An Experimental Study on Concrete Cloth
In this investigation, materials used are as given below: 12% and 14%, beyond which no further improvement can
The OPC of 53 grade conforming to IS: 12269-2013. be obtained.
GGBS (Ground Granulated Blast Furnace Slag) Table 2: GGBS - PP & CC.
conforming to IS: 12089-1987.
Sand confirming zone II as per IS: 383 - 1970. CC (Chemical Composition) PP (Physical Properties)
Crushed coarse aggregates below 4.75mm.
Accelerator (CaCl2) CaO 40% Colour Off - white
Hydrophilic material (Nylon Cloth)
Air Mesh SiO2 35% G 2.85
PVC backing
Adhesive (SR 998) Al2O3 13% Bulk 1200 kg/m3
Density
Fine Aggregates:
Published By:
Blue Eyes Intelligence Engineering
Retrieval Number H6592068819/19©BEIESP 1117 & Sciences Publication
International Journal of Innovative Technology and Exploring Engineering (IJITEE)
ISSN: 2278-3075, Volume-8 Issue-8 June, 2019
Published By:
Blue Eyes Intelligence Engineering
Retrieval Number H6592068819/19©BEIESP 1118 & Sciences Publication
An Experimental Study on Concrete Cloth
Published By:
Blue Eyes Intelligence Engineering
Retrieval Number H6592068819/19©BEIESP 1119 & Sciences Publication
International Journal of Innovative Technology and Exploring Engineering (IJITEE)
ISSN: 2278-3075, Volume-8 Issue-8 June, 2019
12.5
12.36
12 12.04
11.76
11.5
11.33 11.38
11.15 (1:3)
Figure 7: Side view of CC specimen showing bonding of 11
10.826 (1:2)
fibres with the concrete.
10.5 (1:1)
VI. RESULTS OBTAINED
10.142
Compressive Strength Test: 10
9.84
A total of 9 proportions of CC of size 30cm*30cm were
casted and tested for 7 days testing each of 3 specimens are 9.5
laid to get an average value. The results are tabulated as 0 1 2 3 4
below:
Figure 9: Graphical representation of Compressive
strength of Concrete cloth for Cement : Sand mix
Published By:
Blue Eyes Intelligence Engineering
Retrieval Number H6592068819/19©BEIESP 1120 & Sciences Publication
An Experimental Study on Concrete Cloth
Table 7: Compressive test results for Cement & GGBS : Sand mix
2(a) (0.2+0.8):2 600 150 150 1233 493 830.7 0.0616 13.49
2(b) (0.2+0.8):2 600 150 1500 1249 500 819.5 0.0616 13.31
2(c) (0.2+0.8):2 600 150 1500 1222 492 854.9 0.0616 13.88
3(a) (0.2+0.8):1 800 200 1000 1248 500 914.9 0.0616 14.85
3(b) (0.2+0.8):1 800 200 1000 1256 502 867.6 0.0616 14.09
3(c) (0.2+0.8):1 800 200 1000 1236 494 883.3 0.0616 14.34
15
14.86
14.5
14.34
14.09
14
13.88
(1:2)
13.5 13.49
(1:1)
13.31 13.3
(1:3)
13
12.5
12.44
12.15
12
0 1 2 3 4
Figure 10: Graphical representation of Compressive strength of Concrete cloth for Cement & GGBS : Sand mix
Table 8: Compressive test results for Cement & GGBS : Sand & Crushed Aggregates mix
Published By:
Blue Eyes Intelligence Engineering
Retrieval Number H6592068819/19©BEIESP 1121 & Sciences Publication
International Journal of Innovative Technology and Exploring Engineering (IJITEE)
ISSN: 2278-3075, Volume-8 Issue-8 June, 2019
(Cement+GGBS) Crushed
S. : Cement GGBS sand Aggregate Water Compressive
No (Sand+Crushed.Agg) wt wt wt wt CCwt Content Load Area Stress
gm gm gm gm gm ml KN m2 N/mm2
1(a) (0.2+0.8):(0.6+0.4) 160 40 400 600 1350 540 876.6 0.0616 14.23
1(b) (0.2+0.8):(0.6+0.4) 160 40 400 600 1343 537 835.3 0.0616 13.56
1(c) (0.2+0.8):(0.6+0.4) 160 40 400 600 1365 546 847.7 0.0616 13.76
2(a) (0.2+0.8):(0.5+0.5) 600 150 500 500 1380 552 853.1 0.0616 13.85
2(b) (0.2+0.8):(0.5+0.5) 600 150 500 500 1369 547 812.8 0.0616 13.20
2(c) (0.2+0.8):(0.5+0.5) 600 150 500 500 1393 557 806.2 0.0616 13.09
3(a) (0.2+0.8):(0.4+0.6) 800 200 600 400 1295 500 813.2 0.0616 13.20
3(b) (0.2+0.8):(0.4+0.6) 800 200 600 400 1283 513 798.6 0.0616 12.97
3(c) (0.2+0.8):(0.4+0.6) 800 200 600 400 1309 523 820.8 0.0616 13.33
14.4
14.2 14.23
14
13.85
13.8
13.76
(1:3)
13.6
13.56
(1:2)
13.4 (1:1)
13.33
13.2 13.2 13.2
13.09
13 12.97
12.8
0 1 2 3 4
Figure 11: Graphical representation of Compressive strength of Concrete cloth for Cement & GGBS : Sand &
Crushed aggregates
Published By:
Blue Eyes Intelligence Engineering
Retrieval Number H6592068819/19©BEIESP 1122 & Sciences Publication
An Experimental Study on Concrete Cloth
16
14.439
13.56 13.85 13.38
14 13.166
12.63
12.053
12 11.286
10.269
10
6
Compressive Stress
4
Figure 12: Average compressive test results for all proportions in Bar chart.
S. Proportion Tensile Extension Time
No load taken
4.1.2 Tensile strength test: N % sec
1 (1:3) 1 5.1 18
It the maximum stress obtained before it undergoes 2 (1:2) 108 5.3 24
failure. Tensile strength of concrete is very low with respect 3 (1:1) 111 5.9 27
to its compressive strength. It Is taken as 1/10 of its 4 (0.8+0.2):3 134 6.2 28
compressive strength. 5 (0.8+0.2):2 139 6.3 29
6 (0.8+0.2):1 143 6.6 31
7 (0.8+0.2):(0.4+0.6) 121 5.2 19
8 (0.8+0.2):(0.5+0.5) 124 5.5 22
9 (0.8+0.2):(0.6+0.4) 120 5.1 18
Published By:
Blue Eyes Intelligence Engineering
Retrieval Number H6592068819/19©BEIESP 1123 & Sciences Publication
International Journal of Innovative Technology and Exploring Engineering (IJITEE)
ISSN: 2278-3075, Volume-8 Issue-8 June, 2019
160 143 Figure 14: Tensile load test results for all proportions in
134139 bar chart
140 121124120
120 104108111
100
80
60
40
20 Tensile Load (N)
0
7 6.6
6.2 6.3
5.9
6 5.5
5.1 5.3 5.2 5.1
5
2 Extension (%)
Figure 15: Extension (%) of CC results for all proportions in Bar chart
35
31
28 29
30 27
24
25 22
18 19 18
20
15
Figure 16: Time taken for CC to fail under tension for all proportions in bar chart.
Published By:
Blue Eyes Intelligence Engineering
Retrieval Number H6592068819/19©BEIESP 1124 & Sciences Publication
An Experimental Study on Concrete Cloth
VII. DISCUSSIONS
Let us assume the mix proportions as following in order to
make a comfortable view of the observations that are
discussed below,
Cement: Sand 1:3
M1
Cement: Sand 1:2
M2
Cement: Sand 1:1
M3
(Cement+GGBS): Sand (0.8+0.2):3
M4 Figure 17: 3-point flexural testing machine
(Cement+GGBS): Sand (0.8+0.2):2 4.2.2 Permeability test:
M5 Water Permeability test determines the resistance of
(Cement+GGBS): Sand (0.8+0.2):1 specimen or a material against flow of water under
M6 hydrostatic pressure. It is a prominent one to evaluate the
(Cement+GGBS): (Sand+Crushed.Agg) (0.8+0.2) water passage through material when it is subjected to
:(0.4+0.6) M7 hydrostatic pressure. Durability testing is important to
(Cement+GGBS): (Sand+Crushed.Agg) (0.8+0.2) determine the lifespan of your structure. In this project
:(0.5+0.5) M8 the Permeability test is done on the PVC backing layer to
(Cement+GGBS): (Sand+Crushed.Agg) (0.8+0.2) know whether the CC specimen is impervious to water or
:(0.6+0.4) M9 not. In this test we haven’t used any equipment to
measure the property. The test is conducted by simple
observation by pouring a litre of water into the previously
1. From the results, the Average Compressive strength of mould PVC layer with a measuring jar underneath the
CC (concrete cloth) varies as (0%, 9.9%, 17.37%), (0%, mould for about an hour. It is observed that no leakage of
7.36%, 14.32) and (0%, -4%, -5%) for M1, M2, M3, M4, water takes place through the PVC backing layer. So by
M5, M6, M7, M8, M9 respectively considering the this it could be used as a water resisting sheet where
percentage increase with successive three mixes of all losses are more.
three major types of mixing. 4.2.3 Fire Resisting Test:
2. From the tensile strength of Concrete cloth, it depicts A fire-resistance rating typically means the duration for
clearly that the tensile load carrying capacity of the which a passive fire protection system or a material can
individual mixes increases gradually from M1 to M3, M4 withstand a standard fire resistance test.
to M6 but in the last 3 mixes which are having same parts It is a simple test, to show how much time does a substance
but difference is identified when comes to the other part or a material or any specimen can withstand fire i.e.,
of mix is that there is a variation in fine aggregate and basically melting point of the material due to the transfer of
crushed coarse aggregates. (0.5+0.5) = (F.A+CCA) holds heat produced by the burn out of external activity. The test
greater tensile load. is conducted on both the sides of the CC.
3. The behaviour of the percentage extension and time taken On top side,
for the specimen to break when tensioned to failure
It is noticed that the hydrophilic layer is resisting the fire
follows the same path of the tensile load carrying
which is applied externally, shows no tear or burn out of
capacity.
layer takes place and distribution of heat is limited to less
4.2.1 Flexural strength test: area when applied at 1sq.cm area. The test conducted for
about an hour.
It is the highest stress developed in a material before it On bottom side,
reaching its yield strength (Moment of yield) of the material It is observed that the PVC backing failed by melting off.
in a Flexure strength. It is also known as Modulus of As the air mesh is used as a core element in CC but when
Rupture & some also called as Bend Strength or Transverse tested separately catches fire as they are made of polymers
Rupture Strength. 3-Point method is used to test flexural i.e., plastics. But when CC is tested the flame does not have
strength of a specimen. But, as per experimental point of impact on the fabric. The concrete inside it absorbs the heat
view it is observed that the specimens that are casted to test showing a composite material property.
for flexure haven’t gained enough rigidity i.e., the CC
specimen has attained Semi-Rigid State. So, the specimens CONCLUSION:
with all mixes are failed under Flexure. The CC is flexible
even after the concrete inside the CC is hardened.
Published By:
Blue Eyes Intelligence Engineering
Retrieval Number H6592068819/19©BEIESP 1125 & Sciences Publication
International Journal of Innovative Technology and Exploring Engineering (IJITEE)
ISSN: 2278-3075, Volume-8 Issue-8 June, 2019
Text books:
M.S Shetty “Concrete Technology Theory and Practice”.
Journals:
1) “Revolution In Construction: Concrete Cloth”, International Journal
Of Emerging Trends In Engineering And Basic Sciences (IJEEBS),
ISSN (Online) 2349-6967, Volume 2, Issue 4 (Jul-Aug 2015),
PP.102-108.
2) “Study of Canvas Concrete In Civil Engineering Works”.
International Research Journal of Engineering And Technology
(IRJET), E-ISSN: 2395 -0056, Volume: 02, Issue: 09 | Dec-2015, P-
ISSN: 2395-0072.
3) “CONCRETE CLOTH”, International Journal On Applications In
Civil And Environmental Engineering, Volume 1, Issue 3, March
2015, Pp 6-12.
4) “Study Of Concrete Cloth (CC) In Civil Engineering Constructions
Works”, International Conference On Recent Trends In Engineering
Science And Management (ICRTESM-17), 12th To 13th August 2017,