You are on page 1of 5

INSTALLATIONS

& CONTRACTING

Why ground? Poor grounding not only contributes to unnecessary


downtime, but a lack of good grounding is also dangerous and increases the
risk of equipment failure.

Principles, testing methods and


applications: earth ground resistance
Without an effective grounding system, Information from Comtest
we could be exposed to the risk of electric
shock, not to mention instrumentation
errors, harmonic distortion issues, power
factor problems and a host of possible “a conducting connection, whether
intermittent dilemmas. If fault currents have intentional or accidental between an
no path to the ground through a properly electrical circuit or equipment and the
designed and maintained grounding earth, or to some conducting body that
system, they will find unintended paths serves in place of the earth.” When
that could include people. talking about grounding, it is actually
Good grounding isn't only for safety; two different subjects: earth grounding
it is also used to prevent damage to and equipment grounding. Earth
industrial plants and equipment. grounding is an intentional connection
from a circuit conductor, usually the
Why test grounding systems?
neutral, to a ground electrode placed
Over time, corrosive soils with high in the earth. Equipment grounding
moisture content, high salt content, ensures that operating equipment
and high temperatures can degrade within a structure is properly grounded.
ground rods and their connections. These two grounding systems are Fig. 1: Components of a ground electrode.
So although the ground system, when required to be kept separate except
initially installed, had low earth ground for a connection between the two Components of a ground
resistance values, the resistance of the systems. electrode
grounding system can increase if the
What is a good ground l Ground conductor
ground rods are eaten away.
resistance value? l Connection between the ground
That is why it is highly recommended conductor and the ground
that all grounds and ground connections Ideally a ground should be of zero ohms
resistance. There is not one standard electrode
are checked at least annually as a part
ground resistance threshold that is l Ground electrode
of your normal Predictive Maintenance
recognised by all agencies. However, Locations of resistances
plan. During these periodic checks, if
the NFPA and IEEE have recommended
an increase in resistance of more than
a ground resistance value of 5,0 ohms The ground electrode and its
20% is measured, the technician should connection
or less.
investigate the source of the problem,
and make the correction to lower the The telecommunications industry has The resistance of the ground electrode
resistance, by replacing or adding often used 5,0 ohms or less as their and its connection is generally very
value for grounding and bonding. low. Ground rods are generally made
ground rods to the ground system.
The goal in ground resistance is to of highly conductive/low resistance
What is a ground? material such as steel or copper.
achieve the lowest ground resistance
The NEC, National Electrical Code, value possible that makes sense The contact resistance of the
Article 100 defines a ground as: economically and physically. surrounding earth to the electrode

September 2009 - Vector - Page 66


Fig. 2: Each ground electrode has its own "sphere of influence".

The National Institute of Standards Generally, by doubling the length of


(a governmental agency within the the ground electrode you can reduce
US Dept. Of Commerce) has shown the resistance level by an additional
this resistance to be almost negligible 40%. There are occasions where it is
provided that the ground electrode is physically impossible to drive ground
free of paint, grease, etc. And that the rods deeper – areas that are composed
ground electrode is in firm contact with of rock, granite, etc. In these instances,
the earth. alternative methods including grounding
cement are viable.
The resistance of the surrounding body
of earth Diameter of the ground
electrode
The ground electrode is surrounded
by earth which conceptually is made Increasing the diameter of the ground
up of concentric shells all having the electrode has very little effect in lowering
same thickness. Those shells closest to the resistance. For example, you could
the ground electrode have the smallest double the diameter of a ground
amount of area resulting in the greatest electrode and your resistance would only
degree of resistance. Each subsequent decrease by 10%.
shell incorporates a greater area resulting
in lower resistance. This finally reaches Number of ground electrodes
a point where the additional shells offer Another way to lower ground resistance
little resistance to the ground surrounding is to use multiple ground electrodes. In Fig. 3: Ground systems.
the ground electrode. this design, more than one electrode is
So, based on this information, we should driven into the ground and connected l Fall-of-Potential (using stakes)
focus on ways to reduce the ground in parallel to lower the resistance. For l Selective (using 1 clamp and
resistance when installing grounding additional electrodes to be effective, stakes)
systems. the spacing of additional rods need to l Stakeless (using 2 clamps only)
be at least equal to the depth of the Soil resistivity measurement
What affects the grounding driven rod.
resistance? Why determine the soil
Ground system design resistivity?
First, the NEC code requires a minimum
ground electrode length of 2,5 m to be Simple grounding systems consist of a Soil resistivity is most necessary when
in contact with soil. But, there are four single ground electrode driven into the determining the design of the grounding
variables that affect the ground resistance ground. The use of a single ground system for new installations (green field
of a ground system: electrode is the most common form of applications) to meet your ground
grounding and can be found outside resistance requirements. Ideally, you
l Length/depth of the ground would find a location with the lowest
your home or place of business. Complex
electrode grounding systems consist of multiple possible resistance. It is recommended
l Diameter of the ground electrode ground rods, connected, mesh or grid that the ground rods be placed as deep
networks, ground plates, and ground as possible into the earth, at the water
l Number of ground electrodes
loops. These systems are typically installed table if possible.
l Ground system design
at power generating substations, central For a grounding system to be effective, it
Length/depth of the ground offices, and cell tower sites. should be designed to withstand the worst
electrode possible conditions.
There are four types of earth
One very effective way of lowering ground ground testing methods How do I calculate soil
resistance is to drive ground electrodes available: resistivity?
deeper. l Soil resistivity (using stakes) The measuring procedure described below

September 2009 - Vector - Page 67


Soil Earthing resistance Connect the ground tester as shown in
Type of soil
resistivity Ground electrode depth
Earthing strip (meters)
the picture. Press START and read out
RE (meters) the RE (resistance) value. This is the
ΩM 3 6 10 5 10 20 actual value of the ground electrode
Very moist soil,
swamplike
30 10 5 3 12 6 3 under test. If this ground electrode is
Farming soil loamy
in parallel or series with other ground
100 33 17 10 40 20 10 rods, the RE value is the total value of
and clay soils
Sandy clay soil 150 50 25 15 60 30 15 all resistances.
Moist sandy soil 300 66 33 20 80 40 20
How do you place the stakes?
Concrete 1:5 400 - - - 160 80 40
Moist gravel 500 160 80 48 200 100 50 To achieve the highest degree of
Dry sandy soil 1000 330 165 100 400 200 100 accuracy when performing a 3–pole
Dry gravel 1000 330 165 100 400 200 100 ground resistance test, it is essential that
Stoney soil 30 000 1000 500 300 1200 600 300 the probe is placed outside the sphere of
Rock 107 - - - - - - influence of the ground electrode under
test and the auxiliary earth.
Fig. 4: Changing soil types.
If you do not get outside the sphere
of influence, the effective areas of
resistance will overlap and invalidate
any measurements that you are taking.
The table is a guide for appropriately
setting the probe (inner stake) and
auxiliary ground (outer stake).
To test the accuracy of the results and to
ensure that the ground stakes are outside
the spheres of influence, reposition the
inner stake (probe) 1m in either direction
and take a fresh measurement. If there
is a significant change in the reading
(30%), you need to increase the distance
between the ground rod under test, the
inner stake (probe) and the outer stake
(auxiliary ground) until the measured
values remain fairly constant when
repositioning the inner stake (probe).
Selective measurement
Selective testing is very similar to the
Fall-of-Potential testing, providing
all the same measurements, but in
a much safer and easier way. This
is because with Selective testing, the
earth electrode of interest does not
Fig. 5: Earth electrode, inner stake, outer stake. need to be disconnected from its
connection to the site! The technician
does not have to endanger himself by
uses the universally accepted Wenner dissipate energy from a site.
disconnecting ground, nor endanger
method. First, the earth electrode of interest must other personnel or electrical equipment
The formula. be disconnected from its connection to inside a nongrounded structure.
ρ=2πAR the site.
Just as with the fall-of-potential test,
Where Second, the tester is connected to two earth stakes are placed in the soil
ρ = the average soil resistivity to depth the earth electrode. Then, for the in a direct line, away from the earth
A in ohm-cm 3-pole Fall-of-Potential test, two earth electrode. Normally, spacing of 20 m is
stakes are placed in the soil in a direct sufficient. The tester is then connected to
A = the distance between the electrodes
line – away from the earth electrode. the earth electrode of interest, with the
in cm
Normally, spacing of 20 m is sufficient. A advantage that the connection to the site
R = the measured resistance value in
known current is generated by the Fluke doesn't need to be disconnected.
ohms from the test instrument
1625 between the outer stake (auxiliary Instead, a special clamp is placed around
Note: Divide ohm-cm by 100 to convert earth stake) and the earth electrode,
to ohm-m. Just watch your units! the earth electrode, which eliminates
while the drop in voltage potential is
the effects of parallel resistances in a
Fall-of-potential measurement measured between the inner-earth stake
grounded system, so only the earth
and the earth electrode. Using Ohm's
The fall-of-potential test method is used Law (V = IR), the tester automatically electrode of interest is measured.
to measure the ability of an earth ground calculates the resistance of the earth Just as before, a known current is
system or an individual electrode to electrode. generated by the Fluke 1625 between

September 2009 - Vector - Page 68


Depth of Distance to the Distance to
the ground inner stake the outer
electrode stake
2m 15 m 25 m
3m 20 m 30 m
6m 25 m 40 m
10 m 30 m 50 m

Fig. 6: Placing of stakes.

the outer stake (auxiliary earth stake) any single path (the one under test).
and the earth electrode, while the So, the net resistance of all the parallel
drop in voltage potential is measured return path resistances is effectively zero.
between the inner earth stake and Stakeless measurement only measures
the earth electrode. Only the current individual ground rod resistances in
flowing through the earth electrode of parallel to earth grounding systems.
interest is measured using the clamp. If the ground system is not parallel to
The generated current will also flow earth then you will either have an open
through other parallel resistances, but circuit, or be measuring ground loop
only the current through the clamp (i.e. resistance. Fig. 7: Equivalent circuit for two–point
the current through the earth electrode measurement.
of interest) is used to calculate resistance Ground impedance
(V=IR). measurements l Water pipe, and
If the total resistance of the ground When attempting to calculate possible l Structural or building steel
system should be measured, then each short circuit currents in power plants and First, perform the Stakeless test on all
earth electrode resistance must be other high voltage/current situations, the individual grounds coming off of the
measured by placing the clamp around determining the complex grounding MGB. The purpose is to ensure that all
each individual earth electrode. impedance is important since the the grounds are connected, especially
Then the total resistance of the impedance will be made up of inductive the MGN. It is important to note that
ground system can be determined by and capacitive elements. Because you are not measuring the individual
calculation. inductivity and resistivity are known resistance, rather the loop resistance of
Stakeless measurement in most cases, actual impedance what you are clamped around. Connect
can be determined using a complex the Fluke 1625 or 1623 and both the
The Fluke 1625 earth ground tester computation. inducing and sensing clamps, which
is able to measure earth ground loop
Since impedance is frequency are placed around each connection
resistances for multigrounded systems dependent, the Fluke 1625 uses a to measure the loop resistance of the
using only current clamps. This test 55 Hz signal for this calculation to be MGN, the ground field, the water pipe,
technique eliminates the dangerous, and as close to voltage operating frequency and the building steel.
time consuming activity of disconnecting as possible. This ensures that the
parallel grounds, as well as the process Second, perform the 3-pole fall-of-
measurement is close to the value at potential test of the entire ground system,
of finding suitable locations for auxiliary the true operating frequency. Using this
ground stakes. You can also perform connecting to the MGB. To get to remote
feature of the Fluke 1625, accurate
earth ground tests in places you have earth, many phone companies utilise
direct measurement of grounding
not considered before: inside buildings, impedance is possible. unused cable pairs going out as much
on power pylons or anywhere you don't as a mile. Record the measurement and
Power utilities technicians, testing high repeat this test at least annually.
have access to soil. voltage transmission lines, are interested
With this test method, two clamps are in two things. The ground resistance Third, measure the individual resistances
placed around the earth ground rod in case of a lightning strike, and the of the ground system using the Selective
or the connecting cable and each are impedance of the entire system in case test of the Fluke 1625 or 1623. Connect
connected to the tester. of a short circuit on a specific point in the Fluke tester.
Earth ground stakes are not used at the line. Short circuit in this case, means Measure the resistance of the MGN; the
all. A known voltage is induced by one an active wire breaks loose and touches value is the resistance of that particular
clamp, and the current is measured the metal grid of a tower. leg of the MGB. Then measure the
using the second clamp. At central offices ground field. This reading is the actual
resistance value of the central office
The tester automatically determines the When conducting a grounding audit of ground field. Now move on to the water
ground loop resistance at this ground a central office there are three different pipe, and then repeat for the resistance
rod. If there is only one path to ground, measurements required. of the building steel.
like at many residential situations, Before testing, locate the MGB (Master You can easily verify the accuracy of
the Stakeless method will not provide Ground Bar) within the central office to these measurements through Ohm's
an acceptable value and the Fall-of- determine the type of grounding system Law. The resistance of the individual
Potential test method must be used. that exists. The MGB will have ground legs, when calculated, should equal
The Fluke 1625 works on the principle leads connecting to the: the resistance of the entire system
that in parallel/multi-grounded systems, l MGN (Multi-Grounded Neutral) or given (allow for reasonable error
the net resistance of all ground paths incoming service, since all ground elements may not be
will be extremely low as compared to l Ground field, measured).

September 2009 - Vector - Page 70


The cell site building is grounded
at all four corners connected to the
MGB via a copper cable and the
four corners are also interconnected
via copper wire.
There is also a connection between
the building ground ring and the tower
ground ring.
Electrical substations
A substation is a subsidiary station
Fig. 8: A typical setup at an electrical on a transmission and distribution
substation. system where voltage is normally
transformed from a high value to
low value. A typical substation will
contain line termination structures,
high-voltage switchgear, one or more
power transformers, low-voltage
switchgear, surge protection, controls,
and metering.
Remote switching sites
Remote switching sites also
known as slick sites, where digital
line concentrators and other
telecommunications equipment is
Fig. 9: Using stakeless testing at a remote operating.
switching site.
The remote site is typically grounded at
either end of the cabinet and then will
have a series of ground stakes around
the cabinet connected by copper wire.
For all applications, this is not a true
ground resistance measurement
because of the network ground. This
is mainly a continuity test to verify that
the site is grounded, that we have an
electrical connection, and that the
system can pass current.
3-Pole fall-of-potential
Fig.10: Using selective testing on a measurement
lightning protection system.
Second, we measure the resistance of
the entire system via the 3-Pole fall-of-
These test methods provide the most potential method.
accurate measure of a central office,
because it gives you the individual Selective measurement
resistances and their actual behavior in Lastly, we measure the individual grounds
a ground system. Although accurate, the with the Selective test. This will verify the
measurements would not show how the integrity of the individual grounds, their
system behaves as a network, because connections, and determine whether
in the event of a lightning strike or fault the grounding potential is fairly uniform
current, everything is connected. throughout. If any of the measurements
Application sites show a greater degree of variability than
the other ones, the reason for this should
There are four other particular be determined. The resistances should be
applications where you can use the measured on:
Fluke 1625 to measure the capability l Each leg of the tower and all four
of the earth ground system. corners of the building (cell sites/
Cellular sites/microwave and radio towers)
towers l Individual ground rods and their
At most locations there is a four- connections (electrical substations)
legged tower with each leg individually l Both ends of the remote site (remote
grounded. These grounds are then switching)
connected with a copper cable.
l All four corners of the building
Next to the tower is the cell site
(lightning protection)
building, housing all the transmission
equipment. Inside the building there Contact Val Verwer, Comtest,
is a halo ground and a MGB, with the Tel 011 254-2200,
halo ground connected to the MGB. info@comtest.co.za

September 2009 - Vector - Page 71

You might also like