You are on page 1of 1

Pt 100-Temperature Relays Type TR

Pt 100-Temperature-Relay Type TR111V


1 Sensor

TR111V Temperature-Relays TR111V Application:


3-Leiter can be used as limit-switches Protection from over-temperature in processes,
or 2-point controllers with high plants and machines. Monitoring of temperatures in
repeat accuracy. bearings.
3 measuring-ranges, adjustable Controlling of temperatures in processes and plants.
hysteresis and switching delay
and the choice between opera- Us
ting- and closed-current principle
DC + –
of the relay make it a very univer-
sal device. AC ~ ~
A1 A1 A2 12 11 14
• Measuring input 1x Pt 100 ~ Us ~
+ –
(RTD) / 3-wire Ue = 250 V

.com

12090-1200-01
Ie = 2 A
• measuring-ranges selectable: AC 15
Temperatur- 60
- -10...+40/0...100/0...200 °C Relais
40
80

- 0...100/100...200/200...300/ %T 20
100 %

300...400 °C TR111V 5
0 8 Power
• 1 limit adjustable 0...100 % Hys. 10 K
T1
switching delay adjustable 2 8 Relay
0,1...10 s don 3 10 s
on
T2 /doff 0,1
• Output-relay 1 changeover-
T3
contact (co) 0...100 °C 0...200 °C
T
• Operating- or closed-surrent- -10...40 °C
Part numbers: mode selectable with bridge
T224107 -10...+200 °C T3 T2 T1 nc 1
• Switching off at sensor-short-
T224108 0...+400 °C circuit or break 3) 1)
• LEDs for display state of
operation 4) 2)
• Universal supply-voltage AC/
DC 24-240 V
• Housing for mounting in
Pt 100
switchgear cabinets or fuse-
1) Ruhestrom / closed current mode
boxes, 35 mm wide
2) Arbeitsstrom / operating current mode
Mounting heigt 55 mm 3) 3-Leiter / 3-wire
4) 2-Leiter / 2-wire
Brücke zwischen T2-T3 / Bridge from T2-T3

Technical Data Supply voltageUs AC/DC 24-240 V, 0/50/60 Hz, < 2W, < 3VA
(DC 20,4 - 297, AC 20-264 V)

Pt 100 -Sensor (RTD) EN 60751 / IEC 60751

Measuring ranges ranges selectable


Error of setting ±5K
Repeat error app. 0,5 K
Temperature-dependence ≤0,05 %/K
Hysteresis adjustable 2...10 K
Switching delay don/doff adjustable 0,1...10 s

Relay output 1 change-over contact (co)


Type of contact type 3 see "general technical informations"
Test conditions siehe "general technical informations"

Rated ambient temperature -20°C…+55°C


range

Dimensions (H x W x D) design V4: 90x70x58 [mm], mounting height 55 mm


Attachment on 35 mm DIN-rail according to EN 60 715 or
with screws M4
Protection housing/terminals IP 30 / IP 20
Weight app. 100 g

30 ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, info@ziehl.de, www.ziehl.de 2015-09-30