ACB NA1
Basic information
Accessories
Function
Summary
Fault-breaking
indicator reset button Energy storage &
release indicator
Breaking button
Name plate
Breaking/making indicator
Rotary handle
Inner structure
Closing
Locking device electromagnet
Auxiliary
contact
Intelligent controller
Motor-driven
energy storage
Operating mechanism
mechanism
Inner structure
• Construction
Basic information
Accessories
Function
Summary
Application
Overview
• Standards: IEC/EN 60947-2
• Rated current: 200-6300A
• Poles: 3P,4P
• Certificates:
Frame sizes
Position indication
Operating
Basic information
Accessories
Function
Summary
Installation
Installation
• Fixed type
Mounting
Connection
• Power supply
NA1 device can be supplied either from the top or from the bottom without
reduction in performance.
Basic information
Accessories
Feature
Function
11
7
12 8
13 9
10
14
15
3
5 2
16
6
• Shunt release
Shunt release can realize
the remote control to
break the circuit breaker
• Closing electromagnet
• Auxiliary contact
6N/O(normal open)
and 6N/C(normal
close)
• Locking device
Key lock
Operation pushbutton lock
• Mechanical interlock
• Transparent shield
• Intelligent controller
Basic information
Accessories
Function
Summary
Basic protection
• L. over-load long inverse time-delay protection
• S. short circuit inverse time-delay or definite time-delay
protection
• I. short circuit instantaneous protection
• G. earhing fault protection
• characteristic
Ir
Ig
Isd
Ii
≤0.9Isd Non-trip
>1.1Isd delayed-trip
NA1-2000,(1.3125~15)Isd+OFF
NA1-3200,4000,(1.3125~15)Isd+OFF,Isd≤40KA ±10%
NA1-6300,(1.3125~15)Isd+OFF,Isd≤50KA Time setting (ts) 0.1,0.2,0.3,0.4 ±15%
≤0.85Ii Non-trip
NA1-2000 1.3125In~50kA
NA1-3200,4000 1.3125In~65kA
±15%
NA1-6300 1.3125In~75kA
>1.15Ii Trip
In≤630A,(160~0.8)In+0FF
0.1,0.2,0.3,0.4
±10% Time setting (ts) ±15%
In>630A,(0.2~0.8)In+0FF
0.06,0.14,0.23,0.35
Returnable time ±15%
Discrimination
• Discrimination is achieved by automatic protective
devices if a fault condition occurring at any point in the
installation. It is cleared by the protective device located
immediately upstream of the fault, while all other
protective devices remain unaffected
Discrimination
Object :
Uninterrupted
supply, but
highest safety,
Discrimination
If fault current
≤Is=42kA
NA1-2000
A B C NA1-1000
Discrimination
Other branches
still be powered
A B C
Here is an example:
• Load monitor
Mode 1
Control
load monitor can two
control the different loads
load of the circuit
Load breaker, so as to
monitor ensure the power
supply of the
important load. Mode 2 Control
one load
If In=2000A
Ie we set
Ic1=0.6In=1200A,
Ic2=0.4In=800A
B A
Ic2 Ic1
Ie
B A
Ic2 Ic1
Ie
B A
Ic2 Ic1
If In=2000A
Ie we set
Ic1=0.8In=1600A,
Ic2=0.6In=1200A
Ie
A Ic1
Ie
A Ic2
Basic information
Accessories
Function
Summary
• Wide application
• Easy installation
• Compact design
• Full range of accessories
• Comprehensive function
• Intelligent
• Communication