Volume 87 – Issue 8/2007 ∙ Page 64 to 72

RDS-PP – Transition from the KKS


to an international standard
Up-dated version of an article from
VGB PowerTech 8/2007 concerning RDS-PP

By Dipl.-Ing. Harry Königstein,


Ing. (grad.) Heinz Müller and Dipl.-Ing. Jörg Kaiser
The RDS-PP

RDS-PP – Transition from the KKS


to an international standard
Up-dated version of an article from VGB PowerTech 8/2007 concerning RDS-PP

Abstract and technical product documentation – Part


New and withdrawn standards and the revised General 10: Power plants”. This standard has been
EU Directives relating to reference designa- published as an international standard ISO/
tion and plant documentation also have a sig- TS 16952-10 “Technical product documenta-
nificant impact also on the KKS power plants The KKS Identification System for Power
reference designation system run by VGB
tion – Reference designation system – Part 10:
Plants has been successfully used worldwide
PowerTech. Power plants” in 2008.
since the early nineteen seventies for the des-
To gain acceptance on the international mar-
kets, to ensure compliance with valid stand-
ignation of plants, technical equipment and The KKS successor system is named: Refer-
ards in conjunction with conformity declara- components in power plants. ence Designation System for Power Plants –
tions and to satisfy safety provisions in plants, RDS-PP.
both manufacturers and operators needed to The issuing of international basic standards on
adopt the KKS to current rules and regulations. reference designation in the year 1996 and the
The work was carried out in the VGB “Refer- quoting of such standards in European direc- History
ence Designation and Plant Documentation” tives and harmonized standards called for an
Working Panel and resulted in a technical
adjustment of the KKS to such specifications. In March 1969, three manufacturing compa-
standard for reference designation in power
plants and a key for power plant systems - nies published in the technical journal “Elek­
The main motivation for this was for the
the “system key”. Experience and known po- trizitätswirtschaft”, an article entitled “System
tentials for improvement in the use of KKS
manufacturers to assert themselves in the
zur Kennzeichnung von Geräten und Anlagen
complete the adoption and creation of the European and worldwide markets by ensur-
in Wärmekraftwerken” (System for the desig-
KKS replacement system. The new standard- ing conformity with the standards and for the
ized reference designation system is called nation of components and plant equipment in
power plant operators to avail themselves of a
“Reference Designation System for Power thermal power plants). The designation system
standardized equipment designation basis for
Plants RDS-PP”. referred to in this article was designed for the
The technical standard is based on the ba- their work.
needs of planning, constructing and operat-
sic principles of international standards and
The basic principles necessary for such ad- ing mechanical and electrical systems and
takes into account nearly all the KKS struc-
tures. Around 90% of the code letters in the justment and certain amendments of the KKS was used by the name of “Anlagenkennzeich-
KKS function key were transferred to the new were developed in the VGB Technical Com- nungssystem” (Plant Designation System), in
system key. KKS aggregate and equipment mittee “Reference Designation and Plant short “AKS” or “AKZ System”. The system
key will be replaced in the new reference Documentation” jointly by manufacturers used various code letters from other stand-
designation system by a standard in which
the code letters are standardised globally for and operators and contributed to the national ards, e.g. the “device identifier” for electrical
specialist fields and sectors. These code let- and international standardizing activities. The components from DIN 40719, supplementary
ters do not unfortunately always match the main objective was to arrive at a sector-spe- sheet 1.
KKS-specifications. cific standard for power plants. The result is
There are tools available for comparing RDS- In the early nineteen seventies, the experience
now available:
PP to KKS and for performing the required gained in the application of the AKZ System
conversion from KKS to RDS-PP. These tools In April 2007, the Joint Committee for Refer- resulted in the further development of the sys-
support the transfer of the KKS function key
to the RDS-PP system key and from the ag-
ence Designation Systems (GAKS) at the DIN tem by the VGB Working Panel “Technical
gregate and equipment key to the code letters published the national standard DIN 6779-10 Classification Systems”, in which operators,
in the international standard. “Structuring principles for technical products experts, authorities and manufacturers were
The article depicts the development of the
new reference designation system from the
point of view of standardisation, describes Electrical DIN EN DIN EN
IEC / ISO
engineering IEC 750 IEC 61346
the main features, mentions offers of support international 81346

by the VGB “Reference designation and plant


documentation” working panel and provides All disciplines
international
recommendations for future use. ISO/TS
16952-1

RDS-PP
ISO/TS
16952-10

Authors All disciplines DIN


international 6779-1
Dipl.-Ing. Harry Königstein
STEAG Power Saar GmbH, Power plant
Saarbrücken/Germany engineering RDS-PP
DIN
international
Electrical DIN 6779-10
Ing. (grad.) Heinz Müller engineering
national
40917-2
19227
Siemens Power Generation,
Erlangen/Germany
Power plant AKS KKS
engineering VGB-B 105e
Dipl.-Ing. Jörg Kaiser national
VGB PowerTech, Essen/Germany
Figure 1. Development of the sector-specific standard for power plants.

VGB PowerTech 8/2007 1


Fig. 1 – Development of the sector-specific standard for power plants

The publication of IEC 61346-2 and DIN EN 61346-2 for the classification of technical objects
The RDS-PP

–– operational safety,
Basic DIN EN 81346 / IEC 81346 DIN ISO/TS 16952-1 –– ergonomics,
standards Industrial systems, installations and equipment and ISO/TS 16952-1
industrial products Technical product –– procurement, and
ducumentation –– declaration of conformity.
DIN EN 81346-1 DIN EN 81346-2 Reference designation
IEC 81346-1 IEC 81346-2 system
Application rules
The RDS-PP is in full agreement with the na-
Structuring principles and Classification of objects
reference designations and codes for classes tional/international sector-specific standards
Basic rules for power plants ISO/TS 16952-10 and DIN
ISO/TS 16952-10 and thus complies with the
Sector specific DIN ISO/TS 16952-10 / ISO/TS 16952-10 mentioned international standard for reference
standard Reference designation system Part 10: Power plants
designation systems.
Guidelines VGB-B 101 The RDS-PP can thus be considered to be a
RDS-PP Letter codes for Power Plant Systems
VGB-B 102 standard-conforming designation system.
RDS-PP Letter Codes for Basic Function and Product Classes in Power Plants

Codes of practice
Application VGB-B 116 Explanations VGB-B 116 Guidelines
explanations Part A general Part D power plant type specific
Application Part B engineering discipline specific - D1 Hydro power plants
guidlines - B1 Mechanical engineering - D2 Wind power plants The Reference Designation System for Pow-
- B2 Civil engeneering
- B3 Electrical- and control engineering
er Plants RDS-PP consists of the following
- B4 Process control standards, guidelines and application expla-
nations:
–– Sector-specific standards DIN ISO/TS
RDS-PP
16952 and ISO TS 16952-10,
Figure 2. Interrelation of designation standards, guidelines and application explanations. –– Guideline VGB-B 101e and VGB- B 102 for
power plant Letter Codes (Systems and/or
equally represented. standard under the number ISO TS 16952-10 pasic functions and product classes)
The result, the “KKS Identification System and DIN ISO/TS 16952-10. IEC and ISO have
–– Discipline-specific and power plant-specif-
for Power Stations” was published by VGB agreed to publish the various standards relat-
ic application explanations and guidelines.
as Guideline VGB-B 105e. The guideline ing to reference designation resulting from the
was complemented by so-called “Key Parts” ongoing revision work under a common series F i g u r e 2 depicts the relation between the
(function, equipment unit and component of standards with the number 81346. basic standards and application guidelines
keys) and “Application Explanations”. Apart
from electrical components, also equipment
items of mechanical systems could be iden- Characteristic features Sector-specific standard
tified according to the KKS specifications.
Furthermore, the KKS was used as a basis for The Reference Designation System for Power The sector-specific standard ISO TS 16952-
the designation of signals, connections and Plants – in short RDS-PP – results from the 10 is based on the general basic standards (see
documents (F i g u r e 1 ). consistent further development of the suc- Fig. 2) and contains sector-specific specifica-
The publication of IEC 61346-2 and DIN EN cessful KKS Identification System for Power tions and rules relating to designation tasks,
61346-2 for the classification of technical ob- Plants. It has thus the characteristic features of code structure and code representation as well
jects across all technical disciplines and the a proven identification system: as examples of use. The appendix (informa-
associated withdrawal of DIN 40719-2 in the –– applicability to all power plant types, tive) offers a check list for the definitions
year 2000 resulted in a situation where KKS between the project-taken part as well as ap-
–– consistency throughout the entire life cycle,
code letters were used which were not covered plication examples.
by a valid standard. International specifica- –– identity in sense for all technical disciplines,
tions and requirements were thus no longer –– language independence. The sector-specific standard is comparable
reflected in the KKS. with VGB guidelines VGB-B 105e for the
The RDS-PP expands the KKS by the desig- KKS.
This was an urgent reason to revise the KKS nation blocks
and adjust it to the new requirements result- Hereinafter, the main focuses of the sector-
–– „Conjoint designation“ for the designation
ing from the international codes. Taking into specific standard are described, pointing out
of plant sites and plant complexes, and
account DIN 6779-1, members of the VGB differences from the KKS.
Working Panel “Reference Designation and –– „Functional allocation“ for the designation
Plant Documentation” (successor panel of the of dynamic processes. The general code structure consists of a maxi-
Technical Committee “Technical Classifica- mum of three parts that can be combined ac-
The RDS-PP is based on structuring princi- cording to defined rules (F i g u r e 3 ):
tion Systems”) were instrumental in devel- ples, designation rules and letter codes, speci-
oping the sector-specific standard for power fied in international standards published by The sector-specific standard fully satisfies
plants DIN 6779-10 entitled “ Structuring IEC and ISO and fulfils the prerequisites for the basic principles of structuring which can
principles for technical products and techni- be done under various aspects. The power
–– finding worldwide acceptance, and
cal product documentation – Part 10: Power plant is broken down according to the aspects
plants”. –– application of the same, standardized code
“Function”, “Product” and “Location”. The
letters.
This national standard was submitted as a Function aspect views an object by its func-
proposal to the ISO and accepted. It has been The RDS fulfils the requirements of European tionality, the Product aspect by its physical
published in the meantime as an international Directives in terms of composition. The Location aspect describes

2 VGB PowerTech 8/2007


The RDS-PP

which locations are made available by the the specific application case, the coding let- D e s i g n a t i o n bl o c k
same object for other objects. For each view/ ters have to be agreed between the parties in- „Functional allocation“
aspect, a tree structure can be developed in volved in the project. The letters used in the
This designation block is used for function-
which the rules of partitive relation prevail Figure 5 were chosen arbitrarily.
oriented designation under the aspect of in-
(“consists of ”/”is part of ”), the relations be-
teraction of technical objects. It differentiates
tween the trees are so-called role relations
between group level and individual level.
(dashed lines in Figure 3).
The designation for various aspects or tasks is Identifier
done in designation blocks with a fixed struc-
ture. The general structure consists of a prefix Conjoint designation Reference designation Specific designation
followed by a designation code consisting of - Site under for
- Factory complex - Function aspect - Signals
letters and numbers. Letters are used for the - Power plant unit - Product aspect - Terminals
classification of technical objects, using letter - Subsystems based on - Location aspect - Documents
project-specific requirements
codes VGB-B 101e and VGB-B 102, respec-
tively; numbers are used to distinguish between
objects designated by the same letter code.
Ta b l e 1 shows the prefixes and their mean-
ings.
Hereinafter, the designation blocks according Function-oriented structure Product-oriented structure Location-oriented structure
to RDS-PP are described. Building
D e s i g n a t i o n bl o c k
Transport Cabinet Floor
„Conjoint designation“
Convey
This designation block can be used for identi- Supply Breaker Room
fying sites, plants, power plant units and has to Protect Switching Contact
be agreed between the parties involved in the
project. It represents none of the three basic is implemented by... is installed in...
aspects.
performs function contains products...
F i g u r e 4 shows several sites, hydroelectric
power plants and control stations in the upper
Danube area. Figure 3. Maximum scope of the designation system, taken aspects, structure and relations
into account.
Designation Block „Function“
This designation block is used for function-
B
oriented designation, from the view of task #D1.KB LWKW
Danube
and purpose of the technical object. It corre- A A
#D1.KA LWKW LWKW #D2.KA
sponds to the breakdown levels 1 and 2 of the
KKS process-oriented identification code, but B
110 kV #D2.VA LWKW #D2.KB
without the prefix number of the system code #D1.PA PSKW
Schl. A C
and the additional equipment unit code. LS #D2.SA LWKW #D2.KC
#D1.KY LS
A novelty compared to the KKS is the change #D2.KY
of breakdown level 0. If necessary, several
systems can be combined here. LS LWKW Run-of-river power plant
#D0.KY LS Pumped storage power plant
F i g u r e 5 illustrates this option, using the PSKW Control station
Schl. Sluice
example of a gas and steam turbine combined 110 kV 110 kV outdoor switch plant
cycle plant.
Figure 4. Example for the “Conjoint designation”.
It is not possible to define universally valid
letter coding for the breakdown level 0. For Table 1. Prefixes for designation tasks.

Steam module = S1 Prefix Prefix origin, basic


Designation Designation tasks / aspects
- Water/steam system
1 2 principles specified in:
- Steam turbine
- Generator
# Number Conjoint designation IEC 81346-1
Gas module = G1 Gas module = G2
- Compressor - Compressor
- Combustion - Combustion
= Equals Function-oriented designation IEC 81346-1
Chamber chamber
- Gas turbine - Gas turbine = = Equals- Equals Functional allocation ISO/TS 16952-1
- Generator - Generator
- Heat recovery - Heat recovery
steam generator steam generator
+ Plus Point of installation designation IEC 81346-1
Workshop = X0
Power transmission = V0 - Mechanical workshop + + Plus-Plus Location designation ISO/TS 16952-1
- Electrical workshop
- 110 kV switchgear
- Main transformer – Minus Product-oriented designation IEC 81346-1
- 400 kV switchgear
: Colon Terminal designation IEC 61666

Figure 5. E  xample for breakdown level 0 in ; Semicolon Signal designation IEC 61175
the designation
Fig. 6 – Example for breakdown levelblock „Function“
0 in the designation for
block "Function"
& Ampersand Document designation IEC 61355
a CCCP.

VGB PowerTech
Designation block "F u n c t i 8/2007 3
o n a l a l l o c a t i o n"
This designation block is used for function-oriented designation under the aspect of
interaction of technical objects. It differentiates between group level and individual level.
This designation block is new. It governs the uniform designation of processes and the
allocation of control tasks, which used to be done differently in the KKS.
The RDS-PP

Supply process Demineralised water


e.g. demineralised water storage

Function aspect Product aspect


Main process ==P2 ==P4
Level 0 Level 1 Level 2 Level 1 Level 2
=Generation
AN(N)of AAANN
RecoveryAANNN
of - AA(N)NN AA(N)NN
Prefixstream of
Main System/energy and
Technical Prefix device/
energy carrying energy carrying Component
system
medium
subsystem
medium equipment assembly
= C01 MDY10 QA001 - QA07
Flue gas Feed
==P1 Designation
water block "Function"
==P3 Designation block "Product"

Energie Transfer of Equipment


Conversion of designation
Conversion of
Fuel release by thermal energy =C01 MDY10 steam into –QA07 mechanical Electrical
Input Example: QA001 energy
Air burning by heat mechanical
Wind power plant C01 (series C,energy
No. 1)into
exchange energy electrical energy
Electrical control and protection system MDY10, power unit QA001,
circuit breaker QA07
Live Steam

Disposal processes
Flue gas e.g. flue gas treatment

Figure 6. Example of “Functional allocation”.

This designation block is new. It governs the


uniform designation of processes and the allo- Designation Designation by inventory number, model designation
cation of control tasks, which used to be done according to RDS-PP etc. N O T according to RDS-PP
differently in the KKS. Equipment Particular Type of
(Position in the plant) equipment equipment
The basic flow diagram in F i g u r e 6 shows
the process of a thermal power plant, identify-
= C01 MDY10 QA001 INV_4712002 TYPE_3RT1026
ing the uppermost structural levels, the func-
–QA07
tional areas. Alternatively without inventory
D e s i g n a t i o n bl o c k „ P r o d u c t “
This designation block is used for product-ori- Legend:
Circuit breaker 7 in the power unit of the wind turbine
ented designation of electrical and mechanical generator control system
objects. Together with the designation block is c u r r e n t l y implemented by INV_4712002 of
“Function” forms the unambiguous compo- TYPE_3RT1026.
nent designation code.
D e s i g n a t i o n bl o c k „ E q u i p m e n t “ +C01 BFA02 This part is c u r r e n t l y installed in section 2 of the
AC distribution board BFA
This designation block is used for unambigu-
ous identification of technical objects (see Figure 7. Example for use of the equipment designation in a maintenance tool.
Table 2). It makes use of the possibility to Fig. 9 – Example for use of the equipment designation in a maintenance tool
consider objects following in succession ac-
cording to different aspects and allocate dif-
ferent prefixes to them. For power plants, the Table 2. Designation block “equipment”, with an example.
Page 11/26
transition from function to product aspect is
used.
Function aspect Product aspect
This designation block corresponds to the
“process-oriented identification” used in the Level 0 Level 1 Level 2 Level 1 Level 2
KKS. = AN(N) AAANN AANNN - AA(N)NN AA(N)NN
Among other things, the component code is Prefix Main System/ Technical Prefix device/
Component
system subsystem equipment assembly
used as an identifier for plant data manage-
= C01 MDY10 QA001 - QA07
ment systems and can be related to equipment
items and/or product types and their data. Designation block "Function" Designation block "Product"
F i g u r e 7 shows the basic principle.
Equipment designation
D e s i g n a t i o n bl o c k
„ Po i n t o f i n s t a l l a t i o n “ Example: = C01 MDY10 QA001 –QA07
Wind power plant C01 (series C, No. 1)
This designation block is used for designating Electrical control and protection system MDY10, power unit QA001,
the points of installation of technical objects. circuit breaker QA07
In addition to the hitherto existing possibil-

4 VGB PowerTech 8/2007


The RDS-PP

ity to identify electrical and I&C installation Table 3. Allocation of code letter sections to codes of practice.
units, designation masks were created for the
location-oriented designation of mechanical
equipment. This permits, for instance, accu- Designation block Function Product
rately locating the sampling point for a meas-
Breakdown level 0 1 2 1
ured value on a pump set by using the compo-
nent code under the location aspect. Section 0 1 2 3 4 1 2
Data digit/type = AN(N) AAA NN AA NNN - AA (N)NN
D e s i g n a t i o n bl o c k „ L o c a t i o n “
This designation block is used for designating Designation of systems
locations, such as structures, areas etc. according to VGB-B 101e

Signal designation Classification of technical equipment and product classes


according to VGB-B 102e
The unambiguous designation of signals is
achieved by combining the reference designa-
tions and the signal name according to the fol-
lowing structure: code letters are fully in accordance with IEC letter code for power plant systems. Due to
61355-1/DIN EN 61355-1. the reference contained in the sector-specific
Reference designation ; Signal name standard ISO/TS 16952-10, this guideline gets
The power plant specific document kind clas-
normative significance.
For power plants, the general provisions in sification codes are collected in the VGB
Guideline VGB-B 103. The guideline VGB-B 101e is based on the
IEC 61175/DIN EN 61175 were specified for
basic standard IEC 81346-2/DIN EN 81346-
the signal name. Structure and code letters Guideline and standard for letter codes 2 (Ta b l e 3 ) and provides a framework for a
of the signal name were transferred from the
The sector-specific standard allocates tables classification model for so-called infrastructure
KKS to the standard without any change.
from two different codes of practice (VGB objects. In this table, the letters A, V to Z are
Prefix Signal name Guidelines) to alpha digits of the individual generally specified, whereas the letter range
designation blocks. from B to U is available for sector-specific
; AA (N)NN
specifications.
Guideline VGB-B 101e „Letter code for
Ranges of numbers were defined for the signal power plant systems (system key)“ This free range from B to U was used to incor-
sections (2nd letter of the signal name) “B = porate - almost without changes – the function
For breakdown level 1 of the designation
single control”, “G = binary process signals” block “Function” Guideline VGB-B 101e, key of the KKS. Systems of new technologies
and “H = limit signals”, e.g. XB01 for check- “Letter code for power plant systems (system like CO2 separation, air separation system,
back signal ON/OPEN, XB02 for check-back key)” is applicable. The system replaces the fermentation, central solar energy utilization
signal OFF/CLOSED. KKS function key. etc., have been implemented.
Te r m i n a l d e s i g n a t i o n Guideline VGB-B 101e was developed by the The system key uses a three-digit letter code
The unambiguous designation of terminals on VGB Working Panel “Reference Designation and defines the limits for certain systems.
electrical or mechanical equipments is accom- and Plant Documentation” and is the binding With regards to the designations, some ad-
plished by combining reference designations
and terminal designations according to the
Table 4. Excerpt from the “VGB System Key” VGB-B 101e.
following structure:

Reference
Terminal designation
designation
150
B101e : 2010-04
For power plants, IEC 61666/DIN EN 61666
are applicable without any reservations.
4.14.2 Data characters 1 (S 1 ), 2 (S 2 ) and 3 (S 3 )
Document designation
a M Systems for transformation in and transmission of electrical energy
Non-manufacturer-specific, object-related
MA Steam turbine system
designation of documents is achieved by com-
MAA High pressure turbine
bining the object designation with the docu- Limits: from incl. steam admission (main stop valve) or combined main stop
ment type class key according to the following and control valve
to incl. extraction nozzles, tapping nozzles and exhaust nozzles
structure: and
to incl. inlet/outlet other turbine-internal systems
Document kind
Object MAB Intermediate pressure turbine
classification Sheet
desig- & / Limits: from incl. crossover line, incl. actuator or
code, nummer from incl. intercept valve
nation
counting number to incl. extraction nozzles, tapping nozzles and exhaust nozzles
and
As object designation, primarily the reference to incl. inlet/outlet other turbine-internal systems
designation should be used, but other classi- MAC Low pressure turbine
Limits: from incl. crossover line, incl. actuator or
fication systems may also be used depending from incl. intercept valve or steam inlet nozzles (in reheat system
on the application case, e.g. type designation without intercept valve)
to incl. extraction nozzles, tapping nozzles and exhaust nozzles
for the dimension drawing of a series product. and
to incl. inlet/outlet other turbine-internal systems
The structure of the document kind classifica-
MAD Bearing
tion code DCC with counting number and the
MAE - reserved for later standardization -
MAF - reserved for later standardization -
VGB PowerTech 8/2007 5
MAG Condensing system
Limits: from incl. condenser neck or inlet nozzle
to incl. condenser outlet nozzle, incl. connected flash tanks, incl.
instrumentation equipment associated with condenser
MAH Motive water system incl. pump equipment and water tank
The RDS-PP

Table 5. Examples according to VGB-B 102. Comparison of structure and content between
KKS and RDS-PP
KKS (Equipment unit key) RDS/PP (VGB-B 102)
AA Valves, dampers etc. Can become FL safety valve Based on the functional designation aspect,
FM fire protection damper the difference between KKS and RDS-PP is
QM isolating valve
QN control valve
depicted in the F i g u r e 8.
RM non-return valve
Application explanations and instructions
BB Storage equipment becomes CM Storage of materials;
(vessels, tanks) containers, tanks, boilers, Standards provide general rules and specifi-
silos
cations. In order to facilitate efficient imple-
CT Direct measuring circuit becomes BT Conversion of an input mentation in practice, application explana-
temperature variable temperature
tions and application instructions have been
justments were made to reflect the terminol- These specifications are generally applicable developed by the VGB Working Panel “Refer-
ogy currently used in international codes and to all disciplines, such as civil, process, me- ence Designation and Plant Documentation”.
standards. chanical and electrical engineering, across all They provide detailed guidance, starting with
sectors of industries. a cross-discipline Part A and then address-
The system key is constantly updated by the ing the specific engineering disciplines of
VGB Working Panel “Reference Designation Ta b l e 5 shows some examples to illustrate mechanical engineering, civil engineering,
and Plant Documentation”. Ta b l e 4 shows the differences in letter codes and designa- electrical and I&C engineering, and I&C
an excerpt from the VGB-B 101e System Key. tions. functions in process systems (Parts B1 to B4).
Guideline VGB-B 102 Letter codes for Basic Ta b l e 6 shows an excerpt from the IEC The application instructions are for particular
functions and Product classes 81346-2, including the subdivision by tech- types of power plants (Part D1 and D2).
nical disciplines according to an example of The application explanations contain exam-
For breakdown level 2 of the designation block
main class “Storage of material and informa- ples from practice and are also available for
“Function” and for the breakdown level 1 of
tion”. training.
the designation block “Product”, the guideline
VGB-B 102 has to be applied. This standard CA – CE
replaces the KKS equipment unit key and the Storage of electric energy
KKS component key. CF – CK Consequences
Storage of information
The guideline VGB-B 102 is based on IEC
CL – CY
81346-2/DIN EN 81346-2, classifying techni- Frequently asked questions in connection with
Storage of materials, thermal and mechanic
cal objects according to their purpose or task the introduction of the RDS-PP include:
energy
and providing letter code for main- and sub-
Ta b l e 7 shows in an excerpt the conversion What does this now mean for
classes.
of table 2 of the basic standard DIN EN – my existing plant,
The guideline VGB-B 102 was developed by
81346-2 with amendments by power plant- – my plant which is currently in the
the VGB Working Panel “Reference Desig-
specific terms in the Guideline VGB-B102. pipeline, or
nation and Plant Documentation” and is the
binding letter code for the power plant. – a new plant I will set up in future?
–– From which time you should make use of
Table 6. Excerpt from the basic standard IEC 81346-2. the RDS-PP?
–– Is the KKS no longer valid?
–– … and so on.
Unfortunately no simple “Yes/No” answers or
binding deadlines can be given to answer these
very important and specific questions.
In general it has to be said that standards are
not binding laws, their application has to be
agreed between the parties to the contract.
However an obligation to apply a stand-
ard can result from legal or administrative
regulations or from contracts or other legal
grounds.
Standards always become a matter of par-
ticular interest if no amicable solution be-
tween contracting parties is found or if man
or equipment suffers damage. In these cases,
the basic principle is applicable that the re-
quirements can be deemed fulfilled if the
state of the art (which is normally reflected
in standards) has been adhered to. That may
be the requirements of a specification in the
bidding process, but that may also be the re-
quirements for the safety of man and equip-

6 VGB PowerTech 8/2007


The RDS-PP

ment. If no valid standards are used, the party Table 7. Excerpt from VGB-B 102.
concerned will have to prove – if necessary
with the assistance of third parties – that the
solution chosen by such party likewise meets 37
the requirements. B102:2010-11

These explanations do certainly not provide a Kennbuch-


concrete answer to the questions asked above stabe Benennung Denomination
Letter code
and do not nearly fully cover the complex of BZ Anzahl von Ereignissen, Zählun- Number of events, counts,
tendering procedures, product safety, industri- gen, Kombinierte Aufgaben combined tasks
al safety etc.; they are merely meant to outline BZ Ereignisanzahlmessung Event-number measuring
the complexity of the issue. BZ Kombiwandler (Spannung und Combined instrument transformer
Strom) (Voltage and current)
Nevertheless the following facts can be
BZ Messung von Anzahl von Ereignis- Measurement of number of events
summed up and should be considered in mak-
sen
ing a decision on the designation system to be
C_ Speichern von Energie, Informa- Storing of energy, information or
used: tion oder Material material
–– The KKS is an (international) „house stand- CA Kapazitive Speicherung elektri- Capacitive storage of electric
ard“ of VGB, which in absence of normative scher Energie energy
standards reflected the state of the art until CA Kompensationskondensator (elekt- Correction capacitor (electrical)
international standards were published. risch)
CA Kondensator (elektrisch) Capacitor (electrical)
–– The RDS-PP – as published ISO/TS 16952-
CA Koppelkondensator Coupling capacitor
10 – is a designation system which is sup-
ported by other international standards. CB Induktive Speicherung elektri- Inductive storage of electric en-
scher Energie ergy
–– The RDS-PP integrates systematic struc- CB Speicher, induktiv Inductive storage
tures and letter codes which are applicable CB Supraleiter Superconductor
to all industries, which – in medium term
– will result in an easier integration of Plant retrofit orCC Chemische
modernization Speicherung elektri-
projects: Chemical storage of electric en-
scher Energie ergy
„standard packages“ into the power plant Existing projectsCCor projects that are in the pi- 2008 Accumulator
on; the only arguments against such a
Akkumulator
business. peline should CC be continued as planned; decision couldrechargeable
be safety-specific aspects at a
Lithium-Metall-Akku Lithium-ion battery
–– Suppliers of „standard packages“ can not decisions should be made in the individual in- common plant site with “KKS power plants”
CC Pufferbatterie Buffer battery
decline the request for designation accord- stance, on occasion of substantial plant modi- (Note: there are also various sites where KKS
CC Sekundärzelle Secondary cell
ing to RDS by just alluding to standards fications or retrofit projects. and the predecessor system AKZ coexist).
CC Speicherbatterie Storage battery
that are applicable in other industries or to New plants
CC Speichern, chemischFor plants already
Chemical storagein the pipeline, the efforts
their house standards. This makes it easier
For completely CFnew plants which are not yet
Speichern von Informationennecessary to change the plans need to be con-
Storage of information
to make also such suppliers adhere to the
in the pipeline, RDS-PP
CF should be used
Analogwertspeicher from sidered.
Analog value storage
RDS-PP; this will relieve planners and op-
erators of time consuming and costly re- CF CD-ROM CD ROM
working. KKS Technical
CF procedure
EPROM code EPROM

–– KKS and RDS-PP will coexist for many CF Ereignisspeicher Event memory
Prefix Overall plant System Equipment Component
years and will also have to be supervised. CF Festplatte Hard disk
designation unit designation
(Function designation (Component
–– Possible problems or additional expenses key) (Equipment key)
may result for the operator if different des- unit key)
V(Z)
ignation systems are used at the same site;
= A/N NAAANN AANNNA AANN
these problems may concern the safety of
plant and persons but also the operation and
maintenance management systems. <1> <2> <3> <4>

–– All users have to develop in-house know-


how for RDS-PP; the VGB training centre
# A../..N = ANN AAANN AANNN - AA(N)NN
for power plant operating staff Kraftwerks­
schule (KWS) support this process with Conjoint Product
Prefix Prefix Function aspect Prefix
designation aspect
suitable training courses.
–– First experiences with the application of
RDS-PP Equipment code
RDS-PP are available.
However, the authors do not want to get <1> Overall plant is partial mapped by new designation block
"Conjoint designation"
around concrete recommendations:
<2> Function key is replaced by VGB-B 101e (System key)
Existing plants:
<3> Equipment unit key is replaced by VGB-B 102e
Currently, there is no need for action,
decisions should be made in the individual in- <4> Component key is replaced by VGB-B 102e

stance, on occasion of substantial plant modi-


fications or retrofit projects. Figure 8. Designation structure and designation content KKS vs. RDS-PP.

VGB PowerTech 8/2007 7


The RDS-PP

6 March 2007 (Federal Law Gazette I p. 261)” VG B G u i d e l i n e s


Maintenance of the RDS-PP Ordinance on safety and health protection in VGB-B 101e
and application support the provision of equipment and its use at the
workplace, on safety during the operation of Reference Designation System for Power
plant subject to inspection and on the organi- Plants RDS-PP, Letter Codes for Power Plant
The Working Panel “Reference Designation
sation of occupational health and safety (Be- Systems (System Key) – 2010
and Plant Documentation” as a collaborator in
standardization and author of the VGB guide- triebssicherheitsverordnung – BetrSichV) VGB-B 102
lines relating to RDS-PP is well aware that GPSG Reference Designation System for Power
suitable assistance will be needed to support
“Equipment and Product Safety Act” of 6 Jan- Plants, Letter Codes for Basic Functions and
the introduction of the RDS-PP.
uary 2004 (Federal Law Gazette I p. 2 (219)), Product Classes - 2010
Questions should be addressed directly to the last amended by Article 3 Para 33 of the law VGB-B 103
VGB office (ak-ad@vgb.org). The persons of 7 July 2005 (Federal Law Gazette I p. 1970)
interested in RDS-PP will be registered and Act on Technical Work Equipment and Con- Designation codes for document kind classifi-
supplied with information about current de- sumer Products (Geräte- und Produktsicher- cation code (DCC key) - 2010
velopments. Current information will also be heitsgesetz - GPSG) VGB-R 171e
provided on the VGB website (www.vgb.org/
db_rds.html). Standards Provision of Technical Documentation (Tech-
IEC 60204-1; DIN EN 60204-1 nical Plant Data, Documents) for Power Plants
There are thematic core teams from the VGB
– 2010
working panel for specific technical inquir- Safety of machinery - Electrical equipment of
ies. The answers of the first level are free of machines - Part 1: General requirements
charge. The core teams are furthermore availa- Te c h n i c a l a r t i c l e s
ble for engineer services or can arrange equiv- IEC 61355-1; DIN EN 61355-1
Horst Anders, Philipp Freymeyer, Helmut
alent contacts. Basically, such effort needs to Classification and designation of documents
Hotes: System zur Kennzeichnung von Ge-
be charged. for plants, systems and equipment
räten und Anlagen in Wärmekraftwerken.
The VGB training centre for power plant oper- “Elektrizitätswirtschaft” Vol. 68, issue 6,
IEC 61175; DIN EN 61175
ating staff, which is likewise a member of the 17 March 1969, pp. 181 - 192
Working Panel “Reference Designation and Industrial systems, installations and equip-
ment and industrial products – Designation of Horst Anders, Philipp Freymeyer, Helmut
Plant Documentation”, will provide training
signals Hotes: Kennzeichnung der elektrotechni-
courses and seminars of RDS-PP on demand.
schen, mess- und regeltechnischen Anlagen,
IEC 61666; DIN EN 61666 Anlagenteile und Geräte in Wärmekraftwer-
Literature ken. “Elektrizitätswirtschaft” Vol. 68, issue 6,
Industrial systems, installations and equip- 17 March 1969, pp. 193 - 197
ment and industrial products - Identification
E U D i r e c t iv e s of terminals within a system Hugo Popp: Die neue Vornorm DIN V 6779-
1. VGB Kraftwerkstechnik 72 (1992), issue 7
DIRECTIVE 2004/17/EC OF THE EU- IEC 81346-1; DIN EN 81346-1
ROPEAN PARLIAMENT AND OF THE Hugo Popp: Der Norm-Entwurf DIN 6779-10/
COUNCIL of 31 March 2004. Coordinating Industrial systems, installations and equip- Mai 1998. VGB Kraftwerkstechnik 3/99
the procurement procedures of entities operat- ment and industrial products – Structuring
principles and reference designations – Part Heinz Müller, Rainer Ahleff: Referenzkenn-
ing in the water, energy, transport and postal
1: Basic rules zeichnung nach ISO/TS 16952-1 and DIN
services sectors
ISO/TS 16952-1. DIN Mitteilungen, 3/2007
DIRECTIVE 2004/18/EC OF THE EUROPE- IEC 81346-2; DIN EN 81346-2
AN PARLIAMENT AND OF THE COUN- Rainer Ahleff, Zbynek Cihlar : ISO/IEC struc-
CIL of 31 March 2004. On the coordination Industrial systems, installations and equip- turing and designation standards – A frame-
of procedures for the award of public works ment and industrial products – Structuring work for industry. ISO Focus May 2007 □
contracts, public supply contracts and public principles and reference designations – Part
service contracts 2: Classification of objects and codes for
classes
DIRECTIVE 2006/42/EC OF THE EU-
ROPEAN PARLIAMENT AND OF THE ISO/TS 16952-1; DIN ISO/TS 16952-1
COUNCIL of 17 May 2006. On machinery,
Technical product documentation – Reference
and amending Directive 95/16/EC (recast)
designation system – Part 1: General applica-
DIRECTIVE 2001/95/EC OF THE EUROPE- tion rules
AN PARLIAMENT AND OF THE COUN-
CIL of 3 December 2001. On general product ISO/TS 16952-10; DIN ISO/TS 16952-10
safety Technical product documentation – Reference
N a t i o n a l l aw s / o r d i n a n c e s designation system – Part 10: Power Plants
BetrSichV
“Operational Safety Ordinance” of 27 Sep-
tember 2002 (Federal Law Gazette I p. 3777),
last amended by Article 5 of the ordinance of

8 VGB PowerTech 8/2007


VGB PowerTech Service GmbH Fon: +49 201 8128 – 288
Klinkestraße 27-31 Fax: +49 201 8128 – 321
45136 Essen, Germany joerg.kaiser@vgb.org - www.vgb.org