ACB NA1

CHINT Group All Rights Reserved


Appearance and structure

Basic information

Installation & connection

Accessories

Function

Summary

CHINT Group All Rights Reserved


Appearance and structure
Secondary connecting part

Enclosure Making button

Fault-breaking
indicator reset button Energy storage &
release indicator
Breaking button

Name plate
Breaking/making indicator

Rotary handle

Structure for in and out

CHINT Group All Rights Reserved


Appearance and structure

 Inner structure

Under voltage release Shunt release

Closing
Locking device electromagnet

Auxiliary
contact
Intelligent controller
Motor-driven
energy storage
Operating mechanism
mechanism

CHINT Group All Rights Reserved


Appearance and structure

 Inner structure

CHINT Group All Rights Reserved


Appearance and structure

• Construction

CHINT Group All Rights Reserved


Appearance and structure

Basic information

Installation & connection

Accessories

Function

Summary

CHINT Group All Rights Reserved


Basic information

 Application

CHINT Group All Rights Reserved


Basic information

Overview
• Standards: IEC/EN 60947-2
• Rated current: 200-6300A
• Poles: 3P,4P
• Certificates:

CHINT Group All Rights Reserved


Basic information

Frame sizes

CHINT Group All Rights Reserved


Basic information

 Types: Fixed & Draw-out Type

CHINT Group All Rights Reserved


Basic information

 Types: Fixed & Draw-out Type

CHINT Group All Rights Reserved


Basic information

Position indication

CHINT Group All Rights Reserved


Basic information
 Position indication

CHINT Group All Rights Reserved


Basic information

 Operating

CHINT Group All Rights Reserved


Appearance and structure

Basic information

Installation & connection

Accessories

Function

Summary

CHINT Group All Rights Reserved


Installation & connection

Installation

CHINT Group All Rights Reserved


Installation & connection

 Installation
• Fixed type

CHINT Group All Rights Reserved


Installation & connection

• Draw out type

CHINT Group All Rights Reserved


Installation & connection

 Mounting

CHINT Group All Rights Reserved


Installation & connection
• Fixed type

CHINT Group All Rights Reserved


Installation & connection
• Draw out type

CHINT Group All Rights Reserved


Installation & connection

 Connection
• Power supply

NA1 device can be supplied either from the top or from the bottom without
reduction in performance.

CHINT Group All Rights Reserved


Installation & connection
• Three bus bar

Horizontal Rotation vertical

CHINT Group All Rights Reserved


Installation & connection

• The connection of bus bar

CHINT Group All Rights Reserved


Installation & connection

• Secondary connecting part

CHINT Group All Rights Reserved


Installation & connection

• Secondary circuit wiring

CHINT Group All Rights Reserved


Appearance and structure

Basic information

Installation & connection

Accessories

Feature

Function

CHINT Group All Rights Reserved


Accessories
 Accessories

11
7

12 8

13 9

10

14

15
3

5 2
16
6

CHINT Group All Rights Reserved


Accessories

• Shunt release
Shunt release can realize
the remote control to
break the circuit breaker

Note: Forbid making the power for long


time to avoid the shunt release being
damaged

CHINT Group All Rights Reserved


Accessories
• Under-voltage release

Action voltage (V) (0.35-0.7)Us

Reliable making voltage (V) (0.85-1.1)Us

Reliable non-making voltage (V) ≤0.35Us

Note: Without power supply, under-voltage release


can’t close. So close the circuit breaker before
operate the circuit breaker.

CHINT Group All Rights Reserved


Accessories

• Closing electromagnet

After the motor finishing


the energy storage,
closing release can
instantly close the circuit
breaker

Note: Forbid making the power for long


time to avoid the closing electromagnet
being damaged

CHINT Group All Rights Reserved


Accessories

• Motor-driven energy-storage mechanism

Ensure closing the


circuit breaker
instantly after breaking
the circuit breaker

Note: Operation frequency should no more


than 3 times per minute

CHINT Group All Rights Reserved


Accessories

• Auxiliary contact

6N/O(normal open)
and 6N/C(normal
close)

CHINT Group All Rights Reserved


Accessories

• Locking device
Key lock
Operation pushbutton lock

Lock the circuit breaker on Used for locking the


the OFF position, then the break pushbutton and
circuit breaker can’t be the close pushbutton
closed

CHINT Group All Rights Reserved


Accessories

• Off position locking mechanism

When the ACB is disconnected, padlock can be used to


lock it after pulling out the lock lever, then the ACB can’t
be “Test” or “connected” position

CHINT Group All Rights Reserved


Accessories

• Mechanical interlock

Cable mechanical interlock Connecting-rod type mechanical


interlock

CHINT Group All Rights Reserved


Accessories
Doorcase

Installed on the door of


the distribution cubicle,
make the protection
class to IP40.

Phase barrier Install between the


bus bars to
increase the
creepage distance

CHINT Group All Rights Reserved


Accessories

• Transparent shield

Installed on the doorcase of


the cubicle’s small door,
make the protection class to
IP54.

CHINT Group All Rights Reserved


Accessories

• Intelligent controller

•Main protection function


•Query function
•Parameter setting function
•Test function
•Load monitor function (optional)

•MCR and HSISC function (optional)

•Signal alarm function (optional)

CHINT Group All Rights Reserved


Accessories

• The setting of intelligent controller

CHINT Group All Rights Reserved


Appearance and structure

Basic information

Installation & connection

Accessories

Function

Summary

CHINT Group All Rights Reserved


Function

 Basic protection
• L. over-load long inverse time-delay protection
• S. short circuit inverse time-delay or definite time-delay
protection
• I. short circuit instantaneous protection
• G. earhing fault protection

CHINT Group All Rights Reserved


Function
• characteristic

CHINT Group All Rights Reserved


Function

• characteristic

Ir
Ig
Isd

Ii

Ir: action current of long time delay


Ig: action current of earthing
Isd: action current of short time delay fault or N phase
Ii: action current of instantaneous

CHINT Group All Rights Reserved


Function

• overload long time-delay protection

Current rating range


Error Current Time( s) Time Error
( Ir)

≤1.05Ir >2h non trip

>1.3Ir <1h trip


±10
(0.4-1) In
%
1.15Ir(setting
15,30,60,120,240,480 ±10%
time)

2.0Ir 8.4,16.9,33.7,67.5,135,270 ±10%

CHINT Group All Rights Reserved


Function

• Short-circuit short-delay protection

Current rating range


Error Current Time (s) Error
( Isd)

≤0.9Isd Non-trip

>1.1Isd delayed-trip
NA1-2000,(1.3125~15)Isd+OFF
NA1-3200,4000,(1.3125~15)Isd+OFF,Isd≤40KA ±10%
NA1-6300,(1.3125~15)Isd+OFF,Isd≤50KA Time setting (ts) 0.1,0.2,0.3,0.4 ±15%

Returnable time 0.06,0.14,0.23,0.35 ±15%

CHINT Group All Rights Reserved


Function

• Short circuit instantaneous protection

Rating range( Ii) Error Current Action characteristic

≤0.85Ii Non-trip
NA1-2000 1.3125In~50kA
NA1-3200,4000 1.3125In~65kA
±15%
NA1-6300 1.3125In~75kA

>1.15Ii Trip

Note : When the controller is of structure I (In=2000A), the instantaneous


protection setting is 1.0In~50KA+OFF; when the controller is of structure I
(In=3200A or 6300A), the instantaneous protection setting is 1.0In~
75KA+OFF;the special order can achieve 100KA+OFF

CHINT Group All Rights Reserved


Function
• Earthing fault protection

CHINT Group All Rights Reserved


Function

• Earthing fault protection

Rating range( Ig) Error Current Time (s) Time Error

≤0.8Ig >2h non trip

>1.0Ig <1h trip

In≤630A,(160~0.8)In+0FF
0.1,0.2,0.3,0.4
±10% Time setting (ts) ±15%
In>630A,(0.2~0.8)In+0FF

0.06,0.14,0.23,0.35
Returnable time ±15%

CHINT Group All Rights Reserved


Function

 Discrimination
• Discrimination is achieved by automatic protective
devices if a fault condition occurring at any point in the
installation. It is cleared by the protective device located
immediately upstream of the fault, while all other
protective devices remain unaffected

CHINT Group All Rights Reserved


Function

Discrimination

Object :
Uninterrupted
supply, but
highest safety,

CHINT Group All Rights Reserved


Function

 Discrimination

If fault current
≤Is=42kA
NA1-2000

A B C NA1-1000

CHINT Group All Rights Reserved


Function

 Discrimination

Other branches
still be powered

A B C

CHINT Group All Rights Reserved


Function
 Optional function
• Zone Selective Interlocking (ZSI)
•In traditional power
distribution system, it is
difficult to fulfill the selectivity
of the cooperation between
the upper side and down side
circuit breakers, and the
ZSI short-current produce strong
stress on system. As a new
protective method, Zone-
selective Interlocking (ZSI)
conquers these
disadvantages. Basing on
original protection system,
using and configuring ZSI
correctly can increase the
reliability of electrical system
effectively.

CHINT Group All Rights Reserved


Function

• Zone Selective Interlocking (ZSI)


A method which allows two or more breakers to communicate with
each other so that a short circuit or ground fault will be cleared by the
breaker closest to the fault in the minimum time.

 Here is an example:

CHINT Group All Rights Reserved


Function

If there is a fault in Zone 3, the


break A will interrupt the fault in
C 0.1 seconds, eliminating the
need for any of the upstream
circuit breakers to trip. And
B sends an zone interlock tripping
signal to the main circuit
breaker in the main switchboard,
If this breaker does not clear
the fault, then the upstream
A breakers B or C will trip
according to their specific time
delays.

CHINT Group All Rights Reserved


Function

the fault has occurred directly


upstream of the main circuit
breaker in the main
switchboard (between Zone 1
and Zone 2). In this case, only
this main
circuit breaker establishes
that a fault has occurred. No
blocking signals are received
from any
of the downstream circuit
breakers so this breaker trips
in 0.1 ms instead of the 0.4 ms
time
delay that it is set for.

CHINT Group All Rights Reserved


Function

• Load monitor

Mode 1
Control
load monitor can two
control the different loads
load of the circuit
Load breaker, so as to
monitor ensure the power
supply of the
important load. Mode 2 Control
one load

CHINT Group All Rights Reserved


Function

•Mode 1: control two loads

CHINT Group All Rights Reserved


Function

If In=2000A
Ie we set
Ic1=0.6In=1200A,
Ic2=0.4In=800A
B A
Ic2 Ic1

Main circuit Subsidiary circuit

CHINT Group All Rights Reserved


Function

Ie

B A
Ic2 Ic1

Main circuit Subsidiary circuit

When the current Ie reach to 960A (1.2Ic2)

CHINT Group All Rights Reserved


Function

Ie

B A
Ic2 Ic1

Main circuit Subsidiary circuit

If the current still rise up, when the current Ie reach to


1440A(1.2Ic1)

CHINT Group All Rights Reserved


Function
•Mode 2: control one load

CHINT Group All Rights Reserved


Function

If In=2000A
Ie we set
Ic1=0.8In=1600A,
Ic2=0.6In=1200A

Main circuit Subsidiary circuit

CHINT Group All Rights Reserved


Function

Ie

A Ic1

Main circuit Subsidiary circuit

When the current Ie reach to


1920A(1.2 Ic1)

CHINT Group All Rights Reserved


Function

Ie

A Ic2

Main circuit Subsidiary circuit

If the current go down to 0.6In,1200A, the A will


be closed automatically.

CHINT Group All Rights Reserved


Function
 Other function
• N-phase protection
• Ground fault trip
• Earth leakage trip
• Remote Communications Protocols
• Advanced L.C.D. display etc.

CHINT Group All Rights Reserved


Appearance and structure

Basic information

Installation & connection

Accessories

Function

Summary

CHINT Group All Rights Reserved


Summary

• Wide application
• Easy installation
• Compact design
• Full range of accessories
• Comprehensive function
• Intelligent
• Communication

CHINT Group All Rights Reserved