You are on page 1of 16

Air Elimination & Control

CA Expansion Tanks
Taco CA Expansion tanks are full acceptance Captive Air expansion tanks that provide
separation of air and water. Tough, durable and long lasting. The Taco CA is available
in a variety of sizes and capacities to fit your application.

©Taco Catalog #400-1.2 Effective Date: 12/01/14


Supersedes: 07/31/14 Printed in USA
Features & benefits

Eliminate Pressure For applications CA Specifications:


and Flow problems: requiring NSF/ANSI 61-G • Shell — Fabricated Steel
• Better comfort. Eliminate Cerification Designed and Constructed
flow problems. Our CA Model and PAX model per ASME Section VIII Div. 1
expansion tanks are available
• Eliminate water logged • Bladder — Field Removable
with an option for NSF/ANSI 61-G
expansion tanks
Certification. This can be requested
• Reduce expansion tank sizes by adding a “P”to the end of a CA NSF/ANSI 61-G [ P] Option,
Example: P/N PAX30-150P)
up to 80%. or PAX type expansion tank model
number. (Example: CA140-125P) Models certified to NSF 61-G are
• Eliminate expansion tank required to be installed on the cold
water side of the hot water heater.
corrosion problems.
Increase Reliability and
• Reduce problems with Reduce Maintenance Costs Standard Optional
burst bladders. • Full Acceptance bladders Working 125 PSIG 150 PSIG
eliminate burst bladders Pressure: (862 KPA) (1034 KPA)

Dramatically Reduce

175 PSIG
(1206 KPA)
Expansion Tank Sizes • Eliminate tank corrosion by
isolating water from tank 250 PSIG
Captive Air expansion tanks (1723 KPA)
eliminate the many gallons of
300 PSIG
water required to compress (2068 KPA)
atmospheric pressure air in an
Operating 240˚F Consult
air cushion plain steel tank to Temperature: (116C) Factory
the fill pressure. This allows a
reduction in Captive Air
expansion tank sizes of up
to 80% compared to air
cushion plain steel tanks.

-2-
Applications

Air Control Through Water contains a certain amount can be dissolved or entrained. For
Pressure Control of entrained air. If this air comes example at 100˚F and 80 PSIA water
All hydronic systems operate under out of solution at lower pressures, can contain 8% air by volume. At
a variable amount of pressure. For it can increase corrosion rates of 100˚F and 20 PSIA the percentage
closed systems the pressure varies metals within the system. In addi- decreases to 2%.
primarily due to the expansion of tion, air can form pockets at the
water as it is heated or cooled. As top of pipes and coils of terminal The conclusion is that air is least
the water is heated the pressure units. These air pockets can actually soluble in water at lowest pressure.
increases and as the water is cooled restrict or block flow in a hydronic Air separators should therefore be
the pressure decreases. piping system. This is referred to as located at these points.
“air locking”. The lowest pressure in a system
The pressure in a closed system var- is typically at the expansion tank,
ies between a minimum and a max- Figure 1 shows a solubility curve since this is the point of no pressure
imum. The minimum is controlled for air in water. Note that at a fixed change and the location of the fill
by the fill valve and the initial fill temperature reducing the pres- valve. Therefore, the general rule of
pressure of the expansion tank. The sure reduces the amount of air that thumb in hydronic systems is that
maximum pressure is determined “Air separators should be
located at the expansion tank
18%

by the relief valve and the size of 16%

the expansion tank allowing the 14%


SOLUBILITY OF AIR
IN WATER AT STANDARD
TEMPERATURE AND PRESSURE
connection to the system.”
water to expand into the tank. 12%

10%

8%

If the pressure is not maintained 6% 90


80
70
between these limits then the sys- 4% 60
50
PSIA

40
30
tem will not perform properly.
2%
20
10
32 50 75 100 125 150 175 200 212
Not maintaining minimum pres- TEMPERATURE (DEGREE F)

sures will create air problems. Figure 1

FAN COIL

TACO
CIRCULATOR

TACO
TWIN TEE

TACO
AIR SEPARATOR

TACO PUMP

TACO TACO
MULTI-PURPOSE SUCTION
TACO
VALVE DIFFUSER
EXPANSION
TANK

BOILER

Figure 2 – Boiler and Expansion Tank/Air Separator Location

-3-
Applications

FAN COIL

TACO
CIRCULATOR

TACO
TWIN TEE

TACO 4900
AIR SEPARATOR

TACO PUMP

TACO
TACO SUCTION
MULTI-PURPOSE DIFFUSER
VALVE
TACO
EXPANSION
TANK

CHILLER

Figure 3 – Chiller and Expansion Tank/Air Separator Location

For multi-story buildings this is solubility of air in water at this pres- is to install additional air separators
important. If the system pressure is sure and 40˚F is 45%. At the top of at upper levels of the building. A
not maintained above atmospheric the building, assuming, 10 psi posi- hydronic system can have multiple
at the top of the building then not tive pressure, the solubility is only air separators, but should have only
only will air come out of solution, 4%. one expansion tank. These air sepa-
but air can actually be drawn into rators should be high efficiency sep-
the system. This will result in loss of Obviously air will come out of solu- arators similar to Taco’s 4900. See
system performance with areas of tion at the top of the building with Taco Catalog #400-1.4 for additional
low and no flow in this portion of the expansion tank and air separa- information.
the system. tor located at the bottom. By “over
pumping”, to maintain 40 psi at the Another solution is to locate the
For high rise buildings this is espe- top of the building, the solubility of expansion tank and air separator at
cially important. Frequently the air goes back up to 10%. the top of the building where the
expansion tank, air separator and pressure is the lowest and the air
fill valve are located at lower levels For pumps located at upper levels
of the building this is even more is least soluble in water. This will
of the building. At upper levels air require the running of a dedicated
will come out of solution as the problematic. Pumps in these loca-
tions can actually be attempting to line from the top of the building to
pressure decreases. This is similar the suction of the system circulat-
to what divers experience as the pump air. For centrifugal pumps the
point at which their head falls off is ing pump. This will also reduce the
“bends”. One solution, which size of the expansion tank since the
designers and maintenance per- in the range of 3% to 5% air volume
in water. difference between the initial fill or
sonnel learned over time, was to minimum pressure and relief valve
“over pump” the system through Maintenance personnel and field or maximum pressure can be larger.
high pump heads. This increased engineers report many instance of
the pressure at upper levels of the poor pump performance due to Not maintaining maximum pres-
building and forced air back into unknown causes. A large portion sure can result in several problems,
the system. of these mysterious problems have including burst diaphragm or blad-
turned out to be secondary pumps ders in partial expansion captive
For example, in a 50 story building, air tanks, weeping relief valves and
the static pressure at the bottom located above expansion tanks.
A better solution to “over pumping” failure of components
of the system could be 250 psi. The
-4-
Applications

Causes of over system pressuriza- The tank must now be sized for the This permanent separation allows the
tion can be undersized expansion initial fill volume plus the volume of tank to be precharged on the air side
tanks, water logged air cushion any expanded water. This makes the of the bladder to the minimum oper-
plain steel expansion tanks and tank much larger. ating or fill pressure. This eliminates
burst diaphragms or bladders in the initial water volume needed to
As air is released through air vents,
Captive Air tanks. compress the air from atmospheric
the air cushion in the tank can be
pressure to the system minimum
absorbed into the system fluid leav-
Pressure Control (fill) pressure. This allows the bladder
ing the tank water logged and elimi-
Through Air Control expansion tank to be charged to the
nating the system pressure control
Many systems designed in the past fill pressure without the introduc-
provided by the plain steel tank.
and some designed today, attempt to tion of system fluid offering a sizable
When this occurs the expanded water
control air by means of an old style air reduction in the required tank volume
volume must now seek a new outlet
cushion plain steel tank and air vents (see figure 5 A). The use of a Captive
which is normally the relief valve or
in the piping. Air expansion tank often allows the
thru the rupture of one of the other
reduction in required tank sizes up to
system componets.
The air cushion plain steel tank uses a 80% compared to air cushion or plain
tank filled with water and an air cush- A better solution is to use a Captive steel tanks.
ion at the top of the tank for water to Air tank. In a Captive Air tank the air
During system operation any expanded
expand into as it is heated. The initial is held captive by the use of a blad-
water, in the diaphragm or bladder,
atmospheric air in the tank must be der or diaphragm with the expanded
compresses the precharge air to the
initially compressed to the fill pres- water being held on one side of the
maximum pressure. This compressed
sure. This requires an initial charge diaphragm or bladder and the air on
air cushion then pushes the fluid back
or fill of water to accomplish this as the other side.
into the system when it contracts.
shown in Figure 4.

A. Empty Tank Pa
A. After system B. At operating pressure
has been filled P1 Boiler in operation Po
Atmospheric
Pressure
Tank Empty

B. After system has been filled P1


Air Cushion at Min. Expanded
Operating Pressure P1 Water

Initial Water Fill


Pre-pressurized air cushion Pre-pressurized air cushion at
at minimum operating pressure. maximum operating pressure.
(Bladder in collapsed condition) (Bladder accommodating expansion volume)
C. At operating pressure Po

Figure 5 – Captive Air pressurization process


Initial Water Fill
Remains Constant
Expanded Water Vol
Air Cushion at Max. Operating
Pressure Boiler in Operation

Figure 4
Plain steel pressurization process -5-
Applications

This can be seen in the following System fill pressure of 10 psig, This is a difference of greater than
example problem. System volume of 3000 gallons, 81% reduction in required tank size
with steel piping system, System
System: Chilled water at 40˚F
fill pressure of 65 psig and a 90 psig Another advantage of the perma-
System volume: 3000 gallons
maxiumum operating pressure. nent separation of air and water in
System piping : Steel
a Captive Air tank is to eliminate
The ASHRAE formula for plain steel Sizing a plain steel expansion tank the absorption of air back into the
expansion tank sizing is: [(v2/ v1) – 1] – 3aΔt water that is found in air cushion or
Vt = Vs plain steel tanks.
[(v2/ v1) – 1] – 3aΔt
(Pa/ P1) – (Pa/ P2)
Vt = Vs
(Pa/ P1) – (Pa/ P2) Location of
For Expansion Tank
Where Location of the expansion tank in
Vs = 3000 gallons
vt = volume of expansion tank, gal v1 = .01602 ft3/lb (40˚F) the system will also affect system
v2 = .01613 ft3/lb (100˚F) performance.
vs = volume of water in system, gal
t1 = lower temperature, ˚F Pa = 14.7 psia
P1 = 65psig +14.7psia = 79.7psia The expansion tank is the point of
t2 = higher temperature, ˚F no pressure change in the system.
P2 = 90psig+14.7 psia = 104.7 psia
Pa = atmospheric pressure, psia a = 6.5x 10-6 in/in˚F for steel This can be seen from Boyle’s Law:
P1 = pressure at lower Dt = 60˚F
temperature, psia P1V1/T1 = P2V2 /T2
P2 = pressure at higher Vt = 388.83 gallons
temperature, psia If the temperature (T1 and T2) and
Sizing of a Captive Air volume (V1 and V2) are constant
v1 = specific volume of water at
lower temperature, ft3/lb expansion tank with the pump on or off, then
the pressure (P1 and P2) must also
v2 = specific volume of water at
higher temperature, ft3/lb Pa= P1 remain constant.

a = linear coefficient of thermal


expansion, in./in. -˚F [(v2/ v1) – 1] – 3aΔt Therefore the point of connection
Vt = Vs of the expansion tank to the system
= 6.5 x 10-6 in./in. -˚F for steel is a point of no pressure change.
1 – (Pa/ P2)
= 9.5 x 10-6 in./in. -˚F for copper For Typically located at the suction side
DT= (t2 - t1), ˚F Vs = 3000 gallons of the system pumps.
V1 = .01602 ft3/lb (40˚F)
Chilled water sizing example: V2 = .01613 ft3/lb (100˚F)
Sizing a plain steel tank for a chilled Pa = 79.7psia (due to tank precharge)
water system with a temperature P1 = 65psig + 14.7psia = 79.7psia
range of 40˚F to 100˚F (ambient P2 = 90psig + 14.7psia = 104.7psia
temperature). a = 6.5x 10-6in/in F for steel
Dt = 60˚F
Vt = 71.55 gallons

-6-
Applications

To prevent air from being drawn Therefore, the general rule of not affect the pressure in the tank.
into the system the pressure in the thumb in hydronic systems is that If there are multiple tanks in the
system must be everywhere above “Expansion tanks should be locat- system then the pump head will
atmospheric pressure. ed on the suction side of pumps.” affect the pressure in the tank.
The pump will be able to transfer
The location of the expansion tank Multiple expansion tanks will cause water from one tank to the other
relative to the pump suction will pressure problems in systems. The depending on the pressure
then determine if the system is location of the expansion tank in difference generated by the
everywhere above atmospheric the system is the point of no pres- pump between the tanks.
pressure. This can be seen in the sure change. The pump head does
following figures.

In Figure 6 the expansion tank is FAN COIL

located on the discharge side of the


pump.
TACO
CIRCULATOR

The fill pressure is 25 psi. The pump


differential pressure is 35 psi. Since TACO
TWIN TEE
DISCHARGE SUCTION
PRESSURE = 25 PSI PRESSURE = -10 PSI

the expansion tank is the point of TACO


MULTI-PURPOSE

no pressure change the pump dif- FILL VALVE


PRESSURE = 25 PSI
VALVE
TACO
AIR SEPARATOR

ferential pressure is subtractive from TACO PUMP


DIFFERENTIAL
PRESSURE = 35 PSI
TACO PRESSURE

the fill pressure. The pump suction REDUCING VALVE

pressure is now -10 psi (25 – 35) or TACO


EXPANSION

below atmospheric. This will cause NOTE: Not Recommended


TANK

CHILLER

air problems with air potentially


being drawn into the system. Figure 6 – Expansion tank located on discharge of pump

Figure 7 is the expansion tank locat-


ed on the suction side of the pump.

The fill pressure, and pump suc- FAN COIL

tion pressure, is 25 psi. The pump


differential pressure is 35 psi. Since
the expansion tank is the point of
TACO
CIRCULATOR

no pressure change the pump dif- TACO


TWIN TEE
DISCHARGE SUCTION

ferential pressure is additive to the PRESSURE = 60 PSI PRESSURE = 25 PSI

TACO

fill pressure. The pump discharge MULTI-PURPOSE


VALVE
FILL VALVE
PRESSURE = 25 PSI

pressure is now 60 psi (25 + 35) or


TACO
AIR SEPARATOR
TACO PUMP
DIFFERENTIAL

above atmospheric. Everywhere in


PRESSURE = 35 PSI TACO PRESSURE
REDUCING VALVE

the system the pressure is above TACO


EXPANSION

atmospheric. TANK

CHILLER

Figure 7 – Expansion tank located on suction side of pump

-7-
Applications

FAN COIL
Figure 8 is a system with two
expansion tanks. The point of no
TACO
EXPANSION
pressure change will be some-
TACO
TANK
where between the two tanks.
CIRCULATOR

TACO
TWIN TEE POINT OF NO PRESSURE CHANGE
IS BETWEEN EXPANSION TANKS
Therefore, the general rule of
TACO
thumb in hydronic systems is that
MULTI-PURPOSE
VALVE

TACO
“Multiple expansion tanks in a system
TACO PUMP
AIR SEPARATOR
is not recommended” since unstable
pressure conditions will result.
TACO

Types of
EXPANSION
TANK

CHILLER
Expansion Tanks
Figure 8 – Multiple expansion tanks in system Air Cushion Plain Steel
Expansion Tank
FAN COIL

TACO
CIRCULATOR

Taco air cushion plain steel tanks


TACO TACO PLAIN STEEL
TWIN TEE EXPANSION TANK
SLOPE PIPE

are applied in commercial, institu-


TACO PRESSURE UP TO TANK
REDUCING VALVE
TANK FITTING
COLD WATER SUPPLY

TACO
tional and industrial applications for
MULTI-PURPOSE
VALVE

TACO
the control of pressure in hydronic
TACO PUMP AIR SEPARATOR
systems. The air cushion plain steel
tank uses a tank filled with water
and an air cushion at the top of the
CHILLER

tank for water to expand into as it


Figure 9 – Air cushion or plain steel expansion tank is heated.

In this tank it is desirable to direct


TANK
the separated air from the air sepa-
AIR rator to the space above the water
level in the expansion tank (Figure
9). The air from the air separator
WATER
is piped to the expansion tank
through a special tank fitting.

BAFFLE TRAPS
AIR AND DIRECTS
This fitting directs the air to the top
portion of the tank, and discour-
IT TO THE TOP OF
TANK THRU
OUTER TUBE

ages air from migrating back into


the system (Figure 10), when the
TANK FITTING
system cools. Note that since
Figure 10 – Expansion tank air fitting

-8-
Applications

the air is “recycled” to provide a Partial Acceptance Captive Air Partial Acceptance
cushion in the expansion tank, this Diaphragm Expansion Tank Captive Air Bladder
system is called an “Air Control” Taco CX partial acceptance Captive Expansion Tank
system. As noted previously the air Air diaphragm expansion tanks Taco CBX partial accep-
cushion in the tank can be deplet- are applied in commercial, institu- tance bladder Captive
ed due to absorption of air into tional and industrial Air expansion tanks are
the water. It can also be depleted applications for the applied in commercial,
by loosing air through air vents in control of pressure institutional and indus-
the piping. Care must also be taken in hydronic systems. trial applications for the
to insure that piping between the Diaphragm tanks use control of pressure in
air separator and the plain steel a diaphragm to per- hydronic systems. CBX
expansion tank is pitched at least manently separate bladder tanks use a field replace-
3 degrees (Figure 9) to facilitate the air and water. able bladder to permanently sepa-
the migration of captured air back In a diaphragm tank rate the air and water.
into the expansion vessel. Systems the air is held captive by the use of This permanent separation allows
with plain steel expansion tanks a diaphragm with the expanded the tank to be precharged on the
must not have automatic air vents water being held on one side of the air side to the minimum operat-
installed as this will lead to the loss diaphragm and air on the other. ing or fill pressure. This eliminates
of the expansion tank air cushion. This permanent separation allows many gallons of water to compress
if air is lost in the tank then the tank the tank to be precharged on the atmospheric pressure air in an air
will become water logged.With a air side to the minimum operat- cushion or plain steel tank to the fill
water-logged expansion tank, the ing or fill pressure. This eliminates pressure. This allows the reduction
expanded water must now seek a many gallons of water to compress in Captive Air expansion tank sizes
new outlet which can be the relief atmospheric pressure air in an air of up to 80% compared to air cush-
valve on one of the major compo- cushion or plain steel tank to the fill ion or plain steel tanks.
nents. pressure. This allows the reduction
As note previously the tank must be in Captive Air expansion tank sizes In a bladder tank the bladder is not
sized for the expansion of the water of up to 80% compared to air cush- attached to the tank wall like a dia-
in the system plus the initial charge ion or plain steel tanks. phragm tank. Rather it is suspended
of water to compress atmospheric In a diaphragm tank the diaphragm inside the tank very much like a bal-
air in the tank to the fill pressure. is attached to the tank wall and loon. Expanded water flows into the
This makes the tank much larger. cannot move inside the tank. As a inside of the bladder. Air is on the
The tank is also subject to corrosion result the tank has a limited accep- outside of the bladder between the
with the presence of air and oxygen tance volume. In addition, there bladder and the tank. As a result
in the tank. is some water in contact with the no water is in contact with the tank
tank wall providing an opportunity wall minimizing corrosion
Applications for corrosions. In a partial acceptance bladder tank
• Smaller systems
the bladder is of limited acceptance
• Lower cost Applications volume and does not stretch. As
• Ceiling mounted to • Smaller systems
a result, if there is an overpressure
save floor space • Lower cost condition in the system the bladder
will burst, again, very much like a
balloon.

Applications
-9- • Larger systems
• Lower cost
Applications

Full Acceptance Captive Air the tank to be precharged on is in contact with the tank wall
Bladder Expansion Tank the air side to the minimum minimizing corrosion. In a full
Taco CA full acceptance bladder operating or fill pressure. This acceptance bladder tank the
Captive Air expansion tanks are eliminates many gallons of water bladder is of full acceptance
applied in com- to compress atmospheric pres- volume and can expand to the
mercial, institu- sure air in an air cushion or plain full volume of the tank. As a
tional and indus- steel tank to the fill pressure. This result, the bladder will not burst
trial applications allows the reduction in Captive Air if the system experiences an
for the control expansion tank sizes of up to 80% overpressure condition.
of pressure in compared to air cushion or plain
hydronic systems. steel tanks. Applications
• Larger systems
CA tanks use a In a bladder tank the bladder is
field replaceable not attached to the tank wall like • Systems where reliability
bladder to per- a diaphragm tank. Rather it is and lower maintenance
costs are important
manently sepa- suspended inside the tank very
rate the air and much like a balloon. Expanded “P” option available for
water. water flows into the inside of the applications requiring
NSF/ANSI 61-G certification
bladder. Air is on the outside of
This permanent the bladder between the bladder
separation allows and the tank. As a result no water

-10-
Selection Procedure

EXAMPLE 1 Sizing of a Captive Air Calculation of Net


expansion tank system expansion —
Problem:
Pa= P1
Select a full acceptance bladder Net
style expansion tank for a chilled [(v2/ v1) – 1] – 3aΔt System
water installation. The mechanical Vt = Vs Expansion = Vs {[(v2/ v1)-1] – 3 α Δt}
room and expansion tank are locat- 1 – (Pa/ P2)
ed on the lower level. Reliability = 3000 {[(.01613/.01602) -1] – 3 (6.5x10-6) 60}
vt = .01602 ft3/lb (40˚F)
and maintenance costs are a consid- v2 = .01613 ft3/lb (100˚F)
eration. Steel system piping. = 3000 {.005696}
a = 6.5x 10-6in/in ˚F for steel
Conditions: Δt = 60˚F = 17.09 gallons
System Volume = 10,000 gallons P1 = 100 ft * .434 psi/ft + 5 psig
Minimum temperature = 40˚F (for positive pressure at top
Maximum temperature = 100˚F of building) + 14.7 psia
Building height = 100 ft.
= 48.4 psia
Relief valve (chiller) = 90psig
P2 = 90psig + 14.7psia = 104.7 psia

Calculate required tank volume – For a system where reliability and


maintenance are important select
[(v2/ v1) – 1] – 3aΔt tank with full acceptance. Captive
Vt = Vs Air bladder tank model CA140.
1 – (Pa/ P2) The bladder on this tank is unaf-
fected by overpressure conditions
Vt = 3000 {[(.01613/.01602) -1] – 3 (6.5x10-6) 60}/ (1 – 48.4/104.7) in the system and is more reliable.
Acceptance volume of the tank is
= 31.78 gallons 37 gallons and the volume of the
tank is 37 gallons.

-11-
Selection Procedure

EXAMPLE 2
Problem:
Select an expansion tank for a heat-
ing water installation. The mechani- Calculation of Net system expansion –
cal room and expansion tank are Net System Expansion
located on the roof. First cost is a = Vs {[(v2/ v1)-1] – 3 α Δt}
major consideration. System piping
copper.
= 1000 {[(.01692/.01602) -1] – 3 (9.5x10-6) 200}
Conditions:
System volume 1,000 gallons. = 1000 {.05047}
Minimum temperature = 40 F
Maximum temperature = 240 F = 50.48 gallons
Building height = 50 ft
Relief Valve at boiler = 50 psig Calculate required tank volume –
Sizing of a Captive Air
expansion tank [(v2/ v1) – 1] – 3aΔt
Vt = Vs
Pa= P1 1 – (Pa/ P2)
[(v2/ v1) – 1] – 3aΔt
Vt = Vs Vt = 1000 {[(.01692/.01602) -1] – 3 (9.5x10-6) 200}/ (1 – 24.04/64.7)
1 – (Pa/ P2)
= 80.32 gallons
v1= .01602 ft3/lb (40˚F)
v2= .01692 ft3/lb (240˚F) Because first cost is a major consideration select a partial acceptance
Captive Air bladder tank model CBX425. This tank is lower first cost than
α=9.5x 10-6in/in F for copper piping a full acceptance Captive Air tank. However, it is subject to a burst blad-
Δt=200 F der under over pressure conditions. Acceptance volume of the tank is
61 gallons. The volume of the tank is 112 gallons.
Determine minimum pressure –
Minimum pressure equals static
pressure plus 5 psi positive pressure
at top of the building (assume 10 ft
of static pressure).

P1
= 10ft x .434 psi/ft + 5 psi
(positive pressure) + 14.7 psia

= 24.04 psi
Maximum pressure equal the
relief valve setting
P2 = 50 psig +14.7 psia
= 64.7 psia
Submittal Data
#401-083 Product Data
#401-083P

Effective December 1, 2014


TANK H B D R SHIPPING SYSTEM
MODEL VOLUME HEIGHT DIAMETER DIAMETER RADIUS WEIGHT CONNECTION
NUMBER SIZE
GAL. LIT. INCH MM INCH MM INCH MM INCH MM LBS. Kg
CA90-125 23 90 29-1/8 740 16 406 20 508 4-1/4 108 120 55 1" NPT (25.4mm)
CA140-125 37 140 40-1/8 1019 16 406 20 508 4-1/2 114 195 88 1" NPT (25.4mm)
CA215-125 57 215 58-7/8 1495 16 406 20 508 4-1/2 114 290 132 1" NPT (25.4mm)
CA300-125 79 300 57-3/4 1467 20 508 24 610 5 127 320 145 1-1/2" NPT (38.1mm)
CA450-125 119 450 77-3/8 1965 20 508 24 610 5 127 400 181 1-1/2" NPT (38.1mm)
CA500-125 132 500 85-3/4 2178 20 508 24 610 5 127 420 191 1-1/2" NPT (38.1mm)
CA600-125 158 600 71-7/8 1826 24 610 30 762 6-1/4 159 460 209 1-1/2" NPT (38.1mm)
CA700-125 185 700 80-5/8 2048 24 610 30 762 6-1/4 159 525 238 1-1/2" NPT (38.1mm)
CA800-125 211 800 89-7/8 2283 24 610 30 762 6-1/4 159 590 268 1-1/2" NPT (38.1mm)
CA900-125 238 900 73-1/8 1857 30 762 36 914 7-7/16 189 690 313 1-1/2" NPT (38.1mm)
CA1000-125 264 1000 79 2007 30 762 36 914 7-7/16 189 790 358 1-1/2" NPT (38.1mm)
CA1100-125 291 1100 85-1/4 2165 30 762 36 914 7-7/16 189 865 392 1-1/2" NPT (38.1mm)
CA1200-125 317 1200 91 2311 30 762 36 914 7-7/16 189 940 426 1-1/2" NPT (38.1mm)
CA1300-125 344 1300 97 2464 30 762 36 914 7-7/16 189 980 445 1-1/2" NPT (38.1mm)
CA1400-125 370 1400 103 2616 30 762 36 914 7-7/16 189 1020 463 1-1/2" NPT (38.1mm)
CA1500-125 396 1500 73-3/8 1864 40 1016 48 1219 10-15/16 278 1200 544 1-1/2" NPT (38.1mm)
CA1600-125 422 1600 76-5/8 1946 40 1016 48 1219 10-15/16 278 1380 626 1-1/2" NPT (38.1mm)
CA1800-125 475 1800 83-1/2 2121 40 1016 48 1219 10-15/16 278 1515 687 1-1/2" NPT (38.1mm)
CA2000-125 528 2000 90-3/8 2296 40 1016 48 1219 10-15/16 278 1650 748 1-1/2" NPT (38.1mm)
CA2500-125 660 2500 107-1/8 2721 40 1016 48 1219 10-15/16 278 1838 834 1-1/2" NPT (38.1mm)
CA3000-125 792 3000 94-1/8 2391 44 1118 54 1372 11-7/16 291 2025 919 2" NPT (50.8mm)
CA4000-125 1056 4000 120-3/4 3067 44 1118 54 1372 11-7/16 291 2400 1089 2" NPT (50.8mm)
CA5000-125 1320 5000 150-1/4 3816 44 1118 54 1372 11-7/16 291 3100 1406 2" NPT (50.8mm)
CA7500-125 1980 7500 128-3/4 3270 62 1575 72 1829 11-1/2 292 3850 1746 3" NPT (76.2mm)
CA10000-125 2640 10000 158-1/4 4020 62 1575 72 1829 11-1/2 292 4500 2041 3" NPT (76.2mm)

System
Charging Valve Enclosure R Connection
(SEE TABLE)
Lifting Ring

1/2” NPT (12.7mm) 1/2” NPT (12.7mm)


(FACTORY USE ONLY) CA600 — 125 & Larger
(FACTORY USE ONLY)
NSF Non-NSF
H
Lifting Ring
NSF/ANSI 61-G [ P] Option,
Example: P/N PAX30-150P)
1/2” NPT (12.7mm) DRAIN
Models certified to NSF 61-G are
required to be installed on the cold (CA140 — 125 to CA2500 — 125)
water side of the hot water heater. 1-1/2” NPT (38.1mm) DRAIN
(CA3000 — 125 to CA10000 — 125)
See Related Documents:
402-002 Instruction Sheet
402-013 Instruction Sheet, Replacement Bag B DO NOT PIPE TO DRAIN
401-083 Submittal Data
401-083P Submittal Data, NSF D
-13-
Mechanical Specifications

Part 1 GENERAL C. Certificates: Inspection 1.6 DELIVERY, STORAGE,


1.1 SECTION INCLUDES
certificates for pressure AND HANDLING
vessels from authority
A. Expansion tanks having jurisdiction. A. Accept equipment on site in
shipping containers with
1.2 RELATED SECTIONS D. Manufacturer’s Installation labeling in place. Inspect
Instructions: Indicate hanging for damage.
A. Section - Hydronic Piping. and support methods, joining
procedures. B. Provide temporary end caps
1.3 REFERENCES and closures on piping and
E. Project Record Documents: fittings. Maintain in place
A. ASME (BPV VIII, 1) - Boiler Record actual locations of until installation.
and Pressure Vessel Code, flow controls.
Section VIII, Division 1 - Rules C. Protect piping components
for Construction of Pressure F. Maintenance Data: Include from entry of foreign materials
Vessels; The American Society installation instructions, by temporary covers, com
of Mechanical Engineers; 2006. assembly views, lubrication pleting sections of the work,
instructions, and replacement and isolating parts of
1.4 SUBMITTALS parts list. completed system.

A. See Section 01300 - 1.5 QUALITY ASSURANCE 1.7 MAINTENANCE SERVICE


Administrative Requirements,
for submittal procedures. A. Manufacturer Qualifications: A. Contractor to furnish service
Company specializing in and maintenance for one year
B. Product Data: manufacturing the type of from date of substantial
Provide product data for products specified in this completion.
manufactured products section, with minimum five
and assemblies required years of documented 1.8 EXTRA MATERIALS
for this project. Include experience.
component sizes, A. See Section 01400 - Project
rough-in requirements, Requirements, for additional
service sizes, and finishes. provisions.
Include product description,
model and dimensions.

-14-
Mechanical Specifications

Part 2 PRODUCTS
2.1 ASME Full Bladder D. Automatic Cold Water Fill Part 3 EXECUTION
TYPE EXPANSION Assembly (field installed 3.1 INSTALLATION
TANKS by others): Pressure
reducing valve, reduced A. Install specialties in
A. Manufactures: pressure double check back accordance with
1. Taco, Inc; Model CA ______: flow preventer, test cocks, manufacturer’s instructions.
www.taco-hvac.com strainer, vacuum breaker, and
valved by-pass. B. Where large air quantities can
2. ITT Bell & Gossett accumulate, provide enlarged
E. Size: air collection standpipes.
3. Amtrol Inc 1. HW Tank Capacity:
___________., C. Provide manual air vents at
4. Substitutions: _____________ system high points and as
See Section 01600 - acceptance volume. indicated.
Product Requirements.
2. CW Tank Capacity: D. For automatic air vents in
B. Construction: Welded steel, ___________., ceiling spaces or other
designed, tested and stamped _____________ concealed locations, provide
in accordance with ASME acceptance volume. vent tubing to nearest drain.
(BPV code sec VIII, div 1);
supplied with National Board F. Hot Water Heating System: E. Air separator and expansion
Form U-1, rated for working tank to be installed on the
pressure of 150 psi , with 1. Select expansion tank suction side of the system
flexible heavy duty butyl pressure relief valve at pumps. Expansion tank to
rubber bladder. Bladder shall _____ psi maximum. be tied into system piping
be able to accept the full in close proximity to air
volume of the expansion tank 2. Set pressure reducing separator and system fill line.
and shall be removable and valve at ____ psi.
replaceable. F. Provide valved drain and hose
G. Chilled Water System: connection on strainer blow
C. Accessories: Pressure gage down connection.
(field installed in adjacent 1. Select expansion tank
piping by others) and pressure relief valve at G. Provide relief valves on
air-charging fitting ; precharge _____ psi maximum. pressure tanks, low
to ____ psi. pressure side of reducing
2. Set pressure reducing valves, heat exchangers, and
valve at _____ psi. expansion tanks.

-15-
Mechanical Specifications

H. Select system relief valve K. Clean and flush glycol system N. Feed glycol solution to system
capacity so that it is greater before adding glycol solution. through make-up line with
than make-up pressure Refer to Section 15189. pressure regulator, venting
reducing valve capacity. system high points.
Select equipment relief L. Feed glycol solution to system
valve capacity to exceed through make-up line with O. Perform tests determin-
rating of connected pressure regulator, venting ing strength of glycol and
equipment. system high points. water solution and submit
written test results.
I. Pipe relief valve outlet to M. Feed glycol solution to system
nearest floor drain. through make-up line with
pressure regulator,
J. Where one line vents several venting system high points.
relief valves, make cross Set to fill at ___ psi.
sectional area equal to sum
of individual vent areas.

Taco quality
through & through
Hydronic professionals everywhere trust Taco for the highest
quality systems, components, technology, and support.
Visit taco-hvac.com for more information on CA Expansion
Tanks, additional products, systems, software & training.

Taco Inc., 1160 Cranston Street, Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360
Taco (Canada) Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8 / (905) 564-9422 / Fax (905) 564-9436
www.taco-hvac.com

You might also like