FIRE ALARM SYSTEM - CAUSE & EFFECT MATRIX

Activated Zone (or if the Mall is One Knock Activation)

Adjacent Zone Cause & Effect ( Yes or No)


Mall's Fire Alarm System Main Panel (Alarm or Fault)
Mall's Security Room (Flasher, Sounder or Both)
Mall's Area Energy Centre or Car Park Line Units Anchor Units (or Mini Major) Food & Beverage Units
Effects Plant Rooms

24/7 Civil Defense Auto Dailer

Alarm Sounder

Magnetic Door Holders (To Release)


Escalators & Travelators

Kitchen Hood Extract

Gas or LPG System


Cinema Projectors
Evacuation Msg.

Evacuation Msg.

Evacuation Msg.

Evacuation Msg.

Evacuation Msg.

Evacuation Msg.
LPG Main Valve
Smoke Curtains

Access Barriers
Alarm Sounder

Alarm Sounder

Alarm Sounder

Alarm Sounder

Alarm Sounder
Smoke Extract

Smoke Extract

Smoke Extract
Access Control

Access Control

Access Control

Access Control
Music System

Music System
Sliding Doors

Smoke Vents

Sliding doors

Suttor Doors
Sutter Doors
Alert Msg.

Alert Msg.

Alert Msg.

Alert Msg.

Alert Msg.

Alert Msg.
Elevators
FA Signal

FA Signal
Elevators

AHUs

AHU

AHU

AHU
Cause
Smoke / Heat Detector Activation D0 D0 D0 D5 D0 D0 D5 D5 D5 D5 D5 D5 NA D5 D5 D5 D5 D5 D0 D5 D5 D5 D5 NA NA NA NA D5 D0 D5 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D0 D5 D0 D5 D0 D5 - D5 D5

Second Smoke / Heat Detector D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA NA NA NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 - D0 D0


Activation

Manual Call Point (MCP) Activation D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA NA NA NA D0 D0 D0 D0 D5 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 - D0 D0


Mall's Security Room
Sprinkler Tamper Switch Activation FAULT
(closing)

Sprinkler Flow Switch Activation D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA NA NA NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 - D0 D0

FM200/CO2/Inergen Automatic Fire


Suppression Activation D0 D0 D0 D5 D0 D0 D5 D5 D5 D5 D5 D5 NA D5 D5 D5 D5 D5 D0 D5 D5 D5 D5 NA NA NA NA D5 D0 D5 D0 D5 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 D0 D5 D0 D5 D0 D5 - D5 D5

Smoke / Heat Detector Activation D0 D0 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 NA D5 D5 D5 D5 D5 D0 D5 D5 D5 D5 NA NA NA NA D5 D0 D5 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D0 D5 D5 D5 D0 D5 - D5 D5

Second Smoke / Heat Detector


D0 D0 D0 D0 D0 D5 D0 D0 D0 D0 D0 D0 NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA NA NA NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 - D0 D0
Activation

Manual Call Point (MCP) Activation D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA NA NA NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 - D0 D0

Sprinkler Tamper Switch Activation FAULT


(closing)

Mall's Area Sprinkler Flow Switch Activation D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA NA NA NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 - D0 D0

Fire Pump Running (Jockey, Electrical D0 D0 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 NA D5 D5 D5 D5 D5 D0 D5 D5 D5 D5 NA NA NA NA D5 D0 D5 D0 D5 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 D0 D5 D5 D5 D0 D5 - D5 D5


or Diesel)

Fire Pump Controller Fault (Jockey,


- D0 - - - - - - - - - - - - - - - - - - - - - NA NA NA NA - - - - - - - - - - - - - - - - - - - - - - - -
Electrical or Diesel)

FM200/CO2/Inergen Automatic Fire


Suppression Activation D0 D0 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 NA D5 D5 D5 D5 D5 D0 D5 D5 D5 D5 NA NA NA NA D5 D5 D5 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D0 D5 D0 D5 D0 D5 - D5 D5

Gas/LPG System Leak Activation D0 D0 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 NA D5 D5 D5 D5 D5 D0 D5 D5 D5 D5 NA NA NA NA D5 D5 D5 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D0 D5 D0 D5 D0 D5 - D5 D5

Smoke / Heat Detector Activation NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA

Second Smoke / Heat Detector


Activation NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA

Car Park Manual Call Point (MCP) Activation NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA

Sprinkler Tamper Switch Activation


(closing) NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA

Sprinkler Flow Switch Activation NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA

Smoke / Heat Detector Activation D0 D0 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 NA D5 D5 D5 D5 D5 D0 D5 D5 D5 D5 NA NA NA NA D5 D0 D5 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D0 D5 D5 D5 D0 D5 - D5 D5

Second Smoke / Heat Detector


D0 D0 D0 D0 D0 D5 D0 D0 D0 D0 D0 D0 NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA NA NA NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 - D0 D0
Activation

Energy Centre or Plant Manual Call Point (MCP) Activation D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA NA NA NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 - D0 D0


Rooms
Sprinkler Tamper Switch Activation
(closing) FAULT

Sprinkler Flow Switch Activation D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA NA NA NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 - D0 D0

Smoke / Heat Detector Activation D0 D0 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 NA D5 D5 D5 D5 D5 D0 D5 D5 D5 D5 NA NA NA NA D5 D0 D5 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D0 D5 D5 D5 D0 D5 - D5 D5

Manual Call Point (MCP) Activation D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA NA NA NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 - D0 D0


Line Units
Sprinkler Tamper Switch Activation
(closing) FAULT

Sprinkler Flow Switch Activation D0 D0 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 NA D5 D5 D5 D5 D5 D0 D5 D5 D5 D5 NA NA NA NA D5 D0 D5 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D0 D5 D5 D5 D0 D5 - D5 D5

Fire Alarm Control Panel (FACP)


D0 D0 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 NA D5 D5 D5 D5 D5 D0 D5 D5 D5 D5 NA NA NA NA D5 D0 D5 D0 NA NA NA NA NA NA NA NA NA NA NA D0 D5 D5 D5 D0 D5 - D5 D5
Activation

Sprinkler Tamper Switch Activation


Anchor Units (closing) - - - - - - - - - - - - - - - - - - - - - - - NA NA NA NA - - - - - - - - - - - - - - - - - - - - - - - -

Sprinkler Flow Switch Activation - - - - - - - - - - - - - - - - - - - - - - - NA NA NA NA - - - - - - - - - - - - - - - - - - - - - - - -

Smoke / Heat Detector Activation D0 D0 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 NA D5 D5 D5 D5 D5 D0 D5 D5 D5 D5 NA NA NA NA D5 D0 D5 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D0 D5 D5 D5 D0 D5 - D5 D5

Manual Call Point (MCP) Activation D0 D0 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 NA D5 D5 D5 D5 D5 D0 D5 D5 D5 D5 NA NA NA NA D5 D0 D5 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D0 D5 D5 D5 D0 D5 - D5 D5

Sprinkler Tamper Switch Activation


FAULT
(closing)
Food & Beverage Units
Sprinkler Flow Switch Activation D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 NA NA NA NA D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 D0 - D0 D0

Gas/LPG System Leak Activation D0 D0 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 NA D5 D5 D5 D5 D5 D0 D5 D5 D5 D5 NA NA NA NA D5 D0 D5 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D0 D5 D5 D5 D0 D5 - D5 D5

Kitchen Hood Fire Suppression system D0 D0 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 NA D5 D5 D5 D5 D5 D0 D5 D5 D5 D5 NA NA NA NA D5 D0 D5 D0 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D5 D0 D5 D5 D5 D0 D5 - D5 D5


Activation

Legend :
- No Action

NA Not Applicable

D0 Immediate Action (No Time Delay)

D(??) Delayed action by (??) minutes from Alarm Activation