOADING See chapter Control panel.
NOT POSSIBLE
UPLOADING Upload function of panel has failed. No data Retry (there might be interference on link).
FAILED has been copied from drive to panel. Contact ABB representative.
WRITE ACCESS Certain parameters do not allow changes while Stop motor, then change parameter value.
DENIED motor is running. If tried, no change is
PARAMETER accepted, and warning is displayed.
SETTING NOT
POSSIBLE Parameter lock is on. Open parameter lock (see parameter 16.02).
Fault tracing
240
ACS800 TEMP Drive IGBT temperature is excessive. Fault trip Check ambient conditions.
(4210) limit is 100%. Check air flow and fan operation.
3.05 FW 1 bit 3 Check heatsink fins for dust pick-up.
Check motor power against unit power.
ACS TEMP xx y Excessive internal temperature in inverter unit Check ambient conditions.
(4210) of several parallel connected inverter modules. Check air flow and fan operation.
3.05 FW 1 bit 3 and xx (1...12) refers to inverter module number
Check heatsink fins for dust pick-up.
4.01 and y refers to phase (U, V, W).
Check motor power against unit power.
AI < MIN FUNC Analogue control signal is below minimum Check for proper analogue control signal
(8110) allowed value due to incorrect signal level or levels.
3.06 FW 2 bit 10 failure in control wiring. Check control wiring.
(programmable Check Fault Function parameters.
Fault Function
30.01)
AD [message] Message generated by an EVENT block in the Consult the documentation or author of the
Adaptive Program. Adaptive Program.
BC SHORT CIR Short circuit in brake chopper IGBT(s) Replace brake chopper.
(7113) Ensure brake resistor is connected and not
3.17 FW 5 bit 2 damaged.
BRAKE ACKN Unexpected state of brake acknowledge signal See parameter group 42 BRAKE CONTROL.
(FF74) Check connection of brake acknowledgement
3.15 FW 4 bit 3 signal.
BR BROKEN Brake resistor is not connected or it is Check resistor and resistor connection.
(7110) damaged. Check that resistance rating meets
3.17 FW 5 bit 0 Resistance rating of brake resistor is too high. specifications. See appropriate drive hardware
manual.
Fault tracing
241
CHOKE OTEMP Excessive temperature of drive output filter. Let drive cool down.
(FF82) Supervision is in use in step-up drives. Check ambient temperature.
Check filter fan rotates in correct direction and
air flows freely.
COMM MODULE Cyclical communication between drive and Check status of fieldbus communication. See
(7510) master is lost. chapter Fieldbus control, or appropriate
3.06 FW 2 bit 12 fieldbus adapter manual.
(programmable Check parameter settings:
Fault Function - group 51 COMM MODULE DATA (for fieldbus
30.18, 30.19) adapter), or
- group 52 STANDARD MODBUS (for
Standard Modbus Link).
Check Fault Function parameters.
Check cable connections.
Check if master can communicate.
CTRL B TEMP Control board temperature is above 88°C. Check ambient conditions.
(4110) Check air flow.
3.06 FW 2 bit 7 Check main and additional cooling fans.
CURR MEAS Current transformer failure in output current Check current transformer connections to Main
(2211) measurement circuit Circuit Interface Board, INT.
CUR UNBAL xx Drive has detected excessive output current Check there are no power factor correction
(2330) unbalance in inverter unit of several parallel capacitors or surge absorbers in motor cable.
3.05 FW 1 bit 4 and connected inverter modules. This can be Check that there is no earth fault in motor or
4.01 caused by external fault (earth fault, motor, motor cables:
(programmable motor cabling, etc.) or internal fault (damaged
- measure insulation resistances of motor and
Fault Function inverter component). xx (1...12) refers to
motor cable.
30.17) inverter module number.
If no earth fault can be detected, contact your
local ABB representative.
DC HIGH RUSH Drive supply voltage is excessive. When Check supply voltage level, drive rated voltage
(FF80) supply voltage is over 124% of unit voltage and allowed voltage range of drive.
rating (415, 500 or 690 V), motor speed rushes
to trip level (40% of nominal speed).
Fault tracing
242
DC UNDERVOLT Intermediate circuit DC voltage is not sufficient Check main supply and fuses.
(3220) due to missing supply voltage phase, blown
3.06 FW 2 bit 2 fuse or rectifier bridge internal fault.
DC undervoltage trip limit is 0.6 × 1.35 × U1min,
where U1min is minimum value of supply
voltage range. For 400 V and 500 V units,
U1min is 380 V. For 690 V units, U1min is 525 V.
Actual voltage in intermediate circuit
corresponding to supply voltage trip level is
307 V DC for 400 V and 500 V units, and
425 V DC for 690 V units.
EARTH FAULT Drive has detected load unbalance typically Check there are no power factor correction
(2330) due to earth fault in motor or motor cable. capacitors or surge absorbers in motor cable.
3.05 FW 1 bit 4 Check that there is no earth fault in motor or
(programmable motor cables:
Fault Function - measure insulation resistances of motor and
30.17) motor cable.
If no earth fault can be detected, contact your
local ABB representative.
ENC CABLE Pulse encoder phase signal is missing. Check pulse encoder and its wiring.
(7310) Check pulse encoder interface module and its
3.33 FW 6 bit 2 wiring.
(programmable
Fault Function
50.07)
ENCODER A<>B Pulse encoder phasing is wrong: Phase A is Interchange connection of pulse encoder
(7302) connected to terminal of phase B and vice phases A and B.
versa.
ENCODER ERR Communication fault between pulse encoder Check pulse encoder and its wiring, pulse
(7301) and pulse encoder interface module and encoder interface module and its wiring and
3.06 FW 2 bit 5 between module and drive parameter group 50 ENCODER MODULE
settings.
EXTERNAL FLT Fault in external device. (This information is Check external devices for faults.
(9000) configured through one of programmable Check parameter 30.03 EXTERNAL FAULT.
3.06 FW 2 bit 8 digital inputs.)
(programmable
Fault Function
30.03)
Fault tracing
243
FORCED TRIP Generic Drive Communication Profile trip See appropriate communication module
(FF8F) command manual.
GD DISABLED AGPS power supply of parallel connected R8i Check Prevention of Unexpected Start-up
(FF53) inverter module has been switched off during circuit.
run. X (1…12) refers to inverter module Replace AGPS board of R8i inverter module.
number.
ID RUN FAIL Motor ID Run is not completed successfully. Check maximum speed (parameter 20.02). It
(FF84) should be at least 80% of motor nominal speed
(parameter 99.08).
IN CHOKE TEMP Excessive input choke temperature Stop drive. Let it cool down.
(FF81) Check ambient temperature.
3.17 FW 5 bit 5 Check that fan rotates in correct direction and
air flows freely.
INT CONFIG Number of inverter modules is not equal to Check status of inverters. See signal 04.01
(5410) original number of inverters. FAULTED INT INFO.
03.17 FW 5 bit 10 Check fibre optic cables between APBU and
inverter modules.
If Reduced Run function is used, remove
faulted inverter module from main circuit and
write number of remaining inverter modules
into parameter 95.03 INT CONFIG USER.
Reset drive.
INV DISABLED Optional DC switch has opened while unit was Close DC switch.
03.17 FW 5 bit 7 running or start command was given. Check AFSC-0x Fuse Switch Controller unit.
(3200)
INV OVERTEMP Converter module temperature is excessive. Check ambient temperature. If it exceeds
(4290) 40°C, ensure that load current does not
exceed derated load capacity of drive. See
3.17 FW 5 bit 13
appropriate hardware manual.
Check that ambient temperature setting is
correct (parameter 95.10).
Check converter module cooling air flow and
fan operation.
Cabinet installation: Check cabinet air inlet
filters. Change when necessary. See
appropriate hardware manual.
Modules installed in cabinet by user: Check
that cooling air circulation in cabinet has been
prevented with air baffles. See module
installation instructions.
Check inside of cabinet and heatsink of
converter module for dust pick-up. Clean when
necessary.
Reset and restart after problem is solved and
let converter module cool down.
Fault tracing
244
I/O COMM ERR Communication error on control board, Check connections of fibre optic cables on
(7000) channel CH1 channel CH1.
3.06 FW 2 bit 6 Electromagnetic interference Check all I/O modules (if present) connected to
channel CH1.
Check for proper earthing of equipment. Check
for highly emissive components nearby.
LINE CONV Fault on line side converter Shift panel from motor side converter control
(FF51) board to line side converter control board.
See line side converter manual for fault
description.
MOD CHOKE T Overtemperature in choke of liquid cooled R8i Check inverter fan.
(FF89) inverter module. Check ambient temperature.
Check liquid cooling system.
MOTOR PHASE One of motor phases is lost due to fault in Check motor and motor cable.
(FF56) motor, motor cable, thermal relay (if used) or Check thermal relay (if used).
3.06 FW 2 bit 15 internal fault.
Check Fault Function parameters. Disable this
(programmable protection.
Fault Function
30.16)
MOTOR STALL Motor is operating in stall region due to e.g. Check motor load and drive ratings.
(7121) excessive load or insufficient motor power. Check Fault Function parameters.
3.06 FW 2 bit 14
(programmable
Fault Function
30.10…30.12)
MOTOR TEMP Motor temperature is too high (or appears to be Check motor ratings and load.
(4310) too high) due to excessive load, insufficient Check start-up data.
3.05 FW 1 bit 6 motor power, inadequate cooling or incorrect
Check Fault Function parameters.
(programmable start-up data.
Fault Function
30.04…30.09)
MOTOR 1 TEMP Measured motor temperature has exceeded Check value of fault limit.
(4312) fault limit set by parameter 35.03. Let motor cool down. Ensure proper motor
3.15 FW 4 bit 1 cooling: Check cooling fan, clean cooling
surfaces, etc.
MOTOR 2 TEMP Measured motor temperature has exceeded Check value of fault limit.
(4313) fault limit set by parameter 35.06. Let motor cool down. Ensure proper motor
3.15 FW 4 bit 2 cooling: Check cooling fan, clean cooling
surfaces, etc.
NO MOT DATA Motor data is not given or motor data does not Check motor data parameters
(FF52) match with inverter data. 99.04…99.09.
3.06 FW 2 bit 1
Fault tracing
245
OVERFREQ Motor is turning faster than highest allowed Check minimum/maximum speed settings.
(7123) speed due to incorrectly set minimum/ Check adequacy of motor braking torque.
3.05 FW 1 bit 9 maximum speed, insufficient braking torque or
Check applicability of torque control.
changes in load when using torque reference.
Check need for brake chopper and resistor(s).
Trip level is 50 Hz over operating range
absolute maximum speed limit (Direct Torque
Control mode active) or frequency limit (Scalar
Control active). Operating range limits are set
by parameters 20.01 and 20.02 (DTC mode
active) or 20.07 and 20.08 (Scalar Control
active).
OVER SWFREQ Switching frequency is too high. Check motor parameter settings (parameter
(FF55) group 99 START-UP DATA)
3.06 FW 2 bit 9 Ensure that ID run has been completed
successfully.
PANEL LOSS Control panel or DriveWindow selected as Check panel connection (see appropriate
(5300) active control location for drive has ceased hardware manual).
3.06 FW 2 bit 13 communicating. Check control panel connector.
(programmable Replace control panel in mounting platform.
Fault Function
Check Fault Function parameters.
30.02)
Check DriveWindow connection.
PARAM CRC CRC (Cyclic Redundancy Check) error Switch control board power off and on again.
(6320) Reload firmware to control board.
Replace control board.
POWERFAIL INT board powerfail in several inverter units of Check that INT board power cable is
(3381) parallel connected inverter modules. connected.
3.17 FW 5 bit 9 Check that POW board is working correctly.
Replace INT board.
Fault tracing
246
POWERF INV xx INT board powerfail in inverter unit of several Check that INT board power cable is
(3381) parallel connected inverter modules. xx (1...12) connected.
refers to inverter module number. Check that POW board is working correctly.
3.17 FW 5 bit 9 and
4.01 Replace INT board.
PPCC LINK Fibre optic link to INT board is faulty. Check fibre optic cables or galvanic link. With
(5210) frame sizes R2-R6 link is galvanic.
3.06 FW 2 bit 11 If RMIO is powered from external supply,
ensure that supply is on. See parameter 16.09
CTRL BOARD SUPPLY.
Check signal 03.19. Contact ABB
representative if any of faults in signal 3.19 are
active.
PPCC LINK xx INT board fibre optic connection fault in Check connection from inverter module Main
(5210) inverter unit of several parallel connected Circuit Interface Board, INT to PPCC
inverter modules. xx refers to inverter module Branching Unit, PBU. (Inverter module 1 is
3.06 FW 2 bit 11 and
4.01
number. connected to PBU INT1 etc.)
Check signal 03.19. Contact ABB
representative if any of faults in signal 3.19 are
active.
SC INV xx y Short circuit in inverter unit of several parallel Check motor and motor cable.
(2340) connected inverter modules. xx (1...12) refers Check power semiconductors (IGBTs) of
to inverter module number and y refers to inverter module.
3.05 FW 1 bit 0, 4.01 phase (U, V, W).
and 4.02
SHORT CIRC Short-circuit in motor cable(s) or motor Check motor and motor cable.
(2340) Check there are no power factor correction
3.05 FW 1 bit 0 and capacitors or surge absorbers in motor cable.
4.02
SLOT OVERLAP Two option modules have same connection Check connection interface selections in group
(FF8A) interface selection. 98 OPTION MODULES.
START INHIBI Safe torque off has been activated during Close Safe torque off switch. If switch is closed
(FF7A) motor run or motor start command has been and fault is still active, check power supply at
3.03 bit 8 given when Safe torque off is active. ASTO board input terminals. Replace ASTO
Or: Optional start inhibit hardware logic is board.
activated. Or: Check start inhibit circuit (AGPS board).
SUPPLY PHASE Intermediate circuit DC voltage is oscillating Check main supply fuses.
(3130) due to missing supply voltage phase, blown Check for main supply imbalance.
3.06 FW 2 bit 0 fuse or rectifier bridge internal fault.
Trip occurs when DC voltage ripple is 13% of
DC voltage.
Fault tracing
247
THERMAL MODE Motor thermal protection mode is set to DTC See parameter 30.05.
(FF50) for high-power motor.
THERMISTOR Motor temperature is excessive. Motor thermal Check motor ratings and load.
(4311) protection mode selection is TEMP SENSOR. Check start-up data.
3.05 FW 1 bit 5 Check thermistor connections to digital input
(programmable DI6.
Fault Function
30.04…30.05)
UNDERLOAD Motor load is too low due to e.g. release Check for problem in driven equipment.
(FF6A) mechanism in driven equipment. Check Fault Function parameters.
3.05 FW 1 bit 8
(programmable
Fault Function
30.13…30.15)
USER L CURVE Integrated motor current has exceeded load Check parameter group 72 USER LOAD
(2312) curve defined by parameter group 72 USER CURVE settings.
LOAD CURVE. After motor cooling time specified by
3.17 FW 5 bit 11
parameter 72.20 LOAD COOLING TIME has
elapsed, fault can be reset.
USER MACRO No User Macro saved or file is defective. Create User Macro.
(FFA1)
3.07 SFW bit 1
Fault tracing
248
Fault tracing
249
Chapter overview
The chapter describes the use of analogue extension module RAIO as an speed
reference interface of ACS800 equipped with Standard Control Program.
Basic checks
Ensure the drive is:
• installed and commissioned, and
• the external start and stop signals are connected.
Ensure the extension module:
• settings are adjusted. (See below.)
• is installed and reference signal is connected to AI1.
• is connected to the drive.
The figure below presents the speed reference corresponding to bipolar input AI1 of
the extension module.
Operation Range
scaled
maxREF1
10.03 DIRECTION =
FORWARD or
REQUEST1)
Speed Reference
minREF1
-minREF1
10.03 DIRECTION =
REVERSE or
REQUEST1)
-scaled
maxREF1
-maxAI5 -minAI5 minAI5 maxAI5
Analogue Input Signal
1) For
the negative speed range, the drive must receive a separate reverse command.
2) Set if supervision of living zero is used.
The figure below presents the speed reference corresponding to bipolar input AI1 of
the extension module in joystick mode.
Operation Range
scaled
maxREF1
10.03 DIRECTION =
FORWARD or
REQUEST1)
Speed Reference
minREF1
-minREF1
10.03 DIRECTION =
REVERSE or
REQUEST1)
-scaled
maxREF1
-maxAI5 -minAI5 minAI5 maxAI5
Analogue Input Signal
Chapter overview
This chapter lists the actual signal and parameter lists with some additional data. For
the descriptions, see chapter Actual signals and parameters.
Absolute Maximum Frequency Value of 20.08, or 20.07 if the absolute value of the minimum limit
is greater than the maximum limit.
Absolute Maximum Speed Value of parameter 20.02, or 20.01 if the absolute value of the
minimum limit is higher than the maximum limit.
Fieldbus addresses
Rxxx adapter modules (such as RPBA-01, RDNA-01, etc.)
See the appropriate fieldbus adapter module User’s Manual.
Actual signals
Index Name Short name FbEq Unit Range PB
01 ACTUAL SIGNALS
01.01 PROCESS VARIABLE PROC VAR 1=1 According to 1
parameter 34.02
01.02 SPEED SPEED -20000 = -100% rpm 2
20000 = 100% of
motor absolute max.
speed
01.03 FREQUENCY FREQ -100 = -1 Hz 100 = 1 Hz 3
Hz
01.04 CURRENT CURRENT 10 = 1 A A 4
01.05 TORQUE TORQUE -10000 = -100% % 5
10000 = 100% of
motor nominal torque
01.06 POWER POWER -1000 = -100% 1000 % 6
= 100% of motor
nominal power
01.07 DC BUS VOLTAGE V DC BUS V 1=1V V 7
01.08 MAINS VOLTAGE MAINS V 1=1V V 8
01.09 OUTPUT VOLTAGE OUT VOLT 1=1V V 9
01.10 ACS800 TEMP ACS TEMP 10 = 1% % 10
01.11 EXTERNAL REF 1 EXT REF1 1 = 1 rpm rpm 11
01.12 EXTERNAL REF 2 EXT REF2 0 = 0% 10000 = % 12
100% 1)
01.13 CTRL LOCATION CTRL LOC (1,2) LOCAL; (3) LOCAL; EXT1; 13
EXT1; (4) EXT2 EXT2
01.14 OP HOUR COUNTER OP HOURS 1=1h h 14
01.15 KILOWATT HOURS KW HOURS 1 = 100 kWh kWh 15
01.16 APPL BLOCK OUTPUT APPL OUT 0 = 0% 10000 = % 16
100%
01.17 DI6-1 STATUS DI6-1 1=1 17
01.18 AI1 [V] AI1 [V] 1 = 0.001 V V 18
01.19 AI2 [mA] AI2 [mA] 1 = 0.001 mA mA 19
01.20 AI3 [mA] AI3 [mA] 1 = 0.001 mA mA 20
01.21 RO3-1 STATUS RO3-1 1=1 21
01.22 AO1 [mA] AO1 [mA] 1 =0.001 mA mA 22
01.23 AO2 [mA] AO2 [mA] 1 = 0.001 mA mA 23
01.24 ACTUAL VALUE 1 ACT VAL1 0 = 0% 10000 = % 24
100%
01.25 ACTUAL VALUE 2 ACT VAL2 0 = 0% 10000 = % 25
100%
01.26 CONTROL DEVIATION CONT DEV -10000 = -100% % 26
10000 = 100%
01.27 APPLICATION MACRO MACRO 1…7 According to 27
parameter 99.02
01.28 EXT AO1 [mA] EXT AO1 1 = 0.001 mA mA 28
01.29 EXT AO2 [mA] EXT AO2 1 = 0.001 mA mA 29
01.30 PP 1 TEMP PP 1 TEM 1 = 1°C °C 30
01.31 PP 2 TEMP PP 2 TEM 1 = 1°C °C 31
01.32 PP 3 TEMP PP 3 TEM 1 = 1°C °C 32
01.33 PP 4 TEMP PP 4 TEM 1 = 1°C °C 33
01.34 ACTUAL VALUE ACT V 0 = 0% 10000 = % 34
100%
01.35 MOTOR 1 TEMP M 1 TEMP 1 = 1°C/ohm °C 35
01.36 MOTOR 2 TEMP M 2 TEMP 1 = 1°C/ohm °C 36
01.37 MOTOR TEMP EST MOTOR TE 1 = 1°C °C 37
01.38 AI5 [mA] AI5 [mA] 1 = 0.001 mA mA 38
Parameters
Index Name/Selection FACTORY HAND/AUTO PID-CTRL T-CTRL SEQ CTRL PB W
10 START/STOP/DIR
10.01 EXT1 STRT/STP/DIR DI1,2 (US: DI1,2 DI1 DI1,2 DI1,2 101 W
DI1P,2P,3)
10.02 EXT2 STRT/STP/DIR NOT SEL DI6,5 DI6 DI1,2 NOT SEL 102 W
10.03 REF DIRECTION FORWARD REQUEST FORWARD REQUEST REQUEST 103 W
10.04 EXT 1 STRT PTR 0 0 0 0 104 W
10.05 EXT 2 STRT PTR 0 0 0 0 0 105 W
10.06 JOG SPEED SELECT NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL 106 W
10.07 NET CONTROL 0 0 0 0 0 107
10.08 NET REFERENCE 0 0 0 0 0 108
10.09 SLS ACTIVE NO NO NO NO NO 109
11 REFERENCE SELECT
11.01 KEYPAD REF SEL REF1 (rpm) REF1 (rpm) REF1 (rpm) REF1 (rpm) REF1 (rpm) 126
11.02 EXT1/EXT2 SELECT EXT1 DI3 DI3 DI3 EXT1 127 W
11.03 EXT REF1 SELECT AI1 AI1 AI1 AI1 AI1 128 W
11.04 EXT REF 1 MINIMUM 0 rpm 0 rpm 0 rpm 0 rpm 0 rpm 129
11.05 EXT REF 1 MAXIMUM 1500 rpm 1500 rpm 1500 rpm 1500 rpm 1500 rpm 130
11.06 EXT REF2 SELECT KEYPAD AI2 AI1 AI2 AI1 131 W
11.07 EXT REF 2 MINIMUM 0% 0% 0% 0% 0% 132
11.08 EXT REF 2 MAXIMUM 100% 100% 100% 100% 100% 133
11.09 EXT 1/2 SEL PTR 0 0 0 0 0 134
11.10 EXT 1 REF PTR 0 0 0 0 0 135
11.11 EXT 2 REF PTR 0 0 0 0 0 136
12 CONSTANT SPEEDS
12.01 CONST SPEED SEL DI5,6 DI4(SPEED4) DI4(SPEED4) DI4(SPEED4) DI4,5,6 151 W
12.02 CONST SPEED 1 300 rpm 300 rpm 300 rpm 300 rpm 300 rpm 152
12.03 CONST SPEED 2 600 rpm 600 rpm 600 rpm 600 rpm 600 rpm 153
12.04 CONST SPEED 3 900 rpm 900 rpm 900 rpm 900 rpm 900 rpm 154
12.05 CONST SPEED 4 300 rpm 300 rpm 300 rpm 300 rpm 1200 rpm 155
12.06 CONST SPEED 5 0 rpm 0 rpm 0 rpm 0 rpm 1500 rpm 156
12.07 CONST SPEED 6 0 rpm 0 rpm 0 rpm 0 rpm 2400 rpm 157
12.08 CONST SPEED 7 0 rpm 0 rpm 0 rpm 0 rpm 3000 rpm 158
12.09 CONST SPEED 8 0 rpm 0 rpm 0 rpm 0 rpm 0 rpm 159
12.10 CONST SPEED 9 0 rpm 0 rpm 0 rpm 0 rpm 0 rpm 160
12.11 CONST SPEED 10 0 rpm 0 rpm 0 rpm 0 rpm 0 rpm 161
12.12 CONST SPEED 11 0 rpm 0 rpm 0 rpm 0 rpm 0 rpm 162
12.13 CONST SPEED 12 0 rpm 0 rpm 0 rpm 0 rpm 0 rpm 163
12.14 CONST SPEED 13 0 rpm 0 rpm 0 rpm 0 rpm 0 rpm 164
12.15 CONST SPEED 14 0 rpm 0 rpm 0 rpm 0 rpm 0 rpm 165
12.16 CONST SPEED 15 0 rpm 0 rpm 0 rpm 0 rpm 0 rpm 166
13 ANALOGUE INPUTS
13.01 MINIMUM AI1 0V 0V 0V 0V 0V 176
13.02 MAXIMUM AI1 10 V 10 V 10 V 10 V 10 V 177
13.03 SCALE AI1 100% 100% 100% 100% 100% 178
13.04 FILTER AI1 0.10 s 0.10 s 0.10 s 0.10 s 0.10 s 179
13.05 INVERT AI1 NO NO NO NO NO 180
13.06 MINIMUM AI2 0 mA 0 mA 0 mA 0 mA 0 mA 181
13.07 MAXIMUM AI2 20 mA 20 mA 20 mA 20 mA 20 mA 182
13.08 SCALE AI2 100% 100% 100% 100% 100% 183
13.09 FILTER AI2 0.10 s 0.10 s 0.10 s 0.10 s 0.10 s 184
13.10 INVERT AI2 NO NO NO NO NO 185
13.11 MINIMUM AI3 0 mA 0 mA 0 mA 0 mA 0 mA 186
13.12 MAXIMUM AI3 20 mA 20 mA 20 mA 20 mA 20 mA 187
13.13 SCALE AI3 100% 100% 100% 100% 100% 188
13.14 FILTER AI3 0.10 s 0.10 s 0.10 s 0.10 s 0.10 s 189
13.15 INVERT AI3 NO NO NO NO NO 190
Chapter overview
Diagram Related
diagrams
Reference control chain sheet 1: PID CTRL macro (continued on the next
page …)
Reference control chain sheet 2: All macros (continued on the next page …)
IN LOCAL MODE
31 AUTORESET AND
AND
AND MAIN CW / B0 (ON/OFF)
FIELDBUS CW / B0
Index
A Application macros 85
factory 85, 87
ABB drives communication profile 210 hand/auto 85, 89
Absolute maximum frequency 99, 253 PID control 85, 91
Absolute maximum speed 99, 253 reference control chain diagram 270
ACCEL TIME 1 136 sequential control 85, 95
ACCEL/DECEL 135 torque control 85, 93
Acceleration user 85, 97
compensation 139 Application, selection for start-up assistant 41
motor 102 Automatic resets 69
ramps 59 Automatic start 54
settings 59 AUXILIARY STATUS WORD 3 223
speed reference ramps 46 AUXILIARY STATUS WORD 4 224
times 20
times, setting 42
B
Actual signals 53, 255–257
defined 99 Boolean values 40
diagnostics 44, 52, 53
display mode 29 C
displaying the full names 30
parameters 52, 53 Cable connection, monitoring 65
PID control 71 Clearing
settings 52, 53 fault history 30
speed controller 60 Communication
speed controller tuning 60 fault protection 66
user-defined variables 69 profiles 210–218
Actual values 53 using a fieldbus adapter module 193
actual signals 52, 53 Communication profiles 210–218
analogue outputs 50 ABB drives 210
defined 205 generic drive 215
digital inputs 51 Constant speeds 59
relay outputs 52 Control block diagrams 267–275
Adapter module, fieldbus 192 Control board temperature fault 68
Advent controller 197–198 Control panel
AI 63 basic keys 35
ALARM WORD 1 222 display mode 29
ALARM WORD 2 223 downloading drive data 37
ALARM WORD 4 225 drive control 27–28
ALARM WORD 5 226 overview 25–26
ALARM WORD 6 227 setting the display contrast 38
Analogue extension module 249 upload drive data 36
Analogue inputs Control word 203
optional, supervising 66 CSA 2.8/3.0 communication profile 218
Analogue outputs Critical speeds 59
diagnostics 50
optional, supervising 66 D
parameters 50 DC
settings 50 hold 57
APPLICATION MACRO 101, 187
Index
278
F I
Factory macros 85–87 ID run procedure 22–23
Input bridge protection 69
Index
279
Input phase loss fault 68 Parameter settings, bipolar input in joystick mode
INT INIT FAULT 226 251
INT SC INFO 230 Parameters
Integer scaling 67 actual signals 52, 53
Internal fault 68 Advent controller 197–198
AI 63
K analogue outputs 50
automatic reset 69
Keys on the control panel 35 communication fault protection 66
data tables 258
L defined 99
LIMIT WORD 1 220 digital inputs 51
LIMIT WORD INV 227 drive control 199–201
Limits, adjustable 68 earth fault protection 65
Local control 44 external fault 63
fieldbus adapter 193–194
hexagonal motor flux 63
M
IR compensation 62
Macros motor phase loss 65
factory 85, 87 motor stall protection 65
hand/auto 85, 89 motor temperature 64
overview 85 motor underload protection 65
PID control 85, 91 operation limits 68
reference control chain diagram 270 optional analogue inputs and outputs 66
sequential control 95 parameter lock 69
defined 85 reference trimming 47
torque control 85, 93 relay outputs 52
user 97 scalar control 62
defined 85 selecting and changing values 32
Modbus speed controller tuning 60
adapter module 192 standard modbus link 195–196
addressing 196 start-up assistant 41
link, communication parameters 195–196 supervision 69
Motor PB, defined 253
identification 53 Performance figures
phase loss 65 speed controller 60
stall protection 65 torque control 60
temperature measurement using standard I/O PID control
72, 73 block diagrams 70
temperature thermal model 64 macro 85, 91
thermal protection 64 macro, reference control diagram 270
underload protection 65 parameters 71
settings 71
O sleep function 71
Power limit 69
Operation limits 68 Power loss ride-through 54
Overcurrent fault 66 Preprogrammed faults 66
Overfrequency fault 68 control board temperature 68
DC undervoltage 67
P drive temperature 67
Panel link ID number, changing 39 Enhanced drive temperature monitoring 67
Panel loss 63 input phase loss 68
Parameter lock 69 internal fault 68
overfrequency 68
Index
280
Index
281
U
Underload protection 65
User macros 97
defined 85
user-defined, supervising 69
V
Variables 69
Viewing fault history 30
Index
282
Index
3AFE64527592 REV L / EN
EFFECTIVE: 2011-08-25
User’s Manual
EFFECTIVE: 1.5.2002
Safety instructions
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
General safety instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
Table of contents
Chapter 1 – Introduction
Intended audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Before you start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
What this manual contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Chapter 2 – Overview
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
The RTAC-01 module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Module layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Delivery check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Warranty and liability information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Chapter 3 – Installation
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Terminal designations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Encoder wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Phasing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Encoder output types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Node address selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Before you start It is assumed that the drive is installed and ready to
operate before starting the installation of the extension
module.
In addition to conventional installation tools, have the
drive manuals available during the installation as they
contain important information not included in this
manual. The drive manuals are referred to at various
points of this document.
Module layout
67
AB E 89
CD
GND
CHA
CHB
WD/
INIT
NODE ID
Diagnostic LEDs
X2
X1
CHASSIS
V OUT
CHA+
CHB+
SHLD
SHLD
CHZ+
CHA-
CHB-
+15V
+24V
CHZ-
V IN
0V
0V
12345678 123456
Fixing screw
(CHASSIS)
Terminal block for
encoder signals (X2)
Terminal block for encoder
power connections (X1)
Warranty and The warranty for your ABB drive and options covers
liability manufacturing defects. The manufacturer carries no
information responsibility for damage due to transport or unpacking.
In no event and under no circumstances shall the
manufacturer be liable for damages and failures due to
misuse, abuse, improper installation, or abnormal
conditions of temperature, dust, or corrosives, or
failures due to operation above rated capacities. Nor
shall the manufacturer ever be liable for consequential
and incidental damages.
The period of manufacturer's warranty is 12 months,
and not more than 18 months, from the date of delivery.
Extended warranty may be available with certified start-
up. Contact your local distributor for details.
Your local ABB Drives company or distributor may have
a different warranty period, which is specified in their
sales terms, conditions, and warranty terms.
If you have any questions concerning your ABB drive,
contact your local distributor or ABB Drives office.
The technical data and specifications are valid at the
time of printing. ABB reserves the right to subsequent
alterations.
Terminal
designations
X1 Marking Description
X2 Marking Description
RTAC
X1
0V 1 0V
2 0V
Vcc 3 V OUT
Vcc 0V
4 +15V
5 V IN
6 +24V
X2
2 SHLD
Pidle + 1.75 W
150 m
Pidle + 1.5 W
Pidle + 1.25 W
100 m
Pidle + 1.0 W
Pidle + 0.75 W
Pidle + 0.5 W
20 m
Pidle + 0.25 W
Pidle
EPN = 1024 ppr: 0 300 600 900 1200 1500 1800 2100 2400 2700 3000 Motor
EPN = 2048 ppr: 0 150 300 450 600 750 900 1050 1200 1350 1500 speed
(rpm)
EPN = 512 ppr: 0 600 1200 1800 2400 3000 3600 4200 4800 5400 6000
A or 1
A or 1
B or 2
B or 2
Z or 0
Z or 0
RL1
RL
Wiring diagrams
RTAC
X2
1 SHLD
2 SHLD
1 3 A+
1 4 A-
2 5 B+
2 6 B-
0 7 Z+
0 8 Z-
VCC 0V
X1
1 0V
2 0V
3 V OUT
4 +15V
Encoder supply 15V
5 V IN
voltage selection 24V
6 +24V
(15 or 24 V)
RTAC
X2
1 SHLD
2 SHLD
1 3 A+
4 A-
2 5 B+
6 B-
0 7 Z+
8 Z-
VCC 0V
X1
1 0V
2 0V
3 V OUT
4 +15V
Encoder supply 15V
5 V IN
voltage selection 24V
6 +24V
(15 or 24 V)
RTAC
X2
1 SHLD
2 SHLD
1 3 A+
4 A-
2 5 B+
6 B-
0 7 Z+
8 Z-
VCC 0V
24V: 1.8…2.2 kΩ
15V: 1.0…1.5 kΩ
0.5 W
X1
1 0V
2 0V
3 V OUT
4 +15V
Encoder supply 15V
5 V IN
voltage selection 24V
6 +24V
(15 or 24 V)
Figure 3-5 Wiring of pulse encoders with open collector (sinking) outputs.
RTAC
X2
1 SHLD
2 SHLD
1 3 A+
4 A-
2 5 B+
6 B-
0 7 Z+
8 Z-
VCC 0V
24V: 1.8…2.2 kΩ
15V: 1.0…1.5 kΩ
0.5 W
X1
1 0V
2 0V
3 V OUT
4 +15V
Encoder supply 15V
5 V IN
voltage selection 24V
6 +24V
(15 or 24 V)
Figure 3-6 Wiring of pulse encoders with open emitter (sourcing) outputs.
Dimensions:
34 mm
CHASSIS
RTAC-01
PULSE ENCODER INTERFACE
GND
12345678 123456
SHLD
F0 1
SHLD
BCDE
23
45
67
CHA 89A
CHA+
CHB
CHA-
CHB+
X2 WD/
95 mm
INIT
CHB-
NODE ID
CHZ+
CHZ-
0V
0V
V OUT
+15V
X1
V IN
+24V
20
62 mm
mm
Encoder interface:
• CH A, CH B, CH Z, differential or single-ended
• Output voltage 1: +24 V DC ±10%, 5 W max., short-
circuit proof
• Output voltage 2: +15 V DC ±10%, 5 W max., short-
circuit proof
• Signal levels:
"1" >7.6 V, "0" < 5 V (for 15 V supply)
"1" >12.2 V, "0" < 8 V (for 24 V supply)
• Frequency: 200 kHz (max.)
• Speed feedback resolution: 0.00305% (15 bits)
• Speed feedback accuracy: 50 ppm
• Maximum encoder cable length:
- 300 m (differential push-pull)
- 200 m (single-ended push-pull)
- 100 m (open collector or emitter)
• Isolated from the logic and earth. Test voltage:
1.5 kV AC, 1 minute
General
• Max. power consumption:
140 mA (5 V) + 55 mA (24 V)
• Estimated min. lifetime: 100 000 h
• All materials UL/CSA-approved
• Complies with EMC standards EN 50081-2 and
EN 50082-2
Hardware Manual
ACS800-11 Drives (5.5 to 110 kW)
ACS800-U11 Drives (7.5 to 125 hp)
List of related manuals
Drive hardware manuals and guides Code (English)
ACS800-11/U11 Drives Hardware Manual (5.5 to 110 kW, 7.5 to 125 hp) 3AFE68367883
You can find manuals and other product documents in PDF format on the Internet. See section
Document library on the Internet on the inside of the back cover. For manuals not available in the
Document library, contact your local ABB representative.
ACS800-11/U11 manuals
ACS800-11 Drives
5.5 to 110 kW
ACS800-U11 Drives
7.5 to 125 hp
Hardware Manual
3AFE68367883 Rev C
EN
EFFECTIVE: 2013-03-04
Safety instructions
Safety instructions
6
WARNING! Ignoring the following instructions can cause physical injury or death, or
damage to the equipment:
• Only qualified electricians are allowed to install and maintain the drive.
• Never work on the drive, motor cable or motor when main power is applied.
After disconnecting the input power, always wait for 5 min to let the intermediate
circuit capacitors discharge before you start working on the drive, motor or
motor cable.
Always ensure by measuring with a multimeter (impedance at least 1 Mohm)
that:
1. voltage between drive input phases U1, V1 and W1 and the frame is close to
0 V.
2. voltage between terminals UDC+ and UDC- and the frame is close to 0 V.
• Do not work on the control cables when power is applied to the drive or to the
external control circuits. Externally supplied control circuits may cause
dangerous voltages inside the drive even when the main power on the drive is
switched off.
• Do not make any insulation or voltage withstand tests on the drive or drive
modules.
• When reconnecting the motor cable, always check that the phase order is
correct.
• Do not change the electrical installations of the drive except for the essential
control and power connections. Changes may affect the safety performance or
operation of the drive unexpectedly. All customer-made changes are on the
customer's responsibility.
Note:
• The motor cable terminals on the drive are at a dangerously high voltage when
the input power is on, regardless of whether the motor is running or not.
Safety instructions
7
• At installation sites above 2000 m (6562 ft), the terminals of the RMIO board
and optional modules attached to the board do not fulfil the Protective Extra
Low Voltage (PELV) requirements stated in EN 50178 and EN 61800-5-1.
• The Safe torque off function (option +Q967) does not remove the voltage from
the main and auxiliary circuits.
Grounding
These instructions are intended for all who are responsible for the grounding of the
drive.
WARNING! Ignoring the following instructions can cause physical injury, death,
increased electromagnetic interference and equipment malfunction:
• Ground the drive, motor and adjoining equipment to ensure personnel safety in
all circumstances, and to reduce electromagnetic emission and pick-up.
• Drives with EMC filter option +E202 or +E200 are not suitable for use in an IT
system (an ungrounded power system or a high-resistance-grounded [over
30 ohms] power system). Before connecting the drive to the power system,
disconnect the EMC filter capacitors as described in section IT (ungrounded)
systems on page 70.
Note:
• Power cable shields are suitable for equipment grounding conductors only
when adequately sized to meet safety regulations.
Safety instructions
8
WARNING! Ignoring the following instructions can cause physical injury or death,
or damage to the equipment:
• ACS800-11: The drive is heavy. Do not lift it alone. Do not lift the unit by the
front cover. Place the unit only on its back.
Do not tilt!
• Make sure that dust from drilling does not enter the drive when installing.
Electrically conductive dust inside the unit may cause damage or
malfunctioning.
Safety instructions
9
WARNING! Ignoring the following instructions can cause damage to the printed
circuit boards:
• Handle the fibre optic cables with care. When unplugging optic cables, always
grab the connector, not the cable itself. Do not touch the ends of the fibres with
bare hands as the fibre is extremely sensitive to dirt. The minimum allowed
bend radius is 35 mm (1.4 in.).
Safety instructions
10
Operation
These warnings are intended for all who plan the operation of the drive or operate
the drive.
WARNING! Ignoring the following instructions can cause physical injury or death,
or damage to the equipment:
• Before adjusting the drive and putting it into service, make sure that the motor
and all driven equipment are suitable for operation throughout the speed range
provided by the drive. The drive can be adjusted to operate the motor at
speeds above and below the speed provided by connecting the motor directly
to the power line.
• Do not activate automatic fault reset functions of the Standard Control Program
if dangerous situations can occur. When activated, these functions will reset
the drive and resume operation after a fault.
• Do not control the motor with the disconnecting device (disconnecting means);
instead, use the control panel keys and , or commands via the I/O
board of the drive. The maximum allowed number of charging cycles of the DC
capacitors (i.e. power-ups by applying power) is five in ten minutes.
• The Safe torque off function (option +Q967) can be used for stopping the drive
in emergency stop situations. In the normal operating mode, use the Stop
command instead.
Note:
• If an external source for start command is selected and it is ON, the drive (with
Standard Control Program) will start immediately after fault reset unless the
drive is configured for 3-wire (a pulse) start/stop.
• When the control location is not set to Local (L not shown in the status row of
the display), the stop key on the control panel will not stop the drive. To stop
the drive using the control panel, press the LOC/REM key and then the stop
key .
Safety instructions
11
WARNING! Do not work on the drive when the permanent magnet motor is rotating.
Also, when the supply power is switched off and the inverter is stopped, a rotating
permanent magnet motor feeds power to the main circuit of the drive including the
input power terminals.
Before installation and maintenance work on the drive:
• Stop the motor.
• Ensure that the motor cannot rotate during work.
• Ensure that there is no voltage on the drive power terminals:
Alternative 1) Disconnect the motor from the drive with a safety switch or by other
means. Measure that there is no voltage present on the drive input, output or DC
terminals (U1, V1, W1, U2, V2, W2, UDC+, UDC-).
Alternative 2) Measure that there is no voltage present on the drive input, output
or DC terminals (U1, V1, W1, U2, V2, W2, UDC+, UDC-). Ground the drive output
terminals temporarily by connecting them together as well as to the PE.
Alternative 3) If possible, both of the above.
WARNING! Do not run the motor over the rated speed. Motor overspeed leads to
overvoltage which may damage the capacitors in the intermediate circuit of the drive.
Safety instructions
12
Safety instructions
13
Table of contents
Safety instructions
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Use of warnings and notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Mechanical installation and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Printed circuit boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Fibre optic cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Permanent magnet motor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Start-up and operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table of contents
Table of contents
14
Mechanical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Unpacking the unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Checking the delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Moving the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Before installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Requirements for the installation site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Free space around the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Mounting the drive on the wall. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Units without vibration dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Units with vibration dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Cabinet installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Preventing cooling air recirculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Unit above another . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Installing cabinet duct plates (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Installation kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Before you start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Assembly drawing for cabinet duct plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Table of contents
15
Electrical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Checking the insulation of the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Supply cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Motor and motor cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
IT (ungrounded) systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Disconnecting the EMC filter capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Units of frame size R5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Units of frame size R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Connecting the power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Conductor stripping lengths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Allowed wire sizes, tightening torques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Wall installed units (European version) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Power cable installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Wall installed units (US version) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Warning sticker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Cabinet installed units (IP00, UL type open) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Connecting the control cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Terminals .............................................................. 78
360 degrees grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Connecting the shield wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Cabling of I/O and fieldbus modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Pulse encoder module cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Fastening the control cables and covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Installation of optional modules and PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Connecting a PC to the motor-side RMIO board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Table of contents
16
Installation checklist
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Table of contents
17
Line-side converter actual signals and parameters in the motor-side converter control program . 103
Terms and abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Actual signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
09 ACTUAL SIGNALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
95 HARDWARE SPECIF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
ACS800-11/U11 specific parameters in the IGBT Supply Control Program . . . . . . . . . . . . . . . . . 105
Terms and abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
16 SYSTEM CTR INPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
31 AUTOMATIC RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Fixed parameters with the ACS800-11 and ACS800-U11 . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Maintenance
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Maintenance intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Heatsink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Main cooling fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Fan replacement (R5, R6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Additional fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Replacement (R5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Replacement (R6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Reforming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Fault tracing
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Faults and warnings displayed by the CDP 312R control panel . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Conflicting ID numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Technical data
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
IEC data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Temperature derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Altitude derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Mains cable fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Cable types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Cable entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Dimensions, weights and noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
NEMA data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Table of contents
18
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Input cable fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Cable types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Cable Entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Dimensions and weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Input power connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Motor connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
AGPS-11C (option +Q950) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
ASTO-11C (option +Q967) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
CE marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Compliance with the European Low Voltage Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Compliance with the European EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Compliance with the European Machinery Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Applicable standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Compliance with EN 61800-3:2004 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
First environment (drive of category C2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Second environment (drive of category C3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Second environment (drive of category C4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
“C-tick” marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
UL/CSA markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
UL checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Dimensional drawings
Frame size R5 (IP21, UL type 1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Frame size R6 (IP21, UL type 1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Cabinet duct plates (optional), frame size R5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Cabinet duct plates (optional), frame size R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Package (frame size R5). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Package (frame size R6). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
AGPS board with enclosure (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
ASTO board with enclosure (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
External +24 V power supply for the RMIO boards via terminal X34
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Parameter settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Connecting +24 V external power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
RMIO board of the motor-side converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
RMIO board of the line-side converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Frame size R5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Frame size R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Table of contents
19
Further information
Product and service inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Product training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Providing feedback on ABB Drives manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Document library on the Internet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Table of contents
20
Table of contents
21
Intended audience
This manual is intended for people who plan the installation, install, commission, use
and service the drive. Read the manual before working on the drive. The reader is
expected to know the fundamentals of electricity, wiring, electrical components and
electrical schematic symbols.
This manual is written for readers worldwide. Both SI and imperial units are shown.
Special US instructions for installations within the United States that must be
installed per the National Electrical Code and local codes are marked with (US).
Contents
The chapters of this manual are briefly described below.
Safety instructions give safety instructions for the installation, commissioning,
operation and maintenance of the drive.
Introduction to this manual lists the steps in checking the delivery and installing and
commissioning the drive and refers to chapters/sections in this manual and other
manuals for particular tasks.
Operation principle and hardware description describes the drive.
Mechanical installation instructs in how to place and mount the drive.
Planning the electrical installation instructs in the motor and cable selection,
protections and cable routing.
Electrical installation shows how to wire the drive.
Installation of the AGPS board (Prevention of unexpected start-up, +Q950)
describes the electrical installation of the optional Prevention of unexpected start-up
function (+Q950).
Installation of the ASTO board (Safe torque off, +Q967) describes the electrical
installation of the optional Safe torque off function (+Q967).
Motor control and I/O board (RMIO) shows the external control connections to the
I/O board.
Installation checklist contains a list for checking the mechanical and electrical
installation of the drive.
Start-up and use contains guide lines of the start-up and use of the drive
Actual signals and parameters contains listings of parameters specific to the
ACS800-11 and ACS800-U11.
Maintenance contains preventive maintenance instructions.
Fault tracing contains guidelines for fault tracing.
Technical data contains the technical specifications of the drive, e.g. the ratings,
sizes and technical requirements and provisions for fulfilling the requirements for CE
and other markings.
Dimensional drawings contains the dimensional drawings of the drive.
External +24 V power supply for the RMIO boards via terminal X34 describes how to
connect an external +24 V power supply for the RMIO board via terminal X34.
Task See
Identify the frame size of your drive: R5 or R6. Technical data / IEC data or NEMA data
Unpack and check the units. Mechanical installation: Unpacking the unit.
Check that all necessary optional modules and If the converter has been non-operational for
equipment are present and correct. more than one year, the converter DC link
Only intact units may be started up. capacitors need to be reformed, see
Maintenance: Capacitors.
Check the insulation of the motor and the motor Electrical installation: Checking the insulation of
cable. the installation
Task See
Connect the control and auxiliary control cables. Electrical installation, Motor control and I/O
board (RMIO), and the optional module manual
delivered with the module.
Product overview
The ACS800-11/U11 is a four-quadrant wall mountable drive for controlling AC
motors. The main circuit consists of two IGBT converters, a line-side converter and a
motor-side converter, integrated into the same frame.
Cooling fan
Control panel
CDP 312R
Heatsink
Front cover
Frame size R6
I/O terminals
U1 V1 W1 U2 V2 W2
PE
I/O terminals
X41
U1 V1 W1 U2 V2 W2
PE
Terms
Line-side converter: A converter that is connected to the supply network and is
capable of transferring energy from the network to the DC link or from the DC link to
the network.
Motor-side converter: A converter that is connected to the motor and controls the
motor operation.
Four-quadrant operation: Operation of a machine as a motor or generator in
quadrants I, II, III and IV as shown below. In quadrants I and III, the machine
operates as a motor, whereas in quadrants II and IV as a generator (regenerative
braking).
Torque
II I
Speed
III IV
Operation principle
The line-side and motor-side converters consist of six insulated gate bipolar
transistors with free wheeling diodes.
The converters have their own control programs. The parameters of both programs
can be viewed and changed using one control panel. The control panel can be
switched between the converters as described in chapter Start-up and use.
Line-side converter
The IGBT supply module rectifies three phase AC current to direct current for the
intermediate DC link of the drive. The intermediate DC link is further supplying the
motor-side converter that runs the motor. The line filter suppresses the AC voltage
and current harmonics.
The IGBT supply module is a four-quadrant switching-mode converter, i.e. the power
flow through the converter is reversible. By default, the converter controls the DC link
voltage to the peak value of the line-to-line voltage. The DC voltage reference can be
set also higher by a parameter. The control of the IGBT power semiconductors is
based on the Direct Torque Control (DTC) method also used in the motor control of
the drive. Two line currents and the DC link voltage are measured and used for the
control.
t (ms)
i (A)
t (ms)
Example spectra of the current and voltage distortion at the output of the transformer
are shown below. Each harmonic is presented as compared to fundamental voltage
(reference value = 1). n denotes the ordinal number of the harmonic.
Test 13 Test 13
1.6 1.6
1.4 1.4
1.2 1.2
1.0 1.0
0.6 0.6
0.4 0.4
0.2 0.2
0.0 0.0
n n
2
5
8
17
20
23
32
35
44
47
50
11
14
26
29
38
41
35
2
8
11
14
17
20
23
26
29
32
38
41
44
47
50
Motor control
The motor control is based on the Direct Torque Control (DTC) method. Two phase
currents and DC link voltage are measured and used for the control. The third phase
current is measured for earth fault protection.
ID number 1
RMBP, RETA, RRIA
ID number 2
Input = ~ Output
power power Application or RTAC
~ = Line-side
specific program Optional module 2: RTAC,
converter
and motor RAIO, RRIA or RDIO
control program
UDC+ UDC- control program DDCS communication
Main circuit and control diagram
U1 U2
K1 V2
V1 M
W2 3~
W1
AI3
FIELD BUS
+ 24 VDC
-
Type code
The type code contains information on the specifications and configuration of the
drive. The first digits from left express the basic configuration (for example,
ACS800-11-0025-3 or ACS800-U11-0025-3). The optional selections are given
thereafter, separated by plus signs (for example, +E200 and +K454). The main
selections are described below. Not all selections are available for all types. For
more information, refer to ACS800 Ordering Information (EN code: 3AFY64556568,
available on request).
Selection Alternatives
Product series ACS800 product series
Type 11 Regenerative, wall mounted. When no options are selected: IP21,
Control Panel CDP 312R, DDCS communication option module
RDCO-03, no EMC filter, Standard Control Program, cable connection
box (cabling from below), boards with coating, one set of English
manuals.
U11 Regenerative, wall mounted (USA). When no options are selected: UL
type 1, Control Panel CDP 312R, DDCS communication option module
RDCO-03, no EMC filter, US version of the Standard Control Program
(three-wire start/stop as default setting), US gland/conduit plate, boards
with coating, one set of English manuals.
Size Refer to Technical data: IEC data or NEMA data.
Voltage range 2 208/220/230/240 VAC
(nominal rating in bold) 3 380/400/415 VAC
5 380/400/415/440/460/480/500 VAC
7 525/575/600/690 VAC
Option codes (+ codes)
Filters E200 EMC/RFI filter for second environment TN (grounded) system,
unrestricted distribution.
E202 EMC/RFI filter for first environment TN (grounded) system, restricted
distribution.
Cabling H357 European lead-through plate
H358 US/UK gland/conduit plate
Control panel 0J400 No control panel
Fieldbus K... Refer to ACS800 Ordering Information (EN code: 3AFY64556568).
I/O L...
control program N...
Manual language R...
Safety features Q950 Prevention of unexpected start-up
Q967 Safe torque off (STO) function without safety relay
Specialities P904 Extended warranty
Duct plates for cabinet installation can be ordered with kit codes:
frame size R5: 68654122
frame size R6: 68654131
Mechanical installation
Mechanical installation
38
To unpack the package, cut the bands (A) and remove the outer box (B) and sleeve
(C).
3AUA0000075717
Mechanical installation
39
The type designation label is attached to the heatsink and the serial number label to
the lower part of the back plate of the unit. Example labels are shown below.
Mechanical installation
40
Before installation
The drive must be installed in an upright position with the cooling section facing a
wall. Check the installation site according to the requirements below. Refer to
chapter Dimensional drawings for frame details.
WARNING! Do not remove the protective film that covers the unit before the
installation procedure is complete. It protects the unit from pieces of wire cuttings or
other solid particles that can penetrate the unit during installation. Remove the film
just before starting up the unit.
Mechanical installation
41
200 [7.9]
50 [2.0] 50 [2.0]
200 [7.9]
Mechanical installation
42
Cabinet installation
The drive can be installed in a cabinet without the plastic front, top and connection
box covers and without the lead-through plate. Vibration dampers are not needed.
The required distance between parallel units is 50 millimetres (1.97 in.) in
installations without the front cover. The cooling air entering the unit must not exceed
+40 °C (+104 °F).
You can also use duct plates in the cabinet installation, see section Installing cabinet
duct plates (optional) on page 43.
HOT
AREA
Main air flow out
COOL AREA
Mechanical installation
43
Mechanical installation
44
Screws are not included in the installation kit. The following screws are needed:
• frame size R5:
18 pieces: M5X12, torque 3 N·m (2.2 lbf·ft)
2 pieces: M4X16, torque 1.2 N·m (0.9 lbf·ft)
2 pieces: M4X12, torque 1.2 N·m (0.9 lbf·ft)
• frame size R6:
20 pieces: M5X12, torque 3 N·m (2.2 lbf·ft)
2 pieces: M4X25, torque 1.2 N·m (0.9 lbf·ft)
2 pieces: M4X12, torque 1.2 N·m (0.9 lbf·ft)
Before you start
Prepare the cabinet by following the requirements given in this manual and the
dimensional drawings on pages 134 and 135.
The drive must always be fixed into the cabinet by using the original 4 fixing holes on
the bottom plate, never by the collars only.
The cabinet supports (E) can be installed before or after installing the drive, but it
may be easier to install the drive before the supports.
Installation
The following figure shows the installation procedure for a drive of frame size R5. In
frame size R6, the design of the bottom collar (D) is slightly different.
1. After the drive and cabinet supports (E) have been installed, install the left (A) and
right collars (B) by pushing them first in the grooves on both sides of the drive,
and fasten them with 10 pcs of M5x12 screws (frame size R6: 12 pcs) in the
cabinet supports.
2. Fix 4 pcs of M5x12 screws in the left (A) and right collars (B), and install the top
collar (C) against the left and right collars through the screws.
3. Push down the top collar in the groove on the top of the drive and tighten the
screws.
4. Fix 4 pcs of M5x12 screws in the left (A) and right collars (B), and install the
bottom collar (D) against the left and right collars through the screws.
5. Push up the bottom collar in the groove on the bottom of the drive and tighten the
screws.
6. Fix the bottom collar to the drive with 2 pcs of M4x16 screws (frame size R6:
M4x25).
7. Secure the bottom collar to the drive with additional 2 pcs of M4x12 screws.
Note: If you install other parts in the cabinet, make sure that the top and bottom
collars can be removed easily for maintenance purposes.
Mechanical installation
45
B
C
A
2
1 4
Mechanical installation
46
Mechanical installation
47
5. Ensure that the motor insulation system withstands the maximum peak voltage in
the motor terminals. See the Requirements table below for the required motor
insulation system and drive filtering.
Example 1: When the supply voltage is 440 V and a drive with a diode supply is
operating in motor mode only, the maximum peak voltage in the motor terminals
can be approximated as follows: 440 V · 1.35 · 2 = 1190 V. Check that the motor
insulation system withstands this voltage.
Example 2: When the supply voltage is 440 V and the drive is equipped with an
IGBT supply, the maximum peak voltage in the motor terminals can be
approximated as follows: 440 V · 1.41 · 2 = 1241 V. Check that the motor
insulation system withstands this voltage.
Requirements table
The following table shows how to select the motor insulation system and when an
optional drive du/dt and common mode filters and insulated N-end (non-drive end)
motor bearings are required. Ignoring the requirements or improper installation may
shorten motor life or damage the motor bearings and voids the warranty.
3.0 5.5
ÛLL/UN 5.0
2.5 du/dt
------------- (1/s)
4.5 UN
2.0 4.0
3.5
1.5
3.0
ÛLL/UN
1.0 2.5
du/dt
------------- (1/s)
UN 2.0
0.5
1.5
0.0 1.0
100 200 300 100 200 300
Note 10: Sine filters protect the motor insulation system. Therefore, du/dt filter can
be replaced with a sine filter. The peak phase-to-phase voltage with the sine filter is
approximately 1.5 × UN.
Supply connection
Fuses
See section Thermal overload and short-circuit protection.
The drive protects the motor cable and motor in a short-circuit situation when the
motor cable is dimensioned according to the nominal current of the drive.
Short-circuit protection
Protect the input cable and drive against short-circuit according to the following
guide lines.
Circuit diagram Drive type Short-circuit
protection
DRIVE IS NOT EQUIPPED WITH INPUT FUSES
ACS800-11 Protect the drive and
Distribution Drive or drive ACS800-U11 input cable with fuses.
board Input cable module See footnote 1).
1)
~ M
~ 3~
1) Size the fuses according to local safety regulations, appropriate input voltage and
the rated current of the drive. Only gG and aR fuses are allowed, see section Mains
cable fuses on page 117.
Standard gG fuses (US: CC or T for ACS800-U11) will protect the input cable in
short-circuit situations, restrict drive damage and prevent damage to adjoining
equipment in case of a short-circuit inside the drive.
Check that the operating time of the fuse is below 0.1 seconds. The operating
time depends on the fuse type (gG or aR), supply network impedance and the cross-
sectional area, material and length of the supply cable. In case the 0.1 seconds
operating time is exceeded with gG fuses (US: CC/T/L), ultrarapid (aR) fuses will in
most cases reduce the operating time to an acceptable level. The US fuses must be
of the “non-time delay” type.
For fuse ratings, see chapter Technical data.
Note: Circuit breakers must not be used.
WARNING! The Prevention of unexpected start-up function does not disconnect the
voltage of the main and auxiliary circuits from the drive. Therefore maintenance work
on electrical parts of the drive or the motor can only be carried out after isolating the
drive system from the main supply.
Note: The Prevention of unexpected start-up function is not intended for stopping
the drive. If the Prevention of unexpected start-up function is activated when the
drive is running, the control voltage of the inverter power semiconductors is cut off
and the motor coasts to a stop.
For detailed instructions for installation, start-up, use and maintenance of the
function, see chapter Installation of the AGPS board (Prevention of unexpected
start-up, +Q950).
WARNING! The Safe torque off function does not disconnect the voltage of the main
and auxiliary circuits from the drive. Therefore maintenance work on electrical parts
of the drive or the motor can only be carried out after isolating the drive system from
the main supply.
Note: The Safe torque off function can be used for stopping the drive in emergency
stop situations. In the normal operating mode, use the Stop command instead. If a
running drive is stopped by using the function, the drive will trip and stop by coasting.
If this is not acceptable, e.g. causes danger, the drive and machinery must be
stopped using the appropriate stopping mode before using this function.
Note concerning permanent magnet motor drives in case of a multiple IGBT
power semiconductor failure: In spite of the activation of the Safe torque off
function, the drive system can produce an alignment torque which maximally rotates
the motor shaft by 180/p degrees. p denotes the pole pair number.
For more information on the installation of the Safe torque off function, see chapter
Installation of the ASTO board (Safe torque off, +Q967).
For more information on the Safe torque off function and the relevant safety data,
see ACS800-01/04/11/31/104/104LC Safe torque off function (+Q967), Application
guide (3AUA0000063373 [English]).
An example circuit diagram is shown below.
General rules
Dimension the mains (input power) and motor cables according to local
regulations:
• The cable must be able to carry the drive load current. See chapter Technical
data for the rated currents.
• The cable must be rated for at least 70 °C (158 °F) maximum permissible
temperature of conductor in continuous use. For US, see Additional US
requirements.
• The inductance and impedance of the PE conductor/cable (grounding wire) must
be rated according to permissible touch voltage appearing under fault conditions
(so that the fault point voltage will not rise excessively when a ground fault
occurs).
• 600 VAC cable is accepted for up to 500 VAC. 750 VAC cable is accepted for up
to 600 VAC. For 690 VAC rated equipment, the rated voltage between the
conductors of the cable should be at least 1 kV.
For drive frame size R5 and larger, or motors larger than 30 kW (40 hp), symmetrical
shielded motor cable must be used (figure below). A four-conductor system can be
used up to frame size R4 with up to 30 kW (40 hp) motors, but shielded symmetrical
motor cable is recommended.
Recommended
Symmetrical shielded cable: three phase conductors A separate PE conductor is required if the conductivity
and a concentric or otherwise symmetrically of the cable shield is < 50 % of the conductivity of the
constructed PE conductor, and a shield phase conductor.
PE conductor Shield
and shield Shield
PE
PE
PE Shield
A four-conductor system:
three phase conductors
and a protective
conductor
Not allowed for motor cables Not allowed for motor cables with phase
conductor cross section larger than 10 mm2
[motors > 30 kW (40 HP)].
Cable core
Additional US requirements
Type MC continuous corrugated aluminium armor cable with symmetrical grounds or
shielded power cable must be used for the motor cables if metallic conduit is not
used. For the North American market, 600 VAC cable is accepted for up to 500 VAC.
1000 VAC cable is required above 500 VAC (below 600 VAC). For drives rated over
100 amperes, the power cables must be rated for 75 °C (167 °F).
Conduit
Where conduits must be coupled together, bridge the joint with a ground conductor
bonded to the conduit on each side of the joint. Bond the conduits also to the drive
enclosure. Use separate conduits for input power, motor, brake resistor, and control
wiring. When conduit is employed, type MC continuous corrugated aluminium armor
cable or shielded cable is not required. A dedicated ground cable is always required.
Note: Do not run motor wiring from more than one drive in the same conduit.
Armored cable / shielded power cable
Six conductor (3 phases and 3 ground) type MC continuous corrugated aluminium
armor cable with symmetrical grounds is available from the following suppliers (trade
names in parentheses):
• Anixter Wire & Cable (Philsheath)
• BICC General Corp (Philsheath)
• Rockbestos Co. (Gardex)
• Oaknite (CLX).
Shielded power cables are available from Belden, LAPPKABEL (ÖLFLEX) and
Pirelli.
If there are power factor compensation capacitors in parallel with the three phase
input of the drive:
1. Do not connect a high-power capacitor to the power line while the drive is
connected. The connection will cause voltage transients that may trip or even
damage the drive.
2. If capacitor load is increased/decreased step by step when the AC drive is
connected to the power line: Ensure that the connection steps are low enough not
to cause voltage transients that would trip the drive.
3. Check that the power factor compensation unit is suitable for use in systems with
AC drives i.e. harmonic generating loads. In such systems, the compensation unit
should typically be equipped with a blocking reactor or harmonic filter.
WARNING! Never connect the supply power to the drive output terminals U2, V2
and W2. If frequent bypassing is required, employ mechanically connected switches
or contactors. Mains (line) voltage applied to the output can result in permanent
damage to the unit.
WARNING! When the DTC motor control mode is in use, never open the output
contactor while the drive controls the motor. The DTC motor control operates
extremely fast, much faster than it takes for the contactor to open its contacts. When
the contactor starts opening while the drive controls the motor, the DTC control will
try to maintain the load current by immediately increasing the drive output voltage to
the maximum. This will damage, or even burn the contactor completely.
RMIO
Relay outputs
Varistor X25
1 RO1
2 RO1
230 VAC
3 RO1
RC filter X26
1 RO2
2 RO2
230 VAC
3 RO2
Diode X27
1 RO3
2 RO3
24 VDC
3 RO3
a b
A double-shielded twisted A single-shielded twisted
pair cable pair cable
Relay cable
The cable type with braided metallic screen (e.g. ÖLFLEX by LAPPKABEL,
Germany) has been tested and approved by ABB.
WARNING! IEC 60664 requires double or reinforced insulation between live parts
and the surface of accessible parts of electrical equipment which are either non-
conductive or conductive but not connected to the protective earth.
To fulfil this requirement, the connection of a thermistor (and other similar
components) to the digital inputs of the drive can be implemented in three alternate
ways:
1. There is double or reinforced insulation between the thermistor and live parts of
the motor.
2. Circuits connected to all digital and analogue inputs of the drive are protected
against contact and insulated with basic insulation (the same voltage level as the
drive main circuit) from other low voltage circuits.
3. An external thermistor relay is used. The insulation of the relay must be rated for
the same voltage level as the main circuit of the drive. For connection, see
ACS800 Firmware Manual.
WARNING! Protect against direct contact when installing, operating and servicing
the RMIO board wiring and optional modules attached to the board. The Protective
Extra Low Voltage (PELV) requirements stated in EN 50178 and IEC 61800-5-1 are
not fulfilled at altitudes above 2000 m (6562 ft).
Motor cable
Drive
min 300 mm (12 in.)
Power cable
Control cables
230 V 230 V
24 V (120 V) 24 V (120 V)
Not allowed unless the 24 V cable is Lead 24 V and 230 V (120 V) control
insulated for 230 V (120 V) or insulated cables in separate ducts inside the
with an insulation sleeving for 230 V cabinet.
(120 V).
Electrical installation
WARNING! The work described in this chapter may only be carried out by a qualified
electrician. Follow the Safety instructions on the first pages of this manual. Ignoring
the safety instructions can cause injury or death.
Make sure that the drive is disconnected from the mains (input power) during
the installation. If the drive is already connected to the mains, wait for 5 min
after disconnecting mains power.
Drive
Do not make any voltage tolerance or insulation resistance tests on any part of the
drive as testing can damage the drive. Every drive has been tested for insulation
between the main circuit and the chassis at the factory. Also, there are voltage-
limiting circuits inside the drive which cut down the testing voltage automatically.
Supply cable
Check the insulation of the supply (input) cable according to local regulations before
connecting to the drive.
Electrical installation
70
U1
M
V1
3~
ohm W1
PE
IT (ungrounded) systems
Drives with EMC filter option +E202 or +E200 are not suitable for use in an IT
(ungrounded) system as such. Disconnect the EMC filter capacitors before
connecting the drive to an ungrounded system as described below.
Electrical installation
71
Note: When the capacitors of EMC filter +E202 or +E200 are disconnected, the
EMC Directive requirements in the second environment will not be fulfilled. See
chapter Technical data: CE marking.
Units of frame size R6
Remove the two screws shown below. Note: Depending on the EMC filter type and
the nominal voltage of the drive, there may be only one screw.
Note: When the capacitors of EMC filter +E202 are disconnected, the EMC Directive
requirements may not be fulfilled in first environment, but are fulfilled in the second
environment.
When the capacitors of EMC filter +E200 are disconnected, the EMC Directive
requirements in the second environment are still fulfilled. See chapter Technical
data: CE marking.
Electrical installation
72
Diagram
Drive
INPUT OUTPUT
PE U1 V1 W1 UDC+ UDC- U2 V2 W2
1) 2)
3) 4)
(PE) PE (PE)
5)
V1
U1 W1
For alternatives, see
Planning the electrical 3 ~
installation: Motor
Disconnecting device
(disconnecting means) L1 L2 L3
b > 1/5 · a
5) Use a separate grounding cable if the conductivity of
the cable shield is < 50% of the conductivity of the b
a
phase conductor and there is no symmetrically
constructed grounding conductor in the cable (see
Planning the electrical installation: Selecting the
power cables).
Note:
If there is a symmetrically constructed grounding
conductor in the motor cable in addition to the
conductive shield, connect the grounding conductor to
the grounding terminal at the drive and motor ends.
Do not use an asymmetrically constructed motor cable
for motors > 30 kW (40 hp). Connecting its fourth
conductor at the motor end increases bearing currents
and causes extra wear.
Electrical installation
73
Electrical installation
74
9 9
1
8
U1 V1 W1 UDC+ UDC- U2 V2 W2
PE 6
5
5
Electrical installation
75
Frame sizes R6: Cable lug installation [16 to 70 mm2 (6 to 2/0 AWG) cables]
5 5
9 9
Frame size R6: Screw terminal installation [95 to 210 mm2 (3/0 to 400 MCM)] cables
PE 6
a
a. Connect the cable to the terminal.
b. Connect the terminal to the drive.
WARNING! If the wire size is less than
95 mm2 (3/0 AWG), a cable lug must
5 5 be used. A cable of wire size less than
95 mm2 (3/0 AWG) connected to this
terminal will loosen and may damage
the drive.
Electrical installation
76
8 8
3 3
2 4 4
See Wall installed units (European version) for cabling figures. In case of a cable
lug installation, use UL listed cable lugs and tools given below or corresponding
to meet UL requirements.
Electrical installation
77
Warning sticker
There are warning stickers in different languages inside the packing box of the drive.
Attach a warning sticker in the language of your choice onto the plastic skeleton
above the power cable terminals.
Electrical installation
78
Terminals
Control panel
Optional module 2
Optional module 1
Control cable
grounding: see Detachable connection terminals (pull up)
section 360
degrees
grounding
Electrical installation
79
Insulation
4
3
2
1
When the outer surface of the shield is covered with non-conductive material:
• Strip the cable carefully (do not cut the grounding wire and the shield)
• Turn the shield inside out to expose the conductive surface.
• Wrap the grounding wire around the conductive surface.
• Slide a conductive clamp onto the conductive part.
• Fasten the clamp to the grounding plate with a screw as close as possible to the
terminals where the wires are about to be connected.
Electrical installation
80
Module
As short as possible
Shield
4
3
2
1
Electrical installation
81
Electrical installation
82
In the example below, one AIMA-01 I/O module adapter is connected to the RMIO
boards of the line-side and motor-side converters.
RDCO RDCO
CH0 CH1
AIMA-01 I/O
module adapter
*) WARNING! In frame size R6, you must remove the top cover to reach the RMIO board.
Read and follow the Safety instructions on the first pages of this manual. Ignoring the safety
instructions can cause injury or death.
For more information, see AIMA-01 I/O Module Adapter User's Manual
(3AFE68295351 [English]).
Electrical installation
83
WARNING! Dangerous voltages can be present on the AGPS board even when the
115...230 V supply is switched off. Follow the Safety instructions on the first pages of
this manual and the instruction in this chapter when working on the AGPS board.
Make sure that the drive is disconnected from the mains (input power) and the
115...230 V source for the AGPS board is switched off during installation and
maintenance. If the drive is already connected to the mains, wait for 5 min after
disconnecting mains power.
WARNING! The supply voltage for the AGPS board is 115...230 V AC. If the board is
supplied with 24 V DC, the board is damaged and it needs to be replaced.
See
• page 27 for location of terminal block X41 of the drive
• page 85 for the circuit diagram
• page 137 for the dimensions of the AGPS board
• section AGPS-11C (option +Q950) in chapter Technical data for the technical
data of the board.
Note: Maximum cable length between AGPS terminal block X2 and the drive
terminal block is restricted to 10 metres (33 ft).
WARNING! Use only the AGPS cable delivered with the kit. Using another cable or
modifying the cable may cause a malfunction of the drive and the safety function.
• Connect a cable between connector X1 of the AGPS board (3) and the
115...230 V source.
• Fasten the enclosure cover back with screws.
X2
X1
115...230 V
3
Circuit diagram
This circuit diagram shows how the AGPS-11 kit is installed.
Drive
115/230 VAC
N
3AFE00374994
Ensure that the drive can be run and stopped freely during the start-up.
Stop the drive (if running), switch the input power off and isolate the drive from the power line by a
disconnector.
Check the Prevention of unexpected start-up circuit connections against the circuit diagram.
Test the operation of the Prevention of unexpected start-up function when the motor is stopped:
• Give a stop command for the drive (if running) and wait until the motor shaft is at standstill.
• Activate the Prevention of unexpected start-up function and give a start command for the drive.
• Ensure that the drive does not start and the motor stays at standstill.
• Deactivate the Prevention of unexpected start-up function.
Use
Activate the function as follows:
• Stop the drive. Use the stop key of the panel (local mode) or give the stop
command through the I/O or fieldbus interface.
• Open the switch activating the Prevention of unexpected start-up function of the
drive. -> The indication lamp (if installed) is lit.
• Lock the switch to the open position.
• Before starting the work on the machinery, ensure that the motor shaft is at
standstill (not freely rotating).
Inactivate the function in reverse order.
Maintenance
After the operation of the circuit is validated at start-up, it does not need any
maintenance. However, it is a good practice to check the operation of the function
when other maintenance routines of the machinery are carried out.
Dimensional drawing
See page 137.
WARNING! Dangerous voltages can be present at the ASTO board even when the
24 V supply is switched off. Follow the Safety instructions on the first pages of this
manual and the instruction in this chapter when working on the ASTO board.
Make sure that the drive is disconnected from the mains (input power) and the
24 V source for the ASTO board is switched off during installation and
maintenance. If the drive is already connected to the mains, wait for 5 min after
disconnecting mains power.
WARNING! The supply voltage for the ASTO-11C board is 24 V DC. If the board is
supplied with 230 V AC, the board is damaged and it needs to be replaced.
See
• page 27 for location of terminal block X41 of the drive
• page 89 for the circuit diagram
• page 138 for the dimensions of the ASTO-11C board
• section ASTO-11C (option +Q967) in chapter Technical data for the technical data
of the ASTO-11C board.
Note: Maximum cable length between ASTO terminal block X2 and the drive
terminal block is restricted to 3 metres (9.8 ft).
Connect the ASTO board as follows:
• Remove the cover of the enclosed ASTO unit by undoing the fixing screws (1).
• Ground the ASTO unit via the bottom plate of the enclosure or via terminal X1:2
or X1:4 of the ASTO board.
• Connect the cable delivered with the kit between terminal block X2 of the ASTO
board (2) and drive terminal block X41.
WARNING! Use only the ASTO cable delivered with the kit. Using another cable or
modifying the cable may cause a malfunction of the drive and the safety function.
• Connect a cable between connector X1 of the ASTO board (3) and the 24 V
source.
• Fasten the cover of the ASTO unit back with screws.
X2
X1
24 V
3
Circuit diagram
The diagram below shows the connection between the ASTO board and the drive
when it is ready. For an example diagram of a complete Safe torque off circuit, see
page 59.
3AUA0000072542
Dimensional drawing
See page 138.
WARNING! If the RMIO board is supplied from an external power source via
terminal X34, the loose end of the cable removed from the RMIO board terminal
must be secured mechanically to a location where it cannot come into contact with
electrical parts. If the screw terminal plug of the cable is removed, the wire ends
must be individually insulated.
Parameter settings
In Standard Control Program, set parameter 16.9 CTRL BOARD SUPPLY to
EXTERNAL 24V if the RMIO board is powered from an external supply.
Analogue outputs
Two programmable current outputs: 0 (4) to 20 mA, RL < 700 ohm
Resolution 0.1% (10 bit)
Inaccuracy ± 1% (Full Scale Range) at 25 °C (77 °F). Temperature coefficient: ± 200 ppm/°C
(± 111 ppm/°F) max.
Digital inputs
Six programmable digital inputs (common ground: 24 VDC, -15% to +20%) and a start
interlock input. Group isolated, can be divided in two isolated groups (see Isolation
and grounding diagram below).
Thermistor input: 5 mA, < 1.5 kohm “1” (normal temperature), > 4 kohm “0”
(high temperature), open circuit “0” (high temperature).
Internal supply for digital inputs (+24 VDC): short-circuit proof. An external 24 VDC
supply can be used instead of the internal supply.
Isolation test voltage 500 VAC, 1 min
Logical thresholds < 8 VDC “0”, > 12 VDC “1”
Input current DI1 to DI 5: 10 mA, DI6: 5 mA
Filtering time constant 1 ms
Relay outputs
Three programmable relay outputs
Switching capacity 8 A at 24 VDC or 250 VAC, 0.4 A at 120 VDC
Minimum continuous current 5 mA rms at 24 VDC
Maximum continuous current 2 A rms
Isolation test voltage 4 kVAC, 1 minute
The terminals on the RMIO board as well as on the optional modules attachable to the board fulfil the Protective Extra
Low Voltage (PELV) requirements stated in EN 50178 provided that the external circuits connected to the terminals also
fulfil the requirements and the installation site is below 2000 m (6562 ft). Above 2000 m (6562 ft), see page 67.
9 AO1+
10 AO1-
11 AO2+
12 AO2-
X22
1 DI1
2 DI2
3 DI3
4 DI4
Jumper J1 settings:
9 DGND1
Installation checklist
Checklist
Check the mechanical and electrical installation of the drive before start-up. Go
through the checklist below together with another person.
WARNING! Only qualified electricians are allowed to commission the drive. Read
and follow the Safety instructions on the first pages of this manual. Ignoring the
safety instructions can cause injury or death.
Check that...
MECHANICAL INSTALLATION
The ambient operating conditions are allowed. (See Mechanical installation, Technical data:
IEC data or NEMA data)
The unit is fixed properly on a vertical non-flammable wall. (See Mechanical installation.)
The cooling air will flow freely.
The motor and the driven equipment are ready for start. (See Planning the electrical
installation: Motor selection and compatibility, Technical data: Motor connection.)
ELECTRICAL INSTALLATION (See Planning the electrical installation, Electrical installation.)
The +E202 and +E200 EMC filter capacitors are disconnected if the drive is connected to an
IT (ungrounded) system. (See Electrical installation: IT (ungrounded) systems)
The capacitors are reformed if stored over one year, refer to Converter modules with
electrolytic DC capacitors in the DC link, Capacitor reforming instructions (3BFE64059629
[English]).
The drive is grounded properly.
The mains (input power) voltage matches the drive nominal input voltage.
The mains (input power) connections at U1, V1 and W1 and their tightening torques are OK.
Appropriate mains (input power) fuses and disconnector are installed.
The motor connections at U2, V2 and W2 and their tightening torques are OK.
The motor cable is routed away from other cables.
Installation checklist
98
Check that...
There are no power factor compensation capacitors in the motor cable.
The external control connections inside the drive are OK.
There are no tools, foreign objects or dust from drilling inside the drive.
Mains (input power) voltage cannot be applied to the output of the drive (with bypass
connection).
Drive, motor connection box and other covers are in place.
Installation checklist
99
WARNING! Only qualified electricians are allowed to commission the drive. Read
and follow the Safety instructions on the first pages of this manual. Ignoring the
safety instructions can cause injury or death.
Drives with option +Q950: Validate and perform the start-up procedure of the
Prevention of unexpected start-up function according to instructions given in chapter
Installation of the ASTO board (Safe torque off, +Q967).
Drives with option +Q967: Validate and perform the start-up procedure of the Safe
torque off function according to instructions given in ACS800-
01/04/11/31/104/104LC Safe torque off function (+Q967), Application guide
(3AUA0000063373 [English]).
Control panel
The drive is equipped with a control panel (type CDP 312R). The CDP 312R is the
user interface of the line-side converter and the motor-side converter of the drive,
providing the essential controls such as Start/Stop/Direction/Reset/Reference, and
the parameter settings for the control programs. More information on using the
control panel can be found in the Firmware Manual delivered with the drive.
The control panel is wired to both the line-side converter and the motor-side
converter using a Y-splitter. The converter that is currently being controlled is
indicated by the converter name on the drive display; the suffix “MR” denotes motor-
side converter, “LR” denotes line-side converter. The control is switched between the
converters as follows:
2. Scroll to ID number 2.
ACS 800 0050_5LR
IXXR7xxx
ID-NUMBER 2
WARNING! The drive does not stop by pressing the control panel Stop key in local
control mode.
2. Scroll to ID number 1.
ACS 800 0050_5MR
ACXR7xxx
ID-NUMBER 1
Actual signal Signal measured or calculated by the drive. Can be monitored by the
user. No user setting possible.
FbEq Fieldbus equivalent: The scaling between the value shown on the control
panel and the integer used in serial communication.
Actual signals
No. Name/Value Description FbEq Def.
09 ACTUAL SIGNALS Signals from the line converter.
09.12 LCU ACT SIGNAL 1 Line converter signal selected by par. 95.08 LCU PAR1 SEL. 1=1 106
09.13 LCU ACT SIGNAL 2 Line converter signal selected by par. 95.09 LCU PAR2 SEL. 1=1 110
Parameters
No. Name/Value Description FbEq Def.
95 HARDWARE SPECIF Line converter references and actual signal selections.
95.06 LCU Q POW REF Reactive power reference for the line converter i.e. the value for 0
par. 24.02 Q POWER REF2 in the IGBT Supply Control Program.
Scaling example 1: 10000 equals to a value of 10000 of
parameter 24.02 Q POWER REF2 and 100% of par. 24.01 Q
POWER REF (i.e. 100% of the converter nominal power given in
par. 04.06 CONV NOM POWER) when par. 24.03 Q POWER
REF2 SEL is set to PERCENT.
Scaling example 2: Par. 24.03 Q POWER REF2 SEL is set to
kVAr. A value of 1000 of par. 95.06 equals to 1000 kVAr of par.
24.02 Q POWER REF2. Value of par. 24.01 Q POWER REF is
then 100 · (1000 kVAr divided by converter nominal power in
kVAr)%.
Scaling example 3: Par. 24.03 Q POWER REF2 SEL is set to
PHI. A value of 10000 of par. 95.06 equals to a value of 100 deg
of parameter 24.02 Q POWER REF2 which is limited to 30 deg.
The value of par. 24.01 Q POWER REF will be determined
approximately according to the following equation where P is read
from actual signal 1.06 POWER:
S
P P Q
cos 30 = --- = -----------------------
S 2 2 30 deg
P +Q
P
Positive reference 30 deg denotes capacitive load.
Negative reference 30 deg denotes inductive load.
Parameters
No. Name/Value Description T./FbEq Def.
16 SYSTEM CTR Parameter lock, parameter back-up etc.
INPUTS
16.15 START MODE Selects I/O control start mode when par. 98.01 COMMAND SEL is B EDGE
set to I/O.
LEVEL Starts converter by level of control command. Control command is 0
selected by parameter 98.01 COMMAND SEL and 98.02 COMM.
MODULE.
WARNING! After a fault reset, the converter will start if the
start signal is on.
Maintenance
Safety
WARNING! Read the Safety instructions on the first pages of this manual before
performing any maintenance on the equipment. Ignoring the safety instructions can
cause injury or death.
Maintenance intervals
If installed in an appropriate environment, the drive requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB.
Every 6 years Main cooling fan change See Main cooling fan.
Consult your local ABB Service representative for more details on the maintenance.
On the Internet, go to http://www.abb.com/drivesservices.
Maintenance
110
Heatsink
The heatsink fins pick up dust from the cooling air. The drive runs into
overtemperature warnings and faults if the heatsink is not clean. In a “normal”
environment (not dusty, not clean) the heatsink should be checked annually, in a
dusty environment more often.
Clean the heatsink as follows (when necessary):
1. Remove the cooling fan (see section Main cooling fan).
2. Blow clean compressed air (not humid) from bottom to top and simultaneously
use a vacuum cleaner at the air outlet to trap the dust. Note: If there is a risk of
the dust entering adjoining equipment, perform the cleaning in another room.
3. Replace the cooling fan.
Maintenance
111
1 1
5
4
Additional fan
Replacement (R5)
Remove the front cover. The fan is located on the right-hand side of the control panel
(R5). Lift the fan out and disconnect the cable. Install the new fan in reverse order.
Maintenance
112
Replacement (R6)
Remove the top cover by lifting it by the rear edge. To remove the fan, release the
retaining clips by pulling the back edge (1) of the fan upwards. Disconnect the cable
(2, detachable terminal). Install the new fan in reverse order.
Capacitors
The drive intermediate circuit employs several electrolytic capacitors. The lifespan
depends on drive loading and ambient temperature. Capacitor life can be prolonged
by lowering the ambient temperature.
It is not possible to predict a capacitor failure. Capacitor failure is usually followed by
a mains fuse failure or a fault trip. Contact ABB if capacitor failure is suspected.
Replacements are available from ABB. Do not use other than ABB specified spare
parts.
Reforming
Reform (re-age) spare part capacitors once a year according to Converter modules
with electrolytic DC capacitors in the DC link, Capacitor reforming instructions
(3BFE64059629 [English]).
Maintenance
113
Fault tracing
FAULT, ID:2
ACS 800 0490_3MR
*** FAULT ***
LINE CONV (FF51)
To display the warning or fault identification text, switch the control panel to view the
line-side converter as described in section Control panel on page 100.
Information on warnings and faults concerning the line-side converter are described
in ACS800 IGBT Supply Control Program Firmware Manual [3AFE68315735
(English)].
The warnings and faults concerning the motor-side converter are described in the
control program (e.g. Standard Control Program) Firmware Manual.
Conflicting ID numbers
If the ID numbers of the line-side and the motor-side converters are set equal, the
control panel stops functioning. To clear the situation:
• Disconnect the panel cable from the RMIO board of the motor-side converter, and
connect it to the RMIO board of the line-side converter.
• Set the ID number of the line-side converter RMIO board to 2. For the setting
procedure, see the control program (e.g. Standard Control Program) Firmware
Manual.
• Disconnect the panel cable from the line-side converter RMIO board, and
reconnect it to the motor-side converter RMIO board.
Fault tracing
114
• Reconnect the panel cable to the RMIO board of the motor-side converter again
and set the ID number to 1.
LEDs
This table describes LEDs of the drive.
Fault tracing
115
Technical data
IEC data
Ratings
The IEC ratings for the ACS800-11 with 50 Hz and 60 Hz supplies are given below.
The symbols are described below the table.
ACS800-11 type Nominal No- Light-overload Heavy-duty use Frame Air flow Heat
overload
ratings use
use size dissipation
Icont.max Imax Pcont.max I2N PN I2hd Phd
A A
kW
A kW A kW m3/h W
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0011-2 34 52 7.5 32 7.5 26 5.5 R5 350 505
-0016-2 47 68 11 45 11 38 7.5 R5 350 694
-0020-2 59 90 15 56 15 45 11 R5 350 910
-0025-2 75 118 22 69 18.5 59 15 R5 350 1099
-0030-2 88 137 22 83 22 72 18.5 R5 350 1315
-0040-2 120 168 37 114 30 84 22 R6 405 1585
-0050-2 150 234 45 143 45 117 30 R6 405 2125
-0060-2 169 264 45 157 45 132 37 R6 405 2530
Three-phase supply voltage 380 V, 400 V or 415 V
-0016-3 34 52 15 32 15 26 11 R5 350 550
-0020-3 38 61 18.5 36 18.5 34 15 R5 350 655
-0025-3 47 68 22 45 22 38 18.5 R5 350 760
-0030-3 59 90 30 56 30 45 22 R5 350 1000
-0040-3 72 118 37 69 37 59 30 R5 350 1210
-0050-3 86 137 45 83 45 65 30 R5 350 1450
-0060-3 120 168 55 114 55 88 45 R6 405 1750
-0070-3 150 234 75 143 75 117 55 R6 405 2350
-0100-3 165 264 90 157 75 132 75 R6 405 2800
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0020-5 31 52 18.5 29 18.5 25 15 R5 350 655
-0025-5 36 61 22 34 22 30 18.5 R5 350 760
-0030-5 47 68 30 45 30 37 22 R5 350 1000
-0040-5 58 90 37 55 37 47 30 R5 350 1210
-0050-5 70 118 45 67 45 57 37 R5 350 1450
-0060-5 82 130 55 78 45 62 37 R5 350 1750
-0070-5 120 168 75 114 75 88 55 R6 405 2350
-0100-5 139 234 90 132 90 114 75 R6 405 2800
-0120-5 156 264 110 148 90 125 75 R6 405 3400
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0060-7 57 86 55 54 45 43 37 R6 405 1750
-0070-7 79 120 75 75 55 60 55 R6 405 2350
-0100-7 93 142 90 88 75 71 55 R6 405 2800
00184674
Technical data
116
Symbols
Nominal ratings
Icont.max continuous rms output current. No overload capability at 40 °C (104 °F).
Imax maximum output current. Available for 10 s at start, otherwise as long as allowed by drive
temperature.
Typical ratings:
No-overload use
Pcont.max typical motor power. The power ratings apply to most IEC 60034 motors at the nominal
voltage, 230 V, 400 V, 500 V or 690 V.
Light-overload use (10% overload capability)
I2N continuous rms current. 10% overload is allowed for one minute every 5 minutes.
PN typical motor power. The power ratings apply to most IEC 60034 motors at the nominal
voltage, 230 V, 400 V, 500 V or 690 V.
Heavy-duty use (50% overload capability)
I2hd continuous rms current. 50% overload is allowed for one minute every 5 minutes.
Phd typical motor power. The power ratings apply to most IEC 60034 motors at the nominal
voltage, 230 V, 400 V, 500 V or 690 V.
Sizing
The current ratings are the same regardless of the supply voltage within one voltage range. To achieve
the rated motor power given in the table, the rated current of the drive must be higher than or equal to
the rated motor current.
Note 1: The maximum allowed momentary motor shaft power is limited to approximately 1.3 · Pcont.max.
If the limit is exceeded, motor torque and current are automatically restricted. The function protects the
input bridge and LCL filter of the drive against overload.
Note 2: The ratings apply at an ambient temperature of 40 °C (104 °F). At lower temperatures the
ratings are higher (except Imax).
Note 3: Use the DriveSize PC tool for a more accurate dimensioning if the ambient temperature is
below 40 °C (104 °F) or the drive is loaded cyclically.
Derating
The load capacity (current and power) decreases if the installation site altitude exceeds 1000 metres
(3300 ft), or if the ambient temperature exceeds 40 °C (104 °F).
Temperature derating
In the temperature range +40 °C (+104 °F) to +50 °C (+122 °F) the rated output current is decreased
1 % for every additional 1 °C (1.8 °F). The output current is calculated by multiplying the current given
in the rating table by the derating factor.
Example If the ambient temperature is 50 °C (+122 °F), the derating factor is 100% - 1 % · 10 °C =
90 % or 0.90. The output current is then 0.90 · I or 0.90 · I . °C
2N 2hd
Altitude derating
In altitudes from 1000 to 4000 m (3300 to 13123 ft) above sea level, the derating is 1% for every 100 m
(328 ft). For a more accurate derating, use the DriveSize PC tool.
Technical data
117
Technical data
118
aR fuses
ACS800-11 type Input Fuse
current 2
A A s (@660V) V Manufacturer Fuse Type DIN 43620
size
Technical data
119
Cable types
The table below gives copper and aluminium cable types for different load currents.
Cable sizing is based on max. 9 cables laid on a cable ladder side by side, ambient
temperature 30 °C, PVC insulation, surface temperature 70 °C (158 °F)
(EN 60204-1 and IEC 60364-5-2/2001). For other conditions, size the cables
according to local safety regulations, appropriate input voltage and the load current
of the drive.
Copper cables with concentric Aluminium cables with concentric
copper shield copper shield
Max. load Cable type Max. load Cable type
current current
2
A mm A mm2
34 3x6 61 3x25
47 3x10 75 3x35
62 3x16 91 3x50
79 3x25 117 3x70
98 3x35 143 3x95
119 3x50 165 3x120
153 3x70 191 3x150
186 3x95 218 3x185
215 3x120
249 3x150
284 3x185
00096931
Cable entries
Mains, DC link and motor cable terminal sizes (per phase), accepted cable
diameters and tightening torques are given below.
Frame size U1, V1, W1, U2, V2, W2, UDC+,UDC- Earthing PE
Wire size Max. cable Ø Tightening Wire size Tightening
IP21 torque torque
mm2 mm N·m mm2 N·m
R5 6…70 35 10 6…35 15
R6 95...185 * 53 20…40 16...95 8
Technical data
120
NEMA data
Ratings
The NEMA ratings for the ACS800-U11 and ACS800-11 with 60 Hz supplies are
given below. The symbols are described below the table. For sizing, derating and
50 Hz supplies, see IEC data.
ACS800-U11 type Imax Normal use Heavy-duty use Frame Air flow Heat
ACS800-11 type size dissipation
I2N PN I2hd Phd
A A hp A hp ft3/min BTU/Hr
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0011-2 52 32 10 26 7.5 R5 206 1730
-0016-2 68 45 15 38 10 R5 206 2380
-0020-2 90 56 20 45 10 R5 206 3110
-0025-2 118 69 25 59 15 R5 206 3760
-0030-2 137 83 30 72 20 R5 206 4500
-0040-2 168 114 40 84 25 R6 238 5420
-0050-2 234 143 50 117 30 R6 238 7260
-0060-2 264 157 60 132 40 R6 238 8650
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V or 480 V
-0020-5 52 29 20 25 15 R5 206 2240
-0025-5 61 34 25 30 20 R5 206 2600
-0030-5 68 45 30 37 25 R5 206 3420
-0040-5 90 55 40 47 30 R5 206 4140
-0050-5 118 67 50 57 40 R5 206 4960
-0060-5 130 78 60 62** 50** R5 206 5980
-0070-5 168 114 75 88 60 R6 238 8030
-0100-5 234 132 100 114 75 R6 238 9570
-0120-5 264 148* 125* 125 100 R6 238 11620
Three-phase supply voltage 525 V, 575 V or 600 V
-0060-7 86 54 50 43 40 R6 238 5980
-0070-7 120 75 60 60 50 R6 238 8030
-0100-7 142 88 75 71 60 R6 238 9570
00184674
* 156 A, motor power < 125 hp and a reactive power reference of 0 allowed with 460 V
**
65 A, motor power < 50 hp and a reactive power reference of 0 allowed with 460 V
Symbols
Nominal ratings
Imax maximum output current. Available for 10 s at start, otherwise as long as allowed by drive
temperature.
Normal use (10% overload capability)
I2N continuous rms current. 10% overload is typically allowed for one minute every 5 minutes.
PN typical motor power. The power ratings apply to most 4-pole NEMA rated motors (230 V,
460 V or 575 V).
Heavy-duty use (50% overload capability)
I2hd continuous rms current. 50% overload is typically allowed for one minute every 5 minutes.
Phd typical motor power. The power ratings apply to most 4-pole NEMA rated motors (230 V,
460 V or 575 V).
Note 1: The ratings apply at an ambient temperature of 40 °C (104 °F). In lower temperatures the
ratings are higher (except Imax).
Technical data
121
Technical data
122
Cable types
Cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire
insulation at 40 °C (104 °F) ambient temperature. Not more than three current-
carrying conductors in raceway or cable or earth (directly buried). For other
conditions, dimension the cables according to local safety regulations, appropriate
input voltage and the load current of the drive.
Copper cables with concentric copper shield
Max. load Cable type
current
A AWG/kcmil
31 10
44 8
57 6
75 4
88 3
101 2
114 1
132 1/0
154 2/0
176 3/0
202 4/0
224 250 MCM or 2 x 1
251 300 MCM or 2 x 1/0
273 350 MCM or 2 x 2/0
00096931
Cable Entries
Input, DC link and motor cable (per phase) terminal sizes, accepted cable diameters
and tightening torques are given below.
Frame size U1, V1, W1, U2, V2, W2, UDC+, UDC- Grounding PE
Wire size Wire Ø Tightening Wire size Tightening
(UL type 1) torque torque
AWG in. lbf·ft AWG lbf·ft
R5 4...2/0 1.39 11.1 4...2/0 11.1
R6 3/0 ... 350 MCM * 2.09 14.8...29.5 4/0 5.9
Technical data
123
Motor connection
Voltage (U2) 0 to U1, 3-phase symmetrical, Umax at the field weakening point
Frequency DTC mode: 0 to 3.2 · fFWP. Maximum frequency 300 Hz.
UNmains
fFWP = · fNmotor
UNmotor
fFWP: frequency at field weakening point; UNmains: mains (input power) voltage;
UNmotor: rated motor voltage; fNmotor: rated motor frequency
Frequency resolution 0.01 Hz
Current See section IEC data or NEMA data.
Power limit Approximately 1.3 · Pcont.max
Field weakening point 8 to 300 Hz
Switching frequency 3 kHz (average)
Maximum recommended 300 m (984 ft). Additional restriction for units with EMC filtering (type code selections
motor cable length +E202 and +E200): max. motor cable length is 100 m (328 ft). With longer cables the EMC
Directive requirements may not be fulfilled.
Efficiency
Approximately 97% at nominal power level
Technical data
124
Cooling
Method Internal fan, flow direction from bottom to top.
Free space around the unit See chapter Mechanical installation.
Degree of protection
IP21 (UL type 1). IPXXD from above.
Without the front cover, the unit must be protected against contact according to IP2x, see
chapter Electrical installation: Cabinet installed units (IP00, UL type open).
Technical data
125
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Operation Storage Transportation
installed for stationary use in the protective package in the protective package
Installation site altitude 0 to 4000 m (13123 ft) above - -
sea level [above 1000 m
(3281 ft), see section
Derating]
Drives with option +Q967:
0 to 2000 (6562 ft)
Air temperature -15 to +50 °C (5 to 122 °F). -40 to +70 °C -40 to +70 °C
No frost allowed. See section (-40 to +158 °F) (-40 to +158 °F)
Derating.
Relative humidity 5 to 95% Max. 95% Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
corrosive gases.
Contamination levels No conductive dust allowed.
(IEC 60721-3-3, IEC 60721-3- Boards with coating: Boards with coating: Boards with coating:
2, IEC 60721-3-1) Chemical gases: Class 3C2 Chemical gases: Class 1C2 Chemical gases: Class 2C2
Solid particles: Class 3S2 Solid particles: Class 1S3 Solid particles: Class 2S2
Atmospheric pressure 70 to 106 kPa 70 to 106 kPa 60 to 106 kPa
0.7 to 1.05 atmospheres 0.7 to 1.05 atmospheres 0.6 to 1.05 atmospheres
Vibration (IEC 60068-2) Max. 1 mm (0.04 in.) Max. 1 mm (0.04 in.) Max. 3.5 mm (0.14 in.)
(5 to 13.2 Hz), (5 to 13.2 Hz), (2 to 9 Hz),
2 2 2 2
max. 7 m/s (23 ft/s ) max. 7 m/s (23 ft/s ) max. 15 m/s2 (49 ft/s2)
(13.2 to 100 Hz) sinusoidal (13.2 to 100 Hz) sinusoidal (9 to 200 Hz) sinusoidal
Shock (IEC 60068-2-27) Not allowed Max. 100 m/s2 (330 ft./s2), Max. 100 m/s2 (330 ft./s2),
11 ms 11 ms
Free fall Not allowed 250 mm (10 in.) for weight 250 mm (10 in.) for weight
under 100 kg (220 lb) under 100 kg (220 lb)
100 mm (4 in.) for weight 100 mm (4 in.) for weight
over 100 kg (220 lb) over 100 kg (220 lb)
Materials
Drive enclosure • PC/ABS 2.5 mm, colour NCS 1502-Y (RAL 9002 / PMS 420 C)
• hot-dip zinc coated steel sheet 1.5 to 2 mm, thickness of coating 100 micrometres
• extruded aluminium AlSi
Package Cardboard, plywood, PP bands (straps), PE plastic
Disposal The drive contains raw materials that should be recycled to preserve energy and natural
resources. The package materials are environmentally compatible and recyclable. All
metal parts can be recycled. The plastic parts can either be recycled or burned under
controlled circumstances, according to local regulations. Most recyclable parts are marked
with recycling marks.
If recycling is not feasible, all parts excluding electrolytic capacitors and printed circuit
boards can be landfilled. The DC capacitors (C1-1 to C1-x) contain electrolyte and the
printed circuit boards contain lead, both of which are classified as hazardous waste within
the EU. They must be removed and handled according to local regulations.
For further information on environmental aspects and more detailed recycling instructions,
please contact your local ABB distributor.
Technical data
126
Applicable standards
The drive complies with the following standards.
• EN 50178:1997 Electronic equipment for use in power installations
• EN 60204-1:2006/ AC:2010 Safety of machinery. Electrical equipment of machines. Part 1: General requirements.
Provisions for compliance: The final assembler of the machine is responsible for installing
- an emergency-stop device
- a supply disconnecting device.
• EN 60529:1991 Degrees of protection provided by enclosures (IP code)
+ corrigendum May 1993
+ A1:2000
• EN 60664-1:2007 Insulation coordination for equipment within low-voltage systems. Part 1: Principles,
requirements and tests.
• EN 61800-3:2004 Adjustable speed electrical power drive systems. Part 3: EMC requirements and specific
test methods
• EN 61800-5-1:2007 Adjustable speed electrical power drive systems - Part 5-1: Safety requirements -
Electrical, thermal and energy
• UL 508C UL Standard for Safety, Power Conversion Equipment, third edition
• NEMA 250-2003 Enclosures for Electrical Equipment (1000 Volts Maximum)
• CSA C22.2 No. 14-05 Industrial control equipment
CE marking
A CE mark is attached to the drive to verify that the unit follows the provisions of the
European Low Voltage and EMC Directives. The CE marking also verifies that the
drive, in regard to its safety functions (such as Safe torque off), conforms with the
Machinery Directive as a safety component.
Technical data
127
Definitions
EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic
equipment to operate without problems within an electromagnetic environment.
Likewise, the equipment must not disturb or interfere with any other product or
system within its locality.
First environment includes establishments connected to a low-voltage network which
supplies buildings used for domestic purposes.
Second environment includes establishments connected to a network not supplying
domestic premises.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be
installed and commissioned only by a professional when used in the first
environment. Note: A professional is a person or organisation having necessary
skills in installing and/or commissioning power drive systems, including their EMC
aspects.
Drive of category C3: drive of rated voltage less than 1000 V and intended for use in
the second environment and not intended for use in the first environment.
Drive of category C4: drive of rated voltage equal to or above 1000 V, or rated
current equal to or above 400 A, or intended for use in complex systems in the
second environment.
First environment (drive of category C2)
The drive complies with the standard with the following provisions:
1. The drive is equipped with EMC filter +E202.
2. The motor and control cables are selected as specified in the Hardware Manual.
3. The drive is installed according to the instructions given in the Hardware Manual.
4. The maximum cable length is 100 metres.
WARNING! The drive may cause radio interference if used in a residential or
domestic environment. The user is required to take measures to prevent
interference, in addition to the requirements for CE compliance listed above, if
necessary.
Note: It is not allowed to install a drive equipped with EMC filter +E202 on IT
(unearthed) systems. The supply network becomes connected to earth potential
through the EMC filter capacitors which may cause danger or damage the unit.
Second environment (drive of category C3)
The drive complies with the standard with the following provisions:
1. The drive is equipped with EMC filter +E200. See also page 70.
2. The motor and control cables are selected as specified in the Hardware Manual.
3. The drive is installed according to the instructions given in the Hardware Manual.
4. The maximum cable length is 100 metres.
Technical data
128
Neighbouring network
Static screen
Point of measurement
Equipment Equipment
“C-tick” marking
A “C-tick” mark is attached to each drive in order to verify compliance with the EMC
product standard (EN 61800-3:2004), required under the Trans-Tasman
Electromagnetic Compatibility Scheme for levels 1, 2 and 3 in Australia and New
Zealand. See section Compliance with EN 61800-3:2004.
Technical data
129
UL/CSA markings
The ACS800-U11 and ACS800-11 drives of UL type 1 are cULus listed and cCSAus
certified.
UL checklist
• The drive is to be used in a heated, indoor controlled environment. The drive must
be installed in clean air according to enclosure classification. Cooling air must be
clean, free from corrosive materials and electrically conductive dust. See section
Ambient conditions for specific limits.
• The maximum ambient air temperature is 40 °C (104 °F) at rated current. The
current is derated for 40 to 50 °C (104 to 122 °F).
• The drive is suitable for use on a circuit capable of delivering not more than 65 kA
rms symmetrical amperes at the drive nominal voltage (600 V maximum for 690 V
units) when protected by T class fuses.
• The cables located within the motor circuit must be rated for at least 75 °C
(167 °F) in UL-compliant installations.
• The input cable must be protected with fuses. Circuit breakers must not be used
without fuses in the USA. Suitable IEC (class aR) fuses and UL (class T) fuses
are listed in the hardware manual.
• For installation in the United States, branch circuit protection must be provided in
accordance with the National Electrical Code (NEC) and any applicable local
codes. To fulfil this requirement, use the UL classified fuses.
• For installation in Canada, branch circuit protection must be provided in
accordance with the Canadian Electrical Code and any applicable provincial
codes. To fulfil this requirement, use the UL classified fuses.
• The drive provides overload protection in accordance with the National Electrical
Code (NEC). See ACS800 Firmware Manual for setting. Default setting is off,
must be activated at start-up.
Technical data
130
Technical data
131
Dimensional drawings
Dimensional drawings
132
US gland/conduit plate
Diameters of knock-out holes:
Dimensional drawings
50 mm [1.97 in.], 22.7 mm
[.89 in.]. The unit is UL type 1
when equipped with the US
gland plate.
Frame size R5 (IP21, UL type 1)
68406200
US gland/conduit
plate
Diameters of knock-
out holes: 63.5 mm
[2.50 in.], 22.7 mm
[.89 in.]. The unit is
UL type 1 when
equipped with the
US gland plate.
Frame size R6 (IP21, UL type 1)
68405726
133
Dimensional drawings
134
Dimensional drawings
135
Dimensional drawings
136
Dimensional drawings
137
3AFE68293898
Dimensional drawings
138
3AUA0000068698
Dimensional drawings
139
Parameter settings
In Standard Application Program, set parameter 16.09 CTRL BOARD SUPPLY to
EXTERNAL 24V if the RMIO board is powered from an external supply.
External +24 V power supply for the RMIO boards via terminal X34
140
2
X34
1
3
4 4
External +24 V power supply for the RMIO boards via terminal X34
141
7 8
RMIO board
1 2 3
X34
+ -
1 2
Connection of a two-way
connector
RMIO board
1 2 3
X34
+ -
1 2 3
Connection of a three-way
connector
External +24 V power supply for the RMIO boards via terminal X34
142
Terminal X34
Frame size R6
1. Remove the top cover by releasing the retaining clip with a screw driver and lifting
the cover upwards.
2. Disconnect the DDCS communication module by undoing the fastening screws
and disconnecting the fibre optic cables. Disconnect other optional modules if
present.
3. Disconnect the control panel cable.
4. Disconnect the additional fan cable (detachable terminal) and release the strain
relief.
5. Remove the I/O terminal blocks.
6. Undo the fastening screws of the upper plastic cover.
7. Lift the cover carefully upwards by the lower sides.
8. Disconnect the control panel cable from the RMIO board.
External +24 V power supply for the RMIO boards via terminal X34
143
1
4
4
6 2
2
3
5 5 5
7 7
External +24 V power supply for the RMIO boards via terminal X34
144
External +24 V power supply for the RMIO boards via terminal X34
Further information
Product and service inquiries
Address any inquiries about the product to your local ABB representative, quoting the type
designation and serial number of the unit in question. A listing of ABB sales, support and
service contacts can be found by navigating to www.abb.com/drives and selecting Sales,
Support and Service network.
Product training
For information on ABB product training, navigate to www.abb.com/drives and select
Training courses.
User’s Manual
PROFIBUS DP Adapter Module
RPBA-01
PROFIBUS DP Adapter Module
RPBA-01
User’s Manual
EFFECTIVE: 20.06.2005
Safety instructions
Overview
This chapter states the general safety instructions that must be
followed when installing and operating the RPBA-01 PROFIBUS
DP Adapter module.
The material in this chapter must be studied before attempting any
work on, or with, the unit.
In addition to the safety instructions given below, read the
complete safety instructions of the specific drive you are working
on.
Safety instructions
6
Safety instructions
7
Table of contents
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
General safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table of contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Intended audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Before you start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
What this manual contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Terms used in this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Further information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
PROFIBUS standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
The RPBA-01 PROFIBUS DP Adapter module . . . . . . . . . . . . . . . . . . . . . . 16
Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Delivery check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Warranty and liability information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Table of contents
8
Mechanical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
General cabling instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Bus termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Node selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
PROFIBUS connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Configuring the system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
PROFIBUS connection configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Control locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
DP-V0 communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
PROFIBUS DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Service Access Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Communication start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
PPO message types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
The Control Word and the Status Word . . . . . . . . . . . . . . . . . . . . . . . . . . 46
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Actual Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Parameter handling in cyclic communication (DP) . . . . . . . . . . . . . . . . . . . . 51
DP-V1 communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
PROFIBUS DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Service Access Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Communication start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
PPO message types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
The Control Word and the Status Word . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Table of contents
9
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Actual Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
DP-V1 read/write request sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Parameter data transfer examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Fault tracing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
LED indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Table of contents
10
Table of contents
11
Introduction
Intended audience
The manual is intended for the people who are responsible for
commissioning and using an RPBA-01 PROFIBUS DP Adapter
module. The reader is expected to have a basic knowledge of
electrical fundamentals, electrical wiring practices and how to
operate the drive.
Introduction
12
Introduction
13
Further information
Further information is available on the World Wide Web from
www.profibus.com.
Introduction
14
Introduction
15
Overview
Overview
This chapter contains a short description of the PROFIBUS
standard and the RPBA-01 PROFIBUS DP Adapter module, a
delivery checklist and warranty information.
PROFIBUS standard
PROFIBUS is an open serial communication standard that
enables data exchange between all kinds of automation
components. There are three main variations of PROFIBUS:
PROFIBUS-FMS (Fieldbus Message Specification),
PROFIBUS-DP (Decentralised Periphery) and PROFIBUS-PA
(Process Automation). The RPBA-01 PROFIBUS DP Adapter
module supports the PROFIBUS DP protocol, including its DP-V1
extension.
The physical transmission medium of the bus is a twisted pair
cable (according to the RS-485 standard). The maximum length of
the bus cable is 100 to 1200 metres, depending on the selected
transmission rate (see Technical data chapter). Up to 31 nodes
can be connected to the same PROFIBUS network segment
without the use of repeaters. With repeaters, it is possible to
connect 127 nodes (including repeaters and master station) to the
network.
In PROFIBUS communication, the master station – usually a
programmable logic controller (PLC) – polls the nodes which
respond and take the actions requested by the master. It is also
possible to send a command to several nodes at the same
broadcast; in this case the nodes do not send a response
message to the master.
The PROFIBUS protocol family is specified in the IEC 61158
standard. The communication with a drive is defined in the
PROFIdrive Profile – The PROFIBUS Profile for Adjustable Speed
Overview
16
Overview
17
address
selection switches
Diagnostic LEDs
Top view (See chapter Side view
Fault tracing)
Compatibility
The RPBA-01 is compatible with all master stations that support
the PROFIBUS DP protocol.
Delivery check
The option package for the RPBA-01 PROFIBUS DP Adapter
module contains:
• PROFIBUS DP Adapter module, type RPBA-01
• two screws (M3x10)
• this manual.
Overview
18
Overview
19
Overview
This chapter presents the steps to take during the start-up of the
RPBA-01 PROFIBUS DP Adapter Module. For more detailed
information, see the chapters Mechanical installation, Electrical
installation, and Programming elsewhere in this manual.
PLC configuration
• Install the RPBA-01 GSD file (e.g. ABB_0812.GSD).
Drive configuration
• Power up the drive.
• The detailed procedure of activating the drive for
communication with the module is dependent on the drive type.
Normally, a parameter must be adjusted to activate the
communication. Refer to the Firmware Manual of the drive for
Mechanical installation
Mounting
The RPBA-01 is to be inserted into its specific position in the drive.
The module is held in place with plastic retaining clips and two
screws. The screws also provide the earthing of the I/O cable
shield connected to the module, and interconnect the GND signals
of the module and the control board of the drive.
On installation of the module, the signal and power connection to
the drive is automatically made through a 34-pin connector.
Mounting procedure:
• Insert the module carefully into its position inside the drive until
the retaining clips lock the module into position.
• Fasten the two screws (included) to the stand-offs.
• Set the bus termination switch of the module to the required
position.
Mechanical installation
28
Mechanical installation
29
Electrical installation
Overview
This chapter contains:
• general cabling instructions
• instructions for setting module node address number and bus
termination
• instructions for connecting the module to the PROFIBUS DP
network.
Bus termination
The DIP switch on the front of the RPBA-01 module is used to
switch on bus termination. Bus termination prevents signal
reflections from the cable ends. Bus termination must be set to ON
if the module is the last or first module on the network. When using
PROFIBUS specific D-sub connectors with built-in termination, the
RPBA-01 termination must be switched off.
Electrical installation
30
ON ON
Node selection
Use the rotary node address selectors on the module to select the
node address number. The node address number is a decimal
number ranging from 01 to 99. The left selector represents the first
digit and the right selector the second digit. The node address can
be changed during operation, but the module must be re-initialised
for changes to take effect.
10x 1x
901 901
23
23
78
78
45 6 45 6
Electrical installation
31
PROFIBUS connection
The bus cable is connected to connector X1 on the RPBA-01.
The connector pin allocation described below follows the
PROFIBUS standard.
5 1
X1
9 6
X1 Description
1 Not used
2 Not used
3 B Data positive (Conductor 1 in twisted pair).
4 RTS Request To Send
5 GND Isolated ground
BUS
6 +5V Isolated 5V DC voltage supply
7 Not used
8 A Data negative (Conductor 2 in twisted pair).
9 Not used
Housing SHLD PROFIBUS cable shield. Internally connected
to GND BUS via an RC filter and directly to
CHGND.
+5V and GND BUS are used for bus termination. Some devices,
like optical transceivers (RS485 to fibre optics) might require
external power supply from these pins.
Electrical installation
32
X1 SHLD X1 SHLD
A 1 A 1
RPBA-01 RPBA-01
B 2 B 2
A 3 A 3
PROFIBUS B 4 B 4
MASTER
A
B
GND
Electrical installation
33
Programming
Overview
This chapter gives information on configuring the PROFIBUS
master station and the drive for communication through the
RPBA-01 PROFIBUS DP Adapter module.
Programming
34
Note: The new settings take effect only when the module is
powered up the next time or when the module receives a ‘Fieldbus
Adapter parameter refresh’ command from the drive.
Programming
35
Note: Set also the extended Parameter Data (see page 67) to
ensure proper operation of the RPBA-01 with the drive.
1 MODULE TYPE
This parameter shows the module type as detected by the drive.
The value cannot be adjusted by the user.
If this parameter is undefined, the communication between the
drive and the module has not been established.
2 NODE ADDRESS
Each device on the PROFIBUS network must have a unique node
number. This parameter is used to define a node number for the
drive it is connected to, if the node address selection switches are
set to the zero position. When the node address selector switches
are used to define the node address (node address selectors not
in zero position) this parameter indicates the set node address.
3 BAUD RATE
Indicates the communication speed detected in kbit/s.
12000 = 12 Mbit/s
6000 = 6 Mbit/s
3000 = 3 Mbit/s
1500 = 1.5 Mbit/s
500 = 500 kbit/s
187 = 187.5 kbit/s
93 = 93.75 kbit/s
45 = 45.45 kbit/s
19 = 19.2 kbit/s
9 = 9.6 kbit/s
Programming
36
4 PPO-TYPE
This parameter indicates the detected PPO message type for the
PROFIBUS communication. See Figures 6 and 10 in the chapters
DP-V0 communication and DP-V1 communication respectively for
the supported PPO message types.
5 PZD3 OUT
This parameter represents process data word 3 of the PPO type
received by the drive over the PROFIBUS network. The content is
defined by a decimal number in the range of 0 to 32767 as follows:
0 not used
1 - 99 data set area of the drive
101 - 9999 parameter area of the drive
10000 - 32767 not supported by the drive
Programming
37
6 PZD3 IN
Process data word 3 of the PPO type sent from the drive to the
PROFIBUS network.
The content is defined by a decimal number in the range of 0 to
32767. See parameter PZD3 OUT for description of decimal
number allocation.
7 to 20 PZD4 OUT to PZD10 IN
See parameters PZD3 OUT and PZD3 IN.
21 DP MODE
Selects the PROFIBUS protocol version (DP-V0 or DP-V1).
Control locations
ABB drives can receive control information from multiple sources
including digital inputs, analogue inputs, the drive control panel
and a communication module (e.g. RPBA-01). ABB drives allow
the user to separately determine the source for each type of
control information (Start, Stop, Direction, Reference, Fault Reset,
etc.). In order to give the fieldbus master station the most
complete control over the drive, the communication module must
be selected as source for this information. See the user
documentation of the drive for information on the selection
parameters.
Programming
38
Programming
39
DP-V0 communication
Overview
This chapter describes the PROFIBUS messaging used in the
communication with the drive when the RPBA-01 module is in DP-
V0 mode.
PROFIBUS DP
The RPBA-01 module supports the PROFIBUS-DP protocol
according to EN 50170 standard. PROFIBUS DP is a distributed
I/O system which enables the master to use a large number of
peripheral modules and field devices. The data transfer is mainly
cyclic: the master reads the input information from the slaves and
sends the output information back to the slaves.
The PROFIBUS DP protocol uses so-called PPOs
(Parameter/Process Data Objects) in cyclic communication. See
Figure 6 for the different PPO types and their composition.
DP-V0 communication
40
Communication start-up
The following Service Access Points (SAPs) are used to initiate
DP communication:
SAP no. Short Name Name
0 (Default) Data_Exch Transfer Input and Output Data
61 Set_Prm Send Parameter Data
62 Chk_Cfg Check Configuration Data
60 Slave_Diag Read Slave Diagnostic
SAP 61 (Set_Prm)
This SAP is used in the parameterisation of the drive.
Prm_Data (Parameter Data Standard)
Type: Octet String - Length: 8
Byte Value Description
0 B8h Station_Status
1 0 1 1 1 0 0 0
Reserved
WD_On
1 = Watchdog on
Freeze_Req
1 = Slave is requested to process in freeze mode
Sync_Req
1 = Slave is requested to process in SYNC mode
00 = Min TSDR and slave-related
Unlock_Req parameters may be overwritten
10 = Slave locked for other masters. All
Lock_Req parameters can be carried over
x1 = Slave released for other masters
DP-V0 communication
41
7 - Reserved
Prm_Data (Parameter Data Extended)
Type: Octet String - Length: 23
8 10h Header byte
(default) 0 0 0 1 0 0 0 0
Fail-safe mode. Defines the action taken when the PLC
is switched from ‘RUN’ to ‘STOP’ mode.
00 = STOP (default)
01 = LAST SPEED
02 = USE FAIL-SAFE. The values of the PZDs are
defined by bytes 11-30 in the Prm_Data telegram.
Reserved
DP-V0 communication
42
DP-V0 communication
43
SAP 60 (Slave_Diag)
This SAP gives diagnostic information on the slave station.
Diag_Data (Diagnostic Data)
Type: Octet String - Length: 6 (Standard) + 2 (Extended Diagnosis)
Byte Description
0 Station_Status_1
x x x x x x x x
Diag.Station_Non_Existent (Set by Master, reset by Slave)
Slave not found
Diag.Stagion_Not_Ready (Set by Slave)
Slave not ready for data exchange
Diag.Cfg_Fault (Set by Slave)
Received configuration data does not match original configuration data
1 Station_Status_2
x 0 x x x 1 x x
Diag.Prm_Req (Set by Slave)
Slave requires re-configuration and re-parameterisation
Diag.Stat_Diag (Set by Slave)
Static diagnosis. Slave (temporarily) unable to provide valid
data
DP-V0 communication
44
Reserved
3 Diag.Master_Add
The address of the master that parameterised this slave
4 - 5 Ident_Number (for RPBA-01: 0812h)
6 Ext_Diag_Data
The number of bytes reserved for Extended Diagnosis
(including this byte)
Fixed to 2
7 Ext_Diag_Data
Bit 0 = Communication temporarily lost
Bit 1 = Communication permanently lost
Bit 2 - 7 = Not used
SAP 0 (Data_Exchange)
Allows the master to send output data to a slave station and to
simultaneously request input data from the same station.
Outp_Data (Output Data)
Type: Octet String - Length: 4 to 28 (depending on the selected PPO Type)
Inp_Data (Input Data)
Type: Octet String - Length: 4 to 28 (depending on the selected PPO Type)
DP-V0 communication
45
Type 1
Type 2
Type 3
Type 4
Type 5
Parameter Identification:
ID – Parameter Identification
IND – Index for Arrays
VALUE – Parameter Value (Max. 4 bytes)
PKW –Parameter ID/Value
Process Data:
CW – Control Word (see Table 7.)
SW – Status Word (see Table 8.)
REF – Reference
ACT – Actual Value
PZD – Process Data (application-specific)
DW – Data Word
DP-V0 communication
46
References
References are 16-bit words containing a sign bit and a 15-bit
integer. A negative reference (indicating reversed direction of
rotation) is formed by calculating the two’s complement from the
corresponding positive reference.
ABB drives can receive control information from multiple sources
including analogue and digital inputs, the drive control panel and a
communication module (e.g. RPBA-01). In order to have the drive
controlled through PROFIBUS, the communication module must
be defined as the source for control information, e.g. Reference.
In the Vendor Specific mode, the scaling of the integer received
from the master as Reference is drive-specific. See its
programming manual for available control source selections and
Reference scaling factors.
In PROFIdrive mode, the speed reference (REF) in hexadecimal
(0…4000h) corresponds to 0…‘motor nominal speed’.
Actual Values
Actual Values are 16-bit words containing information on the
operation of the drive. The functions to be monitored are selected
by a drive parameter. The scaling of the integers sent to the
DP-V0 communication
47
DP-V0 communication
48
DP-V0 communication
49
DP-V0 communication
50
SWITCH-ON
MAINS OFF INHIBIT (SW Bit6=1)
C D ENABLE
OPERATION (SW Bit2=1)
A (CW Bit4=0 Bit5=0 Bit6=0)
(CW Bit5=0) (CW Bit4=1)
Inching 1 or 2 ON
(CW Bit8=1 or Bit9=1)
D RFG: ENABLE
OUTPUT INCHING 1
B or
(CW Bit6=0) (CW Bit5=1) INCHING 2
ACTIVE
RFG: ENABLE Inching 1 or 2 OFF
state ACCELERATION (CW Bit8=0 or Bit9=0)
C
(CW Bit6=1) Inching pause
condition
rising edge OPERATING ‘n=0 or f =0’ and ‘I=0’
of the bit (SW Bit8=1) and inching pause expired
D
DP-V0 communication
51
Parameter
Identification Process Data
CW REF
ID IND VALUE SW ACT (PD1, PD2...)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Request Label
Response Label Parameter Number (PNU)
*Request Signal
*Not used (=0)
DP-V0 communication
52
DP-V0 communication
53
Drive parameters
Range Example
Index Sub-index Request Label
(Decimal) No.
0h 65h 101
0h 66h 102
R/W* 6/7 1, 2
•••
27h 0Fh 9999
*Write access depends on drive parameter type, or operation mode.
DP-V0 communication
54
PROFIdrive parameters
Range Example
Index Sub-index Request Label
(Decimal) No.
2h 2
3h 3
393h 915 R/W 6/7 6
••• •••
9h 9
2h 2
3h 3
394h 916 R/W 6/7 7
••• •••
9h 9
396h 0h 918 R/W 1/2 3, 4
•••
0h 1
9h 9
11h 17
3B3h 947 R 6 5
19h 25
21h 33
29h 41
•••
3CCh 0h 972 R/W 1/2 3,4
DP-V0 communication
55
Req 60 20 DB 00 00 00 00 00 04 7F 34 15 00 00 00 00 00 00 00 00
Resp 40 20 DB 00 00 00 00 64 03 37 34 15 00 00 00 00 00 00 00 00
DP-V0 communication
56
Req 70 04 B2 00 00 00 00 64 04 7F 34 15 00 00 00 00 00 00 00 00
Resp 40 04 B2 00 00 00 00 64 03 37 34 15 00 00 00 00 00 00 00 00
DP-V0 communication
57
Request 13 96 00 00 00 00 00 00 04 7F 34 15
Read:
Response 13 96 00 00 00 00 00 02 03 37 34 15
DP-V0 communication
58
Request 23 CB 00 00 00 00 00 01 04 7F 34 15
Write:
Response 13 CB 00 00 00 00 00 00 03 37 34 15
DP-V0 communication
59
Request 63 B1 09 00 00 00 00 00 04 7F 34 15
Read:
Response 43 B1 09 00 00 00 23 00 03 37 34 15
DP-V0 communication
60
Req 73 93 03 00 00 00 04 B2 04 7F 34 15 00 00 00 00 00 00 00 00
Resp 43 93 03 00 00 00 04 B2 03 37 34 15 00 00 00 00 00 00 00 00
DP-V0 communication
61
Req 73 94 03 00 00 00 00 68 04 7F 34 15 00 00 00 00 00 00 00 00
Resp 43 94 03 00 00 00 00 68 03 37 34 15 00 00 00 00 00 00 00 00
DP-V0 communication
62
DP-V0 communication
63
DP-V1 communication
Overview
This chapter describes the PROFIBUS messaging used in the
communication with the drive when the RPBA-01 module is in DP-
V1 mode.
PROFIBUS DP
The RPBA-01 module supports the PROFIBUS-DP protocol
according to EN 50170 standard. PROFIBUS DP is a distributed
I/O system which enables the master to use a large number of
peripheral modules and field devices. The data transfer is mainly
cyclic: the master reads the input information from the slaves and
sends the output information back to the slaves.
The PROFIBUS DP protocol uses so-called PPOs
(Parameter/Process Data Objects) in cyclic communication. See
Figure 10 for the different PPO types and their composition.
DP-V1 communication
64
Communication start-up
The following Service Access Points (SAPs) are used to initiate
DP communication:
SAP no. Short Name Name
51 Server_SAP Acyclic Read/Write
61 Set_Prm Send Parameter Data
62 Chk_Cfg Check Configuration Data
60 Slave_Diag Read Slave Diagnostic Information
0 (Default SAP) Data_Exch Transfer Input and Output Data
SAP 61 (Set_Prm)
This SAP is used in the parameterisation of the drive.
Prm_Data (Parameter Data Standard)
Type: Octet String - Length: 8
Byte Value Description
0 B8h Station_Status
MSB 1 0 1 1 1 0 0 0 LSB
Reserved
WD_On
1 = Watchdog on
Freeze_Req
1 = Slave is requested to process in freeze mode
Sync_Req
1 = Slave is requested to process in SYNC mode
00 = Min TSDR and slave-related
Unlock_Req parameters may be overwritten
10 = Slave locked for other masters.
Lock_Req All parameters can be carried over
x1 = Slave released for other masters
DP-V1 communication
65
7 DPV1_Status_1
MSB x 0 x 0 0 x x x LSB
Reserved
Publisher_Enabled
0 = Slave not operated in DXB Publisher mode
1 = Slave operated in DXB Publisher mode
(Not supported)
DPV1_Enable
0 = Slave operated in DP mode
1 = Slave operated in DP-V1 mode
DP-V1 communication
66
8 DPV1_Status_2
MSB x x x x x x 0 x LSB
Chk_Cfg_Mode
0 = Chk_Cfg according to EN 50170 (default state)
1 = User-specific evaluation of Chk_Cfg
Enable_Status_Alarm
0 = Enable_Status_Alarm disabled
1 = Enable_Status_Alarm enabled (Not supported)
Enable_Manufacturer_Specific_Alarm
0 = Enable_Manufacturer_Specific_Alarm disabled
1 = Enable_Manufacturer_Specific_Alarm enabled
(Not supported)
Enable_Diagnostic_Alarm
0 = Enable_Diagnostic_Alarm disabled
1 = Enable_Diagnostic_Alarm enabled (Not
supported)
Enable_Process_Alarm
0 = Enable_Process_Alarm disabled
1 = Enable_Process_Alarm enabled (Not supported)
Enable_Pull_Plug_Alarm
0 = Enable_Pull_Plug_Alarm disabled
1 = Enable_Pull_Plug_Alarm enabled (Not
supported)
9 DPV1_Status_3
MSB 0 0 0 x x x x x LSB
Prm_Structure
0 = Prm telegram according to EN 50170
1 = Prm telegram in structure form (DPV2 extension)
(Not supported)
DP-V1 communication
67
Reserved
DP-V1 communication
68
DP-V1 communication
69
SAP 60 (Slave_Diag)
This SAP gives diagnostic information on the slave station.
Diag_Data (Diagnostic Data)
Type: Octet String - Length: 6 (Standard) + 2 (Extended Diagnosis)
Byte Description
0 Station_Status_1
MSB x x x x x x x x LSB
1 Station_Status_2
MSB x 0 x x x 1 x x LSB
DP-V1 communication
70
Reserved
3 Diag.Master_Add
The address of the master that parameterised this slave
4 - 5 Ident_Number (for RPBA-01: 0812h)
6 Header Byte
7 Status Type = Status Message (0x81)
8 Slot Number (0x00)
9 Specifier (0x00)
10 Communication Diagnostic
MSB 0 0 0 0 0 0 x x LSB
SAP 0 (Data_Exchange)
Allows the master to send output data to a slave station and to
simultaneously request input data from the same station.
Outp_Data (Output Data)
Type: Octet String - Length: 4 to 28 (depending on the selected PPO Type)
Inp_Data (Input Data)
Type: Octet String - Length: 4 to 28 (depending on the selected PPO Type)
DP-V1 communication
71
Parameter
channel
DW1.1 DW1.2 DW1.3 DW3.1 DW3.2 DW3.3 DW5.1 DW5.2 DW5.3 DW7.1
OUT area IND VALUE CW REF PZD3 PZD4 PZD5 PZD6 PZD7 PZD8 PZD9 PZD10
IN area ID IND VALUE SW ACT PZD3 PZD4 PZD5 PZD6 PZD7 PZD8 PZD9 PZD10
PKW DW2.1 DW2.2 DW2.3 DW4.1 DW4.2 DW4.3 DW6.1 DW6.2 DW6.3 DW8.1
Type 1 DP-V0
Type 2 DP-V0
Type 3 DP-V1
Type 4 DP-V1
Type 5 DP-V0
Type 6 DP-V1
Parameter Identification:
ID – Parameter Identification
IND – Index for Arrays
VALUE – Parameter Value (Max. 4 bytes)
PKW – Parameter ID/Value
Process Data:
CW – Control Word (see Table 11.)
SW – Status Word (see Table 12.)
REF – Reference
ACT – Actual Value
PZD – Process Data (application-specific)
DW – Data Word
DP-V1 communication
72
References
References are 16-bit words containing a sign bit and a 15-bit
integer. A negative reference (indicating reversed direction of
rotation) is formed by calculating the two’s complement from the
corresponding positive reference.
ABB drives can receive control information from multiple sources
including analogue and digital inputs, the drive control panel and a
communication module (e.g. RPBA-01). In order to have the drive
controlled through PROFIBUS, the communication module must
be defined as the source for control information, e.g. Reference.
In the Vendor Specific mode, the scaling of the integer received
from the master as Reference is drive-specific. See its
programming manual for available control source selections and
Reference scaling factors.
In PROFIdrive mode, the speed reference (REF) in hexadecimal
(0 … 4000h) corresponds to 0 … ‘motor nominal speed’.
Actual Values
Actual Values are 16-bit words containing information on the
operation of the drive. The functions to be monitored are selected
by a drive parameter. The scaling of the integers sent to the
DP-V1 communication
73
DP-V1 communication
74
DP-V1 communication
75
DP-V1 communication
76
DP-V1 communication
77
SWITCH-ON
MAINS OFF INHIBIT (SW Bit6=1)
C D ENABLE
OPERATION (SW Bit2=1)
A (CW Bit4=0 Bit5=0 Bit6=0)
(CW Bit5=0) (CW Bit4=1)
Inching 1 or 2 ON
(CW Bit8=1 or Bit9=1)
D RFG: ENABLE
OUTPUT INCHING 1
B or
(CW Bit6=0) (CW Bit5=1) INCHING 2
ACTIVE
RFG: ENABLE Inching 1 or 2 OFF
state ACCELERATION (CW Bit8=0 or Bit9=0)
C
(CW Bit6=1) Inching pause
condition
rising edge OPERATING ‘n=0 or f =0’ and ‘I=0’
of the bit (SW Bit8=1) and inching pause expired
D
DP-V1 communication
78
Write response
without data
DP-V1 communication
79
request will be repeated by the master until the RPBA-01 has the
PROFIdrive response data ready.
If the write request is invalid, a negative response is returned with
a DP-V1 error code (see Table 17).
DP-V1 communication
80
DP header DP trailer
SD LE LEr SD DA SA FC DSA SSA DU FCS ED
68h x x 68h xx xx x xx xx x… xx 16h
SD = Start Delimiter
LE = Length
LEr = Length repeated
DA = Destination Address
SA = Source Address
FC = Function Code
DSAP = Destination Service Access Point
SSAP = Source Service Access Point
DU = Data Unit for DP services
FCS = Frame Checking Sequence
ED = End Delimiter
Data unit
DP-V1 Command/Response PROFIdrive V3 Parameter Channel
Request/Response header
DU0 DU1 DU2 DU3 Data
(see Table 18/19 below)
DP-V1 communication
81
DP-V1 communication
82
MSB x x x x x x x x LSB
DP-V1 communication
83
DP-V1 communication
84
DP-V1 communication
85
DP-V1 communication
86
DP-V1 communication
87
83h … Manufacturer-specific –
8Bh
8Ch Set torque mode error Cannot change mode to TORQUE
(frequency is used)
90h Illegal Request ID The request ID of the response is illegal
8Dh … Manufacturer-specific –
FFh
DP-V1 communication
88
Note: Only the “Data unit” part of the SD2 telegram is presented in
the examples. See Figure 14 on page 80.
DP 5F 01 2F 0A 05 01 01 01 10 01 00 04 00 B4 DP
header DP-V1 Command PROFIdrive V3 Parameter Channel trailer
DP-V1 communication
89
DP 5E 01 2F 08 05 01 01 01 42 01 05 64 DP
header DP-V1 Response PROFIdrive V3 Parameter Channel trailer
DP 5E 01 2F 08 05 81 01 01 44 01 00 14 DP
header DP-V1 Response PROFIdrive V3 Parameter Channel trailer
DP-V1 communication
90
DP 5F 01 2F 16 06 01 01 03 10 01 00 04 00 B4
•••
header DP-V1 Command PROFIdrive V3 Parameter Channel
10 01 00 04 00 B5
••• •••
(Par. Channel continued)
10 01 00 04 00 B6 DP
•••
(Par. Channel continued) trailer
DP-V1 communication
91
DP 5F 01 2F 10 06 01 01 03 42 01 01 90
•••
header DP-V1 Response PROFIdrive V3 Parameter Channel
42 01 03 84
••• •••
(Par. Channel cont’d)
42 01 01 F4 DP
•••
(Par. Channel cont’d) trailer
The values 190h (400), 384h (900) and 1F4h (500) are returned.
DP-V1 communication
92
Function number
Slot number
Index
Data length
Request reference
Request ID (02h = Change)
Axis
Number of parameters
Attribute (10h = Value)
Number of elements
Parameter index
Subindex
Format (42h = Word)
Number of values
Value
DP 5F 01 2F 0E 07 02 01 01 10 01 00 04 00 B2 42 01 02 58 DP
header DP-V1 Command PROFIdrive V3 Parameter Channel trailer
Slot number
Slot number
Index
Data length
Request reference (mirrored)
Response ID
Axis (mirrored)
Number of parameters
5E 01 2F 04 07 02 01 01
DP DP
header PROFIdrive V3 trailer
DP-V1 Response
Parameter Channel
DP-V1 communication
93
DP 5F 01 2F 14 08 02 01 02 10 01 00 04 00 B2
•••
header DP-V1 Command PROFIdrive V3 Parameter Channel
10 01 00 04 00 B3
••• •••
(Par. Channel continued)
42 01 01 2C
••• •••
(Par. Channel cont’d)
42 01 01 F4 DP
•••
(Par. Channel cont’d) trailer
Value
Number of values
Format (42h = Word)
DP-V1 communication
94
Slot number
Slot number
Index
Data length
Request reference (mirrored)
Response ID
Axis (mirrored)
Number of parameters
5E 01 2F 04 08 02 01 02
DP DP
header PROFIdrive V3 trailer
DP-V1 Response
Parameter Channel
DP 5F 01 2F 0A 09 01 01 01 10 00 03 96 00 00 DP
header DP-V1 Command PROFIdrive V3 Parameter Channel trailer
DP-V1 communication
95
DP 5E 01 2F 08 09 01 01 01 42 01 23 00 DP
header DP-V1 Response PROFIdrive V3 Parameter Channel trailer
DP-V1 communication
96
DP 5F 01 2F 0E 0A 02 01 01 10 01 03 93 00 03 42 01 04 B6 DP
header DP-V1 Command PROFIdrive V3 Parameter Channel trailer
DP 5E 01 2F 08 0A 01 01 01 42 01 00 68 DP
header DP-V1 Response PROFIdrive V3 Parameter Channel trailer
DP-V1 communication
97
DP 5F 01 2F 0A 0B 01 01 01 10 01 03 94 00 03 DP
header DP-V1 Command PROFIdrive V3 Parameter Channel trailer
DP 5E 01 2F 08 0B 01 01 01 42 01 04 B5 DP
header DP-V1 Response PROFIdrive V3 Parameter Channel trailer
DP-V1 communication
98
DP-V1 communication
99
Fault tracing
LED indications
The RPBA-01 module is equipped with three diagnostic LEDs.
The description of the LEDs is below.
Host
ERROR
Indication
Off-line On-line
Green possible.
Off - Module is not On-Line
Lit - Module is Off-Line and no data exchange is
Red possible.
Off - Module is not Off-Line
Fault tracing
100
Host
ERROR
Indication
Off-line On-line
Fault tracing
101
PROFIdrive parameters
PROFIdrive parameters
102
PROFIdrive parameters
103
PROFIdrive parameters
104
PROFIdrive parameters
105
PROFIdrive parameters
106
PROFIdrive parameters
107
PROFIBUS definitions
Acyclic Communication in which messages are sent only once
Communication on request
Array Parameter consisting of data fields of equal data type
Broadcast Non-acknowledged message from master to all bus
participants (compare Multicast)
Command Word See Control Word
Communication Any object of a real device that can be communicated
Object with (variable, program, data range, etc.). Stored locally
in the Object Dictionary.
Control Word 16-bit word from master to slave with bit-coded control
signals (sometimes called the Command Word).
Cyclic Communication in which Parameter-/Process Data-
Communication Objects are sent cyclically at pre-defined intervals
Device Class Classification according to the number of profile
functions included in the device
Drivecast Broad- and Multicast, a special message frame for
drives
Fault Event that leads to tripping of the device
GSD File ASCII-format device description file in a specified form.
Each device (active & passive stations) on PROFIBUS
has to have its own GSD File.
Index Access reference for Objects in PROFIBUS
Information Report Non-acknowledged message from master to one or all
groups of bus participants
PROFIBUS abbreviations
The text in italics is the original German term.
.con Confirmation
.ind Indication
.req Request
.res Response
ACT Actual Value
Istwert
AK Request Label/Response Label
Auftragskennung/Antwortkennung
ALI Application Layer Interface
CR Communication Reference
Kommunikationsreferenz (Kommunikationsbeziehung)
DP Decentralised Periphery
Dezentrale Peripherie
DP-ALI Application Layer Interface for DP
DP-V1 PROFIBUS DP Extensions to the EN 50170 standard,
including e.g. acyclic data exchange
FDL Fieldbus Data Link
FMS Fieldbus Message Specification
FSU Manufacturer Specific Interface
Firmenspezifischer Umsetzer
HIW Main Actual Value
Hauptistwert
HSW Main Reference
Hauptsollwert
Technical data
RPBA-01
Enclosure:
34 mm
95 mm
20 62 mm
mm
Mounting: Into the option slot on the control board of the drive.
Degree of protection: IP20
Ambient conditions: The applicable ambient conditions specified
for the drive in its Hardware Manual are in effect.
Hardware settings:
• Rotary switches for node address selection (address range
00 to 99)
• DIP switch for bus termination selection
Technical data
112
Software settings:
• Input/Output/User Parameter data/Diagnostics format
• Maximum cyclic I/O data size: 28 bytes in, max 28 bytes out,
max. 56 bytes total
• Maximum acyclic I/O data size: 240 bytes in, max. 240 bytes
out, max. 480 bytes total
• Maximum User Parameter data/Diagnostics length: 26 bytes
Connectors:
• 34-pin parallel bus connector
• 9-pin female DSUB connector
Current consumption:
• 350 mA max. (5 V), supplied by the control board of the drive
General:
• Estimated min. lifetime: 100 000 h
• All materials UL/CSA-approved
• Complies with EMC standards EN 50081-2 and EN 50082-2
Technical data
113
PROFIBUS link
Compatible devices: All devices compatible with the PROFIBUS
DP protocol
Size of the link: 127 stations including repeaters (31 stations and
1 repeater per segment)
Medium: Shielded, twisted pair RS-485 cable
• Termination: built in the module
• Specifications:
Line A Line B
Parameter Unit
PROFIBUS DP DIN 19245 Part 1
Impedance 135 to 165 100 to 130 W
(3 to 20 MHz) (f > 100 kHz)
Capacitance < 30 < 60 pF/m
Resistance < 110 – Ω /km
Topology: Multi-drop
Serial communication type: Asynchronous, half Duplex
Transfer rate: 9.6 kbit/s, 19.2 kbit/s, 45.45 kbit/s, 93.75 kbit/s,
187.5 kbit/s, 500 kbit/s, 1.5 Mbit/s, 3 Mbit/s, 6 Mbit/s, or 12 Mbit/s
(automatically detected by RPBA-01)
Protocol: PROFIBUS DP
Technical data
114
Technical data
3AFE64504215 REV F EN
EFFECTIVE: 20.06.2005
Troubleshooting...........................................................11.1 - 11.6 11
2 Safety
This section describes warning and information signs used in this manual.
The user should pay close attention to these signs.
The softstarter should be installed by authorized personnel only.
This manual is a part of the softstarter and should always be accessible to
personnel working with this product.
The manual should always be read before performing any installation or
commissioning tasks.
1
About the documentation for the softstarter .......................................................... 1.2
About the installation and commissioning manual ................................................ 1.2
Intended audience ......................................................................................... 1.2
General....................................................................................................... 1.2
Requirements.............................................................................................. 1.2
Chapters included.................................................................................................. 1.2
Revision notes........................................................................................................ 1.3
Acronyms and abbreviations.................................................................................. 1.3
PST30/PSTB1050 Softstarters
Installation and Maintenance manual
Document ID: 1SXU 132 021 M0201 - English
1SFC132003M0101 (German)
1 1SFC132003M0101 (German)
1SFC132003M3401 (Swedish)
1SFC132003M0301 (French)
1SFC132003M0901 (Italian)
1SFC132003M0701 (Spanish)
1SFC132003M3101 (Dutch)
1SFC132003M1601 (Portuguese)
1SFC132003M1801 (Finnish)
1SFC132003M1101 (Russian)
1SFC132003M2001 (Chinese
1SFC132003M1901 (Turkish)
1:2.1.2 Requirements
All personnel who interact with the softstarter must have a basic knowledge in handling electric equipment. The commissioning and maintenance per-
sonnel must be well experienced in using this kind of equipment.
Acronym/abbreviation Description 1
LED Light Emitting Diode
LCD Liquid Crystal Display
SCR Silicon Controlled Rectifier
IT Information Technology
HMI Human-Machine Interface
FBP Fieldbusplug
PLC Programmable Logic Controller
PCB Printed Circuit Board
TOR Top of Ramp (full voltage)
Connection..............................................................................................................2.2
Configuration...........................................................................................................2.3
Start of the motor.....................................................................................................2.3 2
This chapter is a short guide on how to connect, configure and start the softstarter in the quickest
1 and safest way.
2
! Warning!
Mounting and installing the softstarter shall be done in accordance with local laws and
regulations and must be performed by authorized personnel only.
Do not change any parameters in the Service Settings menu.
2 3
2:1 Connection
1. Mount the softstarter according to Chapter 4 “ Mounting” .
2. Be aware of the ambient temperature. Derating is required above 40 °C (104 °F). See Chapter
4 3 for more information.
Figure 1: 3. Connect the main circuit: terminals 1L1 - 3L2 - 5L3 to the line side and terminals
1 Status indication LEDs 2T1 - 4T2 - 6T3 to the motor side.
2 LCD display 4. Connect the control voltage: terminals 1 and 2 (100-250V 50/60Hz).
3 Selection keys for selecting, changing and storing parameters
4 Navigation keys for navigating in the menus 5. Connect the functional ground: terminal 3.
* Arrows shown in the display indicate that the value/menu is
possible to change or scroll
Information!
The wire shall be as short as possible, and be connected to the mounting plate.The
mounting plate should also be grounded.
6. Connect the start/stop circuits: terminal 4, 5, 8, 9 and 10 according to Figure 2. 24 VDC only!
7. Verify that the main and control voltage corresponds to the softstarter ratings.
8. Switch on the control voltage.
9. The green “Power on” LED should be lit and the LCD should appear as shown in Figure 3.
2:2 Configuration
Application Setting 1. Enter the Application Setting by pressing the left selection key twice. Press Select using the
left selection key. See Figure 4.
Select Back
Figure 4: Application setting menu 2. Select the appropriate type of load by using the navigation keys. See Figure 5.
3. Press Store Set and Next to continue or Back to previous parameter using the selection
keys. See Figure 6.
Centrifugal Pump 4. Set Ie (motor FLA) using the navigation keys.
In Line connected = rated motor current
Store Set Back Inside Delta connected = 58% (1/( 3)) of the rated motor current. For example, if the soft
Figure 5: Centrifugal pump starter is connected in line with a 100A motor, Ie = 100A. If the softstarter is connected inside
the delta of a 100A motor, Ie = 58A. See Figure 7.
5. Press Store and Next to continue or press Back to access the previous parameter. See Fig- 2
Centrifugal Pump ure 8.
Next Back 6. Set the required overload class using the navigation keys. See Figure 9.
Figure 6: Centrifugal pump stored 7. Press Store and Next to continue or press Back to access the previous parameter. See Fig-
ure 10.
Setting Ie 99.0A 8. If an external by-pass contactor is used set Ext ByPass to Yes using the navigation keys.
(PST30...300 only). See Figure 11.
Store 9. Press Store and Next to continue or Back to previous parameter using the selection keys.
Figure 7: Setting Ie See Figure 12.
10. Select Yes if ready or Tune Set if ramp times, initial voltage, current limit etc. need to be
Setting Ie 99.0A adjusted. See Figure 13.
Next Back 11. To change language, see Section 7:2.5.
Figure 8: Setting Ie stored
2:3 Start of the motor
1. Switch on the main voltage.
OL Class 10 2. Give a start command to the softstarter.
Store (To start the softstarter from the keypad, enter the LOCAL CONTROL menu, select Start/
Figure 9: OL Class Stop and press Start. The motor must be stopped before leaving this menu.)
OL Class 10
Next Back
Figure 10: OL Class stored
Ext ByPass No
Store
Figure 11: External Bypass
Ext ByPass No
Next Back
Figure 12: External Bypass stored
Ready?
Yes Tune Set
Figure 13: Ready / Tune Set
Overview.................................................................................................................3.2
Functions.................................................................................................................3.2
Markings and connections.......................................................................................3.3
Type designation.....................................................................................................3.4
Industrial IT..............................................................................................................3.4
3
Environmental influence..........................................................................................3.4
Specifications..........................................................................................................3.4
Technical data.........................................................................................................3.5
General..............................................................................................................3.5
Semi-conductor fuses........................................................................................3.5
Softstarter types.................................................................................................3.6
Weights..............................................................................................................3.7
PSTB AC3 (Across the line) Contactor Ratings.................................................3.7
UL Information....................................................................................................3.7
Dimensions..............................................................................................3.8 - 3.10
This chapter describes the softstarter in general, specifications and available accessories and
spare parts.
3:1 Overview
The PST softstarter is a microprocessor-based softstarter designed with the latest technology for
the soft start and soft stop of squirrel cage motors. The softstarter has several advanced motor
protection features as standard.
The softstarter is designed to be used with or without a by-pass contactor except for the larger
sizes, PSTB370...1050 where the bypass contactor is integrated. In an emergency, it is possible
to start the motor across the line with the integrated bypass contactor. See Section 3:8.4 for AC3
ratings.
The keypad on the front is designed to be as user-friendly as possible, with a clear text display. It
is possible to choose between twelve different languages (default is English).
The softstarter can be controlled in four ways:
• Hardware inputs
3 • Keypad control (local)
• Fieldbus communication interface
• Remote keypad (option)
The integrated fans for cooling are operated only during ramping (start/stop) and when the tem-
perature of the heat sink is too high. The temperature is monitored by a thermistor.
Only one type of control method can be enabled simultaneously.
Default selection is hardware inputs.
Information!
Keypad control has the highest priority and overrides all other control methods.
3:2 Functions
The PST softstarter has several integrated protection and warning functions. Almost any type of
fault can be detected and displayed.
All available protections, warnings and fault indications are listed below.
Start/Stop functions
• Start ramp
• Stop ramp (also called soft stop or decel)
• Initial voltage
• Step down voltage
• Current limit
• Kick Start
• Extended start range
• Extended stop range
• Sequence start
Protection functions
• Motor overload protection
• Locked rotor protection
• Motor underload protection
• High current protection
• Phase imbalance protection
• Phase reversal protection
• SCR overload protection
• PTC input for motor protection
• Shorted SCR
Warning functions
• Warning high current
• Warning low current
• Warning motor overload
• Warning SCR overload
Fault Supervision functions
• Internal softstarter faults
• Shorted SCR
• Non conducting SCR
• Open circuit motor side
• Over-temperature heat sink
• Phase loss
• Frequency out of range
• Fieldbus communication
• Non-closing by-pass contactor
• Non-opening by-pass contactor
3
Other functions
• Jog
• Real time clock
• Event log
• Keypad password
Line side
connection
Bypass connection
(PST30...300 only)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
L N
100-250V
50/60 Hz Stop Start In0 In1 Vc Vn Vp Vp K4 K5 K6
Green
Red
Yellow
Display
Keypad
Terminal marking
of main circuit
1L1 B1 3L2 B2 5L3 B3
Order code
2T1 4T2 6T3
Technical data
according to
UL 508
Us:
100-
Ie:
37-7 250V
2A AC/D
UL C
Ue:
Uc:
100- In line
FLA 250V Ove 220-
: 37-6 AC/D rload 230
Cap 18,5 380-
CA 8A C
acity 400
UT Ue
ION 115% 37 500
Fuse In of Con
Max 250A line 208 tinuo 45 V
shor TYP us kW
t circu OW 20 220-
ER 240
it curr
ZILO 20 440-
ent X 480
65kA LIS
PTC connection
Key at 50 V INDTED
pad Hp . CO 7F3
NT. 9
External keypad
EQ
.
PTC
Wire
1-8
Al
Cu
connection
75C
only
, 35lb
Fie -in
ldb
us
3
30
20
12 91011
1213
5678
Serial number
1234
10
00
01
16
1S
Control Voltage
70 = 100 - 250V 50/60 Hz
Main Voltage
600 = 208 - 600V 50/60 Hz
690 = 400 - 690V 50/60 Hz
Current Rating
600 = 208 - 600V 50/60 Hz
690 = 400 - 690V 50/60 Hz
Bypass contactor
3 600 = 208 - 600V 50/60 Hz
690 = 400 - 690V 50/60 Hz
Softstarter type
3:4 Industrial IT
Thanks to ABB’s broad program of product standardisation, today’s Industrial IT components are - whether they are products or systems, hardware or
software - the building blocks of larger solutions, incorporating functionalities that will allow seamless interactions in real-time automation and informa-
tion systems.
At the product level, ABB’s Industrial IT enabled symbol ensures that all the products can fully interact. All product information pertaining to these
products is available in electronic format, based on Aspect ObjectTM technology. The Industrial IT commitment from ABB ensures that every product is
equipped with the tools necessary to install, operate and maintain it efficiently throughout the product’s life cycle.
The PST softstarters is an Industrial IT enabled product. Documentation such as brochures, catalogues, certificates and drawings can be found at :
www.abb-control.com/products/softstarters.htm#type_pst.
3:7 Specifications
Item Specification
Degree of protection (main circuit) IP 10 for PST30...72; IP 00 for PST85...1050
Operating position Vertical at ± 10°
Ambient temperature Storage: -25°C to +70°C (-13°C to 158°F)
Operation
Without derating 0°C to +40°C (32°F to 104°F)
With derating +40° C to +50°C (104°F to 122°F) of 0.8% / °C (1.8%/°F)
Altitude 1000 m (3281 ft.) above sea level without derating
1000 - 4000 m (3281 - 13,123 ft.) by derating 1% for each 333 ft above 3300 ft.
Pollution degree 3
Relative humidity 5 - 95% (non-condensing)
Standards UL508
IEC 60947-1
IEC 60947-4-2
EN 60947--1
PTC input IEC 60947-8 Mark A detectors, DIN 44081 and DIN 44082
Marine approvals Contact your ABB sales office
3
Programmable inputs 24 VDC, 10 mA
Output relays 250 VAC, Ith = 5A, le = 1.5A (AC-15)
Battery back-up D20mm Lithium 3V CR2032
PTC input 2825 ohm ±20% switch off resistance
1200 ohm ±20% switch on resistance
Cooling system Fan
Recommended fuse for control circuit 6A Delayed
MCB use C characteristics
Service factor 115% (100% for PSTB1050)
Communication protocols AS-Interface DeviceNet / Profibus DP /
Modbus
3:8.4 Weights
3:8.6 UL information
Equipment suitable for use in a circuit with maximum available fault current as shown when protected by devices indicated.
Inches
[[ Millimeters
3:8.7 Dimensions
PST30...72
PST85...142
Inches
[[ Millimeters
PSTB175...300
PSTB370...470
Inches
[[ Millimeters
PSTB570...1050
This chapter describes instructions on how to receive the softstarter and how to mount it in the proper
way.
! Warning!
Do not lift the softstarter by the connection bars. Lifting by the connection bars may cause
damage to the product.
Figure 2: Airways
4:2.2 Requirements
See Chapter 3 “Description” for environmental requirements.
4:2.3 Minimum distance to wall/front
A
To ensure a suitable cooling, the softstarter must be mounted vertically and in such a way that the
airways are not blocked, see Figure 2.
Use the table below and Figure 3 for minimum distances between wall/front of the PST softstarter.
Information!
The values are minimum distances.
A B C
Softstarter type
mm in mm in mm in
B B A
PST30...72 100 3.94 10 0.39 20 0.79
PST85...300 100 3.94 10 0.39 20 0.79
PST175...300 100 3.94 10 0.39 20 0.79
PSTB370...470 150 5.91 15 0.59 20 0.79
General ..................................................................................................................5.2
Electrical connection..............................................................................................5.2
Main circuit........................................................................................................5.2
External Bypass contactor................................................................................5.3
Protective earthing............................................................................................5.3
Control voltage and control circuit.....................................................................5.4
Control voltage, terminals 1 and 2............................................................5.4
Grounding, terminal 3...............................................................................5.4
Start and Stop, terminals 4, 5, 8, 9, 10, 11................................................5.4
Programmable inputs, terminals 6 and 7..................................................5.5
Programmable output relay K4, terminals 12, 13 and 14.........................5.6 5
Programmable output relay K5, terminals 15, 16 and 17.........................5.7
Programmable output relay K6 terminals 18, 19 and 20..........................5.7
PTC input..................................................................................................5.7
Connection of communication devices (optional)...................................................5.8
Fieldbus communication...................................................................................5.8
External keypad................................................................................................5.8
Transferring parameters....................................................................................5.8
Uploading parameters..............................................................................5.8
Technical data...........................................................................................5.9
This chapter describes the electrical connections as well as connections for communication
devices (optional) that must be made before the softstarter can be operated.
5:1 General
PST30...
PSTB1050
Caution!
All wiring and connection must be carried out by a qualified electrician, and in
accordance with installation standards and safety regulations.
Figure 1: In Line Connection
See Chapter 2 “ Quickstart”.
5
Connect the line side to terminals 1L1, 3L2, 5L3.
Connect the motor to terminals 2T1, 4T2, 6T3 on the motor side.
The terminal marking is printed on the front label.
For torque requirements and cable sizes, see Figure 5.
Figure 2: Inside Delta connection
5L3
3L2
1L1
Line side
Motor side
20
19
18
K6
17
16
15 1S
14 K5 FA
13 IEC 894 00
100947- 7
Us:
12 Ie:
37-
-25
0V 4-2
11 K4
UL
72A AC
/DC
10 Vp Ue 72:
AC Ma
9 Uc:
100
:
In line
-53a
de
in
8
-25 220
Vp FLA 0V Ov
erlo -23 Sw
: 37- AC 18, 0 380 : 8- ed
7
ad en
Vn CA 68A
/DC Ca
pac 5 1.6:
-40
6 Vc UT
ION Ue ity
115 37
0
3 4 In0 Ma e 250
x sho A
208 ntin 45 V
Start
TY uou
rt circ 220 s kW
2
PO 20
Stop uit WER -24
1 cur ZIL
ren OX 20
0
440
-48
100-250V
t 65k 0
A at LIS
Hz Ke 50 V INDTED
50/60 y-P
ad Hp . CO7F
NT 39
. EQ
.
PT
C
Wir
e 1-8
Al
Cu
75C
onl
y, 35l
b-in
FIE
LD
BU
S
en
ed
Sw
in
de 39
Ma V 7F .
1.6:500 D . EQ in
kW lb-
TE NT 35
: 8- LIS CO C on
ly, SS
3a0-400 45 IND. 75 BU
C-5 38
LD
Cu FE
: A 30 37
Al
7 V 1-8
4 00 72 22180-2,5 ntinuous 80 Wi
re
89 : Co 44
0-4
FA 4-2 Ue line %
of
40
1S 7- /DC In pacity 115 220-2
C 9450V AC d Ca 20
8
IE: 10 A
0-2
erl
oa
Us Ov C
-72 Ue OX at PT
37
Ie:
/DC R ZIL kA
WE nt 65
V AC
UL100-250
PO rre
TY it cu
0A
: A 25 circu ad
se
Uc
37
-68 Fu x short Key-P
A: Ma
FL
ION
UT
CA
Connect the contactor to terminals B1, B2 and B3 on the line side and terminals 2T1, 4T2
and 6T3 on the motor side.
The terminal markings are printed on the front label.
20
19
18
17
K6
16
15
K5
14
13
12
11 K4
10 Vp
9
8 Vp
7 Vn
6 Vc
5 In1
3 4 In0
Start
1 2 Stop
100-250V
Hz
50/60
Information!
Figure 4: External bypass contactor Do not use terminals B1, B2 or B3 for the “Inside Delta” connection. The current
connection measurement will be wrong.
Warning!
Do not operate machine with the grounding wire disconnected 5
PST 30...72
2
1L1 B1 3L2 B2 5L3 B3 4 mm 1 x 6 ...... 70 mm
2 x 6 ...... 35 mm 2
M8 !WG 1...8
14
1 x 6 ...... 70 mm 22
2 x 6 ...... 35 mm
14
2T1 4T2 6T3 6 Nm - 53 lb.in
PST 85...142
1L1 B1 3L2 B2 5L3 B3
M8
PST 175...300
Figure 5: Protective earthing. 1L1 B1 3L2 B2 5L3 B3
M8
PSTB 370...470
1L1 3L2 5L3
M10
PSTB 570...1050
1L1 3L2 5L3
M12
Information!
6
7
8
Vc
Check that you have the correct control voltage Us.
5 In1
3 4 In0
Start
1 2 Stop
V
100-250Hz
50/60
Information!
This is not a protective ground, it is a functional ground. The grounding cable should be
as short as possible. Maximum length: 1.5 ft.
5
5:2.2.3 Start and Stop, terminals 4, 5, 8, 9, 10, 11
7
6
5
In1
3 4p
In0
Start
1 2 Sto
100-250V
Hz
50/60
12
11
10 Vp
9 Vp
8 Vn
7 Vc
6 In1
5
3 4 rt In
0
Sta
1 2 Stop
V
100-250
Hz
50/60
Figure 10: Holding circuit (momentary start signal required) Figure 11: Conventional circuit (maintained start signal required)
M3 3,5x0,6
? 0,14 ... 2,5 mm 2
1. . . . . . . . . . . . . . . . . . . . . . . . 20
AWG 12 ... 22
0,14 ... 2,5 mm2
0,5 Nm - 4,3 lb.in
5
Figure 13: Holding circuit with external control voltage (momentary start signal required) Figure 14: Conventional circuit with external control voltage (maintained start signal is required)
Information!
See next page for multiple motor (sequence) starting
Figure 15: Terminals 6, 7
Figure 16: Internal control voltage Figure 17: External control voltage
M3 3,5x0,6
? 0,14 ... 2,5 mm 2
1. . . . . . . . . . . . . . . . . . . . . . . . 20
AWG 12 ... 22
0,14 ... 2,5 mm2
0,5 Nm - 4,3 lb.in
Stop
Stop
+
DC
-
5
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
L N L N
100-250V 100-250V
50/60 Hz Stop Start In0 In1 Vc Vn Vp Vp K4 K5 K6 50/60 Hz Stop Start In0 In1 Vc Vn Vp Vp K4 K5 K6
Figure 18: Internal control voltage Figure 19: External control voltage
M3 3,5x0,6
? 0,14 ... 2,5 mm 2
1. . . . . . . . . . . . . . . . . . . . . . . . 20
AWG 12 ... 22
0,14 ... 2,5 mm2
0,5 Nm - 4,3 lb.in
20
19
18
K6
17
16
15
K5
14
13
12
11 K4
10 Vp
9 Vp
8 Vn
7 Vc
6 In1
In0
5
See Chapter 7 “ Settings and configuration” for programming.
Connect the cables to terminal 18, 19 and 20.
20
19
18
17 K6
16
15
K5
14
13
12
11 K4
10 Vp
9 Vp
8 Vn
7 Vc
6 In1
In0
PT
C
Wir
e 1-8
Al
Cu
75C
onl
y, 35l
b-in
FE
LD
BU
SS
M3 3,5x0,6
? 0,14 ... 2,5 mm 2
1. . . . . . . . . . . . . . . . . . . . . . . . 20
AWG 12 ... 22
0,14 ... 2,5 mm2
0,5 Nm - 4,3 lb.in
K6
see Figure 26. Make sure that the plug is in correct position and tighten the screw with 0.8 Nm (7.1 lb in) and
additional 1/4 turn.
16
15
K5
14
13
12
11 K4
10
9 Vp
8
7 Vp
6 Vn
5
For programming and other information, see Chapter 7 “ Settings and configuration” and Chapter 8 “ Field-
3 4 In1
Vc
1 2 t In0
L N Star
Stop
50V Hz
100-2 C, 50/60
AC/D
B3
5L3
B2
3L2
den
B1 Swe
1L1 e in 9
Mad V 7F3EQ.
6T3 .6: kW TED T. 35lb
-in
8-1 500 LIS . CON SS
a: 400 45 IND 75C
only,
DBU
4T2 -53380- Cu FEL
: AC230 37 us
Al
7 V 1-8
4 00 72 220-
2T1
tinuo Wire
18,5 480
89 Con 440-
1S
FA -2 Ue:line of
240
7-4 C In acity 115% 220-
94 AC/D Cap 208
IEC100-250V rload
Us: 2A Ove
37-7 Ue X PTC
Ie: at
C R ZILO
65kA
AC/D OWE nt
UL100-250V TYPit curre
250At circu Pad
Uc: 8A
Fuseshor Key-
: 37-6 Max
FLA
ION
UT
CA
5
Figure 27: Principle of a fieldbus network with PST softstarters connected
K6
To transfer (copy) parameters from one softstarter to another, connect the keypad to the chosen softstarter and follow the
sequence below.
15
K5
14
13
12
11 K4
10
9 Vp
8
7 Vp
6 Vn
5
3 4 In1
Vc
1 2 In0
L N Start
Stop
V Hz
100-250 50/60
AC/DC,
B2
5L3
B3
5:3.3.1 Uploading parameters
3L2 en
B1 Swed
1L1 in
Made
: V 7F39 .
D . EQ
6T3 kW 35lb-in
8-1.6
0
500
45 LISTECONT only, USS
3a: IND. 75C
Enter the menu Transfer par. Select To Keypad and confirm by pressing Select. A text Load to Keypad will be displayed..
4T2 380-40 Cu FELDB
AC-50 37
V 1-8
Al
2T1 007 72: 220-23
18,5
ous 0 Wire
A 894 Ue: of
Continu 440-48
0
1SF 4-2 In
line
ty 115% 220-24
947-0V
AC/DC
Capaci 208
IEC100-25 ad
Us: Overlo
37-72A Ue PTC
Ie: ZILOX at
ER 65kA
AC/DC
UL100-250V TYPOW current
d
250Acircuit
Uc: Fuseshort Key-Pa
37-68A
FLA: Max
ION
CAUT
Continue by pressing Execute and then Yes when the text Are You Sure is displayed. Transfer OK will now be displayed
Figure 29: Upload
if the transmission was successful. Otherwise, Transfer Not OK will be displayed.
K5
18
19
20
K6
displayed. Transfer OK will now be displayed if the transmission was successful; otherwise, Transfer Not OK
will be displayed. Set the parameter Setting le and confirm by pressing Next.
13
12
11 K4
10
9 Vp
8
7 Vp
6 Vn
5
3 4 In1
Vc
1 2 In0
L N Start
Stop
Hz
100-250V50/60
AC/DC,
B3
5L3
B2
3L2 en
B1 Swed
1L1 in
Made
: V 7F39 .
D . EQ
6T3 kW 35lb-in
8-1.6
0
500
LISTECONT only, USS
4T2 3a:
380-40
45
IND. Cu
75C
FELDB
AC-50 37
V 1-8
Al
2T1 007 72: 220-23
18,5
ous 0 Wire
A 894 Ue: of
Continu 440-48
0
1SF 4-2 In
line
ty 115% 220-24
947-0V
AC/DC
d Capaci 208
IEC100-25
Us: Overloa
37-72A Ue PTC
Ie: ZILOX at
ER 65kA
AC/DC
UL100-250V TYPOW current
d
250Acircuit
Uc: Fuseshort Key-Pa
37-68A
FLA: Max
ION
CAUT
To learn how to operate the keypad, see Chapter 6 “Human-Machine Interface (HMI)”
Overview........................................................................................................ 6.2
Application................................................................................................ 6.2
Design....................................................................................................... 6.2
Password.................................................................................................. 6.3
Setting password................................................................................. 6.3
Wrong password................................................................................. 6.3
Locking/unlocking the keypad................................................................... 6.3
Menu tree....................................................................................................... 6.4
Overview................................................................................................... 6.4
Top level.................................................................................................... 6.4
Settings menu........................................................................................... 6.5
Local Control menu................................................................................... 6.5
Start/Stop the motor............................................................................ 6.6
Jog...................................................................................................... 6.6 6
DOL start............................................................................................. 6.6
Event Log menu........................................................................................ 6.7
Status Information menu........................................................................... 6.7
Reset Events menu................................................................................... 6.7
This chapter describes how the human-machine interface (keypad and display) works.
1
2
6:1 Overview
Power on Fault Protection
6:1.1 Application
The Human-Machine Interface is used for several purposes such as programming the softstarter, i.e setup of
inputs and outputs, protection functions, warning levels, fieldbus communication, etc. The HMI is also used for
3 monitoring, local control and receiving status information from the softstarter.
4 6:1.2 Design
Figure 1: Human-Machine Interface
1 Status indication LEDs The HMI consists of:
2 LCD display • Status indication LED indicators
3 Selection keys • LCD display
4 Navigation keys • Selection and Navigation keys
The keypad is based on the same user concept as today’s mobile phones.
Setting Ie 100A
The LCD contains two rows with 20 characters each.
Store Cancel
The top row presents various information depending on its state. The bottom row indicates which function is
Figure 2: Menu examples currently selected.
6
1 Scrolling icons A scrolling icon indicates what parameter or setting value is possible to change at the position.
The Selection keys normally have more than one function, such as selecting, changing and storing parameters.
U = 0% I = 0.0A See the text on the bottom row of the LCD.
Menu The Navigation keys are used for navigating through the various menus to the desired setting.
Figure 3: Top level When selecting from a list, the scrolling is done in a closed loop fashion.
Setting Ie 99.5A
Change Back
Figure 10: Setting Ie menu, changing setting
6:1.3 Password
Change Password To lock the keypad from control and change of settings, a password can be set. When the keypad is locked, all
Select Back menus are available but no changes or actions can be initiated.
Figure 11: Change password
Jog
DOL Start
Event Log
Status Information
Reset Events
6
Figure 18: Menu tree
Top level
Settings
6:2.4 Local Control menu
Local Control Start / Stop The Local Control menu is used to start or stop the motor from the keypad. When local con-
trol is selected, the softstarter can only be controlled by the keypad.
Jog The previous type of control is activated when exiting local control.
Three different selections are possible (see the table below).
6
DOL Start
Event Log Press navigation keys to view different types of local control.
Status Information
Reset Events
Figure 21: Local control menu Information!
The LOCAL CONTROL menu can not be entered if Sequence start is selected.
Once the motor has been started in this menu, it must first be stopped before you leave the
menu. If the motor is already running when the menu is entered, it is possible to leave the
menu without stopping the motor.
Function Description
Start/stop To start and stop the motor with the
keypad
Jog To run the motor as long as Jog is
pressed
DOL start To start and stop the motor with the built-
(PSTB370...PSTB1050 only) in by-pass contactor. (See Chapter 3 for
AC3 ratings.)
Figure 21: Local control menu
Reset Events
Figure 22: Start/Stop menu
Reset Events
Figure 23: Jog menu
! Warning!
The rated motor current must never exceed the AC-3 rating of the integrated by-pass contactor.
See Chapter 3 for AC3 ratings.
100-250V
50/60 Hz
8 8
Figure 25: Connection when the contactor is operated Figure 26: Connection when the by-pass contactor is operated
from the keypad (factory wiring). separately (emergency DOL)
Event Log
Status Information
Reset Events
Figure 25: Event log menu
6
Phase L2 Phase current L2
Phase L3 Phase current L3
Run time Total run time of the motor
No. of Starts Run counter
SW Ver. CU Software version CU.
SW Ver. FU Software version FU.
SW Ver KP 1 Software version External Keypad
DB Version Database version
MAC Address Internal addressing
LV Board No Serial No of the LV PCB
1 Only if connected.
Event Log
Status Information
Reset Events
Figure 27: Reset events menu
Settings................................................................................................................ 7.2
Overview of all accessible settings (different menus)............................. 7.3 - 7.7
Description of menus............................................................................................ 7.8
Top level.......................................................................................................... 7.8
Application Setting................................................................................ 7.9 - 7.10
Basic Settings............................................................................................... 7.10
Functional Settings........................................................................................7.11
Start/Stop.................................................................................................7.11
Protections.................................................................................... 7.12 - 7.13
Warnings................................................................................................. 7.14
Faults............................................................................................ 7.14 - 7.15
Inputs...................................................................................................... 7.16
Outputs.................................................................................................... 7.17
Sequence start.............................................................................. 7.18 - 7.19
Presentation Settings.................................................................................... 7.20 7
Service Settings............................................................................................ 7.21
All Settings.................................................................................................... 7.21
Changed Settings.................................................................................... 7.21
Reset all Settings.................................................................................... 7.22
Operation (test) mode............................................................................. 7.22
Changed settings.................................................................................... 7.23
Reset all settings..................................................................................... 7.23
7:1 Settings
Settings can be done in three different ways:
• Keypad
• Fieldbus communication
• External keypad (optional)
With the keypad, settings can be done as individual parameter settings or by selecting pre-
defined parameters for different applications.
The unit has one complete set of parameters but some parameters have extra settings (i.e.,
sequence start). All default parameters are stored in the unit in case a full reset to default values
is required. When the fieldbus communication is selected, most parameters can also be modified
from this interface.
! Caution!
The motor may start unexpectedly if there is a start signal present when doing any of the actions
listed below:
• Switching from one type of control to another (fieldbus control / hardware control)
• Re-programmming the programmable inuts
• Reset all Settings (programmable input set to Enable).
Password X
Keypad lock/unlock X
Reset to factory default setting X
Application type X
Setting le X X X X
Overload class X X X X
External By-pass X X X X
Start ramp Tune Set X X X
Stop ramp Tune Set X X X
Initial voltage Tune Set X X X
End voltage Tune Set X X X
Step down voltage Tune Set X X X
Current limit Tune Set X X X
Kick start X X
Kick level X X
Kick time X X
Start range X X
Stop range X X
Overload protectcion X X
Overload start class X X
Overload run class X X
Overload operation X X
Locked rotor protection X X
Locked rotor protection level X X
Locked rotor protection time X X
Locked rotor protection operation X X
Underload protection X X
7
Underload protection level X X
Underload protection time X X
Underload protection operation X X
Phase imbalance protection X X
Phase imbalance protection level X X
Phase imbalance protection operation X X
High current protection X X
High current protection operation X X
Phase reversal protection X X
Phase reversal protection operation X X
PTC protection X X
PTC protection operation X X
By-pass fault operation X X
Warning high current X X
Warning high current level X X
Warning low current X X
Warning low current level X X
Warning overload X X
Warning overload level X X
Warning thyristor (SCR) overload X X
Phase loss fault operation X X
Fieldbus fault operation X X
Frequency fault operation X X
7 Current limit 3
Language
X
X
X
X
LCD auto off X X
Date type X X
Date year X X
Date month X X
Date day X X
Time hour X X
Time minutes X X
7
Type of operation for imbalance protection Ph Imb Op Stop-M, Stop-A, Ind Stop-M
High current protection High I Yes, No No
Type of operation for high current protection High I Op Stop-M, Stop-A, Ind Stop-M
Phase reversal protection Phase Rev Yes, No No
Type of operation for phase reversal protection Ph Rev Op Stop-M, Stop-A, Ind Stop-M
PTC protection PTC Yes, No No
Type of operation for PTC protection PTC Op Stop-M, Stop-A, Ind Stop-M
Use of external by-pass contactor Ext ByPass Yes, No No
Type of operation, by-pass doesn’t open BP Closed Op Stop-M, Stop A Stop-M
Type of operation, by-pass doesn’t close BP Open Op Stop-M, Stop A Stop-M
High current warning Warn I=High Yes, No No
Trip level for high current warning Wa I=H Lev 0.5...5.0xle 1.2xle
Low current warning Warn I=Low Yes, No No
Trip level for low current warning Wa I=L Lev 0.4...1.0xle 0.8xle
Motor overload warning Warn OL Yes, No No
Trip level for motor overload warning Wa OL Lev 40...99% 90%
Thyristor overload warning Warn SCR OL Yes, No No
Type of operation for phase loss fault Ph Loss Op Stop-M, Stop-A Stop-M
Type of operation for fieldbus fault FB Fault Op Stop-M, Stop-A Stop-M
Type of operation for frequency fault Freq F Op Stop-M, Stop-A Stop-M
Type of operation for heatsink overtemp fault HS Temp Op Stop-M, Stop-A Stop-M
Type of operation for shorted thyristor fault SCR SC Op Stop-M, Stop-A Stop-M
None, Reset,
Function of programmable input In0 In0 Enable Jog, DOL, Reset
Start 2, FB-Dis
7
Phase reversal event of relay K5 K5 Phase Rev Yes, No No
Warning motor overload event of relay K5 K5 Warn OL Yes, No No
Warning thyristor overload event of relay K5 K5 Wa SCR OL Yes, No No
Warning high current event of relay K5 K5 Wa I=High Yes, No No
Warning low current event of relay K5 K5 Wa I=Low Yes, No No
Overload event of relay K6 K6 Overload Yes, No Yes
Fault event of relay K6 K6 Fault Yes, No Yes
Shunt fault of relay K6 K6 Shunt Fault Yes, No Yes
High current event of relay K6 K6 High I Yes, No Yes
Thyristor overload event of relay K6 K6 SCR OL Yes, No No
Locked rotor event of relay K6 K6 Lock Rot Yes, No No
Underload event of relay K6 K6 Underload Yes, No No
Phase imbalance event of relay K6 K6 Phase Imb Yes, No No
PTC event of relay K6 K6 PTC Yes, No No
Phase reversal event of relay K6 K6 Phase Rev Yes, No No
Warning motor overload event of relay K6 K6 Warn OL Yes, No No
Warning thyristor overload event of relay K6 K6 Wa SCR OL Yes, No No
Warning high current event of relay K6 K6 Wa I=High Yes, No No
Warning low current event of relay K6 K6 Wa I=Low Yes, No No
Overload event of relay V7 V7 Overload Yes, No Yes
Fault event of relay V7 V7 Fault Yes, No Yes
High current event of relay V7 V7 High I Yes, No Yes
Thyristor overload event of relay V7 V7 SCR OL Yes, No No
Locked rotor event of relay V7 V7 Lock Rot Yes, No No
Underload event of relay v7 V7 Underload Yes, No No
Phase imbalance event of relay V7 V7 Phase Imb Yes, No No
U=†††0% †I=0.0A
7:2 Description of menus
Menu For detailed description of each function, see Chapter 10 “ Functions” .
Change Password Uin † OK
Select Back Back 7:2.1 Top level
Keypad is Active Motor Temp 0% This level contains information about output voltage, current, heat sink temperature, real time clock
Lock Back Back and more. From this menu, the keypad can be locked/unlocked and a password can be set. It is
also possible to enter all top level menus.
2003-01-30 11:08 SCR Temp 60%
Back Back
Display at start up
5 )!
When switching on the control voltage, the LCD will first display the text “Hello”, and after a few
-ENU seconds switch to the Top Level start position, Figure 2.
Figure 2: Top level (start position)
Uin status
Uin OK
The softstarter checks and displays the status of the input voltage (line side).
Back
Figure 4: Uin status
Motor temperature
Motor Temp 0%
The consumed thermal capacity of the motor is displayed. 0% means that the motor is in cold state.
Back 50% means that half the capacity is consumed, etc.
Figure 5: Motor temperature
7
In = 0000 Out = 0000 Status of inputs/outputs
Back The status of the Programmable inputs and outputs is displayed with “0” for not activated or “1” for
Figure 6: Input/outputs activated. The figures have the following functions:
In=0100 Start signal high
In=1000 Stop signal high
In=0010 In0 high
In=0001 In1 high
Out=1000 Relay K4 activated
Out=0100 Relay K5 activated
Out=0010 Relay K6 activated
Out=0001 SW V7 activated
All settings Select what type of application the softstarter is used for by pressing Store Set. If the
desired application is not listed, select the one closest to the application and choose Tune
Changed settings Set (see below). Possible applications are:
Reset all settings
• Centrifugal Pump
Operation mode • Hydraulic Pump
Figure 10: Application setting menu • Centrifugal Fan
• Axial Fan
• Compressor
• Conveyor
Application Setting • Crusher
Select • Mixer
Figure 11: Application setting menu • Bow Thruster
Confirm the selected application by pressing Next. If the wrong application type was
Centrifugal Pump selected, press Back and select the correct type.
Store Set Back
Figure 12: Application type
Centrifugal Pump
Next Back
Figure 13: Confirming application type
Setting Ie 100A
Store
Figure 14: Setting Ie menu
Setting Ie (motor FLA) 7
Setting Ie 100A
Set the motor full load current (i.e. rated motor current if the unit is connected In Line).
Next Back For units connected Inside Delta, the Setting Ie must be set according to the current in the
Figure 15: Confirming Setting Ie
delta circuit = 58% (1/( 3)) of the rated motor current.
Press Store to save the data after setting the current.
OL Class 10 Confirm the Setting Ie by pressing Next. If the wrong value is set, press Back and set the
Store correct value.
Figure 16: Overload class
Overload class (OL Class)
Select the desired overload class. Available classes:
OL Class 10 • 10A
Next Back • 10
Figure 17: Confirming OL Class • 20
• 30
Ext ByPass Yes Press Store to save the selected class.
Store Confirm the selected overload class by pressing Next. If the wrong overload class was
Figure 18: External By-Pass selected, press Back and select the correct class.
Tuning parameters
Ready? Six parameters can be tuned individually if a more specific adjustment is required. Each
Yes Back parameter is described in Chapter 10 “ Functions” .
Figure 21: All tuning parameters have been passed • Start ramp
• Stop ramp
• Initial voltage
• End voltage
• Step down voltage
• Current limit level
When all tuning parameters have been cycled through, the following information will be
displayed, Figure 21. Select Yes if all necessary parameters are tuned. If a new tuning is
required, select Back and follow the step Tune Set above
Top level
Settings Application setting
7:2.3 Basic Settings
Basic settings The Basic settings menu consists of the most common start/stop parameters required for
the set-up. Each parameter can be adjusted separately. For a detailed description of each
Functional settings
parameter, see Chapter 10 “ Functions” .
Presentation settings Enter the Basic settings
Service settings Enter the menu by selecting Basic Settings.
All settings Setting Ie (motor FLA)
Set the current that the softstarter will be exposed to (i.e. rated motor current, if the unit is
Changed settings connected In Line).
Reset all settings
Operation mode
Figure 22: Basic Settings menu
Information!
For units connected Inside Delta the Setting Ie must be set according to the current in the
delta circuit = 58% (1/( 3)) of the rated motor current. Press Store to save the data after
setting the current
7 Start ramp
Set the ramp time for start.
Stop ramp
Set the ramp time for stop (softstop). Note that this function should only be used for
applications with small flywheel masses, for example pumps and conveyors (minimizes
product damage during the stop).
Changed settings
7:2.4.1 Start/Stop
Settings To set parameters related to start and stop, enter the Start/Stop group. The following
Functional settings Start / Stop parameters are available in this group:
Protections • Setting Ie
• External By-Pass
Warnings • Start ramp
• Stop ramp
Faults
• Initial voltage
Inputs • End voltage
• Step down voltage
Outputs
• Current limit level
Fieldbus • Kick start
• Kick level
Seq. Start • Kick time
Figure 24: Start/Stop group
• Start range
• Stop range
To set parameters from Setting Ie to Current limit level, see “Basic Settings”.
Kick Start 7
Activate the Kick Start function by entering this menu. Press Store to save the
selection.
Kick Level
Set the required level of the Kick Start. Press Store to save the data.
This menu will only be visible if Kick Start is activated.
Kick Time
Set the required time for the kick start. Press Store to save the data.
This menu will only be visible if Kick Start is activated.
Start Range
The ramp time for start can be set between 1 and 30 seconds as default. If required,
the range can be extended up to 120 seconds by entering this menu. Press Store to
save the data.
Stop Range
The ramp time for stop can be set between 0 and 30 seconds as default. If required,
the range can be extended up to 120 seconds by entering this menu. Press Store to
save the data.
The configuration of the parameters in the Start/Stop group is now completed. It is pos-
sible to return to top level by pressing Back three times. To configure the protections,
proceed to that menu.
7:2.4.2 Protections
Settings
Functional settings Start / Stop To set parameters related to the protections, enter the Protections group.
Protections Overload
Select the required overload type for the application. The following selections are available:
Warnings • No
• Normal
Faults
• Dual
Inputs Press Store to save the selected type.
Outputs If overload “Normal” is selected, the following settings will be available:
Fieldbus
Overload class (OL Class)
Select the overload class. Following classes are available:
Seq. Start • 10A
Figure 25: Protections group • 10
• 20
• 30
Press Store to save the selected class.
7
Press Store to save the selected class.
Overload run class (OL Class R)
Select the required overload class during continuous run. The following overload classes
are available:
• 10A
• 10
• 20
• 30
Press Store to save the selected class.
Locked Rotor
Activate the protection if required by changing to Yes.
If “Yes” is selected, the following settings will be available:
Locked rotor level (Lock R Lev)
Set the level of the locked rotor protection.
Available only if the protection is selected.
Locked rotor time (Lock R Time)
Set the time for the locked rotor protection.
Available only if the protection is selected.
Locked rotor type of operation (Lock R Op)
Select what operation should be initiated if the locked rotor protection is activated:
Stop–M The motor will stop and a manual reset is required.
Stop–A The motor will stop and an automatic reset is performed.
Ind Only indication will be given.
Press Store to save the selected operation.
Underload
Activate the protection if required by changing to Yes.
If “Yes” is selected, the following settings will be available:
Underload level (Underl Lev)
Set the level of the underload protection.
Available only if the protection is selected.
Underload time (Underl Time)
Set the time for the underload protection.
Available only if the protection is selected.
Underload type of operation (Underl Op)
Select what operation should be initiated if the underload protection is activated:
Stop–M The motor will stop and a manual reset is required.
Stop–A The motor will stop and an automatic reset is performed.
Ind Only indication will be given.
Press Store to save the selected operation.
Phase imbalance (Phase Imb)
Activate the protection if required by changing to Yes.
If “Yes” is selected, the following settings will be available:
Phase imbalance level (Ph Imb Lev)
Set the level of the phase imbalance protection.
Available only if the protection is selected.
Phase imbalance type of operation (Ph Imb Op)
Select what operation should be initiated if the phase imbalance protection is activated:
Stop–M The motor will stop and a manual reset is required.
Stop–A The motor will stop and an automatic reset is performed.
Ind Only indication will be given.
Press Store to save the selected operation.
High current (High I)
Activate the high current protection if required by changing to Yes.
If “Yes” is selected, the following setting will be available:
High current type of operation (High I Op)
Select what operation should be initiated if the high current protection is activated: 7
Stop–M The motor will stop and a manual reset is required.
Stop–A The motor will stop and automatic reset is performed.
Ind Only indication will be given.
Press Store to save the selected operation.
Phase reversal (Phase Rev)
Activate the phase reversal protection if required by changing to Yes. If “Yes” is selected,
the following setting will be available:
Phase reversal type of operation (Ph Rev Op)
Select what operation should be initiated if the phase reversal protection is activated:
Stop–M The motor will stop and a manual reset is required.
Stop–A The motor will stop and an automatic reset is performed.
Ind Only indication will be given.
Press Store to save the selected operation.
PTC
Activate the PTC protection if required by changing to Yes.
If “Yes” is selected, the following setting will be available:
PTC type of operation (PTC Op)
Select what operation should be initiated if the PTC protection is activated:
Stop–M The motor will stop and a manual reset is required.
Stop–A The motor will stop and an automatic reset is performed.
Ind Only indication will be given.
Press Store to save the selected operation.
Settings
7:2.4.3 Warnings
Functional settings Start / Stop To set parameters related to the warnings, enter the Warnings group:
Protections Warning high current (Warn I=High)
Activate the warning function if required by changing to Yes.
Warnings Press Store to save the selected operation
Faults
Warning high current level (Wa I=H Lev)
Inputs Set the level of the high current warning.
Available only if the function is selected.
Outputs
Press Store to save the selected operation.
Fieldbus
Warning low current (Warn I=Low)
Seq. Start Activate the warning function if required by changing to Yes.
Figure 26: Warnings group Press Store to save the selected operation.
Warning low current level (Wa I=L Lev)
Set the level of the low current warning.
Available only if the function is selected.
Press Store to save the selected operation.
Warning overload (Warn OL)
Activate the warning function if required by changing to Yes.
Press Store to save the selected operation.
Warning overload level (Wa OL Lev)
Set the level of the overload warning.
Available only if the function is selected.
Press Store to save the selected operation.
Settings Warning SCR overload (Warn SCR OL)
Functional settings Start / Stop Activate the warning function if required by changing to Yes.
Press Store to save the selected operation.
Protections
Warnings 7:2.4.4 Faults
Phase loss type of operation (Ph Loss Op)
7
Faults
Select what operation should be initiated if a phase loss fault occurs:
Inputs Stop–M The motor will stop and a manual reset is required.
Outputs Stop–A The motor will stop and an automatic reset is performed.
Press Store to save the selected operation.
Fieldbus
Seq. Start Fieldbus fault type of operation (FB Fault Op)
Figure 27: Faults group Select what operation should be initiated if a fieldbus communication fault occurs:
Stop–M The motor will stop and a manual reset is required.
Stop–A The motor will stop and an automatic reset is performed.
Press Store to save the selected operation.
Fault Connection, Fault Open SCR, Fault Line Side and Fault Intern
Selected operation for the faults listed above is always:
Stop–M The motor will stop and a manual reset is required.
7
Stop–A The motor will stop and an automatic reset is performed.
Press Store to save the selected operation.
7:2.4.5 Inputs
Settings
Functional settings Start / Stop To set parameters related to the programmable inputs, enter the Inputs group.
! Caution!
The motor may start unexpectedly if there is a start signal present when doing any of the
actions listed below:
• Switching from one type of controol to another (fieldbus control/hardwire control)
• Re-programming the programmable inputs.
• Reset all Settings (programmable input set to Enable)
! Caution!
The motor may start unexpectedly if there is a start signal present when doing any of the
actions listed below:
• Switching from one type of controol to another (fieldbus control/hardwire control)
• Re-programming the programmable inputs.
• Reset all Settings (programmable input set to Enable)
7:2.4.6 Outputs
Settings
Functional settings Start / Stop To set parameters related to the programmable outputs, enter the Outputs group.
Relay K4
Protections
Select the required function for output relay K4.
Warnings One of the following functions can be selected:
Faults
Run Run indication.
TOR Top of ramp indication.
Inputs Event Indication of selected event(s) . The following events can be selected individually:
Outputs • Motor overload protection • Shunt fault
• Fault • Low current warning
Fieldbus
• High current protection • High current warning
Seq. Start • SCR overload protection • SCR overload warning
Figure 29: Outputs group • Locked rotor protection • Overload warning
• Underload protection • Phase reversal protection
• Phase imbalance protection • PTC protection
Press Store to save/activate the selected function.
Relay K5
Select the required function for output relay K5.
One of the following functions can be selected:
Run Run indication.
TOR Top of ramp indication.
Event Indication of selected event(s), see relay K4.
Press Store to save/activate the selected function.
Relay K6
Select the required function for output relay K6.
One of the following functions can be selected:
Run Run indication.
TOR Top of ramp indication.
Event Indication of selected event(s), see relay K4.
Press Store to save/activate the selected function.
SW Outp V7
Select the required function for the fieldbus communication output SW Outp V7.
One of the following functions can be selected: 7
Run Run indication.
TOR Top of ramp indication.
Event Indication of selected event(s), see relay K4.
Press Store to save/activate the selected function.
Settings
Fieldbus
Functional settings Start / Stop To set parameters related to the fieldbus communication, enter the Fieldbus group.
Fieldbus control (Fieldb Ctrl)
Protections
Activate the fieldbus control by changing to Yes.
Warnings Press Store to save the selected function.
Faults Fieldbus type (Fieldb Type)
Select what fieldbus type is used.
Inputs AS-Interface Used for AS-I protocol.
Other Used for protocols other than AS-I (i.e., DeviceNet, Profibus DP, Modbus).
Outputs
Press Store to save/activate the selected function.
Fieldbus Fieldbus address (Fieldb Addr)
Seq. Start Set a unique address number between 1 and 1000 for fieldbus communication.
Figure 30: Fieldbus group
Press Store to save the selected function.
! Caution!
The motor may start unexpectedly if there is a start signal present when doing any of the
actions listed below:
• Switching from one type of controol to another (fieldbus control/hardwire control)
• Re-programming the programmable inputs.
• Reset all Settings (programmable input set to Enable)
Faults
Inputs
Information!
Outputs The LOCAL CONTROL menu can not be entered if Sequence start is selected.
Fieldbus Number of sequences (No of Seq)
Seq. Start To set parameters related to a sequence start, enter the Seq Start group.
Select the required number of parameter sets for the application.
Figure 31: Sequence start group
The following selections are available:
No Sequence start is not activated.
The softstarter is in normal operation.
2 Two different parameter sets will be used.
3 Three different parameter sets will be used.
Press Store to save/activate the selected function.
First sequence setting current (1st Set Ie)
Set the current for the first parameter group and press Store to save the value.
This parameter will only be displayed if parameter
No of Seq is set to 2 or 3.
Second sequence setting current (2nd Set Ie)
Set the current for the second parameter group.
Press Store to save the value.
This parameter will only be displayed if parameter
No of Seq is set to 2 or 3.
Information!
If sequence start was used and the parameter No of Seq is changed to No, the overload
7 protection will automatically be set to Normal regardless of previous settings.
Third sequence setting current (3rd Set Ie)
Set the current for the third parameter group.
Press Store to save the value.
This parameter will only be displayed if parameter
No of Seq is set to 3.
Function of first programmable input (In0)
This parameter will automatically be set as Start2.
Function of second programmable input (In1)
This parameter will automatically be set as Start3.
Overload
The overload protection is not activated when sequence start is selected.
To activate the motor overload protection, enter this group and change to the required
function.
Information!
The overload protection should not be used when starting several motors since the total
starting time will become too long and the protection will trip.Normally the overload should
be turned off and each motor should have separate overload protection.
Information!
For wiring and operation of the start/stop signals, see Chapter 5, “Connection” under
programmable inputs.
Information!
In case the wrong language is selected, follow the “emergency instructions” below to
reach this parameter. (Start from the top level.)
Press left selection key twice.
Press lower navgation key three times.
Press left selection key twice.
Use the navigation keys to find the required language abbeviation.
Press left selection key to save the parameter.
LCD Auto Off
The LCD will be switched off automatically by a pre-set time between 1 - 255 minutes. If
the display has switched off, touch any of the keys to turn it on again.
Date Type
7 The date can be presented in three different ways. Depending on the selected type, the
following will be displayed at the top level:
Date type Display on the LCD
ISO Year - Month - Day
US Month - Day - Year
CE Day - Month - Year
Date Year
To set the year in the real time clock, press Change to enter the setting level. Press Store
to save the set value.
Date Month
To set the month in the real time clock, press Change to enter the setting level. Press
Store to save the set value.
Date Day
To set the day in the real time clock, press Change to enter the setting level. Press Store
to save the set value.
Time Hour
To set the hours in the real time clock, press Change to enter the setting level. Press
Store to save the set value.
Time Min
To set the minutes in the real time clock, press Change to enter the setting level. Press
Store to save the set value.
The configuration of the presentation setting menu is now completed. It is possible to
return to the top level by pressing Back 3 times.
Functional settings
Presentation settings
Service settings
! Warning!
If parameters are changed, the softstarter can be damaged or malfunction. The
All settings warranty will be void if these parameters are changed without factory authoriza-
tion.
Changed settings
Operation mode
Figure 33: Service Settings menu
(for authorized personnel only)
Service settings
All settings
Changed settings
Operation mode
Figure 34: All Settings menu 7
Top level 7:2.7.1 Changed Settings
Settings Application setting The Changed settings menu consists of the parameters that have been changed in
contrast to the factory default setting. If no parameters have been changed, the LCD will
Basic settings display No Changed Settings.
Functional settings
Presentation settings
Service settings
All settings
Changed settings
Operation mode
Figure 35: Changed Settings menu
All settings
Changed settings
! Caution!
The motor may start unexpectedly if there is a start signal present when doing any
Reset all settings
of the actions listed below.
Operation mode • Switching from one type of control to another (fieldbus control / hardwire control)
Figure 36: Reset all Settings menu • Re-programming the programmable inputs
• Reset all Settings (programmable input set to Enable)
!
Service settings
All settings
Caution!
Changed settings Never enter the demo mode with the main voltage connected. The by-pass contactor will
close at TOR and may start the motor.
Reset all settings
7
Operation mode
Figure 37: Reset all Settings menu
Information!
Operation Mode The total run time of the motor and the total number of starts will be counted also
Select Back during demo mode. When exiting demo mode, these values will be reset to previous
Figure 38: Display appearance in normal mode values. Parameters changed and the Event Log will be kept when exiting demo mode.
Operation Mode
Select Back
Figure 39: Display appearance in demo mode
Changed settings
All settings
Changed settings
Overview................................................................................................................. 8.2
Required accessories........................................................................................ 8.2
Instructions......................................................................................................... 8.2
8:1 Overview
The PST softstarter has an interface on the front for connecting the ABB fieldbus plug is
used for fieldbus communication. Through this interface, it is possible to control the soft-
starter, achieve status information, as well as upload and down-load parameters.
The interface between the softstarter and the eplug is always the same. Independent of
softstarter size, it is possible to connect any fieldbus protocol in the future since the protocol
is defined in the eplug itself.
The following fieldbus protocols are available:
• AS-Interface
• DeviceNet
• Profibus DP
• Modbus
8:1.2 Instructions
Made in Sweden Made in Sweden
To set up I/O, parameters, etc., please visit www.abb-control.com, go to the Literature
Key-Pad PTC Fieldbus Key-Pad PTC Fieldbus
Library, select “3. Technical Manual Download Library” and scroll down the page to
locate the Softstarter technical literature library. Engineering document packages can be
downloaded for all available protocols.
This chapter describes the maintenance required for the softstarter. In principle, the product is
maintenance free but some items should be checked regularly.
Caution!
Do not open the softstarter or touch any live parts when the main and control voltage
is connected.
Information!
Service and repair should be performed by authorized personnel only. Unauthorized repair may affect
warranty.
Setting Current....................................................................................................10.3
Start Ramp..........................................................................................................10.3
Stop Ramp..........................................................................................................10.3
Initial voltage.......................................................................................................10.4
End voltage.........................................................................................................10.4
Step down voltage...............................................................................................10.4
Current limit.........................................................................................................10.4
Kick Start.............................................................................................................10.5
Kick Start Level...................................................................................................10.5
Kick Start Time....................................................................................................10.5
Start ramp range.................................................................................................10.5
Stop ramp range..................................................................................................10.5
Motor overload protection....................................................................................10.6
Overload class.....................................................................................................10.6
Overload class, dual type, start class..................................................................10.6
Overload class, dual type, run class....................................................................10.6
Overload protection, type of operation................................................................10.7
Locked rotor protection........................................................................................10.7
Locked rotor protection, trip level........................................................................10.7
Locked rotor protection time................................................................................10.7
Locked rotor protection, type of operation...........................................................10.7
Underload protection...........................................................................................10.8
Underload protection level...................................................................................10.8
Underload protection time...................................................................................10.8
Underload protection, type of operation..............................................................10.8
Phase imbalance protection................................................................................10.8
Phase imbalance protection level........................................................................10.9
Phase imbalance protection, type of operation...................................................10.9
10
High current protection........................................................................................10.9
High current protection, type of operation...........................................................10.9
Phase reversal protection....................................................................................10.9
Phase reversal protection, type of operation.....................................................10.10
PTC protection..................................................................................................10.10
PTC protection, type of operation......................................................................10.10
External By-Pass...............................................................................................10.10
High current warning.........................................................................................10.10
High current warning level................................................................................. 10.11
Low current warning.......................................................................................... 10.11
Low current warning level.................................................................................. 10.11
Overload warning.............................................................................................. 10.11
Overload warning level...................................................................................... 10.11
SCR overload warning...................................................................................... 10.11
Low Voltage Products & Systems 10.1
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 132 021 M0201
Phase loss fault, type of operation....................................................................10.12
Fieldbus fault, type of operation........................................................................10.12
Frequency fault, type of operation.....................................................................10.12
Heatsink over-temperature fault, type of operation...........................................10.12
SCR short circuit fault, type of operation...........................................................10.13
Programmable inputs In0 and In1.....................................................................10.13
Programmable outputs, Relay K4, K5 and K6...................................................10.14
Programmable software output V7....................................................................10.14
Fieldbus control.................................................................................................10.15
Fieldbus type.....................................................................................................10.15
Fieldbus address...............................................................................................10.15
Sequence start, number of sequences..............................................................10.15
Start ramp, first sequence.................................................................................10.16
Initial voltage, first sequence.............................................................................10.16
Current limit, first sequence...............................................................................10.16
Setting current, first sequence...........................................................................10.16
Start ramp, second sequence...........................................................................10.16
Initial voltage, second sequence.......................................................................10.16
Current limit, second sequence.........................................................................10.17
Setting current, second sequence.....................................................................10.17
Start ramp, third sequence................................................................................10.17
Initial voltage, third sequence............................................................................10.17
Current limit, third sequence.............................................................................10.17
Setting current, third sequence.........................................................................10.17
Language..........................................................................................................10.18
LCD displaly automatic switch-off......................................................................10.18
Password...........................................................................................................10.18
Date type...........................................................................................................10.18
Year...................................................................................................................10.18
Month................................................................................................................10.19
Day....................................................................................................................10.19
Hour...................................................................................................................10.19
Minutes..............................................................................................................10.19
By-Pass doesn’t open, type of operation (BP Closed Op).................................10.19
By-Pass doesn’t close, type of operation (BP Open Op)...................................10.19
10
This chapter describes all possible settings and functions in the softstarter, as well as the
easiest way of finding them. The respective default values, setting ranges and parameter
texts shown in the display are also described.
Information!
If the motor is connected Inside Delta, set the current in the Delta circuit by multiplying the
rated motor current by 1/( 3) = 58% (or .58).
10
Information!
This parameter shall be set to 0 for applications when large masses are involved!
U
Example 50% 10:6 Step down voltage
100%
Path in menu:
Menu/SETTINGS/Functional Settings/
End
voltage Start/Stop / Step Down
30% 30%
When stopping a motor using the stop ramp, the speed will not decrease immediately. The
Stop
step down voltage function makes it possible to set a level where the motor speed decreas-
Time es as soon as the stop ramp begins. By using, a more optimized stopping of the motor is
Figure 5: Step down voltage for Stop ramp
achieved. It is mainly used for pump applications.
Parameter text Default value Setting range Description
Voltage value to which
the softstarter will
Step down 100% 30...100% step down at stop and
where it will begin the
stop ramp
10
U
100%
Fixed 10:7 Current limit
voltage Path in menu:
Current limit Menu/SETTINGS/Functional Settings/
setting reached Start/Stop / Current Lim
30%
It is possible to limit the starting current by using this function. When the current limit is
reached, the output voltage stays stable until the current level falls below the limit, then the
t1 t2 Time ramping continues.
t1 + t2 = set ramp time
I
5
Information!
Current limit The starting current must be high enough to make it possible for the motor to reach the rated speed. The
setting lowest possible current depends on the performance of the motor and the characteristics of the load.
2 Parameter text Default value Setting range Description
Level of the current
Current Lim 4.0 x le 2.0...7xle
Figure 6: Current limit limit
Time
Information!
The motor thermal temperature is stored in the event of a power loss.
Information!
This protection could be used to avoid for example a pump running dry or detecting a
broken belt.
! Caution!
The motor may start unexpectedly if there is a start signal present when doing any of the
actions listed below.
• Switching from one type of control to another (fieldbus control / hardwire control)
• Re-programming the programmable inputs
• Reset all Settings (programmable input set to Enable)
Figure 9: Internal control voltage
10
Description
Fault group consists of:
• By-pass contactor does not close
• Phase loss fault
• Fieldbus fault
• Frequency fault
• Heat sink temp. fault
Shunt fault group consists of:
• By-pass contactor does not open
• Shorted thyristor
This signal can be used to trip an upstream breaker in case the softstarter is not able to
stop the motor.
! Caution!
The motor may start unexpectedly if there is a start signal present when doing any of the
actions listed below.
• Switching from one type of control to another (fieldbus control / hardwire control)
• Re-programming the programmable inputs
• Reset all Settings (programmable input set to Enable)
Information!
The LOCAL CONTROL menu cannot be entered if Sequence start is selected.
Start Ramp3 10s 1...30s, 1...120s Third sequence, time for start ramp
10:67 Language
Path in menu:
Menu/SETTINGS/Presentation Set./Language
The text on the LCD display can be presented in 12 different languages. This parameter
makes it possible to select among the following languages:
• English • Turkish
• Chinese • Russian
• German • Finnish
• Spanish • Swedish
• French • Portuguese
• Italian • Dutch
Parameter text Default value Setting range Description
US/UK, CN, DE, ES,
Language to use on
Language By country FR, IT, NL, PT, SE, FI,
display
RU, TR
10:69 Password
Path in menu: Top level
Press Upper navigation key once.
This parameter makes it possible to set a password to lock the keypad. All menus are avail-
able when the keypad is locked but no changes or actions can be done.
Parameter text Default value Setting range Description
10:71 Year
Path in menu:
Menu/SETTINGS/Presentation Set./Date Year
This parameter makes it possible to set the current year for the real time clock.
Parameter text Default value Setting range Description
10:72 Month
Path in menu:
Menu/SETTINGS/Presentation Set./Date Month
This parameter makes it possible to set the current month for the real time clock.
Parameter text Default value Setting range Description
Date Month Individual 1...12 Month
10:73 Day
Path in menu:
Menu/SETTINGS/Presentation Set.Date Day
This parameter makes it possible to set the current day for the real time clock.
Parameter text Default value Setting range Description
Date Day Individual 1...31 Day
10:74 Hour
Path in menu:
Menu/SETTINGS/Presentation Set./Time Hour
This parameter makes it possible to set the current hour for the real time clock.
10:75 Minutes
Path in menu:
Menu/SETTINGS/Presentation Set./Time Min
This parameter makes it possible to set the current minutes for the real time clock.
10
General.....................................................................................................11.2
Overview of indications.............................................................................11.2
General problems and faults . ..................................................................11.2
Start up faults............................................................................................11.3
Fault indication................................................................................11.3 - 11.4
Protection indication........................................................................11.5 - 11.6
11
11:1 General
This chapter is a guide that can be used in case problems arise with the softstarter or the application.
The softstarter normally indicates a fault with LED Fault, and the LCD displays what type of fault it is. When a protection is activated, it will be indicated with LED Protection
and the LCD displays what type of protection is active.
Faults not displayed in the softstarter can also be found in this chapter.
Fault FB Timeout
Fault Connection
Fault BP Closed
Prot Locked Rot
Fault HS Temp
Fault BP Open
Warn SCR OL
Fault Kick-Cur
Prot Motor OL
Fault SC SCR
Prot SCR OL
Warn I=High
Warn I=Low
Prot High I
Prot PTC
Warn OL
Stand by X – – X – – X X – – – – X – – X1 – – X X – –
At start signal X – – X – X X X X X X X X X2 X – X1 – – X X – –
Ramp up X – – X – – X X X – – – X – X X1 – – X X – –
TOR X X X X X – X X X – – – X – X X1 – X3 X X X X
At stop signal X – – X – – X X X – – – X X4 X X1 X3 – X X – –
Ramp down X – – X – – X X X – – – X X X X 1
– – X X – –
1) Only if Fieldbus control is selected
2) Only if Kick-start is selected.
3) Only if by-pass is used.
4) Only if by-pass is not used.
11
LCD Auto shut off the keypad Touch any key onn the keypad
Power on Fault Protection The main contactor or circuit breaker is open Check and close contactor / breaker or any external
switching device
Fault Phase Loss Fuse blown Check and replace the fuse in all (3) three phases
Reset Back Any external device open / tripped Check upstream disconnect or fuses. Check all power
cable connections..
Main contactor opens too quickly
Add a time delay before opening
Power on Fault Protection The motor connection is not correct In Line connected
• Check that there are no connections missing to the
motor
Fault Connection • Check that the connections are carried out correctly
Shorted SCR at start • Check and replace
Reset Back Inside Delta connected
• Check that there are no connections missing to the
motor
• Check that the circuits are closed and correspond to
the circuit diagram
Shorted SCR at start • Check and replace
Frequency fault The frequency is out of range. (47.5 - 52.5Hz or Check and correct the frequency
Power on Fault Protection 57-63 Hz)
Reset Back
Shorted SCR fault One or several SCRs are shorted Check and replace. Contact your ABB sales office for
Power on Fault Protection replacement parts.
Fault SC SCR
Reset Back
Non conducting SCR fault One or several SCRs are not conducting Check and replace. Contact your ABB sales office for
Power on Fault Protection replacement parts.
Fault Intern 2
Reset Back
Power on Fault Protection
Fault Intern 3
Reset Back
Power on Fault Protection
11 Fault Intern 4
Reset Back
Underload protection The motor current is below set level and time Check and correct the reason for the underload
Power on Fault Protection Check that the settings are according to the operation
conditions
Prot Underload
Reset Back
Locked rotor protection The motor is running stiff for some reason. Check the bearings of the motor and load
Power on Fault Protection A damaged bearing or a stuck load could be possible Check that the load is not running stiff.
causes
Prot High I
Reset Back
Phase imbalance protection Unbalance in the phase currents Check the main voltage and the motor circuit
Power on Fault Protection Restart the motor and check the phase currents
Prot PTC
Reset Back
SCR overload protection The softstarter is too small Check and replace the softstarters with one of a
Power on Fault Protection Too many starts/hour suitable size
The ramp time for start is too long Check and decrease number of starts/hour
Check that current limit level is not set too low
Prot SCR OL Check that the ramp time for start is not too long
Reset Back
11
12
12
Terminal 3 is a functional ground, it is not a protective ground. It shall be connected to the
mounting plate.
(IGH VOLTAGE
12
(IGH VOLTAGE
12
Figure 4: Circuit diagram PSTB370...PSTB1050
12
April, 2005
ABB Inc.
1206 Hatton Road
Wichita Falls, TX 76302
Telephone 888-385-1221; 940-397-7000
Fax 940-397-7085
http://www.abb-control.com
6.
TRANSMITTERS
Technical Information
Nivotester FTC325
Point level switch
With intrinsically safe signal circuit for connection
to a capacitance sensor
TI00380F/00/EN/13.13
71214509
Nivotester FTC325
Table of contents
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Overvoltage category as per EN 61010 . . . . . . . . . . . . . . . . . . . . . 8
Protection class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Ambient temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Climatic and mechanical application class . . . . . . . . . . . . . . . . . 10
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . 10
Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 10
Design, dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Operability. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Ordering information. . . . . . . . . . . . . . . . . . . . . . . . . 14
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Protective housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2 Endress+Hauser
Nivotester FTC325
PFM 3–WIRE
The electronic insert FEI57 converts the change of The electronic insert FEI53 converts the change of
capacitance into a change of frequency, which switches the capacitance into a voltage signal, which switches the
output relay in the Nivotester FTC325 PFM. output relay in the Nivotester FTC325 3-WIRE.
Signal transmission
The signal input of the Nivotester FTC325 point level switch is galvanically isolated from the power supply and
from the output.
PFM 3–WIRE
The Nivotester supplies the capacitance sensor with The Nivotester supplies the capacitance sensor with direct
intrinsically safe direct current via a two-wire cable and from current via a two-wire cable and receives the voltage signal
there receives a frequency, which signals whether the point via a third wire, which signals whether the point level has
level has been reached or not. been reached or not.
Here, the transmitter superimposes current impulses (PFM The measuring capacitance lies in the range from
signals) with a pulse width of approx. 200 μs and a current 10 pF to 350 pF.
intensity of approx. 10 mA on the supply current. The This corresponds to a voltage of 3V to 12V.
measuring capacitance lies in the range from 20 pF to 350 pF.
This corresponds to a transmission frequency of
185 Hz to 116 Hz.
Signal evaluation
The Nivotester analyses the frequency or the voltage signal, and switches the output relay for the level alarm.
The switching state of the relay (energized or de-energized) is displayed on the front panel of the Nivotester by
means of two yellow light emitting diodes.
Fail-safe circuit
The choice of fail-safe circuit affects how the relay works in quiescent current fail-safe mode.
• MAX = Maximum fail-safe mode: the relay de-energizes when the level rises above the switch point (probe
covered), a fault occurs or the power fails. For use with overfill protection, for instance.
• MIN = Minimum fail-safe mode: the relay de-energizes when the level falls below the switch point (probe
uncovered), a fault occurs or the power fails. For use with dry running protection or pump protection, for
instance.
PFM
NC NO NC NO
MAX
22 23 24 15 16 15 16 22 23 24 15 16 15 16
CH1 CH1
NC NO NC NO
MIN 22 23 24 15 16 15 16 22 23 24 15 16 15 16
CH1 CH1
L00–FTC325xx–15–06–xx–en–001
Function of the point level indicator dependent on the level and fail-safe circuit.
Endress+Hauser 3
Nivotester FTC325
3–WIRE
MAX
4 5 6 17 15 16 4 5 6 17 15 16
CH1 CH1
MIN
4 5 6 17 15 16 4 5 6 17 15 16
CH1 CH1
L00-FTC325xx-15-06-xx-en-002
Function of the point level indicator dependent on the level and fail-safe circuit.
Function monitoring
To increase operational safety the Nivotester is equipped with a function monitoring facility. A fault is displayed
by the red light emitting diode and de-energizes the relay for the level alarm and the alarm relay. A fault is
reported if the Nivotester is no longer receiving a measuring signal. This occurs, for example, when:
• there is a short-circuit
• the signal line to the sensor is interrupted
• the sensor electronics are defective
• the Nivotester's input switching is defective
After calibration, every further change to the device configuration de-energizes the relay.
A fault message is signaled via the red LED.
Measuring device A simple measuring system consists of a capacitance sensor, a Nivotester FTC325 and the control or signal
instruments. The following sensors can be used in conjunction with the electronic inserts (FEIx) listed.
4 Endress+Hauser
Nivotester FTC325
Probe construction
The measuring system consists of: The measuring system consists of:
• Sensor • Sensor
– capacitance probe – one or two capacitance probes
– electronic insert – electronic insert
– FEI57S – FEI53
• Nivotester FTC325 PFM • Nivotester FTC325 3-WIRE
• Control or signal instruments • Control or signal instruments
FTC325 T
CH1
L00–FTC325xx–14–06–xx–xx–001
Endress+Hauser 5
Nivotester FTC325
3-WIRE
FTC325
CH1
L00-FTC325xx-14-06-xx-xx-002
MAX
Δs 3-WIRE
FTC325
MIN
CH1
L00-FTC325xx-14-06-xx-xx-004
1 2
12 3 4 5 6
1 EC61
FEI53 /
EC61
Coaxial cable
3-WIRE
FTC325
Ds
CH1
L00-FTC325xx-14-06-xx-en-001
Two-point control with two fully or partially insulated probes and an electronic insert FEI53.
The probes are connected by a coaxial cable.
6 Endress+Hauser
Nivotester FTC325
Input
Measured variable The limit signal is generated at a MIN or MAX level, depending on the selection
Measuring range The measuring range is dependent on the mounting location of the probes.
FTC325 3-WIRE
• FTC325 3-WIRE input: galvanically isolated from power supply and output
• Type of protection: version for non-hazardous areas
• Connectable sensors:
Liquicap M (FTI51, FTI52) with FEI53S
Solicap M (FTI55, FTI56) with FEI53S
Solicap S (FTI77) with FEI53S
• Sensor's power supply: from Nivotester FTC325 3-WIRE
• Connecting cable: three-wire, shielding not required, except for strong electromagnetic interferences (see
also Electromagnetic Compatibility (EMC) ä 10)
• Cable resistance: max. 25 per wire
• Signal transmission: voltage change is transmitted via a separate wire
Endress+Hauser 7
Nivotester FTC325
Output
Output signal FTC325 PFM and FTC325 3-WIRE
• Relay output: a potential-free change-over contact for the level alarm
• Quiescent current fail-safe circuit: MIN/MAX fail-safe mode can be selected using the DIL switch
• Alarm relay: potential-free changeover contact for fault indication; with the PFM version, only two contacts
are available (quote NC (normally closed) or NO (normally open) when ordering a PFM device)
• Switching delay: 0 to 45 s
Relay switches when covering or uncovering the probe, depending on the setting
• Switching capacity of relay contacts:
U~ maximum 253 V
I~ maximum 2 A
P~ maximum 500 VA at cos 0.7
U- maximum 40 V
I- maximum 2 A
P- maximum 80 W
Signal on alarm Limit relay de-energized; fault indication via red LED, alarm relay de-energized
Galvanic All input and output channels and relay contacts are provided with secure galvanic isolation from each other.
isolation In the case of simultaneous connection of the power supply circuit or the alarm relay contacts to the functional
extra-low voltage, the secure galvanic isolation is guaranteed up to a voltage of 150 V AC.
Power supply
Electrical connection Terminal blocks
The removable terminal blocks are isolated after intrinsically safe connections (top of device) and non-
intrinsically safe connections (bottom of device). Furthermore, the terminal blocks are also color-coded. Blue
is for the intrinsically safe area and gray for the non-intrinsically safe area. These distinctions allow for safe cable
routing.
Sensor connection
(To the upper, blue/gray terminal blocks).
Use a usual commercial instrument cable or multi-core cable for measuring purposes for the connecting cable
between the Nivotester FTC325 and the sensor. Cable resistance of maximum 25 per wire.
If strong electromagnetic interferences have to be expected, e.g. from machines or radios, a shielded cable must
be used. Only connect the shielding to the grounding connection in the sensor, not to the Nivotester.
8 Endress+Hauser
Nivotester FTC325
DC version
maximum 2.0 W (at Umin 20 V)
Installation
Installation instructions Installation location
The Nivotester must be housed outside of hazardous areas in a cabinet. A protective housing ( ä 14
"Accessories") is also available for installation outdoors.
! Note!
The devices should be installed in locations which are protected from direct solar radiation, weather and
impacts. This is of particular importance in hot climates.
Orientation
EX EX
EN 60715
EX
TH35-7,5/15
mm (in)
L00-FTW325xx-06-06-xx-xx-000
Endress+Hauser 9
Nivotester FTC325
Environment
Ambient temperatures • For single mounting: –20 to +60 °C (–4 to +140 °F)
• For series mounting without lateral spacing: –20 to +50 °C (–4 to +122 °F)
• Storage temperature: –25 to +85 °C (–77 to +185 °F)
• Installation of a maximum of three Nivotester devices in the protective housing: –20 to +40 °C (–4 to +104
°F)
Mechanical construction
Design, Dimensions: 3-WIRE PFM
dimensions
x2 x1
108 (4,25)
95 (3,74)
x2 x1
L00-FTxxxxxx-06-06-xx-xx-004
! Note!
mm (in)
10 Endress+Hauser
Nivotester FTC325
Connection cross-section
maximum 1 x 2.5 mm (0.1 in) or 2 x 1.5 mm (0.06 in)
PFM T
3-WIRE
FTC325 FTW 325
FTC325
2 2
* *
1 2 1 2
* * * *
– + – + S
11 12 22 23 24 11 12 13 4 5 6 17
1 2 15 16 15 16 1 2 15 16
L00–FTC325xx–04–06–xx–en–001
Endress+Hauser 11
Nivotester FTC325
Operability
Operating concept Onsite configuration with switches behind the folding front panel
A
N
O
1 2
E
B
N
O1 2 3 4 5 6 7 8
A
E
N
O
1 2 3 4 5 6 7 8
B D D
- +
11 12
C
2 1
2 3s
1 6s
3
12 s
4
T 24 s
5
6 t S
MIN 7 Offset
MAX
8
L+ L-
L1 N 22 23 24
CH1
1 2 15 16
L00–FTC325xx–03–06–06–xx–001
12 Endress+Hauser
Nivotester FTC325
N
O
1 2 3
E
N
O
1
B E
N
O
A
1 2 3 4 5 6 7 8
N
O
1 2 3 4 5 6 7 8
7 8
3362
B
C
3362
X1 X2
– + s
11 12 13
1 2 3 4
3s
2 6s
1 12s
24s
ts
5 6 7 8
T
MIN MAX
Off s
s cal_ s
Offset
4 5 6 17
L+ L-
L1 N
1 2 15 16
L00-FTC325xx-03-06-06-xx-002
Ex approval Endress+Hauser Sales Centers provide information about the currently available versions for use in hazardous
areas (ATEX Ex ia IIC; FM IS; CSA IS).
All the relevant data for explosion protection is contained in separate Ex documentation ä 14
"Supplementary Documentation", which can be requested.
! Note!
Suitable for powering devices with an IP54 housing in explosive dust atmospheres.
Endress+Hauser 13
Nivotester FTC325
Other standards and Other standards and guidelines which were observed during the conceptual design and development of the
guidelines Nivotester FTC325.
• EN 60529: Degrees of protection provided by enclosures (IP code)
• EN 61010: Safety requirements for electrical equipment for measurement, control and laboratory use
• EN 61326: Interference emission (Equipment Class B), interference immunity (Annex A - Industrial)
Ordering information
Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser website: www.endress.com Select country
Instruments Select device Product page function: Configure this product
• From your Endress+Hauser Sales Center: www.endress.com/worldwide
Accessories
Protective housing The protective housing in protection class IP66 is equipped with an integrated DIN rail and closed by a
transparent cover, which can also be lead-sealed.
Dimensions:
W/H/D: 180/182/165 (mm); 7,09/7,17/6,5 (in)
Technical data:
• Degree of protection (EN 60529): IP66
• Lower housing section: fiber-glass reinforced polycarbonate, grey
• Upper housing section: polycarbonate, transparent
• Cover screws: polyamide, 4 pieces, 2 of which can be lead-sealed
• Seal: PU seal
• Top-hat rail (EN 50022): galvanized
• Cable entries: 5 pieces M 20x1.5
• Part number: 52010132
Supplementary Documentation
System Information (SI) • Capacitance level measurement
SI00001F/00
14 Endress+Hauser
Nivotester FTC325
Protective housing
• Protective housing
TI00367F/00
WHG (DIBt):
• Nivotester FTC325
ZE00211F/00
Endress+Hauser 15
Instruments International
Endress+Hauser
Instruments International AG
Kaegenstrasse 2
4153 Reinach
Switzerland
Tel.+41 61 715 81 00
Fax+41 61 715 25 00
www.endress.com
info@ii.endress.com
TI00380F/00/EN/13.13
71214509
FM 9.0
71214509
https://www.phoenixcontact.com/in/products/2891002
Ethernet switch, 8 TP RJ45 ports, automatic detection of data transmission speed of 10/100 Mbps (RJ45),
autocrossing function
Product Features
■ Auto negotiation and autocrossing detection simplifies installation and setup
GTIN
Technical data
Note
EMC: class A product, see manufacturer's declaration in the download
Utilization restriction
area
Dimensions
Width 50 mm
Height 110 mm
Depth 70 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -10 °C ... 60 °C
Ambient temperature (storage/transport) -20 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
Air pressure (operation) 86 kPa ... 108 kPa (up to 1500 m above mean sea level)
05/23/2016 Page 1 / 4
https://www.phoenixcontact.com/in/products/2891002
Function
Unmanaged switch / auto negotiation, complies with IEEE 802.3, store
Basic functions
and forward switching mode
Status and diagnostic indicators LEDs: US, link and activity per port
Supply voltage
Supply voltage 24 V DC
Residual ripple 3.6 VPP (within the permitted voltage range)
Supply voltage range 9 V DC ... 32 V DC
Typical current consumption 140 mA (at US = 24 V DC)
Max. current consumption 380 mA (@9 V DC)
General
Mounting type DIN rail
Type AX Block design
Net weight 385 g
Housing material Aluminum
Classifications
eCl@ss
ETIM
UNSPSC
Approvals
Approvals
Approvals
Ex Approvals
UL Listed / cUL Listed / UL Listed / cUL Listed / UL Listed / cUL Listed / cULus Listed
Approvals submitted
Approval details
UL Listed
cUL Listed
EAC
EAC
05/23/2016 Page 3 / 4
https://www.phoenixcontact.com/in/products/2891002
KC
cULus Listed
05/23/2016 Page 4 / 4
https://www.phoenixcontact.com/us/products/2891314
Ethernet switch, 6 TP RJ45 ports, 2 FO ports, 100 Mbps full duplex in SC-D format, automatic detection of data
transmission speed of 10 or 100 Mbps (RJ45), autocrossing function
Product Features
■ Auto negotiation and autocrossing detection simplifies installation and setup
■ RJ45 ports support a transmission speed of 10/100 Mbps; fiber optic ports support 100 Mbps
Technical data
Note
EMC: class A product, see manufacturer's declaration in the download
Utilization restriction
area
Dimensions
Width 50 mm
Height 120 mm
Depth 70 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) 0 °C ... 60 °C
Ambient temperature (storage/transport) -20 °C ... 70 °C
05/26/2016 Page 1 / 5
https://www.phoenixcontact.com/us/products/2891314
Interfaces
Interface 1 Ethernet (RJ45)
No. of ports 6 (RJ45 ports)
Connection method RJ45
Note on connection method Auto negotiation and autocrossing
Transmission physics Ethernet in RJ45 twisted pair
Transmission speed 10/100 MBit/s
Interface 2 Fiber optic interface
No. of ports 2 (SC multi-mode)
Connection method SC
Transmission physics multi-mode fiberglass
Transmission speed 100 MBit/s (full duplex)
Transmission length 2000 m (Fiberglass 50/125)
2000 m (Fiberglass 62.5/125)
Wavelength 1300 nm
Function
Unmanaged switch / auto negotiation, complies with IEEE 802.3, store and
Basic functions
forward switching mode
Status and diagnostic indicators LEDs: US, link and activity per port
Supply voltage
Supply voltage 24 V DC
Residual ripple 3.6 VPP (within the permitted voltage range)
Supply voltage range 9 V DC ... 32 V DC
Typical current consumption typ. 230 mA (at US = 24 V DC)
General
Mounting type DIN rail
Type AX Block design
Net weight 365 g
05/26/2016 Page 2 / 5
https://www.phoenixcontact.com/us/products/2891314
Classifications
eCl@ss
05/26/2016 Page 3 / 5
https://www.phoenixcontact.com/us/products/2891314
UNSPSC
Approvals
Approvals
Approvals
Ex Approvals
Approvals submitted
Approval details
UL Listed
cUL Listed
EAC
05/26/2016 Page 4 / 5
https://www.phoenixcontact.com/us/products/2891314
EAC
KC
cULus Listed
05/26/2016 Page 5 / 5
Electronic Weight Sensors
OL3000 A, WT1, WT2
OL3000 A
EZ-LIGHT® TL50HZ High Brightness
Universal AC Voltage Tower Light
Datasheet
Multi-Color General-Purpose or Audible Indicators
Non-Audible Models
Model1 # of LED Colors LED Function2 Connection3 Inputs
TL50HZR 1 Red
For additional models and colors, visit Banner Engineering website at www.bannerengineering.com.
1 Cabled Black models only are listed. For gray housing, add suffix C at the end of the model number (cabled models) or before the QP (pigtail
models), for example, TL50HZRC or TL50HZRCQP.
2 The first color listed is the bottom color, going up in successive order. Contact the factory for other colors and color combinations. Five color
options are only available in non-audible cabled models. Four color options are only available in audible cabled models.
3 Cabled models only are listed; mating cordset required for pigtail models (see Cordsets on page 4). For 150 mm (5.9 in) PVC pigtail with QD,
add QP to the end of the model number, for example, TL50HZRQP.
169422
EZ-LIGHT® TL50HZ High Brightness Universal AC Voltage Tower Light
Audible Models
# of LED
Standard Audible Models4 LED Function5 Connection6 Inputs
Colors
TL50HZRA 1 Red
4-wire PVC cable
TL50HZGRA 2 Green, Red
85-264 V
ac
TL50HZGYRA 3 Green, Yellow, Red 5-wire PVC cable
TL50HZBGYRALS TL50HZBGYRALS3 TL50HZBGYRALS4 4 Blue, Green, Yellow, Red 6-wire PVC cable
TL50HZBGYRAOS TL50HZBGYRAOS3 TL50HZBGYRAOS4 4 Blue, Green, Yellow, Red 6-wire PVC cable
TL50HZBGYRAOSI TL50HZBGYRAOS3I TL50HZBGYRAOS4I 4 Blue, Green, Yellow, Red 6-wire PVC cable
Specifications
Supply Voltage and Current Supply Protection Circuitry
85–264 V ac; 50 or 60 Hz Protected against reverse polarity and transient voltages
Indicators—maximum current per LED color: Input Response Time
80 mA at 85 V ac Indicator On/Off: 500 ms (maximum)
60 mA at 120 V ac Connections
40 mA at 240 V ac 4-wire, 5-wire, or 6-wire 2 m (6.5 ft) integral cable; 4-pin or 5-pin 150
35 mA at 264 V ac mm (6 in) PVC pigtail with QD, depending on model
4 Cabled Black models only are listed. For gray housing, add suffix C at the end of the model number (cabled models) or before the QP (pigtail
models), for example, TL50HZRC or TL50HZRCQP.
5 The first color listed is the bottom color, going up in successive order. Contact the factory for other colors and color combinations. Five color
options are only available in non-audible cabled models. Four color options are only available in audible cabled models.
6 Cabled models only are listed; mating cordset required for pigtail models (see Cordsets on page 4). For 150 mm (5.9 in) PVC pigtail with QD,
add QP to the end of the model number, for example, TL50HZRQP.
20 5.0
22 3.0
24 2.0
26 1.0
28 0.8
30 0.5
Dimensions
2 170.9 mm (6.7 in) 201.7 mm (7.9 in) 224.8 mm (8.9 in) 238.8 mm (9.4 in)
19
[0.75] 3 211.6 mm (8.3 in) 242.4 mm (9.5 in) 265.5 mm (10.5 in) 279.5 mm (11.0 in)
M30 x 1.5 4 252.3 mm (9.9 in) 283.1 mm (11.1 in) 306.2 mm (12.1 in) 320.2 mm (12.6 in)
Ø50
1/2-14 NPSM [1.97]
* Tower height (H) with top unscrewed approximately 3.5 mm to allow sound to escape
Wiring Diagram
4-wire 5-wire 6-wire
Indicator 3
Color Neutral
Indicator 3 1 85-264V ac
Color Neutral C1 Hot
Indicator 4
Neutral 1 85-264V ac
Color 2
C1 Hot C2
1 85-264V ac
C1 Hot 2 4
C2 C3
2
C2/A 4 5
C3 C4
3
C3/A 5
C4/A 6
C5/A
Accessories
Cordsets
4-Pin Micro-Style Cordsets
1
Straight 2
1/2-20 UNF-28 1 = Brown
MQAC2-430 9.14 m (30 ft)
ø 14.5 2 = Blue
3 = Black
4 = White
Mounting Brackets
SMB30A 45 SMB30FA
• Right-angle bracket with • Swivel bracket with tilt and 83.2
curved slot for versatile C pan movement for precise
orientation 61 adjustment
• Clearance for M6 (¼ in) B • Mounting hole for 30 mm
hardware sensor
A 36.3 B 68.9
• Mounting hole for 30 mm • 12-ga. 304 stainless steel
sensor 69 • Easy sensor mounting to A
• 12-ga. stainless steel extrude rail T-slot
• Metric and inch size bolt
Hole center spacing: A to B=40 available
Hole size: A=ø 6.3, B= 27.1 x 6.3, C=ø 30.5
Bolt thread: SMB30FA, A= 3/8 - 16 x 2 in; SMB30FAM10, A= M10 -
1.5 x 50
Hole size: B= ø 30.1
45
SMB30MM SMBAMS30P
70 57
• 12-ga. stainless steel bracket • Flat SMBAMS series bracket C
with curved mounting slots • 30 mm hole for mounting
for versatile orientation C sensors A
57 93
• Clearance for M6 (¼ in) • Articulation slots for 90°+
B B
hardware rotation
• Mounting hole for 30 mm • 12-ga. 300 series stainless
A
sensor steel
Hole center spacing: A = 51, A to B = 25.4 Hole center spacing: A=26.0, A to B=13.0
Hole size: A = 42.6 x 7, B = ø 6.4, C = ø 30.1 Hole size: A=26.8 x 7.0, B=ø 6.5, C=ø 31.0
67
SMBAMS30RA SMB30SC
45
• Right-angle SMBAMS series • Swivel bracket with 30 mm B
bracket C mounting hole for sensor
• 30 mm hole for mounting 53 • Black reinforced 58
A
sensors thermoplastic polyester
B
• Articulation slots for 90°+ • Stainless steel mounting and
rotation swivel locking hardware
48 29
• 12-ga. (2.6 mm) cold-rolled included A
steel
Hole center spacing: A=ø 50.8
Hole center spacing: A=26.0, A to B=13.0 Hole size: A=ø 7.0, B=ø 30.0
Hole size: A=26.8 x 7.0, B=ø 6.5, C=ø 31.0
LMBE12RA Pipe-Mount Models: Bracket kit with base, ½-14 Black polycarbonate
pipe adapter, set screw, fasteners, o-rings, and
gaskets. For use with stand-off pipe (listed and
LMBE12RAC Gray polycarbonate
sold separately)
1/2-14 54
• For use elevated stand-off pipes (½ NPSM
4x ø5.5
in, NPSM/DN15) Die-cast zinc base with
SA-F12 ø28
• M5 mounting hardware and nitrile black paint
gasket included 10 ø70
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION,
ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE
OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE
LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL,
CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER
ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product
previously manufactured by Banner Engineering Corp.
IS1A45G015P58
Characteristics:
The combined gyro-inclination sensor is suitable to measure the rotational speed and inclination of one axis.
The full-scale readings are calibrated factory made at 25 °C.
The extremely robust plastic housing makes the sensor a suitable angle measurement device in rough
surroundings for different applications.
Applications:
General Parameters: Ta = 25 °C
Measurement axes 1 axis
Measurement range gyro / inclination ± 15 °/s ± 45°
Resolution (at zero point) gyro / 0.015 °/s 0.05°
inclination
Nonlinearity gyro / inclination (sine) max. ± 0.035 °/s ± 0.3°
Temperature coefficient (zero point) max. 0.005 °/s/K 0.025°
gyro / inclination
Cross sensitivity max. 5 %
Critical frequency gyro / inclination typically 7 Hz / 7 Hz (other values on request)
Operating temperature - 40 °C ... 80 °C
Characteristics
Interface Current loop 4...20 mA ; max. burden-resistor at U=11 V : 250 Ohm
Calculation formula
Gyro value [°/s] / Angle value [°] Imeas−12mA
8 mA ∗range value arcsin
[
Imeas −12 mA
8 mA
∗sin rangevalue
]
Electrical Parameters
Supply voltage 11 V DC ... 30 V DC
Current consumption max. 120 mA
Mechanical Parameters
Connector 5-pole M12 sensor connector, IEC 61076-2-101, IEC 60947-2
Mounting 4 x hexagon socket screws M5 DIN 912; Strongly recommended: use 4x spring washers
DIN 6796 when mounting this sensor!
Degree of Protection IP65/67 min locking torque of the sensor connector: 0.9 Nm
Shock survival max. 3 500 g
Dimensions 66 mm x 90 mm x 36 mm
Weight about 200 g
Standards
ISO13766 (earthmoving machines Test pulse 5 min Level 1
EMC)
ISO 10605:2001 Severity level IV: direct discharge ± 8 kV ; air discharge ± 15 kV
VDE 0879-2:1999, CISPR25 radio Measured with absorber room method
interference suppression Narrow band peak value: @ 0.15 MHz...1 GHz max 19 dB (µV/m)
Broad band peak value: @ 0.15 MHz...1 GHz max 35 dB (µV/m)
ISO 7637-2: 2004 (24 V System) 27 V Impulses 1-4: severity level 3; Impulse 5: severity level 1
ISO 11452-5: 2005 strip line AM 80 % 1 kHz 60 V/m
IEC 60068-2-6 vibration sinusoidal, 3 5 – 2000 Hz; ± 1, 5 mm (p-p) / 30 ms-2; transit frequency 57 Hz
axis cycle rate 1 Okt./min; test duration 2 hrs each in 3 axis (X, Y, Z)
IEC 60068-2-27 Ea shock transport, 3 50 g, 11 ms, 1/s, 3/axis
axis
DIN-IEC 60068-2-14 Na TW (-40... Transition period 1 min; retention period 1 h; 5 cycles; specimen passive
+80)°C
DIN EN 60068-2-14 Test Nb (-40... Temperature gradient 3 K/min; retention period 1 h; 5 cycles; specimen active
+80)°C
DIN-IEC 60068-2-2Bb (B dry heat) +85 °C
DIN-IEC 60068-2-2 Ab (test group A low -40 °C
temperature)
DIN-IEC 60068-2-32 1x free fall per axis from 1 m height
Pin Allocation
1 Supply voltage (V+)
2 Sensor signal gyro (Gyro-OUT)
3 GND supply (V- / GND)
4 Sensor signal inclination (INCL-OUT)
5 Reference potential for sensor signal
(GND-SENS)
Order information:
FO converter (replacement device A), for full duplex transmission from 10/100Base-T(X) to individual simplex
fiberglass with WDM (wavelength division multiplex) technology, SC simplex fiber optic connection (1310/1550
nm). Device set (type A and type B) required for operation.
Product Features
■ Full duplex communication with only one fiber
■ Transmission ranges up to 38 km
■ Auto negotiation
■ Link fault pass through (LFP) and far end fault (FEF) functions for easy connection monitoring
Technical data
Note
EMC: class A product, see manufacturer's declaration in the download
Utilization restriction
area
Dimensions
Width 22.5 mm
Height 99 mm
Depth 114.5 mm
Ambient conditions
05/26/2016 Page 1 / 7
https://www.phoenixcontact.com/us/products/2902658
General
Electrical isolation according to IEEE 802.3
VCC // FE // Ethernet
± 1.3 µs (Store&Forward mode, 10/100 Mbps, depending on the frame
Latency
size)
Test voltage data interface/power supply 1.5 kVrms (50 Hz, 1 min.)
Standards/regulations EN 60950-1
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Net weight 120 g
Housing material PA 6.6-FR
Color green
492 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5
MTBF
days a week, 8 hours a day))
133 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle
(5 days a week, 12 hours a day))
1400 Years (SN 29500 standard, temperature 25°C, operating cycle 21 %
MTTF
(5 days a week, 8 hours a day))
599 Years (SN 29500 standard, temperature 40 °C, operating cycle 34.25
% (5 days a week, 12 hours a day))
101 Years (SN 29500 standard, temperature 40°C, operating cycle 100 %
(7 days a week, 24 hours a day))
Conformance CE-compliant
II 3 G Ex nA IIC T4 Gc X (Please follow the special installation
ATEX
instructions in the documentation!)
UL, USA / Canada cULus listed UL 508
Class I, Zone 2, AEx nA IIC T4
Class I, Zone 2, Ex nA IIC T4 Gc X
Class I, Div. 2, Groups A, B, C, D
Power supply
Supply voltage range 18 V DC ... 30 V DC (Screw connection)
18 V DC ... 30 V DC (as an alternative or redundant, via backplane bus
contact and system current supply)
05/26/2016 Page 2 / 7
https://www.phoenixcontact.com/us/products/2902658
Serial interface
Interface 1 Ethernet interface, 10/100BASE-T(X) in acc. with IEEE 802.3u
Connection method RJ45 socket, shielded
Transmission medium Copper
Transmission length 100 m (twisted pair, shielded)
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Auto-negotiation modes Auto
Link through Link fault pass through
Basic functions Store-and-forward media converter
MDI-/MDI-X switchover Auto-MDI(X)
Signal LEDs Activity, link status, 10/100 Mbps
Optical interface FO
Transmit capacity, minimum ≥ -14 dBm ((9/125 µm) dynamic in link mode (average))
Transmit capacity, maximum ≤ -8 dBm ((9/125 µm) dynamic in link mode (average))
Minimum receiver sensitivity -31 dBm (dynamic in link mode (average))
Overrange receiver -3 dBm (dynamic in link mode (average))
Wavelength 1310 nm
1550 nm
Transmission length incl. 3 dB system reserve 38 km (With F-E 9/125 0.36 dB/km)
34 km (With F-E 9/125 0.4 dB/km)
05/26/2016 Page 3 / 7
https://www.phoenixcontact.com/us/products/2902658
Classifications
eCl@ss
ETIM
UNSPSC
Approvals
Approvals
Approvals
Ex Approvals
Approvals submitted
Approval details
UL Listed
05/26/2016 Page 5 / 7
https://www.phoenixcontact.com/us/products/2902658
cUL Listed
DNV
cULus Listed
Drawings
1 2 3 4
114,5 22,5
11 VCC
VCC 10 FEF
LINK
FEF
LINK 9
5
99
8 2
6
FL MC EF WDM-A SC
Ord.-No.: 29 02 658 7 FL MC EF WDM-A SC
Ord.-No.: 29 02 658
Front view
10 1 2
D
N
G
2
S
U
D
N
G
1
S
U
ON 6
1 1
D
N
G
2
S
U
D
N
G
1
S
U
C
VC
F
FE
K
LIN
C
VC
F
FE
K
LIN
3 11
MC o.
FL rd.-N
O
00
MM4
13 0285
EF 29
ST
9
8 00
MM4
85
13 02
ST
4
7
EF 29
MC o.
FL rd.-N
O
Function elements
05/26/2016 Page 6 / 7
https://www.phoenixcontact.com/us/products/2902658
FL MC EF 1300
GN - VCC Device ON
RD - FEF Far End Fault
YE - LINK Link FO Activity FO
GN - RJ45 Full Duplex
GN/YE - RJ45 100/10 MBit/s Activity CU
DIP switches
Block diagram
05/26/2016 Page 7 / 7
https://www.phoenixcontact.com/us/products/2902659
FO converter (replacement device B), for full duplex transmission from 10/100Base-T(X) to individual simplex
fiberglass with WDM (wavelength division multiplex) technology, SC simplex fiber optic connection (1550/1310
nm). Device set (type A and type B) required for operation.
Product Features
■ Full duplex communication with only one fiber
■ Transmission ranges up to 38 km
■ Auto negotiation
■ Link fault pass through (LFP) and far end fault (FEF) functions for easy connection monitoring
Technical data
Note
EMC: class A product, see manufacturer's declaration in the download
Utilization restriction
area
Dimensions
Width 22.5 mm
Height 99 mm
Depth 114.5 mm
Ambient conditions
Ambient temperature (operation) -40 °C ... 65 °C
05/26/2016 Page 1 / 7
https://www.phoenixcontact.com/us/products/2902659
General
Electrical isolation according to IEEE 802.3
VCC // FE // Ethernet
± 1.3 µs (Store&Forward mode, 10/100 Mbps, depending on the frame
Latency
size)
Test voltage data interface/power supply 1.5 kVrms (50 Hz, 1 min.)
Standards/regulations EN 60950-1
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Net weight 120 g
Housing material PA 6.6-FR
Color green
492 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5
MTBF
days a week, 8 hours a day))
133 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle
(5 days a week, 12 hours a day))
Conformance CE-compliant
II 3 G Ex nA IIC T4 Gc X (Please follow the special installation
ATEX
instructions in the documentation!)
UL, USA / Canada cULus listed UL 508
Class I, Zone 2, AEx nA IIC T4
Class I, Zone 2, Ex nA IIC T4 Gc X
Class I, Div. 2, Groups A, B, C, D
Power supply
Supply voltage range 18 V DC ... 30 V DC (Screw connection)
18 V DC ... 30 V DC (as an alternative or redundant, via backplane bus
contact and system current supply)
Typical current consumption < 110 mA (24 V DC)
Protective circuit Reverse polarity protection
Connection method Plug-in screw terminal block (COMBICON), redundancy possible
Conductor cross section flexible max. 2.50 mm²
Conductor cross section flexible min. 0.20 mm²
Conductor cross section solid max. 2.50 mm²
05/26/2016 Page 2 / 7
https://www.phoenixcontact.com/us/products/2902659
Serial interface
Interface 1 Ethernet interface, 10/100BASE-T(X) in acc. with IEEE 802.3u
Connection method RJ45 socket, shielded
Transmission medium Copper
Transmission length 100 m (twisted pair, shielded)
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Auto-negotiation modes Auto
Link through Link fault pass through
Basic functions Store-and-forward media converter
MDI-/MDI-X switchover Auto-MDI(X)
Signal LEDs Activity, link status, 10/100 Mbps
Optical interface FO
Transmit capacity, minimum ≥ ((9/125 µm) dynamic in link mode (average))
Transmit capacity, maximum ≤ -8 dBm ((9/125 µm) dynamic in link mode (average))
Minimum receiver sensitivity min. -31 dBm (dynamic in link mode (average))
Overrange receiver -3 dBm (dynamic in link mode (average))
Wavelength 1550 nm
1310 nm
Transmission length incl. 3 dB system reserve 38 km (With F-E 9/125 0.36 dB/km)
34 km (With F-E 9/125 0.4 dB/km)
28 km (With F-E 9/125 0.5 dB/km)
21 km (with F-G 62,5/125 0,7 dB/km F 1000)
5.5 km (with F-G 62.5/125 2.6 dB/km F 600)
21 km (with F-G 50/125 0,7 dB/km F 1200)
9 km (with F-G 50/125 1,6 dB/km F 800)
Transmission medium Multi-mode fiberglass
05/26/2016 Page 3 / 7
https://www.phoenixcontact.com/us/products/2902659
Classifications
eCl@ss
UNSPSC
Approvals
Approvals
Approvals
Ex Approvals
Approvals submitted
Approval details
UL Listed
cUL Listed
DNV
05/26/2016 Page 5 / 7
https://www.phoenixcontact.com/us/products/2902659
cULus Listed
Drawings
1 2 3 4
114,5 22,5
11 VCC
VCC 10 FEF
LINK
FEF
LINK 9
5
99
8 2
6
FL MC EF WDM-A SC
Ord.-No.: 29 02 658 7 FL MC EF WDM-A SC
Ord.-No.: 29 02 658
Front view
10 1 2
D
N
G
2
S
U
D
N
G
1
S
U
ON 6
1 1
D
N
G
2
S
U
D
N
G
1
S
U
C
VC
F
FE
K
LIN
C
VC
F
FE
K
LIN
3 11
MC o.
FL rd.-N
O
00
MM4
85
13 02
EF 29
ST
9
8 00
MM4
13 0285
ST
4
7
EF 29
MC o.
FL rd.-N
O
Function elements
05/26/2016 Page 6 / 7
https://www.phoenixcontact.com/us/products/2902659
FL MC EF 1300
GN - VCC Device ON
RD - FEF Far End Fault
YE - LINK Link FO Activity FO
GN - RJ45 Full Duplex
GN/YE - RJ45 100/10 MBit/s Activity CU
DIP switches
Block diagram
05/26/2016 Page 7 / 7
DATASHEET
Industrial splice distributor with metal housing for DIN-RAIL, unassembled Art.-No. 53705.1V3
Specifications
• Rugged metal housing
• DIN Rail holder with screw set included
• Incl. splice cassette, splice holder and 1 x cable gland M20
• Dimensions (W x H x D): 61 x 115 x 113 mm
Page 1
EFB Elektronik GmbH | Striegauer Str. 1 | 33719 Bielefeld | www.efb-elektronik.de
fon +49(0)521/40418-0 | fax +49(0)521/40418-50 | info@efb-elektronik.de
DATASHEET
Industrial splice distributor with metal housing for DIN-RAIL, unassembled Art.-No. 53705.1V3
Drawings/ Figures
Page 2
EFB Elektronik GmbH | Striegauer Str. 1 | 33719 Bielefeld | www.efb-elektronik.de
fon +49(0)521/40418-0 | fax +49(0)521/40418-50 | info@efb-elektronik.de
DATASHEET
Industrial splice distributor with metal housing for DIN-RAIL, unassembled Art.-No. 53705.1V3
Drawings/ Figures
Order Data
Art.-No. Type
53705.1V3 Industrial splice distributor with metal housing for DIN-RAIL, unassembled
Art.-No. Accessories
53705.2V2 Front panel for 6 x SC duplex or LC quad
53705.3V2 Front panel for 6 x LC duplex or SC simplex
53705.4V2 Front panel for 12 x SC simplex
Page 3
EFB Elektronik GmbH | Striegauer Str. 1 | 33719 Bielefeld | www.efb-elektronik.de
fon +49(0)521/40418-0 | fax +49(0)521/40418-50 | info@efb-elektronik.de
Technical Information
Application
Solicap M is used for point level detection in bulk solids
and can be operated in minimum or maximum fail-safe
mode.
Due to its robust construction, it can also be used to
provide accurate measurements in applications with very
high tensile loads (up to 60 kN for rope version) or lateral
loads (up to 300 Nm for rod version).
In combination with Fieldgate (for remote interrogation
of measured values using internet technology),
Solicap M represents an ideal solution for material
provisioning and logistical optimization (inventory
control).
Your benefits
• Extremely robust design for harsh process conditions
• Easy and fast commissioning as calibration is
performed at the press of a button
• Universal application thanks to wide range of
certificates and approvals
• Two-stage overvoltage protection against static
discharges from the silo
• Active buildup compensation for bulk solids that tend
to cake
• Use in safety systems with specific requirements
in terms of functional safety to SIL2/SIL3 in
conjunction with electronic insert FEI55
• Increased safety due to permanent automatic
monitoring of electronics
• Reduction in storage costs thanks to easy-to-shorten
rod model (for partial insulation) and rope model (for
partial and full insulation)
• Two-point control (e.g. for controlling a handling
device)
TI418F/00/en
71110976
Solicap M FTI55, FTI56
Table of contents
2 Endress+Hauser
Solicap M FTI55, FTI56
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . 44
Solicap M FTI55 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Solicap M FTI56 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Weather protection cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Overvoltage protection HAW56x . . . . . . . . . . . . . . . . . . . . . . . . 48
Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Patents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3 Endress+Hauser
Solicap M FTI55, FTI56
The point level switch switches when the capacitance CS specified during calibration is reached.
In addition, a probe with inactive length ensures that the effects of medium buildup or condensate near the
process connection are avoided. A probe with active buildup compensation compensates for the effects of
buildup on the probe in the area of the process connection.
1. 2. 3.
CS
CA C
ΔC
R CA
TI418F01
Function
The electronic insert selected for the probe determines the change in capacitance depending on how much of
the probe is covered. This ensures accurate switching at the switchpoint (level) calibrated for this purpose.
Application examples Sand, glass aggregate, gravel, molding sand, lime, ore (crushed), plaster, aluminum shavings, cement, grain,
pumice, flour, dolomite, sugar beet, kaolin, fodder and similar bulk solids.
In general:
Bulk solids with a relative dielectric constant εr ≥ 2.5.
4 Endress+Hauser
Solicap M FTI55, FTI56
Measuring system The make-up of the measuring system depends on the electronic insert selected.
TI418Fen02
! Note!
Partially insulated probes only in conjunction with nonconductive bulk solids.
ON
Conveyor screw
Ds
OFF
TI418Fen03
Endress+Hauser 5
Solicap M FTI55, FTI56
The point level switch can also be used to control a screw conveyor, for example, where the on and off values
can be freely defined.
EX EX
EX FEI53 (no Ex)
FEI57S (Ex i) Ex i
FEI58 (Ex i)
T
FTC625
Ds*
U~
CH1
U–
~
L00-FTI5xxxx-14-00-06-xx-003
The following table shows the transmitter power supply units available which can be operated with electronic
inserts FEI57S and FEI53.
Electronic insert FEI57S FEI53 FEI58
Transmitter power supply unit
FTC625 x – –
FTC325 x x –
FTL325N – – x
FTL375N – – x
FTC470Z x – –
FTC471Z x – –
FTC520Z* x – –
FTC521Z* x – –
FTC420* – x –
FTC421* – x –
FTC422* – x –
x Combination is possible
– Combination is not possible
* Product phase-out 2006
6 Endress+Hauser
Solicap M FTI55, FTI56
FEI55 EX EX
Ex i PLC
Transmitter
power supply
unit e.g. ENDRESS + HAUSER
RMA422
RMA422 or
RN221N On
Q-SET
– + E
TI418Fen67
Endress+Hauser 7
Solicap M FTI55, FTI56
! Note!
For additional information see → ä 31 ff.
FEI57S (PFM)
EX Analog
Ethernet
GSM
Nivotester Fieldgate
FTC625 FXA520
RS485
T
interface
FTC625
U~
–
U~
CH1
TI418Fen06
8 Endress+Hauser
Solicap M FTI55, FTI56
min. 500
a silo, a minimum distance of min. 500 min. 500
Endress+Hauser 9
Solicap M FTI55, FTI56
short
a. d.
b. e.
c.
f.
TI418Fen08
Correct installation
a. For maximum point level detection, a short threaded coupling is used.
b. For minimum point level detection, a short threaded coupling is used.
c. In the event of light buildup on the silo wall, the threaded coupling is welded internally.
The probe tip points slightly downwards so that bulk solids slide off more easily.
Incorrect installation
d. The threaded coupling is too long. This may cause material to settle inside and result in error
switching.
e. Horizontal mounting means a risk of error switching in the event of heavy buildup on the silo
wall.
In this case, the Solicap M FTI55 (rod probe) with inactive length is recommended.
f. In areas where product buildup occurs, the device cannot detect if the silo is "empty".
In this case, the FTI56 (rope probe) should be installed from above.
10 Endress+Hauser
Solicap M FTI55, FTI56
min. ø300
or 300
Heat insulation
TI418Fen09
! Note!
• When selecting the probe length, pay attention to the dependency between the relative dielectric constant
εr and the minimum amount the probe rod needs to be covered (see Table).
• For probe length tolerances see → ä 26.
• To ensure problem-free operation, it is important that the difference in capacitance between the covered and
uncovered parts of the probe is at least 5 pF.
• If you do not know the dielectric constant of the material, contact us for advice.
Product properties,
relative dielectric constant εr
*
TI418F12
* Minimum coverage
Electrically conductive 25 mm
Nonconductive
εr > 10 100 mm
εr > 5 to 10 200 mm
εr > 2 to 5 500 mm
Endress+Hauser 11
Solicap M FTI55, FTI56
D
min. 0.2 m
TI418F13
Correct installation
a. Solicap M FTI55, FTI56 with inactive length in the event of condensation and material
buildup on the silo roof.
b. At the correct distance from the silo wall, the material inlet and the material outlet.
Close to the wall, for reliable switching in the case of a low dielectric constant (not for
pneumatic filling).
For pneumatic filling, the distance from the probe to the wall should not be too short, as the
probe may swing.
Incorrect installation
c. If too close to the material inlet, inflowing bulk solids may damage the sensor.
If close to the center of the material outflow, high tensile forces at this point may cause the
probe to break off or subject the silo roof to excessive strain.
d. The threaded coupling is too long. This may cause condensation and dust to settle inside which
may result in error switching.
e. If too close to the silo wall, the probe may swing slightly against the wall or come in contact
with buildup. This can result in error switching.
12 Endress+Hauser
Solicap M FTI55, FTI56
Silo roof
Ensure that the silo roof is of a sufficiently stable construction.
High tensile forces may occur when material is being extracted, particularly in the case of heavy and powdery
bulk solids which have a tendency to form buildup.
Or:
To reduce the effects of condensation (B) and buildup, the threaded coupling (length: max. 25 mm) must
project into the silo.
Heat insulation reduces condensation and therefore buildup on the steel plate.
A B
Steel plate;
connected to the
reinforcing steel
Silo with walls that conduct electricity Silo with concrete walls
Endress+Hauser 13
Solicap M FTI55, FTI56
BA300Fxx020
Ground connection
Electrical
HF field
Weight Surface area
e.g. 1 m²
Counter electrode
Distance e.g.
e.g. 1 m sheet metal plate
TI418Fen16
14 Endress+Hauser
Solicap M FTI55, FTI56
LB min. 250 *
LB min. 200
Level
TI418Fen17
Electrically conductive Bulk solids with high Bulk solids with low
bulk solids dielectric constant dielectric constant
(e.g. coal) (e.g. rock salt) (e.g. dried grain)
* LB (covered length):
For nonconductive bulk solids with a low dielectric constant, the rope probe must be approx. 5 % (but no
less than 250 mm) longer than the distance between the tank roof and the required point level.
Endress+Hauser 15
Solicap M FTI55, FTI56
! Note!
• For information on how to order, see also "Ordering information" from → ä 44 under "Probe
design".
• The maximum connection length between the probe and the separate housing is 6 m (L4).
When ordering a Solicap M with a separate housing, the desired length must be specified.
• If the connecting cable is to be shortened or passed through a wall, it must be separated from the
process connection. See also → ä 16 (extension heights).
• The cable has a bending radius of r ≥ 100 mm. This must be observed as a minimum.
EX
Zone 1
EX
Zone 0
L1
L4 ≤ 6 m
TI418F18
Extension heights
Housing side: wall mounting Housing side: pipe mounting Sensor side
r ³ 100
~61 B ~75 B
H4
D
H1
H1
H2
~41
~41
r ³ 100
TI418F19
Polyester housing F16 Stainless steel housing F15 Aluminum housing F17
B - 76 64 65
H1 - 172 166 177
D 50 - - -
H4 62 - - -
16 Endress+Hauser
Solicap M FTI55, FTI56
! Note!
• Connecting cable: ø10.5 mm
• Outer jacket: silicone, notch-resistant
! Note!
• The wall holder unit is part of the scope of supply.
• The wall holder unit has to be screwed to the separate housing before you can use it as a drilling template.
The distance between the holes is reduced by screwing it to the separate housing.
86
6.2
28
3 70
TI418F20
Ta
°C +170/
+120
120
+180/
+110
* 100
Ta
80
60
TP
40
20
TP
0
–80 –60 –40 –20 0 20 40 60 80 100 120 140 160 180 200 °C
–20
–40
–60
BA300Fxx021
! Note!
The maximum connection length between the probe and the separate housing is 6 m (L4). When ordering a
device with a separate housing, the desired length must be specified.
If the connecting cable is to be shortened or passed through a wall, it must be separated from the process
connection. See "Documentation" => "Operating Instructions" on → ä 49.
Endress+Hauser 17
Solicap M FTI55, FTI56
Vibration resistance DIN EN 60068-2-64/IEC 68-2-64: 20 Hz– 2000 Hz; 0.01 g2/Hz
Cleaning Housing:
When cleaning, make sure that the cleaning agent used does not corrode the housing surface or the seals.
Probe:
Depending on the application, buildup (contamination and soiling) can form on the probe rod. A high degree
of material buildup can affect the measurement result. If the medium tends to create a high degree of buildup,
regular cleaning is recommended. When cleaning, it is important to make sure that the insulation of the probe
rod is not damaged. If cleaning agents are used make sure the material is resistant to them!
18 Endress+Hauser
Solicap M FTI55, FTI56
! Note!
• The following process temperature ranges only apply for standard applications outside hazardous areas.
• Regulations for use in hazardous areas are provided in the Supplementary Documentation XA389F/00.
Permitted ambient temperature Ta at the housing depending on the process temperature Tp in the tank.
Ta
°C
80
Ta
60
40 TP
20
TP
0
–60 –40 –20 0 20 40 60 80 100 120 140 160 180 200 °C
–20
–40
–60
TI418F60
Ta
°C
80
Ta
60
40 TP
20
TP
0
–60 –40 –20 0 20 40 60 80 100 °C
–20
–40
–60
TI418F61
! Note!
Restriction to Ta –40 °C for polyester housing F16.
Endress+Hauser 19
Solicap M FTI55, FTI56
Ta
°C
80
Ta
60
40 TP
20
TP
0
–60 –40 –20 0 20 40 60 80 100 120 140 160 180 200 °C
–20
–40
–60
TI418F62
Ta
°C
80
Ta
60
40 TP
20
TP
0
–60 –40 –20 0 20 40 60 80 100 120 140 °C
–20
–40
–60
TI418F63
20 Endress+Hauser
Solicap M FTI55, FTI56
! Note!
• The lowest value from the derating curves of the device and the selected flange applies.
• In the case of flange process connections, the maximum pressure is limited by the nominal pressure of the
flange.
• See also "Process connections" on → ä 25.
Pp
bar
40
20
TP
0
–60 –40 –20 0 20 40 60 80 100 120 140 160 180 200 °C
TI418F64
Pp
bar
40
20
TP
0
–60 –40 –20 0 20 40 60 80 100 °C
TI418F65
Pp
bar
40
20
TP
0
–60 –40 –20 0 20 40 60 80 100 120 140 160 180 200 °C
TI418F64
Endress+Hauser 21
Solicap M FTI55, FTI56
Pp
bar
40
20
TP
0
–60 –40 –20 0 20 40 60 80 100 120 140 °C
TI418F66
–1 to 25 bar
(observe dependencies => process connections from → ä 25 and operating conditions: process from
→ ä 19.)
The lowest value from the derating curves of the device and the selected flange applies.
Please refer to the following standards for the pressure values permitted at higher temperatures:
• pR EN 1092-1: 2005 Table, Appendix G2
With regard to its resistance/temperature property, the material 1.4435 is identical to 1.4404
(AISI 316L) which is grouped under 13E0 in EN 1092-1 Tab. 18. The chemical makeup of the
two materials can be identical.
• ASME B 16.5a - 1998 Tab. 2-2.2 F316
• ASME B 16.5a - 1998 Tab. 2.3.8 N10276
• JIS B 2220
22 Endress+Hauser
Polyester housing Stainless steel housing Aluminium housing Aluminium housing Aluminium housing
Overview
F16 F15 F17 F13 T13
with a gas-tight with a separate connection
process seal compartment and gas-tight
Endress+Hauser
process seal
Solicap M FTI55, FTI56
Electronics
!
Note!
seperate housing
All dimensions in mm.
R 1½ NPT 1½ Flange
with build-up
Mechanical construction
with inactive length compensation with inactive length with inactive length
partially fully partially fully partially partially fully partially fully partially fully partially fully
insulated insulated insulated insulated insulated insulated insulated insulated insulated insulated insulated insulated insulated
ø18 ø25 ø18/25 ø18/25 ø18 ø6 ø8 ø6 ø8 ø12 ø14 ø12 ø14
tensioning weight
TI418Fen24
23
Solicap M FTI55, FTI56
Housing
ø85 max. 76
Polyester housing F16
~ 97
TI418F25
ø76 max. 64
Stainless steel housing F15
~ 95
TI418F26
max. 65
Aluminum housing F17
ø80 max. 60
~ 105
TI418F27
max. 65
Aluminum housing F13
with gas-tight process seal ø80 max. 60
118
~118
TI418F28
max. 65 max. 97
Aluminum housing T13
with separate connection
compartment and gas-tight
process seal
~ 135
TI418F29
24 Endress+Hauser
Solicap M FTI55, FTI56
Polyester housing Stainless steel Aluminum housing Aluminum housing Aluminum housing
F16 housing F15 F17 F13* with separate
connection
compartment T13*
H1
H1
H1
H1
H1
Order code 2 1 3 4 5
FTI55, FTI56
Endress+Hauser 25
Solicap M FTI55, FTI56
! Note!
Total length of the probe from the start of the thread: L = L1 + L3
(+ 125 mm with active buildup compensation)
Rod probe Rod probe fully insulated Rod probe with Rod probe with active
partially insulated inactive length buildup compensation
partially/fully insulated partially insulated
AF AF AF AF
H2
H2
H2
H2
H2
NPT / R
H3
H3
H3
H3
L2
125
L3
L1/L2/L3
L2
L1
L1
L2
L1
L1
TI418Fen39
H2 77 77 66 92
H3 25 25 25 25
Total length (L) 200 to 4000 200 to 4000 300 to 6000 225 to 4000
Active rod length (L1) 200 to 4000 200 to 4000 200 to 4000 200 to 4000
ø Inactive length - - 43 -
X = recommended
26 Endress+Hauser
Solicap M FTI55, FTI56
! Note!
Total length of probe from start of thread: L = L1 + L3
Rod probe Rod probe Rope probe with Rope probe with inactive
Partially insulated rope Fully insulated rope inactive length length
Partially insulated rope Fully insulated rope
AF AF AF AF
H2
H2
H2
H2
H2
NPT / R
H3
H3
H3
H3
L2
L1/L2/L3
L3
L3
L1
L1
L2
L1
L1
lg
lg
lg
lg
TI418F38
TI418Fen40
H2 66 66 66 66
H3 25 25 25 25
Across flats (AF) 50 50 50 50
Total length (L) 500 to 20000 500 to 20000 700 to 20000 700 to 20000
Active rope length (L1) 500 to 20000 500 to 20000 500 to 19800 500 to 19800
ø Inactive length - - 43 43
ø Tensioning weight** 30 40 30 40 30 40 30 40
Length of tensioning weight (lg) 150 250 150 250 150 250 150 250
Tensile loading capacity (kN) of probe 30 60 30 60 30 60 30 60
rope at 20 °C
X = recommended
* The length of the partial insulation extends, at maximum, to the tensioning weight.
** The tensioning weight is always uninsulated.
Endress+Hauser 27
Solicap M FTI55, FTI56
Material Housing
• Aluminum housing F17, F13, T13: GD–Al Si 10 Mg, DIN 1725, with plastic coating (blue/gray)
• Polyester housing F16: PBT–FR fiberglass reinforced polyester (blue/gray)
• Stainless steel housing F15: corrosion-resistant steel 316L (14404), uninsulated
Probe material
• Process connection, tensioning weight for rope probe: 1.4404 (316L) or steel
• Inactive length: 1.4404 (316L)
• Probe rope partially insulated: PTFE, 1.4401 (AISI 316)
• Probe rope fully insulated: PA, galvanized steel
• Probe rod partially insulated: PPS, 1.4404 (316L)
• Probe rod fully insulated: PE, galvanized steel
28 Endress+Hauser
Solicap M FTI55, FTI56
Input
Measured variable Measurement of the change in capacitance between the probe rod and the tank wall, depending on the level
of the bulk solids.
Measuring conditions
! Note!
• When installing in a nozzle,
use inactive length (L3).
• To control a screw conveyor (Δs mode),
rod probes and rope probes can be used.
The on-value and off-value are L3 L3
determined by the empty and full
calibration;
– Partially insulated probes are only suitable OFF
for nonconductive bulk solids. OFF
L1 L1
TI418F41
TI418F41
Endress+Hauser 29
Solicap M FTI55, FTI56
Output
Galvanic isolation FEI51, FEI52
between rod probe and power supply
FEI54:
between rod probe, power supply and load
FEI53, FEI55, FEI57S, FEI58
see connected switching device (functional galvanic isolation in the electronic insert)
Switch-on behavior When the power supply is switched on, the switching status of the outputs corresponds to the signal on alarm.
The correct switch condition is reached after max. 3 seconds.
Fail-safe mode Minimum/maximum quiescent current safety can be switched at the electronic insert (for FEI53 and FEI57S
only at Nivotester FTCxxx)
MAX = minimum safety: The output switches safety-oriented when the probe is uncovered
(signal on alarm). For use for dry running protection and pump protection for example
MAX = maximum safety: The output switches safety-oriented when the probe is covered
(signal on alarm). For use with overfill protection for example
30 Endress+Hauser
Solicap M FTI55, FTI56
L+ IL +
1 3
MAX
< 3,8 mA
1 3
L+ IL +
1 3
MIN
< 3,8 mA
1 3
Instrument failure
< 3,8 mA
1 3
BA300Fen017
Output signal Output signal on power failure or in the event of damage to the sensor: < 3.8 mA
Connectable load • For relays with a minimum holding power or rated power > 2.5 VA at 253 V AC (10 mA) or > 0.5 VA at
24 V AC (20 mA)
• Relays with a lower holding power or rated power can be operated by means of an RC module connected in
parallel.
• For relays with a maximum holding power or rated power < 89 VA at 253 V AC or < 8.4 VA at 24 V AC
• Voltage drop across FEI51 max. 12 V
• Residual current with blocked thyristor max. 3.8 mA
• Load switched directly into the power supply circuit via the thyristor.
Endress+Hauser 31
Solicap M FTI55, FTI56
F
0.5A R
–
L+ L–
U…
– 10…55 V (DC)
TI418F42
Output signal
Safety mode Level Output signal LEDs
gn gn rd gn gn ye
L+ + IL = Load current
IL
1 3 (switched through)
MAX IR = Residual current
(blocked)
IR
1 3
L+ IL +
1 3
MIN
IR
1 3
Maintenance
required IL / IR Lit
1 3
Signal on alarm Output signal on power failure or in the event of device failure: IR < 100 μA
Connectable load • Load switched via transistor and separate PNP connection, max. 55 V
• Load current max. 350 mA (cyclical overload and short-circuit protection)
• Residual current < 100 μA (with transistor blocked)
• Capacitance load max. 0.5 μF at 55 V; max. 1.0 μF at 24 V
• Residual voltage < 3 V (for transistor switched through)
32 Endress+Hauser
Solicap M FTI55, FTI56
TI418F45
Output signal
Mode Output signal LEDs
green red
Maintenance
3...12 V
required * Lit
at terminal 3
Connectable load • Floating relay contacts in the connected switching unit Nivotester FTC325 3–WIRE
• For the contact load capacity, refer to the technical data of the switching device.
Endress+Hauser 33
Solicap M FTI55, FTI56
Output:
When connecting an instrument with 1 2 3 4 56 7 8
high inductance, provide a spark arrester
to protect the relay contact.
A fine-wire fuse (depending on the
load connected) protects the relay
contact on short-circuiting. F
0.5A
Both relay contacts switch simultaneously.
NO C NC NO C NC
a u r a u r
L1 N PE
L+ L– (Ground) * *
U~ 19…253 V (AC)
U– 19… 55 V (DC)
TI418F47
Output signal
Safety mode Level Output signal LEDs
gn gn rd gn gn ye
3 4 5 6 7 8
MAX
3 4 5 6 7 8
3 4 5 6 7 8
MIN
Relay energized
3 4 5 6 7 8 Relay de-energized
Maintenance
required Lit
3 4 5 6 7 8 Unlit
TI418Fen48 TI418F49
Signal on alarm Output signal on power failure or in the event of device failure: relay de-energized
34 Endress+Hauser
Solicap M FTI55, FTI56
EEx ia EX
EX
– +
U– 11…36
e.g. PLC
TI418Fen50
Output signal
Safety mode Level Output signal LEDs
gn gn rd gn gn ye
+ ~16 mA
~16 mA = 16 mA ± 5 %
2 1 ~ 8 mA = 8 mA ± 6 %
MAX
+ ~8 mA
2 1
+ ~16 mA
2 1
MIN
+ ~8 mA
2 1
Maintenance +
required * 8/16 mA Lit
2 1
Signal on alarm Output signal on power failure or in the event of device failure: < 3.6 mA
Endress+Hauser 35
Solicap M FTI55, FTI56
0 mA t
TI418F52
Frequency: 17 to 185 Hz
EX
EEx ia
PFM
EX
– + Nivotester
11 12 FTC325
FTC625
d4 d2 FTC470Z
FTC471Z
TI418F53
Signal on alarm
Mode Output signal LEDs
green red
Maintenance
required * 60...185 Hz
1 2 Lit
Connectable load • Floating relay contacts in the connected switching unit Nivotester FTC325, FTC625, FTC470Z, FTC471Z
• For the contact load capacity, refer to the technical data of the switching device.
36 Endress+Hauser
Solicap M FTI55, FTI56
(H-L edge)
Additional function:
EEx ia
Test key on the electronic insert.
Pressing the key interrupts the connection
to the isolating amplifier. EX
! Note! H
In the case of Ex-d operation, the additional function I
can only be used if the housing is not EX
L
exposed to an explosive atmosphere.
L00-FTL5xxxx-04-05-xx-en-002
= Lit 2.2 …
+ 3.5 mA
2 1
= Flashes
Min.
0.6 …
= Unlit + 1.0 mA
2 1
L00-FTL5xxxx-07-05- L00-FTL5xxxx-04-05-xx-xx-007
xx-xx-002
Signal on alarm Output signal in the event of damage to the sensor: < 1.0 mA
Connectable load • See the technical data of the connected isolating amplifier as per IEC 60947-5-6 (NAMUR)
• Connection also to isolating amplifiers which have special safety circuits (I > 3.0 mA)
Endress+Hauser 37
Solicap M FTI55, FTI56
Power supply
Electrical connection Connection compartment
Five housings with the following protection classes are available:
Housing Standard EEx ia EEx d Gas-tight process
seal
Polyester housing F16 X X - -
Stainless steel housing F15 X X - -
Aluminum housing F17 X X - -
Aluminum housing F13 X X X X
Aluminum housing T13 X X X X
(with separate connection compartment)
Connector In the case of the versions with a connector (M12 or 7/8"), the housing does not have to be opened to connect
the signal cable.
3 Signal – Signal –
L00-FMxxxxxx-04-00-00-yy-016
4 Signal + Signal +
PIN assignment for the 7/8" connector (Fieldbus FOUNDATION standard, HART)
1 – 3 nc 1 Signal – Signal –
2 Signal + Signal +
2 + 4
3 External load/ Not assigned
voltage output
L00-FMxxxxxx-04-00-00-yy-017 4 Ground Ground
Cable entry • Cable gland: M20x1.5 (for EEx d only cable entry M20)
Two cable glands included in scope of delivery.
• Cable entry: G ½, NPT ½ , NPT ¾ or M20 thread
38 Endress+Hauser
Solicap M FTI55, FTI56
Performance characteristics
Reference operating • Temperature: +20 °C ±5 °C
conditions
• Pressure: 1013 mbar abs. ±20 mbar
• Humidity: 65 % ±20%
• Medium: water from mains (conductivity ≥ 180 μS/cm)
Endress+Hauser 39
Solicap M FTI55, FTI56
Human interface
Electronic inserts FEI51, FEI52, FEI54, FEI55
1 2 3 4 5 6
A
B C LED
on
7 3
FEI5x - 5 + flashing
- +
offf
of
BA300Fen015
Green LED 1 ( ready for operation), red LED 3 ( error indicated), yellow LED 6 (✲ switching state)
Function switch Function – key + key Light emitting diodes (LED signals)
position
1
7 3 _
5
+
1 (green) 2 (green) 3 (red) 4 (green) 5 (green) 6 (yellow)
Operation Flashes On Flashes On On/off/
1 Operational (MIN-SIL) (warning/ (MAX-SIL) flashes
LED alarm)
Restore factory setting Press both keys for On –> –> –> –> On/off/
approx. 20 s flashes
Empty calibration Press On On/off/
2 (present) flashes
Full calibration Press On On/off/
(present) flashes
Reset: Press both keys for On –> –> –> –> On/off/
Calibration and approx. 10 s flashes
switchpoint adjustment
Dc
Switch point shift Press for < Press for > On Off Off Off Off On/off/
3 (2 pF) (4 pF) (8 pF) (16 pF) (32 pF) flashes
40 Endress+Hauser
Solicap M FTI55, FTI56
A B
1 2
LED
0...1600pF on
FEI5x Standard 0.....500pF
- + flashing
offf
of
BA300Fen016
A B
Endress+Hauser 41
Solicap M FTI55, FTI56
A B
1 2 3
MIN
LED
>2,2mA
FEI58
on
NAMUR
IEC 60947-5-6
MAX
- + flashing
C
off
C DE FG
BA299Fen016
Green LED 1 ( ready for operation), red LED 2 ( error indicated), yellow LED 3 (✲ switching state)
Switchpoint adjustment: 10 pF
E C
Switchpoint adjustment: 2 pF
E C
Switching delay: 5 s
F
Switching delay: 1 s
F
Key Function
A B C
X Display diagnostic code
X Display calibration situation
X X Perform calibration (during operation)
X X Delete calibration points (during startup)
X Test key , (disconnects the transmitter from the switching unit)
42 Endress+Hauser
Solicap M FTI55, FTI56
Endress+Hauser 43
Solicap M FTI55, FTI56
Ordering information
! Note!
In this list, versions which are mutually exclusive are not marked.
40 Insulation:
1 fully insulated PE, max. 80 °C
2 75 mm L2, partially insulated PPS, max. 180 °C
3 3 inch L2, partially insulated PPS, max. 180 °C
9 Special version, to be specified
50 Process connection:
AFJ 2", 150 lbs RF 316/316L
AGJ 3", 150 lbs RF 316/316L
AHJ 4", 150 lbs RF 316/316L
BSJ DN80, PN10/16 A 316L EN1092-1 (DIN2527 B)
BTJ DN100, PN10/16 A 316L EN1092-1 (DIN2527 B)
B3J DN50, PN25/40 A 316L EN1092-1 (DIN2527 B)
KFJ 10K 50, RF 316L JIS B2220
KGJ 10K 80, RF 316L JIS B2220
KHJ 10K 100, RF 316L JIS B2220
RGJ NPT 1½, 316L thread ANSI
RG1 NPT 1½, steel thread ANSI
RVJ R 1½, 316L thread DIN2999
RV1 R 1½, steel thread DIN2999
YY9 Special version, to be specified
60 Electronics; output:
1 FEI51; 2-wire 19 to 253VAC
2 FEI52; 3-wire PNP, 10 to 55VDC
3 FEI53; 3-wire, 3 to 12 V signal
4 FEI54; relay DPDT, 19 to 253VAC, 19 to 55VDC
5 FEI55; 8/16 mA, 11 to 36VDC
44 Endress+Hauser
Solicap M FTI55, FTI56
60 Electronics; output:
7 FEI57S;2–wire PFM
8 FEI58; NAMUR+test key (H-L signal)
W Prepared for FEI5x
Y Special version, to be specified
70 Housing:
1 F15 316L IP66, NEMA4X
2 F16 polyester IP66, NEMA4X
3 F17 aluminum IP66, NEMA4X
4 F13 Alu + gas-tight probe seal IP66, NEMA4X
5 T13 Alu + gas-tight probe seal IP66, NEMA4X
+ separate connection compartment
9 Special version, to be specified
80 Cable entry:
A M20 Threaded joint
B Thread G ½
C Thread NPT ½
D Thread NPT ¾
G Thread M20
E M12 connector
F 7/8" connector
Y Special version, to be specified
90 Probe design:
1 Compact
2 2000 mm L4 cable > separate housing
3 .... mm L4 cable > separate housing
4 80 inch L4 cable > separate housing
5 .... inch L4 cable > separate housing
9 Special version, to be specified
Endress+Hauser 45
Solicap M FTI55, FTI56
40 Insulation:
1 fully insulated PA, max. 120 °C
2 500 mm L2, partially insulated PTFE, max. 180 °C
9 Special version, to be specified
50 Process connection:
AFJ 2", 150 lbs RF 316/316L
AGJ 3", 150 lbs RF 316/316L
AHJ 4", 150 lbs RF 316/316L
BSJ DN80, PN10/16 A 316L EN1092-1 (DIN2527 B)
BTJ DN100, PN10/16 A 316L EN1092-1 (DIN2527 B)
B3J DN50, PN25/40 A 316L EN1092-1 (DIN2527 B)
KFJ 10K 50, RF 316L JIS B2220
KGJ 10K 80, RF 316L JIS B2220
KHJ 10K 100, RF 316L JIS B2220
RGJ NPT 1½ 316L thread ANSI
RG1 NPT 1½, steel thread ANSI
RVJ R 1½, 316L thread DIN2999
RV1 R 1½, steel thread DIN2999
YY9 Special version, to be specified
60 Electronics; output:
1 FEI51; 2-wire 19 to 253VAC
2 FEI52; 3-wire PNP, 10 to 55VDC
3 FEI53; 3-wire, 3 to 12 V signal
4 FEI54; relay DPDT, 19 to 253VAC, 19 to 55VDC
5 FEI55; 8/16 mA, 11 to 36VDC
7 FEI57S;2–wire PFM
8 FEI58; NAMUR+test key (H-L signal)
W Prepared for FEI5x
Y Special version, to be specified
70 Housing:
1 F15 316L IP66, NEMA4X
2 F16 polyester IP66, NEMA4X
46 Endress+Hauser
Solicap M FTI55, FTI56
70 Housing:
3 F17 aluminum IP66, NEMA4X
4 F13 Alu + gas-tight probe seal IP66, NEMA4X
5 T13 Alu + gas-tight probe seal IP66, NEMA4X
+ separate connection compartment
9 Special version, to be specified
80 Cable entry:
A M20 Threaded joint
B Thread G ½
C Thread NPT ½
D Thread NPT ¾
G Thread M20
E M12 connector
F 7/8" connector
Y Special version, to be specified
90 Probe design:
1 Compact
2 2000 mm L4 cable > separate housing
3 .... mm L4 cable > separate housing
4 80 inch L4 cable > separate housing
5 .... inch L4 cable > separate housing
9 Special version, to be specified
Endress+Hauser 47
Solicap M FTI55, FTI56
Accessories
Weather protection cover For F13 and F17 housing
Order number: 71040497
! Note!
These two versions can be screwed directly into the housing (M20x1.5).
Surge arrester for limiting overvoltage in signal lines and components.
ÜS-Ableiter/Arrester
ENDRESS+HAUSER
HAW569
HAW569-A1 Uc 34.8 V
In 10 kA
IL 500 mA
protected
L00-FMI5xxxx-03-05-xx-xx-009
! Note!
• You can order spare parts directly from your E+H service organization by quoting the order number (see
below).
• Before ordering, please note that all ordered spare parts must correspond with the indications on your
nameplate. Otherwise, the indications on the nameplate will no longer correspond with the instrument
version.
Housing cover
Cover Parts number
For aluminum housing F13: gray with sealing ring 52002698
For stainless steel housing F15: with sealing ring 52027000
For stainless steel housing F15: with clasp and sealing ring 52028268
For polyester housing F16, flat: gray with sealing ring 52025606
For aluminum housing F17, flat: with sealing ring 52002699
For aluminum housing T13, flat: gray with sealing ring/electronics compartment 52006903
For aluminum housing T13, flat: gray with sealing ring/connection compartment 52007103
48 Endress+Hauser
Solicap M FTI55, FTI56
Documentation
! Note!
This documentation is available on the product pages at www.endress.com
CRN registration
• CRN 0F1988.75
Other
• AD2000
The wetted material (316L) corresponds to AD2000 – W0/W2
Patents This product is protected by at least one of the patents listed below.
Further patents are under development.
• DE 103 22 279,
WO 2004 102 133,
US 2005 003 9528
• DE 203 13 695,
WO 2005 025 015
Endress+Hauser 49
Solicap M FTI55, FTI56
50 Endress+Hauser
Solicap M FTI55, FTI56
Endress+Hauser 51
Instruments International
Endress+Hauser
Instruments International AG
Kaegenstrasse 2
4153 Reinach
Switzerland
TI418F/00/en/01.10
71110976
FM+SGML 6.0 ProMoDo 71110976
7.
LAMP
Data Sheet LED-510 Series Flood Light
20W, 30W, 50W, 100W, 150W and 200W
IP65 Flood Light in robust design for enlightening of all
types of outdoor areas as; parking lots, walkways,
video surveillance areas and much more.
The robust anodised aluminium housing, secures a
good heat dissipation.
The longest possible lifetime is achieved by the built in
Mean Well drivers, that secures a constant current
through the Bridgelux LED chips.
With an efficiency of 110 lm/W, the LED-510 series
replaces 80-1000W Halite lamps.
General Specifications:
LED Type COB, Bridgelux
Driver type Mean Well
Front glass 5mm clear hardened glass
Colour temperature 5500K
Expected lifetime 50,000 hours (L80)
Input Voltage 85V-265V AC
Power Factor >0.95 (230VAC)
Beam angle 150º
Certificates CE og ROHS
Sensor LED-510, -511 og -512 is available with PIR sensor
LED-TEK A/S · LUNDAGERVEJ 45A · DK-8723 LØSNING · TELEFON +45 7384 1100 · LED-TEK@LED-TEK.DK · WWW.LED-TEK.DK
Data Sheet LED-600 og 610 Series
IP67 Industrial luminaire
The IP67 series is a robust series of waterproof doublet isolated industrial luminaire, with an efficiency
of 100lm/W.
The luminaire is easily mounted with the brackets supplied with the luminaire. Bought directly onto
the ceiling or strapped down in wires.
The cable is mounted through the watertight M16 gland.
The hole series is supplied with a frosted plastic cover and is suitable for use in production halls,
warehouses, animal stables, food production and cold storage, as well as a variety of sports halls, etc.
Furthermore, the series is suitable as built-in lighting in signs.
Specifications:
Voltage: 180-265VAC
Power Factor: >0,9
CRI: (RA) >80
IP class: IP67
LED type: Taiwan Lextar 5630 LED
Expected lifetime: >35.000 timer (L70)
Operation temp.: -24 ºC to +40 ºC
Mounting: Watertight M16 gland
Material: Body: ABS/PC (polycarbonate)
Cover: Plastic (frosted)
Aluminium PCB
Certificates: CE og RoHS
All part numbers are available in 3000 and 5000 Kelvin as well.
LED-TEK A/S · LUNDAGERVEJ 45A · DK-8723 LØSNING · TELEFON +45 7384 1100 · LED-TEK@LED-TEK.DK · WWW.LED-TEK.DK
Data Sheet LED-620 Series IP65 luminaire
Neat and timeless LED luminaire available in several sizes and with several different
options. The fixture is easily mounted with the supplied brackets and can be connected
in series as needed.
All versions are supplied with IP65 waterproof housing.
The luminaires are available with the following options:
Motion sensor - Emergency lighting
Cable backwards - Triac dimming
1-10V dimming *
* Cannot be combined with other options
Specifications:
Voltage: 85-265VAC
Power Factor: >0,9
CRI: (RA) >80 (CRI90 as option)
IP class: IP65
LED type: SMD2835
Light angle: 120º
Expected lifetime: >50.000 timer (L70)
Operations temp.: -20 ºC to +45 ºC
Mounting: Watertight plug
Sensor: The sensor is a combined PIR and Daylight sensor.
Material: Plastic housing and cover in Polycarbonate (frosted)
PCB: Aluminium
Certificates: CE and RoHs
LED-TEK A/S · LUNDAGERVEJ 45A · DK-8723 LØSNING · TELEFON +45 7384 1100 · LED-TEK@LED-TEK.DK · WWW.LED-TEK.DK
8.
ENCODER
IXARC Absolute Rotary Encoder
OCD-DPC1B-1212-B150-H3P
Interface
Interface Profibus DP
Profile DPV0, DPV1 and DPV2 Class 2 (EN50170 +
EN50254)
Diagnostics Memory
Programming Functions Resolution, gearing factor (physical resolution) ,
velocity scaling + filter, preset (zero point),
counting direction, limit switches , node number,
teach-in, diagnosis
Manual Functions Address selector switch 0-99 and terminal
resistor (with connection cap)
Features Round Axis
Transmission Rate ≤12 Mbaud
Interface Cycle Time ≥ 1 ms
Outputs
Output Driver Profibus Data Interface, galvanically isolated via
opto-couplers
Electrical Data
Supply Voltage 10 – 30 VDC (On power supplies comply with EN
50178)
Current Consumption ≤ 230 mA @ 10 V DC, ≤ 100 mA @ 24 V DC
Power Consumption ≤ 2.5 W
Data Sheet
Printed at 26-05-2016 08:05
-1/5-
Start-Up Time <1s
Reverse Polarity Protection Yes
Short Circuit Protection Yes
EMC: Emitted Interference DIN EN 61000-6-4
EMC: Noise Immunity DIN EN 61000-6-2
MTTF 13.5 years @ 40 °C
Sensor
Technology Optical
Resolution Singleturn 12 bit
Resolution Multiturn 12 bit
Multiturn Technology Mechanical Gearing (no Battery)
Accuracy (INL) ±0.0220° (14 – 16 bit), ±0.0439° (≤13 bit)
Code Binary
Environmental Specifications
Protection Class (Shaft) IP65
Protection Class (Housing) IP65
Operating Temperature -40 °C (-40 °F) - +85 °C (+185 °F)
Storage Temperature -40 °C (-40 °F) – +85 °C (+185 °F)
Humidity 98% RH, no condensation
Mechanical Data
Connection Cap Material Aluminum
Housing Material Steel
Housing Coating Cathodic corrosion protection (>720 h salt spay
resistance) + Wet Painted
Flange Type Blind Hollow, ø 58 mm (B)
Flange Material Aluminum
Shaft Type Blind Hollow, Depth = 30 mm
Shaft Diameter ø 15 mm (ø 0.59")
Shaft Material Stainless Steel V2A (1.4305, 303)
Rotor Inertia ≤ 30 gcm² [≤ 0.17 oz-in²]
Friction Torque ≤ 3 Ncm @ 20 °C (4.2 oz-in @ 68 °F)
Max. Permissible Mechanical Speed ≤ 12000 1/min
Shock Resistance ≤ 100 g (half sine 6 ms, EN 60068-2-27)
Permanent Shock Resistance ≤ 10 g (half sine 16 ms, EN 60068-2-29)
Data Sheet
Printed at 26-05-2016 08:05
-2/5-
Vibration Resistance ≤ 10 g (10 Hz – 1000 Hz, EN 60068-2-6)
Length 99 mm (3.90")
Weight 460 g (1.01 lb)
Electrical Connection
Connection Orientation Radial
Connection Type 3 x Cable Gland
Connection Cap Type Removable for easy replacing encoder without
new installation of cable, Rotary switches with
visible node number, No active components,
Terminal resistor switch cut the outgoing bus too,
Big spring clips
Connection Plan
SIGNAL PIN NUMBER
Bus line B (Bus in) B
Bus line A (Bus in) A
GND −
Power Supply +
Bus line B (Bus out) B
Bus line A (Bus out) A
GND −
Power Supply +
Data Sheet
Printed at 26-05-2016 08:05
-3/5-
Connector-View on Encoder
Accessories
Contact
POSITAL
info@posital.com
Data Sheet
Printed at 26-05-2016 08:05
-4/5-
The picture and drawing are for general presentation purposes only. Please refer to the "Download" section for detailed technical drawings.
All dimension in [inch] mm. © FRABA B.V., All rights reserved. We do not assume responsibility for technical inaccuracies or omissions.
Specifications are subject to change without notice.
Data Sheet
Printed at 26-05-2016 08:05
-5/5-
9.
SPARE
10.
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Moulded Case Circuit Breakers » Accessories for
Tmax T
Parts & Services » Robotics » Controllers » IRC5 » IRC5 Single
Ordering
EAN: 8015644517892
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85389099
Dimensions
Product Net Weight: 0.04 kg
Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 110 mm
Package Level 1 Height: 60 mm
Package Level 1 Length: 140 mm
Package Level 1 Gross Weight: 0.06 kg
Package Level 1 EAN: 8015644517892
Environmental
RoHS Status: Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2006-07-
01
Additional Information
Device: T1-T2-T3
Product Main Type: Accessories for Tmax T
Product Name: Accessory for Circuit Breakers
Product Type: ACC
Standards: IEC
Suitable For: T1
T2
T3
T4
T5
T6
Suitable for Product Class: SACE Tmax T
Classifications
E-nummer: 3180985
Object Classification Code: Q
UNSPSC: 39120000
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Moulded Case Circuit Breakers » Accessories for
Tmax XT
Ordering
EAN: 8015644002787
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85389099
Dimensions
Product Net Weight: 0.04 kg
Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 110 mm
Package Level 1 Height: 60 mm
Package Level 1 Length: 140 mm
Package Level 1 Gross Weight: 0.06 kg
Package Level 1 EAN: 8015644002787
Additional Information
Product Main Type: Accessories for Tmax XT
Product Name: Accessory for Circuit Breakers
Product Type: ACC
Standards: IEC 60947-2
Suitable For: XT1
XT2
XT3
XT4
Suitable for Product Class: SACE Tmax XT
Classifications
Object Classification Code: Q
UNSPSC: 39120000
HKF1-11
General Information
Extended Product Type: HKF1-11
Product ID: 1SAM201901R1001
EAN: 4013614320354
Catalog Description: HKF1-11 Auxiliary Contact
Long Description: HKF1-11 Aux.-contact for frontmounting
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85365080
EAN: 4013614320354
Container Information
Package Level 1 Length: 36 mm
Package Level 1 Height: 50 mm
Package Level 1 Gross Weight: 0.195 kg
Package Level 1 EAN: 4013614481413
Package Level 1 Units: 10 piece
Package Level 1 Width: 148 mm
Dimensions
Product Net Height: 12.5 mm
Product Net Depth: 26.5 mm
Product Net Weight: 0.015 kg
Product Net Width: 45 mm
Technical
Rated Operational Current AC-15 (240 V) 4 A
(Ie): (24 V) 6 A
(380 / 400 V) 3 A
(690 V) 1 A
Rated Operational Current DC-13 (125 V) 0.55 A
(Ie): (24 V) 2 A
(250 V) 0.27 A
(440 V) 0 A
(600 V) 0 A
Rated Impulse Withstand Voltage Auxiliary Circuit 6 kV
(Uimp):
Rated Insulation Voltage (Ui): 250 V
Connecting Capacity Auxiliary Flexible with Ferrule 1/2x 0.75 ... 1.5 mm²
Circuit: Flexible with Insulated Ferrule 1/2x 0.75 ... 1.5 mm²
Flexible 1/2x 0.75 ... 1.5 mm²
Rigid 1/2x 1 ... 1.5 mm²
Tightening Torque: Auxiliary Circuit 0.8 ... 1.2 N·m
Wire Stripping Length: Auxiliary Circuit 8 mm
Recommended Screw Driver: M3
Pozidriv 2
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Standards: IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 60947-5-1
UL 60947-1
UL 60947-4-1
Product Name: Auxiliary Contact
Suitable For: MS116
MS132
MO132
Suitable for Product Class: Manual Motor Starter
Rated Operational Voltage: 250 V
Environmental
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Operation -20 ... +55 °C
Storage -50 ... +80 °C
Technical UL/CSA
Connecting Capacity Auxiliary Flexible 1/2x 16-14 AWG
Circuit UL/CSA: Stranded 1/2x 16-14 AWG
Tightening Torque UL/CSA: Auxiliary Circuit 7 in·lb
Contact Rating UL/CSA: B300
R300
Maximum Operating Voltage Main Circuit 250 V AC
UL/CSA:
Classifications
E-nummer: 3112001
ETIM 4: EC002498 - Accessories for low-voltage switch technology
ETIM 5: EC002498 - Accessories for low-voltage switch technology
ETIM 6: EC002498 - Accessories for low-voltage switch technology
eClass: 7.0 27379201
UNSPSC: 39121500
Object Classification Code: Q
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Manual Motor Starters
Products » Low Voltage Products and Systems » Control Products » Manual Motor Starters » Manual Motor Starters
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4013614320286
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 95 mm
Package Level 1 Height: 50 mm
Package Level 1 Gross Weight: 0.24 kg
Package Level 2 Units: 40 piece
Package Level 2 Width: 280 mm
Package Level 2 Length: 395 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 9.986 kg
Package Level 2 EAN: 4013614408656
Package Level 1 Units: 1 piece
Dimensions
Product Net Height: 90 mm
Product Net Depth: 85.6 mm
Product Net Weight: 0.225 kg
Product Net Width: 45 mm
Technical
Rated Ultimate Short-Circuit (230 V AC) 50 kA
Breaking Capacity (Icu): (400 V AC) 50 kA
(440 V AC) 30 kA
(500 V AC) 30 kA
(690 V AC) 30 kA
Rated Instantaneous Short-Circuit 12.5 A
Current Setting (Ii):
Setting Range: 0.63 ... 1 A
Rated Operational Power AC-3 (Pe): (400 V) Three Phase 0.25 kW
Rated Operational Voltage: Main Circuit 690 V AC
Rated Operational Current (Ie): 1A
Rated Operational Current AC-3 (Ie): 1A
Rated Frequency (f): Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage Main Circuit 6 kV
(Uimp):
Rated Insulation Voltage (Ui): 690 V
Power Loss: at Rated Operating Conditions per Pole 0.7 ... 1.7 W
Number of Poles: 3
Conventional Free-air Thermal Main Circuit 1 A
Current (Ith):
Degree of Protection: Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 100000 cycle
Mechanical Durability: 100000 cycle
Connecting Capacity Main Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Tightening Torque: Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length: Main Circuit 9 mm
Recommended Screw Driver: Pozidriv 2
Mounting Position: Position 1 to 6
Actuator Type: Rotary Handle
Contact Position Indication: ON / OFF
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards: IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
Rated Service Short-Circuit (230 V AC) 50 kA
Breaking Capacity (Ics): (400 V AC) 50 kA
(440 V AC) 30 kA
(500 V AC) 30 kA
(690 V AC) 30 kA
Environmental
Ambient Air Temperature Yes
Compensation:
Maximum Operating Altitude 2000 m
Permissible:
Resistance to Shock acc. to IEC 11 ms Pulse 25g
60068-2-27:
Resistance to Vibrations acc. to IEC 5g / 3 ... 150 Hz
60068-2-6:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Around the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Operation Compensated -25 ... +55 °C
Storage -50 ... +80 °C
Technical UL/CSA
Horsepower Rating UL/CSA: (550 ... 600 V AC) Three Phase 0.5 Hp
Ampere Rating UL/CSA: 1A
General Use Rating UL/CSA: (600 V AC) 1 A
Connecting Capacity Main Circuit Flexible 1/2x 16-12 AWG
UL/CSA: Stranded 1/2x 16-12 AWG
Tightening Torque UL/CSA: Main Circuit 10 in·lb
Maximum Operating Voltage Main Circuit 600 V AC
UL/CSA:
Classifications
E-nummer: 3111938
ETIM 4: EC000074 - Motor protective circuit-breaker
ETIM 5: EC000074 - Motor protective circuit-breaker
ETIM 6: EC000074 - Motor protection circuit-breaker
eClass: 7.0 27370401
UNSPSC: 39121521
Object Classification Code: F
MS116-1.6
General Information
Extended Product Type: MS116-1.6
Product ID: 1SAM250000R1006
EAN: 4013614320293
Catalog Description: MS116-1.6 Manual Motor Starter
Long Description: The MS116-1.6 manual motor starter is a compact 45 mm width devices with a rated
operational current of Ie = 1.6 A. This device is used to manually switch on and off motors
and to protect them reliably and without the need for a fuse from short-circuits, overload and
phase failures. The manual motor starter offers a rated service short-circuit breaking
capacity Ics = 50 kA at 400 VAC and the trip class 10A. Further features are the build-in
disconnect function, temperature compensation, trip-free mechanism and a rotary handle
with a clear switch position indication. The manual motor starter is suitable for three- and
single-phase applications. Auxiliary contacts, signalling contacts, undervoltage releases,
shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection
against unauthorized changes are available as accessory.
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4013614320293
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 95 mm
Package Level 1 Height: 50 mm
Package Level 1 Gross Weight: 0.28 kg
Package Level 2 Units: 40 piece
Package Level 2 Width: 280 mm
Package Level 2 Length: 395 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 11.586 kg
Package Level 2 EAN: 4013614408663
Package Level 1 Units: 1 piece
Dimensions
Product Net Height: 90 mm
Product Net Depth: 85.6 mm
Product Net Weight: 0.265 kg
Product Net Width: 45 mm
Technical
Rated Ultimate Short-Circuit (230 V AC) 50 kA
Breaking Capacity (Icu): (400 V AC) 50 kA
(440 V AC) 30 kA
(500 V AC) 30 kA
(690 V AC) 30 kA
Rated Instantaneous Short-Circuit 20 A
Current Setting (Ii):
Setting Range: 1 ... 1.6 A
Rated Operational Power AC-3 (Pe): (400 V) Three Phase 0.55 kW
Rated Operational Voltage: Main Circuit 690 V AC
Rated Operational Current (Ie): 1.6 A
Rated Operational Current AC-3 (Ie): 1.6 A
Rated Frequency (f): Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage Main Circuit 6 kV
(Uimp):
Rated Insulation Voltage (Ui): 690 V
Power Loss: at Rated Operating Conditions per Pole 0.7 ... 1.7 W
Number of Poles: 3
Conventional Free-air Thermal Main Circuit 1.6 A
Current (Ith):
Degree of Protection: Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 100000 cycle
Mechanical Durability: 100000 cycle
Connecting Capacity-Main Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Tightening Torque: Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length: Main Circuit 9 mm
Recommended Screw Driver: Pozidriv 2
Mounting Position: Position 1 to 6
Actuator Type: Rotary Handle
Contact Position Indication: ON / OFF
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards: IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
Rated Service Short-Circuit (230 V AC) 50 kA
Breaking Capacity (Ics): (400 V AC) 50 kA
(440 V AC) 30 kA
(500 V AC) 30 kA
(690 V AC) 30 kA
Environmental
Ambient Air Temperature Yes
Compensation:
Maximum Operating Altitude 2000 m
Permissible:
Resistance to Shock acc. to IEC 11 ms Pulse 25g
60068-2-27:
Resistance to Vibrations acc. to IEC 5g / 3 ... 150 Hz
60068-2-6:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Around the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Operation Compensated -25 ... +55 °C
Storage -50 ... +80 °C
Technical UL/CSA
Horsepower Rating UL/CSA: (440 ... 480 V AC) Three Phase 0.75 Hp
(550 ... 600 V AC) Three Phase 0.75 Hp
Ampere Rating UL/CSA: 1.6 A
General Use Rating UL/CSA: (600 V AC) 1.6 A
Connecting Capacity Main Circuit Flexible 1/2x 16 ... 12 AWG
UL/CSA: Stranded 1/2x 16 ... 12 AWG
Tightening Torque UL/CSA: Main Circuit 10 in·lb
Maximum Operating Voltage Main Circuit 600 V AC
UL/CSA:
Classifications
E-nummer: 3111940
ETIM 4: EC000074 - Motor protective circuit-breaker
ETIM 5: EC000074 - Motor protective circuit-breaker
ETIM 6: EC000074 - Motor protection circuit-breaker
eClass: 7.0 27370401
UNSPSC: 39121521
Object Classification Code: F
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Manual Motor Starters
Products » Low Voltage Products and Systems » Control Products » Manual Motor Starters » Manual Motor Starters
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4013614320330
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 95 mm
Package Level 1 Height: 50 mm
Package Level 1 Gross Weight: 0.28 kg
Package Level 2 Units: 40 piece
Package Level 2 Width: 280 mm
Package Level 2 Length: 395 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 11.586 kg
Package Level 2 EAN: 4013614408700
Package Level 1 Units: 1 piece
Dimensions
Product Net Height: 90 mm
Product Net Depth: 85.6 mm
Product Net Weight: 0.265 kg
Product Net Width: 45 mm
Technical
Rated Ultimate Short-Circuit (230 V AC) 50 kA
Breaking Capacity (Icu): (400 V AC) 50 kA
(440 V AC) 6 kA
(500 V AC) 6 kA
(690 V AC) 2 kA
Rated Instantaneous Short-Circuit 150 A
Current Setting (Ii):
Setting Range: 6.3 ... 10 A
Rated Operational Power AC-3 (Pe): (400 V) Three Phase 4 kW
Rated Operational Voltage: Main Circuit 690 V AC
Rated Operational Current (Ie): 10 A
Rated Operational Current AC-3 (Ie): 10 A
Rated Frequency (f): Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage Main Circuit 6 kV
(Uimp):
Rated Insulation Voltage (Ui): 690 V
Power Loss: at Rated Operating Conditions per Pole 0.9 ... 2.4 W
Number of Poles: 3
Conventional Free-air Thermal Main Circuit 10 A
Current (Ith):
Degree of Protection: Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 100000 cycle
Mechanical Durability: 100000 cycle
Connecting Capacity Main Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Tightening Torque: Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length: Main Circuit 9 mm
Recommended Screw Driver: Pozidriv 2
Mounting Position: Position 1 to 6
Actuator Type: Rotary Handle
Contact Position Indication: ON / OFF
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards: IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
Rated Service Short-Circuit (230 V AC) 50 kA
Breaking Capacity (Ics): (400 V AC) 50 kA
(440 V AC) 6 kA
(500 V AC) 6 kA
(690 V AC) 2 kA
Environmental
Ambient Air Temperature Yes
Compensation:
Maximum Operating Altitude 2000 m
Permissible:
Resistance to Shock acc. to IEC 11 ms Pulse 25g
60068-2-27:
Resistance to Vibrations acc. to IEC 5g / 3 ... 150 Hz
60068-2-6:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Around the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Operation Compensated -25 ... +55 °C
Storage -50 ... +80 °C
Technical UL/CSA
Horsepower Rating UL/CSA: (220 ... 240 V AC) Three Phase 3 Hp
(440 ... 480 V AC) Three Phase 5 Hp
(550 ... 600 V AC) Three Phase 7.5 Hp
Ampere Rating UL/CSA: 10 A
General Use Rating UL/CSA: (600 V AC) 10 A
Connecting Capacity Main Circuit Flexible 1/2x 16-12 AWG
UL/CSA: Stranded 1/2x 16-12 AWG
Tightening Torque UL/CSA: Main Circuit 10 in·lb
Maximum Operating Voltage Main Circuit 600 V AC
UL/CSA:
Classifications
E-nummer: 3111948
ETIM 4: EC000074 - Motor protective circuit-breaker
ETIM 5: EC000074 - Motor protective circuit-breaker
ETIM 6: EC000074 - Motor protection circuit-breaker
eClass: 7.0 27370401
UNSPSC: 39121521
Object Classification Code: F
MS116-12
General Information
Extended Product Type: MS116-12
Product ID: 1SAM250000R1012
EAN: 4013614348211
Catalog Description: MS116-12 Manual Motor Starter
Long Description: The MS116-12 manual motor starter is a compact 45 mm width devices with a rated
operational current of Ie = 12.0 A. This device is used to manually switch on and off motors
and to protect them reliably and without the need for a fuse from short-circuits, overload and
phase failures. The manual motor starter offers a rated service short-circuit breaking
capacity Ics = 25 kA at 400 VAC and the trip class 10A. Further features are the build-in
disconnect function, temperature compensation, trip-free mechanism and a rotary handle
with a clear switch position indication. The manual motor starter is suitable for three- and
single-phase applications. Auxiliary contacts, signalling contacts, undervoltage releases,
shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection
against unauthorized changes are available as accessory.
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Manual Motor Starters
Products » Low Voltage Products and Systems » Control Products » Manual Motor Starters » Manual Motor Starters
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4013614348211
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 95 mm
Package Level 1 Height: 50 mm
Package Level 1 Gross Weight: 0.28 kg
Package Level 2 Units: 40 piece
Package Level 2 Width: 280 mm
Package Level 2 Length: 395 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 11.586 kg
Package Level 2 EAN: 4013614408724
Package Level 1 Units: 1 piece
Dimensions
Product Net Height: 90 mm
Product Net Depth: 85.6 mm
Product Net Weight: 0.265 kg
Product Net Width: 45 mm
Technical
Rated Ultimate Short-Circuit (230 V AC) 25 kA
Breaking Capacity (Icu): (400 V AC) 25 kA
(440 V AC) 6 kA
(500 V AC) 6 kA
(690 V AC) 2 kA
Rated Instantaneous Short-Circuit 180 A
Current Setting (Ii):
Setting Range: 8 ... 12 A
Rated Operational Power AC-3 (Pe): (400 V) Three Phase 5.5 kW
Rated Operational Voltage: Main Circuit 690 V AC
Rated Operational Current (Ie): 12 A
Rated Operational Current AC-3 (Ie): 12 A
Rated Frequency (f): Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage Main Circuit 6 kV
(Uimp):
Rated Insulation Voltage (Ui): 690 V
Power Loss: at Rated Operating Conditions per Pole 1.0 ... 2.3 W
Number of Poles: 3
Conventional Free-air Thermal Main Circuit 12 A
Current (Ith):
Degree of Protection: Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 100000 cycle
Mechanical Durability: 100000 cycle
Connecting Capacity-Main Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Tightening Torque: Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length: Main Circuit 9 mm
Recommended Screw Driver: Pozidriv 2
Mounting Position: Position 1 to 6
Actuator Type: Rotary Handle
Contact Position Indication: ON / OFF
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards: IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
Rated Service Short-Circuit (230 V AC) 25 kA
Breaking Capacity (Ics): (400 V AC) 25 kA
(440 V AC) 6 kA
(500 V AC) 6 kA
(690 V AC) 2 kA
Environmental
Ambient Air Temperature Yes
Compensation:
Maximum Operating Altitude 2000 m
Permissible:
Resistance to Shock acc. to IEC 11 ms Pulse 25g
60068-2-27:
Resistance to Vibrations acc. to IEC 5g / 3 ... 150 Hz
60068-2-6:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Around the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Operation Compensated -25 ... +55 °C
Storage -50 ... +80 °C
Technical UL/CSA
Horsepower Rating UL/CSA: (220 ... 240 V AC) Three Phase 3 Hp
(440 ... 480 V AC) Three Phase 7.5 Hp
(550 ... 600 V AC) Three Phase 10 Hp
Ampere Rating UL/CSA: 12 A
General Use Rating UL/CSA: (600 V AC) 12 A
Connecting Capacity Main Circuit Flexible 1/2x 16 ... 8 AWG
UL/CSA: Stranded 1/2x 16 ... 8 AWG
Tightening Torque UL/CSA: Main Circuit 10 in·lb
Maximum Operating Voltage Main Circuit 600 V AC
UL/CSA:
Classifications
E-nummer: 3111949
ETIM 4: EC000074 - Motor protective circuit-breaker
ETIM 5: EC000074 - Motor protective circuit-breaker
ETIM 6: EC000074 - Motor protection circuit-breaker
eClass: 7.0 27370401
UNSPSC: 39121521
Object Classification Code: F
MS116-16
General Information
Extended Product Type: MS116-16
Product ID: 1SAM250000R1011
EAN: 4013614320347
Catalog Description: MS116-16 Manual Motor Starter
Long Description: The MS116-16 manual motor starter is a compact 45 mm width devices with a rated
operational current of Ie = 16.0 A. This device is used to manually switch on and off motors
and to protect them reliably and without the need for a fuse from short-circuits, overload and
phase failures. The manual motor starter offers a rated service short-circuit breaking
capacity Ics = 16 kA at 400 VAC and the trip class 10A. Further features are the build-in
disconnect function, temperature compensation, trip-free mechanism and a rotary handle
with a clear switch position indication. The manual motor starter is suitable for three- and
single-phase applications. Auxiliary contacts, signalling contacts, undervoltage releases,
shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection
against unauthorized changes are available as accessory.
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4013614320347
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 95 mm
Package Level 1 Height: 50 mm
Package Level 1 Gross Weight: 0.28 kg
Package Level 2 Units: 40 piece
Package Level 2 Width: 280 mm
Package Level 2 Length: 395 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 11.586 kg
Package Level 2 EAN: 4013614408717
Package Level 1 Units: 1 piece
Dimensions
Product Net Height: 90 mm
Product Net Depth: 85.6 mm
Product Net Weight: 0.265 kg
Product Net Width: 45 mm
Technical
Rated Ultimate Short-Circuit (230 V AC) 16 kA
Breaking Capacity (Icu): (400 V AC) 16 kA
(440 V AC) 4 kA
(500 V AC) 4 kA
(690 V AC) 2 kA
Rated Instantaneous Short-Circuit 240 A
Current Setting (Ii):
Setting Range: 10 ... 16 A
Rated Operational Power AC-3 (Pe): (400 V) Three Phase 7.5 kW
Rated Operational Voltage: Main Circuit 690 V AC
Rated Operational Current (Ie): 16 A
Rated Operational Current AC-3 (Ie): 16 A
Rated Frequency (f): Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage Main Circuit 6 kV
(Uimp):
Rated Insulation Voltage (Ui): 690 V
Power Loss: at Rated Operating Conditions per Pole 1.1 ... 2.8 W
Number of Poles: 3
Conventional Free-air Thermal Main Circuit 16 A
Current (Ith):
Degree of Protection: Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 100000 cycle
Mechanical Durability: 100000 cycle
Connecting Capacity Main Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Tightening Torque: Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length: Main Circuit 9 mm
Recommended Screw Driver: Pozidriv 2
Mounting Position: Position 1 to 6
Actuator Type: Rotary Handle
Contact Position Indication: ON / OFF
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards: IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
Rated Service Short-Circuit (230 V AC) 16 kA
Breaking Capacity (Ics): (400 V AC) 16 kA
(440 V AC) 4 kA
(500 V AC) 4 kA
(690 V AC) 2 kA
Environmental
Ambient Air Temperature Yes
Compensation:
Maximum Operating Altitude 2000 m
Permissible:
Resistance to Shock acc. to IEC 11 ms Pulse 25g
60068-2-27:
Resistance to Vibrations acc. to IEC 5g / 3 ... 150 Hz
60068-2-6:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Around the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Operation Compensated -25 ... +55 °C
Storage -50 ... +80 °C
Technical UL/CSA
Horsepower Rating UL/CSA: (220 ... 240 V AC) Three Phase 5 Hp
(440 ... 480 V AC) Three Phase 10 Hp
(550 ... 600 V AC) Three Phase 10 Hp
Ampere Rating UL/CSA: 16 A
General Use Rating UL/CSA: (600 V AC) 16 A
Connecting Capacity Main Circuit Flexible 1/2x 16-8 AWG
UL/CSA: Stranded 1/2x 16-8 AWG
Tightening Torque UL/CSA: Main Circuit 10 in·lb
Maximum Operating Voltage Main Circuit 600 V AC
UL/CSA:
Classifications
E-nummer: 3111950
ETIM 4: EC000074 - Motor protective circuit-breaker
ETIM 5: EC000074 - Motor protective circuit-breaker
ETIM 6: EC000074 - Motor protection circuit-breaker
eClass: 7.0 27370401
UNSPSC: 39121521
Object Classification Code: F
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Manual Motor Starters
Products » Low Voltage Products and Systems » Control Products » Manual Motor Starters » Manual Motor Starters
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4013614320309
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 95 mm
Package Level 1 Height: 50 mm
Package Level 1 Gross Weight: 0.28 kg
Package Level 2 Units: 40 piece
Package Level 2 Width: 280 mm
Package Level 2 Length: 395 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 11.586 kg
Package Level 2 EAN: 4013614408670
Package Level 1 Units: 1 piece
Dimensions
Product Net Height: 90 mm
Product Net Depth: 85.6 mm
Product Net Weight: 0.26 kg
Product Net Width: 45 mm
Technical
Rated Ultimate Short-Circuit (230 V AC) 50 kA
Breaking Capacity (Icu): (400 V AC) 50 kA
(440 V AC) 10 kA
(500 V AC) 10 kA
(690 V AC) 5 kA
Rated Instantaneous Short-Circuit 31.3 A
Current Setting (Ii):
Setting Range: 1.6 ... 2.5 A
Rated Operational Power AC-3 (Pe): (400 V) Three Phase 0.75 kW
Rated Operational Voltage: Main Circuit 690 V AC
Rated Operational Current (Ie): 2.5 A
Rated Operational Current AC-3 (Ie): 2.5 A
Rated Frequency (f): Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage Main Circuit 6 kV
(Uimp):
Rated Insulation Voltage (Ui): 690 V
Power Loss: at Rated Operating Conditions per Pole 0.7 ... 1.8 W
Number of Poles: 3
Conventional Free-air Thermal Main Circuit 2.5 A
Current (Ith):
Degree of Protection: Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 100000 cycle
Mechanical Durability: 100000 cycle
Connecting Capacity Main Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Tightening Torque: Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length: Main Circuit 9 mm
Recommended Screw Driver: Pozidriv 2
Mounting Position: Position 1 to 6
Actuator Type: Rotary Handle
Contact Position Indication: ON / OFF
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards: IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
Rated Service Short-Circuit (230 V AC) 50 kA
Breaking Capacity (Ics): (400 V AC) 50 kA
(440 V AC) 10 kA
(500 V AC) 10 kA
(690 V AC) 5 kA
Environmental
Ambient Air Temperature Yes
Compensation:
Maximum Operating Altitude 2000 m
Permissible:
Resistance to Shock acc. to IEC 11 ms Pulse 25g
60068-2-27:
Resistance to Vibrations acc. to IEC 5g / 3 ... 150 Hz
60068-2-6:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Around the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Operation Compensated -25 ... +55 °C
Storage -50 ... +80 °C
Technical UL/CSA
Horsepower Rating UL/CSA: (220 ... 240 V AC) Three Phase 0.5 Hp
(440 ... 480 V AC) Three Phase 1 Hp
(550 ... 600 V AC) Three Phase 1.5 Hp
Ampere Rating UL/CSA: 2.5 A
General Use Rating UL/CSA: (600 V AC) 2.5 A
Connecting Capacity Main Circuit Flexible 1/2x 16-12 AWG
UL/CSA: Stranded 1/2x 16-12 AWG
Tightening Torque UL/CSA: Main Circuit 10 in·lb
Maximum Operating Voltage Main Circuit 600 V AC
UL/CSA:
Classifications
E-nummer: 3111942
ETIM 4: EC000074 - Motor protective circuit-breaker
ETIM 5: EC000074 - Motor protective circuit-breaker
ETIM 6: EC000074 - Motor protection circuit-breaker
eClass: 7.0 27370401
UNSPSC: 39121521
Object Classification Code: F
MS116-32
General Information
Extended Product Type: MS116-32
Product ID: 1SAM250000R1015
EAN: 4013614405679
Catalog Description: MS116-32 Manual Motor Starter
Long Description: The MS116-32 manual motor starter is a compact 45 mm width devices with a rated
operational current of Ie = 32.0 A. This device is used to manually switch on and off motors
and to protect them reliably and without the need for a fuse from short-circuits, overload and
phase failures. The manual motor starter offers a rated service short-circuit breaking
capacity Ics = 10 kA at 400 VAC and the trip class 10A. Further features are the build-in
disconnect function, temperature compensation, trip-free mechanism and a rotary handle
with a clear switch position indication. The manual motor starter is suitable for three- and
single-phase applications. Auxiliary contacts, signalling contacts, undervoltage releases,
shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection
against unauthorized changes are available as accessory.
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Manual Motor Starters
Products » Low Voltage Products and Systems » Control Products » Manual Motor Starters » Manual Motor Starters
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4013614405679
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 102 mm
Package Level 1 Height: 50 mm
Package Level 1 Gross Weight: 0.325 kg
Package Level 2 Units: 40 piece
Package Level 2 Width: 280 mm
Package Level 2 Length: 395 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 13.386 kg
Package Level 2 EAN: 4013614408755
Package Level 1 Units: 1 piece
Dimensions
Product Net Height: 97.8 mm
Product Net Depth: 86.55 mm
Product Net Weight: 0.31 kg
Product Net Width: 45 mm
Technical
Rated Ultimate Short-Circuit (230 V AC) 10 kA
Breaking Capacity (Icu): (400 V AC) 10 kA
(440 V AC) 6 kA
(500 V AC) 4 kA
(690 V AC) 2 kA
Rated Instantaneous Short-Circuit 480 A
Current Setting (Ii):
Setting Range: 25 ... 32 A
Rated Operational Power AC-3 (Pe): (400 V) Three Phase 15 kW
Rated Operational Voltage: Main Circuit 690 V AC
Rated Operational Current (Ie): 32 A
Rated Operational Current AC-3 (Ie): 32 A
Rated Frequency (f): Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage Main Circuit 6 kV
(Uimp):
Rated Insulation Voltage (Ui): 690 V
Power Loss: at Rated Operating Conditions per Pole 1.9 ... 3.1 W
Number of Poles: 3
Conventional Free-air Thermal Main Circuit 32 A
Current (Ith):
Degree of Protection: Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 50000 cycle
Mechanical Durability: 100000 cycle
Connecting Capacity Main Circuit: Flexible with Ferrule 1/2x 0.75 ... 6 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 6 mm²
Flexible 1/2x 1 ... 2.5 mm²
Flexible 1/2x 2.5 ... 6 mm²
Rigid 1/2x 1 ... 2.5 mm²
Rigid 1/2x 2.5 ... 6 mm²
Tightening Torque: Main Circuit 2 N·m
Wire Stripping Length: Main Circuit 10 mm
Recommended Screw Driver: Pozidriv 2
Mounting Position: Position 1 to 6
Actuator Type: Rotary Handle
Contact Position Indication: ON / OFF
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards: IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
Rated Service Short-Circuit (230 V AC) 10 kA
Breaking Capacity (Ics): (400 V AC) 10 kA
(440 V AC) 3 kA
(500 V AC) 3 kA
(690 V AC) 2 kA
Environmental
Ambient Air Temperature Yes
Compensation:
Maximum Operating Altitude 2000 m
Permissible:
Resistance to Shock acc. to IEC 11 ms Pulse 25g
60068-2-27:
Resistance to Vibrations acc. to IEC 5g / 3 ... 150 Hz
60068-2-6:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Around the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Operation Compensated -25 ... +55 °C
Storage -50 ... +80 °C
Technical UL/CSA
Horsepower Rating UL/CSA: (220 ... 240 V AC) Three Phase 10 Hp
(440 ... 480 V AC) Three Phase 20 Hp
(550 ... 600 V AC) Three Phase 25 Hp
Ampere Rating UL/CSA: 32 A
General Use Rating UL/CSA: (600 V AC) 32 A
Connecting Capacity Main Circuit Flexible 1/2x 16-8 AWG
UL/CSA: Stranded 1/2x 16-8 AWG
Tightening Torque UL/CSA: Main Circuit 18 in·lb
Maximum Operating Voltage Main Circuit 600 V AC
UL/CSA:
Classifications
E-nummer: 3111953
ETIM 4: EC000074 - Motor protective circuit-breaker
ETIM 5: EC000074 - Motor protective circuit-breaker
ETIM 6: EC000074 - Motor protection circuit-breaker
eClass: 7.0 27370401
UNSPSC: 39121521
Object Classification Code: F
MS116-4.0
General Information
Extended Product Type: MS116-4.0
Product ID: 1SAM250000R1008
EAN: 4013614320316
Catalog Description: MS116-4.0 Manual Motor Starter
Long Description: The MS116-4.0 manual motor starter is a compact 45 mm width devices with a rated
operational current of Ie = 4.0 A. This device is used to manually switch on and off motors
and to protect them reliably and without the need for a fuse from short-circuits, overload and
phase failures. The manual motor starter offers a rated service short-circuit breaking
capacity Ics = 50 kA at 400 VAC and the trip class 10A. Further features are the build-in
disconnect function, temperature compensation, trip-free mechanism and a rotary handle
with a clear switch position indication. The manual motor starter is suitable for three- and
single-phase applications. Auxiliary contacts, signalling contacts, undervoltage releases,
shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection
against unauthorized changes are available as accessory.
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Manual Motor Starters
Products » Low Voltage Products and Systems » Control Products » Manual Motor Starters » Manual Motor Starters
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4013614320316
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 95 mm
Package Level 1 Height: 50 mm
Package Level 1 Gross Weight: 0.28 kg
Package Level 2 Units: 40 piece
Package Level 2 Width: 280 mm
Package Level 2 Length: 395 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 11.586 kg
Package Level 2 EAN: 4013614408687
Package Level 1 Units: 1 piece
Dimensions
Product Net Height: 90 mm
Product Net Depth: 85.6 mm
Product Net Weight: 0.265 kg
Product Net Width: 45 mm
Technical
Rated Ultimate Short-Circuit (230 V AC) 50 kA
Breaking Capacity (Icu): (400 V AC) 50 kA
(440 V AC) 6 kA
(500 V AC) 6 kA
(690 V AC) 2 kA
Rated Instantaneous Short-Circuit 50 A
Current Setting (Ii):
Setting Range: 2.5 ... 4 A
Rated Operational Power AC-3 (Pe): (400 V) Three Phase 1.5 kW
Rated Operational Voltage: Main Circuit 690 V AC
Rated Operational Current (Ie): 4A
Rated Operational Current AC-3 (Ie): 4A
Rated Frequency (f): Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage Main Circuit 6 kV
(Uimp):
Rated Insulation Voltage (Ui): 690 V
Power Loss: at Rated Operating Conditions per Pole 0.7 ... 1.8 W
Number of Poles: 3
Conventional Free-air Thermal Main Circuit 4 A
Current (Ith):
Degree of Protection: Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 100000 cycle
Mechanical Durability: 100000 cycle
Connecting Capacity Main Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Tightening Torque: Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length: Main Circuit 9 mm
Recommended Screw Driver: Pozidriv 2
Mounting Position: Position 1 to 6
Actuator Type: Rotary Handle
Contact Position Indication: ON / OFF
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards: IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
Rated Service Short-Circuit (230 V AC) 50 kA
Breaking Capacity (Ics): (400 V AC) 50 kA
(440 V AC) 6 kA
(500 V AC) 6 kA
(690 V AC) 2 kA
Environmental
Ambient Air Temperature Yes
Compensation:
Maximum Operating Altitude 2000 m
Permissible:
Resistance to Shock acc. to IEC 11 ms Pulse 25g
60068-2-27:
Resistance to Vibrations acc. to IEC 5g / 3 ... 150 Hz
60068-2-6:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Around the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Operation Compensated -25 ... +55 °C
Storage -50 ... +80 °C
Technical UL/CSA
Horsepower Rating UL/CSA: (220 ... 240 V AC) Three Phase 1 Hp
(440 ... 480 V AC) Three Phase 2 Hp
(550 ... 600 V AC) Three Phase 3 Hp
Ampere Rating UL/CSA: 4A
General Use Rating UL/CSA: (600 V AC) 4 A
Connecting Capacity Main Circuit Flexible 1/2x 16-12 AWG
UL/CSA: Stranded 1/2x 16-12 AWG
Tightening Torque UL/CSA: Main Circuit 10 in·lb
Maximum Operating Voltage Main Circuit 600 V AC
UL/CSA:
Classifications
E-nummer: 3111944
ETIM 4: EC000074 - Motor protective circuit-breaker
ETIM 5: EC000074 - Motor protective circuit-breaker
ETIM 6: EC000074 - Motor protection circuit-breaker
eClass: 7.0 27370401
UNSPSC: 39121521
Object Classification Code: F
MS116-6.3
General Information
Extended Product Type: MS116-6.3
Product ID: 1SAM250000R1009
EAN: 4013614320323
Catalog Description: MS116-6.3 Manual Motor Starter
Long Description: The MS116-6.3 manual motor starter is a compact 45 mm width devices with a rated
operational current of Ie = 6.3 A. This device is used to manually switch on and off motors
and to protect them reliably and without the need for a fuse from short-circuits, overload and
phase failures. The manual motor starter offers a rated service short-circuit breaking
capacity Ics = 50 kA at 400 VAC and the trip class 10A. Further features are the build-in
disconnect function, temperature compensation, trip-free mechanism and a rotary handle
with a clear switch position indication. The manual motor starter is suitable for three- and
single-phase applications. Auxiliary contacts, signalling contacts, undervoltage releases,
shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection
against unauthorized changes are available as accessory.
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4013614320323
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 95 mm
Package Level 1 Height: 50 mm
Package Level 1 Gross Weight: 0.28 kg
Package Level 2 Units: 40 piece
Package Level 2 Width: 280 mm
Package Level 2 Length: 395 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 11.586 kg
Package Level 2 EAN: 4013614408694
Package Level 1 Units: 1 piece
Dimensions
Product Net Height: 90 mm
Product Net Depth: 85.6 mm
Product Net Weight: 0.265 kg
Product Net Width: 45 mm
Technical
Rated Ultimate Short-Circuit (230 V AC) 50 kA
Breaking Capacity (Icu): (400 V AC) 50 kA
(440 V AC) 6 kA
(500 V AC) 6 kA
(690 V AC) 2 kA
Rated Instantaneous Short-Circuit 78.8 A
Current Setting (Ii):
Setting Range: 4 ... 6.3 A
Rated Operational Power AC-3 (Pe): (400 V) Three Phase 2.2 kW
Rated Operational Voltage: Main Circuit 690 V AC
Rated Operational Current (Ie): 6.3 A
Rated Operational Current AC-3 (Ie): 6.3 A
Rated Frequency (f): Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage Main Circuit 6 kV
(Uimp):
Rated Insulation Voltage (Ui): 690 V
Power Loss: at Rated Operating Conditions per Pole 0.7 ... 1.8 W
Number of Poles: 3
Conventional Free-air Thermal Main Circuit 6.3 A
Current (Ith):
Degree of Protection: Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 100000 cycle
Mechanical Durability: 100000 cycle
Connecting Capacity-Main Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Tightening Torque: Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length: Main Circuit 9 mm
Recommended Screw Driver: Pozidriv 2
Mounting Position: Position 1 to 6
Actuator Type: Rotary Handle
Contact Position Indication: ON / OFF
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards: IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
Rated Service Short-Circuit (230 V AC) 50 kA
Breaking Capacity (Ics): (400 V AC) 50 kA
(440 V AC) 6 kA
(500 V AC) 6 kA
(690 V AC) 2 kA
Environmental
Ambient Air Temperature Yes
Compensation:
Maximum Operating Altitude 2000 m
Permissible:
Resistance to Shock acc. to IEC 11 ms Pulse 25g
60068-2-27:
Resistance to Vibrations acc. to IEC 5g / 3 ... 150 Hz
60068-2-6:
RoHS Status: Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2008 Q1
Ambient Air Temperature: Around the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Operation Compensated -25 ... +55 °C
Storage -50 ... +80 °C
Technical UL/CSA
Horsepower Rating UL/CSA: (220 ... 240 V AC) Three Phase 1.5 Hp
(440 ... 480 V AC) Three Phase 3 Hp
(550 ... 600 V AC) Three Phase 5 Hp
Ampere Rating UL/CSA: 6.3 A
General Use Rating UL/CSA: (600 V AC) 6.3 A
Connecting Capacity Main Circuit Flexible 1/2x 16 ... 12 AWG
UL/CSA: Stranded 1/2x 16 ... 12 AWG
Tightening Torque UL/CSA: Main Circuit 10 in·lb
Maximum Operating Voltage Main Circuit 600 V AC
UL/CSA:
Classifications
E-nummer: 3111946
ETIM 4: EC000074 - Motor protective circuit-breaker
ETIM 5: EC000074 - Motor protective circuit-breaker
ETIM 6: EC000074 - Motor protection circuit-breaker
eClass: 7.0 27370401
UNSPSC: 39121521
Object Classification Code: F
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Manual Motor Starters
Products » Low Voltage Products and Systems » Control Products » Manual Motor Starters » Manual Motor Starters
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4013614485015
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 102 mm
Package Level 1 Height: 50 mm
Package Level 1 Gross Weight: 0.325 kg
Package Level 2 Units: 40 piece
Package Level 2 Width: 280 mm
Package Level 2 Length: 395 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 13.386 kg
Package Level 2 EAN: 4013614487217
Package Level 1 Units: 1 piece
Dimensions
Product Net Height: 97.8 mm
Product Net Depth: 86.05 mm
Product Net Weight: 0.31 kg
Product Net Width: 45 mm
Technical
Rated Instantaneous Short-Circuit 240 A
Current Setting (Ii):
Setting Range: 8 ... 12 A
Rated Operational Voltage: Main Circuit 690 V AC
Rated Operational Current (Ie): 12 A
Rated Frequency (f): Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage Main Circuit 6 kV
(Uimp):
Rated Insulation Voltage (Ui): 690 V
Power Loss: at Rated Operating Conditions per Pole 0.9 … 2.0 W
Number of Poles: 3
Conventional Free-air Thermal 12 A
Current (Ith): Main Circuit 12 A
Degree of Protection: Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 50000 cycle
Mechanical Durability: 100000 cycle
Connecting Capacity-Main Circuit: Flexible with Ferrule 1/2x 0.75 ... 6 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 6 mm²
Flexible 1/2x 1 ... 2.5 mm²
Flexible 1/2x 2.5 ... 6 mm²
Rigid 1/2x 1 ... 2.5 mm²
Rigid 1/2x 2.5 ... 6 mm²
Tightening Torque: Main Circuit 2 N·m
Wire Stripping Length: Main Circuit 10 mm
Recommended Screw Driver: M4
Pozidriv 2
Mounting Position: Position 1 to 6
Actuator Type: Rotary Handle
Contact Position Indication: ON / OFF / TRIP
Standards: IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
Environmental
Ambient Air Temperature Yes
Compensation:
Maximum Operating Altitude 2000 m
Permissible:
Resistance to Shock acc. to IEC 11 ms Pulse 25g
60068-2-27:
Resistance to Vibrations acc. to IEC 5g / 3 ... 150 Hz
60068-2-6:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Around the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Storage -50 ... +80 °C
Technical UL/CSA
Connecting Capacity Main Circuit Flexible 1/2x 16 ... 8 AWG
UL/CSA: Stranded 1/2x 16 ... 8 AWG
Tightening Torque UL/CSA: Main Circuit 16 in·lb
Classifications
ETIM 4: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 6: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
eClass: 7.0 27370409
Object Classification Code: F
MS132-6.3T
General Information
Extended Product Type: MS132-6.3T
Product ID: 1SAM340000R1009
EAN: 4013614484995
Catalog Description: MS132-6.3T Circuit Breaker for Primary Transformer Protection
Long Description: The circuit breaker for transformer protection MS132-6.3T is a compact 45 mm width device
designed to protect control transformers on the primary side. This device has a rated
operational current of Ie = 6.3 A. It allows fuse-less protection against overload and short-
circuit. The short-circuit current setting is fixed to 20 times the rated operational current to
handle the high inrush current generated by transformers. The device allows manually
connect and disconnect the transformer from the mains thanks of its built-in disconnection
function. The circuit breaker for transformer protection offers a rated service short-circuit
breaking capacity of Ics = 100 kA at 400 VAC and a trip class 10. Further features are
temperature compensation, trip-free mechanism, rotary handle with a clear switch position
indication and short circuit trip indicator. The handle is lockable to protect against
unauthorized changes. Auxiliary contacts, signalling contacts, undervoltage releases, shunt
trips, power in-feed blocks are available as accessory.
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Manual Motor Starters
Products » Low Voltage Products and Systems » Control Products » Manual Motor Starters » Manual Motor Starters
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4013614484995
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 95 mm
Package Level 1 Height: 50 mm
Package Level 1 Gross Weight: 0.28 kg
Package Level 2 Units: 40 piece
Package Level 2 Width: 280 mm
Package Level 2 Length: 395 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 11.586 kg
Package Level 2 EAN: 4013614487194
Package Level 1 Units: 1 piece
Dimensions
Product Net Height: 90 mm
Product Net Depth: 86.75 mm
Product Net Weight: 0.265 kg
Product Net Width: 45 mm
Technical
Rated Instantaneous Short-Circuit 126 A
Current Setting (Ii):
Setting Range: 4 ... 6.3 A
Rated Operational Voltage: Main Circuit 690 V AC
Rated Operational Current (Ie): 6.3 A
Rated Frequency (f): Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage Main Circuit 6 kV
(Uimp):
Rated Insulation Voltage (Ui): 690 V
Power Loss: at Rated Operating Conditions per Pole 0.7 … 1.8 W
Number of Poles: 3
Conventional Free-air Thermal 6.3 A
Current (Ith): Main Circuit 6.3 A
Degree of Protection: Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 50000 cycle
Mechanical Durability: 100000 cycle
Connecting Capacity-Main Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Tightening Torque: Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length: Main Circuit 9 mm
Recommended Screw Driver: Pozidriv 2
M3.5
Mounting Position: Position 1 to 6
Actuator Type: Rotary Handle
Contact Position Indication: ON / OFF / TRIP
Standards: IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
Environmental
Ambient Air Temperature Yes
Compensation:
Maximum Operating Altitude 2000 m
Permissible:
Resistance to Shock acc. to IEC 11 ms Pulse 25g
60068-2-27:
Resistance to Vibrations acc. to IEC 5g / 3 ... 150 Hz
60068-2-6:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Around the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Storage -50 ... +80 °C
Technical UL/CSA
Connecting Capacity Main Circuit Flexible 1/2x 16 ... 12 AWG
UL/CSA: Stranded 1/2x 16 ... 12 AWG
Tightening Torque UL/CSA: Main Circuit 10 ... 12 in·lb
Classifications
ETIM 4: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 6: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
eClass: 7.0 27370409
Object Classification Code: F
MS165-54
General Information
Extended Product Type: MS165-54
Product ID: 1SAM451000R1016
EAN: 4013614486104
Catalog Description: MS165-54 Manual Motor Starter
Long Description: MS165-54 Manual motor starter Trip class 10 40 - 54 A
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Manual Motor Starters
Products » Low Voltage Products and Systems » Control Products » Manual Motor Starters » Manual Motor Starters
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4013614486104
Container Information
Package Level 1 Width: 78 mm
Package Level 1 Length: 155 mm
Package Level 1 Height: 155 mm
Package Level 1 Gross Weight: 1.1 kg
Package Level 2 Units: 12 piece
Package Level 2 Width: 330 mm
Package Level 2 Length: 400 mm
Package Level 2 Height: 320 mm
Package Level 2 Gross Weight: 13 kg
Package Level 2 EAN: 4013614503962
Package Level 1 Units: 1 piece
Dimensions
Product Net Height: 142.65 mm
Product Net Depth: 122.1 mm
Product Net Weight: 0.97 kg
Product Net Width: 55 mm
Technical
Rated Ultimate Short-Circuit (230 V AC) 50 kA
Breaking Capacity (Icu): (250 V DC) 100 kA
(400 V AC) 50 kA
(440 V AC) 45 kA
(500 V AC) 20 kA
(690 V AC) 5 kA
Rated Instantaneous Short-Circuit 810 A
Current Setting (Ii):
Setting Range: 40 ... 54 A
Rated Operational Power AC-3 (Pe): (400 V) Three Phase 22 kW
Rated Operational Voltage: Main Circuit 690 V AC
Rated Operational Current (Ie): 54 A
Rated Operational Current AC-3 (Ie): 54 A
Rated Operational Current DC-5 (Ie): 54 A
Rated Frequency (f): Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage Main Circuit 8 kV
(Uimp):
Rated Insulation Voltage (Ui): 1000 V
Power Loss: 3.84 … 6.99 W
Number of Poles: 3
Conventional Free-air Thermal Main Circuit 54 A
Current (Ith):
Degree of Protection: Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 25000 cycle
Mechanical Durability: 50000 cycle
Connecting Capacity Main Circuit: Flexible with Ferrule 1/2x 1 ... 35 mm²
Flexible with Insulated Ferrule 1/2x 1 … 35 mm²
Flexible 1/2x 1 ... 35 mm²
Solid 1/2x 1 … 50 mm²
Tightening Torque: Control Circuit 4 N·m
Main Circuit 4 N·m
Wire Stripping Length: Main Circuit 16 mm
Recommended Screw Driver: Pozidriv 2
Mounting Position: Position 1 to 6
Actuator Type: Rotary Handle
Contact Position Indication: ON / OFF / TRIP
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards: IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-4-1
CSA 22.2 No. 14
Rated Service Short-Circuit (230 V AC) 30 kA
Breaking Capacity (Ics): (250 V DC) 3 Poles in Series 100 kA
(400 V AC) 30 kA
(440 V AC) 30 kA
(500 V AC) 20 kA
(690 V AC) 5 kA
Environmental
Ambient Air Temperature Yes
Compensation:
Maximum Operating Altitude 2000 m
Permissible:
Resistance to Shock acc. to IEC 11 ms Pulse 25g
60068-2-27:
Resistance to Vibrations acc. to IEC 5g / 3 ... 150 Hz
60068-2-6:
RoHS Status: Following EU Directive 2011/65/EC
Ambient Air Temperature: Operation -25 ... +60 °C
Operation Compensated -25 ... +60 °C
Storage -50 ... +80 °C
Technical UL/CSA
Horsepower Rating UL/CSA: (200 V AC) Three Phase 15 Hp
(208 V AC) Three Phase 15 Hp
(220 ... 240 V AC) Three Phase 20 Hp
(440 ... 480 V AC) Three Phase 40 Hp
(550 ... 600 V AC) Three Phase 50 Hp
Ampere Rating UL/CSA: 54 A
General Use Rating UL/CSA: (600 V AC) 54 A
Connecting Capacity Main Circuit Flexible 1/2x 16-0 AWG
UL/CSA: Stranded 1/2x 16-0 AWG
Tightening Torque UL/CSA: 35 in·lb
Main Circuit 35 in·lb
Maximum Operating Voltage Main Circuit 600 V AC
UL/CSA:
Classifications
ETIM 5: EC000074 - Motor protective circuit-breaker
ETIM 6: EC000074 - Motor protection circuit-breaker
eClass: 7.0 27370401
UNSPSC: 39121521
Object Classification Code: F
RHD T4-T5 F/P STAND. DIRECT
General Information
Extended Product Type: RHD T4-T5 F/P STAND. DIRECT
Product ID: 1SDA054926R1
EAN: 8015644557089
Catalog Description: RHD T4-T5 F/P STAND. DIRECT
Long Description: ROTARY HANDLE OPERATING MECHANISM STANDARD DIRECT WITH PADLOCK
DEVICE ON C.BREAKER FIXED-PLUG-IN T4-T5
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Moulded Case Circuit Breakers » Accessories for
Tmax T
Ordering
EAN: 8015644557089
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85389099
Dimensions
Product Net Weight: 0.3 kg
Container Information
Package Level 1 Units: 1 piece
Package Level 1 Gross Weight: 0.4 kg
Package Level 1 EAN: 8015644557089
Environmental
RoHS Status: Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2006-07-
01
Additional Information
Product Main Type: Accessories for Tmax T
Product Name: Accessory for Circuit Breakers
Product Type: ACC
Standards: IEC
Suitable For: T4
T5
Suitable for Product Class: SACE Tmax T
Classifications
E-nummer: 3180997
Object Classification Code: Q
UNSPSC: 39120000
RHD XT2-XT4 F/P STAND. DIRECT
General Information
Extended Product Type: RHD XT2-XT4 F/P STAND. DIRECT
Product ID: 1SDA069053R1
EAN: 8015644697396
Catalog Description: RHD XT2-XT4 F/P STAND. DIRECT
Long Description: ROTARY HANDLE OPERATING MECHANISM STANDARD DIRECT WITH PADLOCK
DEVICE ON C.BREAKER FIXED-PLUG-IN XT2-XT4
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Moulded Case Circuit Breakers » Accessories for
Tmax XT
Ordering
EAN: 8015644697396
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85389099
Container Information
Package Level 1 Units: 1 piece
Package Level 1 EAN: 8015644697396
Additional Information
Product Main Type: Accessories for Tmax XT
Product Name: Accessory for Circuit Breakers
Product Type: ACC
Standards: IEC 60947-2
Suitable For: XT2
XT3
XT4
Suitable for Product Class: SACE Tmax XT
Classifications
Object Classification Code: Q
T5N 400 PR221DS-LS/I In=400 3p F F
General Information
Extended Product Type: T5N 400 PR221DS-LS/I In=400 3p F F
Product ID: 1SDA054317R1
EAN: 8015644552626
Catalog Description: T5N 400 PR221DS-LS/I In=400 3p F F
Long Description: C.BREAKER TMAX T5N 400 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-
STATE RELEASE IN AC PR221DS-LS/I R 400
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Moulded Case Circuit Breakers » Tmax T
Ordering
EAN: 8015644552626
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 140 mm
Product Net Height: 205 mm
Product Net Depth: 103.5 mm
Product Net Weight: 5.1 kg
Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 248 mm
Package Level 1 Height: 240 mm
Package Level 1 Length: 285 mm
Package Level 1 Gross Weight: 5.1 kg
Package Level 1 EAN: 8015644552626
Environmental
RoHS Status: Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2007-01-
01
Additional Information
Electrical Durability: 7000 cycle
60 cycles per hour
IIT Publishing Status: Level 0 - Information enabled
Mechanical Durability: 20000 cycle
120 cycles per hour
Number of Poles: 3
Power Loss: at Rated Operating Conditions per Pole 16,5 W
Product Main Type: SACE Tmax T
Product Name: Automatic Circuit Breaker
Product Type: CB
Rated Current (In): Main Circuit 400 A
Rated Impulse Withstand Voltage 8 kV
(Uimp):
Rated Insulation Voltage (Ui): 1000 V
Rated Operational Voltage: 690 V AC
Rated Service Short-Circuit (220 V AC) 70 kA
Breaking Capacity (Ics): (230 V AC) 70 kA
(380 V AC) 36 kA
(400 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 30 kA
(500 V AC) 25 kA
(690 V AC) 20 kA
Rated Short-time Withstand Current for 1 s 5 A
(Icw):
Rated Ultimate Short-Circuit (220 V AC) 7 kA
Breaking Capacity (Icu): (230 V AC) 7 kA
(380 V AC) 36 kA
(400 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 30 kA
(500 V AC) 25 kA
(690 V AC) 20 kA
(250 V DC) 2 Poles in Series 36 kA
(250 V DC) 3 Poles in Series 25 kA
(500 V DC) 3 Poles in Series 16 kA
Rated Uninterrupted Current (Iu): 400 A
Release Type: EL
Standards: IEC 60947
Sub-type: T5
Suitable For: T5
Suitable for Product Class: Moulded Case Circuit Breakers
Terminal Connection Type: Fixed Circuit-Breakers
Front
Test Voltage Max (Utest): 3500 V
Version: F
Classifications
E-nummer: 3180373
ETIM 4: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification Code: Q
UNSPSC: 39121100
XT1C 160 TMD 100-1000 3p F F
General Information
Extended Product Type: XT1C 160 TMD 100-1000 3p F F
Product ID: 1SDA067397R1
EAN: 8015644012915
Catalog Description: XT1C 160 TMD 100-1000 3p F F
Long Description: C.BREAKER TMAX XT1C 160 FIXED THREE-POLE WITH FRONT TERMINALS AND
THERMOMAGNETIC RELEASE TMD R 100-1000 A
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Moulded Case Circuit Breakers » Tmax XT
Ordering
EAN: 8015644012915
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 76.2 mm
Product Net Height: 130 mm
Product Net Depth: 70 mm
Product Net Weight: 1.1 kg
Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 128 mm
Package Level 1 Height: 135 mm
Package Level 1 Length: 143 mm
Package Level 1 Gross Weight: 1.1 kg
Package Level 1 EAN: 8015644012915
Additional Information
Circuit Breaker Type to be Power distribution
Associated:
Electrical Durability: 120 cycles per hour
8000 cycle
Mechanical Durability: Nr. Operations 240 cycles per hour
Nr. Operations 25000 cycle
Number of Poles: 3
Opening Time: CB with SOR 15 ms
CB with UVR 15 ms
Power Loss: at Rated Operating Conditions per Pole 7 W
Product Main Type: SACE Tmax XT
Product Name: Automatic Circuit Breaker
Product Type: CB
Rated Current (In): 100 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage 8 kV
(Uimp):
Rated Insulation Voltage (Ui): 800 V
Rated Operational Voltage: 690 V AC
500 V DC
Rated Service Short-Circuit (220 V AC) 40 kA
Breaking Capacity (Ics): (220 V AC) 40 kA
(380 V AC) 25 kA
(415 V AC) 25 kA
(440 V AC) 12,5 kA
(500 V AC) 9 kA
(690 V AC) 4 kA
Rated Ultimate Short-Circuit (220 V AC) 40 kA
Breaking Capacity (Icu): (230 V AC) 40 kA
(380 V AC) 25 kA
(415 V AC) 25 kA
(440 V AC) 25 kA
(500 V AC) 18 kA
(690 V AC) 4 kA
(250 V DC) 2 Poles in Series 25 kA
(500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Release Type: TM
Standards: IEC 60947
Sub-type: XT1
Terminal Connection Type: Fixed Circuit-Breakers
Front
Version: F
Classifications
ETIM 4: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification Code: Q
UNSPSC: 39120000
XT1C 160 TMD 63-630 3p F F
General Information
Extended Product Type: XT1C 160 TMD 63-630 3p F F
Product ID: 1SDA067395R1
EAN: 8015644012199
Catalog Description: XT1C 160 TMD 63-630 3p F F
Long Description: C.BREAKER TMAX XT1C 160 FIXED THREE-POLE WITH FRONT TERMINALS AND
THERMOMAGNETIC RELEASE TMD R 63-630 A
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Moulded Case Circuit Breakers » Tmax XT
Ordering
EAN: 8015644012199
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 76.2 mm
Product Net Height: 130 mm
Product Net Depth: 70 mm
Product Net Weight: 1.1 kg
Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 128 mm
Package Level 1 Height: 135 mm
Package Level 1 Length: 143 mm
Package Level 1 Gross Weight: 1.1 kg
Package Level 1 EAN: 8015644012199
Additional Information
Circuit Breaker Type to be Power distribution
Associated:
Electrical Durability: 120 cycles per hour
8000 cycle
Mechanical Durability: Nr. Operations 240 cycles per hour
Nr. Operations 25000 cycle
Number of Poles: 3
Opening Time: CB with SOR 15 ms
CB with UVR 15 ms
Power Loss: at Rated Operating Conditions per Pole 4.3 W
Product Main Type: SACE Tmax XT
Product Name: Automatic Circuit Breaker
Product Type: CB
Rated Current (In): 63 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage 8 kV
(Uimp):
Rated Insulation Voltage (Ui): 800 V
Rated Operational Voltage: 690 V AC
500 V DC
Rated Service Short-Circuit (220 V AC) 40 kA
Breaking Capacity (Ics): (220 V AC) 40 kA
(380 V AC) 25 kA
(415 V AC) 25 kA
(440 V AC) 12,5 kA
(500 V AC) 9 kA
(690 V AC) 4 kA
Rated Ultimate Short-Circuit (220 V AC) 40 kA
Breaking Capacity (Icu): (230 V AC) 40 kA
(380 V AC) 25 kA
(415 V AC) 25 kA
(440 V AC) 25 kA
(500 V AC) 18 kA
(690 V AC) 4 kA
(250 V DC) 2 Poles in Series 25 kA
(500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Release Type: TM
Standards: IEC 60947
Sub-type: XT1
Terminal Connection Type: Fixed Circuit-Breakers
Front
Version: F
Classifications
ETIM 4: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification Code: Q
UNSPSC: 39120000
XT2N 160 Ekip LS/I In=100A 3p F F
General Information
Extended Product Type: XT2N 160 Ekip LS/I In=100A 3p F F
Product ID: 1SDA067057R1
EAN: 8015644007942
Catalog Description: XT2N 160 Ekip LS/I In=100A 3p F F
Long Description: C.BREAKER TMAX XT2N 160 FIXED THREE-POLE WITH FRONT TERMINALS AND
SOLID-STATE RELEASE IN AC EKIP-LS/I R 100 A
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Moulded Case Circuit Breakers » Tmax XT
Ordering
EAN: 8015644007942
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 90 mm
Product Net Height: 130 mm
Product Net Depth: 82.5 mm
Product Net Weight: 1.2 kg
Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 130 mm
Package Level 1 Height: 208 mm
Package Level 1 Length: 145 mm
Package Level 1 Gross Weight: 1.2 kg
Package Level 1 EAN: 8015644007942
Additional Information
Circuit Breaker Type to be Power distribution
Associated:
Electrical Durability: 120 cycles per hour
8000 cycle
Mechanical Durability: Nr. Operations 240 cycles per hour
Nr. Operations 25000 cycle
Number of Poles: 3
Opening Time: CB with SOR 15 ms
CB with UVR 15 ms
Product Main Type: SACE Tmax XT
Product Name: Automatic Circuit Breaker
Product Type: CB
Rated Current (In): 100 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage 8 kV
(Uimp):
Rated Insulation Voltage (Ui): 1000 V
Rated Operational Voltage: 690 V AC
500 V DC
Rated Service Short-Circuit (220 V AC) 65 kA
Breaking Capacity (Ics): (220 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(690 V AC) 10 kA
Rated Ultimate Short-Circuit (220 V AC) 65 kA
Breaking Capacity (Icu): (230 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(690 V AC) 10 kA
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Release Type: EL
Standards: IEC 60947
Sub-type: XT2
Terminal Connection Type: Fixed Circuit-Breakers
Front
Version: F
Classifications
ETIM 4: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification Code: Q
UNSPSC: 39120000
XT2N 160 MA 160 Im=960…2240 3p F F
General Information
Extended Product Type: XT2N 160 MA 160 Im=960…2240 3p F F
Product ID: 1SDA076529R1
Catalog Description: XT2N 160 MA 160 Im=960…2240 3p F F
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Moulded Case Circuit Breakers » Tmax XT
Additional Information
Number of Poles: 3
Power Loss: at Rated Operating Conditions per Pole 16.15 W
Product Main Type: SACE Tmax XT
Product Type: CB
Rated Current (In): Main Circuit 160 A
Rated Impulse Withstand Voltage 8 kV
(Uimp):
Rated Operational Voltage: 690 V
Rated Service Short-Circuit (500 V AC) 30 kA
Breaking Capacity (Ics): (380 V AC) 36 kA
(415 V AC) 36 kA
(220 V AC) 65 kA
(440 V AC) 36 kA
(690 V AC) 10 kA
Rated Ultimate Short-Circuit (230 V AC) 65 kA
Breaking Capacity (Icu): (220 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(250 V DC) 2 Poles in Series 36 kA
(500 V AC) 30 kA
(500 V DC) 3 Poles in Series 36 kA
(690 V AC) 10 kA
(440 V AC) 36 kA
Rated Uninterrupted Current (Iu): 160 A
Release Type: M
Standards: IEC 60947
Sub-type: XT2
Terminal Connection Type: Front
Version: F
XT2N 160 MA 80 Im=480...1120 3p F F
General Information
Extended Product Type: XT2N 160 MA 80 Im=480...1120 3p F F
Product ID: 1SDA067052R1
EAN: 8015644009588
Catalog Description: XT2N 160 MA 80 Im=480...1120 3p F F
Long Description: C.BREAKER TMAX XT2N 160 FIXED THREE-POLE WITH FRONT TERMINALS AND
MAGNETIC RELEASE MA Iu 80 A I3=480...1120 A
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Moulded Case Circuit Breakers » Tmax XT
Ordering
EAN: 8015644009588
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 90 mm
Product Net Height: 130 mm
Product Net Depth: 82.5 mm
Product Net Weight: 1.2 kg
Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 130 mm
Package Level 1 Height: 208 mm
Package Level 1 Length: 145 mm
Package Level 1 Gross Weight: 1.2 kg
Package Level 1 EAN: 8015644009588
Additional Information
Circuit Breaker Type to be Motor protection
Associated:
Electrical Durability: 120 cycles per hour
8000 cycle
Mechanical Durability: Nr. Operations 240 cycles per hour
Nr. Operations 25000 cycle
Number of Poles: 3
Opening Time: CB with SOR 15 ms
CB with UVR 15 ms
Power Loss: at Rated Operating Conditions per Pole 5.8 W
Product Main Type: SACE Tmax XT
Product Name: Automatic Circuit Breaker
Product Type: CB
Rated Current (In): 80 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage 8 kV
(Uimp):
Rated Insulation Voltage (Ui): 1000 V
Rated Operational Voltage: 690 V AC
500 V DC
Rated Service Short-Circuit (220 V AC) 65 kA
Breaking Capacity (Ics): (220 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(690 V AC) 10 kA
Rated Ultimate Short-Circuit (220 V AC) 65 kA
Breaking Capacity (Icu): (230 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(690 V AC) 10 kA
(250 V DC) 2 Poles in Series 36 kA
(500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Release Type: M
Standards: IEC 60947
Sub-type: XT2
Terminal Connection Type: Fixed Circuit-Breakers
Front
Version: F
Classifications
ETIM 4: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification Code: Q
UNSPSC: 39120000
XT2N 160 TMA 125-1250 3p F F
General Information
Extended Product Type: XT2N 160 TMA 125-1250 3p F F
Product ID: 1SDA067019R1
EAN: 8015644009250
Catalog Description: XT2N 160 TMA 125-1250 3p F F
Long Description: C.BREAKER TMAX XT2N 160 FIXED THREE-POLE WITH FRONT TERMINALS AND
THERMOMAGNETIC RELEASE TMA R 125 I3=625...1250 A
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Moulded Case Circuit Breakers » Tmax XT
Ordering
EAN: 8015644009250
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 90 mm
Product Net Height: 130 mm
Product Net Depth: 82.5 mm
Product Net Weight: 1.2 kg
Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 130 mm
Package Level 1 Height: 208 mm
Package Level 1 Length: 145 mm
Package Level 1 Gross Weight: 1.2 kg
Package Level 1 EAN: 8015644009250
Additional Information
Circuit Breaker Type to be Power distribution
Associated:
Electrical Durability: 120 cycles per hour
8000 cycle
Mechanical Durability: Nr. Operations 240 cycles per hour
Nr. Operations 25000 cycle
Number of Poles: 3
Opening Time: CB with SOR 15 ms
CB with UVR 15 ms
Power Loss: at Rated Operating Conditions per Pole 11.4 W
Product Main Type: SACE Tmax XT
Product Name: Automatic Circuit Breaker
Product Type: CB
Rated Current (In): 125 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage 8 kV
(Uimp):
Rated Insulation Voltage (Ui): 1000 V
Rated Operational Voltage: 690 V AC
500 V DC
Rated Service Short-Circuit (220 V AC) 65 kA
Breaking Capacity (Ics): (220 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(690 V AC) 10 kA
Rated Ultimate Short-Circuit (220 V AC) 65 kA
Breaking Capacity (Icu): (230 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(690 V AC) 10 kA
(250 V DC) 2 Poles in Series 36 kA
(500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Release Type: TM
Standards: IEC 60947
Sub-type: XT2
Terminal Connection Type: Fixed Circuit-Breakers
Front
Version: F
Classifications
ETIM 4: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification Code: Q
UNSPSC: 39120000
XT2N 160 TMA 160-1600 3p F F
General Information
Extended Product Type: XT2N 160 TMA 160-1600 3p F F
Product ID: 1SDA067020R1
EAN: 8015644009267
Catalog Description: XT2N 160 TMA 160-1600 3p F F
Long Description: C.BREAKER TMAX XT2N 160 FIXED THREE-POLE WITH FRONT TERMINALS AND
THERMOMAGNETIC RELEASE TMA R 160 I3=800...1600 A
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Moulded Case Circuit Breakers » Tmax XT
Ordering
EAN: 8015644009267
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 90 mm
Product Net Height: 130 mm
Product Net Depth: 82.5 mm
Product Net Weight: 1.2 kg
Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 130 mm
Package Level 1 Height: 208 mm
Package Level 1 Length: 145 mm
Package Level 1 Gross Weight: 1.2 kg
Package Level 1 EAN: 8015644009267
Additional Information
Circuit Breaker Type to be Power distribution
Associated:
Electrical Durability: 120 cycles per hour
8000 cycle
Mechanical Durability: Nr. Operations 240 cycles per hour
Nr. Operations 25000 cycle
Number of Poles: 3
Opening Time: CB with SOR 15 ms
CB with UVR 15 ms
Power Loss: at Rated Operating Conditions per Pole 16.15 W
Product Main Type: SACE Tmax XT
Product Name: Automatic Circuit Breaker
Product Type: CB
Rated Current (In): 160 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage 8 kV
(Uimp):
Rated Insulation Voltage (Ui): 1000 V
Rated Operational Voltage: 690 V AC
500 V DC
Rated Service Short-Circuit (220 V AC) 65 kA
Breaking Capacity (Ics): (220 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(690 V AC) 10 kA
Rated Ultimate Short-Circuit (220 V AC) 65 kA
Breaking Capacity (Icu): (230 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(690 V AC) 10 kA
(250 V DC) 2 Poles in Series 36 kA
(500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Release Type: TM
Standards: IEC 60947
Sub-type: XT2
Terminal Connection Type: Fixed Circuit-Breakers
Front
Version: F
Classifications
ETIM 4: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification Code: Q
UNSPSC: 39120000
XT4N 250 Ekip LS/I In=250A 3p F F
General Information
Extended Product Type: XT4N 250 Ekip LS/I In=250A 3p F F
Product ID: 1SDA068126R1
EAN: 8015644020231
Catalog Description: XT4N 250 Ekip LS/I In=250A 3p F F
Long Description: C.BREAKER TMAX XT4N 250 FIXED THREE-POLE WITH FRONT TERMINALS AND
SOLID-STATE RELEASE IN AC EKIP-LS/I R 250 A
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Moulded Case Circuit Breakers » Tmax XT
Ordering
EAN: 8015644020231
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 105 mm
Product Net Height: 160 mm
Product Net Depth: 82.5 mm
Product Net Weight: 2.5 kg
Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 145 mm
Package Level 1 Height: 210 mm
Package Level 1 Length: 168 mm
Package Level 1 Gross Weight: 2.5 kg
Package Level 1 EAN: 8015644020231
Additional Information
Circuit Breaker Type to be Power distribution
Associated:
Electrical Durability: 120 cycles per hour
8000 cycle
Mechanical Durability: Nr. Operations 240 cycles per hour
Nr. Operations 25000 cycle
Number of Poles: 3
Opening Time: CB with SOR 15 ms
CB with UVR 15 ms
Product Main Type: SACE Tmax XT
Product Name: Automatic Circuit Breaker
Product Type: CB
Rated Current (In): 250 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage 8 kV
(Uimp):
Rated Insulation Voltage (Ui): 1000 V
Rated Operational Voltage: 690 V AC
500 V DC
Rated Service Short-Circuit (220 V AC) 65 kA
Breaking Capacity (Ics): (220 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(690 V AC) 10 kA
Rated Ultimate Short-Circuit (220 V AC) 65 kA
Breaking Capacity (Icu): (230 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(690 V AC) 10 kA
Rated Uninterrupted Current (Iu): 250 A
Rated Voltage (Ur): 690 V
Release Type: EL
Standards: IEC 60947
Sub-type: XT4
Terminal Connection Type: Fixed Circuit-Breakers
Front
Version: F
Classifications
ETIM 4: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification Code: Q
UNSPSC: 39120000
S201-C10NA
General Information
Extended Product Type: S201-C10NA
Product ID: 2CDS251103R0104
EAN: 4016779531757
Catalog Description: Miniature Circuit Breaker - S200 - 2P - C - 10 A
Long Description: System pro M compact S200 miniature circuit breakers are current limiting. They have two
different tripping mechanisms, the delayed thermal tripping mechanism for overload
protection and the electromechanic tripping mechanism for short circuit protection. They are
available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P),
breaking capacities (up to 6 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs
of the product range S200 comply with IEC/EN 60898-1, IEC/EN 60947-2, UL1077 and CSA
22.2 No. 235, allowing the use for residential, commercial and industrial applications.
Bottom-fitting auxiliary contact can be mounted on S200 to save 50% space.
Categories
Products » Low Voltage Products and Systems » Modular DIN Rail Products » Miniature Circuit Breakers MCBs
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4016779531757
Dimensions
Product Net Depth: 69 mm
Product Net Height: 88 mm
Product Net Weight: 0.25 kg
Product Net Width: 35 mm
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 183 mm
Package Level 1 Height: 80 mm
Package Level 1 Gross Weight: 1.3 kg
Package Level 1 EAN: 4016779607575
Package Level 2 Units: 60 piece
Package Level 2 Width: 275 mm
Package Level 2 Length: 395 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 14.8 kg
Package Level 2 EAN: 4016779971485
Package Level 1 Units: 5 piece
Environmental
Ambient Air Temperature: Operation -25 ... +55 °C
Storage -40 ... +70 °C
Resistance to Shock acc. to IEC 25g / 2 shocks / 13 ms
60068-2-27:
Resistance to Vibrations acc. to IEC 5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In
60068-2-6:
Environmental Conditions: 28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Technical
Number of Poles: 2
Tripping Characteristic: C
Rated Current (In): 10 A
Rated Operational Voltage: acc. to IEC 60898-1 230 V AC
acc. to IEC 60947-2 440 V AC
Power Loss: 4.2 W
at Rated Operating Conditions per Pole 2.1 W
Rated Insulation Voltage (Ui): acc. to IEC/EN 60664-1 440 V
Operational Voltage: Maximum (Incl. Tolerance) 253 V AC
Minimum 12 V AC / 12 V DC
Rated Frequency (f): 50 Hz
60 Hz
Rated Short-Circuit Capacity (Icn): (AC) 6 kA
6 kA (DC) kA
Rated Ultimate Short-Circuit 10 kA
Breaking Capacity (Icu): 10 kA (DC) kA
Rated Service Short-Circuit 7.5 kA
Breaking Capacity (Ics):
Energy Limiting Class: 3
Overvoltage Category: III
Pollution Degree: 3
Rated Impulse Withstand Voltage 4 kV
(Uimp): (6.2 kV @ sea level)
(5.0 kV @ 2000 m)
Dielectric Test Voltage: 50 / 60 Hz, 1 min: 2 kV
Housing Material: Insulation Group II, RAL 7035
Actuator Type: Insulation group II, black, sealable
Contact Position Indication: Red ON / Green OFF
Degree of Protection: IP20
Remarks: IP40 in enclosure with cover
Electrical Endurance: 20000 AC cycle
Mechanical Endurance: 20000 cycle
Terminal Type: Screw Terminals
Screw Terminal Type: Failsafe Bi-directional Cylinder-lift Terminal
Connecting Capacity: Busbar 10 / 10 mm²
Flexible with Ferrule 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Rigid 0.75 ... 35 mm²
Stranded 0.75 ... 35 mm²
Tightening Torque: 2.8 N·m
Recommended Screw Driver: Pozidriv 2
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting Position: Any
Standards: IEC/EN 60898-1
IEC/EN 60947-2
UL 1077
Technical UL/CSA
Connecting Capacity UL/CSA: Busbar 18 ... 8 AWG
Conductor 18 ... 4 AWG
Tightening Torque UL/CSA: 25 in·lb
Interrupting Rating acc. to UL1077: 6 kA
(DC) 10 kA
Maximum Operating Voltage 277 V AC
UL/CSA:
Classifications
ETIM 4: EC000042 - Miniature circuit breaker (MCB)
ETIM 5: EC000042 - Miniature circuit breaker (MCB)
ETIM 6: EC000042 - Miniature circuit breaker (MCB)
eClass: 7.0 27141901
UNSPSC: 39121614
Object Classification Code: F
Categories
Products » Low Voltage Products and Systems » Modular DIN Rail Products » Miniature Circuit Breakers MCBs
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4016779531726
Dimensions
Product Net Depth: 69 mm
Product Net Height: 88 mm
Product Net Weight: 0.25 kg
Product Net Width: 35 mm
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 183 mm
Package Level 1 Height: 80 mm
Package Level 1 Gross Weight: 1.3 kg
Package Level 1 EAN: 4016779607506
Package Level 2 Units: 60 piece
Package Level 2 Width: 275 mm
Package Level 2 Length: 395 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 14.8 kg
Package Level 2 EAN: 4016779971409
Package Level 1 Units: 5 piece
Environmental
Ambient Air Temperature: Operation -25 ... +55 °C
Storage -40 ... +70 °C
Resistance to Shock acc. to IEC 25g / 2 shocks / 13 ms
60068-2-27:
Resistance to Vibrations acc. to IEC 5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In
60068-2-6:
Environmental Conditions: 28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Technical
Number of Poles: 2
Tripping Characteristic: C
Rated Current (In): 4A
Rated Operational Voltage: acc. to IEC 60898-1 230 V AC
acc. to IEC 60947-2 440 V AC
Power Loss: 3.6 W
at Rated Operating Conditions per Pole 1.8 W
Rated Insulation Voltage (Ui): acc. to IEC/EN 60664-1 440 V
Operational Voltage: Maximum (Incl. Tolerance) 253 V AC
Minimum 12 V AC / 12 V DC
Rated Frequency (f): 50 Hz
60 Hz
Rated Short-Circuit Capacity (Icn): (AC) 6 kA
6 kA (DC) kA
Rated Ultimate Short-Circuit 10 kA
Breaking Capacity (Icu): 10 kA (DC) kA
Rated Service Short-Circuit 7.5 kA
Breaking Capacity (Ics):
Energy Limiting Class: 3
Overvoltage Category: III
Pollution Degree: 3
Rated Impulse Withstand Voltage 4 kV
(Uimp): (6.2 kV @ sea level)
(5.0 kV @ 2000 m)
Dielectric Test Voltage: 50 / 60 Hz, 1 min: 2 kV
Housing Material: Insulation Group II, RAL 7035
Actuator Type: Insulation group II, black, sealable
Contact Position Indication: Red ON / Green OFF
Degree of Protection: IP20
Remarks: IP40 in enclosure with cover
Electrical Endurance: 20000 AC cycle
Mechanical Endurance: 20000 cycle
Terminal Type: Screw Terminals
Screw Terminal Type: Failsafe Bi-directional Cylinder-lift Terminal
Connecting Capacity: Busbar 10 / 10 mm²
Flexible with Ferrule 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Rigid 0.75 ... 35 mm²
Stranded 0.75 ... 35 mm²
Tightening Torque: 2.8 N·m
Recommended Screw Driver: Pozidriv 2
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting Position: Any
Standards: IEC/EN 60898-1
IEC/EN 60947-2
UL 1077
Technical UL/CSA
Connecting Capacity UL/CSA: Busbar 18-8 AWG
Conductor 18-4 AWG
Tightening Torque UL/CSA: 25 in·lb
Interrupting Rating acc. to UL1077: 6 kA
(DC) 10 kA
Maximum Operating Voltage 277 V AC
UL/CSA:
Classifications
ETIM 4: EC000042 - Miniature circuit breaker (MCB)
ETIM 5: EC000042 - Miniature circuit breaker (MCB)
ETIM 6: EC000042 - Miniature circuit breaker (MCB)
eClass: 7.0 27141901
UNSPSC: 39121614
Object Classification Code: F
Categories
Products » Low Voltage Products and Systems » Modular DIN Rail Products » Miniature Circuit Breakers MCBs
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4016779550437
Dimensions
Product Net Depth: 69 mm
Product Net Height: 88 mm
Product Net Weight: 0.375 kg
Product Net Width: 52.5 mm
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 58 mm
Package Level 1 Height: 80 mm
Package Level 1 Gross Weight: 0.4 kg
Package Level 1 EAN: 4016779605922
Package Level 2 Units: 36 piece
Package Level 2 Width: 275 mm
Package Level 2 Length: 400 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 9.94 kg
Package Level 2 EAN: 4016779978071
Package Level 1 Units: 1 piece
Environmental
Ambient Air Temperature: Operation -25 ... +55 °C
Storage -40 ... +70 °C
Resistance to Shock acc. to IEC 25g / 2 shocks / 13 ms
60068-2-27:
Resistance to Vibrations acc. to IEC 5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In
60068-2-6:
Environmental Conditions: 28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Technical
Number of Poles: 3
Tripping Characteristic: C
Rated Current (In): 10 A
Rated Operational Voltage: acc. to IEC 60898-1 400 V AC
acc. to IEC 60947-2 440 V AC
Power Loss: 6.3 W
at Rated Operating Conditions per Pole 2.1 W
Rated Insulation Voltage (Ui): acc. to IEC/EN 60664-1 440 V
Operational Voltage: Maximum (Incl. Tolerance) 440 V AC
Minimum 12 V AC / 12 V DC
Rated Frequency (f): 50 Hz
60 Hz
Rated Short-Circuit Capacity (Icn): 10 kA (AC) kA
Rated Ultimate Short-Circuit 15 kA
Breaking Capacity (Icu): 15 kA (DC) kA
Rated Service Short-Circuit 11.25 kA
Breaking Capacity (Ics):
Energy Limiting Class: 3
Overvoltage Category: III
Pollution Degree: 3
Rated Impulse Withstand Voltage 4 kV
(Uimp): (6.2 kV @ sea level)
(5.0 kV @ 2000 m)
Dielectric Test Voltage: 50 / 60 Hz, 1 min: 2 kV
Housing Material: Insulation Group II, RAL 7035
Actuator Type: Insulation group II, black, sealable
Contact Position Indication: Red ON / Green OFF
Degree of Protection: IP20
Remarks: IP40 in enclosure with cover
Electrical Endurance: 20000 AC cycle
Mechanical Endurance: 20000 cycle
Terminal Type: Screw Terminals
Screw Terminal Type: Failsafe Bi-directional Cylinder-lift Terminal
Connecting Capacity: Busbar 10 / 10 mm²
Flexible with Ferrule 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Rigid 0.75 ... 35 mm²
Stranded 0.75 ... 35 mm²
Tightening Torque: 2 N·m
Recommended Screw Driver: Pozidriv 2
Mounting on DIN Rail: TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting Position: Any
Standards: IEC/EN 60898-1
IEC/EN 60947-2
Technical UL/CSA
Connecting Capacity UL/CSA: Busbar 14-8 AWG
Conductor 14-4 AWG
Tightening Torque UL/CSA: 18 in·lb
Interrupting Rating acc. to UL1077: 6 kA
(DC) 10 kA
Maximum Operating Voltage 480Y / 277 V AC
UL/CSA:
Classifications
E-nummer: 2101242
ETIM 4: EC000042 - Miniature circuit breaker (MCB)
ETIM 5: EC000042 - Miniature circuit breaker (MCB)
ETIM 6: EC000042 - Miniature circuit breaker (MCB)
eClass: 7.0 27141901
UNSPSC: 39121614
Object Classification Code: F
Categories
Products » Low Voltage Products and Systems » Modular DIN Rail Products » Miniature Circuit Breakers MCBs
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4016779550468
Dimensions
Product Net Depth: 69 mm
Product Net Height: 88 mm
Product Net Weight: 0.375 kg
Product Net Width: 52.5 mm
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 58 mm
Package Level 1 Height: 80 mm
Package Level 1 Gross Weight: 0.4 kg
Package Level 1 EAN: 4016779605984
Package Level 2 Units: 36 piece
Package Level 2 Width: 275 mm
Package Level 2 Length: 400 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 9.94 kg
Package Level 2 EAN: 4016779978187
Package Level 1 Units: 1 piece
Environmental
Ambient Air Temperature: Operation -25 ... +55 °C
Storage -40 ... +70 °C
Resistance to Shock acc. to IEC 25g / 2 shocks / 13 ms
60068-2-27:
Resistance to Vibrations acc. to IEC 5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In
60068-2-6:
Environmental Conditions: 28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Technical
Number of Poles: 3
Tripping Characteristic: C
Rated Current (In): 20 A
Rated Operational Voltage: acc. to IEC 60898-1 400 V AC
acc. to IEC 60947-2 440 V AC
Power Loss: 7.5 W
at Rated Operating Conditions per Pole 2.5 W
Rated Insulation Voltage (Ui): acc. to IEC/EN 60664-1 440 V
Operational Voltage: Maximum (Incl. Tolerance) 440 V AC
Minimum 12 V AC / 12 V DC
Rated Frequency (f): 50 Hz
60 Hz
Rated Short-Circuit Capacity (Icn): 10 kA (AC) kA
Rated Ultimate Short-Circuit 15 kA
Breaking Capacity (Icu): 15 kA (DC) kA
Rated Service Short-Circuit 11.25 kA
Breaking Capacity (Ics):
Energy Limiting Class: 3
Overvoltage Category: III
Pollution Degree: 3
Rated Impulse Withstand Voltage 4 kV
(Uimp): (6.2 kV @ sea level)
(5.0 kV @ 2000 m)
Dielectric Test Voltage: 50 / 60 Hz, 1 min: 2 kV
Housing Material: Insulation Group II, RAL 7035
Actuator Type: Insulation group II, black, sealable
Contact Position Indication: Red ON / Green OFF
Degree of Protection: IP20
Remarks: IP40 in enclosure with cover
Electrical Endurance: 20000 AC cycle
Mechanical Endurance: 20000 cycle
Terminal Type: Screw Terminals
Screw Terminal Type: Failsafe Bi-directional Cylinder-lift Terminal
Connecting Capacity: Busbar 10 / 10 mm²
Flexible with Ferrule 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Rigid 0.75 ... 35 mm²
Stranded 0.75 ... 35 mm²
Tightening Torque: 2 N·m
Recommended Screw Driver: Pozidriv 2
Mounting on DIN Rail: TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting Position: Any
Standards: IEC/EN 60898-1
IEC/EN 60947-2
Technical UL/CSA
Connecting Capacity UL/CSA: Busbar 14-8 AWG
Conductor 14-4 AWG
Tightening Torque UL/CSA: 18 in·lb
Interrupting Rating acc. to UL1077: 6 kA
(DC) 10 kA
Maximum Operating Voltage 480Y / 277 V AC
UL/CSA:
Classifications
E-nummer: 2101245
ETIM 4: EC000042 - Miniature circuit breaker (MCB)
ETIM 5: EC000042 - Miniature circuit breaker (MCB)
ETIM 6: EC000042 - Miniature circuit breaker (MCB)
eClass: 7.0 27141901
UNSPSC: 39121614
Object Classification Code: F
Categories
Products » Low Voltage Products and Systems » Modular DIN Rail Products » Miniature Circuit Breakers MCBs
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4016779550482
Dimensions
Product Net Depth: 69 mm
Product Net Height: 88 mm
Product Net Weight: 0.375 kg
Product Net Width: 52.5 mm
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 58 mm
Package Level 1 Height: 80 mm
Package Level 1 Gross Weight: 0.4 kg
Package Level 1 EAN: 4016779606028
Package Level 2 Units: 36 piece
Package Level 2 Width: 275 mm
Package Level 2 Length: 400 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 9.94 kg
Package Level 2 EAN: 4016779978323
Package Level 1 Units: 1 piece
Environmental
Ambient Air Temperature: Operation -25 ... +55 °C
Storage -40 ... +70 °C
Resistance to Shock acc. to IEC 25g / 2 shocks / 13 ms
60068-2-27:
Resistance to Vibrations acc. to IEC 5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In
60068-2-6:
Environmental Conditions: 28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Technical
Number of Poles: 3
Tripping Characteristic: C
Rated Current (In): 32 A
Rated Operational Voltage: acc. to IEC 60898-1 400 V AC
acc. to IEC 60947-2 440 V AC
Power Loss: 11.1 W
at Rated Operating Conditions per Pole 3.7 W
Rated Insulation Voltage (Ui): acc. to IEC/EN 60664-1 440 V
Operational Voltage: Maximum (Incl. Tolerance) 440 V AC
Minimum 12 V AC / 12 V DC
Rated Frequency (f): 50 Hz
60 Hz
Rated Short-Circuit Capacity (Icn): 10 kA (AC) kA
Rated Ultimate Short-Circuit 15 kA
Breaking Capacity (Icu): 15 kA (DC) kA
Rated Service Short-Circuit 11.25 kA
Breaking Capacity (Ics):
Energy Limiting Class: 3
Overvoltage Category: III
Pollution Degree: 3
Rated Impulse Withstand Voltage 4 kV
(Uimp): (6.2 kV @ sea level)
(5.0 kV @ 2000 m)
Dielectric Test Voltage: 50 / 60 Hz, 1 min: 2 kV
Housing Material: Insulation Group II, RAL 7035
Actuator Type: Insulation group II, black, sealable
Contact Position Indication: Red ON / Green OFF
Degree of Protection: IP20
Remarks: IP40 in enclosure with cover
Electrical Endurance: 10000 AC cycle
Mechanical Endurance: 20000 cycle
Terminal Type: Screw Terminals
Screw Terminal Type: Failsafe Bi-directional Cylinder-lift Terminal
Connecting Capacity: Busbar 10 / 10 mm²
Flexible with Ferrule 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Rigid 0.75 ... 35 mm²
Stranded 0.75 ... 35 mm²
Tightening Torque: 2 N·m
Recommended Screw Driver: Pozidriv 2
Mounting on DIN Rail: TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting Position: Any
Standards: IEC/EN 60898-1
IEC/EN 60947-2
Technical UL/CSA
Connecting Capacity UL/CSA: Busbar 14-8 AWG
Conductor 14-4 AWG
Tightening Torque UL/CSA: 18 in·lb
Interrupting Rating acc. to UL1077: 6 kA
(DC) 10 kA
Maximum Operating Voltage 480Y / 277 V AC
UL/CSA:
Classifications
E-nummer: 2101247
ETIM 4: EC000042 - Miniature circuit breaker (MCB)
ETIM 5: EC000042 - Miniature circuit breaker (MCB)
ETIM 6: EC000042 - Miniature circuit breaker (MCB)
eClass: 7.0 27141901
UNSPSC: 39121614
Object Classification Code: F
Categories
Products » Low Voltage Products and Systems » Modular DIN Rail Products » Miniature Circuit Breakers MCBs
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
EAN: 4016779544009
Dimensions
Product Net Depth: 69 mm
Product Net Height: 88 mm
Product Net Weight: 0.375 kg
Product Net Width: 52.5 mm
Container Information
Package Level 1 Width: 92 mm
Package Level 1 Length: 58 mm
Package Level 1 Height: 80 mm
Package Level 1 Gross Weight: 0.4 kg
Package Level 1 EAN: 4016779606080
Package Level 2 Units: 36 piece
Package Level 2 Width: 275 mm
Package Level 2 Length: 400 mm
Package Level 2 Height: 210 mm
Package Level 2 Gross Weight: 9.94 kg
Package Level 2 EAN: 4016779978644
Package Level 1 Units: 1 piece
Environmental
Ambient Air Temperature: Operation -25 ... +55 °C
Storage -40 ... +70 °C
Resistance to Shock acc. to IEC 25g / 2 shocks / 13 ms
60068-2-27:
Resistance to Vibrations acc. to IEC 5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In
60068-2-6:
Environmental Conditions: 28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Technical
Number of Poles: 3
Tripping Characteristic: C
Rated Current (In): 63 A
Rated Operational Voltage: acc. to IEC 60898-1 400 V AC
acc. to IEC 60947-2 440 V AC
Power Loss: 14.4 W
at Rated Operating Conditions per Pole 4.8 W
Rated Insulation Voltage (Ui): acc. to IEC/EN 60664-1 440 V
Operational Voltage: Maximum (Incl. Tolerance) 440 V AC
Minimum 12 V AC / 12 V DC
Rated Frequency (f): 50 Hz
60 Hz
Rated Short-Circuit Capacity (Icn): 10 kA (AC) kA
Rated Ultimate Short-Circuit 15 kA
Breaking Capacity (Icu): 15 kA (DC) kA
Rated Service Short-Circuit 7.5 kA
Breaking Capacity (Ics):
Energy Limiting Class: 3
Overvoltage Category: III
Pollution Degree: 3
Rated Impulse Withstand Voltage 4 kV
(Uimp): (6.2 kV @ sea level)
(5.0 kV @ 2000 m)
Dielectric Test Voltage: 50 / 60 Hz, 1 min: 2 kV
Housing Material: Insulation Group II, RAL 7035
Actuator Type: Insulation group II, black, sealable
Contact Position Indication: Red ON / Green OFF
Degree of Protection: IP20
Remarks: IP40 in enclosure with cover
Electrical Endurance: 10000 AC cycle
Mechanical Endurance: 20000 cycle
Terminal Type: Screw Terminals
Screw Terminal Type: Failsafe Bi-directional Cylinder-lift Terminal
Connecting Capacity: Busbar 10 / 10 mm²
Flexible with Ferrule 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Rigid 0.75 ... 35 mm²
Stranded 0.75 ... 35 mm²
Tightening Torque: 2 N·m
Recommended Screw Driver: Pozidriv 2
Mounting on DIN Rail: TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting Position: Any
Standards: IEC/EN 60898-1
IEC/EN 60947-2
Technical UL/CSA
Connecting Capacity UL/CSA: Busbar 14-8 AWG
Conductor 14-4 AWG
Tightening Torque UL/CSA: 18 in·lb
Interrupting Rating acc. to UL1077: 6 kA
(DC) 10 kA
Maximum Operating Voltage 480Y / 277 V AC
UL/CSA:
Classifications
E-nummer: 2101250
ETIM 4: EC000042 - Miniature circuit breaker (MCB)
ETIM 5: EC000042 - Miniature circuit breaker (MCB)
ETIM 6: EC000042 - Miniature circuit breaker (MCB)
eClass: 7.0 27141901
UNSPSC: 39121614
Object Classification Code: F
Categories
Products » Low Voltage Products and Systems » Modular DIN Rail Products » Miniature Circuit Breakers MCBs Accessories
» Auxiliary / Signal Contacts
Ordering
EAN: 4016779563826
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85365080
Dimensions
Product Net Width: 8.8 mm
Product Net Height: 85 mm
Product Net Depth: 69 mm
Product Net Weight: 0.043 kg
Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 20 mm
Package Level 1 Height: 115 mm
Package Level 1 Length: 104 mm
Package Level 1 Gross Weight: 0.045 kg
Package Level 1 EAN: 4016779678865
Package Level 2 Units: 60 piece
Package Level 2 Width: 820 mm
Package Level 2 Height: 560 mm
Package Level 2 Length: 1200 mm
Package Level 2 Gross Weight: 7 kg
Package Level 2 EAN: 4016779946193
Environmental
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Additional Information
Accessory Type: Auxiliary Contact
Function: Auxiliary Contact
Power Loss: 0,5 W
Product Main Type: S2C
Product Name: Auxiliary Contact
RoHS Date: 0335
Standards: UL 1077
GB14048.5
CSA Class 3215-30
CSA Class 3215-90
IEC/EN 60947-5-1
Suitable For: S200
S200M
S200P
S200S
SN201L
SN201
SN201M
F200
DS201
DS202C
DS200
Suitable for Product Class: Miniature Circuit Breaker
Residual Current Device
Technical Information: AUXILIARYCONTACT
Classifications
eClass: 7.0 27143502
E-nummer: 2102500
ETIM 4: EC001286 - Auxiliary contact unit for distribution board
ETIM 5: EC001286 - Auxiliary contact unit for distribution board
ETIM 6: EC001286 - Auxiliary contact unit for distribution board
AF09-30-01-11
General Information
Extended Product Type: AF09-30-01-11
Product ID: 1SBL137001R1101
EAN: 3471523110113
Catalog Description: AF09-30-01-11 24-60V50/60HZ 20-60VDC Contactor
Long Description: AF09 contactors are used for controlling power circuits up to 690 V AC and 220 V DC. They
are mainly used for controlling 3-phase motors, non-inductive or slightly inductive loads.
AF... contactors include an electronic coil interface accepting a wide control voltage Uc min.
... Uc max. Only four coils cover control voltages between 24...500 V 50/60 Hz or 20...500 V
DC. AF contactors can manage large control voltage variations. One coil can be used for
different control voltages used worldwide without any coil change. AF contactors have built-in
surge protection and do not require additional surge suppressors. The AF... series 1-stack
3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3
main poles, 1 built-in auxiliary contact, front and side-mounted add-on auxiliary contact
blocks (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1.
N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC or DC
operated - Accessories: a wide range of accessories is available. Note: AF..-30-..-11 not
suitable for a direct control by PLC-output. AF..-30-..-11 contactor type available in some
countries: please consult your ABB representative.
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85369085
EAN: 3471523110113
Dimensions
Product Net Depth: 77 mm
Product Net Height: 86 mm
Product Net Weight: 0.270 kg
Product Net Width: 45 mm
Container Information
Package Level 1 Width: 87 mm
Package Level 1 Length: 79 mm
Package Level 1 Height: 47 mm
Package Level 1 Gross Weight: 0.27 kg
Package Level 1 EAN: 3471523110113
Package Level 2 Units: 54 piece
Package Level 2 Width: 250 mm
Package Level 2 Length: 300 mm
Package Level 2 Height: 315 mm
Package Level 3 Units: 1296 piece
Package Level 1 Units: 1 piece
Technical
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 0
Number of Auxiliary Contacts NC: 1
Standards: IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14
Rated Operational Voltage: Auxiliary Circuit 690 V
Main Circuit 690 V
Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal acc. to IEC 60947-4-1, Open Contactors q = 40 °C 35 A
Current (Ith): acc. to IEC 60947-5-1, q = 40 °C 16 A
Rated Operational Current AC-1 (Ie): (690 V) 40 °C 25 A
(690 V) 60 °C 25 A
(690 V) 70 °C 22 A
Rated Operational Current AC-3 (Ie): (220 / 230 / 240 V) 60 °C 9 A
(380 / 400 V) 60 °C 9 A
(415 V) 60 °C 9 A
(440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
Rated Operational Power AC-3 (Pe): (220 / 230 / 240 V) 2.2 kW
(380 / 400 V) 4 kW
(415 V) 4 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
Rated Operational Current AC-15 (220 / 240 V) 4 A
(Ie): (24 / 127 V) 6 A
(400 / 440 V) 3 A
(500 V) 2 A
(690 V) 2 A
Rated Short-time Withstand Current at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A
(Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Maximum Electrical Switching AC-1 600 cycles per hour
Frequency: AC-15 1200 cycles per hour
AC-2 / AC-4 300 cycles per hour
AC-3 1200 cycles per hour
DC-13 900 cycles per hour
Rated Operational Current DC-13 (110 V) 0.55 A / 60 W
(Ie): (125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(24 V) 6 A / 144 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(48 V) 2.8 A / 134 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
(72 V) 1 A / 72 W
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage 6 kV
(Uimp):
Maximum Mechanical Switching 3600 cycles per hour
Frequency:
Rated Control Circuit Voltage (Uc): 50 Hz 24 ... 60 V
60 Hz 24 ... 60 V
DC Operation 20 ... 60 V
Operate Time: Between Coil De-energization and NC Contact Closing 13...98 ms
Between Coil De-energization and NO Contact Opening 11...95 ms
Between Coil Energization and NC Contact Opening 38...90 ms
Between Coil Energization and NO Contact Closing 40...95 ms
Connecting Capacity-Main Circuit: Flexible with Insulated Ferrule 1x 0.75...4 mm²
Flexible with Insulated Ferrule 2x 0.75...2.5 mm²
Flexible with Ferrule 1/2x 0.75...6 mm²
Rigid 1/2x 1...6 mm²
Connecting Capacity-Auxiliary Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Circuit: Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1...2.5 mm²
Connecting Capacity-Control Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75...2.5 mm²
Flexible with Insulated Ferrule 2x 0.75...1.5 mm²
Rigid 1/2x 1...2.5 mm²
Wire Stripping Length: Auxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 10 mm
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Terminal Type: Screw Terminals
Number of Main Contacts NO: 3
Environmental
Maximum Operating Altitude 3000 m
Permissible:
Resistance to Vibrations acc. to IEC 5...300 Hz 4 g closed position / 2 g open position
60068-2-6:
Resistance to Shock acc. to IEC Closed, Shock Direction: B1 25 g
60068-2-27: Open, Shock Direction: B1 5 g
Shock Direction: A 30 g
Shock Direction: B2 15 g
Shock Direction: C1 25 g
Shock Direction: C2 25 g
RoHS Status: Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2008 Q1
Ambient Air Temperature: Close to Contactor for Storage -60...+80 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Technical UL/CSA
General Use Rating UL/CSA: (600 V AC) 25 A
Horsepower Rating UL/CSA: (120 V AC) Single Phase 3/4 Hp
(240 V AC) Single Phase 1-1/2 Hp
(200 ... 208 V AC) Three Phase 2 Hp
(220 ... 240 V AC) Three Phase 2 Hp
(440 ... 480 V AC) Three Phase 5 Hp
(550 ... 600 V AC) Three Phase 7-1/2 Hp
Tightening Torque UL/CSA: Auxiliary Circuit 11 in·lb
Control Circuit 11 in·lb
Main Circuit 13 in·lb
Classifications
E-nummer: 3210015
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
Object Classification Code: Q
AF09-30-01-13
General Information
Extended Product Type: AF09-30-01-13
Product ID: 1SBL137001R1301
EAN: 3471523110137
Catalog Description: AF09-30-01-13 100-250V50/60HZ-DC Contactor
Long Description: AF09 contactors are used for controlling power circuits up to 690 V AC and 220 V DC. They
are mainly used for controlling 3-phase motors, non-inductive or slightly inductive loads.
AF... contactors include an electronic coil interface accepting a wide control voltage Uc min.
... Uc max. Only four coils cover control voltages between 24...500 V 50/60 Hz or 20...500 V
DC. AF contactors can manage large control voltage variations. One coil can be used for
different control voltages used worldwide without any coil change. AF contactors have built-in
surge protection and do not require additional surge suppressors. The AF... series 1-stack
3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3
main poles, 1 built-in auxiliary contact, front and side-mounted add-on auxiliary contact
blocks (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1.
N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC or DC
operated - Accessories: a wide range of accessories is available.
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85369085
EAN: 3471523110137
Dimensions
Product Net Depth: 77 mm
Product Net Height: 86 mm
Product Net Weight: 0.270 kg
Product Net Width: 45 mm
Container Information
Package Level 1 Width: 87 mm
Package Level 1 Length: 79 mm
Package Level 1 Height: 47 mm
Package Level 1 Gross Weight: 0.27 kg
Package Level 1 EAN: 3471523110137
Package Level 2 Units: 54 piece
Package Level 2 Width: 250 mm
Package Level 2 Length: 300 mm
Package Level 2 Height: 315 mm
Package Level 3 Units: 1296 piece
Package Level 1 Units: 1 piece
Technical
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 0
Number of Auxiliary Contacts NC: 1
Standards: IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14
Rated Operational Voltage: Auxiliary Circuit 690 V
Main Circuit 690 V
Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal acc. to IEC 60947-4-1, Open Contactors q = 40 °C 35 A
Current (Ith): acc. to IEC 60947-5-1, q = 40 °C 16 A
Rated Operational Current AC-1 (Ie): (690 V) 40 °C 25 A
(690 V) 60 °C 25 A
(690 V) 70 °C 22 A
Rated Operational Current AC-3 (Ie): (220 / 230 / 240 V) 60 °C 9 A
(380 / 400 V) 60 °C 9 A
(415 V) 60 °C 9 A
(440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
Rated Operational Power AC-3 (Pe): (220 / 230 / 240 V) 2.2 kW
(380 / 400 V) 4 kW
(415 V) 4 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
Rated Operational Current AC-15 (220 / 240 V) 4 A
(Ie): (24 / 127 V) 6 A
(400 / 440 V) 3 A
(500 V) 2 A
(690 V) 2 A
Rated Short-time Withstand Current at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A
(Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Maximum Electrical Switching AC-1 600 cycles per hour
Frequency: AC-15 1200 cycles per hour
AC-2 / AC-4 300 cycles per hour
AC-3 1200 cycles per hour
DC-13 900 cycles per hour
Rated Operational Current DC-13 (110 V) 0.55 A / 60 W
(Ie): (125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(24 V) 6 A / 144 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(48 V) 2.8 A / 134 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
(72 V) 1 A / 72 W
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage 6 kV
(Uimp):
Maximum Mechanical Switching 3600 cycles per hour
Frequency:
Rated Control Circuit Voltage (Uc): 50 Hz 100 ... 250 V
60 Hz 100 ... 250 V
DC Operation 100 ... 250 V
Operate Time: Between Coil De-energization and NC Contact Closing 13...98 ms
Between Coil De-energization and NO Contact Opening 11...95 ms
Between Coil Energization and NC Contact Opening 38...90 ms
Between Coil Energization and NO Contact Closing 40...95 ms
Connecting Capacity-Main Circuit: Flexible with Insulated Ferrule 1x 0.75...4 mm²
Flexible with Insulated Ferrule 2x 0.75...2.5 mm²
Flexible with Ferrule 1/2x 0.75...6 mm²
Rigid 1/2x 1...6 mm²
Connecting Capacity-Auxiliary Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Circuit: Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1...2.5 mm²
Connecting Capacity-Control Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75...2.5 mm²
Flexible with Insulated Ferrule 2x 0.75...1.5 mm²
Rigid 1/2x 1...2.5 mm²
Wire Stripping Length: Auxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 10 mm
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Terminal Type: Screw Terminals
Number of Main Contacts NO: 3
Environmental
Maximum Operating Altitude 3000 m
Permissible:
Resistance to Vibrations acc. to IEC 5...300 Hz 4 g closed position / 2 g open position
60068-2-6:
Resistance to Shock acc. to IEC Closed, Shock Direction: B1 25 g
60068-2-27: Open, Shock Direction: B1 5 g
Shock Direction: A 30 g
Shock Direction: B2 15 g
Shock Direction: C1 25 g
Shock Direction: C2 25 g
RoHS Status: Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2008 Q1
Ambient Air Temperature: Close to Contactor for Storage -60...+80 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Technical UL/CSA
General Use Rating UL/CSA: (600 V AC) 25 A
Horsepower Rating UL/CSA: (120 V AC) Single Phase 3/4 Hp
(240 V AC) Single Phase 1-1/2 Hp
(200 ... 208 V AC) Three Phase 2 Hp
(220 ... 240 V AC) Three Phase 2 Hp
(440 ... 480 V AC) Three Phase 5 Hp
(550 ... 600 V AC) Three Phase 7-1/2 Hp
Tightening Torque UL/CSA: Auxiliary Circuit 11 in·lb
Control Circuit 11 in·lb
Main Circuit 13 in·lb
Classifications
E-nummer: 3210010
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
UNSPSC: 39121529
Object Classification Code: Q
AF09-30-10-13
General Information
Extended Product Type: AF09-30-10-13
Product ID: 1SBL137001R1310
EAN: 3471523110038
Catalog Description: AF09-30-10-13 100-250V50/60HZ-DC Contactor
Long Description: AF09 contactors are used for controlling power circuits up to 690 V AC and 220 V DC. They
are mainly used for controlling 3-phase motors, non-inductive or slightly inductive loads.
AF... contactors include an electronic coil interface accepting a wide control voltage Uc min.
... Uc max. Only four coils cover control voltages between 24...500 V 50/60 Hz or 20...500 V
DC. AF contactors can manage large control voltage variations. One coil can be used for
different control voltages used worldwide without any coil change. AF contactors have built-in
surge protection and do not require additional surge suppressors. The AF... series 1-stack
3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3
main poles, 1 built-in auxiliary contact, front and side-mounted add-on auxiliary contact
blocks (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1.
N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC or DC
operated - Accessories: a wide range of accessories is available.
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85369085
EAN: 3471523110038
Dimensions
Product Net Depth: 77 mm
Product Net Height: 86 mm
Product Net Weight: 0.270 kg
Product Net Width: 45 mm
Container Information
Package Level 1 Width: 87 mm
Package Level 1 Length: 79 mm
Package Level 1 Height: 47 mm
Package Level 1 Gross Weight: 0.27 kg
Package Level 1 EAN: 3471523110038
Package Level 2 Units: 54 piece
Package Level 2 Width: 250 mm
Package Level 2 Length: 300 mm
Package Level 2 Height: 315 mm
Package Level 3 Units: 1296 piece
Package Level 1 Units: 1 piece
Technical
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 0
Standards: IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14
Rated Operational Voltage: Auxiliary Circuit 690 V
Main Circuit 690 V
Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal acc. to IEC 60947-4-1, Open Contactors q = 40 °C 35 A
Current (Ith): acc. to IEC 60947-5-1, q = 40 °C 16 A
Rated Operational Current AC-1 (Ie): (690 V) 40 °C 25 A
(690 V) 60 °C 25 A
(690 V) 70 °C 22 A
Rated Operational Current AC-3 (Ie): (220 / 230 / 240 V) 60 °C 9 A
(380 / 400 V) 60 °C 9 A
(415 V) 60 °C 9 A
(440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
Rated Operational Power AC-3 (Pe): (220 / 230 / 240 V) 2.2 kW
(380 / 400 V) 4 kW
(415 V) 4 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
Rated Operational Current AC-15 (220 / 240 V) 4 A
(Ie): (24 / 127 V) 6 A
(400 / 440 V) 3 A
(500 V) 2 A
(690 V) 2 A
Rated Short-time Withstand Current at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A
(Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Maximum Electrical Switching AC-1 600 cycles per hour
Frequency: AC-15 1200 cycles per hour
AC-2 / AC-4 300 cycles per hour
AC-3 1200 cycles per hour
DC-13 900 cycles per hour
Rated Operational Current DC-13 (110 V) 0.55 A / 60 W
(Ie): (125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(24 V) 6 A / 144 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(48 V) 2.8 A / 134 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
(72 V) 1 A / 72 W
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage 6 kV
(Uimp):
Maximum Mechanical Switching 3600 cycles per hour
Frequency:
Rated Control Circuit Voltage (Uc): 50 Hz 100 ... 250 V
60 Hz 100 ... 250 V
DC Operation 100 ... 250 V
Operate Time: Between Coil De-energization and NC Contact Closing 13...98 ms
Between Coil De-energization and NO Contact Opening 11...95 ms
Between Coil Energization and NC Contact Opening 38...90 ms
Between Coil Energization and NO Contact Closing 40...95 ms
Connecting Capacity-Main Circuit: Flexible with Insulated Ferrule 1x 0.75...4 mm²
Flexible with Insulated Ferrule 2x 0.75...2.5 mm²
Flexible with Ferrule 1/2x 0.75...6 mm²
Rigid 1/2x 1...6 mm²
Connecting Capacity-Auxiliary Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Circuit: Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1...2.5 mm²
Connecting Capacity-Control Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75...2.5 mm²
Flexible with Insulated Ferrule 2x 0.75...1.5 mm²
Rigid 1/2x 1...2.5 mm²
Wire Stripping Length: Auxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 10 mm
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Terminal Type: Screw Terminals
Number of Main Contacts NO: 3
Environmental
Maximum Operating Altitude 3000 m
Permissible:
Resistance to Vibrations acc. to IEC 5...300 Hz 4 g closed position / 2 g open position
60068-2-6:
Resistance to Shock acc. to IEC Closed, Shock Direction: B1 25 g
60068-2-27: Open, Shock Direction: B1 5 g
Shock Direction: A 30 g
Shock Direction: B2 15 g
Shock Direction: C1 25 g
Shock Direction: C2 25 g
RoHS Status: Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2008 Q1
Ambient Air Temperature: Close to Contactor for Storage -60...+80 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Technical UL/CSA
General Use Rating UL/CSA: (600 V AC) 25 A
Horsepower Rating UL/CSA: (120 V AC) Single Phase 3/4 Hp
(240 V AC) Single Phase 1-1/2 Hp
(200 ... 208 V AC) Three Phase 2 Hp
(220 ... 240 V AC) Three Phase 2 Hp
(440 ... 480 V AC) Three Phase 5 Hp
(550 ... 600 V AC) Three Phase 7-1/2 Hp
Tightening Torque UL/CSA: Auxiliary Circuit 11 in·lb
Control Circuit 11 in·lb
Main Circuit 13 in·lb
Classifications
E-nummer: 3210009
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
UNSPSC: 39121529
Object Classification Code: Q
AF09Z-30-01-21
General Information
Extended Product Type: AF09Z-30-01-21
Product ID: 1SBL136001R2101
EAN: 3471523113312
Catalog Description: AF09Z-30-01-21 24-60V50/60HZ 20-60VDC Contactor
Long Description: AF09Z contactors are used for controlling power circuits up to 690 V AC and 220 V DC.
They are mainly used for controlling 3-phase motors, non-inductive or slightly inductive
loads. AF..Z contactors include an electronic coil interface accepting a wide control voltage
Uc min. ... Uc max. Only four coils cover control voltages between 24...250 V 50/60 Hz or
12...250 V DC. AF..Z contactors can manage large control voltage variations. One coil can
be used for different control voltages used worldwide without any coil change. AF..Z
contactors allow direct control by PLC-output ≥ 24 V DC 500 mA and obtain a reduced
holding coil consumption. AF..Z contactors withstand short voltage dips and voltage sags
(SEMI F47-0706 compliance) between 24...250 V 50/60 Hz AF..Z contactors have built-in
surge protection and do not require additional surge suppressors The AF... series 1-stack 3-
pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3
main poles, 1 built-in auxiliary contact, front and side-mounted add-on auxiliary contact
blocks. (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1.
N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC or DC
operated - Accessories: a wide range of accessories is available.
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85369085
EAN: 3471523113312
Dimensions
Product Net Depth: 77 mm
Product Net Height: 86 mm
Product Net Weight: 0.310 kg
Product Net Width: 45 mm
Container Information
Package Level 1 Width: 87 mm
Package Level 1 Length: 79 mm
Package Level 1 Height: 47 mm
Package Level 1 Gross Weight: 0.31 kg
Package Level 1 EAN: 3471523113312
Package Level 2 Units: 54 piece
Package Level 2 Width: 250 mm
Package Level 2 Length: 300 mm
Package Level 2 Height: 315 mm
Package Level 3 Units: 1296 piece
Package Level 1 Units: 1 piece
Technical
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 0
Number of Auxiliary Contacts NC: 1
Standards: IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14
Rated Operational Voltage: Auxiliary Circuit 690 V
Main Circuit 690 V
Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal acc. to IEC 60947-4-1, Open Contactors q = 40 °C 35 A
Current (Ith): acc. to IEC 60947-5-1, q = 40 °C 16 A
Rated Operational Current AC-1 (Ie): (690 V) 40 °C 25 A
(690 V) 60 °C 25 A
(690 V) 70 °C 22 A
Rated Operational Current AC-3 (Ie): (220 / 230 / 240 V) 60 °C 9 A
(380 / 400 V) 60 °C 9 A
(415 V) 60 °C 9 A
(440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
Rated Operational Power AC-3 (Pe): (220 / 230 / 240 V) 2.2 kW
(380 / 400 V) 4 kW
(415 V) 4 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
Rated Operational Current AC-15 (220 / 240 V) 4 A
(Ie): (24 / 127 V) 6 A
(400 / 440 V) 3 A
(500 V) 2 A
(690 V) 2 A
Rated Short-time Withstand Current at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A
(Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Maximum Electrical Switching AC-1 600 cycles per hour
Frequency: AC-15 1200 cycles per hour
AC-2 / AC-4 300 cycles per hour
AC-3 1200 cycles per hour
DC-13 900 cycles per hour
Rated Operational Current DC-13 (110 V) 0.55 A / 60 W
(Ie): (125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(24 V) 6 A / 144 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(48 V) 2.8 A / 134 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
(72 V) 1 A / 72 W
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage 6 kV
(Uimp):
Maximum Mechanical Switching 3600 cycles per hour
Frequency:
Rated Control Circuit Voltage (Uc): 50 Hz 24 ... 60 V
60 Hz 24 ... 60 V
DC Operation 20 ... 60 V
Operate Time: Between Coil De-energization and NC Contact Closing 13...98 ms
Between Coil De-energization and NO Contact Opening 11...95 ms
Between Coil Energization and NC Contact Opening 38...90 ms
Between Coil Energization and NO Contact Closing 40...95 ms
Connecting Capacity-Main Circuit: Flexible with Insulated Ferrule 1x 0.75...4 mm²
Flexible with Insulated Ferrule 2x 0.75...2.5 mm²
Flexible with Ferrule 1/2x 0.75...6 mm²
Rigid 1/2x 1...6 mm²
Connecting Capacity-Auxiliary Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Circuit: Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1...2.5 mm²
Connecting Capacity-Control Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75...2.5 mm²
Flexible with Insulated Ferrule 2x 0.75...1.5 mm²
Rigid 1/2x 1...2.5 mm²
Wire Stripping Length: Auxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 10 mm
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Terminal Type: Screw Terminals
Number of Main Contacts NO: 3
Environmental
Maximum Operating Altitude 3000 m
Permissible:
Resistance to Vibrations acc. to IEC 5...300 Hz 4 g closed position / 2 g open position
60068-2-6:
Resistance to Shock acc. to IEC Closed, Shock Direction: B1 25 g
60068-2-27: Open, Shock Direction: B1 5 g
Shock Direction: A 30 g
Shock Direction: B2 15 g
Shock Direction: C1 25 g
Shock Direction: C2 25 g
RoHS Status: Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2008 Q1
Ambient Air Temperature: Close to Contactor for Storage -60...+80 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Technical UL/CSA
General Use Rating UL/CSA: (600 V AC) 25 A
Horsepower Rating UL/CSA: (120 V AC) Single Phase 3/4 Hp
(240 V AC) Single Phase 1-1/2 Hp
(200 ... 208 V AC) Three Phase 2 Hp
(220 ... 240 V AC) Three Phase 2 Hp
(440 ... 480 V AC) Three Phase 5 Hp
(550 ... 600 V AC) Three Phase 7-1/2 Hp
Tightening Torque UL/CSA: Auxiliary Circuit 11 in·lb
Control Circuit 11 in·lb
Main Circuit 13 in·lb
Classifications
E-nummer: 3210006
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
UNSPSC: 39121529
Object Classification Code: Q
AF116-30-11-13 100-250V 50/60Hz / DC
General Information
Extended Product Type: AF116-30-11-13 100-250V 50/60Hz / DC
Product ID: 1SFL427001R1311
EAN: 7320500476376
Catalog Description: AF116-30-11-13 Contactor
Long Description: A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-
pass and Distribution application up to max 690 V. Operated with wide control voltage range
100-250 V, 50/60 Hz and DC
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
EAN: 7320500476376
Dimensions
Product Net Depth: 126.0 mm
Product Net Height: 150.0 mm
Product Net Weight: 1.644 kg
Product Net Width: 90.0 mm
Container Information
Package Level 1 Width: 194 mm
Package Level 1 Length: 115 mm
Package Level 1 Height: 169 mm
Package Level 1 Gross Weight: 1.57 kg
Package Level 1 EAN: 7320500476376
Package Level 1 Units: 1 piece
Technical
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Rated Operational Voltage: Main Circuit 690 V
Rated Frequency (f): Main Circuit 50/60 Hz
Conventional Free-air Thermal acc. to IEC 60947-4-1, Open Contactors q = 40 °C 160 A
Current (Ith):
Rated Operational Current AC-1 (Ie): (690 V) 55 °C 145 A
(690 V) 40 °C 160 A
(690 V) 70 °C 130 A
Rated Operational Current AC-3 (Ie): (690 V) 55 °C 65 A
(415 V) 55 °C 116 A
(220 / 230 / 240 V) 55 °C 116 A
(440 V) 55 °C 116 A
(380 / 400 V) 55 °C 116 A
(500 V) 55 °C 110 A
Rated Operational Power AC-3 (Pe): (500 V) 75 kW
(220 / 230 / 240 V) 30 kW
(690 V) 55 kW
(380 / 400 V) 55 kW
(440 V) 75 kW
(415 V) 55 kW
Rated Breaking Capacity AC-3 acc. 8 x Ie AC-3
to IEC 60947-4-1:
Rated Making Capacity AC-3 acc. to 10 x Ie AC-3
IEC 60947-4-1:
Short-Circuit Protective Devices: gG Type Fuses 250 A
Rated Short-time Withstand Current at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 160 A
(Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 536 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 928 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1160 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 379 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2000 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1000 A
Maximum Electrical Switching AC-3 300 cycles per hour
Frequency: AC-1 300 cycles per hour
AC-2 / AC-4 150 cycles per hour
Rated Operational Current DC-1 (Ie): (110 V) 2 Poles in Series, 40 °C 145 A
(220 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Current DC-3 (Ie): (110 V) 2 Poles in Series, 40 °C 145 A
(220 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Current DC-5 (Ie): (110 V) 2 Poles in Series, 40 °C 145 A
(220 V) 3 Poles in Series, 40 °C 145 A
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage Main Circuit 8 kV
(Uimp):
Mechanical Durability: 5 million
Maximum Mechanical Switching 300 cycles per hour
Frequency:
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) °C
Rated Control Circuit Voltage (Uc): 60 Hz 100…250 V
50 Hz 100…250 V
DC Operation 100…250 V
Coil Consumption: Pull-in at Max. Rated Control Circuit Voltage 60 Hz 130 V·A
Holding at Max. Rated Control Circuit Voltage DC 3 W
Holding at Max. Rated Control Circuit Voltage 50 Hz 6 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 135 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 130 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 6 V·A
Operate Time: Between Coil Energization and NO Contact Closing 25…55 ms
Between Coil De-energization and NO Contact Opening 37…47 ms
Connecting Capacity Main Circuit: Flexible 2x10…70 mm²
Rigid Cu-Cable 2x10…95 mm²
Connecting Capacity Auxiliary Solid 2x1…4 mm²
Circuit: Flexible with Insulated Ferrule 1x0.75…2.5 mm²
Stranded 2x1…4 mm²
Flexible 2x0.75…2.5 mm²
Flexible with Ferrule 2x0.75…2.5 mm²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type: Double Clamp
Number of Main Contacts NO: 3
Environmental
Maximum Operating Altitude 3000 m
Permissible:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25…+50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40…+70 °C
Close to Contactor for Storage -40…+70 °C
Technical UL/CSA
General Use Rating UL/CSA: (600 V AC) 160 A
Horsepower Rating UL/CSA: (208 V AC) Three Phase 30 Hp
(440 ... 480 V AC) Three Phase 75 Hp
(550 ... 600 V AC) Three Phase 100 Hp
(220 ... 240 V AC) Three Phase 40 Hp
(200 V AC) Three Phase 30 Hp
Maximum Operating Voltage Main Circuit 600 V
UL/CSA:
Classifications
E-nummer: 3210068
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
UNSPSC: 39121529
Object Classification Code: Q
AF140-30-11-13 100-250V 50/60Hz / DC
General Information
Extended Product Type: AF140-30-11-13 100-250V 50/60Hz / DC
Product ID: 1SFL447001R1311
EAN: 7320500476949
Catalog Description: AF140-30-11-13 Contactor
Long Description: A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-
pass and Distribution application up to max 690 V. Operated with wide control voltage range
100-250 V, 50/60 Hz and DC
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
EAN: 7320500476949
Dimensions
Product Net Depth: 126.0 mm
Product Net Height: 150.0 mm
Product Net Weight: 1.644 kg
Product Net Width: 90.0 mm
Container Information
Package Level 1 Width: 194 mm
Package Level 1 Length: 115 mm
Package Level 1 Height: 169 mm
Package Level 1 Gross Weight: 1.57 kg
Package Level 1 EAN: 7320500476949
Package Level 1 Units: 1 piece
Technical
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Rated Operational Voltage: Main Circuit 690 V
Rated Frequency (f): Main Circuit 50/60 Hz
Conventional Free-air Thermal acc. to IEC 60947-4-1, Open Contactors q = 40 °C 200 A
Current (Ith):
Rated Operational Current AC-1 (Ie): (690 V) 55 °C 175 A
(690 V) 40 °C 200 A
(690 V) 70 °C 160 A
Rated Operational Current AC-3 (Ie): (690 V) 55 °C 80 A
(415 V) 55 °C 140 A
(220 / 230 / 240 V) 55 °C 140 A
(440 V) 55 °C 140 A
(380 / 400 V) 55 °C 140 A
(500 V) 55 °C 130 A
Rated Operational Power AC-3 (Pe): (500 V) 90 kW
(690 V) 75 kW
(220 / 230 / 240 V) 37 kW
(380 / 400 V) 75 kW
(440 V) 90 kW
(415 V) 75 kW
Rated Breaking Capacity AC-3 acc. 8 x Ie AC-3
to IEC 60947-4-1:
Rated Making Capacity AC-3 acc. to 10 x Ie AC-3
IEC 60947-4-1:
Short-Circuit Protective Devices: gG Type Fuses 315 A
Rated Short-time Withstand Current at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 200 A
(Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1500 A
Maximum Electrical Switching AC-3 300 cycles per hour
Frequency: AC-1 300 cycles per hour
AC-2 / AC-4 150 cycles per hour
Rated Operational Current DC-1 (Ie): (110 V) 2 Poles in Series, 40 °C 160 A
(220 V) 3 Poles in Series, 40 °C 160 A
Rated Operational Current DC-3 (Ie): (110 V) 2 Poles in Series, 40 °C 160 A
(220 V) 3 Poles in Series, 40 °C 160 A
Rated Operational Current DC-5 (Ie): (110 V) 2 Poles in Series, 40 °C 160 A
(220 V) 3 Poles in Series, 40 °C 160 A
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage Main Circuit 8 kV
(Uimp):
Mechanical Durability: 5 million
Maximum Mechanical Switching 300 cycles per hour
Frequency:
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) °C
Rated Control Circuit Voltage (Uc): 60 Hz 100…250 V
50 Hz 100…250 V
DC Operation 100…250 V
Coil Consumption: Pull-in at Max. Rated Control Circuit Voltage 60 Hz 130 V·A
Holding at Max. Rated Control Circuit Voltage DC 3 W
Holding at Max. Rated Control Circuit Voltage 50 Hz 6 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 135 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 130 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 6 V·A
Operate Time: Between Coil Energization and NO Contact Closing 25…55 ms
Between Coil De-energization and NO Contact Opening 37…47 ms
Connecting Capacity Main Circuit: Rigid Cu-Cable 2x10…95 mm²
Flexible 2x10…70 mm²
Connecting Capacity Auxiliary Solid 2x1…4 mm²
Circuit: Flexible with Insulated Ferrule 2x0.75…2.5 mm²
Stranded 2x1…4 mm²
Flexible 2x0.75…2.5 mm²
Flexible with Ferrule 2x0.75…2.5 mm²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type: Double Clamp
Number of Main Contacts NO: 3
Environmental
Maximum Operating Altitude 3000 m
Permissible:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25…+50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40…+70 °C
Close to Contactor for Storage -40…+70 °C
Technical UL/CSA
General Use Rating UL/CSA: (600 V AC) 200 A
Horsepower Rating UL/CSA: (208 V AC) Three Phase 40 Hp
(440 ... 480 V AC) Three Phase 100 Hp
(550 ... 600 V AC) Three Phase 125 Hp
(220 ... 240 V AC) Three Phase 50 Hp
(200 V AC) Three Phase 40 Hp
Maximum Operating Voltage Main Circuit 600 V
UL/CSA:
Classifications
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
UNSPSC: 39121529
Object Classification Code: Q
AF146-30-11-13 100-250V 50/60Hz / DC
General Information
Extended Product Type: AF146-30-11-13 100-250V 50/60Hz / DC
Product ID: 1SFL467001R1311
EAN: 7320500476994
Catalog Description: AF146-30-11-13 Contactor
Long Description: A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-
pass and Distribution application up to max 1000 V. Operated with wide control voltage
range 100-250 V, 50/60 Hz and DC
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
EAN: 7320500476994
Dimensions
Product Net Depth: 126.0 mm
Product Net Height: 150.0 mm
Product Net Weight: 1.644 kg
Product Net Width: 90.0 mm
Container Information
Package Level 1 Width: 194 mm
Package Level 1 Length: 115 mm
Package Level 1 Height: 169 mm
Package Level 1 Gross Weight: 1.57 kg
Package Level 1 EAN: 7320500476994
Package Level 1 Units: 1 piece
Technical
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Rated Operational Voltage: Main Circuit 1000 V
Rated Frequency (f): Main Circuit 50/60 Hz
Conventional Free-air Thermal acc. to IEC 60947-4-1, Open Contactors q = 40 °C 225 A
Current (Ith):
Rated Operational Current AC-1 (Ie): (690 V) 55 °C 200 A
(690 V) 40 °C 225 A
(1000 V) 40 °C 225 A
(1000 V) 55 °C 200 A
(690 V) 70 °C 175 A
(1000 V) 70 °C 175 A
Rated Operational Current AC-3 (Ie): (1000 V) 55 °C 60 A
(690 V) 55 °C 93 A
(415 V) 55 °C 146 A
(220 / 230 / 240 V) 55 °C 146 A
(440 V) 55 °C 146 A
(380 / 400 V) 55 °C 146 A
(500 V) 55 °C 93 A
Rated Operational Power AC-3 (Pe): (500 V) 55 kW
(1000 V) 75 kW
(690 V) 90 kW
(220 / 230 / 240 V) 45 kW
(380 / 400 V) 75 kW
(440 V) 90 kW
(415 V) 75 kW
Rated Breaking Capacity AC-3 acc. 8 x Ie AC-3
to IEC 60947-4-1:
Rated Making Capacity AC-3 acc. to 10 x Ie AC-3
IEC 60947-4-1:
Short-Circuit Protective Devices: gG Type Fuses 315 A
Rated Short-time Withstand Current at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 A
(Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 200 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1500 A
Maximum Electrical Switching AC-3 300 cycles per hour
Frequency: AC-1 300 cycles per hour
AC-2 / AC-4 150 cycles per hour
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Impulse Withstand Voltage Main Circuit 8 kV
(Uimp):
Mechanical Durability: 5 million
Maximum Mechanical Switching 300 cycles per hour
Frequency:
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) °C
Rated Control Circuit Voltage (Uc): 60 Hz 100…250 V
50 Hz 100…250 V
DC Operation 100…250 V
Coil Consumption: Pull-in at Max. Rated Control Circuit Voltage 60 Hz 130 V·A
Holding at Max. Rated Control Circuit Voltage DC 3 W
Holding at Max. Rated Control Circuit Voltage 50 Hz 6 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 135 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 130 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 6 V·A
Operate Time: Between Coil Energization and NO Contact Closing 25…55 ms
Between Coil De-energization and NO Contact Opening 37…47 ms
Connecting Capacity Main Circuit: Rigid Cu-Cable 1x10…95 mm²
Flexible 1x10…70 mm²
Connecting Capacity Auxiliary Solid 2x1…4 mm²
Circuit: Flexible with Insulated Ferrule 2x0.75…2.5 mm²
Stranded 1x1…4 mm²
Flexible 2x0.75…2.5 mm²
Flexible with Ferrule 2x0.75…2.5 mm²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type: Double Clamp
Number of Main Contacts NO: 3
Environmental
Maximum Operating Altitude 3000 m
Permissible:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25…+50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40…+70 °C
Close to Contactor for Storage -40…+70 °C
Technical UL/CSA
General Use Rating UL/CSA: (600 V AC) 200 A
Horsepower Rating UL/CSA: (208 V AC) Three Phase 40 Hp
(440 ... 480 V AC) Three Phase 100 Hp
(550 ... 600 V AC) Three Phase 125 Hp
(220 ... 240 V AC) Three Phase 50 Hp
(200 V AC) Three Phase 40 Hp
Maximum Operating Voltage Main Circuit 600 V
UL/CSA:
Classifications
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
UNSPSC: 39121529
Object Classification Code: Q
AF190-30-11-13 100-250V 50/60Hz / DC
General Information
Extended Product Type: AF190-30-11-13 100-250V 50/60Hz / DC
Product ID: 1SFL487002R1311
EAN: 7320500480434
Catalog Description: AF190-30-11-13 Contactor
Long Description: A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-
pass and Distribution application up to max 1000 V. Operated with wide control voltage
range 100-250 V, 50/60 Hz and DC
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
EAN: 7320500480434
Dimensions
Product Net Depth: 152.0 mm
Product Net Height: 196.0 mm
Product Net Weight: 2.778 kg
Product Net Width: 105.0 mm
Container Information
Package Level 1 Width: 223 mm
Package Level 1 Length: 133 mm
Package Level 1 Height: 186 mm
Package Level 1 Gross Weight: 3.228 kg
Package Level 1 EAN: 7320500480434
Package Level 1 Units: 1 piece
Technical
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Rated Operational Voltage: Main Circuit 1000 V
Rated Frequency (f): Main Circuit 50/60 Hz
Conventional Free-air Thermal acc. to IEC 60947-4-1, Open Contactors q = 40 °C 275 A
Current (Ith):
Rated Operational Current AC-1 (Ie): (690 V) 55 °C 250 A
(690 V) 40 °C 275 A
(1000 V) 40 °C 250 A
(1000 V) 55 °C 225 A
(690 V) 70 °C 200 A
(1000 V) 70 °C 185 A
Rated Operational Current AC-3 (Ie): (1000 V) 55 °C 85 A
(415 V) 55 °C 190 A
(690 V) 55 °C 135 A
(220 / 230 / 240 V) 55 °C 190 A
(440 V) 55 °C 190 A
(380 / 400 V) 55 °C 190 A
(500 V) 55 °C 135 A
Rated Operational Power AC-3 (Pe): (500 V) 90 kW
(1000 V) 110 kW
(690 V) 132 kW
(220 / 230 / 240 V) 55 kW
(380 / 400 V) 90 kW
(440 V) 110 kW
(415 V) 90 kW
Rated Breaking Capacity AC-3 acc. 8 x Ie AC-3
to IEC 60947-4-1:
Rated Making Capacity AC-3 acc. to 10 x Ie AC-3
IEC 60947-4-1:
Short-Circuit Protective Devices: gG Type Fuses 355 A
Rated Short-time Withstand Current at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 275 A
(Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1520 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 878 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1900 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 621 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3300 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2200 A
Maximum Electrical Switching AC-3 300 cycles per hour
Frequency: AC-1 300 cycles per hour
AC-2 / AC-4 150 cycles per hour
Rated Operational Current DC-1 (Ie): (110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated Operational Current DC-3 (Ie): (110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated Operational Current DC-5 (Ie): (110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Impulse Withstand Voltage Main Circuit 8 kV
(Uimp):
Mechanical Durability: 5 million
Maximum Mechanical Switching 300 cycles per hour
Frequency:
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) °C
Rated Control Circuit Voltage (Uc): 60 Hz 100…250 V
50 Hz 100…250 V
DC Operation 100…250 V
Coil Consumption: Pull-in at Max. Rated Control Circuit Voltage 60 Hz 220 V·A
Holding at Max. Rated Control Circuit Voltage DC 2.5 W
Holding at Max. Rated Control Circuit Voltage 50 Hz 7 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 190 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 220 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 7 V·A
Operate Time: Between Coil Energization and NO Contact Closing 25…55 ms
Between Coil De-energization and NO Contact Opening 37…47 ms
Connecting Capacity Main Circuit: Rigid Al-Cable 1x95…185 mm²
Flexible 2x50…95 mm²
Rigid Cu-Cable 1x6…150 mm²
Connecting Capacity Auxiliary Solid 2x1…4 mm²
Circuit: Flexible with Insulated Ferrule 1x0.75…2.5 mm²
Stranded 2x1…4 mm²
Flexible 2x0.75…2.5 mm²
Flexible with Ferrule 2x0.75…2.5 mm²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type: Main Circuit: Bars
Number of Main Contacts NO: 3
Environmental
Maximum Operating Altitude 3000 m
Permissible:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25…+50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40…+70 °C
Close to Contactor for Storage -40…+70 °C
Technical UL/CSA
General Use Rating UL/CSA: (600 V AC) 250 A
Horsepower Rating UL/CSA: (208 V AC) Three Phase 50 Hp
(440 ... 480 V AC) Three Phase 125 Hp
(550 ... 600 V AC) Three Phase 150 Hp
(220 ... 240 V AC) Three Phase 60 Hp
(200 V AC) Three Phase 50 Hp
Maximum Operating Voltage Main Circuit 600 V
UL/CSA:
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
EAN: 7320500480564
Dimensions
Product Net Depth: 152.0 mm
Product Net Height: 196.0 mm
Product Net Weight: 2.778 kg
Product Net Width: 105.0 mm
Container Information
Package Level 1 Width: 200 mm
Package Level 1 Length: 220 mm
Package Level 1 Height: 280 mm
Package Level 1 Gross Weight: 3.228 kg
Package Level 1 EAN: 7320500480564
Package Level 1 Units: 1 piece
Technical
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Rated Operational Voltage: Main Circuit 1000 V
Rated Frequency (f): Main Circuit 50/60 Hz
Conventional Free-air Thermal acc. to IEC 60947-4-1, Open Contactors q = 40 °C 350 A
Current (Ith):
Rated Operational Current AC-1 (Ie): (690 V) 55 °C 300 A
(690 V) 40 °C 350 A
(1000 V) 40 °C 275 A
(1000 V) 55 °C 250 A
(690 V) 70 °C 240 A
(1000 V) 70 °C 200 A
Rated Operational Current AC-3 (Ie): (1000 V) 55 °C 100 A
(690 V) 55 °C 165 A
(220 / 230 / 240 V) 55 °C 205 A
(415 V) 55 °C 205 A
(440 V) 55 °C 205 A
(380 / 400 V) 55 °C 205 A
(500 V) 55 °C 165 A
Rated Operational Power AC-3 (Pe): (500 V) 110 kW
(1000 V) 132 kW
(690 V) 160 kW
(220 / 230 / 240 V) 55 kW
(380 / 400 V) 110 kW
(440 V) 132 kW
(415 V) 110 kW
Rated Breaking Capacity AC-3 acc. 8 x Ie AC-3
to IEC 60947-4-1:
Rated Making Capacity AC-3 acc. to 10 x Ie AC-3
IEC 60947-4-1:
Short-Circuit Protective Devices: gG Type Fuses 400 A
Rated Short-time Withstand Current at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 350 A
(Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 947 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1640 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2050 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 670 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3500 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2500 A
Maximum Electrical Switching AC-3 300 cycles per hour
Frequency: AC-1 300 cycles per hour
AC-2 / AC-4 150 cycles per hour
Rated Operational Current DC-1 (Ie): (110 V) 2 Poles in Series, 40 °C 275 A
(220 V) 3 Poles in Series, 40 °C 275 A
Rated Operational Current DC-3 (Ie): (110 V) 2 Poles in Series, 40 °C 275 A
(220 V) 3 Poles in Series, 40 °C 275 A
Rated Operational Current DC-5 (Ie): (110 V) 2 Poles in Series, 40 °C 275 A
(220 V) 3 Poles in Series, 40 °C 275 A
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Impulse Withstand Voltage Main Circuit 8 kV
(Uimp):
Mechanical Durability: 5 million
Maximum Mechanical Switching 300 cycles per hour
Frequency:
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) °C
Rated Control Circuit Voltage (Uc): 60 Hz 100…250 V
50 Hz 100…250 V
DC Operation 100…250 V
Coil Consumption: Pull-in at Max. Rated Control Circuit Voltage 60 Hz 220 V·A
Holding at Max. Rated Control Circuit Voltage DC 2.5 W
Holding at Max. Rated Control Circuit Voltage 50 Hz 7 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 190 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 220 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 7 V·A
Operate Time: Between Coil Energization and NO Contact Closing 25…55 ms
Between Coil De-energization and NO Contact Opening 37…47 ms
Connecting Capacity Main Circuit: Rigid Al-Cable 1x95…185 mm²
Rigid Cu-Cable 1x6…150 mm²
Flexible 2x50…95 mm²
Connecting Capacity Auxiliary Solid 1x1…4 mm²
Circuit: Flexible with Insulated Ferrule 2x0.75…2.5 mm²
Stranded 1x1…4 mm²
Flexible 2x0.75…2.5 mm²
Flexible with Ferrule 1x0.75…2.5 mm²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type: Main Circuit: Bars
Number of Main Contacts NO: 3
Environmental
Maximum Operating Altitude 3000 m
Permissible:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25…+50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40…+70 °C
Close to Contactor for Storage -40…+70 °C
Technical UL/CSA
General Use Rating UL/CSA: (600 V AC) 300 A
Horsepower Rating UL/CSA: (208 V AC) Three Phase 60 Hp
(440 ... 480 V AC) Three Phase 150 Hp
(550 ... 600 V AC) Three Phase 200 Hp
(220 ... 240 V AC) Three Phase 75 Hp
(200 V AC) Three Phase 60 Hp
Maximum Operating Voltage Main Circuit 600 V
UL/CSA:
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
EAN: 7320500481776
Dimensions
Product Net Depth: 180.0 mm
Product Net Height: 225.0 mm
Product Net Weight: 4.640 kg
Product Net Width: 140.0 mm
Container Information
Package Level 1 Width: 223 mm
Package Level 1 Length: 175 mm
Package Level 1 Height: 270 mm
Package Level 1 Gross Weight: 5.31 kg
Package Level 1 EAN: 7320500481776
Package Level 1 Units: 1 piece
Technical
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Rated Operational Voltage: Main Circuit 1000 V
Rated Frequency (f): Main Circuit 50/60 Hz
Conventional Free-air Thermal acc. to IEC 60947-4-1, Open Contactors q = 40 °C 500 A
Current (Ith):
Rated Operational Current AC-1 (Ie): (690 V) 55 °C 400 A
(690 V) 40 °C 500 A
(1000 V) 40 °C 375 A
(1000 V) 55 °C 325 A
(690 V) 70 °C 325 A
(1000 V) 70 °C 260 A
Rated Operational Current AC-3 (Ie): (1000 V) 55 °C 100 A
(220 / 230 / 240 V) 55 °C 305 A
(690 V) 55 °C 290 A
(415 V) 55 °C 305 A
(440 V) 55 °C 305 A
(380 / 400 V) 55 °C 305 A
(500 V) 55 °C 290 A
Rated Operational Power AC-3 (Pe): (500 V) 200 kW
(1000 V) 132 kW
(690 V) 250 kW
(220 / 230 / 240 V) 90 kW
(380 / 400 V) 160 kW
(440 V) 160 kW
(415 V) 160 kW
Rated Breaking Capacity AC-3 acc. 8 x Ie AC-3
to IEC 60947-4-1:
Rated Making Capacity AC-3 acc. to 10 x Ie AC-3
IEC 60947-4-1:
Short-Circuit Protective Devices: gG Type Fuses 500 A
Rated Short-time Withstand Current at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 500 A
(Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2440 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1409 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 3050 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 996 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 4600 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 3800 A
Maximum Electrical Switching AC-3 300 cycles per hour
Frequency: AC-1 300 cycles per hour
AC-2 / AC-4 150 cycles per hour
Rated Operational Current DC-1 (Ie): (110 V) 2 Poles in Series, 40 °C 400 A
(220 V) 3 Poles in Series, 40 °C 400 A
Rated Operational Current DC-3 (Ie): (110 V) 2 Poles in Series, 40 °C 400 A
(220 V) 3 Poles in Series, 40 °C 400 A
Rated Operational Current DC-5 (Ie): (110 V) 2 Poles in Series, 40 °C 400 A
(220 V) 3 Poles in Series, 40 °C 400 A
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Impulse Withstand Voltage Main Circuit 8 kV
(Uimp):
Mechanical Durability: 5 million
Maximum Mechanical Switching 300 cycles per hour
Frequency:
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) °C
Rated Control Circuit Voltage (Uc): 60 Hz 100…250 V
50 Hz 100…250 V
DC Operation 100…250 V
Coil Consumption: Pull-in at Max. Rated Control Circuit Voltage 60 Hz 385 V·A
Holding at Max. Rated Control Circuit Voltage DC 4.5 W
Holding at Max. Rated Control Circuit Voltage 50 Hz 17.5 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 410 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 385 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 17.5 V·A
Operate Time: Between Coil Energization and NO Contact Closing 25…55 ms
Between Coil De-energization and NO Contact Opening 37…47 ms
Connecting Capacity Main Circuit: Rigid Al-Cable 1x185…240 mm²
Flexible 1x16…240 mm²
Rigid Cu-Cable 2x70…185 mm²
Connecting Capacity Auxiliary Solid 2x1…4 mm²
Circuit: Flexible with Insulated Ferrule 2x0.75…2.5 mm²
Stranded 1x1…4 mm²
Flexible 1x0.75…2.5 mm²
Flexible with Ferrule 1x0.75…2.5 mm²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type: Main Circuit: Bars
Number of Main Contacts NO: 3
Environmental
Maximum Operating Altitude 3000 m
Permissible:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25…+50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40…+70 °C
Close to Contactor for Storage -40…+70 °C
Technical UL/CSA
General Use Rating UL/CSA: (600 V AC) 400 A
Horsepower Rating UL/CSA: (208 V AC) Three Phase 100 Hp
(440 ... 480 V AC) Three Phase 250 Hp
(550 ... 600 V AC) Three Phase 300 Hp
(220 ... 240 V AC) Three Phase 125 Hp
(200 V AC) Three Phase 100 Hp
Maximum Operating Voltage Main Circuit 600 V
UL/CSA:
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Parts & Services » Drives » Low voltage AC drives » Legacy AC drives » MoCon
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
EAN: 7320500217665
Dimensions
Product Net Depth: 216.0 mm
Product Net Height: 278.0 mm
Product Net Weight: 12.000 kg
Product Net Width: 186.0 mm
Container Information
Package Level 1 Width: 260 mm
Package Level 1 Length: 250 mm
Package Level 1 Height: 350 mm
Package Level 1 Gross Weight: 12 kg
Package Level 1 EAN: 7320500217665
Package Level 1 Units: 1 piece
Technical
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Rated Operational Voltage: Main Circuit 1000 V
Rated Frequency (f): Main Circuit 50/60 Hz
Conventional Free-air Thermal acc. to IEC 60947-4-1, Open Contactors q = 40 °C 600 A
Current (Ith):
Rated Operational Current AC-1 (Ie): (690 V) 55 °C 500 A
(690 V) 40 °C 600 A
(1000 V) 40 °C 600 A
(1000 V) 55 °C 500 A
(690 V) 70 °C 400 A
(1000 V) 70 °C 400 A
Rated Operational Current AC-3 (Ie): (1000 V) 55 °C 155 A
(690 V) 55 °C 350 A
(415 V) 55 °C 400 A
(220 / 230 / 240 V) 55 °C 400 A
(440 V) 55 °C 400 A
(380 / 400 V) 55 °C 400 A
(500 V) 55 °C 400 A
Rated Operational Power AC-3 (Pe): (500 V) 250 kW
(690 V) 315 kW
(220 / 230 / 240 V) 110 kW
(380 / 400 V) 200 kW
(440 V) 220 kW
(415 V) 220 kW
Rated Breaking Capacity AC-3 acc. 8 x Ie AC-3
to IEC 60947-4-1:
Rated Making Capacity AC-3 acc. to 10 x Ie AC-3
IEC 60947-4-1:
Short-Circuit Protective Devices: gG Type Fuses 630 A
Rated Short-time Withstand Current at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 3100 A
(Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 4400 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 840 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 4600 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 2500 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 4000 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 3500 A
Maximum Electrical Switching AC-3 300 cycles per hour
Frequency: AC-1 300 cycles per hour
AC-2 / AC-4 60 cycles per hour
Rated Operational Current DC-1 (Ie): (600 V) 3 Poles in Series, 40 °C 600 A
(110 V) 1-Pole, 40 °C 600 A
(110 V) 2 Poles in Series, 40 °C 600 A
(220 V) 3 Poles in Series, 40 °C 600 A
Rated Operational Current DC-3 (Ie): (600 V) 3 Poles in Series, 40 °C 600 A
(110 V) 1-Pole, 40 °C 600 A
(110 V) 2 Poles in Series, 40 °C 600 A
(220 V) 3 Poles in Series, 40 °C 600 A
Rated Operational Current DC-5 (Ie): (600 V) 3 Poles in Series, 40 °C 600 A
(110 V) 1-Pole, 40 °C 600 A
(110 V) 2 Poles in Series, 40 °C 600 A
(220 V) 3 Poles in Series, 40 °C 600 A
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Impulse Withstand Voltage Main Circuit 8 kV
(Uimp):
Mechanical Durability: 5 million
Maximum Mechanical Switching 300 cycles per hour
Frequency:
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) °C
Rated Control Circuit Voltage (Uc): 60 Hz 100 … 250 V
50 Hz 100 … 250 V
DC Operation 100 … 250 V
Coil Consumption: Pull-in at Max. Rated Control Circuit Voltage 60 Hz 955 V·A
Holding at Max. Rated Control Circuit Voltage DC 5 V·A
Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 895 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 955 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A
Operate Time: Between Coil Energization and NO Contact Closing 50 ... 120 ms
Between Coil De-energization and NO Contact Opening 48 ... 58 ms
Between Coil De-energization and NC Contact Closing 45 ... 55 ms
Between Coil Energization and NC Contact Opening 45 ... 115 ms
Connecting Capacity Main Circuit: Rigid Al-Cable 2x240 mm²
Bar 47 mm
Rigid Cu-Cable 240 mm²
Connecting Capacity Auxiliary Solid 2x1…4 mm²
Circuit: Flexible with Insulated Ferrule 2x0.75…2.5 mm²
Stranded 2x1…4 mm²
Flexible 2x0.75…2.5 mm²
Flexible with Ferrule 2x0.75…2.5 mm²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type: Main Circuit: Bars
Number of Main Contacts NO: 3
Environmental
Maximum Operating Altitude 3000 m
Permissible:
Resistance to Shock acc. to IEC Shock Direction: A 5 g
60068-2-27: Shock Direction: C2 5 g
Shock Direction: B2 5 g
Shock Direction: C1 5 g
Shock Direction: B1 5 g
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25…+50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40…+70 °C
Close to Contactor for Storage -40…+70 °C
Technical UL/CSA
General Use Rating UL/CSA: (600 V AC) 550 A
Horsepower Rating UL/CSA: (208 V AC) Three Phase 125 Hp
(440 ... 480 V AC) Three Phase 350 Hp
(550 ... 600 V AC) Three Phase 400 Hp
(220 ... 240 V AC) Three Phase 150 Hp
(200 V AC) Three Phase 125 Hp
Maximum Operating Voltage Main Circuit 600 V
UL/CSA:
Classifications
E-nummer: 3228335
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
UNSPSC: 39121529
Object Classification Code: Q
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85369085
EAN: 3471523132030
Dimensions
Product Net Depth: 111 mm
Product Net Height: 125.5 mm
Product Net Weight: 0.950 kg
Product Net Width: 55 mm
Container Information
Package Level 1 Width: 150 mm
Package Level 1 Length: 150 mm
Package Level 1 Height: 97 mm
Package Level 1 Gross Weight: 1.05 kg
Package Level 1 EAN: 3471523132030
Package Level 2 Units: 12 piece
Package Level 2 Width: 300 mm
Package Level 2 Length: 320 mm
Package Level 2 Height: 500 mm
Package Level 1 Units: 1 piece
Technical
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 0
Number of Auxiliary Contacts NC: 0
Rated Operational Voltage: Main Circuit 690 V
Rated Frequency (f): Main Circuit 50 / 60 Hz
Conventional Free-air Thermal acc. to IEC 60947-4-1, Open Contactors q = 40 °C 105 A
Current (Ith):
Rated Operational Current AC-1 (Ie): (690 V) 40 °C 70 A
(690 V) 60 °C 60 A
(690 V) 70 °C 50 A
Rated Operational Current AC-3 (Ie): (220 / 230 / 240 V) 60 °C 40 A
(380 / 400 V) 60 °C 40 A
(415 V) 60 °C 40 A
(440 V) 60 °C 40 A
(500 V) 60 °C 35 A
(690 V) 60 °C 25 A
Rated Operational Power AC-3 (Pe): (220 / 230 / 240 V) 11 kW
(380 / 400 V) 18.5 kW
(415 V) 22 kW
(440 V) 22 kW
(500 V) 22 kW
(690 V) 22 kW
Rated Short-time Withstand Current at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A
(Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Maximum Electrical Switching AC-1 600 cycles per hour
Frequency: AC-2 / AC-4 150 cycles per hour
AC-3 1200 cycles per hour
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage 6 kV
(Uimp):
Maximum Mechanical Switching 3600 cycles per hour
Frequency:
Rated Control Circuit Voltage (Uc): 50 Hz 100 ... 250 V
60 Hz 100 ... 250 V
DC Operation 100 ... 250 V
Operate Time: Between Coil De-energization and NC Contact Closing 19 ... 105 ms
Between Coil De-energization and NO Contact Opening 17 ... 100 ms
Between Coil Energization and NC Contact Opening 38 ... 95 ms
Between Coil Energization and NO Contact Closing 42 ... 100 ms
Connecting Capacity Main Circuit: Flexible with Insulated Ferrule 1/2x 4...35 mm²
Flexible with Ferrule 1/2x 4...35 mm²
Rigid 1/2x 6...35 mm²
Connecting Capacity Control Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75...2.5 mm²
Flexible with Insulated Ferrule 2x 0.75...1.5 mm²
Rigid 1/2x 1...2.5 mm²
Wire Stripping Length: Main Circuit 16 mm
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Terminal Type: Screw Terminals
Number of Main Contacts NO: 3
Environmental
Maximum Operating Altitude 3000 m
Permissible:
Resistance to Vibrations acc. to IEC 5...300 Hz 3 g closed position / 3 g open position
60068-2-6:
Resistance to Shock acc. to IEC Closed, Shock Direction: A 25 g
60068-2-27: Closed, Shock Direction: B1 25 g
Closed, Shock Direction: B2 15 g
Closed, Shock Direction: C1 25 g
Closed, Shock Direction: C2 25 g
Open, Shock Direction: B1 5 g
Ambient Air Temperature: Close to Contactor for Storage -60...+80 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Technical UL/CSA
General Use Rating UL/CSA: (600 V AC) 60 A
Horsepower Rating UL/CSA: (120 V AC) Single Phase 3 Hp
(240 V AC) Single Phase 7-1/2 Hp
(200 ... 208 V AC) Three Phase 10 Hp
(220 ... 240 V AC) Three Phase 15 Hp
(440 ... 480 V AC) Three Phase 30 Hp
(550 ... 600 V AC) Three Phase 40 Hp
Tightening Torque UL/CSA: Control Circuit 11 in·lb
Main Circuit 35 in·lb
Classifications
E-nummer: 3210033
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
UNSPSC: 39121529
Object Classification Code: Q
AF65-30-00-13
General Information
Extended Product Type: AF65-30-00-13
Product ID: 1SBL387001R1300
EAN: 3471523132634
Catalog Description: AF65-30-00-13 100-250V50/60HZ-DC Contactor
Long Description: AF65 contactors are used for controlling power circuits up to 690 V AC and 220 V DC. They
are mainly used for controlling 3-phase motors, non-inductive or slightly inductive loads.
AF... contactors include an electronic coil interface accepting a wide control voltage Uc min.
... Uc max. Only four coils cover control voltages between 24...500 V 50/60 Hz or 20...500 V
DC. AF contactors can manage large control voltage variations. One coil can be used for
different control voltages used worldwide without any coil change. AF contactors have built-in
surge protection and do not require additional surge suppressors. The AF... series 1-stack
3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3
main poles, front and side-mounted add-on auxiliary contact blocks (mechanically-linked
auxiliary contacts compliant with Annex L of IEC 60947-5-1. N.C. mirror contacts compliant
with Annex F of IEC 60947-4-1) - Control circuit: AC or DC operated - Accessories: a wide
range of accessories is available.
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85369085
EAN: 3471523132634
Dimensions
Product Net Depth: 111 mm
Product Net Height: 125.5 mm
Product Net Weight: 0.950 kg
Product Net Width: 55 mm
Container Information
Package Level 1 Width: 150 mm
Package Level 1 Length: 150 mm
Package Level 1 Height: 97 mm
Package Level 1 Gross Weight: 1.05 kg
Package Level 1 EAN: 3471523132634
Package Level 2 Units: 12 piece
Package Level 2 Width: 300 mm
Package Level 2 Length: 320 mm
Package Level 2 Height: 500 mm
Package Level 1 Units: 1 piece
Technical
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 0
Number of Auxiliary Contacts NC: 0
Rated Operational Voltage: Main Circuit 690 V
Rated Frequency (f): Main Circuit 50 / 60 Hz
Conventional Free-air Thermal acc. to IEC 60947-4-1, Open Contactors q = 40 °C 105 A
Current (Ith):
Rated Operational Current AC-1 (Ie): (690 V) 40 °C 105 A
(690 V) 60 °C 90 A
(690 V) 70 °C 80 A
Rated Operational Current AC-3 (Ie): (220 / 230 / 240 V) 60 °C 65 A
(380 / 400 V) 60 °C 65 A
(415 V) 60 °C 65 A
(440 V) 60 °C 65 A
(500 V) 60 °C 55 A
(690 V) 60 °C 39 A
Rated Operational Power AC-3 (Pe): (220 / 230 / 240 V) 18.5 kW
(380 / 400 V) 30 kW
(400 V) 30 kW
(415 V) 37 kW
(440 V) 37 kW
(500 V) 37 kW
(690 V) 37 kW
Rated Short-time Withstand Current at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A
(Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Maximum Electrical Switching AC-1 600 cycles per hour
Frequency: AC-2 / AC-4 150 cycles per hour
AC-3 1200 cycles per hour
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage 6 kV
(Uimp):
Maximum Mechanical Switching 3600 cycles per hour
Frequency:
Rated Control Circuit Voltage (Uc): 50 Hz 100 ... 250 V
60 Hz 100 ... 250 V
DC Operation 100 ... 250 V
Operate Time: Between Coil De-energization and NC Contact Closing 19 ... 105 ms
Between Coil De-energization and NO Contact Opening 17 ... 100 ms
Between Coil Energization and NC Contact Opening 38 ... 95 ms
Between Coil Energization and NO Contact Closing 42 ... 100 ms
Connecting Capacity Main Circuit: Flexible with Insulated Ferrule 1/2x 4...35 mm²
Flexible with Ferrule 1/2x 4...35 mm²
Rigid 1/2x 6...35 mm²
Connecting Capacity Control Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length: Main Circuit 16 mm
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Terminal Type: Screw Terminals
Number of Main Contacts NO: 3
Environmental
Climatic Withstand: Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude 3000 m
Permissible:
Resistance to Vibrations acc. to IEC 5...300 Hz 3 g closed position / 3 g open position
60068-2-6:
Resistance to Shock acc. to IEC Closed, Shock Direction: A 25 g
60068-2-27: Closed, Shock Direction: B1 25 g
Closed, Shock Direction: B2 15 g
Closed, Shock Direction: C1 25 g
Closed, Shock Direction: C2 25 g
Open, Shock Direction: B1 5 g
Ambient Air Temperature: Close to Contactor for Storage -60...+80 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Technical UL/CSA
Horsepower Rating UL/CSA: (120 V AC) Single Phase 5 Hp
(240 V AC) Single Phase 15 Hp
(200 ... 208 V AC) Three Phase 20 Hp
(220 ... 240 V AC) Three Phase 25 Hp
(440 ... 480 V AC) Three Phase 50 Hp
(550 ... 600 V AC) Three Phase 60 Hp
Tightening Torque UL/CSA: Control Circuit 11 in·lb
Main Circuit 35 in·lb
Classifications
E-nummer: 3210045
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
ETIM 6: EC000066 - Power contactor, AC switching
UNSPSC: 39121529
Object Classification Code: Q
CA4-01
General Information
Extended Product Type: CA4-01
Product ID: 1SBN010110R1001
EAN: 3471523130029
Catalog Description: CA4-01 Auxiliary Contact Block
Long Description: CA4-01 Auxiliary Contact Block
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors Accessories
Ordering
EAN: 3471523130029
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85389099
Dimensions
Product Net Weight: 0.014 kg
Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 100 mm
Package Level 1 Height: 10 mm
Package Level 1 Length: 100 mm
Package Level 1 Gross Weight: 0.014 kg
Package Level 1 EAN: 3471523130029
Package Level 2 Units: 720 piece
Package Level 3 Units: 12960 piece
Product Packing Type: Bag
Environmental
RoHS Status: Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2008 Q1
Technical UL/CSA
Tightening Torque UL/CSA: Auxiliary Circuit 11 in·lb
Additional Information
Connecting Capacity-Auxiliary Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Circuit: Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1...2.5 mm²
Conventional Free-air Thermal acc. to IEC 60947-5-1, q = 40 °C 16 A
Current (Ith):
IIT Publishing Status: Level 0 - Information enabled
Maximum Electrical Switching AC-15 1200 cycles per hour
Frequency: DC-13 900 cycles per hour
Maximum Mechanical Switching 3600 cycles per hour
Frequency:
Mounted Auxiliary Contacts: 0 NO, 1 NC
Number of Auxiliary Contacts NC: 1
Number of Auxiliary Contacts NO: 0
Product Main Type: Accessories for Block Contactors
Product Name: Auxiliary Contact Block
Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz
Rated Impulse Withstand Voltage 6 kV
(Uimp):
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V
Rated Operational Current AC-15 (220 / 240 V) 4 A
(Ie): (24 / 127 V) 6 A
(400 / 440 V) 3 A
(500 V) 2 A
(690 V) 2 A
Rated Operational Current DC-13 (110 V) 0.55 A / 60 W
(125 V) 0.55 A / 69 W
(Ie): (220 V) 0.27 A / 60 W
(24 V) 6 A / 144 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(48 V) 2.8 A / 134 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
(72 V) 1 A / 72 W
Rated Operational Voltage: Auxiliary Circuit 24 ... 690 V
Rated Short-time Withstand Current for 0.1 s 140 A
(Icw): for 1 s 100 A
RoHS Date: 20090609
Suitable For: AF09
AF12
AF16
AF26
AF30
AF38
AF40
AF52
AF65
AF80
AF96
NF
Terminal Type: Screw Terminals
Tightening Torque: Auxiliary Circuit 1.2 N·m
Wire Stripping Length: Auxiliary Circuit 10 mm
Classifications
E-nummer: 3211410
ETIM 4: EC002498 - Accessories for low-voltage switch technology
ETIM 5: EC002498 - Accessories for low-voltage switch technology
Object Classification Code: K
UNSPSC: 39121500
CA4-10
General Information
Extended Product Type: CA4-10
Product ID: 1SBN010110R1010
EAN: 3471523130005
Catalog Description: CA4-10 Auxiliary Contact Block
Long Description: CA4-10 Auxiliary Contact Block
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors Accessories
Ordering
EAN: 3471523130005
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85389099
Dimensions
Product Net Weight: 0.014 kg
Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 100 mm
Package Level 1 Height: 10 mm
Package Level 1 Length: 100 mm
Package Level 1 Gross Weight: 0.014 kg
Package Level 1 EAN: 3471523130005
Package Level 2 Units: 720 piece
Package Level 3 Units: 12960 piece
Product Packing Type: Bag
Environmental
RoHS Status: Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2008 Q1
Technical UL/CSA
Tightening Torque UL/CSA: Auxiliary Circuit 11 in·lb
Additional Information
Connecting Capacity Auxiliary Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Circuit: Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1...2.5 mm²
Conventional Free-air Thermal acc. to IEC 60947-5-1, q = 40 °C 16 A
Current (Ith):
IIT Publishing Status: Level 0 - Information enabled
Maximum Electrical Switching AC-15 1200 cycles per hour
Frequency: DC-13 900 cycles per hour
Maximum Mechanical Switching 3600 cycles per hour
Frequency:
Mounted Auxiliary Contacts: 1 NO, 0 NC
Number of Auxiliary Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Product Main Type: Accessories for Block Contactors
Product Name: Auxiliary Contact Block
Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz
Rated Impulse Withstand Voltage 6 kV
(Uimp):
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V
Rated Operational Current AC-15 (220 / 240 V) 4 A
(Ie): (24 / 127 V) 6 A
(400 / 440 V) 3 A
(500 V) 2 A
(690 V) 2 A
Rated Operational Current DC-13 (110 V) 0.55 A / 60 W
(125 V) 0.55 A / 69 W
(Ie): (220 V) 0.27 A / 60 W
(24 V) 6 A / 144 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(48 V) 2.8 A / 134 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
(72 V) 1 A / 72 W
Rated Operational Voltage: Auxiliary Circuit 24 ... 690 V
Rated Short-time Withstand Current for 0.1 s 140 A
(Icw): for 1 s 100 A
RoHS Date: 20090609
Suitable For: AF09
AF12
AF16
AF26
AF30
AF38
AF40
AF52
AF65
AF80
AF96
NF
Terminal Type: Screw Terminals
Tightening Torque: Auxiliary Circuit 1.2 N·m
Wire Stripping Length: Auxiliary Circuit 10 mm
Classifications
E-nummer: 3211416
ETIM 4: EC002498 - Accessories for low-voltage switch technology
ETIM 5: EC002498 - Accessories for low-voltage switch technology
Object Classification Code: K
UNSPSC: 39121500
CAL4-11
General Information
Extended Product Type: CAL4-11
Product ID: 1SBN010120R1011
EAN: 3471523130043
Catalog Description: CAL4-11 Auxiliary Contact Block
Long Description: CAL4-11 Auxiliary Contact Block
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors Accessories
Ordering
EAN: 3471523130043
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85389099
Dimensions
Product Net Weight: 0.040 kg
Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 125 mm
Package Level 1 Height: 20 mm
Package Level 1 Length: 125 mm
Package Level 1 Gross Weight: 0.04 kg
Package Level 1 EAN: 3471523130043
Package Level 2 Units: 300 piece
Package Level 3 Units: 5400 piece
Product Packing Type: Bag
Environmental
RoHS Status: Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2008 Q1
Technical UL/CSA
Tightening Torque UL/CSA: Auxiliary Circuit 11 in·lb
Additional Information
Connecting Capacity Auxiliary Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Circuit: Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1...2.5 mm²
Conventional Free-air Thermal acc. to IEC 60947-5-1, q = 40 °C 16 A
Current (Ith):
IIT Publishing Status: Level 0 - Information enabled
Maximum Electrical Switching AC-15 1200 cycles per hour
Frequency: DC-13 900 cycles per hour
Maximum Mechanical Switching 3600 cycles per hour
Frequency:
Mounted Auxiliary Contacts: 1 NO, 1 NC
Number of Auxiliary Contacts NC: 1
Number of Auxiliary Contacts NO: 1
Product Main Type: Accessories for Block Contactors
Product Name: Auxiliary Contact Block
Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz
Rated Impulse Withstand Voltage 6 kV
(Uimp):
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V
Rated Operational Current AC-15 (220 / 240 V) 4 A
(Ie): (24 / 127 V) 6 A
(400 / 440 V) 3 A
(500 V) 2 A
(690 V) 2 A
Rated Operational Current DC-13 (110 V) 0.55 A / 60 W
(125 V) 0.55 A / 69 W
(Ie): (220 V) 0.27 A / 60 W
(24 V) 6 A / 144 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(48 V) 2.8 A / 134 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
(72 V) 1 A / 72 W
Rated Operational Voltage: Auxiliary Circuit 24 ... 690 V
Rated Short-time Withstand Current for 0.1 s 140 A
(Icw): for 1 s 100 A
RoHS Date: 20090609
Suitable For: AF09
AF12
AF16
AF26
AF30
AF38
AF40
AF52
AF65
AF80
AF96
NF
Terminal Type: Screw Terminals
Tightening Torque: Auxiliary Circuit 1.2 N·m
Wire Stripping Length: Auxiliary Circuit 10 mm
Classifications
E-nummer: 3211435
ETIM 4: EC002498 - Accessories for low-voltage switch technology
ETIM 5: EC002498 - Accessories for low-voltage switch technology
ETIM 6: EC002498 - Accessories for low-voltage switch technology
Object Classification Code: K
UNSPSC: 39121500
https://www.phoenixcontact.com/us/products/2833628
Relay retaining bracket, wiring to suit relay socket RIF-3 and PR3, for 52 mm high octal relay
Product Features
■ Relay base family that can be fitted with 2 PDT or 3 PDT relays
Technical data
Classifications
eCl@ss
ETIM
04/17/2016 Page 1 / 2
https://www.phoenixcontact.com/us/products/2833628
UNSPSC
04/17/2016 Page 2 / 2
https://www.phoenixcontact.com/us/products/2833615
Relay socket - PR3-BSC1/3X21 - 2833615
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Relay socket PR3..., for octal relay REL-OR with 3 PDT, screw connections, connection facility for input/
interference suppression modules, for mounting on NS 35/7.5
Product Features
■ Relay base family that can be fitted with 2 PDT or 3 PDT relays
Technical data
Dimensions
Width 38 mm
Height 75 mm
Depth with retaining bracket 84 mm (EL3-M52)
Ambient conditions
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
04/17/2016 Page 1 / 5
https://www.phoenixcontact.com/us/products/2833615
Relay socket - PR3-BSC1/3X21 - 2833615
Technical data
Connection data, input side
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (2 conductors with the same cross-section)
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (2 conductors with the same cross-section)
Conductor cross section AWG 26 ... 14
26 ... 14 (2 conductors with the same cross-section)
General
Nominal voltage UN 400 V AC/DC
Nominal current IN 10 A
Color green
Classifications
eCl@ss
Relay socket - PR3-BSC1/3X21 - 2833615
Classifications
ETIM
UNSPSC
Approvals
Approvals
Approvals
Ex Approvals
Approvals submitted
Approval details
UL Recognized
cUL Recognized
CSA
04/17/2016 Page 3 / 5
https://www.phoenixcontact.com/us/products/2833615
Relay socket - PR3-BSC1/3X21 - 2833615
Approvals
EAC
cULus Recognized
Accessories
Required add-on products
Pluggable octal relay with power contacts, 3 PDT, test button, mechanical switching position indication, coil voltage 24 V
DC
Pluggable octal relay with power contacts, 3 PDT, test button, mechanical switching position indication, coil voltage 24 V
AC
Single relay - REL-OR-120AC/3X21 - 2834290
Pluggable octal relay with power contacts, 3 PDT, test button, mechanical switching position indication, coil voltage 120 V
AC
Single relay - REL-OR-230AC/3X21 - 2834300
Pluggable octal relay with power contacts, 3 PDT, test button, mechanical switching position indication, input voltage: 230
V AC
04/17/2016 Page 4 / 5
https://www.phoenixcontact.com/us/products/2833615
04/17/2016 Page 5 / 5
https://www.phoenixcontact.com/us/products/2834274
Pluggable octal relay with power contacts, 3 PDT, test button, mechanical switching position indication, coil
voltage 24 V DC
Product Features
■ Extremely rugged design
Technical data
Dimensions
Width 34.5 mm
Height 34.5 mm
Depth 52.5 mm
Ambient conditions
Ambient temperature (operation) -40 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 60 °C
Coil side
Nominal input voltage UN 24 V DC
Input voltage range in reference to UN 0.8 ... 1.1
05/20/2016 Page 1 / 5
https://www.phoenixcontact.com/us/products/2834274
Contact side
Contact type 3 PDTs
Contact material AgSnIn
Maximum switching voltage 250 V AC/DC
Minimum switching voltage 1V
Min. switching current 10 mA
Maximum inrush current on request
Limiting continuous current 10 A (N/O contact)
5 A (N/C contact)
Interrupting rating (ohmic load) max. 2500 VA (for 250 V AC)
General
Test voltage relay winding/relay contact 2.5 kV AC (50 Hz, 1 min.)
Test voltage relay contact/relay contact 2.5 kV AC (50 Hz, 1 min.)
Operating mode 100% operating factor
Mechanical service life 6
10 x 10 cycles
Standards/regulations IEC 60664
Degree of pollution 3
Overvoltage category II
Mounting position any
Assembly instructions On relay base PR3
05/20/2016 Page 2 / 5
https://www.phoenixcontact.com/us/products/2834274
Classifications
eCl@ss
ETIM
UNSPSC
Approvals
Approvals
Approvals
Ex Approvals
05/20/2016 Page 3 / 5
https://www.phoenixcontact.com/us/products/2834274
Approvals submitted
Approval details
UL Recognized
cUL Recognized
EAC
EAC
cULus Recognized
Accessories
Additional products
Relay socket - PR3-BSC1/3X21 - 2833615
Relay socket PR3..., for octal relay REL-OR with 3 PDT, screw connections, connection facility for input/interference
suppression modules, for mounting on NS 35/7.5
Drawings
05/20/2016 Page 4 / 5
https://www.phoenixcontact.com/us/products/2834274
20
3
2
1
10 20 30 50 70 100 200 300
Switching voltage [V]
(14)
(12)
(A1) 3
4
1 2 (22)
5
0,9
(11)
1
(21)
0,8 6
Reduction factor
11
0,7 (31)
7
0,6 10 (24)
8
(A2) 9
0,5 (32)
(34)
0,4
0,3
1 0,9 0,8 0,7 0,6 0,5 0,4 0,3 0,2
COS j
05/20/2016 Page 5 / 5
https://www.phoenixcontact.com/in/products/2834300
Single relay - REL-OR-230AC/3X21 - 2834300
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Pluggable octal relay with power contacts, 3 PDT, test button, mechanical switching position indication, input
voltage: 230 V AC
Product Features
■ With detectable manual operation
GTIN
Technical data
Dimensions
Width 34.5 mm
Height 34.5 mm
Depth 52.5 mm
Ambient conditions
Ambient temperature (operation) -40 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 60 °C
Coil side
Nominal input voltage UN 230 V AC
Input voltage range in reference to UN 0.8 ... 1.1
Typical input current at UN 10 mA (at 50 Hz)
11 mA (At 60 Hz)
Typical response time 5 ms ... 20 ms (AC, depending on phase relation)
05/24/2016 Page 1 / 5
https://www.phoenixcontact.com/in/products/2834300
Single relay - REL-OR-230AC/3X21 - 2834300
Technical data
Coil side
Typical release time range 5 ms ... 20 ms (AC, depending on phase relation)
Coil resistance 6170 Ω ±15 % (at 20 °C)
Contact side
Contact type 3 PDTs
Contact material AgSnIn
Maximum switching voltage 250 V AC/DC
Minimum switching voltage 1V
Min. switching current 10 mA
Maximum inrush current on request
Limiting continuous current 10 A (N/O contact)
5 A (N/C contact)
Interrupting rating (ohmic load) max. 2500 VA (for 250 V AC)
General
Test voltage relay winding/relay contact 2.5 kV AC (50 Hz, 1 min.)
Test voltage relay contact/relay contact 2.5 kV AC (50 Hz, 1 min.)
Operating mode 100% operating factor
Mechanical service life 6
10 x 10 cycles
Standards/regulations IEC 60664
Degree of pollution 3
Overvoltage category II
Mounting position any
Assembly instructions On relay base PR3
Classifications
eCl@ss
05/24/2016 Page 2 / 5
https://www.phoenixcontact.com/in/products/2834300
Single relay - REL-OR-230AC/3X21 - 2834300
Classifications
eCl@ss
eCl@ss 4.1 27371104
eCl@ss 5.0 27371001
eCl@ss 5.1 27371001
eCl@ss 6.0 27371001
eCl@ss 7.0 27371001
eCl@ss 8.0 27371601
eCl@ss 9.0 27371601
ETIM
UNSPSC
Approvals
Approvals
Approvals
Ex Approvals
Approvals submitted
Approval details
UL Recognized
05/24/2016 Page 3 / 5
https://www.phoenixcontact.com/in/products/2834300
Single relay - REL-OR-230AC/3X21 - 2834300
Approvals
cUL Recognized
EAC
EAC
cULus Recognized
Accessories
Additional products
Relay socket - PR3-BSC1/3X21 - 2833615
Relay socket PR3..., for octal relay REL-OR with 3 PDT, screw connections, connection facility for input/interference
suppression modules, for mounting on NS 35/7.5
Drawings
Diagram Diagram
20
1
Switching current [A]
10
7
5
3
2
1
10 20 30 50 70 100 200 300
Switching voltage [V]
05/24/2016 Page 4 / 5
https://www.phoenixcontact.com/in/products/2834300
Single relay - REL-OR-230AC/3X21 - 2834300
Diagram Circuit diagram
(14)
(12)
(A1) 3
4
1 2 (22)
5
0,9
(11)
1
(21)
0,8 6
Reduction factor
11
0,7 (31)
7
0,6 10 (24)
8
(A2) 9
0,5 (32)
(34)
0,4
0,3
1 0,9 0,8 0,7 0,6 0,5 0,4 0,3 0,2
COS j
05/24/2016 Page 5 / 5
https://www.phoenixcontact.com/in/products/2966634
PLC-INTERFACE, consisting of PLC-BSC…/21 basic terminal block with screw connection and plug-in
miniature solid-state relay, for mounting on DIN rail NS 35/7,5, 1 N/O contact, input: 24 V DC, output: 3 - 33 V
DC/3 A
Product Features
■ Slim design
GTIN
Technical data
Note
EMC: class A product, see manufacturer's declaration in the download
Utilization restriction
area
Dimensions
Width 6.2 mm
Height 80 mm
Depth 94 mm
05/23/2016 Page 1 / 11
https://www.phoenixcontact.com/in/products/2966634
Input data
Nominal input voltage UN 24 V DC
Input voltage range in reference to UN 0.8 ... 1.2
Switching threshold "0" signal in reference to UN ≤ 0.4
Switching threshold "1" signal in reference to UN ≥ 0.8
Typical input current at UN 8.5 mA
Typical response time 20 µs (at UN)
Typical turn-off time 300 µs (at UN)
Operating voltage display Yellow LED
Type of protection Reverse polarity protection
Free-wheeling diode
Protective circuit/component Polarity protection diode
Damping diode
Transmission frequency 300 Hz
Power dissipation for nominal condition 0.6 W
Output data
Output voltage range 3 V DC ... 33 V DC
Limiting continuous current 3 A (see derating curve)
Maximum inrush current 15 A (10 ms)
Voltage drop at max. limiting continuous current ≤ 200 mV
Output circuit 2-wire, floating
Type of protection Reverse polarity protection
Surge protection
Protective circuit/component Polarity protection diode
General
Test voltage input/output 2.5 kV (50 Hz, 1 min.)
Mounting position any
Assembly instructions In rows with zero spacing
Operating mode 100% operating factor
Flammability rating according to UL 94 V0
Designation Standards/regulations
Standards/regulations IEC 60664
EN 50178
IEC 62103
Rated surge voltage/insulation Basic insulation
Degree of pollution 2
Overvoltage category III
Classifications
eCl@ss
05/23/2016 Page 3 / 11
https://www.phoenixcontact.com/in/products/2966634
UNSPSC
Approvals
Approvals
Approvals
UL Recognized / UL Listed / cUL Recognized / cUL Listed / GL / EAC / EAC / cULus Recognized / cULus Listed
Ex Approvals
Approvals submitted
Approval details
UL Recognized
UL Listed
cUL Recognized
05/23/2016 Page 4 / 11
https://www.phoenixcontact.com/in/products/2966634
cUL Listed
GL
EAC
EAC
cULus Recognized
cULus Listed
Accessories
Accessories
Bridge
05/23/2016 Page 5 / 11
https://www.phoenixcontact.com/in/products/2966634
Controller board
05/23/2016 Page 6 / 11
https://www.phoenixcontact.com/in/products/2966634
System connection - PLC-V8/FLK14/OUT - 2295554
V8-OUTPUT adapter for eight 6.2 mm PLC interfaces (1 PDT, etc./see "Supplementary Products"). 14-pos. flat-
ribbon cable connection for the PLC system cabling, control logic: Plus switching
System connection - PLC-V8/FLK14/OUT/M - 2304102
V8-OUTPUT adapter for eight 6.2 mm PLC interfaces (1 PDT, etc./see "Supplementary Products"). 14-pos. flat-
ribbon cable connection for the PLC system cabling, control logic: Minus switching
System connection - PLC-V8/D15S/OUT - 2296058
V8-OUTPUT adapter for eight 6.2 mm PLC interfaces (1 PDT, etc./see "Additional Products"). 15-pin D-SUB male
connector, control logic: Positive switching
System connection - PLC-V8/D15B/OUT - 2296061
V8-OUTPUT adapter for eight 6.2 mm PLC interfaces (1 PDT, etc./see "Additional Products"). 15-pin D-SUB female
connector, control logic: Positive switching
DIN rail
DIN rail, unperforated, Width: 35 mm, Height: 7.5 mm, Length: 2000 mm, Color: silver
05/23/2016 Page 7 / 11
https://www.phoenixcontact.com/in/products/2966634
DIN rail, material: steel galvanized and passivated with a thick layer, perforated, height 7.5 mm, width 35 mm, length:
2000 mm
DIN rail, material: Copper, unperforated, height 7.5 mm, width 35 mm, length: 2 m
DIN rail, material: Steel, unperforated, height 15 mm, width 35 mm, length: 2 m
DIN rail, material: Copper, unperforated, 1.5 mm thick, height 15 mm, width 35 mm, length: 2 m
DIN rail, material: Steel, unperforated, 2.3 mm thick, height 15 mm, width 35 mm, length: 2 m
05/23/2016 Page 8 / 11
https://www.phoenixcontact.com/in/products/2966634
DIN rail, deep drawn, high profile, unperforated, 1.5 mm thick, material: aluminum, height 15 mm, width 35 mm,
length 2000 mm
DIN rail, material: steel galvanized and passivated with a thick layer, perforated, height 15 mm, width 35 mm, length:
2000 mm
DIN rail, material: Steel, unperforated, height 7.5 mm, width 35 mm, length: 2 m
Zack marker strip, Strip, white, labeled, can be labeled with: Plotter, Printed horizontally: Consecutive numbers 1 - 10,
11 - 20, etc. up to 491 - 500, Mounting type: Snap into tall marker groove, for terminal block width: 6.2 mm, Lettering
field: 6.15 x 10.5 mm
Partition plate
Separating plate, 2 mm thick, required at the start and end of a PLC terminal strip. Furthermore, it is used for: visual
separation of groups, safe isolation of different voltages of neighboring PLC relays in acc. with DIN VDE 0106-101,
isolation
Power module
05/23/2016 Page 9 / 11
https://www.phoenixcontact.com/in/products/2966634
Power terminal block, for the input of up to four potentials, for mounting on NS 35/7.5
Relay socket
6.2 mm PLC basic terminal block with screw connection, without relays or solid-state relay, for mounting on DIN rail
NS 35/7,5, 1 PDT, input voltage 24 V DC
Screwdriver tools
Screwdriver - SZF 1-0,6X3,5 - 1204517
Actuation tool, for ST terminal blocks, also suitable for use as a bladed screwdriver, size: 0.6 x 3.5 x 100 mm, 2-
component grip, with non-slip grip
Plug-in miniature solid-state relay, power solid-state relay, 1 N/O contact, input: 24 V DC, output: 3 - 33 V DC/3 A
Terminal marking
Zack marker strip, Strip, white, unlabeled, can be labeled with: Plotter, Mounting type: Snap into tall marker groove,
for terminal block width: 6.2 mm, Lettering field: 6.15 x 10.5 mm
05/23/2016 Page 10 / 11
https://www.phoenixcontact.com/in/products/2966634
6.2 mm PLC basic terminal block with screw connection, without relays or solid-state relay, for mounting on DIN rail
NS 35/7,5, 1 PDT, input voltage 24 V DC
Plug-in miniature solid-state relay, power solid-state relay, 1 N/O contact, input: 24 V DC, output: 3 - 33 V DC/3 A
Drawings
2
A2 13+
1
0 A1 14
10 20 30 40 50 60
Ambient temperature [°C]
05/23/2016 Page 11 / 11
Data sheet 3NC1450-5
SITOR CYLIND. FUSE-LINK AR WITH STRIKER 14X51
50 A, 690V AC/ 600V DC
Model
product brand name SENTRON
Dissipation
Power loss [W]
● for rated value of the current / at AC / in hot W 9
operating state / per pole
Main circuit
Operating voltage / rated value V 690
Operating current / Rated value A 50
Product details
Product component / striker Yes
Net weight g 26
Equipment marking
● acc. to DIN EN 61346-2 F
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/lowvoltage/catalogs
Industry Mall (Online ordering system)
https://eb.automation.siemens.com/mall/en/WW/Catalog/Product/3NC14505
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
http://support.automation.siemens.com/WW/view/en/3NC14505/all
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3NC14505
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://ausschreibungstexte.siemens.com/tiplv
Tip-top Reliability
performance Venting grooves and cooling
chambers improve heat
E 90 fuseholders can be used dissipation even in multiple-pole
in any applications where configurations. The reduced
operating temperature inside
you need to ensure electrical
fuseholders ensures durability and
protection, isolation and reliability of the devices over time.
switching under load of
inductive or resistive loads in
compliance with IEC 60947-3
Standard, AC-22B utilization
category. The technology
solutions applied to reduce
power dissipation help to
minimize module heating.
Compactness
When open, the drawer projection is
only 17 mm more than in the normal
closed position.
The compact dimensions enable
to close the switchboard door
even when the fuseholder is open,
thus ensuring total safety during
maintenance. 1P+N versions in
Reliable connections
Wide terminals allow the use of cables with
section up to 25 mm2, whereas the antivibration
knurling on the terminal cages ensures safe and
reliable connections.
Ease of use
Fuseholder profile has been
designed for maximum ease
of use: the 90° flip hinge with
ergonomic knob, makes the
replacement of fuses easier
even in small spaces or when
wearing protective gloves.
Safety
To ensure protection and safety
during maintenance operations
and avoid any accidental switching,
fuseholders can be sealed in
closed position, and padlocked
in open position. The protection
degree is IP20 when the unit is
installed behind the switchboard
slotting.
Environmental protection.
The fuseholders are compliant with RoHS (Restriction of Hazardous Substances)
European directive, which prohibits the use of hazardous substances in the
manufacture of electrical and electronic equipment.
E 90 range of fuse disconnectors and fuseholders | 7
Smart protection for installations
with E 90s
Flexible:
E 90: 24 to 690 V operation in
AC networks. Can be powered
from both the load side and
the supply side
E 90 PV: 24 to 1000 V
operation in DC networks with
upstream supply
Simple:
No need for auxiliary supply
or specific wiring
Effective:
Local fuse tripping signal
Allows the faulty phase
to be immediately detected
– –
+ +
+ ~ – + ~ –
Wiring diagram for d.c. networks Wiring diagram for a.c. networks
E 90 Wizard
Application example
Here you can find a typical industrial control application. According to
IEC 60364-1 Standard, the secondary winding of a control transformer must
be protected against short circuits and overload. The transformer provides
dedicated 230 V a.c. power supply to a battery of industrial contactors.
Terminal protection of: in single phase and in three-phase networks with neutral. They
are particularly suitable inside switchboards and consumer
-E lectric auxiliaries units for protecting lighting circuits, modular sockets and
electrical devices for monitoring, measuring and signalling.
- Switchboard instrumentation
- Surge arresters
Application example
Here you can find a typical application inside a secondary distribution
switchboard. Following the manufacturer’s instruction, the voltmetric
inputs of the multimeter are protected with fuses.
Application examples
String protection
To prevent damage to the equipment in the direct current
lines of photovoltaic installations and ensure that it remains
isolated when maintenance work is performed, E 90 PV fuse
disconnectors can be installed downstream of the inverter so
as to protect each string. The fuses must be selected to suit
the rated current of the line.
- Rated current 30 A 200 kA. The limiting properties of the Class CC fuses are
particularly appreciated in the North American market, allowing
- Versions 1, 1N, 2, 3, 3N, 4 poles suitable protection even of equipment with limited resistance to
short-circuit. The use of Class CC fuses is continuously
- Rejection member to increasing in the American market, since the safety and reliability
prescriptions of end users have become stricter and do not
allow just the insertion tolerate any permanent damage to motor starts.
of a class CC fuse
Terminals' section mm 2 25 16 25 35 50
Cross section rigid copper conductors mm 2 1,5 - 25 1,5 - 16 1,5 - 25 2,5 - 35 4 - 50
Cross section stranded copper conductors mm 2 1,5 - 16 1,5 - 10 1,5 - 16 2,5 - 25 4 - 35
Operating temperature °C -5 / +40*** -5 / +40*** -5 / +40*** -5 / +40***
Storage temperature °C -25 / +70**** -25 / +70**** -25 / +70**** -25 / +70****
Altitude m 2000 2000 2000 2000
Voltage range for LED indicator light 24 - 1000 AC/DC – – 24 - 1000 24 - 1000 AC/DC
(only s version) AC/DC (only (only s version)
s version)
Marks and approvals E 90/20 E 90/32 E 90hN/20 E 90hN/32 E 90/32 PV E 930/50 E 930/125
IMQ •*(1) •*(1) •* •*
NF •** (1) •**(1)
CCC - Cina •*(1) •*(1) •* •*
cURus • (2)
UR •
UL •(3)
CSA •
RINA •*(1) •*(1) •* •*
LLOYD •* (1) •*(1) •* •*
BV • (1) • (1) • • • •
GOST - Russia • • • • • •
GOST - Ukraina • • • • • •
Poles Rated Modu- Description ABB code Bbn Piece Pack unit
current les Type 8012542 weight pcs
EAN kg
E 90 fuse disconnectors for 10.3 x 38 mm fuses
38 ø 10,3 1 32 1 E 91/32 2CSM200923R1801 009238 0,061 6
1 32 1 E 91/32s* 2CSM202483R1801 024835 0,062 6
1+N 32 2 E 91N/32 2CSM200893R1801 008934 0,130 3
1+N 32 2 E 91N/32s* 2CSM251503R1801 515036 0,131 3
2 32 2 E 92/32 2CSM200883R1801 008835 0,122 3
2 32 2 E 92/32s* 2CSM251493R1801 514930 0,123 3
3 32 3 E 93/32 2CSM204753R1801 047537 0,183 2
3 32 3 E 93/32s* 2CSM202063R1801 020639 0,184 2
3+N 32 4 E 93N/32 2CSM204733R1801 047339 0,252 1
3+N 32 4 E 93N/32s* 2CSM251483R1801 514831 0,254 1
4 32 4 E 94/32 2CSM204723R1801 047230 0,244 1
Poles Rated Modu- Description ABB code Bbn Piece Pack unit
current les Type 8012542 weight pcs
EAN kg
E 90h fuseholders for 10.3 x 38 mm fuses
38 ø 10,3 1+N 32 1 E 91hN/32 2CSM200913R1801 009139 0,070 6
1+N 32 1 E 91hN/32s* 2CSM206573R1801 065739 0,071 6
3+N 32 3 E 93hN/32 2CSM204743R1801 047438 0,192 2
3+N 32 3 E 93hN/32s* 2CSM274343R1801 743439 0,193 2
31,5 ø 8,5
E 90h fuseholders for 8.5 x 31.5 mm fuses
1+N 20 1 E 91hN/20 2CSM200963R1801 009634 0,070 6
1+N 20 1 E 91hN/20s* 2CSM200703R1801 007036 0,071 6
3+N 20 3 E 93hN/20 2CSM200933R1801 009337 0,192 2
3+N 20 3 E 93hN/20s 2CSM289603R1801 896036 0,193 2
The most widely used codes are in green
*s: versione with blown fuse indicator
Poles Rated Modules Description ABB code Bbn Piece Pack unit
current Type 8012542 weight pcs
EAN kg
E 90 CC fuseholders for Class CC 10.4 x 38.1 mm fuses
38,1 ø 10,4 1 30 1 E 91/30 CC 2CSM299872R1801 998723 0,061 6
1 30 1 E 91/30 CCs* 2CSM299882R1801 998822 0,062 6
1+N 30 2 E 91N/30 CC 2CSM299892R1801 998921 0,13 3
1+N 30 2 E 91N/30 CCs* 2CSM299902R1801 999027 0,131 3
2 30 2 E 92/30 CC 2CSM299912R1801 999126 0,122 3
2 30 2 E 92/30 CCs* 2CSM299922R1801 999225 0,123 3
3 30 3 E 93/30 CC 2CSM299932R1801 999324 0,183 2
3 30 3 E 93/30 CCs* 2CSM299942R1801 999423 0,184 2
3+N 30 4 E 93N/30 CC 2CSM299952R1801 999522 0,252 1
3+N 30 4 E 93N/30 CCs* 2CSM299962R1801 999621 0,253 1
4 30 4 E 94/30 CC 2CSM299972R1801 999720 0,244 1
4 30 4 E 94/30 CCs* 2CSM299982R1801 999829 0,245 1
The most widely used codes are in green
*s: version with blown fuse indication indicator
Poles Rated Modules Description ABB code Bbn Piece Pack unit
current Type 8012542 weight pcs
EAN kg
E 930 fuse disconnectors for 14 x 51 mm fuses (AC-20B)
1 50 1,5 E 931/50 2CSM361610R1801 446804 0,200 6
51 ø 14
1+N 50 3 E 931N/50 2CSM365610R1801 446903 0,400 3
2 50 3 E 932/50 2CSM362610R1801 447009 0,400 3
3 50 4,5 E 933/50 2CSM363610R1801 447108 0,600 1
3+N 50 6 E 933N/50 2CSM367610R1801 447207 0,800 1
Poles Rated Modules Description ABB code Bbn Piece Pack unit
current Type 8012542 weight pcs
EAN kg
E 930 fuse disconnectors for 22 x 58 mm fuses (AC-20B)
1 125 2 E 931/125 2CSM371710R1801 447504 0,200 6
Poles Rated Modules Description ABB code Bbn Piece Pack unit
current Type 8012542 weight pcs
EAN kg
Accessories for E 930 series fuseholders
Microswitch for fuse blown signalling
E 90 wiring diagrams
1P 1P+N 2P 3P 3P+N 4P
1P+N 3P+N 1P 2P
Overall dimensions
1P (E 91hN) 1P+N, 2P 3P, 3P+N (E 93hN) 3P+N, 4P
85
45
17.5 35 52.5 70 64
Wiring diagrams
1P 1P+N 2P 3P 3P+N
Overall dimensions:
76.5
50 A
1P 1P+N, 2P 3P 3P+N, 4P 50
45
107
60
26.5 53 79.5 106
76.5
125 A
1P 1P+N, 2P 3P 3P+N, 4P 50
45
126.5
60
35 70 105 140
Maximum rated current The maximum rated current values of the fuse that can
be installed in the fuseholder are given in the table below.
value of the fuse These values depend on the rated voltage of the network
and conform to the maximum limits of the power dissipated
by the protection system, formed by the fuse and fuseholder.
ABB fuses and fuseholders allow all the requirements
established by the standards to be met in full safety.
The performance provided by ABB products allows a fuse with
a rated current that exceeds the limit dictated by standard
IEC 60269-2-1 (Art. 5-3-1) to be installed in certain situations.
Fuseholders
Rated Fuse E 90/20 E 90/32 E 930/50 E 930/125
voltage curve 8,5 x 31,5 10,3 x 38 14 x 51 22 x 58
mm mm mm mm
400 V c.a. gG 20 A 32 A 50 A 100 A
aM 10 A 32 A 50 A 125 A*
500 V c.a. gG - 25 A 40 A 100 A
aM - 25 A 40 A 100 A
690 V c.a. gG - 10 A 25 A 80 A
aM - - 25 A 80 A
* = to be used in combination with a device which guarantees protection
against overload.
Derating values Depending on the rated current, the number of poles installed
side by side or the temperature and relative humidity, the
for E 90 fuseholders derating parameters in the table must be considered if several
poles are installed side by side or if the equipment is installed
in unusual climatic conditions.
Climatic conditions
Maximum temperature 20 °C 30 °C 40 °C 50 °C
Maximum humidity 95 % 90 % 80 % 50 %
Maximum current In In x 0,95 In x 0,9 In x 0,8
51 ø 14
Rated D e s c r i p t i o n ABB code Bbn Piece weight Package
current Type 8012542 kg
In [A] EAN
2 E 9F14 GG2 2CSM277523R1801 775232 0,018 10
4 E 9F14 GG4 2CSM277303R1801 773030 0,018 10
6 E 9F14 GG6 2CSM277083R1801 770831 0,018 10
8 E 9F14 GG8 2CSM291003R1801 910039 0,018 10
10 E 9F14 GG10 2CSM290983R1801 909835 0,018 10
12 E 9F14 GG12 2CSM290963R1801 909637 0,018 10
16 E 9F14 GG16 2CSM258783R1801 587835 0,018 10
20 E 9F14 GG20 2CSM257603R1801 576037 0,018 10
25 E 9F14 GG25 2CSM256423R1801 564232 0,018 10
32 E 9F14 GG32 2CSM258693R1801 586937 0,018 10
40 E 9F14 GG40 2CSM257513R1801 575139 0,018 10
50 E 9F14 GG50 2CSM256333R1801 563334 0,018 10
E 9F 22 gG 22 x 58 mm cylindrical fuses
Rated D e s c r i p t i o n ABB code Bbn Piece weight Package
current Type 8012542 kg
58 ø 22 In [A] EAN
4 E 9F22 GG4 2CSM257183R1801 571834 0,048 10
6 E 9F22 GG6 2CSM259283R1801 592839 0,048 10
8 E 9F22 GG8 2CSM258103R1801 581031 0,048 10
10 E 9F22 GG10 2CSM256923R1801 569237 0,048 10
12 E 9F22 GG12 2CSM259403R1801 594031 0,048 10
16 E 9F22 GG16 2CSM258223R1801 582236 0,048 10
20 E 9F22 GG20 2CSM257043R1801 570431 0,048 10
25 E 9F22 GG25 2CSM259533R1801 595335 0,048 10
32 E 9F22 GG32 2CSM258353R1801 583530 0,048 10
40 E 9F22 GG40 2CSM257173R1801 571735 0,048 10
50 E 9F22 GG50 2CSM259393R1801 593935 0,048 10
63 E 9F22 GG63 2CSM258213R1801 582137 0,048 10
80 E 9F22 GG80 2CSM257033R1801 570332 0,048 10
100 E 9F22 GG100 2CSM259523R1801 595236 0,048 10
125 E 9F22 GG125 2CSM258343R1801 583431 0,048 10
Technical specifications
Rated voltage [V] 400, 500, 690 AC
Rated current [A] 0,5…125
Breaking capacity [kA] 20, 80, 120
Overall dimensions [mm] 8,5 x 31,5, 10,3 x 38, 14 x 51, 22 x 58
Weight [g] 4, 7, 18, 48
Marks LLOYD, BV
Standards IEC 60269-2; ROHS 2002/98/CE
103
104
102
103
101
t2 S (A2 S)
t [S]
100
102
10-1
101 690 V
Operating I²t
10-2 500 V
400 V
lp [A]
Temperature increase
°C
90
80
70
60
50
40
30
20
10
2 4 5 8 10 12 16 20 25 32 2 4 5 8 10 12 16 20 25 32 40 50 16 20 25 32 40 50 63 80 100 125
10 x 38 14 x 51 22 x 58
Use this table to find the cable length, Just cross the rated current of the fuse (in the columns)
with the section of the conductor (on the lines).
in meters, that is protected by a fuse. The resulting number corresponds to the protected length
of the conductor: for example, a 32 A fuse can protect up
to 214 meters of 6 mm2 section cable. When there are two
values, it means that the maximum length of the cable is
between the two numbers given in the table.
E 9F aM series fuses are the best way to protect against overloads and
short-circuits together with series fuse E 90 and E 930. They feature a delayed
tripping curve and are therefore ideal for protecting industrial motors that
require high inrush current during the starting phase. The E 9F aM series
is available for all the main sizes (8.5 x 31.5 mm, 10.3 x 38 mm, 14 x 51 mm
e 22 x 58 mm) and with a wide range of rated current values (from 1 A to 125 A
and up to 690 V a.c.). All the E 9F series fuses conform to the RoHS directive
and are type-approved in accordance with the most important international
naval marks.
E 9F 22 aM 22 x 58 mm cylindrical fuses
Rated D e s c r i p t i o n ABB code Bbn Piece weight Package
current Type 8012542 kg
58 ø 22 In [A] EAN
6 E 9F22 AM6 2CSM258603R1801 586036 0,048 10
8 E 9F22 AM8 2CSM257423R1801 574231 0,048 10
10 E 9F22 AM10 2CSM256243R1801 562436 0,048 10
12 E 9F22 AM12 2CSM277513R1801 775133 0,048 10
16 E 9F22 AM16 2CSM277293R1801 772934 0,048 10
20 E 9F22 AM20 2CSM277073R1801 770732 0,048 10
25 E 9F22 AM25 2CSM277493R1801 774938 0,048 10
32 E 9F22 AM32 2CSM277273R1801 772736 0,048 10
40 E 9F22 AM40 2CSM277053R1801 770534 0,048 10
50 E 9F22 AM50 2CSM259413R1801 594130 0,048 10
63 E 9F22 AM63 2CSM258233R1801 582335 0,048 10
80 E 9F22 AM80 2CSM257053R1801 570530 0,048 10
100 E 9F22 AM100 2CSM259543R1801 595434 0,048 10
125 E 9F22 AM125 2CSM258363R1801 583639 0,048 10
Technical specifications
Rated voltage [V] 400, 500, 690 AC
Rated current [A] 0,5…125
Breaking capacity [kA] 20, 80, 120
Overall dimensions [mm] 8,5 x 31,5, 10,3 x 38, 14 x 51, 22 x 58
Weight [g] 4, 7, 18, 48
Marks LLOYD, BV
Standards IEC 60269-2; ROHS 2002/98/CE
103
104
102
101
103
t [S]
t2 S (A2 S)
100
102
10-1
Operating I²t
10-2 101 690 V
500 V
400 V
10-3
100 101 102 103 104
100 Pre-arcing I²t
lp [A] lp [A]
Temperature increase
°C
90
80
70
60
50
40
30
20
10
1 2 4 6 8 10 12 16 20 25 32 1 2 4 6 8 10 12 16 20 25 32 40 50 1 2 4 6 8 10 12 16 20 25 32 40 50 63 80 100
125
10 x 38 14 x 51 22 x 58
Use this table to find the cable length, Just cross the rated current of the fuse (in the columns)
with the section of the conductor (on the lines).
in meters, that is protected by a fuse. The resulting number corresponds to the protected length
of the conductor: for example, a 32 A fuse can protect up
to 214 meters of 6 mm2 section cable. When there are two
values, it means that the maximum length of the cable is
between the two numbers given in the table.
Technical specifications
Rated voltage [V] 1000 DC
Rated current [A] 1...30
Breaking capacity [kA] 10
Minimum breaking capability da 1A a 7A = 1.3 x In
da 8A a 30A = 2.0 x In
Derating Coefficient
1.0
-30 -10 30 50 70
E 9F25 PV 25 1,20 1,70 2,90 132 1650 10
The power dissipation of the fuse cannot exceed the maximum power
dissipation accepted by the fuseholder.
1000 1000
700 700
500 1A 500
2A
300 300
3A
200 200
4A
5A
100 100
6A 8A
70 70
10A
50 7A 50 12A
15A
30 30 20A
20 20
25A
10 10 30A
7 7
5 5
t [S]
t [S]
3 3
2 2
1 1
-7 -7
-5 -5
-3 -3
-2 -2
-1 -1
-0,7 -0,7
-0,5 -0,5
-0,3 -0,3
-0,2 -0,2
-0,1 -0,1
0,5
0,7
1
2
3
5
7
10
20
30
50
70
100
200
300
500
700
1000
2000
3000
5000
7000
10000
0,5
0,7
1
2
3
5
7
10
20
30
50
70
100
200
300
500
700
1000
2000
3000
5000
7000
10000
lp [A] lp [A]
Maximum rated current for cylindrical fuses according Can fuses with rated current values higher than the
to IEC 60269-2-1 (Art. 5-3-1). one indicated in the table be used? For example, can a
10.3 x 38 mm 32 A gG fuse be used in a 10.3 x 38 mm
Size of fuse 400 V a.c. 500 V a.c. 690 V a.c. E 90/32 fuseholder?
[mm] gG aM gG aM gG aM Yes, in compliance with the instructions provided by the
In A manufacturer: make sure that the power dissipated at the
8,5 x 31,5 16 10 - -- - - rated voltage value declared by the manufacturer for the size
10,3 x 38 - - 25 16 10 - considered does not exceed the maximum dissipated power
14 x 51 - - 50 40 25 25 limit of the fuseholder. In this specific case, an E 9F10 GG32
22 x 58 - - 100 100 50 50 fuse dissipates 3 W at 400 V rated voltage. Since an E 90/32
series fuseholder for 10.3 x 38 mm fuses achieves 3 W
thermal dissipation, the fuse in question can be used at 400 V
The Standard also allows the use of fuses with rated current rated voltage or less.
values that are higher than the value in the table.
The maximum rated current values envisaged for the Can a 10.3 x 38 mm 32 A gG fuse be used in a
fuseholders are indicated 10.3 x 38 mm E 90/32 fuseholder with a rated voltage
exceeding 400 V?
In the specific case of E 9F10 GG32, use of rated voltage
exceeding 400 V fails to allow the equipment to comply with
the maximum dissipated power limit.
ABB SACE
2CSC444002B0203 - 11/2013
The data and illustrations are not binding. We reserve
the right to modify the contents of this document on the
A division of ABB S.p.A. basis of technical development of the products,
Line Protection Devices without prior notice.
Viale dell’Industria, 18
Copyright 2013 ABB. All rights reserved.
20010 Vittuone (MI) - Italy
Tel.: +39 02 9034 1
Fax: +39 02 9034 7609
www.abb.com
11.
SPARE
12.
SPARE
13.
SPARE
14.
TOUCHVIEW SCREEN
Extract from the online
catalog
VL PPC 6015 FLS
Order No.: 2913031
http://eshop.phoenixcontact.dk/phoenix/treeViewClick.do?UID=2913031
IPC with touch screen
Product notes
WEEE/RoHS-compliant since:
Commercial data 17-08-2011
Note Made-to-order
EAN 4046356651158
Pack 1 pcs.
Customs tariff 84714100
Gross weight in pieces 6800.00 g Please note that the data given
here has been taken from the
Product key 11N online catalog. For comprehensive
information and data, please refer
country of origin TW
to the user documentation at http://
www.download.phoenixcontact.com.
The General Terms and Conditions
of Use apply to Internet downloads.
Technical data
Display data
Display 38.1 cm/15" TFT active
Resolution 1024 x 768 Pixel (XGA)
Backlighting CCFL
Display backlight MTBF 50000 h
Touch screen Resistive industrial touch screen
Computer data
Processor Atom™ 1.6 GHz N270
General data
External dimension, width 410 mm
External dimension, height 309 mm
External dimension, depth 96 mm
Installation dimension, width 386.6 mm
Installation dimension, height 285.6 mm
Mounting type Panel PC for mounting in the front panel
Ambient Conditions
Degree of protection IP65 (front), IP20 (back)
Ambient temperature (operation) 0 °C ... 55 °C (Configuration options can affect the operating
temperature. See user manual for details)
Ambient temperature (storage/transport) -40 °C ... 70 °C
Permissible humidity (operation) 5 % ... 95 % (no condensation)
Permissible humidity (storage/transport) 5 % ... 95 % (no condensation)
Vibration (operation) DIN EN 60068-2-6
Shock 15g, 11 ms in accordance with IEC 60068-2-27
Certificates
Certification
Certifications applied for:
Certification Ex:
Address
PLC
Data sheet 6ES7155-6AA00-0BN0
SIMATIC ET 200SP, PROFINET INTERFACE MODULE IM155-6PN
STANDARD, MAX. 32 PERIPHERY MODULES, INCL.
SERVERMODUL, INCL. BUSADAPTER BA 2X RJ45
General information
Product type designation IM 155-6 PN ST with BA 2xRJ45 and server module
Firmware version V3.3
Product function
● I&M data Yes; I&M0 to I&M3
Engineering with
● STEP 7 TIA Portal configurable/integrated as of V13 SP1
version
● STEP 7 configurable/integrated as of version V5.5 SP4 and higher
● PROFINET as of GSD version/GSD revision V2.3 / -
Configuration control
via dataset Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Mains buffering
Input current
Current consumption, max. 450 mA
Inrush current, max. 3.7 A
I²t 0.09 A²·s
Power loss
Power loss, typ. 1.9 W
Address area
Address space per module
● Address space per module, max. 256 byte; per input / output
Address space per station
● Address space per station, max. 512 byte; Dependent on configuration
Hardware configuration
Rack
● Modules per rack, max. 32; + 16 ET 200AL modules
Submodules
● Number of submodules per station, max. 256
Interfaces
Number of PROFINET interfaces 1; 2 ports (switch)
1. Interface
Interface types
● Number of ports 2
● integrated switch Yes
● RJ 45 (Ethernet) Yes; Pre-assembled BusAdapter BA 2x RJ45
● Bus adapter (PROFINET) Yes; Applicable BusAdapters: BA 2x RJ45, BA 2x FC
Functionality
● PROFINET IO Device Yes
● Open IE communication Yes
● Media redundancy Yes; PROFINET MRP
Interface types
RJ 45 (Ethernet)
● 10 Mbps Yes; for Ethernet services
● 100 Mbps Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX)
● Transmission procedure PROFINET with 100 Mbit/s full duplex (100BASE-TX)
● Autonegotiation Yes
● Autocrossing Yes
Protocols
PROFINET IO Device
Services
Isochronous mode
Isochronous operation (application synchronized up No
to terminal)
Interrupts/diagnostics/status information
Status indicator Yes
Alarms Yes
Diagnostic functions Yes
Diagnostics indication LED
● RUN LED Yes; Green LED
● ERROR LED Yes; Red LED
● MAINT LED Yes; yellow LED
● Monitoring of the supply voltage (PWR-LED) Yes; Green LED
● Connection display LINK TX/RX Yes; 2x green link LEDs on BusAdapter
Potential separation
between backplane bus and electronics No
between PROFINET and all other circuits Yes
between supply and all other circuits Yes
Isolation
Isolation tested with 707 V DC between supply voltage and electronics; 1 500 V AC
between Ethernet and electronics
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. 0 °C
● horizontal installation, max. 60 °C
● vertical installation, min. 0 °C
● vertical installation, max. 50 °C
Connection method
ET-Connection
● via BU/BA Send Yes; + 16 ET 200AL modules
Dimensions
Width 50 mm
Height 117 mm
Depth 74 mm
Weights
Weight, approx. 191 g; IM155PN ST with BA 2x RJ45 (mounted)
General information
Hardware product version 01
Firmware version V3.2
Engineering with
● Programming package STEP7 V 5.5 or higher
Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
external protection for power supply lines 2 A min.
(recommendation)
Mains buffering
● Mains/voltage failure stored energy time 5 ms
● Repeat rate, min. 1 s
Input current
Current consumption (rated value) 750 mA
Current consumption (in no-load operation), typ. 150 mA
Power loss
Power loss, typ. 4.65 W
Memory
Work memory
● integrated 384 kbyte
● expandable No
● Size of retentive memory for retentive data 128 kbyte
blocks
Load memory
● Plug-in (MMC) Yes
● Plug-in (MMC), max. 8 Mbyte
● Data management on MMC (after last 10 y
programming), min.
Backup
● present Yes; Guaranteed by MMC (maintenance-free)
● without battery Yes; Program and data
CPU-blocks
Number of blocks (total) 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks
can be reduced by the MMC used.
DB
● Number, max. 1 024; Number range: 1 to 16000
● Size, max. 64 kbyte
FB
● Number, max. 1 024; Number range: 0 to 7999
● Size, max. 64 kbyte
FC
● Number, max. 1 024; Number range: 0 to 7999
● Size, max. 64 kbyte
OB
● Size, max. 64 kbyte
● Number of free cycle OBs 1; OB 1
● Number of time alarm OBs 1; OB 10
● Number of delay alarm OBs 2; OB 20, 21
● Number of cyclic interrupt OBs 4; OB 32, 33, 34, 35
Address area
I/O address area
● Inputs 2 048 byte
● Outputs 2 048 byte
of which distributed
— Inputs 2 048 byte
— Outputs 2 048 byte
Process image
● Inputs 2 048 byte
● Outputs 2 048 byte
● Inputs, adjustable 2 048 byte
● Outputs, adjustable 2 048 byte
● Inputs, default 128 byte
● Outputs, default 128 byte
Subprocess images
● Number of subprocess images, max. 1; With PROFINET IO, the length of the user data is limited to
1600 bytes
Digital channels
● Inputs 16 384
— of which central 1 024
● Outputs 16 384
— of which central 1 024
Analog channels
● Inputs 1 024
— of which central 256
● Outputs 1 024
— of which central 256
Hardware configuration
Number of expansion units, max. 3
Time of day
Clock
● Hardware clock (real-time clock) Yes
● retentive and synchronizable Yes
● Backup time 6 wk; At 40 °C ambient temperature
● Deviation per day, max. 10 s; Typ.: 2 s
● Behavior of the clock following POWER-ON Clock continues running after POWER OFF
● Behavior of the clock following expiry of backup Clock continues to run with the time at which the power failure
period occurred
Operating hours counter
● Number 1
● Number/Number range 0
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1 hour
● retentive Yes; Must be restarted at each restart
Clock synchronization
● supported Yes
● to MPI, master Yes
● to MPI, slave Yes
● to DP, master Yes; With DP slave only slave clock
● to DP, slave Yes
● in AS, master Yes
● in AS, slave Yes
● on Ethernet via NTP Yes; As client
Digital inputs
Number of digital inputs 0
Digital outputs
Number of digital outputs 0
Analog inputs
Number of analog inputs 0
Interfaces
Number of industrial Ethernet interfaces 1; 2 ports (switch) RJ45
Number of RS 485 interfaces 1; Combined MPI / PROFIBUS DP
Number of RS 422 interfaces 0
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
● MPI Yes
● PROFIBUS DP master Yes
● PROFIBUS DP slave Yes
● Point-to-point connection No
MPI
● Transmission rate, max. 12 Mbit/s
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes
— S7 communication, as client No; but via CP and loadable FB
— S7 communication, as server Yes
DP master
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 124
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication Yes; I blocks only
— S7 communication Yes
— S7 communication, as client No
— S7 communication, as server Yes
— Equidistance mode support Yes
— Isochronous mode Yes; OB 61; isochronous mode can only be used alternatively on
PROFIBUS DP or PROFINET IO
— SYNC/FREEZE Yes
2. Interface
Interface type PROFINET
Physics Ethernet RJ45
Isolated Yes
automatic detection of transmission rate Yes; 10/100 Mbit/s
Autonegotiation Yes
Autocrossing Yes
Change of IP address at runtime, supported Yes
Interface types
● Number of ports 2
● integrated switch Yes
Isochronous mode
Isochronous operation (application synchronized up Yes; Via PROFIBUS DP or PROFINET interface
to terminal)
S7 message functions
Number of login stations for message functions, max. 16; Depending on the configured connections for PG/OP and S7
basic communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 300
Ambient conditions
Ambient temperature during operation
● min. 0 °C
● max. 60 °C
Configuration
Configuration software
● STEP 7 Yes; V5.5 or higher
Programming
● Command set see instruction list
● Nesting levels 8
● System functions (SFC) see instruction list
● System function blocks (SFB) see instruction list
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC Yes
— GRAPH Yes
— HiGraph® Yes
Know-how protection
● User program protection/password protection Yes
● Block encryption Yes; With S7 block Privacy
Dimensions
Width 40 mm
Height 125 mm
Depth 130 mm
Weights
Weight, approx. 340 g
General information
Hardware product version 01
Firmware version V3.2
Engineering with
● Programming package STEP 7 V5.5 or higher
Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
external protection for power supply lines 2 A min.
(recommendation)
Mains buffering
● Mains/voltage failure stored energy time 5 ms
● Repeat rate, min. 1 s
Input current
Current consumption (rated value) 750 mA
Current consumption (in no-load operation), typ. 150 mA
Power loss
Power loss, typ. 4.65 W
Memory
Work memory
● integrated 1 024 kbyte
● expandable No
● Size of retentive memory for retentive data 256 kbyte
blocks
Load memory
● Plug-in (MMC) Yes
● Plug-in (MMC), max. 8 Mbyte
● Data management on MMC (after last 10 y
programming), min.
Backup
● present Yes; Guaranteed by MMC (maintenance-free)
● without battery Yes; Program and data
CPU-blocks
Number of blocks (total) 2 048; (DBs, FCs, FBs); the maximum number of loadable blocks
can be reduced by the MMC used.
DB
● Number, max. 2 048; Number range: 1 to 16000
● Size, max. 64 kbyte
FB
● Number, max. 2 048; Number range: 0 to 7999
● Size, max. 64 kbyte
FC
● Number, max. 2 048; Number range: 0 to 7999
● Size, max. 64 kbyte
OB
● Size, max. 64 kbyte
● Number of free cycle OBs 1; OB 1
● Number of time alarm OBs 1; OB 10
● Number of delay alarm OBs 2; OB 20, 21
● Number of cyclic interrupt OBs 4; OB 32, 33, 34, 35
Address area
I/O address area
● Inputs 8 192 byte
● Outputs 8 192 byte
of which distributed
— Inputs 8 192 byte
— Outputs 8 192 byte
Process image
● Inputs 8 192 byte
● Outputs 8 192 byte
● Inputs, adjustable 8 192 byte
● Outputs, adjustable 8 192 byte
● Inputs, default 256 byte
● Outputs, default 256 byte
Subprocess images
● Number of subprocess images, max. 1; With PROFINET IO, the length of the user data is limited to
1600 bytes
Digital channels
● Inputs 65 536
— of which central 1 024
● Outputs 65 536
— of which central 1 024
Analog channels
● Inputs 4 096
— of which central 256
● Outputs 4 096
— of which central 256
Hardware configuration
Time of day
Clock
● retentive and synchronizable Yes
● Backup time 6 wk; At 40 °C ambient temperature
● Deviation per day, max. 10 s; Typ.: 2 s
● Behavior of the clock following POWER-ON Clock continues running after POWER OFF
● Behavior of the clock following expiry of backup Clock continues to run with the time at which the power failure
period occurred
Operating hours counter
● Number 4
● Number/Number range 0 to 3
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1 hour
● retentive Yes; Must be restarted at each restart
Clock synchronization
● supported Yes
● to MPI, master Yes
● to MPI, slave Yes
● to DP, master Yes; With DP slave only slave clock
● to DP, slave Yes
● in AS, master Yes
● in AS, slave Yes
● on Ethernet via NTP Yes; As client
Digital inputs
Number of digital inputs 0
Digital outputs
Number of digital outputs 0
Analog inputs
Number of analog inputs 0
Analog outputs
Interfaces
Number of industrial Ethernet interfaces 1; 2 ports (switch) RJ45
Number of RS 485 interfaces 1; Combined MPI / PROFIBUS DP
Number of RS 422 interfaces 0
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
● MPI Yes
● PROFIBUS DP master Yes
● PROFIBUS DP slave Yes
● Point-to-point connection No
MPI
● Transmission rate, max. 12 Mbit/s
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes
— S7 communication, as client No; but via CP and loadable FB
— S7 communication, as server Yes
DP master
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 124
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication Yes; I blocks only
— S7 communication Yes
— S7 communication, as client No
— S7 communication, as server Yes
— Equidistance mode support Yes
— Isochronous mode Yes; OB 61; isochronous mode can only be used alternatively on
PROFIBUS DP or PROFINET IO
— SYNC/FREEZE Yes
— Activation/deactivation of DP slaves Yes
2. Interface
Interface type PROFINET
Physics Ethernet RJ45
Isolated Yes
automatic detection of transmission rate Yes; 10/100 Mbit/s
Autonegotiation Yes
Autocrossing Yes
Change of IP address at runtime, supported Yes
Interface types
● Number of ports 2
● integrated switch Yes
Media redundancy
Isochronous mode
Isochronous operation (application synchronized up Yes; Via PROFIBUS DP or PROFINET interface
to terminal)
Communication functions
S7 message functions
Number of login stations for message functions, max. 32; Depending on the configured connections for PG/OP and S7
basic communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 300
Ambient conditions
Ambient temperature during operation
● min. 0 °C
● max. 60 °C
Configuration
Configuration software
● STEP 7 Yes; V5.5 or higher
Programming
● Command set see instruction list
● Nesting levels 8
● System functions (SFC) see instruction list
● System function blocks (SFB) see instruction list
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC Yes
— GRAPH Yes
— HiGraph® Yes
Know-how protection
● User program protection/password protection Yes
● Block encryption Yes; With S7 block Privacy
Dimensions
Width 40 mm
Height 125 mm
Depth 130 mm
Weights
Weight, approx. 340 g
Accessories
belongs to product S7-300
Dimensions
Width 160 mm
Height 122 mm
Weights
Weight, approx. 243 g
Accessories
belongs to product SIMATIC S7
Weights
Weight, approx. 131 g
Memory
Type of memory Flash-EPROM
Memory size 2 Mbyte
Number of write/delete operations, min. 100 000
Data retention (after final programming action), min. 10 y
Accessories
belongs to product S7-300 / ET200
Dimensions
Width 24 mm
Height 32 mm
Depth 1.4 mm
Weights
Weight, approx. 2 g
Suitability for use For connecting PROFIBUS nodes to the PROFIBUS bus cable
Transmission rate
Transfer rate / with PROFIBUS DP 9.6 kbit/s ... 12 Mbit/s
Interfaces
Number of electrical connections
● for PROFIBUS cables 2
● for network components or terminal equipment 1
Type of electrical connection
● for PROFIBUS cables Screw
● for network components or terminal equipment Sub-D connector (9-pin)
Type of electrical connection / FastConnect No
Mechanical data
Design of terminating resistor Integrated resistor combination that can be selected with slide
switch
Material / of the enclosure plastic
Locking mechanism design Screw
24.05.2016 5:25:08 AM
6XV18303GH10
SIMATIC NET, PROFIBUS FESTOON CABLE GP FOR FESTOONED CABLING, 2WIRE, SHIELDED, MAX. ACCELERATION: 4 M/QS, MIN. 5 MIO BENDING CYCLES, SOLD BY THE METER, MAX.
CONSIGNMENT: 1000 M, MIN. ORDERING QUANTITY: 20 M
List Price Show prices
Customer Price Show prices
DataSheet in PDF Download
Service & Support (Manuals, Certificates, FAQs...) Download
Product
Article Number (Market Facing Number) 6XV18303GH10
Product Description SIMATIC NET, PROFIBUS FESTOON CABLE GP FOR FESTOONED CABLING, 2WIRE, SHIELDED, MAX.
ACCELERATION: 4 M/QS, MIN. 5 MIO BENDING CYCLES, SOLD BY THE METER, MAX. CONSIGNMENT: 1000 M, MIN.
ORDERING QUANTITY: 20 M
Product family PROFIBUS bus cables
Product Lifecycle (PLM) PM300:Active Product
Price data
Price Group
List Price Show prices
Customer Price Show prices
Surcharge for Raw Materials None
Metal Factor None
Delivery information
Export Control Regulations AL : N / ECCN : N
Delivery Time 1 Day/Days
Net Weight (kg) 0,056 Kg
Product Dimensions (W x L x H) Not available
Packaging Dimension 0,10 x 0,10 x 0,10
Package size unit of measure CM
Quantity Unit 1 Meter
Packaging Quantity 1
Additional Product Information
EAN 4019169400732
UPC 662643227963
Commodity Code 85444920
LKZ_FDB/ CatalogID IK
Product Group 2451
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 01.12.2005
Product class C: products manufactured / produced to order, which cannot be reused or reutilised or be returned against credit.
Obligation Category for taking back electrical and electronic equipment after use No obligation to take back electrical and electronic equipment after use
Classifications
Version Classification
eClass 5.1 27061801
eClass 6 27061801
eClass 7.1 27061801
eClass 8 27061801
eClass 9 27061801
ETIM 4 EC000830
ETIM 5 EC000830
UNSPSC 14 26121609
UNSPSC 15 26121609
https://mall.industry.siemens.com/mall/en/WW/Catalog/Product/6XV18303GH10 1/1
Data sheet 6ES7131-6BH00-0BA0
SIMATIC ET 200SP, DIGITAL INPUT MODULE, DI 16X 24VDC
STANDARD, FITS TO BU-TYPE A0, COLOR CODE CC00,
MODULE DIAGNOSIS
General information
Product type designation ET 200SP, DI 16x24VDC ST, VPE 1
Firmware version V1.1
● FW update possible Yes
usable BaseUnits BU type A0
Color code for module-specific color identification CC00
plate
Product function
● I&M data Yes; I&M0 to I&M3
Engineering with
● STEP 7 TIA Portal configurable/integrated as of V13 SP1
version
● STEP 7 configurable/integrated as of version V5.5 / -
● PCS 7 configurable/integrated as of version V8.1 SP1
● PROFIBUS as of GSD version/GSD revision GSD Revision 5
● PROFINET as of GSD version/GSD revision GSDML V2.3
Operating mode
● DI Yes
● Counter No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 90 mA
Encoder supply
Short-circuit protection No
24 V encoder supply
● 24 V No
● Short-circuit protection No
Power loss
Power loss, typ. 1.7 W
Address area
Address space per module
● Address space per module, max. 2 byte; + 2 bytes for QI information
Hardware configuration
Automatic encoding
● Mechanical coding element Yes
Selection of BaseUnit for connection variants
● 1-wire connection BU type A0
● 2-wire connection BU type A0 + external terminals
● 3-wire connection BU type A0 + external terminals
● 4-wire connection BU type A0 + external terminals
Digital inputs
Number of digital inputs 16
m/p-reading p-reading
Input characteristic curve in accordance with IEC Yes
61131, type 1
Input characteristic curve in accordance with IEC No
61131, type 2
Input characteristic curve in accordance with IEC Yes
61131, type 3
Pulse extension No
Input voltage
● Type of input voltage DC
● Rated value (DC) 24 V
Encoder
Connectable encoders
● 2-wire sensor Yes
— permissible quiescent current (2-wire 1.5 mA
sensor), max.
Isochronous mode
Isochronous operation (application synchronized up No
to terminal)
Interrupts/diagnostics/status information
Diagnostics Yes
Alarms
● Diagnostic alarm Yes
Diagnostic messages
● Diagnostic information readable Yes
● Monitoring the supply voltage Yes
— parameterizable Yes
● Monitoring of encoder power supply No
● Wire-break Yes; Module-wise
● Short-circuit No
● Group error Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
Potential separation
Potential separation channels
● between the channels No
● between the channels and backplane bus Yes
● between the channels and the power supply of No
the electronics
Isolation
Isolation tested with 707 V DC (type test)
Dimensions
Width 15 mm
Height 73 mm
Depth 58 mm
Weights
Weight, approx. 28 g
General information
Product type designation ET 200SP, DQ 16x24VDC/0.5A ST, VPE 1
Firmware version V1.0
● FW update possible Yes
usable BaseUnits BU type A0
Color code for module-specific color identification CC00
plate
Product function
● I&M data Yes; I&M0 to I&M3
Engineering with
● STEP 7 TIA Portal configurable/integrated as of V11 SP2 / V13
version
● STEP 7 configurable/integrated as of version V5.5 SP3 / -
● PCS 7 configurable/integrated as of version V8.1 SP1
● PROFIBUS as of GSD version/GSD revision GSD Revision 5
● PROFINET as of GSD version/GSD revision GSDML V2.3
Operating mode
● DQ Yes
● DQ with energy-saving function No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 60 mA; without load
Output voltage
Rated value (DC) 24 V
Power loss
Power loss, typ. 1 W
Address area
Address space per module
● Address space per module, max. 2 byte
Digital outputs
Number of digital outputs 16
Current-sinking No
Current-sourcing Yes
Short-circuit protection Yes
● Response threshold, typ. 0.7 to 1.3 A
Limitation of inductive shutdown voltage to Typ. L+ (-50 V)
Controlling a digital input Yes
Switching capacity of the outputs
● with resistive load, max. 0.5 A
● on lamp load, max. 5 W
Load resistance range
● lower limit 48 Ω
● upper limit 12 kΩ
Output current
● for signal "1" rated value 0.5 A
● for signal "0" residual current, max. 0.1 mA
Output delay with resistive load
● "0" to "1", typ. 50 µs
● "1" to "0", typ. 100 µs
Parallel switching of two outputs
● for uprating No
● for redundant control of a load Yes
Isochronous mode
Isochronous operation (application synchronized up No
to terminal)
Interrupts/diagnostics/status information
Diagnostics Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
Diagnostic messages
● Monitoring the supply voltage Yes
● Wire-break Yes; Module-wise
● Short-circuit Yes; Module-wise
● Group error Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Channel status display Yes; Green LED
● for channel diagnostics No
● for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
Isolation
Isolation tested with 707 V DC (type test)
Dimensions
Width 15 mm
Weights
Weight, approx. 28 g
General information
Firmware version V1.1
● FW update possible Yes
usable BaseUnits BU type A0, A1
Color code for module-specific color identification CC03
plate
Product function
● I&M data Yes; I&M0 to I&M3
● Scalable measuring range No
Engineering with
● STEP 7 TIA Portal configurable/integrated as of V11 SP2 / V13
version
● STEP 7 configurable/integrated as of version V5.5 SP3 / -
● PCS 7 configurable/integrated as of version V8.1 SP1
● PROFIBUS as of GSD version/GSD revision GSD Revision 5
● PROFINET as of GSD version/GSD revision GSDML V2.3
Operating mode
● Oversampling No
● MSI No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 37 mA; without sensor supply
Encoder supply
24 V encoder supply
● 24 V Yes
● Short-circuit protection Yes
● Output current, max. 20 mA; max. 50 mA per channel for a duration < 10 s
Power loss
Power loss, typ. 0.85 W; Without encoder supply voltage
Address area
Address space per module
● Address space per module, max. 8 byte; + 1 byte for QI information
Analog inputs
Number of analog inputs 4; Differential inputs
permissible input current for current input (destruction 50 mA
limit), max.
Cycle time (all channels), min. Sum of the basic conversion times and additional processing
times (depending on the parameterization of the active channels)
Input ranges (rated values), currents
● 0 to 20 mA Yes
● Input resistance (0 to 20 mA) 100 Ω; + approx. 0.7 V diode forward voltage in 2-wire operation
● -20 mA to +20 mA Yes
● Input resistance (-20 mA to +20 mA) 100 Ω
● 4 mA to 20 mA Yes
● Input resistance (4 mA to 20 mA) 100 Ω; + approx. 0.7 V diode forward voltage in 2-wire operation
Cable length
● shielded, max. 1 000 m
Encoder
Connection of signal encoders
● for voltage measurement No
● for current measurement as 2-wire transducer Yes
— Burden of 2-wire transmitter, max. 650 Ω
● for current measurement as 4-wire transducer Yes
Errors/accuracies
Linearity error (relative to full-scale), (+/-) 0.01 %
Temperature error (relative to full-scale), (+/-) 0.005 %/K
Crosstalk between the inputs, min. 50 dB; Applies to up to + /-5 V overvoltage in other channels
Repeat accuracy in steady state at 25 °C (relative to 0.05 %
full-scale), (+/-)
Operational error limit in overall temperature range
● Current, relative to full-scale, (+/-) 0.5 %
Basic error limit (operational limit at 25 °C)
● Current, relative to full-scale, (+/-) 0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of 70 dB
interference < rated value of input range), min.
● Common mode voltage, max. 10 V
● Common mode interference, min. 90 dB
Isochronous mode
Isochronous operation (application synchronized up No
to terminal)
Interrupts/diagnostics/status information
Diagnostics Yes
Alarms
● Diagnostic alarm Yes
● Limit value alarm No
Diagnostic messages
● Monitoring the supply voltage Yes
● Wire-break Yes; at 4 to 20 mA
● Short-circuit Yes; 2-wire mode: Short-circuit of the encoder supply to ground or
of an input to the encoder supply
Potential separation
Potential separation channels
● between the channels Yes; channel group-specific between 2-wire current input group
and 4-wire voltage input group
● between the channels and backplane bus Yes
● between the channels and the power supply of Yes; only for 4-wire transducer
the electronics
Isolation
Isolation tested with 707 V DC (type test)
Dimensions
Width 15 mm
Weights
Weight, approx. 31 g
General information
Product type designation ET 200SP, AQ 4xU/I Standard
Firmware version V1.1
usable BaseUnits BU type A0, A1
Color code for module-specific color identification CC00
plate
Product function
● I&M data Yes; I&M0 to I&M3
● Scalable output range No
Engineering with
● STEP 7 TIA Portal configurable/integrated as of V11 SP2 / V13
version
● STEP 7 configurable/integrated as of version V5.5 SP3 / -
● PCS 7 configurable/integrated as of version V8.1 SP1
● PROFIBUS as of GSD version/GSD revision GSD Revision 5
● PROFINET as of GSD version/GSD revision GSDML V2.3
Operating mode
● Oversampling No
● MSO No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 150 mA
Power loss
Power loss, typ. 1.5 W
Address area
Address space per module
● Address space per module, max. 8 byte; + 1 byte for QI information
Analog outputs
Number of analog outputs 4
Voltage output, short-circuit current, max. 45 mA
Cycle time (all channels), min. 5 ms
Analog output with oversampling No
Output ranges, voltage
● 0 to 10 V Yes; 15 bit
● 1 V to 5 V Yes; 13 bit
● -5 V to +5 V Yes; 15 bit incl. sign
● -10 V to +10 V Yes; 16 bit incl. sign
Output ranges, current
● 0 to 20 mA Yes; 15 bit
● -20 mA to +20 mA Yes; 16 bit incl. sign
● 4 mA to 20 mA Yes; 14 bit
Connection of actuators
● for voltage output two-wire connection Yes
● for voltage output four-wire connection Yes
● for current output two-wire connection Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 2 kΩ
● with voltage outputs, capacitive load, max. 1 µF
● with current outputs, max. 500 Ω
● with current outputs, inductive load, max. 1 mH
Destruction limits against externally applied voltages and currents
● Voltages at the outputs 30 V
Errors/accuracies
Linearity error (relative to output range), (+/-) 0.03 %
Temperature error (relative to output range), (+/-) 0.005 %/K
Crosstalk between the outputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to 0.05 %
output range), (+/-)
Operational error limit in overall temperature range
● Voltage, relative to output range, (+/-) 0.5 %
● Current, relative to output range, (+/-) 0.5 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output range, (+/-) 0.3 %
● Current, relative to output range, (+/-) 0.3 %
Isochronous mode
Isochronous operation (application synchronized up No
to terminal)
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
Diagnostic messages
● Monitoring the supply voltage Yes
● Wire-break Yes
● Short-circuit Yes
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Channel status display Yes; Green LED
● for channel diagnostics No
● for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
Isolation
Isolation tested with 707 V DC (type test)
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. 0 °C
● horizontal installation, max. 60 °C; Observe derating
● vertical installation, min. 0 °C
● vertical installation, max. 50 °C; Observe derating
Dimensions
Width 15 mm
Weights
Weight, approx. 31 g
General information
Product type designation BU Type A0, BU15-P16+A0+2B, VPE 1
Supply voltage
Rated value (DC) 24 V
external protection for power supply lines Yes; 24 V DC/10 A miniature circuit breaker with type B or C
tripping characteristic
Potential separation
between backplane bus and supply voltage Yes
Isolation
Isolation tested with 707 V DC (type test)
Dimensions
Width 15 mm
Height 117 mm
Weights
Weight, approx. 40 g
General information
Product type designation BU Type A0, BU15-P16+A0+2D, VPE 1
Supply voltage
Rated value (DC) 24 V
external protection for power supply lines Yes; 24 V DC/10 A miniature circuit breaker with type B or C
tripping characteristic
Potential separation
between backplane bus and supply voltage Yes
between the potential groups Yes
Isolation
Isolation tested with 707 V DC (type test)
Dimensions
Width 15 mm
Height 117 mm
Depth 35 mm
CABIN
Abb. 1: Schnappbefestigung auf 35 mm-Tragschiene Abb. 2: Bereichseinengung Abb. 3: Anschlußschema
nach EN 50 022 Fig. 2: Range restriction Fig. 3: Connection diagram
Fig. 1: Clip-on fastening on 35 mm support rail to Fig. 2: Réduction de la plage de température Fig. 3: Schéma de connexion
EN 50 022 Afb. 2: Instelling van het bereik Afb. 3: Aansluitschema
Fig. 1: Fixation par encliquetage sur rail porteur de Bild 2: Anslutningssättet Bild 3: Anslutningsschema
35 mm selon EN 50 022 Fig. 2: Limitazione di campo della temperatura Fig. 3: Schema di allacciamento
Afb. 1: Snapbevestiging op 35 mm montagerail Fig. 2: Ajuste del campo de temperatura Fig. 3: Esquema de conexión
Schaltschrank-
volgens EN 50 022
temperaturregler
Bild 1: Snäppfastsättning på 35 mm profilskena Einstellbereich Regler
enligt EN 50 022
Fig. 1: Fissaggio a scatto su guida a 35 mm secondo °F °C
48V (L2*)
Enclosurethermostat
EN 50 022 60V 24V (L1*) 250V 115V
Régulatuer de température Fig. 1: Clips de sujeción sobre guía soporte N N U P L N N
60
pour armoires électriques de 35 mm según EN 50 022
131
Schakelkasttem- 50 1 2 3 4 5 6 7
peratuurregelaar
113
Apparatskåps-
40
temperaturregulator
95
Termostato per armadi per
quadri di comando 30
77
Termostato para armariosde
SK 3110.000 distribución 20
59
10
41 5
Montageanleitung 1 2 3 4 5 6
Assembly instructions Bereichseinengung im Einstellknopf
Notice de montage
Montage-instruktie
Montageanvisning
Istruzioni di montaggio
Instrucciones de montaje
Enclosures
Power Distribution
Climate Control
IT Infrastructure
Software & Services
U 468 931 012 946-2
5. Aufl. 12.2012 / Id-Nr. 232 588
3237xxx 3241xxx
3238xxx 3243xxx
3239xxx 3244xxx
3240xxx 3245xxx
+KteĮ
The air throughput volume will
be reduced.
Special filter mats are required
for EMC fan-and-filter units
(see accessories).
5.1 Connecting the power supply 5.2 Rotating the voltage connection
Complete the electrical connection by If the position of the voltage connection is
following the wiring plans. not ideally accessible, it may be rotated
through 90° and snapped into position.
+KteĮ To this end, press down on the release
button of the bayonet connection at the rear
For technical data, refer to the
rating plate. of the fan. Units 3238.xxx to 3239.xxx are
released by pulling out the clip (see fig. 4)
Remove the red cover from the electrical of the bayonet connection.
connection.
3238.xxx
3239.xxx
FaJaJdfiHter uJit
– 3237100 3237110 3237124 3238100 3238110 3238124
RA) 7035
FaJaJdfiHter uJit
–
E+
3239100 3239110 3239124
RA) 7035
FaJaJdfiHter
E+
uJit
– 3243.100 3243.110 3244.100 3244.110 3244.140 3245.500 3245.510
RA) 7035
E*C faJaJd
fiHter uJit
– 3243.600 – 3244.600 – – 3245.600 –
RA) 7035
230, 115, 230, 115, 400/460, 200…240 100…130
Rated operating V
1~, 1~, 1~, 1~, 3~, 1~, 1~,
voltage Hz
50/60 50/60 50/60 50/60 50/60 50/60 50/60
Rated current
A 0.37/0.39 0.78/0.8 0.43/0.6 0.9/1.25 0.17/0.21 1.33 2.1
max.
Power
W 70/87 75/90 95/135 100/145 93/140 165 165
consumption
Motor
Pre-fuse T A 4 6 4 6 circuit- 4 6
breaker
Dimensions
Width (B1) x
mm 323 x 323
height (H1)
Required
mounting cut-out mm 292 x 292
(B2 x H2)
Depth (T1) mm 25
Max. installation
mm 118.5 130.5 130.5
depth (T2)
Air throughput,
m³/h 550/600 700/770 900
unimpeded airflow
T2
*KdeH +K B2 x H2 II T2 II
T1
3237xxx 92 x 92 43
3238xxx 124 x 124 58.5
H2
3239xxx 177 x 177 90
3240xxx 224 x 224 107
H1
*KdeH +K m II F II
+KteĮ
EMC protection can only be
guaranteed when using original
Rittal EMC filter media (Model
Nos. 3237.066, 3238.066,
3239.066, 3240.066, 3243.066).
L N PE L N PE L N P
M M M
1~ 3~ 24 V DC
L N PE L1 L2 L3 PE – 24 +
3240.100/.110/.600 3244.140 3237.124
3241.100/.110/.600 3238.124
3239.124
3240.124
3241.124
+10 V 1 3
3
3 4 I max. = 1.1 mA 2 4
15 V 10 V/PWM
2
47 k 47 k 1 uF
3
I max. = 10 mA GND
1
2 2
10 K
Speed 3 1
4
12 V
680 R 4 2
1 1
ZMM 47
100 % PWM n = max.
10 % PWM n = min.
<10 % PWM n=0
www.powerflex.as Telefon 48 47 66 44
Multi-Seal FL 21
Patenteret flange for indføring af flere kabler – runde såvel som flade – i én og samme flange.
Måledata:
www.powerflex.as Telefon 48 47 66 44
1(4)
A/S Løgstrup-Steel
Egeskovvej 16-18
CHECK BEFORE COMMISSIONING DK-3490 Kvistgård
Telephone +45 49 12 75 00
Telefax +45 49 12 75 01
Reg.nr. 47.699
AND
3. Tighten up. All screwed connections (electrical as well as mechanical) must only be
tightened up with a torque wrench (see product catalogue Sec. 04 Page 43 or information
from component supplier).
4. High voltage and megger test (remember to switch off electronic and pilot voltage
circuits and to switch off outgoing circuits).
2. Cleaning, especially insulation parts and ventilation gaps to be cleaned for dust and
moisture.
7. Worn out parts to be replaced, e.g. based on service periods or number of operations.
8. High voltage and megger test (remember to switch off electronic and pilot voltage
circuits, and to switch off outgoing circuits).
10. After heavy short circuits, all the above-mentioned points should be checked and all
damaged parts replaced.
MANUAL
SECTION III, OPERATIONAL LEVEL
Encl. 13
B 09.315
Catalogue No. LR-No. Description Moment Cable Socket ABB connected on busbars
………. 481202-001 Wiedlandkl. 16q 2,4 Nm M5 5 Nm
………. 481202-010 Wiedlandkl. 4q 0,6 Nm M6 9 Nm
………. 481201-006 8JH4112 1.5-16q 2,4 Nm M8 21 Nm
11526 421201-003 8JH4105 16-70q 12,0 Nm M10 42 Nm
M12 70 Nm
M16 170 Nm
Operation Data
Schwitchboard Identification The schwitchboard is installed and
put into operation by:
Drawing No. ……...: Date……..:
Placing……..……...: Company..:
Busbars Connections
Connection / Logstrup X X X X
Flex IBS 25 ( 180A ) 9,4Nm 10,0Nm 30,0Nm 44,0Nm
Flex IBS 50 ( 265A ) 9,4Nm 10,0Nm 30,0Nm 44,0Nm
Logstrup 98230 Washer for FLEX 6mm 6.2x17,8x1.5
Arvid Nilsson 826-08-000 Washer for FLEX 8mm 8,2x24x2,0
Arvid Nilsson 826-10-000 Washer for FLEX 10mm 10.2x30x2,5
Logstrup 98269 Washer for FLEX 12mm 13x30x3
400A > 630A 2x9,4Nm 2x20,0Nm 44,0Nm 75,0Nm 75,0Nm
Arvid Nilsson 826-10-000 Washer for FLEX 10mm 10.2x30x2,5
Logstrup 98269 Washer for FLEX 12mm 13x30x3
FLEX 2004.11.16
MOTOR
19.
CABLE DRUMS/
SLIPRING SYSTEM
20.