Professional Documents
Culture Documents
K. D. D. S. Kumarage
AM - 13288
8/6/2020
Executive Summary
A storm water pumping station project of 10 m³/S capacity is under construction to safe guard the people
and properties from floods in the canal catchment area of St. Sebastian South. Similarly, another pumping
station of 30 m³/S capacity, is being constructed at the Northern end of the canal.
Generally, the canal flow in both directions with respect to the intensity of the rainfall throughout the year.
One direction towards the southern end which flows through the Beira Lake which spills at the Galle Face
front at +1.8mMSL. The other end flows to the north which flourishes the Kelani River at +0.5mMSL.
Even though, there is another gravity outlet gate, located in the lake, at “McCallum Gate” which is closed
to avoid sea water contamination of the lake.
Furthermore, the authorities have identified that maintaining the water level at +1.6 ~ +1.8mMSL of the
Beira Lake side is mandatory to avoid collapsing of the existing structures adjacent the canal and lake.
Accordingly, the southern end which is the location of “St. Sebastian South Pumping Station” has become
a dead-end due to the water level differences.
Hence, the present design has create a dam across the canal at the pump discharge bay. It has blocked the
possibility of inland transportation that has been properly functioned in ancient era through the waterways
in the greater Colombo city.
However, I found it is possible to maintain the water levels by improving the design of the pumping station
where the boat navigation can be facilitated.
In addition, the continuous flow though the canal improves the biodiversity of the canal while enhancing
the quality of human life. Apart from all, the boat transportation is one of the most economical and
environment friendly method of transport and surely will attract the tourists at a larger scale.
In view of this, the Design Report itself will only be considered on the design, selection, and sizing of the
equipment for the Flood Control/ Storm water Pumping station with possibility for canal transportation.
i
Declaration
I declare that this report was created from the genuine efforts to fulfill the requirements of the mechanical
engineering design for the Professional Review process of the Institution of Engineers of Sri Lanka (IESL).
As per the evaluation guidelines, the report is prepared and presented to elevate the Associate membership
to the Corporate membership category of the Institution. In my understanding, the entire design which is
described in this report has not previously mentioned, remarked, published nor used anywhere in the world.
Nevertheless, it includes ideas or concepts obtained from the previous projects that serve the communities
at a bigger scale all over the world.
ii
Preface
Stormwater or floods creates hazardous situations for the living beings and the properties. These damages
not withstand to a specific area nor for an ethnic group. As per the records of the Ministry of Disaster
management, yearly Sri Lanka losses over five billion Sri Lankan rupees economically while having more
than hundreds of fatalities. So, seeking for a solid solution by addressing all associated concerns is a key
for a sustainable solution.
Generally, the risks do not completely disappear soon after the water levels fallen down. What does most
reports are considered, the physical damages of the disaster while some burning issues continue for a
considerable period. For instance, the viral diseases like, Dengue, Diarrhea or even long lasting life threats
of kidney problems can be spread among the generations of a flood affected areas. And, the psychological
impact on humans by losing their loved ones and belongings are vital matters to be considered. Hence,
having a properly maintained stormwater management system is a must for a country in its long run.
By considering a small scale, the St. Sebastian canal catchment area often faces difficulties by handling
excess water. The area is drained to the canal and it is connected to the Beira Lake and the Kelani River.
With respect to the seasonal water level variations that occurs throughout the year canal discharges water
either the river or the lake. By utilizing the phenomenon, ancient records reveal that a properly functioned
naval system has been established and maintained for the transportation purpose of the city. Some parts
of the old system, including the lock gates can still be witnessed along the canal. Therefore, a solution
should be generated by improving the existence.
However, the recent developments have been forgotten to consider the value of the functioning canal
network until the floods/stormwater becomes a threat. More numbers of people are occupied adjacent the
canal and mega structures were created closer the water bodies without considering the water level
variations or the environment aspects. This way, the problem of the quality of water management has been
fallen drastically.
All in all, the design report is suggested an improvement for the pumping station that can provide
necessary space for the boat transport which can be improved further possibilities as mentioned in the
report.
iii
Acknowledgement
I would like to express my sincere thanks to the Institute of Engineers, Sri Lanka for initiating the
Continuous Professional Development (CPD) Course on Mechanical Engineering Design in order to guide
and assist the Associate members to fulfill the design requirement necessary for acquiring the Corporate
membership of the Institution.
And, I am grateful to the Course Coordinator of the CPD Course, Eng. P. Kalubowila, and the Senior
Engineers who presented during the sessions for devoting their valuable time in preparation of the design
course and improving its quality up to date. Further, their enormous encouragement and the guidance gave
me sufficient energy and the enthusiasm to present the design.
Also, my gratitude goes to all the Lecturers who conducted lectures during the CPD course. Especially, I
am highly grateful to my mentor Eng. T. Jayasekara for allocating his precious time to provide tremendous
guidance to complete this report.
Moreover, I highly appreciate the assistance given by some of the officers of the Sri Lanka Land
Development Reclamation Corporation and Department of Irrigation while preparing the report.
Further, I thank and highly appreciate the engineers of the China Geo Engineering Corporation. Especially
Eng. C. D. Mahagamage and Eng. H. Chathuranga.
Also, I would like to thank one of my senor colleagues who gave novel ideas, Eng. O. U. Pathirathna and
Grundfos Korea Pump manufacturing team namely, Gyung Ho Jung, and Hyun Jo Kim and all others who
helped me to complete the design report.
Last, but not least, I am grateful to my loving wife for encouraging me continuously mostly by providing
ideas from different perspectives when I come across with problems in the conceptual design, and giving
me immense support by allocating enough time required to complete the design, especially during the
Covid-19 quarantine period.
iv
Table of Contents
1. Problem Statement ...........................................................................................................................1
3. Objectives and Envisaged Outcomes from the Suggested Improvement .................................... 5-7
v
1. The problem Statement:
How to upgrade the ongoing pumping station design and select the equipment that can help to
activate the waterway transportation and the circulation of water through the canal to improve the
quality of life while maintaining the critical requirements of the ongoing project?
2. Introduction
The initial plan of the project was to facilitate the naval transport and flood control. However,
subsequently, the requirements were reduced forgoing the naval transport and limiting the pumping
station for the flood control. Accordingly, this study is to critically analyze the design of the ongoing
project and enable to include the naval transportation through the canal while preventing the floods in
the catchment area.
The present project is planned to evacuate the flood waters of the canal catchment area which is
approximately 20km² and the land area is mostly low-lying, with the elevations varying between -2.00
to +6.00 mMSL approximately. At present, the Northern end of the canal (North Lock Gate) at the
Nagalagam Street has a gated outlet to the Kelani River, which functions only when the water level of
the Kelani River is low (low Kelani condition). When the river reaches high levels (high Kelani
condition), the gates are closed to prevent river water entering the land side.
At present, a pumping station is under construction at St. Sebastian North Lock Gates to pump 12 m³/S
capacity for reverse pumping. Which will fulfil the requirement of the canal flushing during the dry
season.
Consequently, the Southern end of the canal (South Lock Gate) near the St. Sebastian Hill at Maradana
is presently a dead end. Since the water level of the Beira Lake is higher (+1.60~1.80 mMSL) than the
normal water level of the canal (+0.6~0.40 mMSL). To prevent sea water inflow to the canal a stop log
arrangement is in place. (A stop log structure)This enables to maintain the water level in the lake at
(+1.60~1.80 mMSL).
By the present design, the LWL and the HWL of the canal are maintained at +0.3mMSL and
+1.3mMSL. However, the water level of the Beira Lake is maintained at +1.8mMSL by the spillover
1
at the Galle face front. The maximum allowed water level is +2.6mMSL. The topography of the
Colombo canal network and the water level variations are depicted in figures 01 & 02.
Figure 2.01
Figure 2.02
The new pumping station will create a barrier to the gravity flow. The plan and the section are as
below.
2
Figure 2.03
Figure 2.04
3
The shortcomings of the present project design are as follows:
1. Boat navigation through the canal up to the lake is not possible in future.
2. Stagnant water throughout the year will create a health hazard and bad smell due to growth
of algae. The aquatic life will also subjected to danger.
3. The present design require a higher discharge pressure (5.5m) resulting a higher power
consumption consequently high cost for the ancillaries (Generators and panels).
4. The pump operation is by two pumps without any standby facility. Therefore a failure of
any pump will lower the install capacity by 50%.
With the suggested improvements, it is expected to create necessary facilities for the canal
transportation by a canal boat which has a length of 57ft (17.37m), beam of less than 06ft (2.08m)
and draught of less than 04ft (1.06m), which can carry twelve people, as shown in the figure below.
Figure 2.04
4
3. Objectives and Envisaged outcomes from the suggested improvement
1. The all facilities of the pumping station shall be planned in the determined land
area. Hence, the determined boundary line of the Pumping Station is shown in the
Site Layout drawing (Annexure
(Section 9). – 03).
Therefore, the Designer shall not request any additional land acquisition from the
Project Owner/ Employer for the installation or the construction of all facilities of
pumping station.
(*Length about 75m and width 11m approximately, yet it not an exact rectangular
canal.)
1. Selection of equipment during the design shall be carried out considering the energy
efficient and the environmentally friendly manner.
2. The efficiency of the pump shall be 75% and performance test criteria shall be
according to the ISO 9906: Grade 2B.
3. Pump motors shall be rated a minimum of 10% higher than the maximum power
required by the pump across the whole of its operating duty.
5
3.1.4. Desired Objectives
1. 10m³/S of the flood waters shall be removed from the St. Sebastian South canal.
The pumping operation shall be restricted not exceed the High-Water Level (HWL)
of the downstream of the canal.
2. Low Water Level (LWL) is defined to ensure the required submergence for the
pumps.
3. The construction of the pumping station shall not obstruct the naval transport
system. Instead, shall be able provide suitable space for the operation with the
support of naval lock gate system.
1. -3.40 mMSL which is the sump bottom shall be maintained as shown in the drawing
(Annexure
(Section 9). – 04).
The St. Sebastian canal will become a navigable path for the narrowboats with a proper
functioning lock gate mechanism. (The design of the lock gate mechanism will not be part
of this report.)
The following benefits are directly associated with the country’s economical and
sociological developments while enhancing the environmental friendly operation.
1. Transportation system can be improved to avoid traffic congestion and to attract both
local and international tourists.
6
2. The circulation of water inside the lake will improve its quality while improving the
aquatic life.
3. The quality of human life of the surrounding area of the canal and lake will improve.
4. Electrical Power consumption of the pumping station will be reduced nearly by a half
compared to the ongoing project.
5. Mechanical and Electrical cost of the pumping station will be reduced comparatively
by its low head immerse operation.
6. With more numbers of pumps the operation is more flexible.
7. Only 20% of pumping capacity will be reduced when a single pump is out of order.
7
4. The Design Approach
The pumping station layout will be enhanced to an arrangement where passenger boats (a
Narrowboat) can pass through the pumping station. These changes are done without violating the
project restrictions like, maximum allowable width of the canal and maximum allowable depth of
the canal for the sump bottom. The general requirements of the Stormwater Pumping Station which
3 under the objectives of the project shall be maintained.
are mentioned in the chapter 4.IV
Initially, the advantages and disadvantages of more number of pumps, pump arrangement and flow
discharge pattern shall be studied.
Then, the conceptual design is evaluated by changing the numbers of pumps and the arrangement
of the pumps.
Finally, an evaluation of though a solution matrix shall be done to select the optimized design.
***Figures 3.01 and 3.02 illustrate the Pumping arrangement and the Flow discharge pattern.
8
Vertical Pump Configuration Horizontal Pump Configuration
Figure 3.01
Figure 3.02
9
For the particular application, it is considered to handle higher volume (above 500 liters
per second) of water carrying solid particles against a low head, typically, less than ten
meters of total head.
Instead of most common centrifugal, radial flow pumps it is advisable to use centrifugal
axial flow pumps by considering the flow rate, pressure and the ability of handling solid
particles. (Please see the 05. Solution)
However, availability of centrifugal axial flow pumps are limited with horizontal
configuration where the pump and motor are combined to serve as one unit. (Submersible
pump)
Advantages:
The discharge head is constant and equal for any numbers of pumps. (Please see the section
05. Solution)
The flow rate can be varied by selecting the combination of pumps.
Option 01
For example, 10 numbers of pumps can be selected with each pump having discharge
capacity of 01 m³/S and discharge head of 5.5m. The pump characteristic curve of the
proposed pump is given below.
According to the curves, duty point lies between 19 degree and 21 degree propeller angles.
As the pumps are customized versions the manufacture will be produced the matching
curve at about 19.5 or 20 degree angles. And, below are the plus points.
10
3. In the event of maintenance or breakdown of one pump, the system will not lose
the operation of the considerable amount of flow during the floods.
4. Since, minimum submergence is low the sump bottom level will be
comparatively less than the present selection.
Figure 4.01
5. Electrical power demand can be optimized since the motors will be working at
optimum efficiency.
6. Electrical equipment appliances cost can be lowered. E.g. Switch gears, cables,
generators, etc
11
Disadvantages:
Option 02
However, at present, pumps of capacity 10 required for the present design is not any of the
established, reputed manufactures. Therefore, the next available option is two pumps which
has 05 m³/S of each at the head of 5.5m
Figure 4.02
According to the curves, the duty point is on 23 degree propeller angle. And, following
points should be noted on the selection.
12
1. The pumping system can only provide 05 m³/S and 10 m³/S which are the 100%
capacity requirement during the flood and the 50%.
2. With the variable speed/frequency drives, the theoretical system variability can
achieve a lower of 2.5 m³/S.
3. In the event of maintenance or breakdown of one pump, the system will be lowered
by 50%.
4. Minimum submergence, which is the decision factor of sump bottom level will be
higher than that of a small pump. (Please see: Pump Manufacturer's design
guidelines. Nominal column diameter represents the pump size and the comparison
was done between KPL700 vs KPL1500)
Figure 4.03
Therefore more numbers of pumps will be beneficial to obtain small flow rates upon
the same discharge head. However, it will increase the cost of the maintenance and the
building footprint.
For this project, there is a limitation on building footprint based on the existing canal
size. (Please see the 05. Solution) Therefore, the number of pumps can go only up
to FIVE.
13
4.2.2 Pumps Arrangement
Figure 4.04
To facilitate the water flow during normal condition, it is required to construct a bypass
canal (Figure 4.04), in vertical configuration. In other words, pumping station itself is
an obstacle to the normal flow with the construction constrains and only will operate
when forced flow is required.
14
In horizontal concept, the facility is covered by lifting the gate where the pump is
mounted on the Gate (Figure 4.04).
15
4.2.3. Flow Discharge Pattern
Figure 4.05
The discharge arrangement is a key factor to influence the discharge head (power
consumption), numbers of ancillaries like valves and expansion joints (cost), safety, and
the ease of control.
16
Advantages: (Pipe Discharge)
a) A controlled discharge can be obtained through the pipe and fittings.
b) Compared to the open discharge safety of falling objects or living things are
improved.
c) Backflow prevention is facilitated.
Disadvantages:
a) Mechanical and Electrical equipment cost will be high.
b) Maintenance cost will be high.
17
5. Selecting the Optimized Solution
Work Flow:
Availability of Pumps for above 500 liters per second will be;
a.) Centrifugal radial flow, double suction volute shape, split casing single stage pumps.
There are pump manufacturers who have high-power pumps as below specified.
Flow rate: up to 40,000 m³/h
Head: up to 250 m
Power: up to 7,000 KW
Max: particle size: 70mm
18
However, the volute casing design is suitable for the higher head requirements with respect to
the best efficiency point of the pump curves. And, the maximum particle size that can be handle
is also a limitation.
There are no openly and widely available design guidelines for the screw pumps and
availability of pump manufacturers are fairly low compared to the axial flow pumps. Also, the
equipment cost high and history of reference projects still new.
Axial flow pumps are available with the submersible motor facility and long-shaft models
whereas motor driven or engine driven.
By considering below factors it was decided to proceed further with the centrifugal axial
flow submersible motor pumps.
Equipment cost
Effect on the construction cost
Maintenance cost and time
Ease of operation.
Widely available in numbers of reference projects (success records)
19
Openly available design guidelines from the pump manufacturers which complies to the
ANSI HI intake structure designs.
Case 01: Canal water level is at LWL and Beira lake water level is at HWL (usually considered
as pump switched off level where the flood situation seems to be controlled, which provides the
maximum static head)
Hs.max = 2.6 – 0.3 = 2.3m
Case 02: Canal water level is at HWL and Beira water level is at HWL (pumping operation will
have to be stopped at this level since the flood situation has reached the maximum
operational level of the pumping operation and the surrounding. Unless, the excess water will
return to the canal by directly or indirectly. Nevertheless, for the specific project location there
is a considerable advantage of the Beira lake spillover which is maintained at +1.8mMSL.
Therefore, at the HWL of both canal and lake side will not significantly effect to the switch off
level unless a flash flood occurs.)
20
Hs.op1 = 2.6 – 1.3 = 1.3m
Case 03: Canal water level is at HWL and Beira water level is at LWL (All pumps are in
operation)
Hs.op2 = 1.8 – 1.3 = 0.5m
Case 04: Duty point where the maximum efficiency occurs, a theoretical point to determine the
best efficiency points at each service points.
Hs. duty = [discharge side (LWL+HWL)/2 - intake side (LWL+HWL)/2] = 1.4m
Selection A: Ten numbers of 01 m³/S capacity pumps with Vertical Pipe discharge pattern.
Points to concern:
Figure 5.01 (ANSI/HI 9.8-2012 Figure 9.8.2.1.4a - Rectangular intake structure layout, page 05)
21
Since the Beira lake (discharge side) flood level is +2.60mMSL, the flat form level of the pumping
station to be defined above that to avoid any damages due to the flooding for the electrical
appliances.
- Flat form level +3.00 is selected.
Column pipe diameter of the pump which is the key point to determine the total length and width
of the pumping bay area.
- Grundfos KPL700 pump model is selected based on the discharge flow 01m³/S and
assuming the total discharge head is 5.5m.
Figure 5.02
Minimum submergence requirement of the pump from the manufacture's design guidelines.
22
KPL 700
PUMP
Figure 5.03
23
Dynamic head calculations:
where,
f - friction factor
l – length of the pipe(m)
D – Diameter of the pipe(m)
V – flow velocity through pipe(m/s)
g – acceleration of gravity(m/s2)
where,
ρ – density of water assumed as 998 kgm-3 at room temperature, (250C)
μ - viscosity of water 0.001Nsm-2 at room temperature, (250C)
24
Figure 4.04
Accordingly,
Head-loss through the pipes (HL pipe ) = 0.016 (10.5/ 0.7) (2.632/ 2x 9.81)
= 0.068m
Local Losses as below (HL LOCAL ) = (HL Tee )+(HL Flap v/v )+(HL EXP.J )+(HL DISCH );
By using Darcy-Weisbach equation for all the necessary pipe fittings as below;
2. Head loss of the Swing check valve. (HL Flap v/v ) = K(V2/2g)
= 0.70m, where K=2 from table Appendix
25
3. Head loss through Expansion joint. (HL EXP.J ) = K(V2/2g)
= 0.35m, where K=1 from table Appendix
4. Discharge Head loss. (HL DISCH ) = K(V2/2g)
= 0.35m, where K=1 from table Appendix
Accordingly, total dynamic head loss, (HL TOTAL ) = (HL pipe ) + (HL LOCAL )
= 1.818m
Therefore, new maximum Total head = Maximum Static Head + (HL TOTAL )
= 5.368m ~ 5.5m
and, new minimum Total head = Minimum Static Head + (HL TOTAL )
= 4.368m
Correspondingly, to meet the design requirements, the pump shall operation on above both points.
In short, the assumption is satisfied for the selections. At this point, it can be considered Grundfos
KPL700 model as the selection 01 for the preliminary design, as mentioned in chapter 4.
Figure 4.05
26
Width of the pumping station = 2 x Pump Diameter x Numbers of pumps + Separation wall widths
= 2 x 700mm x 10 + 250mm x 9
= 16.25m
However, maximum allowed width for any type of construction on the canal is 11m. And, there
is no support for reduction of the total width even the pump placed horizontal.
Selection B: five numbers of 02 m³/S pumps with Vertical Pipe discharge pattern
The next option is to check the feasibility of five numbers of 02 m³/S pumps to fulfill the
requirement(10m³/S). Similar to the above procedure it is to be selected a pump from the
manufacture's data.
Assumptions: (And this can be justified as above calculations if the selection can fulfill the design
constrains, which is the total width of the pumping station.)
Though, there are pump models with the diameter of 800mm and 900mm, those do not fulfill the
best efficiency points as above defined. So, the next available pump model is KPL1000.
27
Figure 4.06
Now,
Width of the pumping station = 2 x Pump Diameter x Numbers of pumps + Separation wall widths
= 2 x 1000mm x 5 + 250 x 4
= 11m
Finally, it is satisfied the maximum allowable width for the construction.
Selection C: five numbers of 02 m³/S pumps with Horizontal and Immerse into water(Gate Pump)
Here, the width of the pumping station is same as above, Selection B. But, the discharge head
will be changed as below.
Total discharge head(Max) = Hs.max (from case 01) + (HL DISCHARGE = as per 02 m³/S)
Hence, HL DISCHARGE = K(V2/2g), where K=1 and V= (2.55 m/S)/ ( π·r2 ), r = 0.5m
= 0.33m
28
Therefore,
Total discharge head(Max) = 2.3 + 0.33
= 2.63m
And,
Total discharge head(Min) = 0.5 + 0.33
= 0.83m
Figure 4.07
Figure 4.08
29
As mentioned in the Chapter 4, this setup reduces the total discharge head compared to the same
pump model with the previous selection. Whereas to reduce the power consumption. And, the
selected pump curve is as shown above.
Selection D: Four numbers of 2.5 m³/S pumps with Vertical Pipe discharge pattern
The next option is to check the feasibility of four numbers of 2.5 m³/S pumps to fulfill the
requirement(10m³/S). Similar to the above procedures it is to be selected a pump from the
manufacture's data.
Assumptions: (And this can be justified as above calculations if the selection can fulfill the design
constrains, which is the total width of the pumping station.)
Figure 4.09
30
Though, the pump manufacture has a pump model which can cater the demand, the pump cure
itself produces less flow sensitivity against flow changes. That defines an older term called “steep
pump curve”. For the specific requirement, flood control it is advisable to maintain higher flow
changes at a low pressure (head) difference. On the other hand, it consumes high-power at the
same operational point.
Correspondingly, below pump model (Figure 4.10) was selected.
Figure 4.10
Then,
Width of the pumping station = 2 x Pump Diameter x Numbers of pumps + Separation wall widths
= 2 x 1200mm x 4 + 250 x 3
= 10.35m
It is also satisfied the maximum allowable width for the construction.
Selection E: Four numbers of 2.5 m³/S pumps with Horizontal and Immerse into water(Gate
Pump)
31
In this selection, the width of the pumping station is same as above, Selection D. But, the
discharge head will be changed as below.
Total discharge head(Max) = Hs.max (from case 01) + (HL DISCHARGE = as per 2.5 m³/S)
Hence, HL DISCHARGE = K(V2/2g), where K=1 and V= (2.21 m/S)/ ( π·r2 ), r = 0.6m
= 0.25m
Therefore, (similar to Figure 4.07)
Total discharge head(Max) = 2.3 + 0.25
= 2.55m
And,
Total discharge head(Min) = 0.5 + 0.25
= 0.75m
Figure 4.11
32
Similar to the Selection C, the power consumption is low and the selected pump curve is as above
shown, Figure 4.11.
Selection F: Three numbers of 3.3 m³/S pumps with Vertical Pipe discharge pattern
It will be another option to check the feasibility of three numbers of 3.3 m³/S pumps to fulfill the
requirement(10m³/S). Similar to the above procedures it is to be selected a pump from the
manufacture's data.
Assumptions: (And this can be justified as above calculations if the selection can fulfill the design
constrains, which is the total width of the pumping station.)
Figure 4.12
33
Then,
Width of the pumping station = 2 x Pump Diameter x Numbers of pumps + Separation wall widths
= 2 x 1200 x 03 + 250 x 2
= 7.7m < 11m
Accordingly, the width of the pumping station is to be reduced with a convergent section.
However, it will be a negative point if the structure is to be built by supporting the naval functions.
Even the horizontal configuration will cost the same width as above. Therefore, it is not required
to include a selection for the report.
Selection G: Two numbers of 05 m³/S pumps with Vertical Pipe discharge pattern
The pump selection is exactly similar with the ongoing project.
Assumptions: (And this can be justified as above calculations if the selection can fulfill the design
constrains, which is the total width of the pumping station.)
Total Discharge Head = 5.5m
Figure 4.12
34
Furthermore, the selection of two pumps as per the ongoing project does not facilitate the naval
function as the building footprint itsef cost more than 7m of space as the Pumbay area. The pumps
are used in the project, KPL1500 which has the nominal diameter of 1500mm. And, there is no
space for the bypass arrangement for the specific project location.
According to the pros & cons and the work flow of selections, the evaluation of concepts will be
as stated below.
Selection A: Ten numbers of 01 m³/S capacity pumps with Vertical Pipe discharge pattern.
Selection B: five numbers of 02 m³/S pumps with Vertical Pipe discharge pattern
Selection C: five numbers of 02 m³/S pumps with Horizontal and Immerse into water(Gate Pump)
Selection D: Four numbers of 2.5 m³/S pumps with Vertical Pipe discharge pattern
Selection E: Four numbers of 2.5 m³/S pumps with Horizontal and Immerse into water(Gate
Pump)
Selection F: Three numbers of 3.3 m³/S pumps with Vertical Pipe discharge pattern
Selection G: Two numbers of 05 m³/S pumps with Vertical Pipe discharge pattern
Numbers of Pumps – Higher the numbers of pumps, more the flexibility in operation.
Pump Arrangement – Horizontal: More suitable for the project.
Flow discharge pattern – Immerse into water will reduce power consumption and allows
sufficient space
Objectives of the Project –
1. Functional Requirement[FR] – Need to be complied
2. Pysical needs[PN] – Need to be complied
3. Performance needs[PFN] – More is better
4. Desired Objectives[DO] – More outcomes will increase the value of the project.
*Passenger boat transportation – Only will get marks.
35
5. Constrains of the project[COP] – Need to be complied
Above bulletins are a summary of the chapter 4. Advantages and disadvantages. (Please refer for
more details.)
SELECTION CRITERIA
Numbers
of Flow Discharge
pumps Pump Arrangement Pattern Objectives of the Project
SELECTION Horizontal Vertical Pipe Immerese FR PN PFN DO COP
A
B
C
D
E
F
G
Table 01
Then, the weights have been given for Two Key Factors.
Function as a Stormwater Pumping station 0.5 and Posibility for the Boat transportation
0.5
36
SELECTION CRITERIA WITH WEIGHTS (PAIRWISE COMPARISON)
Numbers
of Pump Flow Discharge
pumps Arrangement Pattern Objectives of the Project
SELECTION Horizontal Vertical Pipe Immerese FR PN PFN DO COP TOTAL WEIGHT*MARKS
A 0.5 0.5 0.5 0.5 0 0.5 0 0.5 3 156
B 0.5 0.5 0.5 0.5 0.5 0.5 0 0.5 3.5 196
C 1 1 1 1 1 1 1 1 8 592
D 0.5 0.5 0.5 0.5 0.5 0.5 0 0.5 3.5 196
E 1 1 1 1 1 0.5 1 1 7.5 555
F 0.5 0.5 0.5 0.5 0.5 0.5 0 0.5 3.5 196
G 0.5 0.5 0.5 0.5 0.5 0.5 0 0.5 3.5 182
Table 03
Accordingly, the Selection C has been selected to proceed as the optimized design.
Hence, the identified problems are clearly addressed whereas the circulation of water, and navigable
operation at a minimum power requirement of having 75kW five identical pumps for the operation.
Accordingly, the detailed design in the next section is elaborated the design with the suitable major
equipment selection with the specific specifications for the operation of the stormwater pumping station.
37
6. Detailed Design
Correspondingly, the Selection C, the Detailed Design process is as follows;
At this stage, it is required to smoothen the pump performance and match the specific
specifications with the collaboration of the Pump Manufacturer. Which is included of the
operational performances, such as catering of duty point, efficiency, and NPSH (Minimum
Submergence requirement) and the long-lasting of the pump by selecting suitable materials
against the operational conditions.
PUMP
HL FLAP VALVE = K (V2/2g), where K=1 and V= (2.55 m/S)/ (π·r2) and r = 0.5m
= 0.33m
= 2.96 ~ 3m
= 1.16 ~ 1.2m
= 2.1m
38
b.) Flow - 2 m³/S (Total capacity 10 m³/S is to be covered with five pumps)
c.) Expected Pump efficiency – above 75%
d.) Factory acceptance test standard – ISO 9906:2012 Grade B
e.) Installation method – Horizontal Gate Mounted
f.) NPSH available (For the axial flow pumps, minimum submergence available)
= (LWL – Sump bottom level)
= 3700mm
g.) Fluid flow type/ Application – Stormwater/flood
h.) Fluid temperature - 25°C
i.) Density - 998.2 kg/m³
j.) PH level – 5.5 to 8
MATERIAL OF CONSTRUCTION
Normally, the submersible pumps are manufactured within the certain standard materials
that allows to operate them for variety of applications. However, it is a responsibility of
the specifier let manufacturer know the exact quality of fluid that pump is handling through
its life and what kind of environment it is exposed. Hence, below specific materials were
specified to the some components of the pump.
39
pump vane design such that, it allows stormwater to pass through without clogging or
imparting with its considerable free passage of 120mm and the pump approach canal
design. Therefore, it is suitable to select Stainless Steel 316 for the propeller of the pump.
40
outside diameter of a rotating silicon carbide face to give it more mechanical strength and
prevent catastrophic failure.
e.) Bearing life – higher than 20,000hrs
The pumps shall be fitted with bearings greased for life. As, there are two positioned
bearings for rotating the pump shaft. The upper bearing shall be a cylindrical roller or single
ball type bearing to handle radial loads. The lower bearing shall be a double row angular
contact ball bearing to compensate for axial thrust and radial forces. The bearings shall be
lubricated by grease for open type or closed type. The minimum L10 bearing life shall be
60,000 hours at the most efficient operating point.
MOTOR
a.) Rated Voltage – 400V
b.) Rated Power – shall be less than 75kW
Sizing of the motor:
= 42.20 kW
= 42.02/0.75
= 62.26 kW
41
c.) Main Frequency – 50Hz
d.) Number of Phases – Three Phase
e.) Starting Method – VFD
f.) Minimum allowable numbers of starts per hour – 10
g.) Enclosure class (IEC 34-5) – IP 68
h.) Insulation class (IEC 85) – Insulation Class F and Temperature rise Class B
i.) Cable type – PNCT (EPR/Rubber insulated, 0.6/1kV rated cable)
As per the above inputs, the selected pump model is GRUNDFOS KPG.1000.10.T.50.E
and selected pump engineering data sheets are attached as an annexure.
Figure 6.01
42
Figure 6.02
Further to the chapter 5, Solution details, the conceptual design is developed as follows;
Figure 6.02
43
Figure 6.03
As per the guidelines of the pump manufacturer, Grundfos which are complying with the
ANSI-HI 9.8_2012 intake structure is conceptualized.
1. As mentioned in the chapter 5. (Solution 5.3), the width of the pumping station;
= 05 x 02 x 1000mm + 02 x 400mm
= 10,800mm
2. Minimum Submergence requirement of the pump from the Figure 4.03/ 5.03
= 2700mm
44
However, it is to be noted that above submerge requirement is for the vertical
installation and for the horizontal (Gate mounted Pump) installation it should be
modified with the pump manufacturer installation data.
Table 6.01
Figure 6.03
45
According to the table 6.01 and the figure 6.03 the minimum submergence requirement for
a Gate mounted pump is 1750mm, which should be below the low water level (+
0.3mMSL) of the St. Sebastian canal side. Hence, the available submergence is 3750mm
with the maximum allowable sump bottom level of -3.4mMSL.
3. For the Length of the pumping station, it has the freedom to move up to 60m. So, the
placing of major equipment like Automatic Trash Removal System, Stop logs, Penstock,
Naval Lock Gate System have the sufficient space along the canal.
Pump Gate
The pump gate should be a combination of a pump and flood gate and to be used for
purposes to discharge canal into the lake. The condition of design should be which the
pump gate is installed in the waterway.
Figure 6.04
46
Table 6.02
However, I found using a steel structure (a gate) to mount a pump creates additional problems
for the space of the boat transfer. Further, it generate extra costs for the equipment and
maintenance. Also, there is no such requirement of lifting the pumps unless an event of repair
or maintenance. For that emptying the pump pit is the ideal solution.
Figure 6.05
47
Hence, I decided to install the pumps on a concrete bed with the support of the column pipe
which usually use for the vertical installation. In addition, a simple pipe clamp will be used to
increase the holding strength of the system. And that can be fasten the concrete by using the
chemical anchoring.
However, the spacing between pumps, minimum submergence and all the necessary
geographical constraints as advised by the pump manufacturer will remain unchanged.
Accordingly, the pumping stations conceptual drawings are updated and include in section 9.
Drawings.
Boat Navigation
The present allocation for the boat transport is only for a channel as marked in the drawings.
The suggested operation is mentioned in the Section 7.
Figure 6.06
48
Width of the stop log = 4000mm and 6000mm
Height of the stop log = HWL – Canal bed level
= 2.6mMSL – (-1.0mMSL)
= 3.6 ~ 4m
Table 6.03
1. ALLOWABLE STRESSES
For Thickness < 40mm vertical lift gate type stop logs.
1) Tensile stress in axis direction : (for net sectional area) 1,200 kg/cm²
2) Bending stress : 1,200 kg/cm² for beam (for net sectional area)
2. MATERIAL
The material to be used in this construction shall be same as below material or higher.
49
b. Rubber
Material : NEOPRENE
Specific gravity : 1.1-1.4
Materials
AISI 316
1 Screen Frame :
AISI 316
2 Screen Bar:
50
AISI 316+ PE
3 Wiper :
AISI 316
4 Dead Plate
AISI 316
5 Rake:
AISI 316
6 Discharge Chute
AISI 316
7 Cover
AISI 316
8 Chain
Motor
Squirrel cage
1 Type :
F
2 Class of insulation :
380 V, 3 phases, 50 Hz
3 Power Supply :
5.5 kW
4 Motor Power :
IP 55
5 Enclosure Protection :
Table 6.04
6.3.3.2 Conveyor
Specifications:
Details
Description
Horizontal trough type belt
1 Type
conveyor
12m
2 Length
18.6 m3/hr
3 Maximum Capacity
Non inclined (0⁰)
4 Installation Angle
Stainless steel 304
5 Inlet
51
Materials
Stainless steel 304
1 Trough :
Stainless steel 304
2 Screw:
Stainless steel 304
3 Wearing Shoe :
Stainless steel 304
1 Legs
Drive/ motor
Synchronous motor
1 Type :
F
2 Class of insulation :
AC 3phase
3 Power Supply :
3.7 kW
4 Motor Power :
IP 55
5 Enclosure Protection :
Table 6.05
5 tons
2 Carrying Capacity
15 m maximum
3 Lift Height
9.5m
4 Crane Beam Length
12m
5 Gantry Beam length
18 / 6 m/min
6 Traversing Speed
52
30 / 10 m/min
7 Traveling Speed
8 / 1.3 m/min
8 Hoist Speed
Materials
Drive /Motor
F
2 Class of insulation :
400V 3 Phase 50 Hz
3 Power Supply :
IP55
4 Enclosure Protection :
53
7. Control Philosophy
7.1. Pumping station
The pump station has five pump systems utilizing a local pump control panel to manage the
speed of the pumps based on level settings using float switches or other means. Pump speeds are
controlled by the VFD.
When the water level in the well reaches LS-2, the lead pumps turns ON with minimum speed. If
the water level continues to rise, motor speed increases proportional to water level until pump
reaches to its rated speed.
When the water level reaches LS-3, the lag pump turns ON. The lead and/or lag pumps shall
continue to run until the water level falls to the LS-1 (All Pumps– Off) level setting.
LS-0 is a Redundant Off level setting, which will turn off the lead and lag pumps in the event of
failure of the LS-1 level device. The LS-0 level shall be set at the pump minimum submergence
as required by the pump manufacturer.
LS-4 level will be defined as the high level alarm to the station’s telemetry system. The LS-4
level is typically set at the same level or slightly higher level as the LS-3 (Lag Pump –
ON/Alarm) level setting.
The LS-1 (All – Pumps OFF) level will be set at a location meeting the pump manufacturer’s
recommended pump off-elevation but no lower than the minimum submergence requirement of
the pump.
Also, the Pump-ON and Pump-OFF elevations will be based on the calculations to limit the
pump cycle time to less than the specified 10 starts per hour and Limit the well fill times under
design average flow conditions to 30 minutes or less.
54
7.2. Suggested Procedure for the Boat operation.
The channel with the Removable Screen and Conveyor belt is to be used for the boat navigation.
The stop logs, on top of the pumps, at the lake side and the canal side will be removed further the
trash removal system.
55
8. Cost Estimation
Sub
5 total 338,680 16,680,780.00 16,495,938.00
Table 8.01
*Above cost is displayed without VAT
* 01 USD = 180.00LKR, exchange rate.
56
9. Drawings
No Drawing Number TITLE
1 SSPS/DWG/D/G/001 P & I DIAGRAM – NAVIGABLE STORMWATER
PUMPING STATION
2 SSPS/DWG/D/G/002 GENERAL ARRANGEMENT – LAYOUT PLAN
3 SSPS/DWG/D/M/003 GENERAL ARRANGEMENT – PUMPING STATION
SECTION VIEW
4 NA GENERAL ARRANGEMENT – OVERALL LAYOUT
PLAN OF THE ONGING PROJECT
5 NA GENERAL ARRANGEMENT – PUMPING STATION
SECTION VIEW OF THE ONGOING PROJECT
Table 9.1
57
PIT EMPTYING
PUMPS
MOVABLE
GANTRY CRANE
GARBAGE
CONTAINER UPSTREAM
BEIRA LAKE
(STORMWATER DISCHARGE)
STOP LOGS TO
ISOLATE THE
PUMPING
STATION
DURING
MAINTENANCE
OR REPAIR
58
SSPS/DWG/D/P/002
59
SSPS/DWG/D/S/003
60
LAYOUT PLAN
4:1
61
62
10. Maintenance Schedules
10.1. Stormwater Pumps
EQUIPMENT FREQUENCY
NO NAME NATURE OF WORK D W 2W M 3M 6M A
63
1. MAKE SURE ALL THE ELECTRICAL SWITCHES ARE IN "OFF" POSITION BEFORE CAARYING INSPECTIONS ON
ROTATING PARTS.
2. FOLLOW INSPECTIONS FOR ALL THE PUMPS*
3. WAER A PROPER PPE FOR THE SAFETY PURPOSES.
REMARKS/ OBSERVATIONS:
EQUIPMENT FREQUENCY
NO NAME NATURE OF WORK D W 2W M 3M 6M A
64
VISUAL INSPECTION OF RAKES AND CHAINS X
1. MAKE SURE ALL THE ELECTRICAL SWITCHES ARE IN "OFF" POSITION BEFORE CAARYING INSPECTIONS ON
ROTATING PARTS.
2. FOLLOW INSPECTIONS FOR THE TWO SETS.
3. WAER A PROPER PPE FOR THE SAFETY PURPOSES.
4. REMOVE/LIFT RAKE AND CONVEYOR BELT WHEN NOT IN USE.
REMARKS/ OBSERVATIONS:
65
D : DAILY 3M: QUARTERLY
6M: SIX
W: WEEKLY MONTHLY
2W: FORTNIGHTLY A: ANNUALY
M: MONTHLY
EQUIPMENT FREQUENCY
NO NAME NATURE OF WORK D W 2W M 3M 6M A
OVERHEAD
1 GANTRY DAILY HEALTH CHECKS
2 VISUAL INSPECTION X
WEEKLY CHECKS
66
CHECK ANY WEAR MARKS OF PULLEYS OR
WHEELS X
06 MONTHS
1. MAKE SURE ALL THE ELECTRICAL SWITCHES ARE IN "OFF" POSITION BEFORE CAARYING INSPECTIONS ON
ROTATING PARTS.
2. WEAR A PROPER PPE FOR THE SAFETY PURPOSES.
REMARKS/ OBSERVATIONS:
67
11. Suggestions for further improvements.
A properly design screening mechanism that is capable of lifting or removing while not in
operation will improve the ease of operation and risk of falling objects or debris.
By improving the ability of lifting or removing when not in operation of the trash removal
system, can increase the usage of other 4m width channel for the boat navigation.
Having two sets of sludge pumps will improve the time taken to empty the pump pit in
case of maintenance or repair.
A properly designed bracket for holding the stormwater pumps can help to eliminate the
use of steel, column pipes and flanges.
By improving the water quality (with a treatment process) of the lake and canal the water
can be used for gardening or farming purposes with the modern concepts of vertical
farming.
68
12. References and Annexures
The following standards are used for the design of pump intake and the selection of the
pump.
Procedures
Boat Handling
1. https://www.gov.uk/guidance/inland-waterways-and-categorisation-of-waters#safety-
requirements-for-boats-to-operate-on-inland-waters
2. www.black-prince.com
3. https://en.wikipedia.org/wiki/Canals_of_the_United_Kingdom
4. https://en.wikipedia.org/wiki/Narrowboat
69
Automatic Bar Screens and trash removal systems
5. https://www.huber.de/products/screens-and-fine-screens/perforated-plate-and-bar-
screens/huber-multi-rake-bar-screen-rakemaxr.html
6. https://www.chinaboeep.com/Bar-Screen-pl6446456.html
Gate Pumps
7. http://en.eastpump.com/792b9977-f23d-718a-6a81-dbade5bfbe3b/47c4ff47-f08a-d4fe-
1fa8-3eae14a8a24c.shtml
8. http://www.hasuh.co.kr/new2/eng/main/main.php
70
71
72
73