All pressures are absolute values
Project name Run Compr Green Yellow Drycooler Bypass Final Budget 12/13/2019 / All data subject to change
0 Multiplier:
Low temperature 1X
Compressors 4ESL-9K 4ESL-9K 4ESL-9K Total
Motor code 40S (Y) 40S (Y) 40S (Y)
Variable speed drive 69 Hz No No
Cooling cap. compressor 176 kBTU/h 152 kBTU/h 152 kBTU/h 481 kBTU/h
Evaporator capacity 165 kBTU/h 143 kBTU/h 143 kBTU/h 451 kBTU/h
Power input 7.78 kW 6.43 kW 6.43 kW 20.64 kW
Current (460 V) --- 10.55 A 10.55 A ---
Max. current 18.90 A 18.90 A 18.90 A 56.70 A
Project name: Run Compr Green Yellow Drycooler Bypass Final Budget
p, h - diagram
14 Low temperature
50 86 122 158 194 230 266 302
2200
Pressure [psi]
Medium temperature
2000 Critical point 180
Isochors [m³/kg]
1400
54 2 120
C proportion [-]
Vapor
1200 h
1000 90
800
60
600 8 7 15
4 16 13 1 3 2
400 30
11 17 12
200 1
11 12
0
150 200 250 300 350 400 450 500 550 600
Enthalpy [kJ/kg]
Low temperature
Mass flow 4,344 lb/h
Application limits
90
Int. heat exch. ∆Tlog / cap. 0 kBTU/h
Condensing temperature [°F]
0.0 °F
80
External subcooling cap. 0 kBTU/h
70
Desuperheater cap. 9 kBTU/h
60
40 Hz COP/EER LT Stage
50
35 Hz
40 30 Hz COP/EER evap. = [451.4 / (20.6+76.8)] 4.63
30
20
10 SL & ME
0 Motor 2
7
-10
-70 -60 -50 -40 -30 -20 -10 0 10 20 30 40 0.430029
Project name: Run Compr Green Yellow Drycooler Bypass Final Budget
Schematic piping diagram
4: 95 °F
5: 94.5 °F
2: 233.1 °F
16: 16 °F 17: 16 °F
15: 33.3
1: 36 °F
7: 33.3 °F
8: 33.3 °F
13: 36 °F
3: 100 °F
2: 108.3
4: 33.3 1: 20 °F
Page 3 / 5
CO2 Calculation Tool Version 1.54
Project name: Run Compr Green Yellow Drycooler Bypass Final Budget
1 2 3 4 11 12
Pressure [psi] 231.24 396.45 396.45 515.00 231.24 231.24
Temperature [°F] 20.00 108.30 100.00 33.27 -16.00 -6.00
Enthalpy [kJ/kg] 459.12 496.84 491.88 201.73 201.73 443.45
Density [kg/m³] 36.30 52.21 53.42 923.17 39.83
Entropy [kJ/(kg*K)] 2.07 2.11 2.09 1.01 2.01
Vapor proport. [%] 20.70
Medium temperature
1 2 4 5 7 8
Pressure [psi] 396.45 1271.70 1271.70 1271.70 515.00 515.00
Temperature [°F] 36.00 233.08 95.00 94.48 33.27 33.27
Enthalpy [kJ/kg] 450.44 529.94 302.71 300.84 300.84 201.73
Density [kg/m³] 66.65 148.62 643.17 650.60 923.17
Entropy [kJ/(kg*K)] 1.95 2.02 1.33 1.32 1.01
Vapor proport. [%] 43.32
11 12 13 15 16 17
Pressure [psi] 396.45 396.45 396.45 515.00 396.45 396.45
Temperature [°F] 16.00 26.00 36.00 33.27 16.00 16.00
Enthalpy [kJ/kg] 201.73 442.94 450.44 430.47 430.47 434.80
Density [kg/m³] 69.86 66.65 99.87 73.73
Entropy [kJ/(kg*K)] 1.92 1.95 1.84 1.89
Vapor proport. [%] 8.87 98.30
Page 4 / 5
CO 2 Calculation Tool Version 1.54
Project name: Run Compr Green Yellow Drycooler Bypass Final Budget
Remarks
- In case of a compressor failure, the decision on a potential warranty claim remains reserved to a diagnosis and examination of the compressor at the
BITZER factory. Design, operation, and monitoring of the system is in the responsibility of the designer or executing company.
- The heat exchangers are calculated theoretic. Heat losses or heat influence from the surrounding is not considered.
- The optimum high pressure is calculated iterative. Depending on the selection, COP or cooling capacity will be maximized.
- The cooling cap. compressor is calculated by multiplying the mass flow compressor with the enthalpie difference between
state point 1 and 4.
- External variable speed drive: Inverter losses are considered
- All pressure values are absolut pressures.
- More information about subcritical compressors see leaflet KP-120 and operating instruction KB-120.
- More information about transcritical compressors see leaflets KP-130, KP-132 and operating instruction KB-130.
- Please doublecheck the VARIPACK selection in the official BITZER software. Especially when using special motors or DELTA connection, please contact
your BITZER contact.
Status messages
Warning messages
Low temperature:
- CME and TE - Compressors : All data subject to change
Additional notes
Page 5 / 5