Instruction Manual

FCX-A II SERIES TRANSMITTERS

TYPE: FKA
FKG
FKC
FKE
FKB, FKD, FKM

INF-TN4FCXA2b-E
INTRODUCTION
Thank you very much for your purchase of the Fuji FCX-A2 Series Transmitter.
This instruction manual covers version 4 of the FCX series and contains information about the installation,
piping, wiring, operation and maintenance of 9 types belonging to the FCX-A2 series.

• First read this instruction manual carefully until an adequate understanding is required, and then
proceed to installation, operation and maintenance of the FCX-A2 Series transmitter.
• The specifications of the transmitter will be changed without prior notice for further product improve-
ment.
• Modification of the transmitter without permission is strictly prohibited. Fuji will not bear any re-
sponsibility for a trouble caused by such a modification.
• This instruction manual should be kept by a person who is actually using the transmitter.
• After reading this manual, keep it at a place easier to access.
• This manual should be delivered to the end user without fail.
• For detail specifications and outline diagrams, refer to the specifications furnished separately.

The product conforms to the requirements of the Electromagnetic


compatibility Directive 89/336/EEC as detailed within the
technical construction file number TN513035. The applicable
standards used to demonstrate compliance are :

EN 50081-2 : 1993 Conducted and Radiated emissions

EN 50082-2 : 1995 Radiated immunity, ESD and FBT

Manufacturer: Fuji Electric Instruments Co., Ltd.


Type: Described in nameplate on main frame (see Page iv)
Date of manufacture: Described in nameplate on main frame
Product nationality: Japan

© Fuji Electric Instruments Co., Ltd. 2001


Request Issued in February, 2001
• Transcription of a part or the whole of this manual without permission is
prohibited.
• The contents of this manual are subject to change without prior notice.

i
CAUTION ON SAFETY
First of all, read this “Caution on Safety” to ensure correct operation of the transmitter.

• The cautionary descriptions listed here contain important information about safety, so they should be
observed without fail. Those safety precautions are classified into ranks "DANGER" and "CAUTION".

Wrong handling may cause a dangerous situation, in which there is a


DANGER risk of death or heavy injury.

Wrong handling may invite a dangerous situation, in which there is a

CAUTION possibility of medium-level trouble or slight injury or only physical


damage is predictable.

On items listed under “ CAUTION ”, they may also lead to serious accidents depending on circum-
stances, and must be fully observed.

• The signs of prohibition and indication are explained in the following.

PROHIBITION General items which pertain to prohibition (DO NOT)

INDICATION General items which pertain to user’s action

Installation and Piping

DANGER
• Non-explosion-proof transmitter must not be used in a place with explosive gases to prevent serious
accidents such as explosion, fire, etc.

CAUTION
• The transmitter is heavy. Be careful when handling it.
• The transmitter should be installed in a place that meets the operating conditions shown in DS sheet
or this instruction manual.
• Install the transmitter according to the instruction manual. Improper installation may lead to the
cause of fall, trouble or incorrect operation.
• When installing, make sure that the transmitter interior is free from cable chips and other foreign
objects to prevent fire, trouble, or incorrect operation.
• When power is ON, do not change the position of the field indicator in an explosion-proof area.
• When power is ON, do not change the position of the transmission unit in an explosion-proof area.
• When power is ON, do not change the angle of the indicator.
• Main valve used for piping should be selected with the maximum pressure of the process taken into
account (piping parts such as main valve, etc. should be furnished by user). If the main valve and
other parts do not meet the rating, it may result in leakage of gas or liquid which could lead to hazard.
• Pressure pipes to be used must meet the temperature/pressure rating.

ii
Wiring

DANGER
• On explosion-proof type transmitter, its wiring work must be performed according to the required
laws and regulations. Incorrect wiring may cause explosion, fire or other serious accidents.

CAUTION
• Before making wiring work, be sure to turn OFF the main power to prevent electric shocks.
• Use wiring materials of correct rating to prevent fire accidents.
• Connect a power source of correct rating to prevent fire accidents.
• The transmitter should be grounded as specified to prevent electric shocks or incorrect operation.
• After installing the transmitter, firmly close the covers of the transmission unit and terminal box. If
not, rain water enter the transmitter which may result in trouble or incorrect operation.

Adjustment

DANGER
• When using a flame-proof transmitter, do not connect HHC to the transmitter terminals and junction
terminals.

Replacement of Maintenance Parts

DANGER
• When removing an explosion-proof transmitter, turn OFF the main power, then disconnect the piping
and wiring. Do not remove it when the power is ON to prevent serious accident such as explosion,
fire, etc.

iii
CAUTIONS ON USE
Be sure to observe the following instructions

Storage for a long period

Store the transmitter in a dry room at normal temperature and humidity.


Keep protection caps in place at the conduit connection and process connection.

For installation, select an appropriate place

Site at location with minimal vibration, dust and corrosive gas

At a place allowing an adequate space for checkup

Site at location large enough to allow maintenance and checking.

Mounting angle

Mount to a pipe horizontally or vertically.

Attention to overload

Do not apply a pressure outside the specified range.

Other

Besides the above, be sure to observe the cautions given in this manual.

CONFIRMATION OF YOUR SPECIFICATION


The instrument nameplate as shown below is attached at the transmission unit of this transmitter. Before use,
make sure the contents of the nameplate agree exactly with your specifications.

Tag No.

Transmitter
Type
Range

Power Supply
Output 4 – 20mADC
Span Limit

M.W.P.
Ser.No. Mfd.
Made in Japan TK4G5370

iv
CONTENTS
INTRODUCTION ....................................................................................................................... i
CAUTION ON SAFETY ............................................................................................................ ii
CAUTIONS ON USE ............................................................................................................... iv
CONFIRMATION OF YOUR SPECIFICATION .................................................................... iv
CONTENTS ............................................................................................................................... v
1. OUTLINE ........................................................................................................................... 1
2. OPERATING PARTS AND THEIR FUNCTIONS ............................................................. 2
3. OPERATION AND SHUTDOWN ..................................................................................... 4
3.1 Preparation for operation ................................................................................................................... 4
3.2 Operation ............................................................................................................................................ 5
3.3 Shutdown ............................................................................................................................................ 6
4. ADJUSTMENT ................................................................................................................... 8
4.1 Adjustment with HHC ....................................................................................................................... 8
4.1.1 Connection of HHC ...................................................................................................................... 9
4.1.2 Outline of HHC operation ........................................................................................................... 8
4.1.3 Operating procedure ................................................................................................................... 10
• TAG NO. .................................................................................................................................. 10
• TYPE ........................................................................................................................................ 11
• Display of SERIAL NO. .......................................................................................................... 11
• Industrial value unit ................................................................................................................. 12
• Range limit, Range change (LRV, URV) ............................................................................... 13
• Damping adjustment ................................................................................................................ 14
• Output mode ............................................................................................................................. 15
• Burnout direction ..................................................................................................................... 16
• Zero/span adjustment ............................................................................................................... 17
• Calibration of output circuit (D/A) ......................................................................................... 18
• Indication of measured data ..................................................................................................... 19
• Self-diagnosis ........................................................................................................................... 19
• Printer function ........................................................................................................................ 20
• Lock of adjustment function .................................................................................................... 21
• Indication of digital indicator .................................................................................................. 22
• Programmable linearization function ...................................................................................... 25
• Rerange (Set LRV/URL calibration) ....................................................................................... 27
4.2 Zero adjustment by the external screw ............................................................................................ 28
4.3 Span adjustment by the external screw ........................................................................................... 29
4.4 Local adjustment unit with LCD display ........................................................................................ 30
5. MAINTENANCE ............................................................................................................... 33
5.1 Periodic inspection .......................................................................................................................... 33
5.2 Troubleshooting ............................................................................................................................... 34

v
5.3 Replacement of parts ....................................................................................................................... 35
5.4 Adjustment after replacement of unit .............................................................................................. 42
6. INSTALLATION AND PIPING ....................................................................................... 43
6.1 Installation ....................................................................................................................................... 43
6.2 Piping ................................................................................................................................................ 47
6.2.1 Piping of differential pressure (flow) transmitters (type: FKC) .............................................. 47
6.2.2 Piping of pressure and absolute pressure transmitters (types: FKG, FKA) ........................... 51
6.2.3 Piping of level transmitter (type: FKE, FKY) ......................................................................... 53
6.2.4 Piping of remote seal type transmitter (types: FKB, FKD, FKM) .......................................... 56
7. WIRING ............................................................................................................................ 61
7.1 Wiring procedure .............................................................................................................................. 61
7.2 Power voltage and load resistance .................................................................................................. 63
7.3 Grounding ........................................................................................................................................ 64
8. SPARE PARTS .................................................................................................................. 65
A1 BUILT-IN ARRESTER ...................................................................................................... 78
A2 CALIBRATION ................................................................................................................ 70
A3 PARAMETER SETTING PRIOR TO DELIVERY ............................................................ 73
A4 HAZARDOUS LOCATION INSTALLATION INFORMATION ...................................... 74

vi
1. OUTLINE
The FCX-A2 series transmitter detects the differential pressure or pressure of various fluids, converts it
into a current signal of 4 to 20mA DC and transmits it.
All the adjustment functions are incorporated in the transmission unit for making adjustments easily and
exactly.
Transmitter settings (such as range and damping time constant, etc.) can be changed from an HHC (Hand
Held Communicator).

Principle
The operating principle of the FCX-A2 series transmitter is shown in the block diagram below.
The input pressure is changed into an electrostatic capacitance in the detecting unit. The change
proportional to the pressure undergoes conditioning and amplification in the transmission unit, and is
then output as a current of 4 to 20mA DC.

Displacement Capacitance
Input change Measur- Operational Output
differential Diaphragm Sensor ing amplification
circuit circuit current
pressure

Detecting unit Transmission unit

1
2. OPERATING PARTS AND THEIR FUNCTIONS
FCX-A2 Series transmitter

Terminal unit Transmission unit


Analog indicator
CK
connector

+
CK

Detecting unit
Digital indicator
Process connection connector

Indicator
(Digital) (Analog)

OUT
DISP
% 0
FIX % 10

0
Vent/drain 20
ZERO 40 60 80
plug abs
Transmission
unit Zero adjustment
screw

Description of FCX-A2 Series transmitter


Part name Description
Detecting unit Detects pressure, differential pressure or level of fluid.
Transmission unit Converts the detected signal into an output signal.
Vent/drain plug Used for gas discharge or draining.
(Attention should be paid under a high pressure.)
Process connection Connects impulse pipes from the process.
Conduit connection Connects the output cable.
Zero adjustment screw Adjusts zero (Refer to Section 7.)

Transmission unit
Part name Description
Analog indicator connector Used for connecting an analog indicator.
Digital indicator connector Used for connecting a digital indicator.
Indicator (option) Analog or digital indicator, available.

Terminals
Symbol Description
+, – Connects the output cable.
CK+, CK– Used for checking the output or connecting an indicator.
An external terminal used for grounding.

2
Mode indicating function of digital indicator

OUT
DISP
FIX %
ZERO
abs

Mode indication
Mode When indicated When not indicated
% % output Actual scale
ZERO External zero adjustment possible External zero adjustment impossible
DISP Digital indicator display Digital indicator proportional display
OUT output Proportional output
FIX Fixed current mode Measurement mode
Sampling status (Flicker)
abs Absolute pressure Gage pressure
– Output value < Zero Output value Zero
N (a part of unit indicator)

3
3. OPERATION AND SHUTDOWN

3.1 Preparation for operation


Before operating the transmitter, be sure to perform the following checks and procedures. On zero
point check or zero adjustment in hazardous area, do not open terminal cover and do not use HHC.
Use the transmitter indicator and the external adjustment screw.
Preparation procedure

(1) Check for liquid or gas leakage from the process con-
nection, etc. by applying soapy water or the like.
(2) Check the signal wiring according to the “Terminal
block connection diagram” shown in 7.1.
(3) Vent gas from the transmitter in the case of liquid
measurement.

When the plant requires chemical cleaning at the start of operation, be sure to close the
Important valve of the transmitter to prevent entry of cleaning liquid into the pressure receiving
unit.

(4) Perform zero point adjustment.

Zero point check

Turn on the power to the transmitter.


Check the output signal of the transmitter by connecting a DC ammeter across CK+ and CK– of the
terminal block.
After ten minutes or longer, adjust the transmitter output current to 4 mA (zero adjustment). (See
below.)

Zero adjustment
Decrease
(1) Adjustment by zero adjustment screw
Adjust zero point of the transmitter to 4 mA by
turning the zero adjustment screw.
Increase
Note 1) If the transmitter is locked (see section 4.1.3
Operating procedure, Lock of adjustment
function.), this adjustment cannot be made
with the external adjustment screw.
Note 2) When a digital indicator is attached to the
transmitter, make sure that the LCD lamp
“ZERO” is ON.
(2) Adjustment by HHC Fine adjustment : turning slowly
Refer “zero adjustment” explained in section 4.1. Rough adjustment turning quickly

1. After adjustment of the transmitter, it should be kept energized for about 10 seconds
Important to write the adjustment results into memory.
2. Use a blade-edge screwdriver for adjusting the zero adjustment screw.

4
3.2 Operation
(1) Operation of pressure transmitter
Open the valve slowly to apply a pressure. When a pressure is applied, the transmitter is set in
the operating status.

Open

(2) Operation of differential pressure transmitter


Set the operating status by manipulating the manifold valve.
Stop valve
on the low
pressure side

Open Make sure the equalizing valve is open.


Stop valv
on the high
pressure side
Equalizing
valve

Open the stop valve on the high pressure side


Open slowly.

Close

Close the equalizing valve.

5
Open

Finally, open the stop valve on the low pressure side slowly.

Check of operating status

Use a field indicator, receiving instrument or HHC to check the operating status.

3.3 Shutdown
(1) Shutdown of pressure transmitter
Close the valve slowly to stop applying a pressure. The transmitter is set in the measurement
stop status.

Close

6
(2) Shutdown of differential pressure transmitter
Set the shutdown status by manipulating the manifold valve.
Turn off power supply.

Close the stop valve on the high pressure side (H side)


slowly.

Close

Open Open the equalizing valve.

Close

Close the stop valve on the low pressure side (L side)


slowly.

Before a long shutdown, discharge the process fluid and drain completely from the trans-
Important mitter.
This is to protect the transmitter from freezing, corrosion, etc.

7
4. ADJUSTMENT
To operate the FCX-A2 series transmitter, the HHC is used for each adjustment.

4.1 Adjustment with HHC


Startup and usage of the Hand Held Communicator (HHC) are detailed in the instruction manual for
HHC. Please refer to this manual before commencing adjustment.

After adjustment of the transmitter, it should be kept energized for about 10 sec-
Important onds to write the adjustment results into memory.

4.1.1 Connection of HHC


The HHC can be connected to the transmitter, junction terminal or the terminals in the instrument
room.


CK
+
CK

Field device To junction


terminal or
instrumen
To HHC room

Instrument room

Junction terminal Zener barrier Terminal block

DC power supply
16.1 to 45V DC

Load resistor
250Ω or more Note)

Note) See 7.2 “Power voltage


and load resistance”.

In the case of a flameproof transmitter, never connect the HHC to the terminal
DANGER block of the transmitter in hazardous area installations.

8
4.1.2 Outline of HHC operation
The following shows the flow of key operations, explained for FXW Version 6.0
(FXW 1- 3).
FXW prior to Version 6.0 (FXW 1- 3) are not available of operation of FCX-A2
sereis transmitter.
In this case, the user is requested to contract our office for ROM Version Up.
Referential
Classification Display symbol Key symbol page
1 TAG No. INC 1: TAG N MENU 10

2 Type INC 2: TYPE MENU INC 11

3 Display of serial No. INC 3: SERIAL No. MENU INC INC 11

4 Industrial value unit INC 4: UNIT UNIT 12

5 Range limit INC 5: RANGE LIMIT UNIT INC 13

6 Range change INC 6: RANGE RANG 13


(LRV, URV)
7 Damping adjustment INC 7: DAMPING DAMP 14

8 Output mode INC 8: OUTPUT MODE LIN


/
15

9 Burnout direction INC 9: BURNOUT LIN


/
INC 16

A Zero/span adjustment INC A: CALIBRATE CALB 17


Calibration of INC B: OUTPUT ADJ
B OUT 18
output circuit
Indication of INC C: DATA
C DATA 19
measured data

D Self-diagnosis INC D: SELF CHECK DATA INC 19

E Printer function INC E: PRINT DATA INC INC 20

F Lock of adjustment INC F: XMTR EXT.SW DATA INC INC INC 21


functions
Indication of digital
G INC G: XMTR DISPLAY DATA INC INC INC INC 22
indicator
Programmable Lineari-
H INC H: LINEARIZE DATA INC INC INC INC INC 25
zation function
I Rerange (Set LRV/URV INC I: RERANGE DATA INC INC INC INC INC INC 2
calibration)

9
4.1.3 Operating procedure
In case of a flameproof transmitter, never connect the HHC to the terminal block of
transmitter in hazardous area installations.

TAG N°.

0: PUSH MENU KEY


To set the TAG N°. of each field de-
vice, use the procedures shown in
MENU
the following diagram. TAG N°.
1: TAG No 1-1: TAG CHANGE can be inputted up to 26 characters
CHNG CL
FICRA-1234 xxxxxxxxx FICRA-1234 xxxxxxxxx
xxxxxxxxxxxxxxxxxxx xxxxxxxxxxxxxxxxxxx of alphanumeric codes.
< INC > < CHANGE > < ENT > < CL >
INC 1 ENT 2 • After PUSH MENU KEY is displayed,
press the <MENU> key to display
1-1: TAG CHANGE TAG N°.
To menu CL
FICRA-4321 xxxxxxxxx
2 : TYPE xxxxxxxxxxxxxxxxxxx • To make changes press the <CHNG>
CHNG OK?< ENT/CL >
after setting 3 key and the cursor will be displayed
ENT
under display 1 .
1-2: TAG WRITE
FICRA-4321 xxxxxxxxx
• Set the alphanumeric keys as necessary
xxxxxxxxxxxxxxxxxxx under display 2 . To set the alphabet,
4 press the <CHNG ALHA> key first.
Using < > < > keys, cursor position
can be moved.
• At the completion of setting, press the
<ENT> key and a prompt is displayed
check entry under display 2 .
• If the entry is correct, press the
<ENT> key to input it to the field
device under display 3 and 4 and the
initial image 1 is displayed.
• To display TYPE display, press the
<INC> key under display 1 .

10
TYPE

Menu 1 : TAG N°
Type of field device is displayed and
changed (ex. of differential pressure
INC
transmitter).
• After TAG N°. is displayed, press the
2: TYPE
CHNG
2-1: TYPE CHANGE CL
<INC> key to display TYPE image.
FKCXXXXX-XXXXX FKCXXXXX-XXXXX
• To make changes press the <CHNG>
< INC > < CHANGE > < ENT > < CL >
1 ENT 2
key under display 1 and the cursor
INC
will be displayed under display 2 .
2-1: TYPE CHANGE
CL • Set the alphanumeric keys as
FKCXXXXX-XXXXX
CHNG OK?< ENT/CL > necessary under display 2 . To set the
after setting 3 alphabet, press the <CHNG ALHA>
To Menu ENT
key first. Using < > < > keys, cursor
3 : SERIAL N° 2-2: TYPE WRITE
FKCXXXXX-XXXXX
position can be moved.
• At the completion of setting, press the
4 <ENT> key and a prompt is displayed
check entry under display 2 .
• If the entry is correct, press the
<ENT> key to input it to the field
device under display 3 and 4 and the
initial image 1 is displayed.
• To display SERIAL NO., press the
<INC> key under display 1 .

2 : TYPE

INC

3: SERIAL No.
N8G07131
VERSION 1.1
< INC >
Display of SERIAL N°.
INC

4 : UNIT SERIAL N°. and transmitters


software version are displayed.
• After setting TYPE, press the
<INC> key to display SERIAL
NO. and software version of
transmitter.
• By pressing the <INC> key,
UNIT setting image is displayed.

11
Industrial value unit
Menu N°3 :
SERIAL N° Available unit for FCX-A2
INC mmH2 O
cmH 2 O
4: UNIT mH 2 O
kPa g/cm 2
< INC > < CHNG > 1
kg/cm2
Pa
INC CHNG
hPa
4-1: UNIT CHANGE kPa
kPa MPa
(NEXT MPa) mbar
< INC > < ENT > < CL > 2 bar
INC ENT CL psi
< UNIT CHANG >
inH 2 O
ftH 2 O
4-1: UNIT CHANGE mmAq
kPa cmAq
(NEXT MPa)
CHNG OK? < ENT/CL > 3
mAq
ENT CL mmWC
cmWC
mWC
mmHg
4-1: UNIT WRITE
kPa cmHg
mHg
4 inHg
< Torr >
Not suitable unit display < atm >
4-1: UNIT WRITE INC DEC
To menu N° 5 : Pa
RANGE LIMIT NOT SUITABLE
UNIT < CL >
Note: The mark < > is settable for abso-
CL lute pressure transmitter only.
• When pressing <CHNG> under
display 1 , the display for chang-
ing the unit of industrial value 2
appears.
• The desired unit of industrial
value is selectable by using
<INC> or <DEC> under display
2 .
• Display 3 is provided for con-
firming your change.
• Display 4 is for registering the
unit of industrial value.

Important
The unit of industrial value is set according to the range as ordered, but the display
resolution lowers depending on the unit being set.
When 4-1:UNIT CHANGE
Pa
NOT SUITABLE
UNIT <CL>

is displayed upon changing the unit of industrial value, output cannot be displayed in the
engineering unit selected.

In this case, press the CL key and change the engineering unit to a different one.

12
Menu N°4 :
Range limit
UNIT

INC
Indicates the maximum measuring
5: RANGE LIMIT
× × × kPa range of this transmitter.
< INC >
Range change (LRV, URV)
INC

LRV: Lower range value (0% point)


CHNG URV: Upper range value (100% point)
6: RANGE 6-1: RANGE CHANGE
LRV ±× × × . × kPa LRV ±× × × . × kPa
URV ±× × × . × kPa URV ±× × × . × kPa
• When pressing <CHNG> under dis-
< INC > < CHANGE > < LRV > < URV > < CL >
CL play 1 , display changes to the LRV
INC 1 2
LRV CL and URV selection screen.
6-2: RANGE CHANGE Press <LRV> for presenting the dis-
LRV ±× × × . × kPa
URV ±× × × . × kPa play for setting the zero point range
< LRV > < URV > < CL >
3
(display 3 ), or <URV> for present-
URV CL
ing the display for setting the span
6-2: RANGE CHANGE range (display 4 ).
LRV ±× × × . × kPa
URV ±× × × . × kPa
< LRV > < URV > < CL >
• Under displays 3 and 4 , input zero
4 point and span values.
ENT CL
* Press <ENT> after setting LRV
6-2: RANGE CHANGE
To menu N°7 : LRV ±× × × . × kPa and URV.
DAMPING URV ±× × × . × kPa
CHNG OK? < ENT/CL > • When pressing <+/–> under display
5
ENT 3 , 4 , negative value is available.
6-3: RANGE WRITE
LRV ±× × × . × kPa
URV ±× × × . × kPa Selectable setting range
Output (mA)
6 20
Reverse
action
Normal
action Input
URV LRV LRV 4 URV
Maximum measuring range

In case of the actual scale specification with a digital indicator provided, if the
Important range is changed, indicator display does not match. So, setting is required
again in response to the display in the digital indicator (G: XMTR DIS-
PLAY). In case of the actual scale specification with an analog indicator
provided, if the range is changed, indicator display does not match. So, re-
placement of the analog indicator is required.

13
Menu N°6 :
Damping adjustment
RANGE

When process input changes exces-


sively, an appropriate damping time
CHNG
constant should be set.
7: DAMPING 7-1: DAMP CHANGE
0.3SEC 0.3SEC

< INC > < CHANGE > < ENT > < CL >
CL after
INC 1
setting CL
2 Input time constant value under display
ENT 2 , time constant can be changed.
7-1: DAMP CHANGE
1.2SEC

CHNG OK? < ENT/CL >


3
ENT
Selectable time constant value
7-2: DAMP WRITE
1.2SEC No damping ( = measuring period) to
32 sec
To menu N°8 : 4
OUTPUT MODE
Note)
The above damping constants are
used only for the electronics unit.
The detecting unit has its own con-
stants independent of the
electronics unit (for details, refer to
the data sheet).

14
Output mode

(a) The output mode is used to select the


D
LIN/
proportional mode (proportional to
(DP) GP, AP, LL (Liquid Level)
8: OUTPUT MODE 8 : OUTPUT MODE
input differential pressure) or square
XMTR:DP XMTR:GP
OUT=LIN OUT=LIN
root extraction mode (proportinal to
< INC > < CHANGE > < INC > < CHANGE >
1
flow rate) for output signal (4 to 20
CHNG INC CHNG 1
INC
mA). In case of square root
8-1: MODE CHANGE 8-1: MODE CHANGE
XMTR : DP XMTR : GP extraction mode, the cut point and
Menu No.9 OUT=LIN OUT=LIN
< INC > < ENT > < CL > < ENT > < CL > the mode below the cut point can be
2
*1 ENT
<OUTPUT MODE
CL CL set. Under display 2 , press <INC>
In case of OUT=LIN
CHANGE> In case of OUT= SQR or <DEC> for selection of the square
8-1: MODE CHANGE 8-1: MODE CHANGE
XMTR:DP XMTR:DP root extraction mode or proportional
OUT=SQR OUT=LIN
CHNG OK? < ENT/CL > CHNG OK? < ENT/CL > mode.
ENT CL 5 ENT CL 3

8-2: MODE WRITE 8-2: MODE WRITE


XMTR:DP
OUT=SQR
XMTR:DP
OUT=LIN
Change of output mode
6 4
<INC> <DEC>
ENT
a OUT=LIN
8-3: LOW CUT
POINT=××.××%FLOW b OUT=SQR
MODE=  = LINEAR or ZERO
< CHANGE > < CL >
CHNG CL 7
(a) Since display 7 is presented when
8-4: POINT CHANGE the square root extraction mode is
××.××%FLOW *2
selected, the low flow cut point
< ENT > < CL >
ENT CL 8 *1 < INC > < DEC > Available Mode should be set.
8-4: POINT CHANGE 1 OUT=LIN
Cut point is adjustable within the
××.××%FLOW 2 OUT=SQR range of 0.00 to 20.00%. The cut
CHNG OK? < ENT/CL >
ENT CL 9
Note) GP, AP, LL : OUT = LIN only point is used for stabilizing output
*2 0.00% Cut Point 20.00% FLOW
near 0% when the square root extrac-
8-5: POINT WRITE
××.××%FLOW tion mode is selected for output
signal. There are two modes; in one
10
mode, proportional output is selected
8-6: LOW CUT MODE
LINEAR
8-6: LOW CUT MODE
ZERO
for output below a cut point (Fig. A)
< CHANGE > < CL > < CHANGE > < CL >
and in the other mode, output is forc-
CHNG CL 11 CHNG CL 12 ibly reduced to 0% for output below
8-7: LOW CUT MODE a cut point (Fig. B).
< 1 > LINEAR Output Output
< 2 > ZERO
< 1 > < 2 > <CL >
1 2 CL 13

8-7: MODE CHANGE 8-7: MODE CHANGE


LINEAR ZERO

CHNG OK? < ENT/CL > CHNG OK? < ENT/CL >
ENT CL 14 ENT CL 16
Differential Differential
input input
8-8: MODE WRITE 8-8: MODE WRITE
LINEAR ZERO Fig. A: With linear Fig. B: With zero
output selected in output selected in
15 17
low cut mode low cut mode

Under display 13 , linear or zero


output is selectable for output below
the cut point.

15
Burnout direction
CHNG
9: BURNOUT 9-1: BURNOUT
NOT USED < 1 > NOT USED Used for selecting output at occurrence
(HOLD) < 2 > OVER SCALE
< INC > < CHANGE > < 3 > UNDER SCALE of a fault in the detecting unit. Burnout
INC
1 2 direction is selectable under display 2
1
or
2
or
3 • For selection of NOT USED, press
Selection of <1>.
burnout direction
• For selection of OVER SCALE, press
(ex) 3 <2>.
• For selection of UNDER SCALE,
9-2: BURNOUT
A : CALIBRATE
CHANGE press <3>.
UNDER SCALE
< ENT > < CL > CL The meaning of each condition
3 above is as follows.
ENT CL
• NOT USED Not used
9-2: BURNOUT (Output hold)
CHANGE
UNDER SCALE
CHNG OK? < ENT/CL >
Saturation current = 3.8, 20.8mA
ENT 4 Note) Output value just before the occur-
rence of trouble is given in the out-
9-5: BURNOUT CL 9-4: BURNOUT
put hold mode.
Saturate Current
3.8-20.8mA
UNDER SCALE
Y.YmA
• OVER SCALE Over scale
< CL > < CHANGE > < CL > (Output 20.8 to 21.6mA)
CL 6 CHNG 5
Saturation current = 3.8, 20.8mA
CL • UNDER SCALE Under scale
9-5: BURNOUT CHNG (Output 3.2 to 3.8 mA)
UNDER SCALE
Y.YmA Saturation current = 3.8, 20.8mA
< DEC > <ENT > < CL >
7 Burnout Current of FCX-CII series
UNDER SCALE (burnout current) transmitter
Y.YmA Over scale burnout current = 20.8 to
3.8mA
3.7mA ENT CL 21.6mA
3.6mA 9-5: BURNOUT CHNG Under scale burnout current=3.2 to
INC 3.5mA DEC UNDER SCALE
3.4mA Y.YmA 3.8mA
CHNG OK? < ENT/CL >
3.3mA
ENT
8
Saturation current=3.8, 20.8mA
3.2mA

9-7: BURNOUT
Change of Over scale current
Upon pressing <DEC> or <INC> Saturate Current
burnout current can be changed. 3.8-20.8mA 21.6mA
(See above.) < CL > 21.5mA
9 21.4mA
CL 21.3mA
INC DEC
21.2mA
9: BURNOUT
UNDER SCALE 21.1mA
Y.YmA 21.0mA
< INC > < CHANGE > 20.9mA
INC 10 20.8mA
CHNG

A : CALIBRATE

16
Zero/span adjustment
LRV < Zero adjustment >
A: CALIBRATE A-1: CALIBRATE
LRV ×××.××%
Zero and span are adjustable by apply-
×××.× kPa ing an actual pressure.
< INC > < LRV > < URV > < ENT > < CL > 2
1 CL
When pressing <LRV> under display 1
INC
ENT CL the screen for zero adjustment 2
A-1: CALIBRATE
appears, and that for span adjustment 5
URV
LRV ×××.××% appears when pressing <URV>.
×××.× kPa
CHNG OK? < ENT/CL > 3 Under display 2 , after applying actual
ENT pressure equal to zero point, press
<ENT> two times. Zero adjustment will
A-2: CALIBRATING
LRV ×××.××% be over.
×××.× kPa
4
When adjustment is made at any point
other than zero, input the pressure value
< Span adjustment >
at that point at the display of 2 , then
A-3: CALIBRATE
press the <ENT> key at the display of 3
URV ×××.××% while applying a corresponding pres-
×××.× kPa
< ENT > < CL > 5 sure to the transmitter.
CL
CL ENT Under display 5 , after applying actual
pressure equal to desired span, press
A-3: CALIBRATE
URV ×××.××% <ENT> two times. Span adjustment
×××.× kPa
CHNG OK? < ENT/CL > 6
will be over.
ENT When adjustment is made at any point
other than span, input the pressure value
A-4: C ALIBRATING
B : OUTPUT ADJ URV ×××.××% at that point at the display of 5 , then
×××.× kPa
7
press the <ENT> key at the display of 6
while applying a corresponding pres-
sure to the transmitter.
Important
Press LRV or URV at display of 1 .
When the following is displayed, it means that calibration can not be made because
Menu No. H: LINEARIZE is effective. In this case, set INVALID on the panel of No. H: LIN-
EARIZE.
A-1:CALIBRATE
Can’t proceed.
Set Linearize
invalid <CL>

1. Span adjustment should be performed after zero adjustment is completed.


2. When the actual input exceeds the adjustable range, [NOT CALB <CL>] is displayed.
In this case, adjustment is required again.
Adjustable range
Zero adjustment: Within ±40% of maximum span
Span adjustment: Within ±20% of calibrated span
3. When the adjustment point does not meet the following condition,
[SETTING ERR<CL>] is displayed. In this case, adjustment is required again.
Adjustment point setting condition
–1.000%CS (*) PL 100.000%CS(*) 0.000%CS(*) PH 110.000%CS(*)
(Lower adjustment point) - LRV
PL = × 100
URV - LRV
(Higher adjustment point) - LRV
PH = × 100
URV - LRV
(*) : CS (Calibrated Span) is equal to measuring range.

17
Calibration of output circuit (D/A)
G
OUT The output circuit (D/A) should be
calibrated by the following procedure
B: OUTPUT ADJ
when necessary.
< INC > < CHANGE >
INC CHNG Make calibration wiring transmitter ac-
cording to "Calibration" in Appendix
B-1 : OUTPUT SET A2, and calibrate the output circuit
0mA
with the HHC using the following
< LRV/URV/ENT/CL >
1 LRV URV ENT CL
procedure.
(Input of XX.XXXmA at 1 )

B-1: OUTPUT SET B-1: OUTPUT SET B-1: OUTPUT SET When the <LRV> key is pressed at the
4.000mA 20.000mA XX.XXXmA display of 1 , the display 2 for 4mA
CHANGE OK? < ENT/CL > CHANGE OK? < ENT/CL > CHANGE OK? < ENT/CL > current output and its calibration will
2 ENT CL 7 ENT CL 8 ENT CL
appear on the screen. When the
(OTHERS) <URV> key is pressed, the display 7
(4 , 20mA) < OTHERS >
for 20mA current output and its
B-2: OUTPUT MODE B-2: OUTPUT MODE calibration will appear on the screen.
XX.XXXmA XX.XXXmA
CURRENT CONST. CURRENT CONST.
< CALB > < CHNG > < CL > < CHANGE > < CL >
3 9 CHNG
Under display 1 , input a desired value
CALB CHNG CL CL
within a range of 3.8 to 20.8mA and
then press <ENT> two times.
At this input value, a regulated current
B-3: OUTPUT CALIB output is available.
XX.XXXmA CONST.
0mA (EXT.mA)
< ENT > < CL >
Under display 4 , input digital values
4 ENT CL
measured by digital voltmeter.

B-3: OUTPUT CALIB Under display 4 , the output circuit is


XX.XXXmA CONST.
YY.YYYmA (EXT.mA)
calibrated when pressing <ENT>.
CHANGE OK? < ENT/CL >
5 ENT CL

Important
B-4: OUTPUT
XX.XXXmA CONST. After setting and calibrating the constant
YY.YYYmA (EXT.mA)
CALIBRATING current output, be sure to reset the HHC
6
display to the initial display.
Calibration B: OUTPUT ADJ
impossible
B-4: OUTPUT 10appears when the <INC> <CHANGE>
XX.XXXmA CONST. adjustable range is
YY.YYYmA (EXT.mA) exceeded. In this way, the transmitter output is re-
NOT CAL1B. < CL >
10 CL set to the measurement output. It should
be noted that if HHC is removed from
the transmitter loop or the HHC power is
C: DATA turned OFF when the constant current
output has been set, the transmitter
output is retained at the constant current
output.

18
Indication of measured data

B
DATA
The measured value can be indicated.
For more information about operating
procedure, refer to the instruction
C: DATA C-1: DATA
XXX. X %FLOW manual of HHC.
XXXXX kPa
< INC > < ENT > < CHANGE > < CL >
INC ENT CHNG CL

:
"FLOW" is displayed C-1: DATA
when output mode is XXX. XX %FLOW
square root extraction XXXXX kPa
mode. < CHANGE > < CL >

: CHNG CL
" flicker" is displayed
when the communica-
tion between transmitter (HHC is not used for 10 minutes)
and HHC is normal.
STANDBY
Self-diagnosis
PUSH CL KEY

CL Use for displaying the measured tem-


perature in the transmitter and the
ENT alarm information.
D: SELF CHECK D-1:SELF CHECK When pressing <1> on display 2 , the
< 1 > AMP TEMP
< 2 > ALM CHECK temperature in the amplifier (AMP
< INC > < ENT > < 1 > < 2 > <CL >
INC 1 1 2 CL 2 TEMP) is displayed. When pressing
<2>, result of self-diagnosis about
D-2:SELF CHECK transmitter (ALM CHECK) is
TEMP=XXX.X °C
(YYY.Y °F) displayed.
< CL > <INC>
CL 3
Result of diagnosis
D-2: SELF CHECK When the temperature in the amplifier
ALM CHECK
GOOD is normal:
< CL >
D-2: SELF CHECK
CL 4 TEMP= ×××.×ûC

(Temperature alarm is displayed) <CL>


D-2: SELF CHECK
TEMP=XXX.X °C
TEMP.ALARM
When temperature alarm is detected:
D-2: SELF CHECK
INC 5 TEMP= ×××.×ûC
TEMP. ALARM
Temperature is displayed in °C and °F <CL>
alternately at each press of the <INC> key.
When no error has occurred:
(Trouble in transmitter)
D-2: SELFCHECK
E: PRINT D-2: SELF CHECK ALM CHECK
CELL FAULT (C1) GOOD
<CL>
< CL > < INC >
CL 6 When an error has occurred:
D-2: SELF CHECK
CELL FAULT (C1)

<CL> <INC>

For contents of error, refer to "Contents


of message" on the next page.

19
[Contents of message]
As a result of self-diagnosis, the message below is appeared on the LCD display of HHC, when
there are trouble in the transmitter. For each error, its cause and remedy are suggested.
Indication on
Message digital indicator Cause Remedy

CELL FAULT (C1)


FL-1 Error of detecting unit Replacement of detecting unit
(*1)
CELL FAULT (C9)
EEPROM (AMP) FLT FL-2 EEPROM error on amplifier side Replacement of amplifier
EEPROM (CELL) FLT FL-3 EEPROM error on cell side Replacement of detecting unit
TEMP. ALARM T.ALM Transmitter temperature is not Transmitter temperature is
(*2) within the allowable range (–45 normalized.
ZERO to 90°C).
XMTR FAULT FL-1 Amplifier error Replacement of amplifier
OVER Input pressure is 105% or higher
(*2)
of setting range. Properly controlled.
ZERO

Under Input pressure is –1.25% or


(*2)
lower of setting range. Properly controlled.
ZERO

(*1) CELL FALUT (C5) to (C9) are appeared in case of “9” in 6th digit code of FKC.
(*2) Real indication

With Printer Unit


E: PRINT
Printer function

< INC > < ENT >


INC ENT Set Year/Month/Date Usable only when a printer is con-
Time (Hour, Minute)
E-1: PRINT nected.
DATE YY : MM : DD
TIME HH : MM Refer to the instruction manual of
< ENT > < CL >
ENT CL
HHC.
(Indicated when the printer unit is active)
E-2: PRINT OUT

INC E-3: PRINT OUT


PRINT OUT END
< INC >PAPER FEED
< CL >
CL

Paper Feed (Printer)

Without Printer Unit


E: PRINT
NO CONNECTION

< INC >


INC

F : XMTR EXT.SW

20
Lock of adjustment function
CHNG
F: XMTR EXT. SW F-1: XMTR EXT. SW
< 1 > INHIBIT
The zero adjustment function can be
ENABLE < 2 > ENABLE locked by the transmitter adjust screw.
< INC > < CHANGE > < 1 > < 2 > < CL > 2

1 CL
INC
1 CL
When pressing <1> (INHIBIT) under
F-2: XMTR EXT. SW display 2 , the external switch lock
CHANGE
INHIBIT function is activated, and it is released
< ENT > < CL > 3
when pressing <2> (ENABLE).
ENT

F-2: XMTR EXT. SW


CHANGE
INHIBIT
CHNG OK? < ENT/CL > 4

CL
ENT

F-3: XMTR EXT. SW


WRITE
INHIBIT
5

F : XMTR DISPLAY

21
1 2
G : XMTR DISPLAY G : XMTR DISPLAY ±YYYYYY=XMTR DISPLAY Indication of digital indicator
% DISPLAY or ±YYYYYY/±ZZZZZZ at 4mA
X.XX-XXX.XX%YYYY Note 1 UUUUUUU ±ZZZZZZ=XMTR DISPLAY
< INC > < CHANGE > < INC > < CHANGE > at 20mA For digital indicator, either % display
UUUUUUU=XTMR DISPLAY
CHNG INC CHNG
UNIT or actual-scale display is selectable.
INC
Note1) 0.00-100.00%LIN In display on the actual scale, display
0.0-100.0% LIN
3 G-1: DISP. CHANGE values corresponding to 0% (4mA)
0-100% LIN
< 1 > % DISPLAY 0.00-100.00% FLOW
< 2 >ACTUAL DISP. 0.0-100.0% FLOW and 100% (20mA) are settable.
H : LINEARISE < 1 > < 2 > < CL > 0-100% FLOW
1 2 CL

1 or 2
In setting % display, proportional
4 A
mode and square root extraction mode
G-2: DISP. CHANGE is selectable as shown in 4 .
< 1 > % LIN
< 2 > % FLOW In 4 ,
< 1 > < 2 > < CL >
1 2 CL <1> %LIN is displayed in % in the
<2> % FLOW proportional mode
GP, AP, LL
5
<1> % LIN
8
DP (liquid Level) <2> %FLOW is set by % in the square
G-3: DISP. CHANG G-3: DISP. CHANGE G-3: DISP. CHANGE
1 < 1 > 0.00-100.00% 1 < 1 > 0.00-100.00% Can't proceed
root extraction mode (proportional to
2 < 2 > 0.0-100.0% 2 < 2 > 0.0-100.0% XMTR doesn't flow)
< 3 > 0-100% < CL > < 3 > 0-100% < CL > support. < CL >
3 3
CL 4 CL 4 CL 4
In case of pressure transmitter,
6 9 absolute pressure transmitter and
G-4: DISP. CHANGE G-4: DISP. CHANGE 0.00-100.00%
X.XX-XXX.XX%LIN X.XX-XXX.XX%FLOW or 0.0-100.0% level transmitter, <2> % FLOW
or 0-100%
CHNG OK?<ENT/CL> CHNG OK?<ENT/CL> cannot be set in 4 .
ENT CL 4 ENT CL 4
7 10
G-4: DISP. WRITE G-4: DISP. WRITE
X.XX-XXX.XX%LIN X.XX-XXX.XX% FLOW

1 B

22
A When setting the actual-scale
11
G-2 : DISP. CHANGE
display, first select <2> ACTUAL
LRV: 4mA=±YYYYYY Already set value DISP in 3 . Next, after setting the
URV: 20mA=±ZZZZZZ of transmitter
< LRV >< URV ><CL> actual-scale display value ( 11 to 14
LRV URV CL ), perform the actual-scale display
3
12 13 unit setting
G-2 : DISP. CHANGE G-2 : DISP. CHANGE
LRV: 4mA=±YYYYYY LRV: 4mA=±YYYYYY ( 16 to 19 ).
URV: 20mA=±ZZZZZZ URV: 20mA=±ZZZZZZ
< ENT >< URV ><CL> < ENT >< URV ><CL> In case of pressure transmitter,
ENT URV CL
11
ENT URV CL
11
absolute pressure transmitter and
13 12
level transmitter, the flow units can-
14 15
G-2 : DISP. CHANGE G-2 : DISP. CHANGE not be set as shown in 17 .
LRV: 4mA=±YYYYYY LRV: 4mA=±YYYYYY
URV: 20mA=±ZZZZZZ URV: 20mA=±ZZZZZZ After making sure of the setting of
SET OK?< ENT ><CL> SETTING ERR <CL>
the actual scale display 20 , enter
ENT CL CL
11 11 the [ENT] and then data is written
16
G-3 : DISP. CHANGE in the transmitter.
DispUNIT=UUUUUUU Already set value of transmitter
()  = PRESS./LEVEL/FLOW
<CHNG><ENT><CL>
CHNG ENT CL 40 GP, AP, LL
11
19 (liquid Level)
17
G-4 : DISP. CHANGE G-2: DISP. CHANGE
<1>PRESS.<3>FLOW Can’t proceed.
<2>LEVEL XMTR doesn't
<1><2><3><CL> support. < CL >
1 2 3 CL CL 17
16 <3>FLOW
40
<1>PRESS <2>LEVEL DP
18 18 18
G-5 : DISP. CHANGE G-5 : DISP. CHANGE G-5 : DISP. CHANG
DispUNIT=UUUUUUU DispUNIT=UUUUUUU DispUNIT=UUUUUUU
(NEXT XXXXXXX) (NEXT XXXXXXX) (NEXT XXXXXXX)
<INC><ENT><CL> <INC><ENT><CL> <INC><ENT><CL>
INC ENT CL INC ENT CL INC ENT CL
17 17 17
(b) (c)
(a)
19 19
G-5 : DISP. CHANGE G-5 : DISP. CHANGE
<DISP. UNIT CHANGE> DispUNIT=UUUUUUU DispUNIT=UUUUUUU
(a) (b) (c)
mmH2O mm Nm3/s SET OK?<ENT><CL> SET OK?<ENT><CL>
cmH2O cm Nm3/min ENT CL ENT CL
mH2O m Nm3/h 17 17
2 3
g/cm in Nm /d 20 20
2 3
kg/cm ft m /s G-6 : DISP. CHANGE G-6 : DISP. CHANGE
Pa m3/min ±YYYYYY/±ZZZZZZ ±YYYYYY/±ZZZZZZ
hPa m3/h UUUUUUU UUUUUUU
kPa m3/d CHNG OK?<ENT/CL> CHNG OK?<ENT/CL>
MPa t/s
mbar t/min ENT CL ENT CL
11 11
bar t/h 21 21
NC DEC psi t/d
inH2O l/s G-7 : DISP. CHANGE G-7 : DISP. CHANGE
ftH2O l/min ±YYYYYY/±ZZZZZZ ±YYYYYY/±ZZZZZZ
mmAq l/h UUUUUUU UUUUUUU
cmAq l/d
mAq gal/s
mmWC gal/min
cmWC gal/h
mWC gal/d
mmHg ft3/s
cmHg ft3/min 2 B
mHg ft3/h
(UNIT=PRESS. LEVEL) (UNIT=FLOW)
inHg ft3/d
(Torr) bbl/s
(atm) bbl/min
( ) is available bbl/h
for GP and AP. bbl/d

(C) is available for DP.

23
B When setting of % Flow in %display or
Flow unit in actual scale display, low
OUT=SQR at Menu No.8
OUT=LIN at flow cut point and low flow cut mode
Menu No.8
22 23 are displayed ( 22 or 23 ).
G-8 : LOW CUT G-8 : LOW CUT
POINT=XX.XX%FLOW POINT=XX.XX%FLOW
MODE=YYYYYY MODE=YYYYYY When, in the OUTPUT MODE (Menu
<CHANGE><CL> <CL>
No. 8), OUT = SQR is set, already set
CHNG CL CL
1 or 2 1 or 2 low flow cut point and low flow cut
24
G-9 : POINT CHANGE
Note2) CUT POINT mode are displayed ( 23 ).
and
XX.XX%FLOW
CUT MODE With OUT = LIN set, the present low
are set at Menu No.8
<ENT><CL>
YYYYYY=LINEAR or ZERO flow cut point and low flow cut mode
ENT CL
22 are displayed (22). Then, enter
25
G-9 : POINT CHANGE
<CHANGE>, and the setting can be re-
XX.XX%FLOW newed.
CHNG OK?<ENT/CL>
ENT CL
24
26
G-A : POINT WRITE
XX.XX%FLOW

27 27
G-B : LOW CUT MODE G-B : LOW CUT MODE
LINEAR ZERO

<CHANGE><CL> <CHANGE><CL>
CHNG CL CHNG CL
1 or 2 1 or 2

28
G-C : MODE CHANGE
<1>LINEAR
<2>ZERO
<1><2><CL>
1 2 CL
27

29 29
G-D : MODE CHANGE G-B : MODE CHANGE
LINEAR ZERO

CHNG OK?<ENT/CL> CHNG OK?<ENT/CL>


ENT CL ENT CL
28 28
30 30
G-D : MODE WRITE G-B : MODE WRITE
LINEAR ZERO

24
Programmable linearization function
H: LINEARIZE User can set output compensation
INVALID
against the input using 14
< INC > < CHNG >
1
compensation points, (X 1, Y 1), (X 2,
INC CHNG Y2)…(X14, Y14). Each compensation
CL value between (Xn, Yn) and (Xn+1,
CHNG
H-1: LINEARIZE H-2: LINEARIZE Yn+1) is connected by first order
INVALID < 1 > INVALID
< 2 > EFFECTIVE approximate formula.
< INC > < CHNG > < CL > CL < 1 > < 2 > < CL >
2 19
This linearization function is useful to
INC 2
compensate the tank figure in level
CL CL
H-2: LINEARIZE H-3: LINEARIZE
measurement application and the flow
CHANGE rate of steam or gas in flow measure-
POINT 0 EFFECTIVE
< INC > < CHNG > < CL > CHNG OK? < ENT/CL > ment application .
3
CHNG ENT 20 Functions for LINEARIZE are
H-3: LINEARIZE
CHANGE For DP available for FXW Version 6.0 and
POINT 0
< ENT > < CL >
H-3: LINEARIZE
Set Output Mode
upward.
CL 4 LIN-LIN or SQR-SQR
Input the value of
point and press
< CL > By pressing INC at display of 2 , the
21
ENT (POINT XX) display is shifted to the setting of LIN-
ENT CHNG CL
INC EARIZE POINT 3 . Press CHNG at
H-2: LINEARIZE
In the case display of 3 and input POINT XX to
where POINT
XX has been POINT XX be compensated. Then press ENT and
set < INC > < CHNG > < CL >
INC CL 5 the display will be shifted to 5 .
Press INC at display of 5 and the dis-
H-3:LINEARIZE play will be shifted to y for selection of
< 1 >Lin. point:LP
< 2 >Comp value:CV CL <1> Lin. point: LP and <2> Comp.
< 1 > < 2 > < CL >
CL 6 value : CV.
1 2
Select <1> Lin. point: LP at display of
H-4: LINEARIZE H-4: LINEARIZE 6 and input XXX.XX% to each point
LP1 XXX.XX% LP3 XXX.XX%
(LP1-LP ).
< INC > < CNG/ENT/CL > < INC > < CNG/ENT/CL > At the completion of input to all the
7 INC 9
INC
Next compensated points, press ENT twice
15 16 CL parameter 15 16 CL
and the write of LP will be finished.
H-4: LINEARIZE H-4: LINEARIZE
At this time, the display is shifted to 6 .
LP2 XXX.XX% LP14 XXX.XX% Select <2> Comp. point: CV at display
< INC > < CNG/ENT/CL > < INC > < CNG/ENT/CL >
CL
INC 8 INC 10 of 6 and input XXX. XX% to each
for display for display CL point (CV1-CV ) in the same manner
7 15 16
15 16
for display
as noted in <1> LP. At the completion
I : Rerange 11 of input to all the compensated points,
press ENT twice and the write of CV
will be finished.
At the completion of write of compen-
Important sated program for LP/CV, press CL
Note) In the key stroke for Linearization, please set twice at the display of 6 for shifting to
each parameter in the below sequence. 2 . Then, press CHNG for selection of
1. Set the number of compensation points in the <1> INVALID and <2> EFFECTIVE
range of 2 to 14. of 19 . At display of 19 , press <2>
2. Set each linearization option point (LP*) correctly, and the display will be changed to
and write them. EFFECTIVE.
3. Set each compensation value (CV*) correctly, and LP1
write them. Change of compensated LP2
point for LP LP3
4. Set linearization option into EFFECTIVE and INC DEC

write.
LP14

25
6 Change of compensated
point for CV
CL
2 CV1
CV2
H-4:LINEARIZE H-4:LINEARIZE
CV3
INC DEC
CV1 XXX.XX% CV3 XXX.XX%
< INC> < CNG/ENT/CL > < INC> < CNG/ENT/CL >
11 CL INC 13 CV14
Next
INC 17 18 parameter 17 18

H-4:LINEARIZE H-4:LINEARIZE
Important
CV2 XXX.XX% CL CV14 XXX.XX%
< INC> < CNG/ENT/CL > < INC> < CNG/ENT/CL >
When INC is pressed at display of 3 ,
INC 8 INC 14 the following is displayed,
for display H-2: LINEARIZE
for display CL
17 18 11 17 18 POINT 0
SETTING ERR <CL>

or
H-5:LINEARIZE H-5:LINEARIZE When ENT is pressed at display of 4 ,
CHANGE CHANGE the following is displayed,
LPM XXX.XX% LP1-14
< ENT > <CL > CHNG OK? < ENT/CL > H-3: LINEARIZE
CL 15 16 POINT 15
ENT ENT
POINT SET
SETTING ERR <CL>
for display 8
for display 7 , 8 , 9 , 10
CL POINT=2 (number of correction) 14
for display 7 , 8 , 9 , 10
setting err=00 or 01 or 15

When ENT is pressed at display of 15 ,


H-5:LINEARIZE H-5:LINEARIZE
CHANGE CHANGE
the following is displayed,
CVM XXX.XX% CV1-14 H-5: LINEARIZE
< ENT > <CL > CHNG OK? < ENT/CL > CHANGE
LPM 150.01%
ENT CL 17 ENT 18
SETTING ERR <CL>

for display 11, 12 , 13, 14 for display 8 Requirement of setting


CL
-1.25% LP1 < LP2… <
for display 11, 12 , 13, 14 LP14 +110%
Important
When ENT is pressed at display of 17 ,
When ENT is pressed at display the following is displayed,
of @0, the following is displayed, H-5: LINEARIZE
CHANGE
H-3: LINEARIZE CVM 100.01%
Set LINEARIZE SETTING ERR <CL>
Point, LP and CV
correctly. <CL> Requirement of setting
Requirement of setting -100% CV1 < CV2… <
1. LP LP2 LP3…LP8 LP9…LP13 LP14 (In CV14 +100%
the case that LP1-LP14=All Zero, it is inhibited to Before performing the LINEARIZE
be set enable) setting, set either of the following
2. If CVa≠CVb, then it must be LPa < LPb. (Note 1) equations in the OUTPUT mode
(Menu No. 8) and XMTR DISPLAY
3. If LPa =LPb, then it must be CVa= CVb. (Note 1)
(Menu No. G):
Note 1) a, b show next numeral such as a=1 b=2
OUT = LIN SMTR DISP = LIN or
or a=2 b=3 or ………a=13 b=14.
OUT =SQR XMTR DISP = FLOW
or
(Note 1)
the following is displayed.
Note 1) XMTR DISP = FLOW means the
H-3: LINEARIZE
Set OUTPUT MODE settings of % FLOW in %display
LIN-LIN or or of FLOW units in actual-scale
SQR-SQR <CL>
display.

26
I:RERANGE
Rerange (Set LRV/URV calibration)
< INC > < CHNG >
CHNG 1

I-1:RERANGE
(application to level measurement) at
INC
change of level (LRV/URV)
< LRV > < URV > < CL > Functions of RERANGE can be made
2
CL URV CL
CL
LRV with FXW Version 6.0 or upward.
I-2: RERANGE I-2:RERANGE

LRV 0.00%
When the lower range value (LRV) and
URV 100.00%
< ENT > < CL > < ENT > < CL > uppeer range value (URV) need to be
CL 3 CL
ENT ENT 6
adjusted again during measurement of
I-3:RERANGE I-3:RERANGE
CHANGE CHANGE tank level, the measurement levels can
LRV . % URV % be changed at the same time by setting
CHNG OK? < ENT/CL > CHNG OK? < ENT/CL >
ENT 4 ENT 7 the LRV or URV to be adjusted from
I-5:RERANGE I-5:RERANGE FXW.
LRV ± kPa LRV ± kPa
LRV ± kPa URV ± kPa Apply an input pressure required for
< CL > < CL >

CL 5 CL 8 rerange of LRV at display of 3 and


press ENT twice.
1:TAG N°
In this way, the rerange of LRV is com-
pleted, then the new measurement
range LRV and URV, which conforms
Important to the actual input pressure, is dis-
played.
Adjustment point setting condition
When rerange is made at a point other
-1.00% LRV 100.00% 0.00% URV 110.00%
In the case that point is out of setting limit. than 0%, input the set value (PV%) of
(Ex) that point at display of 3 , and press
1-2: RERANGE ENT at display of 4 while applying a
LRV 100.01%
corresponding pressure. In this way,
SETTING ERR <CL> the measurement range can be changed
In case of the actual scale specification with a digital to the input corresponding to that pres-
indicator provided, if the range is changed, indicator sure.
display might not match. So, setting is required again in Apply an input pressure required for
response to the display in the digital indicator rerange of URV at display of 6 and
(G:XMTR DISPLAY).
press ENT twice. The rerange of URV
In case of the actual scale specification with an analog
is completed, then the new
indicator provided, if the range is changed, the scale for
measurement range LRV and URV
indicator might not ensure exact reading.
corresponding to the actual input pres-
sure is displayed. When rerange is
When CHNG is pressed at display of q, the following is
made at a point other than 100%, input
displayed.
1-1: RERANGE the set value (PV%) of that point at dis-
Can’t proceed. play of 6 and press ENT at display of
Set Linearize
invalid. <CL> 7 while applying a corresponding pres-
This means that RERANGE cannot be made because sure. In this way, the measurement
MENU No. H: LINEARIZE is set in EFFECTIVE. In range can be changed to the input cor-
this case, press the CL key and set in INVALID on the responding to that pressure.
panel of No. H: LINEARIZE. Note)The unit of LRV/URV at 5 and 8 are
displayed in theunit selected by Menu No.
4:UNIT.

27
4.2 Zero adjustment by the screw
Zero point of the transmitter is adjustable by the outside screw with the mode setting switch in the
housing set at zero position. The figure shown below is an example of “Mode setting switch” is
attached.
(1) Set the mode setting switch to zero position.

Mode setting switch

Set switch to “zero”


for zero calibration

(2) Apply standard input pressure corresponding to new Lower Range Value
(3) Adjust output to 4mA by turning the outside screw

Decrease

Increase
For zero suppression or elevation, apply the
specified input pressure in advance and adjust the
output to 4mA using the outside screw.

Fine adjustment : turning slowly


Rough adjustment turning quickly

Note 1) If the transmitter is locked, it cannot be adjusted by the external adjustment screw.
Note 2) When a digital indicator is attached to the transmitter, make sure that the LCD lamp “ZERO” is ON.

After adjustment, the transmitter should be kept energized at about 10 seconds to


Important write the adjustment results into memory.

28
4.3 Span adjustment by the screw
The measuring range for each transmitter is determinated according to its type.
Span is changed by the outside screw with the mode setting switch in the housing set at span
position. The figure shown below is an example of “Mode setting switch” is attached.
(1) Set the mode setting switch to span position.

Mode setting switch

Set switch to “span”


for span calibration

(2) Apply standard input pressure corresponding to new Upper Range Value.
(3) Adjust output to 20mA by turning the outside screw
Decrease

Increase

Fine adjustment : turning slowly


Rough adjustment : turning quickly
(4) Then return to applying input pressure of zero again and make sure output is 4mA.

Note 1) If the transmitter is locked, it cannot be adjusted by the external adjustment screw.
Note 2) When a digital indicator is attached to the transmitter, make sure that the LCD lamp “ZERO” is ON.

After adjustment, the transmitter should be kept energized at about 10 seconds to


Important write the adjustment results into memory.

29
4.4 Local adjustment unit with LCD display
1. Outline
When local adjustment unit with LCD display (Parts number is *ZZPFCX4-A055) is installed in the
FCX-AII transmitter, some functions are available without HHC (Hand Held Communicator).
Name of each part in local adjustment unit with LCD display and their functions are indicated
below.

Mode setting
Damping setting
switch
switch

LOCAL/COMM.
LCD display changing switch

Table 1.Functions of Mode setting switch


Positions of Functions of external Output
switch adjustment screw Difference pressure & Flow transmitter Pressure and Absolute pressure
(Model:FKC) transmitter (Model:FKG,FKA)
0 Zero adjustment Proportional to differential pressure Proportional to pressure
1 Span adjustment Proportional to differential pressure Proportional to pressure
2 Locking of function Proportional to differential pressure Proportional to pressure
3 Adj. fixed current 4mA fixed current 4mA fixed current
4 Adj. fixed current 12mA fixed current 12mA fixed current
5 Adj. fixed current 20mA fixed current 20mA fixed current
6 Span adjustment Proportional to flow Proportional to pressure
7 Locking of function Proportional to flow Proportional to pressure

Table 2.Functions of Damping setting switch


Positions of Time constant (sec.)
switch
0 0
1 0,3
2 0,6
3 1,2
4 2,4
5 4,8
6 9,6
7 19,2

Table 3. LOCAL/COMM. Changing switch


Positions of switch Adjustment methods

Adjustments of transmitter are carried


LOCAL out by Mode setting switch and Damping
setting switch.
Adjustments of transmitter are carried
COMM.
out by HHC.

30
2.Selection of transmitter adjustment method

LOCAL/COMM. Changing switch decides the method of FCX-AII transmitter adjustment. If switch
is set to “COMM.” side, adjustment of transmitter is carried out by HHC. This method is explained
in instruction manual.
If switch is set to “LOCAL” side, adjustment of transmitter is carried out by Mode setting switch
and Damping setting switch.
This method is explain below.

3.Range change procedure


For changing the measuring range, carry out zero adjustment first, and span adjustment next. (If
zero adjustment is performed after span adjustment, the 100% point may not be adjusted correctly.).
There is no interference between zero adjustment and span adjustment.

3.1 Zero adjustment (Change Lower Range Value)


Zero point of the transmitter is adjustable by the external adj. screw with the mode setting
switch set at “0” position.

(1) Check if “ZERO” is lit on the LCD indicator.


If not lit, set the mode setting switch to “0” position.
(2) Apply standard input pressure corresponding to new Lower Range Value
(3) Adjust output signal to 4.00mA by turning the external adj. screw
Decrease

Increase

For zero suppression or elevation ranges, apply the specified LRV pressure in advance and adjust
the output signal to 4.00mA using the external adj. screw.

Max zero elevation with : Output Max Zero suppression with :


max span signal min span
min span max span
100% (20mA)

0% Input signal
(4mA) %URL
0%
-100% Zero elevation Zero suppression +100%

31
3.2 Span adjustment (Change Upper Range Value)

The measuring range for each transmitter is determined according to its type.
The span is changed by the external adj. screw when the mode setting switch is set at “1” or ”6"
position.
(1) Set the mode setting switch to “1” or ”6” position.
(2) Apply standard input pressure corresponding to new Upper Range Value.
(3) Adjust output to 20.00mA by turning the external adj. screw.
Decrease

Increase

(4) Then, apply input pressure corresponding to new Lower Range Value again and make sure
output is 4mA.
(5) After span adjustment according to above procedure from 3.2-(1) to (4), please set mode
setting switch to appropriate position

After adjustment, the transmitter should be kept energized at about 10 seconds to write
Important the adjustment parameter into memory.

4. Damping adjustment

If a pulsation of the output current is caused due to flow noise etc., it can be attenuated by performing
damping adjustment.
Damping is adjustable in 8 steps. The damping constant becomes lager in the order of 0,1,2,3and 4.
These damping constant correspond to time constant 0, 0.3, 0.6, 1.2, 2.4, 4.8, 9.6, 19.2 seconds for the
transmission unit regardless of span.
The relationship between position of switch and time constant are indicated in table 2.

Note)
The damping constant above is a time constant applied to the transmission unit only. The
detecting unit has additional time constant
(Please see data sheet about details)

When the transmitter respose speed is changed, the time constant of the control system
Important is also changed. Be sure to check the controllability again.

5. Fixed current output and its adjustment

Output of fixed current regardless of input is available.


Output of fixed current is convenient for loop check.
When the output(4 or 20mA)is in error, it can be adjusted by the external adjustment screw.
32
5. MAINTENANCE

5.1 Periodic inspection


In order to ensure the measurement accuracy and long life of the transmitter, it is essential to inspect
the transmitter periodically according to the operating conditions.
Visual inspection
Visually inspect each part of the transmitter for damage, corrosion, etc.
If you detect any material which may cause corrosion, it should be cleaned off.
Check of cover and O-ring
The transmitter has a water and dust-proof construction.
Make sure the O-ring of the case cover is not damaged or deteriorated.
Carefully prevent foreign materials from sticking to threads.

Piping leakage check


Using soapy water or the like, check the all process connections for leakage of process fluid. If
necessary, drain the moisture which has accumulated in the transmitter and process pipe.

33
5.2 Troubleshooting
If an abnormality occurred in the process or transmitter, action should be taken with reference to the
table below.
Symptom Cause Remedy
(1) The manifold valve does Repair the valve so that it opens/closes normally.
not open/close normally.
(2) Pressure leak is occurring. Repair a leak.
(3) Process piping is improper. Make correct piping.
(4) Process pipe is clogged. Eliminate the cause of clogging.
(5) Power supply voltage Make arrangement to obtain proper values. For
and/or load resistance is power supply voltage and load resistance, refer to
Output current improper. 7.2.
overshoots scale (For intrinsically safe installations, the power
(exceeds 20mA). supply voltage should be 16.1 to 26V DC.)
(6) Voltage between the Check for faulty cable, insulation, etc. and repair
external connection as needed.
terminals of transmission For power supply voltage and load resistance,
unit is wrong. refer to “7.2”.
(For intrinsically safe installations, the power
supply voltage should be 16.1 to 26V DC.)
(7) Zero and span are not Readjust according to chapter 4.
adjusted.
(8) Electronics unit is faulty. Replace the electronics unit according to 5.3.
(1) Same as (1) to (4) above
(2) Power supply polarity is Correct wiring according to 7.1.
wrong.
(3) Power supply voltage Make arrangement to obtain proper values.
and/or load resistance is (For power supply voltage and load resistance,
No output
improper. refer to 7.2.)
current (less than
(For intrinsically safe installations, the power
3.8 mA).
supply voltage should be 16.1 to 26V DC.)
(4) Voltage between the Check for faulty cable, insulation, etc. and repair
external connection as needed.
terminals is wrong. (For power supply voltage and load resistance,
refer to 7.2.)
(For intrinsically safe installations, the power
supply voltage should be 16.1 to 26V DC.)
(5) Electronics unit is faulty. Replace the electronics unit according to 5.3.
(1) Process piping is improper. Correct the piping.
(2) Gas or solution is mixed in. Vent or drain the transmitter.
Output current (3) Liquid density changes. Perform density compensation.
error (4) Ambient temperature Minimize the temperature change.
changes widely.
(5) Zero or span has deviated. Readjust zero or span.
(6) Electronics unit is faulty. Replace the electronics unit according to 5.3.

If remedy is impossible, contact Fuji Electric’s service department.

34
5.3 Replacement of parts
If the transmitter requires a replacement part, drain process fluid from the transmitter, disconnect it
from the process and carry out replacement in an instrument room.

When removing an explosion-proof transmitter, turn OFF the main power, then discon-
nect the piping and wiring. Do not remove it when the power is ON to prevent serious
DANGER accident such as explosion, fire, etc.

To identify faulty part

Replace the transmission unit with a spare one in order to determine whether it is the detecting unit or
transmission unit which is faulty.
When the faulty unit is identified, it should be replaced with a new one.

Replacement of electronics unit

Electronics unit

Indicator

Connection at rear
of electronics unit

Replacing procedure
(1) Turn off the power supply.
(2) Remove the indicator.
(3) Remove the electronics unit.
Unplug each connector.
(4) Replace the electronics unit with a new one and assemble it by reversing the above procedure
from (3) to (1).

When installing the electronics unit, make sure that the


Important
zero adjust screw end is in front of the groove in the Groove
Zero
amplifier unit. adjustment screw

(5) After completion of replacement, perform zero and span adjustments.

The electronics unit should be removed carefully so as not to damage the internal
Important wiring.

35
Replacement of detecting unit

Hexagonal socket bolt

Transmission unit

Detecting unit

Flatcable

Replacing procedure
(1) Remove the electronics unit according to "Replacement of electronics unit."
(2) Remove the hex. socket bolts from the electronic housing.
Pull the electronics housing straight forward and away from the detecting unit.
(3) Replace the detecting unit with a new one of the same type.
(4) Fit the transmission unit to the detecting unit and tighten it.
(5) Connect each connector of the electronics unit and attach it to the transmission unit.
(6) After reassembly, carry out zero and span adjustments.

Important • Ensure that replacement detector unit is the same specification as the original
by comparing dataplates.
• When removing the transmitter case, pay attention not to damage the flatcable.

36
Replacement of the internal parts of detecting unit

In case of differential and flow transmitter (code symbol: FKC)

Nut
O-ring (or gasket)

Seal diaphragm

Measurement
chamber cover

Bolt

Seal tape

Replacing procedure
(1) Remove four hexagon socket head bolts with a torque wrench, etc..
(2) Disassembly gives access to the casing covers, O-rings (or gasket), hexagon socket head bolts
and nuts.
(3) After disassembly, replace the faulty part with a new one.
(4) Before reassembly, clean the O-ring face of casing cover with the soft cloth immersed in water,
alcohol, or similar detergent.
(5) Reassemble the detecting unit by reversing the disassembling procedure. The casing covers
should be assembled so as to be symmetrical with each other in the left-right direction and care-
fully so as not to damage the seal diaphragm. Tightening torque should follow the table below.
Tightening Maximum working
torque pressure
Bolt size Bolt material [N·m] [MPa] Application
(kgf·m) {bar}
<ft-lb> <psi>
50 42
M10 Cr-Mo steel (5) {420} Working pressure 42 MPa {420 bar} <6000 psi> or less
<36> <6000>
SUS304 30 10
M10 ASTMB7M (3) {100} Working pressure 10MPa {100 bar} <1400 psi> or less
ASTML7M <22> <1400>
50 42
M10 SUS630 (5) {420} Working pressure 42 MPa {420 bar} <6000 psi> or less
<36> <6000>

(6) After assembly, carry out a pressure test. Apply a pressure equal to 150% of the maximum
working pressure to both high pressure (H) and low pressure (L) measurement chambers of the
transmitter simultaneously for 15 minutes, and make sure there is no leakage.

37
In case of absolute pressure and gauge pressure transmitter (code symbol: FKA and FKG)

Nut

In case of FKA Seal diaphragm

Bolt

O ring Measurement
(or gasket) chamber cover

(1) Remove four bolts with a torque wrench, etc..


(2) Disassembly gives access to casing covers, O-rings (or gasket), bolts and nuts.
(3) After disassembly, replace the faulty part with a new one.
(4) Before reassembly, clean the O-ring face of casing cover with the soft cloth immersed in water,
alcohol, or similar detergent.
(5) Reassemble the detecting unit by reversing the disassembling procedure. The casing covers
should be assembled so as to be symmetrical with each other in the left-right direction and care-
fully so as not to damage the seal diaphragm. Tightening torque should follow the table below.

In case of absolute pressure transmitter (FKA)


Tightening Maximum working
torque pressure
Bolt size Bolt material [N·m] [kPa] Application
(kgf·m) {bar abs}
<ft-lb> <psi>
50 3000
M10 Cr-Mo steel (5) {30}
<36> <430>
Common over entire range
SUS304 30 3000
M10 ASTMB7M (3) {30}
ASTML7M <22> <430>

In case of gauge pressure transmitter (FKG)


Tightening Maximum working
torque pressure
Bolt size Bolt material [N·m] [kPa] Application
(kgf·m) {bar}
<ft-lb> <psi>
50 50000
M10 Cr-Mo steel (5) {500} Common over entire range
<36> <7100>
SUS304 30 10000
M10 ASTMB7M (3) {100} Range 10000 [kPa] <1400 psi> or less
ASTML7M <22> <1400>
50 50000
M10 SUS630 (5) {500} Exclusive for range 50000 [kPa]
<36> <7100>

• After assembly, carry out a pressure test.


Apply a pressure equal to 150% of the maximum working pressure to the high pressure measure-
ment chamber of the transmitter for 15 minutes, and make sure there is no leakage.

38
In case of level transmitter (code symbol: FKE)

Bolt
Measurement
chamber cover
O-ring (or gasket)
Seal tape
Seal diaphragm

(1) Remove four hexagon socket head bolts with a torque wrench, etc..
(2) Disassembly gives access to the casing cover, O-ring (or gasket) and hexagon socket head bolts.
(3) After disassembly, replace the faulty part with a new one.
(4) Before reassembly, clean the O-ring face of casing cover with the soft cloth immersed in water,
alcohol, or similar.
(5) Reassemble the detecting unit by reversing the disassembling procedure. The casing cover
should be assembled carefully so as not to damage the seal diaphragm. Tightening torque should
follow the table below.
Tightening torque
[N·m]
Bolt size Bolt material Maximum working pressure
(kgf·m)
<ft-lb>
50
M10 Cr-Mo steel (5) Up to rated flange oressure
<36>
SUS304 30
M10 ASTMB7M (3) Up to rated flange pressure
ASTML7M <22>
(6) After assembly, carry out a pressure test. Apply a pressure equal to 150% of the maximum
working pressure to both flange side (high pressure side) and low pressure (L) measurement
chamber of the transmitter simultaneously for 15 minutes, and make sure there is no leakage.

39
Replacement of field indicator

1. Replacement of analog indicator

Analog indicator

Transmitter cover

Replacing procedure
(1) Detach the transmitter cover.
(2) Remove the analog indicator.
(3) Pull out the connector extending from the analog indicator.
(4) Connect the connector of a new analog indicator to the electronics section. (See the figure below.)
(5) Then, mount the analog indicator at the electronics section.

6) Attach the transmitter cover.

40
2. Replacement of digital indicator

Digital indicator mounting board

Digital indicator

Transmitter cover

Replacing procedure
(1) Detach the transmitter cover.
(2) Remove two fixing screws which fasten the digital indicator and separate the indicator.
(3) Pull out the leading end of the flatcable extending from the digital indicator after raising the
slider (white knob) in the electronics section. (See the figure below.)
(4) Insert the leading end of the flatcable of a new digital indicator into the connector plug-in port of
the electronics section and fix it by pushing in the slider. Before inserting the flexible PC board,
confirm its correct orientation.
(5) Fasten the digital indicator to the electronics section by tightening two fixing screws.

Digital indicater
plugin port

Pin plug

Before tightening, make sure a small recess on the surface is positioned at the top as shown
below.
When twisting the flexible PC board for mounting, adequate attention should be paid not to
damage the board.

Fixing screws

Small recess
(6) Attach the transmitter cover.

41
5.4 Adjustment after replacement of unit
Adjustment

After completion of the assembly work mentioned above, use the following procedures for adjust-
ment and setting. Adjustment should be performed using the HHC.
(1) After replacement of electronics unit (including replacement of internal parts)
Step Adjustment item Relevant page
1 Constant current output (output circuit) P18
2 TAG. No. P10
3 Type P11
4 Industrial value unit P12
5 Range (zero/span) P13
6 Zero/span adjustment P17
7 Damping P14
8 Output mode (LIN/ selection) P15
9 Burnout direction P16
10 Lock of adjustment function P21

(2) After replacement of detecting unit (including replacement of internal parts)


Step Adjustment item Relevant page
1 Range (zero/span) P13

42
6. INSTALLATION AND PIPING

6.1 Installation
After unpacking, check the delivered items.
This transmitter can be mounted on a pipe or on a wall.
(However, level transmitters (types: FKE) require flange mounting).
Note that the bolts (M8) for wall mounting should be supplied by the customer.
• The transmitter is heavy. Be careful when handling it.
• The transmitter should be installed in a place that meets the operating conditions
shown in DS sheet or instruction manual.
• Install the transmitter according to the instruction manual. Improper installation may
CAUTION
lead to the cause of fall, trouble or incorrect operation.
• When installing, make sure that the transmitter interior is free from cable chips and
other foreign objects to prevent fire, trouble or incorrect operation.

• Non-explosion-proof transmitter must not be used in a place with explosive gas to


DANGER prevent serious accidents such as explosion, fire, etc.

If the transmitter is not used soon after delivery, then leave it packed and store it in a
Important room at the normal temperature and humidity (25°C <77°F>, 60%RH).

Bracket mounting
Mount the bracket to the transmitter.
The bracket should be mounted to the process cover as shown below.
(Differential pressure/flow transmitters, pressure (Remote seal type transmitters, types: FKD, FKB,
transmitters, and absolute pressure transmitters, types: FKM)
FKC, FKG, FKA)
Transmitter Transmitter
Mesurement chamber cover
Bracket Bracket
Plain washer
Spring washer Plain washer
Mounting bolt Spring washer
(M8 12)
Mounting bolt
(M8 12)
Mounting
Pipe mounting (FKC, FKG, FKA) (FKD, FKB, FKM)

(1) Fasten the transmitter to a vertical or hori-


zontal pipe using the supplied U-bolt
(Tightening torque approximately 15 N·m
(1.5 kgf·m)<11ft-lb>).
(2) Use a pipe of outside diameter
ø60.5<2.38">mm. Transmitter
(FKE)
Wall mounting
(1) Fasten to wall face by M8 bolt utilizing the
U-bolt holes. Nut
Spring washer
Flange mounting Plain washer
Bolt to tank flange. Bolt

43
Change of field indicator position

Avoid the following procedure in an explosionproof area.


CAUTION
It is sometimes preferable to mount the indicator on the terminal block side due to installation loca-
tion.
In such a case, the following mounting procedure should be followed for analog indicator.

Digital indicator cannot be mounted on the terminal block side.

Indicator attached
to electronics unit
side.

1 Remove the cover with 2 Remove the cover.


window and indicator.

3 Mount the supplied


attachment to the
pin plug.
Pin plug 4 Mount the supplied studs
on the terminal block.
Attachment

Studs

5 Attach the cover. 6 Connect the red wire


(+) of the indicator to
CK+ and the black
wire (-) of the indicator
to CK-, then attach the
cover with window.

Indicator attached to
terminal block side.

44
Change of transmission unit position

Avoid the following procedure in an explosionproof area.


CAUTION
Wiring is sometimes difficult depending on the installation location. In such a case, it is convenient
to carry out the following.
Before turning the transmission unit, remove the electronics unit.
The transmission unit is secured by 2 hex socket bolts.
Loosen the bolts, turn the transmission unit at 90˚ or 180˚ in the clockwise or counterclockwise direc-
tion and fix it by the screws. Then, carry out wiring.

If the transmission unit has been turned ex- Hex


Important cessively without removing the electronics socket bolt
unit, straighten the flatcable which connects
the electronics unit in the transmission unit
and the detecting unit, and set the transmis-
sion unit again.

Change of indicator angle

Avoid the following procedure in an


explosionproof area.
CAUTION

The analog or digital indicator can be turned ±180˚ in 90˚ increments because
it is connected with a pin plug.
0

0
10
80
20

60
40

% 0
%

10
0

40

20
60

40 80
60
20
80

0
10
0

45
Check space

Ensure a space of about 500mm against the cover in order to facilitate check, adjustment, etc.

500

500

Change of vent/drain plug position

Grasp the hexagon part of vent/drain plug and rotate it to remove.


Bind vent/drain plug's thread with new seal tape and mount vent/drain plugs to new process connec-
tions.
Tightening torque : 25N·m (2.5kgf·m) <18ft·lb>

Process connection

46
6.2 Piping
It is generally recognized that there are appropriate positioning relationship between the transmitter
and main process piping for accurate measurement to avoid harmful gas or liquid accumulation.
General recognizations are;
1 Mount transmitter below main process piping for liquid or steam measurement.
2 Mount transmitter above main process piping for gas measurement.
The standard style of FCX-A2 series transmitter correspond to the piping procedure 1 mentioned
above. Change the vent/drain plug to correspond to the piping procedure 2.
Main valve used for piping should be selected with the maximum pressure of the pro-
cess taken into account (piping parts such as main valve, etc. should be furnished by
CAUTION user). If the main valve and other parts do not meet the rating, it may result in leakage
of gas or liquid which could lead to a hazard.

6.2.1 Piping of differential pressure and flow transmitters (type: FKC.)


Check of high/low pressure sides of transmitter
The detecting unit of the differential pressure transmitter
bears symbols H and L which represent high and low pres-
sure sides, respectively.
Also, vent/drain plugs are provided at the lower process
connection, while impulse pipes are connected at the upper
process connections.
L H

Removal of protective cap


The process connection ports of the transmitter and manifold (equalizer) valve are fitted with
protective caps. Before piping, be sure to remove the caps. When removing the caps, carefully
protect the threaded portion and sealing face from damage.
Connection of transmitter and impulse pipes
(1) When using the manifold valve, it should be fixed to the transmitter by tightening four oval
flange setbolts (7/16-20UNF), and then the impulse pipe should be connected to the manifold
valve. Tightening torque of 7/16-20UNF mounting bolt should be 30 to 40 N·m (3 to 4 kgf·m).
(2) If a manifold valve is not used, the impulse pipes can directly be screwed into the transmitter. If
thread size does not match between the transmitter and impulse pipes, an oval flange should be
used. Tightening torque of 7/16-20UNF mounting bolt in an oval flange should be 30 to 40 N·m
(3 to 4 kgf·m).
Position of process taps (Horizontal main process piping)
The position of the process tap is determined by the relationship between the condition, charac-
teristics and measuring point of the process fluid.
Note the following figures when planning and installing the piping.
Gas measurement Liquid measurement Steam measurement
45
45° ° Main process piping Differential pressure source
Upper 45° 45°
Upper

Lower 45° 45° Lower


Differential pressure Differential pressure Differential pressure
source is located upper source is located lower source is located upper
side of main process piping side of main process piping side of main process piping
Within 45°upward from Within 45° downward Within 45° upward from
vertical direction from horizontal direction horizontal direction

47
Typical examples of piping
1 Flow measurement (in case of gas)
Place the transmitter above the differential pres- % 10
0

0
20 80
40 60

sure source.
Manifold valve

Impulse pipe

Stop valve

Process pipe

Differencial pressure source (orifice)

2 Flow measurement (in case of liquid) Differencial pressure source (orifice)


Place the transmitter below the differential pres-
sure source.
Process pipe
Make piping so that gas in the impulse pipe is not
Stop valve
delivered to the transmitter, and incorporate gas
reservoirs as required. Impulse pipe
Manifold valve

% 10
0

0
20 80
40 60

3 Flow measurement (in case of steam)


Process pipe
Stop valve
Set two condensers at the same height near the pro-
cess tap. Fill the line between the condensers and Condenser
transmitter with condensed water.
Install a drain port as required.
Impulse pipe
Manifold valve

% 10
0
0

20 80
40 60

4 Pressure measurement (in case of liquid)


Zero point can be checked with a manifold valve
installed. Pressure source

Atmospheric air inlet Process pipe


Stop valve
Impulse pipe
Manifold valve

% 10
0
0

20 80
40 60

48
(1) Protection is required to prevent dust from entering through the atmospheric
Important air inlet after installation of the manifold valve.
(2) If process pressure range is narrow (below 10kPa (1000mmH2O)), the follow-
ing should be considered.
• Pressure variation due to wind around atmospheric air inlet
• Temperature variation near process taps
• Difference in atmospheric pressure between process tap and transmitter location
To overcome this, provide atmospheric pressure-side pipe with a proper orifice
and consider accommodating the transmitter and atmospheric air inlet in a box.

5 Pressure measurement (in case of gas)


% 10
0

Mount the transmitter above the process pipes to

0
20 80
40 60

preventing moisture from entering the inside of


transmitter. Manifold valve
Impulse pipe
Stop valve
Atmospheric Process pipe
6 Level measurement air inlet

(1) In case of wet leg: Pressure source

For measurement, connect the highest liquid level tapping of tank with the low pressure
side of transmitter, and the lowest liquid level tapping of tank with the high pressure
side of transmitter.
Condensor ρ1
Level calculation formula
Max. liquid level
LRV : ρH2 – ρ0H1 h
Min. liquid level
URV : ρH2 + ρ1h – ρ0H1
Span (∆P): ρ1h ρ0 ρ
LRV : Low limit of measurement
H1 H2
(0% point) Manifold
valve
URV : High limit of measurement Low pressure High pressure
(100% point) side side

ρ0,ρ,ρ1: Density % 10
0
0

20 80
40 60

H1, H2: Liquid level, h: Liquid level change

(2) In case of dry leg: Max. liquid level


ρ1 h
For an open tank, leave the low Min. liquid level
Atomospheric
pressure side of transmitter open to air inlet ρ
atmosphere.
H1
Level calculation formula Manifold
valve
LRV: ρH1 Low pressure High pressure side
URV: ρH1 + ρ1h side

Span (DP): ρ1h % 10


0
0

20 80
40 60

LRV: Low limit of measurement (0% point)


URV: High limit of measurement (100% point)
ρ,ρ1: Density
H1: Liquid level, h: Liquid level change

49
Cautions on impulse piping
• For liquid, the impulse pipes should have an upward slope of 1/10 or more between the
process connection and the transmitter to prevent accumulation of gas, etc. in the detecting
unit.
• For gas, the impulse pipes should have a downward slope of 1/10 or more between the
process connection and transmitter to prevent accumulation of moisture, etc. in the detecting
unit.
• Avoid any sharp bends in impulse pipe which may cause gas or moisture to accumulate in
the impulse pipe.
• In order to prevent vibration of the transmitter body and capillary from interfering with
output, the transmitter body should be installed at a vibration-free place and the capillary
should be fixed to a stable support.
• Take care not to apply an excessive force to the transmitter during its connection.
• The impulse pipes used should be suitable for the working temperature, pressure, etc.
• When the measuring fluid is likely to freeze in the cover of the measurement chamber, the
cover needs to be warmed up with steam or a heater.

50
6.2.2 Piping of pressure and absolute pressure transmitters
(types: FKG, FKA)
Removal of protective cap
The process connection port of the transmitter is fitted with a protective cap. Before piping,
remove the cap carefully. When removing the cap, carefully protect the threaded portion and
sealing face from damage.
Connection of transmitter and impulse pipe
• Impulse pipe should be connected with an oval flange. Also, the pipe can directly be
screwed into the transmitter. Tightening torque of 7/16-20UNF mounting bolt in an oval
flange should be 30 to 40 N·m (3 to 4 kgf·m).
• After connection, close the stop valve of transmitter in order to prevent foreign materials
from entering the inside.
Position of process taps (Horizontal main process piping)
The position of the process tap is determined by the relationship between condition, characteris-
tics and measurement point of process fluid. Note the following figures when planning and
installing the piping.
Gas measurement Liquid measurement Steam measurement
45
45° ° Main process piping Pressure source
Upper 45° 45°
Upper

Lower 45° 45° Lower


Pressure source is Pressure source is Pressure source is
located upper side of located lower side of located upper side of
main process piping main process piping main process piping
Within 45°upward from Within 45° downward Within 45° upward from
vertical direction from horizontal direction horizontal direction

51
Typical examples of piping
1 Gas measurement
Place the transmitter above the pressure source. % 10
0

0
20 80
40 60

Manual valve

Impulse pipe
Stop valve
Process pipe

Pressure source

2 Liquid measurement
Pressure source
Place the transmitter below the pressure source.
Make piping so that gas in the process pipe is not Process pipe
delivered to the transmitter, and incorporate gas Stop valve
Impulse pipe
reservoirs as required.
Manual valve

% 10
0

0
20 80
40 60

3 Steam measurement
Place the transmitter below the pressure source. Pressure source

Stop valve
Impulse pipe
Manual valve

% 10
0
0

20 80
40 60

Cautions on impulse piping


• For liquid, the impulse pipe should have an upward slope of 1/10 or more between the pro-
cess connection and transmitter to prevent accumulation of gas, etc. in the detecting unit.
• For gas, the impulse pipe should have a downward slope of 1/10 or more between process
connection and transmitter to prevent accumulation of moisture, etc. in the detecting unit.
• Avoid any sharp bends in impulse pipe which may cause gas or moisture to accumulate in
the impulse pipe.
• In order to prevent vibration of the transmitter body and capillary from interfering with
output, the transmitter body should be installed at a vibration-free place and the capillary
should be fixed to a stable support.
• Take care not to apply an excessive force to the transmitter during its connection.

The impulse pipe used should be suitable for the working temperature, pres-
CAUTION sure, etc.

• When the measuring fluid is likely to freeze in the cover of the measurement chamber, the
cover needs to be warmed up with steam or a heater.

52
6.2.3 Piping of level transmitter (type: FKE)
Check of high/low pressure sides of transmitter
The detecting unit of the level transmitter bears symbols H and L which represent high and low
pressure sides, respectively.

L H

Seal on mounting flange face


When mounting the flange on the high pressure side, a gasket should be inserted as follows.

Transmitter flange Process side flange

Gasket

Minimum internal diameter of non-projection type gasket


Flange size Minimum internal diameter of gasket
DN80/3” SS : 49mm
DN100/4” SS : 100mm

It should be noted that leakage of fluid from the wetted parts would affect the
Important performance due to the progress of corrosion.

53
Connecting method of the mounting flange
Tighten bolts of mounting flange and process flange in a diagonal order and about three cycles.
Removal of protective cap from process connection port
The process connection port on the low pressure side is fitted with a protective cap. Before
piping, remove the cap carefully. When removing the cap, carefully protect the threaded portion
and sealing face from damage.
Connection of transmitter and impulse pipe
• The pipe on the low pressure side can be connected with an oval flange. Also, the impulse
pipe can directly be screwed into the transmitter. Tightening torque of 7/16-20UNF mount-
ing bolt in an oval flange should be 30 to 40 N·m (3 to 4 kgf·m).
• After connection, close the stop valve of transmitter in order to prevent foreign materials
from entering the inside.

Typical examples of piping


1 Level measurement of open tank
Leave the low pressure side of transmitter
open to atmosphere. Max. liquid level
ρ
Level calculation formula h
LRV: ρH1 Min. liquid level
URV: ρ (H1 + h) H1
Span (∆P): ρh
LRV: Low limit of measurement (0%)
URV: High limit of measurement (100%)
ρ: Measuring liquid density
H1: Liquid level (Refer to “Cautions on installation”)
h: Liquid level change

2 Level measurement of enclosed tank


(1) In case of wet leg:
Connect the highest liquid level tapping of tank to the low pressure side of transmitter,
and the lowest liquid level tapping of tank to the high pressure side (flange side) of
transmitter.
Level calculation formula ρ Stop valve Drain port
LRV: ρH1 – ρ0H2
URV: ρ (H1 + h) – ρ0H2
Max. liquid level
Span (∆P): ρh ρ0
LRV: Low limit of measurement h H2
Min. liquid level
(0%)
H1
URV: High limit of measurement
(100%)
ρ: Measuring liquid density
ρ0: Seal liquid density
H1: Liquid level (Refer to "Cautions on installation")
h: Liquid level change
H2: Seal liquid level

54
(2) In case of dry leg:
Connect the highest liquid level tapping of tank to the low pressure side of transmitter,
and the lowest liquid level tapping of tank to the high pressure side (flange side) of
transmitter.
Stop valve
Level calculation formula ρ
LRV: ρH1
URV: ρ (H1 + h) Max. liquid level
h
Span (∆P): ρh
LRV: Low limit of measurement (0%) Min. liquid level
URV: High limit of measurement H 1

(100%)
ρ: Measuring liquid density
H1: Liquid level (Refer to “Cautions on installation”)
h: Liquid level change

Cautions on installation
• Restriction on H1
Liquid level is not proportional to the transmitter output at some points inside the seal dia-
phragm.
Therefore, H1 should be set higher than the value shown in the table below.
• In order to prevent vibration of the transmitter body and capillary from interfering with
output, the transmitter body should be installed at a vibration-free place and the capillary
should be fixed to a stable support.
• Do not shock the seal diaphragm by hitting hard object against it, for example.
• Take care not to apply an excessive force to the flange during connection.
• When the measuring fluid is likely to freeze in the cover of the low pressure measurement
chamber, the cover needs to be warmed up with steam or a heater.

Minimum value of H1
Flange size Non-projection type Projection type
1
40A (1 /2B) 30mm ––––
50A (2B) 30mm 30mm
80A (3B) 55mm 40mm
100A (4B) 55mm 55mm

55
6.2.4 Piping of remote seal type transmitter
(types: FKB, FKD, FKM)
(1) Piping of remote seal type differential pressure transmitter (type : FKD)

Check of high/low pressure sides of transmitter


The detecting unit of the remote seal type differential pressure transmitter bears symbols H and L
which represent high and low pressure sides, respectively. Both high and low pressure sides
employ flange connection.

H L

Seal on mounting flange face


When mounting the flange, a gasket should be inserted as follows.

On the non-projection type, be sure to use a gasket with an internal diameter


Important larger than shown in the table below, to prevent the gasket from touching the
seal diaphragm.
On the 80A (3B) type particularly, it should be noted that the 80A (3B) gasket
available from the market is such that its inside diameter is smaller than the
size shown below. If it is used, it touches the seal diaphragm and cause errors
in measurements.

Minimum internal diameter of non-projection type gasket


Flange size Minimum internal diameter of gasket
40A (11/2B), 50A (2B) 49mm
80A (3B), 100A (4B) 100mm

Transmitter flange
Gasket
Process side
flange

When measuring a highly corrosive process fluid, care should be taken as


Important corrosion may occur if the fluid leaks past wetted parts.

Connecting method of the mounting flange


Tighten the bolts of mounting flange and process flange in a diagonal order and about three
cycles.

56
Piping for small flange transmitter with direct mount adaptor
When connecting the direct mount adaptor to the
Process Direct mount
process piping, make sure that the 2 vent/drain piping adaptor
plugs fitted to the adaptor are positioned up and Capillary

down, respectively.
Gaskets, bolt and nuts used for connecting the pro-
cess piping are not supplied from Fuji, and should
be prepared by user. Vent/drain
plug

Scope of supply from Fuji


Typical examples of piping
Level measurement
(1) Open tank
An open tank should be piped so that the flange on Max. liquid level
the low pressure side is open to atmosphere. h ρ
D
Min. liquid level
Level calculation formula H1
LRV: ρH1 – ρ’D
URV: ρ (H1 + h) – ρ’D
ρ’
Span (∆P): ρh
LRV: Low limit of measurement (0%)
URV: High limit of measurement (100%)
ρ: Measuring liquid density Low pressure High pressure
side side
ρ’: Seal liquid density
H1: Liquid level (Refer to “Cautions on installation”)
h: Level change
(2) Enclosed tank
Connect the low pressure side flange to the highest
liquid level tapping of tank, and the high pressure Max. liquid level
h ρ
side flange to the lowest liquid level tapping of tank. D
Min. liquid level
Level calculation formula H1

LRV: ρH1 – ρ’D


URV: ρ (H1 + h) – ρ’D ρ’
Span (∆P): ρh
LRV: Low limit of measurement (0%)
URV: High limit of measurement (100%)
ρ: Measuring liquid density Low pressure High pressure
side side
ρ’: Seal liquid density
H1: Liquid level (Refer to “Cautions on installation”)
h: Level change

57
* The seal liquid density ρ’ is a value at 25°C.
13th digit of type code Density Description
Y, G 0.95 For general measurement (silicone oil)
For oxygen and chlorine measurement
W, A, D 1.9
(fluorine-group oil)
H, S, K 1.07 For high temperature, high temperature and
vacuum, and high temperature and high vacuum
J, T 1.09 (silicone oil)

The transmitter body should be installed below any pressure receiving unit. This
Important is mandatory where process pressure may become vacuum due to application.

Cautions on installation
• Restriction on H1
Liquid level is not proportional to the transmitter output at some pints inside the seal dia-
phragm. Therefore, H1 should be set higher than the value shown in the table below.
Minimum value of H1
Flange size Non-projection type Projection type
40A (11/2B) 30mm ––––
50A (2B) 30mm 30mm
80A (3B) 55mm 40mm
100A (4B) 55mm 55mm

• In order to prevent vibration of the transmitter body and capillary from interfering with
output, the transmitter body should be installed at a vibration-free place and the capillary
should be fixed to a stable support.
• For minimizing the influence by a difference in the ambient temperature, the capillaries on
the high and low pressure sides should be laid together.
• Do not shock the seal diaphragm by hitting a hard object against it, for example.
• Water head pressure due to difference in the height of flange
When there is a difference (D) in flange mounting position between the high-pressure side
and the low-pressure side, a water pressure head “–ρ’D” is applied to the transmitter, so a
zero point shift for the water head pressure (–ρ’D) due to difference in height of flange is
required at range setting as shown in the example of typical piping.
On the FCX-A2 series transmitter, it is made by setting LRV, URV and –ρ’D with HHC (for
details, refer to Item 4 “Adjustment”, 4.1 Adjustment with HHC and operation procedure,
range change).

58
(2) Piping of remote seal type pressure transmitter (type: FKB, FKM)
Seal on mounting flange face
When mounting the flange, a gasket should be inserted as follows.
Transmitter flange
Gasket
Process side
flange

When measuring a highly corrosive process fluid, care should be taken as


Important corrosion may be aggravated if the fluid leaks out of wetted parts.

Minimum internal diameter of non-projection type gasket


Flange size Minimum internal diameter of gasket
DN80/3” SS : 73mm
DN100/3” SS : 100mm

Connecting method of the mounting flange


Tighten the bolts of mounting flange and process pipe flange in a diagonal order and about three
cycles.
Mounting of flange and bed
The bed has two screw holes on the back face. It is therefore recommended to mount the bed to
the flange in advance by tightening screws (M6). The flange should be supplied by the customer.

Bed Flange

59
Typical examples of piping
Pressure receiving unit
1 Gas measurement
Locate the process tap above the pressure source.

Atmospheric
air leak valve Stop valve
Transmitter
Process tap

Pressure source
2 Liquid measurement
Pressure source
Locate the process tap below the pressure source.

Process tap

Stop valve

Pressure receiving unit

Atmospheric air leak valve

3 Level measurement
Transmitter
Open tank
An open tank should be connected on the low- Max. liquid
est liquid level tapping point. level
Pressure receiving unit Min. liquid
• Restriction on H1 level
H1
Liquid level is not proportional to the
transmitter output at some pints inside the Stop valve
seal diaphragm. Therefore, H1 should be
set higher than the value shown in the
Transmitter
table below.
Minimum value of H1
Flange size Non-projection type Projection type
40A (11/2B) 30mm ––––
50A (2B) 30mm 30mm
80A (3B) 55mm 40mm
100A (4B) 55mm 55mm

The transmitter body should be installed below any pressure receiving unit. This
Important is mandatory where process pressure becomes vacuum due to application.

Cautions on process piping


• In order to prevent vibration of the transmitter body and capillary from interfering with
output, the transmitter body should be installed at a vibration-free place and the capillary
should be fixed to a stable support.
• Do not shock the seal diaphragm by hitting hard object against it, for example.

60
7. WIRING
Cautions on wiring

(1) Application of a voltage exceeding 60 V DC or 40 V AC (exceeding 33 V DC or 23 V AC when


arrester equipped) between “+” and “–” terminals may result in damage to the transmitter.
(2) Use a shielded cable for the transmission line where possible.
(3) Avoid installation of signal cable and power cable in same conduit or cable tray in order to
prevent increased noise. Also, do not bring the signal cable close to large electrical equipment.

In case of an explosionproof arrangement, wiring shall be made in accordance with the


DANGER relevant regulations to ensure the explosionproofing.

7.1 Wiring procedure


• Before making wiring work, be sure to turn OFF the main power to prevent electric
shocks.
• Use wiring materials of correct rating to prevent fire accidents.
CAUTION • After installing the transmitter, firmly close the covers of the transmission unit and
terminal box. If not, rain water enter the transmitter which may result in trouble or
incorrect operation.

Sealing of conduit connection

Use sealing tape, if using metal pipe screw coupling or rubber gasket and fastening gland in the case
of cable (outside diameter ø11) <0.43"> to ensure airtightness of the connection box.

1. If the connection box is located above the transmitter when using a protective tube
Important for the wiring, then moisture may enter the protective tube and have an adverse ef-
fect on the transmitter. So maintaining airtightness of the connection box is an im-
portant practice.
2. The thread of conduit tube should meet the selected size and a seal fixture should be
used.

Metal
pipe

61
Terminal block connection diagram

Tighten the terminal screws (M4 ✕ 10) to a torque of approximately 1.5 N·m (15 kgf·cm) <11ft-lb>
so that the wires will not loosen.
After connection, fasten the cover until it does not turn.

Terminal


CK
+
– CK

10.5 to 45 V DC

Output DC4 to 20mA Conveter

When using an external field indicator


For direct connection to an external field indicator, connect the “+” and “–” sides of the field
indicator to CK+ and CK– of the transmitter as shown below.
Use an external field indicator with internal resistance of 12Ω or less.

+
4 to 20mA DC

CK

+
CK

10.5 to 45 V DC

Converter
Output DC4 to 20mA

62
Things convenient to know beforehand

When using conduit connection at the top


(In the case of 4th digit of type code “S, T, V, W, X”)
For wiring from the top conduit connection, use the following procedure.
(1) Remove the screw plug of the top conduit connection.
(2) Screw the removed screw plug into the bottom conduit connection.
(3) Insert the cable from the top and connect it.

Hexagon key
wrench

Flash screw

• The unused conduit connection is of great importance to flameproofing and moisture


Important prevention. So be sure to tighten the flush screw and packing into the connection.
• When performing an insulation check after wiring, use a Megger (insulation resis-
tance meter) of 250 V DC or less and avoid applying a high voltage. If an arrester is
equipped, avoid the insulation resistance test and the dielectric strength measure-
ment.

7.2 Power voltage and load resistance


Make sure the load resistance of the wiring connected to the loop is within the range shown below.
Connect power source of correct rating. Use of power source in excess of the rating
CAUTION may cause a fire.

1533
Load resistance ( )

Note)
600
Operating zone

250

0
10.5 16.1 24 45
Power voltage (VDC)

Note) For communication with HHC, minimum load resistance of 250 Ω required.

63
7.3 Grounding
The transmitter must be grounded. Otherwise, it may cause electric shocks or incorrect
CAUTION operation.

Grounding terminals are provided at two places (at the inside of terminal box and on the side of
conduit connection).
By any of the methods given below, ground the transmitter in compliance with the relevant stipula-
tion in the standard on explosionproof installation (for example, grounding resistance 100 Ω or less
by one of the methods given below). In case of intrinsically safe and flameproof installation, be sure
to use the ground terminal for grounding.

Grounding of transmitter casing Grounding from ground terminal


CK

+
CK

+
External grounding terminal

64
8. SPARE PARTS
This diagram shows main parts of the differential pressure (flow) transmitter (FKC) and pressure
transmitter (FKG). For details, contact our office.

80A

66A

64A
62

64
65
101
100
FKG

103
80A

68
66A
66A

64A
62

2A
64
65
61
60
FKC

61
62

68

13A
11A

20A
66A

31A
12
12 12A
28

24A
40
39, 42
10
6

1A
5
5

3A

65
No. Parts No. Part Name Q'ty Material Remarks

1A *ZZPFCX4-A010 Cover 1 ADC12 Blind cover for electronics compartment.


2A *ZZPFCX4-A021 Cover 1 ADC12 Blind cover for terminal box cover.
3A *ZZPFCX4-A030 Cover ass'y 1 Aluminum Window cover for indicator option.
alloy
ADC12
5 *ZZPFCX4-A050 Incicator kit 1 Analog, 0- 100% linear.
*ZZPFCX4-A051 Indicator kit 1 Analog, 0- 100% square - root.
*ZZPFCX4-A052 Incicator kit 1 Analog, dual scale.
*ZZPFCX4-A053 Indicator kit 1 Analog, actual scale.
*ZZPFCX4-A054 Indicator kit 1 LCD Meter.
6 *ZZPFCX4-A060 Amplifier Unit 1 Common for any FCX-A2 models.
10 *ZZPFCX4-A101 Electronics housing 1 ADC12 With G1/2 connection. Conduit connection
1 location.
*ZZPFCX4-A102 Electronics housing 1 ADC12 With Pg13.5 connection. Conduit
connection 1 location.
*ZZPFCX4-A103 Electronics housing 1 ADC12 With 1/2 - 14NPT connection. Conduit
connection 1 location.
*ZZPFCX4-A104 Electronics housing 1 ADC12 With M20 ✕ 1.5 connection. Conduit
connection 1 location.
*ZZPFCX4-A109 Electronics housing 1 ADC12 With G1/2 connection. Conduit connection
2 locations.
*ZZPFCX4-A10A Electronics housing 1 ADC12 With Pg13.5 connection. Conduit
connection 2 locations.
*ZZPFCX4-A10B Electronics housing 1 ADC12 With 1/2 - 14NPT connection. Conduit
connection 2 locations.
*ZZPFCX4-A10C Electronics housing 1 ADC12 With M20 ✕ 1.5 connection. Conduit
connection 2 locations.
11A *ZZPFCX1-A110A Cable gland kit 1 Requires only for JIS flameproof.
G1/2 connection.
4th digit of
type code
12A *ZZPFCX4-A120A Plug kit 1 Plug for G1/2 connection. S
*ZZPFCX4-A121A Plug kit 1 Plug for Pg13.5 connection. V
*ZZPFCX4-A123A Plug kit 1 Plug for M20 ✕ 1.5 connection. W
12 *ZZPFCX1-A122 Plug 1 Stainless steel Plug for NPT1/2 connection. T
13A *ZZPFCX4-A132 Terminal block unit 1 Round washer type.
*ZZPFCX4-A133 Terminal block unit 1 Wire retaining washer type.
*ZZPFCX4-A134 Terminal block unit 1 Round washer type with arrester.
*ZZPFCX4-A135 Terminal block unit 1 Wire retaining washer type with arrester.
20A *ZZPFCX1-A200A Cable gland kit 1 Required only for transmitter with Pg13.5
connections.
Minimum order q’ty 10 pcs.
Note)
24A *ZZPFCX2-A241A Fastener kit 1 Required only for BASEEFA or JIS
flameproof (Exd) transmitters.
Minimum order q’ty 10 pcs.
31A *ZZPFCX1-A310A Hex. socket screw kit 2 Minimum order q’ty 10 pcs.

66
No. Parts No. Part Name Q'ty Material Remarks
39 *ZZPFCX2-A391 Blank name plate 1 Stainless steel Standard.
Minimum order q’ty 5 pcs.
Note)
*ZZPFCX4-A392 Blank name plate 1 Stainless steel FM Explosionproof.
Minimum order q’ty 5 pcs.
Note)
*ZZPFHX4-A393 Blank name plate 1 Stainless steel CSA Explosionproof.
Minimum order q’ty 5 pcs.
Note)
*ZZPFCX4-A394 Blank name plate 1 Stainless steel BASEEFA Explosionproof.
Minimum order q’ty 5 pcs.
Note)
*ZZPFCX4-A395 Blank name plate 1 Stainless steel FM Intrinsic safety.
Minimum order q’ty 5 pcs.
Note)
*ZZPFCX4-A396 Blank name plate 1 Stainless steel CSA Intrinsic safety.
Minimum order q’ty 5 pcs.
Note)
*ZZPFCX4-A397 Blank name plate 1 Stainless steel BASEEFAS intrinsic safety. Minimum
order q’ty 5 pcs.
Note)
*ZZPFCX4-A398 Blank name plate 1 Stainless steel BASEEFA type N intrinsic safety.
Minimum order q’ty 5 pcs.
40 *ZZPFCX1-A400 Rivet 2 Stainless steel Minimum order q’ty 50 pcs.
Note)
42 *ZZPFCX1-A420 Ex. plate 1 Alminum JIS Explosionproof and Intrinsic safety

*ZZPFCX1-A42R Minimum order q’ty 5 pcs.


Need inquiry.
60 –––––––– Detecting unit 1 Contact our office for inquiry.
61 *ZZPFCX4-B080 O - Ring 2 Viton 
 Minimum order q’ty 10 pcs.
*ZZPFCX4-B081 Gasket 2 Teflon 

4th digit of 5th digit of


type code type code
62 *ZZPFCX4-B091 Cover 2 SCS14 A,S
*ZZPFCX4-B093 Cover 2 SCS14 B,E,T,X
*ZZPFCX4-B095 Cover 2 SCS14 V,W 1,2,3
*ZZPFCX4-B097 Cover 2 SCS14 V,W 4

64A *ZZPFHC1-B121 Vent / drain kit 2 Stainless steel Rc 1/4


*ZZPFHC1-B122 Vent / drain kit 2 Stainless steel NPT 1/4
66A *ZZPFHC1-B143 Bolt / Nut kit 4 C.S. Hexagon socket head cap screw
15th digit of type code
*ZZPFHC1-B144 Bolt / Nut kit 4 Stainless steel E,S
*ZZPFHC1-B145 Bolt / Nut kit 4 Stainless steel F,T
68 *ZZPFHC1-B160 O - Ring 1 Chloroprene Minimum order q’ty 10 pcs.
80A *ZZPFHC1-B171 Mounting braket kit 1 Stainless steel

Note) Approval pending

67
A1 BUILT-IN ARRESTER
General

An arrester is used to protect a transmitter or receiver from an abnormal voltage such as lightning
surges induced into signal lines. A built-in type arrester is mounted behind the terminal unit. A
nameplate marked “with arrester” is attached to the terminal unit of transmitter with a built-in arrester.

Installation

The built-in arrester should be used in combination with panel mounting type arrester (type PXC) for
distributor protection.

+ 1 2 –
PXC PTL

– 5 E 6 + E

Transmitter Panel mounting Distributor


(with arrester) type arrester

Grounding

Since transmitter and arrester groundings are internally connected together, user have only to connect
the external grounding terminals to ground.
Grounding terminal must be used, in case of the explosionproof or intrinsic safety type transmitter.

FCX-A2 series transmitter


Grounding terminal

CK

+
CK

External grounding terminal

1. Grounding resistance should be 100Ω or less.


Important 2. Avoid common grounding with a lightning rod.

68
Maintenance

Check of arrester
• Measure output current from the transmitter check terminals and output current to flow into
transmitter (see figure below).
When current is measured with an ammeter connected to CK+ and CK– terminals, the inter-
nal resistance of the ammeter should be 12Ω or less.
• If the measured two output current are the same, the arrester is normal.
• In case the measured values have a difference of 0.1% (0.016mA) or more, the arrester is not
functioning.
• In the above case, the arrester unit (terminal unit) should be replaced with a new one.
Limitation of insulation resistance and dielectric strength test
An insulation resistance and dielectric strength test should be avoided as a rule, since it may
damage the arrester.

Output measurement at check terminals


Digital voltmeter

To CK +

To CK –

Standard resistor
(1 or 10 )

Output measurement outside transmitter


* Disconnect the wire from the – (minus)
terminal and connect the measurement
To (–) terminal
device a shown below.

Digital voltmeter

To (+) terminal

DC power To (+) side wiring


supply To (–) side
wiring

Standard resistance

69
A2 CALIBRATION
Preparation for calibration

The transmitter should be calibrated in a calibration room. For calibration of each transmitter, the
following devices are required.
• Pressure source and pressure measuring equipment (should have as high an accuracy as possible)
* Measurable ranges are listed in the table below.
• Power supply: DC power supply (24 V DC) or Fuji Electric FC series power supply unit
(type PXJ)
• Load resistor: Standard resistor 250 W (within ±0.0125 W)
• Measuring device: Digital voltmeter (capable of measuring transmitter output with an accuracy
better than 0.1%)
* Use meter having a 5-digit display.
• Hand Held Communicator (HHC) type FXW
Measurable range

Differential pressure range of FKC

Differential pressure range


[kPa] {mbar} <inH2O>
0.1 to 1 {1 to 10} <0.4 to 4>
0.1 to 6 {1 to 60} <0.4 to 24>
0.32 to 32 {3.2 to 320} <1.25 to 12.5>
1.3 to 130 {13 to 1300} <5.2 to 520>
5 to 500 {50 to 5000} <0.7 to 70psi>
30 to 3000 {300 to 30000} <4.3 to 430psi>

Pressure range of FKG


Pressure range
[kPa] {bar} <psi>
1.3 to 130 {0.013 to 1.3} <0.2 to 20>
5 to 500 {0.05 to 5} <0.7 to 70>
30 to 3000 {0.3 to 30} <4.3 to 430>
100 to 10000 {1 to 100} <15 to 1500>
500 to 50000 {5 to 500} <70 to 7000>

Pressure range of FKA


Pressure range
[kPa abs] {bar•abs} <inHg abs>
1.6 to 16 {0.016 to 0.16} <0.46 to 4.6>
1.6 to 130 {0.16 to 1.3} <0.46 to 38>
5 to 500 {0.05 to 5} <0.7 to 70psi abs>
30 to 3000 {0.3 to 30} <4.3 to 430psi abs>

70
Differential pressure range of FKD
Differential pressure range
[kPa] {bar} <inH2O>
0.32 to 32 {0.0032 to 0.32} <1.25 to 125>
1.3 to 130 {0.013 to 1.3} <5.2 to 520>
5 to 500 {0.05 to 5} <0.7 to 70psi>

Pressure range of FKB


Pressure range
[kPa] {bar} <psi>
1.3 to 130 {0.013 to 1.3} <0.2 to 20>
5 to 500 {0.05 to 5} <0.7 to 70>
30 to 3000 {0.3 to 30} <4.3 to 430>
100 to 10000 {1 to 100} <15 to 1500>
500 to 50000 {5 to 500} <70 to 7000>

Differential pressure range of FKE


Differential pressure range
[kPa] {mbar} <inH2O>
0.32 to 32 {3.2 to 320} <1.25 to 125>
1.3 to 130 {13 to 1300} <5.2 to 520>
5 to 500 {50 to 5000} <0.7 to 70psi>

71
Calibration procedure

(1) Make wiring according to the diagram below.


Connect DC power supply (power source), digital voltmeter (measuring device), standard resis-
tance and HHC (Hand Held Communicator):
When current is measured with an ammeter connected to CK+ and CK – terminals, the internal
resistance of the ammeter should be 12Ω or less.

HHC

Digital voltmeter

DC power supply
Load resistance

Standard resistance

Important For communication with the HHC, a load resistor of 250Ω is necessary.

(2) Calibration of output circuit (D/A)


Calibrate the output circuit with reference to “Calibration of output circuit” in “ADJUSTMENT”
in Chapter 4.

(3) Zero/span adjustment


Refer to “Zero/span adjustment” in Chapter 4.
(4) Accuracy test
Apply input pressures in the order of 0%, 25%, 50%, 75%, 100%, 75%, 50%, 25% and 0%, and
read output at each input pressure.
Make sure the difference between each output value and input pressure (%) is within the accu-
racy rating listed in the table below.
The voltage values in the table are dependent on use of “DC power supply + standard resistor
250Ω + digital voltmeter (measuring device).

Accuracy (example)
Measurement category Reference value
Accuracy:0.1% Accuracy:0.2%
Percent display (%) 0, 25, 50, 75, 100 ±0.1 ±0.2
Current measurement (mA) 4, 8, 12, 16, 20 ±0.016 ±0.032
Voltage measurement (V) 1, 2, 3, 4, 5 ±0.004 ±0.008

72
A3 PARAMETER SETTING PRIOR TO DELIVERY
The damping value (time constant), function of zero/span adjust screw, output current mode, indicator
scale, cut point, mode below cut point and burnout, have been set prior to delivery as shown in the
following. Each parameter is changed by using HHC.

No. Item Contents of parameter

Damping value No damping


1
(time constant) (= measuring period)

Zero adjust Zero point adjustment possible


2
screw function (Note 1)

To be set by designation
Current output mode
when ordering (Note 2)
3
Digital indicator scale
To be set by designating type
(9th digit of code
when ordering
symbols)
Cut point
4 (square-root extraction 7.07%
mode setting)

Mode below cut point


5 Linear
(square-root setting)

To be set by designation
6 Burnout
when ordering (Note 3)

7 Linearization function Invalid

Note 1) For span adjustment, HHC should be used. HHC can also be used for zero adjustment.
Note 2) In both the differential pressure transmitter (Type: FKC) and remote seal type (Type:
FKD), the output current mode is set in linear unless it is designated.
Note 3) Burnout direction is selectable from HHC, Hold, Over scale (20.8 to 21.6mA), under scale
(3.2 to 3.8mA).

73
A4 HAZARDOUS LOCATION INSTALLATION INFORMATION
This appendix contains documents that present installation instruction for the FCX-AII Series
Transmitter in a hazardous location. refer to these figures when installing or servicing a transmitter
mounted in a hazardous location.
When installed, the apparatus must be provided with a voltage limited device which prevent the rated
voltage of 45V being exceeded.

74
INSTALLATION INSTRUCTIONS
+ 4-20mA


Any electrical devices
FM approved FM approved ≤ 250Vrms / 250Vdc
FCX-A Transmitters safety barrier

Vmax = 42.4V
Imax = 113mA
Li ≤ 1.134mH
Ci ≤ 34.2nF FM approved
Hand Held Communicator
Model FXW
FCX-A Transmitters : J.I. 4R3A2. AX
Class I, II, II Vmax = 42.4V
Division 1, 2 Imax = 225mA
Groups A,B,C,D,E,F and G Li = 0
Ci 10nF
Hand Held Communicator
Class I
Division 1, 2
Groups A,B,C and D

Hazardous Locations Non Hazardous Locations

Notes :
1) The Intrinsic Safety Entity concept allows the interconnection of FM Approved Intrinsically safe
devices with entity parameters not specifically examinated in combination as a system when :
Uo orVoc or Vt ≤ Vmax, Io or Isc or It ≤ Imax, Ca or Co ≥ Ci+Ccable, La or Lo ≥ Li + Lcable, Po ≤ Pi.
2) The Hand Held Communicator, Model FXW may be connected at any point between the transmitter
and the safety barrier, Provided the hand held communicator is a FM Approved model.
3) Dust-tight conduit seal must be used when installed in Class II and Class III environments.
4) Control equipment connected to the Associated Apparatus must not use or generate more than
250Vrms or Vdc.
5) Installation should be in accordance with ANSI/ISA RP12.6 “Installation of Intrinsically Safe systems
for Hazardous (Classified) Locations” and the National Electrical Code® (ANSI/NFPA70) sections
504 and 505.
6) The configuration of associated Apparatus must be Factory Mutual Research Approved under Entity
Concept.
7) Hand Held Communicator and Associated Apparatus manufacturer’s installation drawing must be
followed when installing this equipment.
8) AEx ib is suitable only for Class I, Zone 1, Hazardous (Classified) Locations and is not suitable for
Class I, Zone 0, or Class I, Division 1 Hazardous (Classified) Locations.
9) No revision to drawing without prior Factory Mutual Research Approval.
10) Simple Apparatus is defined as a device that neither generates nor stores more than 1.2V, 0.1A 20uJ or
25mW.
Contents on this page are based on TC520807
Figure 1. FCX-AII Series transmitter, Intrinsically Safe Installation or FM

75
Fuji Electric France S.A.
46, Rue Georges Besse - Z I du Brézet
63 039 Clermont-Ferrand cedex 2 — FRANCE
France : Tél. 04 73 98 26 98 - Fax 04 73 98 26 99
International : Tél. (33) 4 7398 2698 - Fax. (33) 4 7398 2699
E-mail : sales.dpt@fujielectric.fr