GAS SUPPRESSION SYSTEM: ROOM SCHEDULE - RAS BU ABBOUD (As on 20.09.

2016)

Area Height Volume


S. No. Room Name Room Tag No. Room Level Drawings Reference
(m²) (m) (m3)

1 UPS / +D5:D49 BATTERY ROOM 1.711 AT GRADE 43.65 5.10 222.62 Arch Drg. Ref. No. YEST030-AG-29253

2 UPS / BATTERY ROOM 1.712/ 1.671 AT GRADE 43.06 5.10 219.59 Arch Drg. Ref. No. YEST030-AG-29253 Rev 2.

3 ELECTRICAL ROOM 1.716 AT GRADE 25.70 3.48 89.44 Arch Drg. Ref. No. YEST030-AG-29259

4 ELECTRICAL ROOM 1.771 AT GRADE 45.11 4.50 202.98 Arch Drg. Ref. No. YEST030-AG-29253 Rev 2

5 ELECTRICAL ROOM 1.714 AT GRADE 50.18 3.55 178.12 Arch Drg. Ref. No. YEST030-AG-29256

6 UPS / BATTERY ROOM 2.772 FIRST FLOOR 74.82 5.10 381.58 Arch Drg. Ref. No. YEST030-ZZ-29252

7 UPS / BATTERY ROOM 2.781/2.775 FIRST FLOOR 73.70 5.10 375.85 Arch Drg. Ref. No. YEST030-ZZ-29252

8 STATION CONTROL ROOM -1.578 CONCOURSE 51.36 2.80 143.81

9 MCC -1.713 CONCOURSE 74.06 5.11 378.24 Arch Drg. Ref. No. YEST030-CL-28269

10 MCC -1.714 CONCOURSE 32.77 5.29 173.53 Arch Drg. Ref. No. YEST030-CL-28275

11 AC/DC/SCADA ROOM -1.715 CONCOURSE 35.14 5.32 186.91

12 UPS / BATTERY ROOM -1.716 CONCOURSE 35.18 5.30 186.25 Arch Drg. Ref. No. YEST030-CL-28276

13 TEL / IT ROOM -1.719 CONCOURSE 17.85 5.40 96.38 Arch Drg. Ref. No. YEST030-CL-28272

14 TEL / IT ROOM -1.720 CONCOURSE 28.09 5.09 143.14 Arch Drg. Ref. No. YEST030-CL-28272

15 ELECTRICAL ROOM -1.723 CONCOURSE 18.76 4.00 75.02 Arch Drg. Ref. No. YEST030-CL-28270

16 ELECTRICAL RM (HVAC MCC) -1.724 CONCOURSE 32.39 4.00 129.55 Arch Drg. Ref. No. YEST030-CL-28272

17 ELECTRICAL ROOM -1.725 CONCOURSE 58.12 4.00 232.49 Arch Drg. Ref. No. YEST030-CL-28272

18 ELECTRICAL ROOM -1.726 CONCOURSE 25.81 6.00 154.88 Arch Drg. Ref. No. YEST030-CL-28276 Rev 3

19 ELECTRICAL RM (HVAC MCC) -1.728 CONCOURSE 22.75 4.00 90.99 Arch Drg. Ref. No. YEST030-CL-28276

20 MCC -1.743 CONCOURSE 38.52 5.12 197.22 Arch Drg. Ref. No. YEST030-CL-28269

21 MCC -1.744 CONCOURSE 34.64 5.30 183.39 Arch Drg. Ref. No. YEST030-CL-28275

22 AC/DC/SCADA ROOM -1.745 CONCOURSE 72.70 6.25 454.40 Arch Drg. Ref. No. YEST030-CL-28275

23 TEL / IT ROOM -1.749 CONCOURSE 28.08 5.09 143.08

24 TEL / IT ROOM -1.750 CONCOURSE 17.85 5.09 90.94

25 ELECTRICAL ROOM -1.753 CONCOURSE 19.79 4.00 79.15 Arch Drg. Ref. No. YEST030-CL-28269

26 ELECTRICAL RM (HVAC MCC) -1.754 CONCOURSE 32.39 4.00 129.55 Arch Drg. Ref. No. YEST030-CL-28271

27 ELECTRICAL ROOM -1.755 CONCOURSE 58.13 4.00 232.50 Arch Drg. Ref. No. YEST030-CL-28271

28 ELECTRICAL ROOM -1.756 CONCOURSE 25.81 6.00 154.88 Arch Drg. Ref. No. YEST030-CL-28275

29 ELECTRICAL ROOM (HVAC MCC) -1.758 CONCOURSE 22.34 6.00 134.06 Arch Drg. Ref. No. YEST030-CL-28275

30 TEL / IT ROOM MAIN ROOM -1.771 CONCOURSE 58.81 3.90 229.36 Arch Drg. Ref. No. YEST030-CL-28273

31 TEL / IT ROOM THIRD PARTIES -1.772 CONCOURSE 33.81 5.65 191.03 Arch Drg. Ref. No. YEST030-CL-28273

32 TEL / IT ROOM -1.773 CONCOURSE 26.57 5.08 135.02 Arch Drg. Ref. No. YEST030-CL-28273

33 TELECOM SAFETY POLICE -1.775 CONCOURSE 12.28 5.79 71.09 Arch Drg. Ref. No. YEST030-CL-28273

34 TELECOM SECURITY QAF -1.776 CONCOURSE 12.18 5.80 70.57 Arch Drg. Ref. No. YEST030-CL-28273

35 ELECTRICAL ROOM -1.784 ENTRANCE 02 - SUBWAY 40.10 4.00 160.41 Arch Drg. Ref. No. YEST030-SW-28294

36 TEL / IT ROOM -1.785 SUBWAY 15.29 1.85 28.20 Arch Drg. Ref. No. YEST030-SW-28294

37 ELECTRICAL ROOM (HVAC MCC) -1.787 ENTRANCE 02 - SUBWAY 24.35 4.00 97.40 Arch Drg. Ref. No. YEST030-SW-28294

38 TEL / IT -1.788 SUBWAY 19.58 4.00 78.32 Arch Drg. Ref. No. YEST030-SW-28294

PLATFORM /
39 SIGNALLING ROOM -2.711 48.63 3.57 173.46 Arch Drg. Ref. No. YEST030-PL-28282/4
UNDERPLATFORM

40 SPS MV/LV ROOM -2.712 PLATFORM 55.41 6.00 332.44 Arch Drg. Ref. No. YEST030-PL-28284

41 ELECTRICAL ROOM -2.713 PLATFORM / 25.74 8.50 218.82 Arch Drg. Ref. No. YEST030-PL-28284
UNDERPLATFORM

42 ELECTRICAL ROOM -2.714 PLATFORM 25.28 4.00 101.12 Arch Drg. Ref. No. YEST030-PL-28284

43 SIGNALLING ROOM -2.741 PLATFORM 43.05 5.65 243.22 Arch Drg. Ref. No. YEST030-PL-28283

44 SPS MV/LV ROOM -2.742 PLATFORM 58.23 6.00 349.36 Arch Drg. Ref. No. YEST030-PL-28283

45 TEL / IT ROOM -2.743 PLATFORM 13.06 6.00 78.35 Arch Drg. Ref. No. YEST030-PL-28283

46 ELECTRICAL ROOM -2.744 PLATFORM 26.78 4.00 107.12 Arch Drg. Ref. No. YEST030-PL-28283

47 DC TPS SUBSTATION -3.716 UNDERPLATFORM BLUE 252.80 6.57 1660.08 Arch Drg. Ref. No. YEST030-UP-28292
LINE

AC/DC/SCADA ROOM+SPS MV/LV UNDERPLATFORM BLUE


48 -3.744 135.94 4.80 652.49 Arch Drg. Ref. No. YEST030-UP-28285
ROOM LINE

UNDERPLATFORM BLUE
49 DC TPS SUBSTATION -3.746 288.25 5.40 1556.17 Arch Drg. Ref. No. YEST030-UP-28291
LINE

50 TEL/IT ROOM -3.745 UNDERPLATFORM BLUE 12.56 5.50 69.08 Arch Drg. Ref. No. YEST030-UP-28285
LINE

UNDERPLATFORM BLUE
51 ELECTRICAL ROOM -3.743 25.85 5.50 142.19 Arch Drg. Ref. No. YEST030-UP-28285
LINE

SPS MV/LV ROOM + AC/DC SCADA UNDERPLATFORM BLUE


52 -3.712 / -3.714 137.14 5.50 754.28 Arch Drg. Ref. No. YEST030-UP-28286
ROOM LINE

UNDERPLATFORM BLUE
53 ELECTRICAL ROOM -3.713 25.74 5.50 141.59 Arch Drg. Ref. No. YEST030-UP-28286
LINE

54 TEL/IT ROOM -3.715 UNDERPLATFORM BLUE 12.56 5.50 69.08 Arch Drg. Ref. No. YEST030-UP-28286
LINE
GAS SUPPRESSION SYSTEM: Room Schedule - NATIONAL MUSEUM of QATAR Station (As on 29.09.2016) - Rev. 02

Room Tag Area Height Volume


S. No. Name No. Room Level (m2) (m) (m3)
Architectural Reference

1 FIRE CONTROL PANEL 0.109 AT GRADE 4.00 2.50 10.00 M006-GDB-ARC-DWG-YEST020-AG-52272

EXIT STAIRS S07 & S08


2 ELECTRICAL ROOM 0.019 17.10 4.10 70.11 M006-GDB-ARC-DWG-YEST020-AG-52272
LEVEL

3 UPS ROOM 0.119 GRADE LEVEL 109.10 3.10 338.21 M006-GDB-ARC-DWG-YEST020-ZZ-55260

4 ELECTRICAL ROOM 0.120 GRADE LEVEL 35.00 3.10 108.50 M006-GDB-ARC-DWG-YEST020-ZZ-55260

5 AC/DC SCADA ROOM 1 -1.001 INTERMEDIATE LEVEL 66.25 4.95 327.93 M006-GDB-ARC-DWG-YEST020-IL-30273

6 UPS BATTERY ROOM 1 -1.027 INTERMEDIATE LEVEL 8.92 4.95 44.14 M006-GDB-ARC-DWG-YEST020-IL-30273

7 TEL/IT ROOM -1.009 INTERMEDIATE LEVEL 17.27 4.95 85.50 M006-GDB-ARC-DWG-YEST020-IL-30273

8 ELECTRICAL ROOM -1.017 INTERMEDIATE LEVEL 50.04 4.95 247.70 M006-GDB-ARC-DWG-YEST020-IL-30274

9 AC/ DC SCADA ROOM 2 -1.024 INTERMEDIATE LEVEL 40.00 4.95 198.00 M006-GDB-ARC-DWG-YEST020-IL-30275

10 UPS BATTERY ROOM 2 -1.025 INTERMEDIATE LEVEL 46.00 4.95 227.70 M006-GDB-ARC-DWG-YEST020-IL-30275

11 ELECTRICAL ROOM -1.056 INTERMEDIATE LEVEL 39.93 4.95 197.65 M006-GDB-ARC-DWG-YEST020-IL-30274

12 TEL/IT ROOM -1.032 INTERMEDIATE LEVEL 27.36 4.95 135.41 M006-GDB-ARC-DWG-YEST020-IL-30274

13 ELECTRICAL ROOM -1.095 INTERMEDIATE LEVEL 30.86 4.95 152.75 M006-GDB-ARC-DWG-YEST020-IL-30274

14 ELECTRICAL ROOM -2.005 CONCOURSE LEVEL 40.87 5.65 230.91 M006-GDB-ARC-DWG-YEST020-CL-30270

15 MCC 1 & 2 -2.095 CONCOURSE LEVEL 35.69 6.10 217.71 M006-GDB-ARC-DWG-YEST020-CL-30270

16 TEL/IT THIRD PARTIES -2.063 CONCOURSE LEVEL 30.00 5.65 169.50 M006-GDB-ARC-DWG-YEST020-CL-30270

17 TEL/IT ROOM -2.076 CONCOURSE LEVEL 12.14 5.65 68.61 M006-GDB-ARC-DWG-YEST020-CL-30270

18 STATION CONTROL ROOM -2.015 CONCOURSE LEVEL 28.71 3.75 107.66 M006-GDB-ARC-DWG-YEST020-CL-30272

19 ELECTRICAL CLOSET -2.017 CONCOURSE LEVEL 1.86 5.65 10.51 M006-GDB-ARC-DWG-YEST020-CL-30272

20 ELECTRICAL ROOM -2.033 CONCOURSE LEVEL 28.18 5.65 159.20 M006-GDB-ARC-DWG-YEST020-CL-30272

21 TEL/IT MAIN ROOM -2.038 CONCOURSE LEVEL 48.26 5.65 272.65 M006-GDB-ARC-DWG-YEST020-CL-30272

22 TELECOM ROOM QAF -2.039 CONCOURSE LEVEL 12.00 5.65 67.81 M006-GDB-ARC-DWG-YEST020-CL-30272

23 TELECOM SAFETY POLICE -2.074 CONCOURSE LEVEL 13.35 5.65 75.42 M006-GDB-ARC-DWG-YEST020-CL-30272

24 MCC 3 & 4 -2.097 CONCOURSE LEVEL 35.91 5.65 202.86 M006-GDB-ARC-DWG-YEST020-CL-30272

25 ESCALATOR CONTROL ROOM -2.136 CONCOURSE LEVEL 3.50 3.20 11.20 M006-GDB-ARC-DWG-YEST020-SW-30285

26 ELECTRICAL ROOM -2.130 SUBWAY LEVEL 41.04 10.00 410.36 M006-GDB-ARC-DWG-YEST020-SW-30286/ ZZ-
30558

27 ESCALATOR CONTROL ROOM -2.126 SUBWAY LEVEL 3.20 3.20 10.24 M006-GDB-ARC-DWG-YEST020-SW-30286

28 ELECTRICAL ROOM -2.140 SUBWAY LEVEL 41.01 10.00 410.10 M006-GDB-ARC-DWG-YEST020-SW-30285

29 ELECTRICAL ROOM -2.151 SUBWAY LEVEL 32.40 4.80 155.52 M006-GDB-ARC-DWG-YEST020-SW-52262

ESCALATOR CONTROL PANEL


30 -2.155 SUBWAY LEVEL 4.80 3.90 18.72 M006-GDB-ARC-DWG-YEST020-SW-52262
ROOM

31 TEL/IT ROOM -3.022 PLATFORM LEVEL 25.91 3.60 93.27 M006-GDB-ARC-DWG-YEST020-PL-30278

32 ELECTRICAL ROOM -3.015 PLATFORM LEVEL 27.30 3.60 98.28 M006-GDB-ARC-DWG-YEST020-PL-30278

33 SPS MV/LV ROOM -3.111 PLATFORM LEVEL 50.04 6.11 305.74 M006-GDB-ARC-DWG-YEST020-PL-30276

34 SPS MV/LV ROOM 2 -3.004 PLATFORM LEVEL 67.56 6.65 449.29 M006-GDB-ARC-DWG-YEST020-PL-30278

35 SIGNALLING ROOM -3.005 PLATFORM LEVEL 43.65 6.65 290.27 M006-GDB-ARC-DWG-YEST020-PL-30278

36 ELECTRICAL ROOM -4.039 UNDERPLATFORM LEVEL 29.70 3.20 95.04 M006-GDB-ARC-DWG-YEST020-UL-30279

37 TEL/IT ROOM -4.032 UNDERPLATFORM LEVEL 12.60 3.10 39.06 M006-GDB-ARC-DWG-YEST020-UL-30279

38 CABLE DRAW UTILITY ACCESS -4.033 UNDERPLATFORM LEVEL 58.40 2.65 154.76 M006-GDB-ARC-DWG-YEST020-UL-30281

39 CABLE DRAW -4.135 UNDERPLATFORM LEVEL 48.70 3.10 150.97 M006-GDB-ARC-DWG-YEST020-UL-30279

40 IT ROOM -4.017 UNDERPLATFORM LEVEL 18.82 3.20 60.23 M006-GDB-ARC-DWG-YEST020-UL-30281

41 TPS ROOM -4.006 UNDERPLATFORM LEVEL 307.06 9.75 2,993.84 M006-GDB-ARC-DWG-YEST020-UL-30279

42 ELECTRICAL ROOM -4.021 UNDERPLATFORM LEVEL 30.07 3.20 96.23 M006-GDB-ARC-DWG-YEST020-SW-30281


GAS SUPPRESSION SYSTEM CYLINDER LOCATIONS - Souq Waqif Station (As on 29.09.2016)

Room Tag Volume


S. No. Room Name Room Level Area (m²) Height (m) Architectural Drg Ref.
No. (m3)

1 UPS BATTERY ROOM 1 & 2 +1.010 FIRST FLOOR LEVEL 99.80 4.00 399.20 M006-GDB-ARC-DWG-YEST010-ZZ-31534

2 ESCALATOR & LIFT CONTROL ROOM -1.019 CONCOURSE LEVEL 5.80 5.50 31.90 M006-GDB-ARC-DWG-YEST010-CL-31291

3 ELECTRICAL ROOM -1.020 CONCOURSE LEVEL 14.30 4.60 65.78 M006-GDB-ARC-DWG-YEST010-CL-31291

4 TELECOM SECURITY QAF -1.105 CONCOURSE LEVEL 12.50 5.40 67.50 M006-GDB-ARC-DWG-YEST010-CL-31270

5 TELECOM SAFETY POLICE -1.106 CONCOURSE LEVEL 12.90 5.50 70.95 M006-GDB-ARC-DWG-YEST010-CL-31270

STATION CONTROL & FIRE COMMAND


6 CENTRE -1.116 CONCOURSE LEVEL 30.60 3.40 104.04 M006-GDB-ARC-DWG-YEST010-CL-31270

7 TELECOM THIRD PARTIES -1.123 CONCOURSE LEVEL 30.00 5.00 150.00 M006-GDB-ARC-DWG-YEST010-CL-31270

8 ELECTRICAL ROOM -1.124 CONCOURSE LEVEL 18.70 3.20 59.84 M006-GDB-ARC-DWG-YEST010-CL-31270

9 TEL/IT MAIN ROOM -1.144 CONCOURSE LEVEL 41.80 3.60 150.48 M006-GDB-ARC-DWG-YEST010-CL-31270

M006-GDB-ARC-DWG-YEST010-CL-31272/
10 ELECTRICAL ROOM -1.147 CONCOURSE LEVEL 28.50 5.50 156.75 31271

11 TEL/IT ROOM -1.149 INTERMEDIATE LEVEL 15.40 5.00 77.00 M006-GDB-ARC-DWG-YEST010-IL-31273

12 ELECTRICAL ROOM -1.168 CONCOURSE LEVEL 12.10 5.50 66.55 M006-GDB-ARC-DWG-YEST010-CL-31291

13 ELECTRICAL CLOSET -1.192 CONCOURSE LEVEL 3.20 2.40 7.68 M006-GDB-ARC-DWG-YEST010-CL-31270

14 ESCALATOR & LIFT CONTROL ROOM -1.229 CONCOURSE LEVEL 14.10 1.70 23.97 M006-GDB-ARC-DWG-YEST010-CL-31577/
ZZ-52432

15 TEL/IT ROOM -1.286 CONCOURSE LEVEL 17.20 5.50 94.60 M006-GDB-ARC-DWG-YEST010-CL-31291

16 MCC 1 & 2 -2.043 INTERMEDIATE LEVEL 39.40 4.80 189.12 M006-GDB-ARC-DWG-YEST010-IL-31273

17 TEL/IT ROOM -2.153 INTERMEDIATE LEVEL 19.80 4.80 95.04 M006-GDB-ARC-DWG-YEST010-IL-31275

18 ELECTRICAL CLOSET -2.160 INTERMEDIATE LEVEL 3.20 4.80 15.36 M006-GDB-ARC-DWG-YEST010-IL-31275

19 ELECTRICAL ROOM -2.161 INTERMEDIATE LEVEL 51.90 4.80 249.12 M006-GDB-ARC-DWG-YEST010-IL-31275

20 ELECTRICAL ROOM -2.164 INTERMEDIATE LEVEL 46.50 4.80 223.20 M006-GDB-ARC-DWG-YEST010-IL-


31275/31292

21 MCC 3 & 4 -2.165 INTERMEDIATE LEVEL 32.00 4.80 153.60 M006-GDB-ARC-DWG-YEST010-IL-31292

22 AC/DC SCADA ROOM 2 -2.169 INTERMEDIATE LEVEL 75.80 4.80 363.84 M006-GDB-ARC-DWG-YEST010-IL-31275

23 AC/DC SCADA ROOM 1 -3.103 PLATFORM LEVEL 78.50 6.10 478.85 M006-GDB-ARC-DWG-YEST010-PL-31276

24 ELECTRICAL ROOM -3.107 PLATFORM LEVEL 29.80 6.10 181.78 M006-GDB-ARC-DWG-YEST010-PL-31276

25 SPS MV/LV MAIN ROOM 1 -3.115 PLATFORM LEVEL 50.30 6.20 311.86 M006-GDB-ARC-DWG-YEST010-PL-31276

26 SIGNALLING ROOM -3.118 PLATFORM LEVEL 28.80 5.80 167.04 M006-GDB-ARC-DWG-YEST010-PL-31276

27 SPS MV/LV MAIN ROOM 2 -3.134 PLATFORM LEVEL 53.90 6.10 328.79 M006-GDB-ARC-DWG-YEST010-PL-31293

28 CABLE CHAMBER -4.100 UNDER PLATFORM LEVEL 51.00 3.20 163.20 M006-GDB-ARC-DWG-YEST010-UL-31279

29 ELECTRICAL ROOM -4.102 UNDER PLATFORM LEVEL 25.00 3.20 80.00 M006-GDB-ARC-DWG-YEST010-UL-31279

30 ELECTRICAL ROOM -4.113 UNDER PLATFORM LEVEL 12.50 3.20 40.00 M006-GDB-ARC-DWG-YEST010-UL-31294

31 CABLE CHAMBER -4.140 UNDER PLATFORM LEVEL 24.90 3.20 79.68 M006-GDB-ARC-DWG-YEST010-UL-31294

32 DC TPS SUBSTATION UNDERCROFT -4.145 UNDER PLATFORM LEVEL 250.80 7.10 1,780.68 M006-GDB-ARC-DWG-YEST010-UL-31294

33 TEL / IT -4.148 UNDER PLATFORM LEVEL 29.60 3.20 94.72 M006-GDB-ARC-DWG-YEST010-UL-31281


GAS SUPPRESSION SYSTEM CYLINDER LOCATIONS - BIN MAHMOUD Station (As on 23.10.2016)

Room Tag Volume


S. No. Name Room Level Area (m2) Height (m) Architectural Reference
No. (m3)

1 MCC +1.710 GROUND LEVEL 128.48 5.85 751.61 M006-GDB-ARC-DWG-YWST010-00-34462/ZZ-34464


2 UPS +1.712 GROUND LEVEL 45.68 5.85 267.25 M006-GDB-ARC-DWG-YWST010-00-34462/ZZ-34464

3 UPS +1.713 GROUND LEVEL 74.53 5.70 424.80 M006-GDB-ARC-DWG-YWST010-00-34462/ZZ-34464

4 ELECTRICAL CLOSET -0.772 INTERMEDIATE LEVEL 3.30 2.30 7.59 M006-GDB-ARC-DWG-YWST010-ZZ-34527


STATION CONTROL ROOM &
5 FIRE COMMAND CENTRE -1.671 CONCOURSE LEVEL 44.40 4.20 186.48 M006-GDB-ARC-DWG-YWST010-CL-33295/34353

6 TEL/IT ROOM -1.711 CONCOURSE LEVEL 35.37 6.00 212.22 M006-GDB-ARC-DWG-YWST010-CL-33294/ZZ-33346

7 ELECTRICAL ROOM -1.713 CONCOURSE LEVEL 24.41 9.60 234.34 M006-GDB-ARC-DWG-YWST010-CL-33291/ZZ-33332

8 ELECTRICAL ROOM -1.714 CONCOURSE LEVEL 41.70 9.30 387.81 M006-GDB-ARC-DWG-YWST010-CL-33290


9 AC/DC/SCADA ROOM -1.716 CONCOURSE LEVEL 54.98 6.70 368.37 M006-GDB-ARC-DWG-YWST010-CL-33295

10 ELECTRICAL ROOM -1.719 CONCOURSE LEVEL 18.81 8.60 161.77 M006-GDB-ARC-DWG-YWST010-CL-33290

11 ELECTRICAL ROOM -1.720 CONCOURSE LEVEL 92.91 6.80 631.79 M006-GDB-ARC-DWG-YWST010-CL-33294/33295

12 ELECTRICAL ROOM -1.721 CONCOURSE LEVEL 28.64 6.10 174.70 M006-GDB-ARC-DWG-YWST010-CL-33297

13 TEL/IT MAIN ROOM -1.722 CONCOURSE LEVEL 52.77 6.50 343.01 M006-GDB-ARC-DWG-YWST010-CL-33294

14 ELECTRICAL ROOM -1.724 CONCOURSE LEVEL 48.70 9.30 452.91 M006-GDB-ARC-DWG-YWST010-CL-33291/ZZ-33332

15 ELECTRICAL ROOM -1.731 CONCOURSE LEVEL 38.12 6.10 232.53 M006-GDB-ARC-DWG-YWST010-CL-33294/95

16 TEL/IT ROOM -1.732 CONCOURSE LEVEL 29.77 6.20 184.57 M006-GDB-ARC-DWG-YWST010-CL-33289


17 TELECOM SAFETY POLICE -1.733 CONCOURSE LEVEL 12.02 6.50 78.13 M006-GDB-ARC-DWG-YWST010-CL-33294
18 TELECOM SECURITY QAF -1.734 CONCOURSE LEVEL 12.06 6.50 78.39 M006-GDB-ARC-DWG-YWST010-CL-33294

19 TEL/IT THIRD PARTIES -1.735 CONCOURSE LEVEL 39.34 5.80 228.17 M006-GDB-ARC-DWG-YWST010-CL-33294

20 MCC -1.739 CONCOURSE LEVEL 30.05 6.10 183.31 M006-GDB-ARC-DWG-YWST010-CL-33289


21 MCC -1.740 CONCOURSE LEVEL 42.02 6.60 277.33 M006-GDB-ARC-DWG-YWST010-CL-33288

22 MCC -1.741 CONCOURSE LEVEL 42.33 6.50 275.15 M006-GDB-ARC-DWG-YWST010-CL-33297

23 UPS/BATTERY ROOM -1.744 CONCOURSE LEVEL 25.11 6.70 168.24 M006-GDB-ARC-DWG-YWST010-CL-33295


24 TEL/IT ROOM -1.750 CONCOURSE LEVEL 29.81 6.50 193.77 M006-GDB-ARC-DWG-YWST010-CL-33288
25 TEL/IT ROOM -1.751 CONCOURSE LEVEL 24.47 6.50 159.06 M006-GDB-ARC-DWG-YWST010-CL-33289
26 TEL/IT ROOM -1.752 CONCOURSE LEVEL 19.27 6.50 125.26 M006-GDB-ARC-DWG-YWST010-CL-33294

27 ELECTRICAL CLOSET -1.771 CONCOURSE LEVEL 4.60 1.50 6.90 M006-GDB-ARC-DWG-YWST010-CL-33294/ZZ-34517

28 ELECTRICAL CLOSET -1.772 CONCOURSE LEVEL 3.17 3.50 11.10 M006-GDB-ARC-DWG-YWST010-CL-33297/34523/


33337
ZZ-

29 SIGNALLING ROOM -1.773 CONCOURSE LEVEL 46.41 8.10 375.95 M006-GDB-ARC-DWG-YWST010-CL-33294

30 SPS MV/LV ROOM -2.714 PLATFORM LEVEL 75.32 6.50 489.58 M006-GDB-ARC-DWG-YWST010-PL-33305

31 ELECTRICAL ROOM -2.721 PLATFORM LEVEL 32.75 5.00 163.75 M006-GDB-ARC-DWG-YWST010-PL-33304


32 TEL/IT ROOM -3.711 UNDERPLATFORM LEVEL 19.16 6.00 114.96 M006-GDB-ARC-DWG-YWST010-UL-33317

33 TEL/IT ROOM -3.712 UNDERPLATFORM LEVEL 14.25 3.40 48.45 M006-GDB-ARC-DWG-YWST010-UL-33314

-3.713,
34 SPS MV/LV ROOM/AC/DC/ -3.714 & UNDERPLATFORM LEVEL 142.18 7.30 1,037.89 M006-GDB-ARC-DWG-YWST010-UL-33309
SCADA/UPS/BATTERY ROOM
-3.715

35 ELECTRICAL ROOM -3.716 UNDERPLATFORM LEVEL 52.01 5.30 275.66 M006-GDB-ARC-DWG-YWST010-UL-33308

36 ELECTRICAL ROOM -3.717 UNDERPLATFORM LEVEL 32.40 8.70 281.85 M006-GDB-ARC-DWG-YWST010-UL-33317


37 ELECTRICAL ROOM -3.718 UNDERPLATFORM LEVEL 26.03 8.70 226.46 M006-GDB-ARC-DWG-YWST010-UL-33309

38 TEL/IT ROOM -3.727 UNDERPLATFORM LEVEL 16.18 6.00 97.07 M006-GDB-ARC-DWG-YWST010-UL-33308

39 DC TPS SUBSTATION -3.743 UNDERPLATFORM LEVEL 250.00 9.00 2,250.00 M006-GDB-ARC-DWG-YWST010-UL-33314/33316


40 ELECTRICAL ROOM -3.745 UNDERPLATFORM LEVEL 35.46 8.70 308.48 M006-GDB-ARC-DWG-YWST010-UL-33317
GAS SUPPRESSION SYSTEM CYLINDER LOCATIONS - AL SADD C RING Station (As on 22.10.2016)

Room Tag Area Height Volume


S. No. Name No. Room Level Architectural Reference
(m2) (m) (m3)

1 UPS Room +1.772 GRADE LEVEL 76.51 5.00 382.55 M006-GDB-ARC-DWG-YWST020-00-54238


2 UPS ROOM +1.773 GRADE LEVEL 79.25 5.60 443.80 M006-GDB-ARC-DWG-YWST020-00-54238
3 UPS ROOM +1.775 GRADE LEVEL 31.66 5.60 177.30 M006-GDB-ARC-DWG-YWST020-00-54238
4 UPS ROOM +1.776 GRADE LEVEL 33.72 5.60 188.83 M006-GDB-ARC-DWG-YWST020-00-54238
5 ELECTRICAL ROOM +1.780 GRADE LEVEL 47.71 5.60 267.18 M006-GDB-ARC-DWG-YWST020-00-54238
6 MCC ROOM +1.783 GRADE LEVEL 70.66 5.30 374.50 M006-GDB-ARC-DWG-YWST020-00-54238
7 ELECTRICAL ROOM -0.776 SUBWAY LEVEL 38.38 4.60 176.55 M006-GDB-ARC-DWG-YWST020-SW-35292
8 ELECTRICAL ROOM -0.778 SUBWAY LEVEL 36.36 5.70 207.25 M006-GDB-ARC-DWG-YWST020-SW-35296
9 ELECTRICAL CLOSET -0.779 SUBWAY LEVEL 167.39 2.30 385.00 M006-GDB-ARC-DWG-YWST020-SW-54331
10 ELECTRICAL CLOSET -0.780 SUBWAY LEVEL 2.60 2.30 5.98 M006-GDB-ARC-DWG-YWST020-ZZ-54340
11 ELECTRICAL CLOSET -0.781 SUBWAY LEVEL 3.44 5.70 19.62 M006-GDB-ARC-DWG-YWST020-SW-35296
12 ELECTRICAL CLOSET -0.782 SUBWAY LEVEL 24.54 2.30 56.44 M006-GDB-ARC-DWG-YWST020-SW-35292
13 STATION CONTROL ROOM -1.580 CONCOURSE LEVEL 43.26 4.00 173.04 M006-GDB-ARC-DWG-YWST020-CL-35304
14 MCC -1.713 CONCOURSE LEVEL 37.78 5.80 219.12 M006-GDB-ARC-DWG-YWST020-CL-35301
15 MCC -1.714 CONCOURSE LEVEL 32.06 5.80 185.95 M006-GDB-ARC-DWG-YWST020-CL-35304
16 ELECTRICAL ROOM -1.760 CONCOURSE LEVEL 40.28 3.90 157.09 M006-GDB-ARC-DWG-YWST020-CL-35305
17 TEL/IT ROOM -1.768 CONCOURSE LEVEL 22.55 5.80 130.79 M006-GDB-ARC-DWG-YWST020-CL-35307
18 ELECTRICAL ROOM -1.771 CONCOURSE LEVEL 27.30 6.10 166.53 M006-GDB-ARC-DWG-YWST020-CL-35302
19 ELECTRICAL ROOM -1.772 CONCOURSE LEVEL 28.50 6.10 173.85 M006-GDB-ARC-DWG-YWST020-CL-35307
20 ELECTRICAL ROOM -1.773 CONCOURSE LEVEL 35.30 6.10 215.33 M006-GDB-ARC-DWG-YWST020-CL-35307
21 ELECTRICAL ROOM -1.774 CONCOURSE LEVEL 19.80 6.10 120.78 M006-GDB-ARC-DWG-YWST020-CL-35301
22 ELECTRICAL ROOM -1.775 CONCOURSE LEVEL 24.20 6.10 147.62 M006-GDB-ARC-DWG-YWST020-CL-35305
23 ELECTRICAL ROOM -1.776 CONCOURSE LEVEL 31.80 6.10 193.98 M006-GDB-ARC-DWG-YWST020-CL-35305
24 ELECTRICAL CLOSET -1.777 CONCOURSE LEVEL 8.40 2.30 19.32 M006-GDB-ARC-DWG-YWST020-CL-54336
25 TELECOM SECURITY QAF -1.790 CONCOURSE LEVEL 15.60 5.80 90.48 M006-GDB-ARC-DWG-YWST020-CL-35304
26 TEL/IT MAIN ROOM -1.791 CONCOURSE LEVEL 50.30 5.80 291.74 M006-GDB-ARC-DWG-YWST020-CL-35307
27 TEL/IT ROOM -1.793 CONCOURSE LEVEL 24.50 5.80 142.10 M006-GDB-ARC-DWG-YWST020-CL-35305
28 TEL/IT ROOM -1.794 CONCOURSE LEVEL 16.20 5.80 93.96 M006-GDB-ARC-DWG-YWST020-CL-35301
29 TELECOM THIRD PARTIES -1.795 CONCOURSE LEVEL 32.70 5.80 189.66 M006-GDB-ARC-DWG-YWST020-CL-35304
30 TELECOM SAFETY POLICE -1.796 CONCOURSE LEVEL 15.80 5.80 91.64 M006-GDB-ARC-DWG-YWST020-CL-35304
31 AC/DC/SCADA ROOM + -2.711 & GOLDLINE PLATFORM OR 107.60 6.30 677.88 M006-GDB-ARC-DWG-YWST020-ZZ-35314
SPS MV/LV Room -2.713 INTERMEDIATE LEVEL

32 SIGNALLING ROOM -2.712 GOLDLINE PLATFORM OR 57.80 6.00 346.80 M006-GDB-ARC-DWG-YWST020-ZZ-35314/17


INTERMEDIATE LEVEL

33 UPS/BATTERY ROOM -2.714 GOLDLINE PLATFORM OR 39.50 6.30 248.85 M006-GDB-ARC-DWG-YWST020-ZZ-35314


INTERMEDIATE LEVEL

34 ELECTRICAL ROOM -2.773 GOLDLINE PLATFORM OR 55.00 6.30 346.50 M006-GDB-ARC-DWG-YWST020-ZZ-35317


INTERMEDIATE LEVEL

35 ELECTRICAL ROOM -2.775 GOLDLINE PLATFORM OR 17.40 6.30 109.62 M006-GDB-ARC-DWG-YWST020-ZZ-35315


INTERMEDIATE LEVEL

36 ELECTRICAL ROOM -2.776 GOLDLINE PLATFORM OR 47.80 6.30 301.14 M006-GDB-ARC-DWG-YWST020-ZZ-35317


INTERMEDIATE LEVEL

37 TEL/IT ROOM -2.782 GOLDLINE PLATFORM OR 32.00 6.00 192.00 M006-GDB-ARC-DWG-YWST020-ZZ-35315


INTERMEDIATE LEVEL

38 TEL/IT ROOM -2.783 GOLDLINE PLATFORM OR 15.10 6.00 90.60 M006-GDB-ARC-DWG-YWST020-ZZ-35317


INTERMEDIATE LEVEL

39 ELECTRICAL CLOSET -2.786 GOLDLINE PLATFORM OR 17.00 6.00 102.00 M006-GDB-ARC-DWG-YWST020-ZZ-35316


INTERMEDIATE LEVEL

40 ELECTRICAL ROOM -2.791 GOLDLINE PLATFORM OR 45.40 6.30 286.02 M006-GDB-ARC-DWG-YWST020-ZZ-35316


INTERMEDIATE LEVEL

41 ELECTRICAL ROOM -2.792 GOLDLINE PLATFORM OR 33.40 6.30 210.42 M006-GDB-ARC-DWG-YWST020-ZZ-35316


INTERMEDIATE LEVEL
GAS SUPPRESSION SYSTEM CYLINDER LOCATIONS - AL SADD C RING Station (As on 22.10.2016)

Room Tag Area Height Volume


S. No. Name No. Room Level Architectural Reference
(m2) (m) (m3)

42 ELECTRICAL CLOSET -2.798 GOLDLINE PLATFORM OR 18.00 12.20 219.60 M006-GDB-ARC-DWG-YWST020-ZZ-35318


INTERMEDIATE LEVEL

43 ELECTRICAL CLOSET -2.799 GOLDLINE PLATFORM OR 18.60 2.30 42.78 M006-GDB-ARC-DWG-YWST020-ZZ-54385


INTERMEDIATE LEVEL

44 DC TPS SUBSTATION -3.710 GOLDLINE UNDERPLATFORM LEVEL 256.61 8.20 2,104.17 M006-GDB-ARC-DWG-YWST020-ZZ-35324

45 AC/DC SCADA ROOM + SPS MV/LV -3.711 + - GOLDLINE UNDERPLATFORM LEVEL 139.10 4.80 667.68 M006-GDB-ARC-DWG-YWST020-ZZ-35321
ROOM 3.717

46 ELECTRICAL ROOM -3.713 GOLDLINE UNDERPLATFORM LEVEL 12.50 2.40 30.00 M006-GDB-ARC-DWG-YWST020-ZZ-35324

47 ELECTRICAL ROOM -3.720 GOLDLINE UNDERPLATFORM LEVEL 21.40 4.70 100.58 M006-GDB-ARC-DWG-YWST020-ZZ-35321

48 TEL/IT ROOM -3.723 GOLDLINE UNDERPLATFORM LEVEL 15.20 7.30 110.96 M006-GDB-ARC-DWG-YWST020-ZZ-35321

49 ELECTRICAL ROOM -4.757 INTERMEDIATE TRANSFER LEVEL 33.80 5.90 199.42 M006-GDB-ARC-DWG-YWST020-ZZ-35324 &
M006-GDB-ARC-DWG-YWST020-TX-35332
50 ELECTRICAL ROOM -4.758 INTERMEDIATE TRANSFER LEVEL 13.70 7.70 105.49 M006-GDB-ARC-DWG-YWST020-TX-35334

51 ELECTRICAL ROOM -4.759 INTERMEDIATE TRANSFER LEVEL 24.50 5.90 144.55 M006-GDB-ARC-DWG-YWST020-TX-35335

52 MCC ROOM -4.760 INTERMEDIATE TRANSFER LEVEL 40.88 8.20 335.22 M006-GDB-ARC-DWG-YWST020-TX-35335

53 MCC ROOM -4.761 INTERMEDIATE TRANSFER LEVEL 36.58 8.20 299.96 M006-GDB-ARC-DWG-YWST020-ZZ-35325 - Rev
2/33
54 AC/DC SCADA ROOM -4.762 INTERMEDIATE TRANSFER LEVEL 38.63 8.50 328.36 M006-GDB-ARC-DWG-YWST020-TX-35335

55 UPS/BATTERY ROOM -4.763 INTERMEDIATE TRANSFER LEVEL 37.38 8.40 313.99 M006-GDB-ARC-DWG-YWST020-TX-35335

56 TEL/IT ROOM -4.764 INTERMEDIATE TRANSFER LEVEL 28.70 7.40 212.38 M006-GDB-ARC-DWG-YWST020-TX-35334

57 OPTIONAL TEL/IT ROOM -4.765 INTERMEDIATE TRANSFER LEVEL 18.30 8.20 150.06 M006-GDB-ARC-DWG-YWST020-TX-35335

58 TEL/IT ROOM -4.769 INTERMEDIATE TRANSFER LEVEL 15.53 8.20 127.35 M006-GDB-ARC-DWG-YWST020-TX-35335

59 ELECTRICAL CLOSET -4.774 INTERMEDIATE TRANSFER LEVEL 18.83 1.80 33.89 M006-GDB-ARC-DWG-YWST020-TX-35331

60 ELECTRICAL CLOSET -4.776 INTERMEDIATE TRANSFER LEVEL 12.53 2.30 28.82 M006-GDB-ARC-DWG-YWST020-TX-35334

61 ELECTRICAL CLOSET -4.778 INTERMEDIATE TRANSFER LEVEL 12.49 1.80 22.48 M006-GDB-ARC-DWG-YWST020-TX-35334/
M006-GDB-ARC-DWG-YWST020-ZZ-54373

62 SIGNALLING ROOM -5.746 INTERMEDIATE TRANSFER LEVEL 42.36 5.80 245.69 M006-GDB-ARC-DWG-YWST020-PL-35343

63 AC/DC/SCADA ROOM -6.741 INTERMEDIATE TRANSFER LEVEL 39.37 5.20 204.72 M006-GDB-ARC-DWG-YWST020-UL-35345

64 DC TPS SUBSTATION -6.744 INTERMEDIATE TRANSFER LEVEL 250.86 7.30 1,831.28 M006-GDB-ARC-DWG-YWST020-UL-35348

65 ELECTRICAL ROOM -6.747 INTERMEDIATE TRANSFER LEVEL 26.26 8.90 233.71 M006-GDB-ARC-DWG-YWST020-UL-35348

66 ELECTRICAL ROOM -6.748 INTERMEDIATE TRANSFER LEVEL 28.96 7.90 228.78 M006-GDB-ARC-DWG-YWST020-UL-35345

67 SPS MV/LV ROOM -6.749 INTERMEDIATE TRANSFER LEVEL 53.10 4.60 244.26 M006-GDB-ARC-DWG-YWST020-UL-35348

68 SPS MV/LV ROOM -6.750 INTERMEDIATE TRANSFER LEVEL 58.93 5.20 306.44 M006-GDB-ARC-DWG-YWST020-UL-35345
GAS SUPPRESSION SYSTEM CYLINDER LOCATIONS - AL SADD C RING Station (As on 22.10.2016)

Room Tag Area Height Volume


S. No. Name No. Room Level Architectural Reference
(m2) (m) (m3)

69 TEL/IT ROOM -6.751 INTERMEDIATE TRANSFER LEVEL 17.54 5.20 91.21 M006-GDB-ARC-DWG-YWST020-UL-35345

70 UPS BATTERY ROOM -6.754 INTERMEDIATE TRANSFER LEVEL 35.00 5.20 182.00 M006-GDB-ARC-DWG-YWST020-UL-35345
GAS SUPPRESSION SYSTEN CYLINDER LOCATIONS - AL JOAAN STATION (As on 01.10.2016) - Rev. 02

Area Height Volume


S. No. Name Room Tag No. Room Level Architectural Drawing Reference No.
(sq.m.) (m) (cu.m.)

1 EMERGENCY PANEL ROOM 0.001 GRADE LEVEL 6.80 4.40 29.92 M006-GDB-ARC-DWG-YWST030-ZZ-37576

2 ELECTRICAL ROOM 0.041 GRADE LEVEL 131.20 4.10 537.92 M006-GDB-ARC-DWG-YWST030-ZZ-55288

3 UTILITY CHASE -1.021 CONCOURSE (SUBWAY) LEVEL 19.60 9.00 176.40 M006-GDB-ARC-DWG-YWST030-SW-37283

4 TEL/IT MAIN ROOM -1.035 CONCOURSE LEVEL 40.60 5.50 223.30 M006-GDB-ARC-DWG-YWST030-CL-37272

5 TELECOM ROOM QAF -1.037 CONCOURSE LEVEL 14.00 5.50 77.00 M006-GDB-ARC-DWG-YWST030-CL-37272

6 TELECOM SAFETY POLICE -1.038 CONCOURSE LEVEL 13.20 5.50 72.60 M006-GDB-ARC-DWG-YWST030-CL-37272

7 ELECTRICAL CLOSET -1.045 CONCOURSE LEVEL 3.30 2.00 6.60 M006-GDB-ARC-DWG-YWST030-CL-37272

8 TELECOM THIRD PARTIES -1.036 CONCOURSE LEVEL 33.90 5.40 183.06 M006-GDB-ARC-DWG-YWST030-CL-37270

9 TEL/IT ROOM -1.039 CONCOURSE LEVEL 17.60 5.50 96.80 M006-GDB-ARC-DWG-YWST030-CL-37270/71

10 ELECTRICAL ROOM -1.042 CONCOURSE LEVEL 14.20 5.50 78.10 M006-GDB-ARC-DWG-YWST030-CL-37270/71

11 ELECTRICAL ROOM -1.043 CONCOURSE LEVEL 28.20 5.50 155.10 M006-GDB-ARC-DWG-YWST030-CL-37272

12 ELECTRICAL ROOM -1.044 CONCOURSE LEVEL 34.40 5.50 189.20 M006-GDB-ARC-DWG-YWST030-CL-37270

13 TEL/IT ROOM -1.047 CONCOURSE LEVEL 17.60 5.50 96.80 M006-GDB-ARC-DWG-YWST030-CL-37272

M006-GDB-ARC-DWG-YWST030-ZZ-55288
14 UPS/BATTERY ROOM 2 -1.080 UPS Floor Level 71.02 3.00 213.06 (Currently not shown on area schedule drawing
AA-37256)

M006-GDB-ARC-DWG-YWST030-ZZ-55288
15 UPS BATTERY ROOM 1 -1.090 UPS Floor Level 34.53 3.00 103.59 (Currently not shown on area schedule drawing
AA-37256)

16 ELECTRICAL ROOM -1.095 CONCOURSE (SUBWAY) LEVEL 40.90 3.30 134.97 M006-GDB-ARC-DWG-YWST030-SW-37283

STATION CONTROL ROOM AND FIRE


17 -1.120 CONCOURSE LEVEL 35.40 2.80 99.12 M006-GDB-ARC-DWG-YWST030-CL-37272
COMMAND CENTRE

18 ESCALATOR CONTROL ROOM -1.145 CONCOURSE LEVEL 3.00 3.30 9.90 M006-GDB-ARC-DWG-YWST030-CL-37272

19 ELECTRICAL ROOM -1.400 CONCOURSE (SUBWAY) LEVEL 38.00 3.20 121.60 M006-GDB-ARC-DWG-YWST030-SW-37284

20 ESCALATOR CONTROL ROOM -1.404 CONCOURSE LEVEL 3.30 2.40 7.92 M006-GDB-ARC-DWG-YWST030-SW-37284

21 MCC 1 & 2 -2.054 INTERMEDIATE LEVEL 35.70 4.80 171.36 M006-GDB-ARC-DWG-YWST030-IL-37273

22 MCC 3 & 4 -2.055 INTERMEDIATE LEVEL 35.00 4.80 168.00 M006-GDB-ARC-DWG-YWST030-IL-37275

23 ELECTRICAL ROOM -2.062 INTERMEDIATE LEVEL 25.80 4.80 123.84 M006-GDB-ARC-DWG-YWST030-IL-37273

24 ELECTRICAL ROOM -2.063 INTERMEDIATE LEVEL 34.40 4.80 165.12 M006-GDB-ARC-DWG-YWST030-IL-37274

25 AC/DC/SCADA ROOM 1 -2.086 INTERMEDIATE LEVEL 82.00 4.90 401.80 M006-GDB-ARC-DWG-YWST030-IL-37273

26 SCADA ROOM 2 -2.088 INTERMEDIATE LEVEL 62.50 4.80 300.00 M006-GDB-ARC-DWG-YWST030-IL-37275

27 UPS BATTERY ROOM 2 -2.089 INTERMEDIATE LEVEL 24.50 4.50 110.25 M006-GDB-ARC-DWG-YWST030-IL-37275

28 TEL/IT ROOM -2.101 INTERMEDIATE LEVEL 25.80 4.90 126.42 M006-GDB-ARC-DWG-YWST030-IL-37273

29 TEL/IT ROOM -2.102 INTERMEDIATE LEVEL 15.70 4.80 75.36 M006-GDB-ARC-DWG-YWST030-IL-37274

30 ELECTRICAL ROOM -2.103 INTERMEDIATE LEVEL 25.40 4.80 121.92 M006-GDB-ARC-DWG-YWST030-IL-37273

31 ELECTRICAL ROOM -2.104 INTERMEDIATE LEVEL 13.20 4.80 63.36 M006-GDB-ARC-DWG-YWST030-IL-37274

32 ELECTRICAL ROOM -2.160 INTERMEDIATE LEVEL 48.40 4.80 232.32 M006-GDB-ARC-DWG-YWST030-IL-37274

33 ELECTRICAL ROOM -2.162 INTERMEDIATE LEVEL 28.40 4.80 136.32 M006-GDB-ARC-DWG-YWST030-IL-37273

34 SPS MV/LV ROOM 1 -3.068 PLATFORM LEVEL 58.70 6.10 358.07 M006-GDB-ARC-DWG-YWST030-PL-37278

35 SPS MV/LV ROOM 2 -3.069 PLATFORM LEVEL 50.80 6.10 309.88 M006-GDB-ARC-DWG-YWST030-PL-37276

36 ELECTRICAL ROOM -3.083 PLATFORM LEVEL 32.50 2.90 94.25 M006-GDB-ARC-DWG-YWST030-PL-37278

37 SIGNALLING ROOM -3.090 PLATFORM LEVEL 40.00 6.10 244.00 M006-GDB-ARC-DWG-YWST030-PL-37278

38 TEL/IT ROOM -3.092 PLATFORM LEVEL 12.40 6.30 78.12 M006-GDB-ARC-DWG-YWST030-PL-37278

39 ELECTRICAL ROOM -4.068 UNDER PLATFORM LEVEL 37.90 3.20 121.28 M006-GDB-ARC-DWG-YWST030-UL-37281

40 CABLE DRAW -4.077 UNDER PLATFORM LEVEL 56.80 2.60 147.68 M006-GDB-ARC-DWG-YWST030-UL-37281

41 ELECTRICAL ROOM -4.082 UNDER PLATFORM LEVEL 37.70 3.20 120.64 M006-GDB-ARC-DWG-YWST030-UL-37279

42 TPS -4.093 UNDER PLATFORM LEVEL 248.20 6.60 1,638.12 M006-GDB-ARC-DWG-YWST030-UL-37279

43 CABLE DRAW -4.154 UNDER PLATFORM LEVEL 83.50 3.20 267.20 M006-GDB-ARC-DWG-YWST030-UL-37279
GAS SUPPRESSION SYSTEN CYLINDER LOCATIONS - AL JOAAN STATION (As on 01.10.2016) - Rev. 02

Area Height Volume


S. No. Name Room Tag No. Room Level Architectural Drawing Reference No.
(sq.m.) (m) (cu.m.)

44 IT ROOM -4.163 UNDER PLATFORM LEVEL 12.90 3.50 45.15 M006-GDB-ARC-DWG-YWST030-UL-37280

45 IT ROOM -4.167 UNDER PLATFORM LEVEL 21.80 3.30 71.94 M006-GDB-ARC-DWG-YWST030-UL-37281


PROJECT: 3367- DAB
TITLE: 4522 AHUs & IDU Condensate Drain calculations Date:- 12/12/2020

Resultant DB temp Condensate


Off coil (Taken
Supply Air on coil (Taken Taken from McQuay - Psychrometric Density of air Specific Drain for 1 Latent load
Outdoor Air Cooling Capacity from eroclima Difference Condensate Flow
Flow from eroclima Analyser (Specific Humidity) @ off coil vloume kW of latent contribution
AHUs selection
S no Equipment Ref. AHUs selection load
Off coil
On coil
(m3/s) (m3/s) TCL (kW) SCL (kW) LCL (kW) DB (°C) WB (°C) DB (°C) WB (°C) (kg water/kg dry ΔѠ Kg/m3 m3/Kg (Kg/hr.) (Kg/hr.) %
(kg water/kg dry air)
air)

1 GF -IDU AHU ROOM 0.000 0.180 3.5 2.9 0.60 26.0 17.8 12.9 11.6 0.009300 0.008010 0.001290 1.219512 0.82000 1.0194 1.70 17.14%

2 FF-QESC 0.000 0.608 9.3 9.0 0.30 26.0 17.0 13.7 12.3 0.008450 0.008290 0.000160 1.215067 0.82300 0.4255 1.42 3.23%

3 GF-ELEC 0.000 0.332 4.7 4.4 0.30 25.7 17.6 14.6 13.3 0.009260 0.009000 0.000260 1.209190 0.82700 0.3758 1.25 6.38%

4 RESTRICTED SER 0.158 4.190 24.1 23.5 0.60 21.4 14.5 10.6 9.9 0.007430 0.007320 0.000110 1.230012 0.81300 2.0409 3.40 2.49%

5 SECURE SERVER 0.126 0.963 13.1 12.6 0.50 21.1 14.3 10.2 9.6 0.007340 0.007170 0.000170 1.231527 0.81200 0.7258 1.45 3.82%

6 FF-QESC 0.000 0.620 9.5 9.2 0.30 26.0 17.0 13.7 12.3 0.008440 0.008290 0.000150 1.215067 0.82300 0.4068 1.36 3.16%

7 FF-ELEC 0.000 0.319 4.6 4.4 0.20 26.0 17.7 14.6 13.3 0.009190 0.008940 0.000250 1.209190 0.82700 0.3472 1.74 4.35%

8 FF-SATE 0.000 1.168 15.5 15.2 0.30 21.4 14.5 10.6 9.9 0.007440 0.007330 0.000110 1.230012 0.81300 0.5689 1.90 1.94%

9 FF -PACKAGE UNIT 0.736 4.660 123.2 84.0 39.20 27.5 19.8 12.5 11.9 0.011260 0.008410 0.002850 1.221001 0.81900 58.3780 1.49 31.82%

10 FF -PACKAGE UNIT 0.627 4.782 118.8 81.9 36.90 27.1 19.7 12.9 12.3 0.011280 0.008660 0.002620 1.218027 0.82100 54.9377 1.49 31.06%

11 GF-AHU 1.683 5.604 189.9 117.4 72.50 30.2 21.8 12.8 12.2 0.012980 0.008580 0.004400 1.218027 0.82100 108.1210 1.49 38.18%

Recommended factor
Condensate drain (Kg/hr) per 1
kW of latent load
S no Equipment
Max Min Mean

SERVER ROOM
1 3.401 1.253 1.776
(IDU)

2 AHU & PACU 1.491 1.489 1.490

Desnsity of air 1.2 to 1.17 KG/M3


2.7 FAN COIL UNITS - Bin Mahmoud SPECIFIED PROPOSED

Cooling CHW Tot. CHW


External Cooling Capacity Specific Humidity
Room Indicative Air External Static Capacity Flow Flow Elec. Power Room Air Flow Off coil CHW
Room Served Unit Type Trane Proposed FCU Dimensions Static
Temp Flow Rate Pressure Input Temp Rate Temp Flow
Sr. No. Level Unit Reference No. Qty Latent/ Pressure
Total Sens. Rate Rate Total Sensible Latent Diffrence Condensate Flow Condensate Drian for 1 kW of latent load
Unit On Coil Off coil Density of air @ off coil
(kg water/kg dry air) (kg water/kg dry air) Kg/m3
Name Rm No. (°C ) (L/s) (Pa) (kW) (kW) (kW) (L/s) (L/s) (kW) Sel. Ref. Model Length Width Height (°C ) (L/s) °C (Pa) (kW) Total (kW) Total Total (L/s) Total ΔѠ (Kg/hr) (Kg/hr)

Ceiling Suspended-
1 AT GRADE FCU-AG-01 1 FAN PRESSURISATION ROOM 0.876 24 303 Free Discharge 4.6 3.63 1.0 0.20 0.20 0.363 FCU-BM-E-08 HFXF-10 1349 748 409 24 398.1 15.9 0 5.7 5.7 3.7 3.7 2.0 0.2 0.24 0.011896 0.011022 0.000874 0.81883 0.781 0.805
Exposed Type

Ceiling Suspended-
2 AT GRADE FCU-AG-02 1 FAN PRESSURISATION ROOM 0.888 24 330 Free Discharge 5.5 3.96 1.5 0.23 0.23 0.363 FCU-BM-E-09 HFXF-10 1902 545 255 24 389.8 14.1 0 6.6 6.6 4.5 4.5 2.2 0.3 0.28 0.011896 0.009608 0.002288 0.81704 2.221 1.442
Exposed Type
Ceiling Suspended-
3 AT GRADE FCU-AG-03,04 & 05 3 UPS 1.713 24 477 Free Discharge 10.2 5.72 4.5 0.44 1.32 0.61 FCU-BM-E-12 HCCA-10 (S) 1349 748 409 24 452.0 11.5 0 10.13 30.4 6.95 20.9 9.5 0.430 1.29 0.011896 0.009608 0.002288 0.81704 3.210 0.717
Exposed Type
Ceiling Suspended-
4 AT GRADE FCU-AG-06 & 07 2 UPS 1.712 24 651 Free Discharge 13.3 7.81 5.5 0.57 1.14 0.72 FCU-BM-E-16C HCCA-14 (S) 1208 748 416 24 618 10.0 0 15.040 30.1 10.620 21.2 8.8 0.640 1.28 0.011896 0.0074 0.004496 0.81171 8.553 1.558
Exposed Type
Ceiling Suspended-
5 AT GRADE FCU-AG-08,09 & 10 3 MCC--(C.B.S) 1.710 24 743 Free Discharge 14.3 8.91 5.4 0.61 1.83 1.116 FCU-BM-E-16C HCCA-14 (S) 1208 748 416 24 618 10.0 0 15.040 45.1 10.620 31.9 13.3 0.640 1.92 0.011896 0.0074 0.004496 0.81171 9.762 1.811
Exposed Type
Ceiling Suspended-
6 AT GRADE FCU-AG-11 1 STORE ROOM 1.716 24 110 Free Discharge 3.9 1.32 2.6 0.16 0.16 0.157 FCU-BM-E-06 HFXF-06 1372 545 255 24 232 13.3 0 4.800 4.8 2.880 2.9 1.9 0.200 0.20 0.011896 0.009292 0.002604 0.82246 0.848 0.329
Exposed Type
Ceiling Suspended-
7 AT GRADE FCU-AG-12 1 HVAC ROOM 1.717 24 339 Free Discharge 6.9 4.07 2.8 0.30 0.30 0.467 FCU-BM-E-10 HCCA-10 (S) 1349 748 409 24 378 14.1 0 7.980 8.0 5.080 5.1 2.9 0.340 0.34 0.011896 0.009608 0.002288 0.81704 2.281 0.806
Exposed
Ceiling Suspended-
8 AT GRADE FCU-AG-13 1 CHILLED WATER PUMP ROOM 1.711 24 633 Free Discharge 13.6 7.59 6.0 0.58 0.58 0.72 FCU-BM-E-16C HCCA-14 (S) 1208 748 416 24 618 10.0 0 15.040 15.0 10.620 10.6 4.4 0.640 0.64 0.011896 0.0074 0.004496 0.81171 8.316 1.384
Exposed Type
CUSTOMER SERVICE/TVM Ceiling Suspended-
9 CONCOURSE FCU-CL-01 1 -1.171 24 880 75 12.2 10.56 1.6 0.52 0.52 0.72 FCU-BM-D-08 HCCA-18 1624 799 448 24 728 10.6 75 12.920 12.9 11.950 12.0 1.0 0.550 0.55 0.011896 0.0074 0.004496 0.81171 11.561 7.050
ROOM Concealed Type
Ceiling Suspended-
10 CONCOURSE FCU-CL-02 1 FEMALE ABLUTION ROOM -1.272 24 110 75 3.3 1.32 2.0 0.14 0.14 0.142 FCU-BM-D-04 HFCF-06 1153 520 277 24 154 12.9 75 3.350 3.4 1.980 2.0 1.4 0.140 0.14 0.011896 0.009045 0.002851 0.82246 0.929 0.469
Concealed Type
Ceiling Suspended-
11 CONCOURSE FCU-CL-03 1 FEMALE PRAYER ROOM -1.273 24 367 75 8.8 4.4 4.4 0.38 0.38 0.467 FCU-BM-D-07 HCCA-14 1349 748 409 24 571 13.5 75 8.880 8.9 8.080 8.1 0.8 0.380 0.38 0.011896 0.009292 0.002604 0.82246 2.830 0.643
Concealed Type

12 FEMALE PUBLIC TOILET -1.274 3.6 0.011896 0.008521 0.003375 0.81883 3.194 0.887
Ceiling Suspended-
CONCOURSE FCU-CL-04 1 24 321 75 7.5 3.9 0.32 0.32 0.47 FCU-BM-D-06 HFCF-10 1543 520 277 24 283 12 75 7.640 7.6 3.930 3.9 3.7 0.330 0.33
Concealed Type
13 FEMALE DISABLED TOILET -1.271 0.0

Ceiling Suspended-
14 CONCOURSE FCU-CL-05 1 MALE ABLUTION ROOM -1.275 24 110 75 3.3 1.32 2.0 0.14 0.14 0.142 FCU-BM-D-04 HFCF-06 1153 520 277 24 154 12.9 75 3.350 3.4 1.980 2.0 1.4 0.140 0.14 0.011896 0.009045 0.002851 0.82246 0.929 0.469
Concealed Type
Ceiling Suspended-
15 CONCOURSE FCU-CL-06 1 MALE PRAYER ROOM -1.276 24 367 75 8.9 4.4 4.5 0.38 0.38 0.61 FCU-BM-D-07 HCCA-14 1349 748 409 24 571 13.5 75 8.880 8.9 8.080 8.1 0.8 0.380 0.38 0.011896 0.009292 0.002604 0.82246 2.830 0.629
Concealed Type

16 MALE PUBLIC TOILET -1.277 3.9 0.011896 0.008521 0.003375 0.81883 2.915 0.747
Ceiling Suspended-
CONCOURSE FCU-CL-07 1 24 293 75 7.4 3.5 0.31 0.31 0.47 FCU-BM-D-06 HFCF-10 1543 520 277 24 283 12 75 7.640 7.6 3.930 3.9 3.7 0.330 0.33
Concealed Type
17 MALE DISABLED TOILET -1.270 0.0

Ceiling Suspended-
18 CONCOURSE FCU-CL-88 1 GOLD CARD CENTRE -1.372 24 257 75 5.4 3.08 2.3 0.23 0.23 0.363 FCU-BM-D-06 HFCF-10 1543 520 277 24 283 12.1 75 7.640 7.6 3.930 3.9 3.7 0.330 0.33 0.011896 0.008521 0.003375 0.81883 2.557 1.102
Concealed Type
FEMALE STAFF MESS & Ceiling Suspended-
19 CONCOURSE FCU-CL-08 1 -1.570 24 183 75 4.6 2.2 2.4 0.20 0.20 0.363 FCU-BM-D-05 HFCF-08 1423 520 277 24 227 13.4 75 4.7 4.7 2.8 2.8 1.9 0.2 0.20 0.011896 0.009292 0.002604 0.82246 1.411 0.588
LOCKER ROOM Concealed Type
Ceiling Suspended-
20 CONCOURSE FCU-CL-09 1 FEMALE STAFF RESTROOM -1.571 24 92 75 2.2 1.1 1.1 0.09 0.09 0.142 FCU-BM-D-03 HFCF-04 898 520 277 24 102 13.1 75 2.2 2.2 1.3 1.3 1.0 0.1 0.10 0.011896 0.009045 0.002851 0.82246 0.777 0.706
Concealed Type
Ceiling Suspended-
21 CONCOURSE FCU-CL-10 1 FIRST AID ROOM -1.572 24 92 75 1.4 1.1 0.3 0.06 0.06 0.1 FCU-BM-D-01 HFCF-04 898 520 277 24 102 15.9 75 1.58 1.6 1.33 1.3 0.3 0.07 0.07 0.011896 0.011022 0.000874 0.83368 0.241 0.804
Concealed Type
GARBAGE COLLECTION Ceiling Suspended-
22 CONCOURSE FCU-CL-11 1 -1.573 24 55 Free Discharge 1.4 0.66 0.7 0.06 0.06 0.1 FCU-BM-E-01 HFXF-02 867 545 255 24 81 15.9 0 1.520 1.5 1.000 1.0 0.5 0.060 0.06 0.011896 0.011022 0.000874 0.83368 0.144 0.195
ROOM Exposed Type
MALE STAFF MESS & LOCKER Ceiling Suspended-
23 CONCOURSE FCU-CL-12 1 -1.574 24 174 75 4.6 2.09 2.5 0.20 0.20 0.363 FCU-BM-D-05 HFCF-08 1423 520 277 24 227 13.4 75 4.7 4.7 2.8 2.8 1.9 0.2 0.20 0.011896 0.009292 0.002604 0.83368 1.360 0.542
ROOM Concealed Type
Ceiling Suspended-
24 CONCOURSE FCU-CL-13 1 MALE STAFF RESTROOM -1.575 24 92 75 2.2 1.1 1.1 0.09 0.09 0.142 FCU-BM-D-03 HFCF-04 898 520 277 24 102 13.1 75 2.2 2.2 1.3 1.3 1.0 0.1 0.10 0.011896 0.009045 0.002851 0.82246 0.777 0.706
Concealed Type
Ceiling Suspended-
25 CONCOURSE FCU-CL-14 1 POLICE BOOTH -1.576 24 156 75 2.5 1.87 0.6 0.11 0.11 0.142 FCU-BM-D-04 HFCF-06 1153 520 277 24 154 12.9 75 3.350 3.4 1.980 2.0 1.4 0.140 0.14 0.011896 0.009045 0.002851 0.82246 1.317 2.090
Concealed Type
Ceiling Suspended-
26 CONCOURSE FCU-CL-15 1 QAF ROOM -1.577 24 101 75 1.7 1.21 0.5 0.07 0.07 0.1 FCU-BM-D-02 HFCF-04 898 520 277 24 102 13.4 75 1.7 1.7 1.3 1.3 0.4 0.1 0.07 0.011896 0.009292 0.002604 0.82246 0.779 1.589
Concealed Type
Ceiling Suspended-
27 CONCOURSE FCU-CL-16 1 STORE ROOM -1.670 24 28 Free Discharge 1.1 0.33 0.8 0.05 0.05 0.1 FCU-BM-E-01 HFXF-02 867 545 255 24 81 15.9 0 1.520 1.5 1.000 1.0 0.5 0.060 0.06 0.011896 0.011022 0.000874 0.83368 0.073 0.095
Exposed Type
STATION CONTROL ROOM Ceiling Suspended-
28 CONCOURSE FCU-CL-17 1 -1.671 24 1412 75 18.5 16.94 1.6 0.79 0.79 1.6 FCU-BM-D-09 HCCA-24 2074 799 448 24 890 9.0 75 18.940 18.9 16.320 16.3 2.6 0.810 0.81 0.011896 0.006914 0.004982 0.80822 20.468 13.120
/FIRE COMMAND CENTRE Concealed Type
Ceiling Suspended-
29 CONCOURSE FCU-CL-19 1 CLEANER'S ROOM -1.672 24 55 Free Discharge 1.1 0.66 0.4 0.05 0.05 0.1 FCU-BM-E-01 HFXF-02 867 545 255 24 81 15.9 0 1.520 1.5 1.000 1.0 0.5 0.060 0.06 0.011896 0.011022 0.000874 0.83368 0.144 0.328
Exposed Type
Ceiling Suspended-
30 CONCOURSE FCU-CL-20 1 STORE ROOM -1.673 24 92 Free Discharge 1.5 1.1 0.4 0.07 0.07 0.1 FCU-BM-E-02 HFXF-03 1102 545 255 24 124 15.2 0 1.520 1.5 1.270 1.3 0.3 0.060 0.06 0.011896 0.010328 0.001568 0.82989 0.431 1.077
Exposed Type
Ceiling Suspended-
31 CONCOURSE FCU-CL-21 1 STORE ROOM -1.675 24 37 Free Discharge 1.1 0.44 0.7 0.05 0.05 0.1 FCU-BM-E-01 HFXF-02 867 545 255 24 81 15.9 0 1.520 1.5 1.000 1.0 0.5 0.060 0.06 0.011896 0.011022 0.000874 0.83368 0.097 0.147
Exposed Type

Ceiling Suspended-
32 CONCOURSE FCU-CL-22,23 & 24 3 HVAC ROOM -1.710 24 376 Free Discharge 9.8 4.51 5.3 0.42 1.26 0.61 FCU-BM-E-12 HCCA-10 (S) 1349 748 409 24 452.0 11.5 0 10.13 30.4 6.95 20.9 9.5 0.430 1.29 0.011896 0.0081704 0.0037256 0.81704 4.120 0.779
Exposed Type

Ceiling Suspended-
33 CONCOURSE FCU-CL-25 1 TEL/IT ROOM -1.711 24 752 Free Discharge 10.6 9.02 1.6 0.45 0.45 0.61 FCU-BM-E-15 HCCA-14 (S) 1208 748 416 24 625 11.2 0 12.100 12.1 9.800 9.8 2.3 0.510 0.51 0.011896 0.0081704 0.0037256 0.81704 8.241 5.216
Exposed Type
Ceiling Suspended-
34 CONCOURSE FCU-CL-26 1 ELECTRICAL ROOM -1.713 28 26 Free Discharge 1.4 0.44 1.0 0.06 0.06 0.1 FCU-BM-E-19 HFXF-02 867 545 255 24 81 13.4 0 2.000 2.0 1.370 1.4 0.6 0.090 0.09 0.011896 0.009292 0.002604 0.81704 0.199 0.207
Exposed Type
Ceiling Suspended-
35 CONCOURSE FCU-CL-27 1 ELECTRICAL ROOM -1.714 28 262 Free Discharge 13.1 4.4 8.7 0.56 0.56 0.72 FCU-BM-E-22 HCCA-10 (S) 1349 748 409 28 452 15.0 0 13.220 13.2 9.050 9.1 4.2 0.560 0.56 0.011896 0.010328 0.001568 0.82989 1.227 0.141
Exposed Type
Ceiling Suspended-
36 CONCOURSE FCU-CL-28 & 29 2 AC/DC/SCADA ROOM -1.716 24 743 Free Discharge 10.3 8.91 1.4 0.44 0.88 0.61 FCU-BM-E-15 HCCA-14 (S) 1208 748 416 24 625 11.2 0 12.100 24.2 9.800 19.6 4.6 0.510 1.02 0.011896 0.0081704 0.0037256 0.81704 8.142 5.858
Exposed Type
Ceiling Suspended-
37 CONCOURSE FCU-CL-30 1 ELECTRICAL ROOM -1.719 28 118 Free Discharge 3.2 1.98 1.2 0.14 0.14 0.142 FCU-BM-E-20 HFXF-03 1102 545 255 24 119 13.4 0 3.230 3.2 2.100 2.1 1.1 0.140 0.14 0.011896 0.009292 0.002604 0.81704 0.904 0.741
Exposed Type
Ceiling Suspended-
38 CONCOURSE FCU-CL-31 & 89 2 ELECTRICAL ROOM -1.720 28 196 Free Discharge 9.1 3.3 5.8 0.39 0.78 0.61 FCU-BM-E-21 HCCA-10 (S) 1349 748 409 24 452 14.8 0 9.340 18.7 7.020 14.0 4.6 0.400 0.80 0.011896 0.010328 0.001568 0.82989 0.918 0.158
Exposed Type
Ceiling Suspended-
39 CONCOURSE FCU-CL-32 1 ELECTRICAL ROOM -1.721 28 170 Free Discharge 8.0 2.86 5.1 0.34 0.34 0.467 FCU-BM-E-21 HCCA-10 (S) 1349 748 409 24 452 14.8 0 9.340 9.3 7.020 7.0 2.3 0.400 0.40 0.011896 0.010328 0.001568 0.82989 0.796 0.155
Exposed Type
Ceiling Suspended-
40 CONCOURSE FCU-CL-33 & 90 2 ELECTRICAL ROOM -1.724 28 213 Free Discharge 9.3 3.58 5.7 0.40 0.80 0.61 FCU-BM-E-21 HCCA-10 (S) 1349 748 409 24 452 14.8 0 9.340 18.7 7.020 14.0 4.6 0.400 0.80 0.011896 0.010328 0.001568 0.82989 0.998 0.174
Exposed Type
Ceiling Suspended-
41 CONCOURSE FCU-CL-34 1 HVAC ROOM -1.725 24 284 Free Discharge 8.9 3.41 5.5 0.38 0.38 0.61 FCU-BM-E-12 HCCA-10 (S) 1349 748 409 24 452.0 11.5 0 10.13 10.1 6.95 7.0 3.2 0.430 0.43 0.011896 0.0081704 0.0037256 0.81704 3.112 0.567
Exposed Type
Ceiling Suspended-
42 CONCOURSE FCU-CL-35 1 HVAC ROOM -1.726 24 449 Free Discharge 12.7 5.39 7.3 0.54 0.54 0.721 FCU-BM-E-16C HCCA-14 (S) 1208 748 416 24 618 10.0 0 15.040 15.0 10.620 10.6 4.4 0.640 0.64 0.011896 0.0074 0.004496 0.81171 5.899 0.807
Exposed Type
Ceiling Suspended-
43 CONCOURSE FCU-CL-36 1 ELECTRICAL ROOM -1.731 28 190 Free Discharge 9.0 3.19 5.8 0.39 0.39 0.61 FCU-BM-E-21 HCCA-10 (S) 1349 748 409 24 452 14.8 0 9.340 9.3 7.020 7.0 2.3 0.400 0.40 0.011896 0.010328 0.001568 0.82989 0.890 0.153
Exposed Type
Ceiling Suspended-
44 CONCOURSE FCU-CL-37 1 TEL/IT ROOM -1.732 24 587 Free Discharge 8.5 7.04 1.5 0.36 0.36 0.467 FCU-BM-E-14 HCCA-14 (S) 1208 748 416 24 626 9.4 0 10.600 10.6 7.560 7.6 3.0 0.380 0.38 0.011896 0.006914 0.004982 0.80822 8.509 5.828
Exposed Type
Ceiling Suspended-
45 CONCOURSE FCU-CL-38 1 TELECOM SAFETY POLICE -1.733 24 92 Free Discharge 1.5 1.1 0.4 0.07 0.07 0.1 FCU-BM-E-02 HFXF-03 1102 545 255 24 124 15.2 0 1.520 1.5 1.270 1.3 0.3 0.060 0.06 0.011896 0.010328 0.001568 0.82989 0.431 1.077
Exposed Type
Ceiling Suspended-
46 CONCOURSE FCU-CL-39 1 TELECOM SECURITY QAF -1.734 24 119 Free Discharge 2.1 1.43 0.7 0.09 0.09 0.142 FCU-BM-E-03 HFXF-03 1102 545 255 24 119 12.4 0 2.110 2.1 1.590 1.6 0.5 0.090 0.09 0.011896 0.008521 0.003375 0.81883 1.184 1.767
Exposed Type
Ceiling Suspended-
47 CONCOURSE FCU-CL-40 & 41 2 TEL/IT THIRD PARTIES -1.735 24 568 Free Discharge 7.8 6.82 1.0 0.33 0.66 0.467 FCU-BM-E-13 HCCA-14 (S) 1208 748 416 24 627 11.6 0 10.600 21.2 7.560 15.1 6.1 0.380 0.76 0.011896 0.0081704 0.0037256 0.81704 6.224 6.351
Exposed Type
Ceiling Suspended-
48 CONCOURSE FCU-CL-42 & 43 2 TUNNEL AHU ROOM -1.736 24 367 Free Discharge 9.4 4.4 5.0 0.40 0.80 0.61 FCU-BM-E-12 HCCA-10 (S) 1349 748 409 24 452.0 11.5 0 10.13 20.3 6.95 13.9 6.4 0.430 0.86 0.011896 0.0081704 0.0037256 0.81704 4.022 0.804
Exposed Type
Ceiling Suspended-
49 CONCOURSE FCU-CL-44 & 45 2 TVF ROOM -1.737 24 312 Free Discharge 7.5 3.74 3.8 0.32 0.64 0.467 FCU-BM-E-10 HCCA-10 (S) 1349 748 409 24 378 14.1 0 7.980 16.0 5.080 10.2 5.8 0.340 0.68 0.011896 0.009608 0.002288 0.81704 2.100 0.558
Exposed Type
Ceiling Suspended-
50 CONCOURSE FCU-CL-46,47 & 48 3 TVF ROOM -1.738 24 464 Free Discharge 11.9 5.57 6.3 0.51 1.53 0.721 FCU-BM-E-16A HCCA-10 (S) 1208 748 416 24 447 10.0 0 11.650 35.0 7.940 23.8 11.1 0.470 1.41 0.011896 0.0074 0.004496 0.81171 6.096 0.963
Exposed Type

Ceiling Suspended-
51 CONCOURSE FCU-CL-49,50 & 51 3 MCC -1.739 24 880 Free Discharge 11.0 10.56 0.4 0.47 1.41 0.610 FCU-BM-E-16B HCCA-14 (S) 1208 748 416 24 618 10.0 0 14.090 42.3 10.690 32.1 10.2 0.600 1.80 0.011896 0.0074 0.004496 0.81171 11.561 26.276
Exposed Type

Ceiling Suspended-
52 CONCOURSE FCU-CL-52,53 & 54 3 MCC -1.740 24 898 Free Discharge 11.3 10.78 0.5 0.48 1.44 0.721 FCU-BM-E-17 HCCA-18 (S) 1624 799 448 24 772 11.2 0 13.18 39.5 11.98 35.9 3.6 0.48 1.44 0.011896 0.0081704 0.0037256 0.81704 9.841 18.924
Exposed Type

Ceiling Suspended-
53 CONCOURSE FCU-CL-55,56 & 57 3 MCC -1.741 24 990 Free Discharge 12.5 11.88 0.6 0.54 1.62 0.721 FCU-BM-E-17 HCCA-18 (S) 1624 799 448 24 772 11.2 0 13.180 39.5 11.980 35.9 3.6 0.480 1.44 0.011896 0.0081704 0.0037256 0.81704 10.849 17.498
Exposed Type

Ceiling Suspended-
54 CONCOURSE FCU-CL-58,59 & 60 3 TVF ROOM -1.743 24 400 Free Discharge 10.0 4.796 5.2 0.43 1.29 0.61 FCU-BM-E-12 HCCA-10 (S) 1349 748 409 24 452.0 11.5 0 10.13 30.4 6.95 20.9 9.5 0.430 1.29 0.011896 0.0081704 0.0037256 0.81704 4.383 0.842
Exposed Type

Ceiling Suspended-
55 CONCOURSE FCU-CL-61 1 UPS/BATTERY ROOM -1.744 24 642 Free Discharge 14.3 7.7 6.6 0.61 0.61 1.116 FCU-BM-E-16B HCCA-14 (S) 1208 748 416 24 618 10.0 0 14.090 14.1 10.690 10.7 3.4 0.600 0.60 0.011896 0.0074 0.004496 0.81171 8.435 1.278
Exposed Type
Ceiling Suspended-
56 CONCOURSE FCU-CL-62 1 REFUSE / RECYCLING ROOM -1.745 24 156 Free Discharge 5.0 1.87 3.1 0.21 0.21 0.363 FCU-BM-E-08 HFXF-10 1902 545 255 24 398 15.9 0 5.7 5.7 3.7 3.7 2.0 0.2 0.24 0.011896 0.011022 0.000874 0.83368 0.409 0.131
Exposed Type
Ceiling Suspended-
57 CONCOURSE FCU-CL-63 1 WASTE ROOM -1.746 24 138 Free Discharge 4.8 1.65 3.2 0.21 0.21 0.363 FCU-BM-E-06 HFXF-06 1372 545 255 24 232 13.3 0 4.800 4.8 2.880 2.9 1.9 0.200 0.20 0.011896 0.009292 0.002604 0.82246 1.064 0.338
Exposed Type
Ceiling Suspended-
58 CONCOURSE FCU-CL-64 & 65 2 HVAC ROOM -1.747 24 504 Free Discharge 11.6 6.05 5.6 0.49 0.98 0.721 FCU-BM-E-16A HCCA-10 (S) 1208 748 416 24 447 10.0 0 11.650 23.3 7.940 15.9 7.4 0.470 0.94 0.011896 0.0074 0.004496 0.81171 6.622 1.193
Exposed Type
Ceiling Suspended-
59 CONCOURSE FCU-CL-66 1 HVAC ROOM -1.748 24 578 Free Discharge 11.6 6.93 4.7 0.49 0.49 0.721 FCU-BM-E-16A HCCA-10 (S) 1208 748 416 24 447 10.0 0 11.650 11.7 7.940 7.9 3.7 0.470 0.47 0.011896 0.0074 0.004496 0.81171 7.594 1.626
Exposed Type
Ceiling Suspended-
60 CONCOURSE FCU-CL-67 1 HVAC ROOM -1.749 24 385 Free Discharge 9.4 4.62 4.8 0.40 0.40 0.61 FCU-BM-E-12 HCCA-10 (S) 1349 748 409 24 452.0 11.5 0 10.13 10.1 6.95 7.0 3.2 0.430 0.43 0.011896 0.0081704 0.0037256 0.81704 4.219 0.883
Exposed Type
Ceiling Suspended-
61 CONCOURSE FCU-CL-68 1 TEL/IT ROOM -1.750 24 605 Free Discharge 8.7 7.26 1.4 0.37 0.37 0.61 FCU-BM-E-14 HCCA-14 (S) 1208 748 416 24 626 9.4 0 10.600 10.6 7.560 7.6 3.0 0.380 0.38 0.011896 0.006914 0.004982 0.80822 8.770 6.090
Exposed Type
Ceiling Suspended-
62 CONCOURSE FCU-CL-69 1 TEL/IT ROOM -1.751 24 623 Free Discharge 8.6 7.48 1.1 0.37 0.37 0.61 FCU-BM-E-14 HCCA-14 (S) 1208 748 416 24 626 9.4 0 10.600 10.6 7.560 7.6 3.0 0.380 0.38 0.011896 0.006914 0.004982 0.80822 9.031 8.063
Exposed Type
Ceiling Suspended-
63 CONCOURSE FCU-CL-70 1 TEL/IT ROOM -1.752 24 605 Free Discharge 8.1 7.26 0.8 0.35 0.35 0.61 FCU-BM-E-14 HCCA-14 (S) 1208 748 416 24 626 9.4 0 10.600 10.6 7.560 7.6 3.0 0.380 0.38 0.011896 0.006914 0.004982 0.80822 8.770 10.440
Exposed Type
Ceiling Suspended-
64 CONCOURSE FCU-CL-71 & 72 2 TUNNEL AHU ROOM -1.755 24 394 Free Discharge 7.9 4.73 3.2 0.34 0.68 0.61 FCU-BM-E-10 HCCA-10 (S) 1349 748 409 24 378 14.1 0 7.980 16.0 5.080 10.2 5.8 0.340 0.68 0.011896 0.009608 0.002288 0.81704 2.652 0.836
Exposed Type
Ceiling Suspended-
65 CONCOURSE FCU-CL-73 & 74 2 TUNNEL AHU ROOM -1.756 24 550 Free Discharge 10.8 6.6 4.2 0.46 0.92 0.61 FCU-BM-E-15 HCCA-14 (S) 1208 748 416 24 625 11.2 0 12.100 24.2 9.800 19.6 4.6 0.510 1.02 0.011896 0.0081704 0.0037256 0.81704 6.027 1.435
Exposed Type
Ceiling Suspended-
66 CONCOURSE FCU-CL-75 1 HVAC ROOM -1.787 24 55 Free Discharge 2.0 0.66 1.3 0.08 0.08 0.1 FCU-BM-E-03 HFXF-03 1102 545 255 24 119 12.4 0 2.110 2.1 1.590 1.6 0.5 0.090 0.09 0.011896 0.008521 0.003375 0.81883 0.547 0.408
Exposed Type
Ceiling Suspended-
67 CONCOURSE FCU-CL-76 1 WATER WALL PUMP ROOM -1.788 24 46 Free Discharge 1.3 0.55 0.8 0.06 0.06 0.1 FCU-BM-E-01 HFXF-02 867 545 255 24 81 15.9 0 1.520 1.5 1.000 1.0 0.5 0.060 0.06 0.011896 0.011022 0.000874 0.83368 0.121 0.161
Exposed Type
Ceiling Suspended-
68 CONCOURSE FCU-CL-77 1 ZONE 3 CORRIDOR -1.810 24 413 Free Discharge 5.7 4.95 0.8 0.24 0.24 0.363 FCU-BM-E-10 HCCA-10 (S) 1349 748 409 24 378 14.1 0 7.980 8.0 5.080 5.1 2.9 0.340 0.34 0.011896 0.009608 0.002288 0.81704 2.779 3.706
Exposed Type
Ceiling Suspended-
69 CONCOURSE FCU-CL-78 1 ZONE 2 CORRIDOR -1.814 24 92 Free Discharge 1.4 1.1 0.3 0.06 0.06 0.1 FCU-BM-E-02 HFXF-03 1102 545 255 24 124 15.2 0 1.520 1.5 1.270 1.3 0.3 0.060 0.06 0.011896 0.010328 0.001568 0.82989 0.431 1.437
Exposed Type
Ceiling Suspended-
70 CONCOURSE FCU-CL-79 1 ZONE 2 CORRIDOR -1.815 24 128 Free Discharge 1.9 1.54 0.4 0.08 0.08 0.1 FCU-BM-E-03 HFXF-03 1102 545 255 24 119 12.4 0 2.110 2.1 1.590 1.6 0.5 0.090 0.09 0.011896 0.008521 0.003375 0.81883 1.273 3.537
Exposed Type
Ceiling Suspended-
71 CONCOURSE FCU-CL-80 & 81 2 ZONE 3 CORRIDOR -1.817 24 669 Free Discharge 8.5 8.03 0.5 0.36 0.72 0.467 FCU-BM-E-14A HCCA-14 (S) 1208 748 416 24 624 9.4 0 13.660 27.3 8.970 17.9 9.4 0.490 0.98 0.011896 0.006914 0.004982 0.80822 9.698 20.633
Exposed Type

72 ZONE 2 CORRIDOR -1.820 1.5 0.011896 0.009045 0.002851 0.82246 1.933 1.333
Ceiling Suspended-
CONCOURSE FCU-CL-82 1 24 229 Free Discharge 4.2 2.8 0.18 0.18 0.36 FCU-BM-E-06 HFXF-06 1372 545 255 24 232 13 0 4.800 4.8 2.880 2.9 1.9 0.200 0.20
Exposed Type
73 GSS -1.919 0.0

Ceiling Suspended-
74 CONCOURSE FCU-CL-83 1 ZONE 3 CORRIDOR -1.822 24 257 Free Discharge 3.4 3.08 0.3 0.15 0.15 0.142 FCU-BM-E-07 HFXF-08 1652 545 255 24 299 14.5 0 4.69 4.7 3.28 3.3 1.4 0.20 0.20 0.011896 0.00999 0.001906 0.82989 1.463 4.573
Exposed Type
Ceiling Suspended-
75 CONCOURSE FCU-CL-84 1 ZONE 3 CORRIDOR -1.831 24 183 Free Discharge 2.4 2.2 0.2 0.10 0.10 0.142 FCU-BM-E-06 HFXF-06 1372 545 255 24 232 13.3 0 4.800 4.8 2.880 2.9 1.9 0.200 0.20 0.011896 0.009292 0.002604 0.82246 1.411 7.055
Exposed Type
Ceiling Suspended-
76 CONCOURSE FCU-CL-85 1 GSS -1.910 24 138 Free Discharge 2.9 1.65 1.3 0.12 0.12 0.142 FCU-BM-E-05 HFXF-04 1202 545 255 24 154 13.3 0 2.920 2.9 1.910 1.9 1.0 0.120 0.12 0.011896 0.009292 0.002604 0.82246 1.064 0.851
Exposed Type
Ceiling Suspended-
77 CONCOURSE FCU-CL-86 1 GSS -1.911 24 156 Free Discharge 3.3 1.87 1.4 0.14 0.14 0.142 FCU-BM-E-06 HFXF-06 1372 545 255 24 232 13.3 0 4.800 4.8 2.880 2.9 1.9 0.200 0.20 0.011896 0.009292 0.002604 0.82246 1.203 0.841
Exposed Type
Ceiling Suspended-
78 CONCOURSE FCU-CL-87 1 MECHANICAL ROOM -0.773 24 128 Free Discharge 3.9 1.54 2.4 0.16 0.16 0.157 FCU-BM-E-06 HFXF-06 1372 545 255 24 232 13.3 0 4.800 4.8 2.880 2.9 1.9 0.200 0.20 0.011896 0.009292 0.002604 0.82246 0.987 0.418
Exposed Type
Ceiling Suspended-
79 PLATFORM FCU-PL-01 1 ELECTRICAL ROOM -2.721 24 142 Free Discharge 4.8 1.7 3.1 0.21 0.21 0.363 FCU-BM-E-06 HFXF-06 1372 545 255 24 232 13.3 0 4.800 4.8 2.880 2.9 1.9 0.200 0.20 0.011896 0.009292 0.002604 0.82246 1.095 0.353
Exposed Type

80 ZONE 3 CORRIDOR -2.820 0.6 0.011896 0.011022 0.000874 0.83368 0.191 0.348
Ceiling Suspended-
PLATFORM FCU-PL-02 1 24 73 Free Discharge 1.4 0.9 0.06 0.06 0.10 FCU-BM-E-01 HFXF-02 867 545 255 24 81 16 0 1.520 1.5 1.000 1.0 0.5 0.060 0.06
Exposed Type
81 GSS -2.902 0.0

Ceiling Suspended-
82 UNDER PLATFORM FCU-UL-04 1 ELECTRICAL ROOM -3.718 24 266 Free Discharge 4.8 3.19 1.6 0.21 0.21 0.363 FCU-BM-E-08 HFXF-10 1902 545 255 24 398 15.9 0 5.7 5.7 3.7 3.7 2.0 0.2 0.24 0.011896 0.011022 0.000874 0.83368 0.698 0.433
Exposed Type
Ceiling Suspended-
83 UNDER PLATFORM FCU-UL-24 1 TEL / IT ROOM (NEW) -3.933 24 504 Free Discharge 6.2 6.05 0.2 0.26 0.26 0.467 FCU-BM-E-11 HCCA-10 (S) 1349 748 409 24 452 13.9 0 7.56 7.6 6.92 6.9 0.6 0.27 0.27 0.011896 0.009608 0.002288 0.81704 3.392 22.612
Exposed Type
Ceiling Suspended-
84 UNDER PLATFORM FCU-UL-09 1 DEWATERING SUMP ROOM -3.733 28 85 Free Discharge 2.6 1.43 1.2 0.11 0.11 0.142 FCU-BM-E-20 HFXF-03 1102 545 255 24 119 13.4 0 3.230 3.2 2.100 2.1 1.1 0.140 0.14 0.011896 0.009292 0.002604 0.81704 0.651 0.556
Exposed Type
Ceiling Suspended-
85 UNDER PLATFORM FCU-UL-11 1 DEWATERING SUMP ROOM -3.731 28 79 Free Discharge 2.4 1.32 1.1 0.10 0.10 0.142 FCU-BM-E-20 HFXF-03 1102 545 255 24 119 13.4 0 3.230 3.2 2.100 2.1 1.1 0.140 0.14 0.011896 0.009292 0.002604 0.81704 0.605 0.560
Exposed Type
Ceiling Suspended-
86 UNDER PLATFORM FCU-UL-17 1 DEWATERING SUMP ROOM -3.732 28 46 Free Discharge 1.3 0.77 0.5 0.06 0.06 0.1 FCU-BM-E-18 HFXF-02 867 545 255 28 83 17.3 0 1.310 1.3 1.030 1.0 0.3 0.060 0.06 0.011896 0.009662 0.002234 0.81704 0.302 0.570
Exposed Type
Ceiling Suspended-
87 UNDER PLATFORM FCU-UL-05 1 ELECTRICAL ROOM -3.716 24 376 Free Discharge 6.4 4.51 1.9 0.27 0.27 0.467 FCU-BM-E-10 HCCA-10 (S) 1349 748 409 24 378 14.1 0 7.980 8.0 5.080 5.1 2.9 0.340 0.34 0.011896 0.009608 0.002288 0.81704 2.530 1.339
Exposed Type

88 ZONE 3 CORRIDOR 0.879 1.5 0.011896 0.008521 0.003375 0.81883 0.458 0.299
Ceiling Suspended-
UNDER PLATFORM FCU-UL-03 1 24 46 Free Discharge 2.3 0.8 0.10 0.10 0.14 FCU-BM-E-04 HFXF-03 1102 545 255 24 119 12 0 2.300 2.3 1.590 1.6 0.7 0.100 0.10
Exposed Type
89 GSS -3.917 0.0

Ceiling Suspended-
90 UNDER PLATFORM FCU-UL-19 1 TEL / IT ROOM -3.727 24 532 Free Discharge 7.2 6.38 0.8 0.31 0.31 0.467 FCU-BM-E-13 HCCA-14 (S) 1208 748 416 24 627 11.6 0 10.600 10.6 7.560 7.6 3.0 0.380 0.38 0.011896 0.0081704 0.0037256 0.81704 5.830 7.110
Exposed Type
DOMESTIC WATER PUMP Ceiling Suspended-
91 UNDER PLATFORM FCU-UL-02 1 xxxx 28 79 Free Discharge 1.7 1.32 0.4 0.07 0.07 0.1 FCU-BM-E-19 HFXF-02 867 545 255 24 81 13.4 0 2.000 2.0 1.370 1.4 0.6 0.090 0.09 0.011896 0.009292 0.002604 0.81704 0.605 1.592
ROOM (NEW) Exposed Type
Ceiling Suspended-
92 UNDER PLATFORM FCU-UL-08 1 SEWAGE PUMP & TANK -3.728 28 39 Free Discharge 2.0 0.66 1.3 0.08 0.08 0.1 FCU-BM-E-19 HFXF-02 867 545 255 24 81 13.4 0 2.000 2.0 1.370 1.4 0.6 0.090 0.09 0.011896 0.009292 0.002604 0.81704 0.299 0.223
Exposed Type
Ceiling Suspended-
93 UNDER PLATFORM FCU-UL-07 1 UNALLOCATED AREA (NEW) -3.719 24 358 Free Discharge 6.6 4.29 2.3 0.28 0.28 0.467 FCU-BM-E-09 HFXF-10 1902 545 255 24 390 14.1 0 6.6 6.6 4.5 4.5 2.2 0.3 0.28 0.011896 0.009608 0.002288 0.81704 2.409 1.043
Exposed Type

94 ZONE 3 CORRIDOR -3.816 0.9 0.011896 0.009045 0.002851 0.82246 0.388 0.431
Ceiling Suspended-
UNDER PLATFORM FCU-UL-01 1 24 46 Free Discharge 2.6 1.7 0.11 0.11 0.14 FCU-BM-E-05 HFXF-04 1202 545 255 24 154 13 0 2.920 2.9 1.910 1.9 1.0 0.120 0.12
Exposed Type
95 GSS ROOM -3.914 0.0

Ceiling Suspended-
96 UNDER PLATFORM FCU-UL-18 1 TEL / IT ROOM -3.712 24 523 Free Discharge 6.7 6.27 0.4 0.29 0.29 0.467 FCU-BM-E-11 HCCA-10 (S) 1349 748 409 24 452 13.9 0 7.56 7.6 6.92 6.9 0.6 0.27 0.27 0.011896 0.009608 0.002288 0.81704 3.520 8.185
Exposed Type
Ceiling Suspended-
97 UNDER PLATFORM FCU-UL-25 1 ZONE 3 CORRIDOR -3.819 24 42 Free Discharge 1.0 0.5 0.5 0.04 0.04 0.1 FCU-BM-E-01 HFXF-02 867 545 255 24 81 15.9 0 1.520 1.5 1.000 1.0 0.5 0.060 0.06 0.011896 0.011022 0.000874 0.83368 0.110 0.220
Exposed Type
Ceiling Suspended-
98 UNDER PLATFORM FCU-UL-10 1 DEWATERING SUMP ROOM -3.73 28 46 Free Discharge 1.3 0.77 0.5 0.06 0.06 0.1 FCU-BM-E-18 HFXF-02 867 545 255 28 83 17.3 0 1.310 1.3 1.030 1.0 0.3 0.060 0.06 0.011896 0.009662 0.002234 0.81704 0.302 0.570
Exposed Type
Ceiling Suspended-
99 UNDER PLATFORM FCU-UL-12 1 SEWAGE PUMP & TANK -3.729 28 52 Free Discharge 2.0 0.88 1.1 0.08 0.08 0.1 FCU-BM-E-19 HFXF-02 867 545 255 24 81 13.4 0 2.000 2.0 1.370 1.4 0.6 0.090 0.09 0.011896 0.009292 0.002604 0.81704 0.398 0.356
Exposed Type
Ceiling Suspended-
100 UNDER PLATFORM FCU-UL-13 & 20 2 FIRE PUMP ROOM -3.726 28 432 Free Discharge 13.3 7.26 6.0 0.57 1.14 0.72 FCU-BM-E-22 HCCA-10 (S) 1349 748 409 28 452 15.0 0 13.220 26.4 9.050 18.1 8.3 0.560 1.12 0.011896 0.010328 0.001568 0.82989 2.024 0.335
Exposed Type

ZONE 3 CORRIDOR -3.817 1.0 0.011896 0.010328 0.001568 0.82989 1.246 1.234
Ceiling Suspended-
101 UNDER PLATFORM FCU-UL-26 1 24 266 Free Discharge 4.2 3.2 0.18 0.18 0.36 FCU-BM-E-07 HFXF-08 1652 545 255 24 299 15 0 4.690 4.7 3.280 3.3 1.4 0.200 0.20
Exposed Type
GSS ROOM -3.912 0.0

Ceiling Suspended-
103 UNDER PLATFORM FCU-UL-14 1 ELECTRICAL ROOM -3.745 24 275 Free Discharge 5.6 3.3 2.3 0.24 0.24 0.363 FCU-BM-E-08 HFXF-10 1902 545 255 24 398 15.9 0 5.7 5.7 3.7 3.7 2.0 0.2 0.24 0.011896 0.011022 0.000874 0.83368 0.721 0.314
Exposed Type
Ceiling Suspended-
104 UNDER PLATFORM FCU-UL-15 1 ELECTRICAL ROOM -3.717 24 284 Free Discharge 5.6 3.41 2.2 0.24 0.24 0.363 FCU-BM-E-08 HFXF-10 1902 545 255 24 398 15.9 0 5.7 5.7 3.7 3.7 2.0 0.2 0.24 0.011896 0.011022 0.000874 0.83368 0.745 0.340
Exposed Type
Ceiling Suspended-
105 UNDER PLATFORM FCU-UL-16 1 TEL / IT ROOM -3.711 24 550 Free Discharge 7.5 6.6 0.9 0.32 0.32 0.467 FCU-BM-E-13 HCCA-14 (S) 1208 748 416 24 627 11.6 0 10.600 10.6 7.560 7.6 3.0 0.380 0.38 0.011896 0.0081704 0.0037256 0.81704 6.027 6.697
Exposed Type
Ceiling Suspended-
106 UNDER PLATFORM FCU-UL-21 1 UNALLOCATED AREA -2.731 24 642 Free Discharge 11.4 7.7 3.7 0.49 0.49 0.721 FCU-BM-E-16A HCCA-10 (S) 1208 748 416 24 447 10.0 0 11.650 11.7 7.940 7.9 3.7 0.470 0.47 0.011896 0.0074 0.004496 0.81171 8.435 2.280
Exposed Type
Ceiling Suspended-
107 UNDER PLATFORM FCU-UL-23 1 UNALLOCATED AREA -3.915 24 73 Free Discharge 1.3 0.88 0.4 0.06 0.06 0.1 FCU-BM-E-01 HFXF-02 867 545 255 24 81 15.9 0 1.520 1.5 1.000 1.0 0.5 0.060 0.06 0.011896 0.011022 0.000874 0.83368 0.191 0.456
Exposed Type
Ceiling Suspended-
108 UNDER PLATFORM FCU-UL-22 1 UNALLOCATED AREA -3.747 24 55 Free Discharge 1.2 0.66 0.5 0.05 0.05 0.1 FCU-BM-E-01 HFXF-02 867 545 255 24 81 15.9 0 1.520 1.5 1.000 1.0 0.5 0.060 0.06 0.011896 0.011022 0.000874 0.83368 0.144 0.267
Exposed Type

Total 129 0.0 39.7 1031.0 745.1 285.9 42.27


GAS SUPPRESSION SYSTEM CYLINDER LOCATIONS - AL AZIZIZYAH Station (As on 02.10.2016)

Room Tag
S. No. Name Level Area (m2) Height (m) Volume (m3) Architectural Reference
No.

1 ELECTRICAL ROOM 0.025 ABOVE GRADE LEVEL 113.60 4.00 454.40 M006-GDB-ARC-DWG-YWST070-AG-43288

2 UPS ROOM 1 -0.113 ABOVE GRADE LEVEL 61.54 3.10 190.77 M006-GDB-ARC-DWG-YWST070-AG-55273

3 UPS ROOM 2 0.109 ABOVE GRADE LEVEL 41.80 3.10 129.58 M006-GDB-ARC-DWG-YWST070-AG-55273

4 ELECTRICAL ROOM -1.006 CONCOURSE (SUBWAY) LEVEL 20.90 3.50 73.15 M006-GDB-ARC-DWG-YWST070-SW-43283

5 ELECTRICAL CLOSET -1.025 CONCOURSE LEVEL 4.40 5.45 23.98 M006-GDB-ARC-DWG-YWST070-CL-43272

6 ELECTRICAL ROOM -1.027 CONCOURSE LEVEL 61.10 3.50 213.85 M006-GDB-ARC-DWG-YWST070-CL-43270

7 ELECTRICAL CLOSET -1.036 CONCOURSE LEVEL 2.80 5.45 15.26 M006-GDB-ARC-DWG-YWST070-CL-43272

8 MAIN TEL/IT ROOM -1.038 CONCOURSE LEVEL 53.90 5.45 293.76 M006-GDB-ARC-DWG-YWST070-CL-43272/57001

9 MCC 1 & 2 -1.065 CONCOURSE LEVEL 34.70 5.00 173.50 M006-GDB-ARC-DWG-YWST070-CL-43270

STATION CONTROL ROOM & FIRE


10 COMMAND CENTRE -1.091 CONCOURSE LEVEL 28.71 3.75 107.66 M006-GDB-ARC-DWG-YWST070-CL-43272

11 ELECTRICAL ROOM -1.095 CONCOURSE LEVEL 17.20 5.45 93.74 M006-GDB-ARC-DWG-YWST070-CL-43272/57001

12 AC/DC SCADA ROOM 2 -1.107 CONCOURSE LEVEL 75.90 5.45 413.66 M006-GDB-ARC-DWG-YWST070-CL-43270

13 AC/DC SCADA ROOM 1 -1.108 CONCOURSE LEVEL 38.30 7.65 293.00 M006-GDB-ARC-DWG-YWST070-CL-57001

14 ELECTRICAL ROOM 2 -1.116 CONCOURSE LEVEL 27.80 5.15 143.17 M006-GDB-ARC-DWG-YWST070-CL-57001

15 TELECOM SECURITY QAF -1.118 CONCOURSE LEVEL 9.40 5.15 48.41 M006-GDB-ARC-DWG-YWST070-CL-43272/57001

16 TELECOM SAFETY POLICE -1.119 CONCOURSE LEVEL 13.40 5.15 69.01 M006-GDB-ARC-DWG-YWST070-CL-57001

17 TEL/IT ROOM -1.120 CONCOURSE LEVEL 13.40 5.15 69.01 M006-GDB-ARC-DWG-YWST070-CL-43270

18 UPS BATTERY ROOM 1 -1.131 CONCOURSE LEVEL 38.00 7.85 298.30 M006-GDB-ARC-DWG-YWST070-CL-57001

19 MCC 3 & 4 -1.171 CONCOURSE LEVEL 34.80 5.00 174.00 M006-GDB-ARC-DWG-YWST070-CL-57001

20 UPS BATTERY ROOM 1 -1.175 CONCOURSE LEVEL 28.50 5.45 155.33 M006-GDB-ARC-DWG-YWST070-CL-43270

21 TELECOM THIRD PARTY -1.179 CONCOURSE LEVEL 30.50 5.60 170.80 M006-GDB-ARC-DWG-YWST070-CL-57001

22 ELECTRICAL ROOM -1.300 CONCOURSE (SUBWAY) LEVEL 40.10 5.45 218.55 M006-GDB-ARC-DWG-YWST070-SW-43283

23 ESCALATOR CONTROL ROOM -1.307 CONCOURSE (SUBWAY) LEVEL 7.40 2.50 18.50 M006-GDB-ARC-DWG-YWST070-SW-43283

24 ELECTRICAL ROOM -1.328 CONCOURSE (SUBWAY) LEVEL 41.10 5.00 205.50 M006-GDB-ARC-DWG-YWST070-SW-57004

25 ESCALATOR CONTROL ROOM -1.336 CONCOURSE LEVEL 4.30 2.50 10.75 M006-GDB-ARC-DWG-YWST070-SW-57004

26 UTILITY CHASE -1.347 CONCOURSE LEVEL 23.40 7.40 173.16 M006-GDB-ARC-DWG-YWST070-SW-57004

27 ELECTRICAL ROOM -2.006 PLATFORM LEVEL 26.10 6.10 159.21 M006-GDB-ARC-DWG-YWST070-PL-43276

28 TEL/IT ROOM -2.024 PLATFORM LEVEL 22.70 3.04 69.01 M006-GDB-ARC-DWG-YWST070-PL-43276

29 SIGNALLING ROOM -2.025 PLATFORM LEVEL 42.50 6.14 260.95 M006-GDB-ARC-DWG-YWST070-PL-43276

30 SPS MV/LV ROOM 1 -2.027 PLATFORM LEVEL 50.70 6.10 309.27 M006-GDB-ARC-DWG-YWST070-PL-57002

31 SPS MV/LV ROOM 2 -2.029 PLATFORM LEVEL 47.50 5.80 275.50 M006-GDB-ARC-DWG-YWST070-PL-43276

32 ELECTRICAL CLOSET -2.081 PLATFORM LEVEL 0.60 2.40 1.44

33 CABLE CHAMBER -3.043 UNDERPLATFORM LEVEL 31.60 3.20 101.12 M006-GDB-ARC-DWG-YWST070-UL-57003

34 CABLE CHAMBER -3.063 UNDERPLATFORM LEVEL 41.00 3.20 131.20 M006-GDB-ARC-DWG-YWST070-UL-43279

35 DC TPS ROOM -3.082 UNDERPLATFORM LEVEL 255.40 9.60 2,451.84 M006-GDB-ARC-DWG-YWST070-UL-57003

36 ELECTRICAL ROOM -3.034 UNDERPLATFORM LEVEL 25.20 3.20 80.64 M006-GDB-ARC-DWG-YWST070-UL-43279

37 ELECTRICAL ROOM -3.073 UNDERPLATFORM LEVEL 12.90 3.20 41.28 M006-GDB-ARC-DWG-YWST070-UL-43281

38 IT ROOM -3.064 UNDERPLATFORM LEVEL 15.20 3.20 48.64 M006-GDB-ARC-DWG-YWST070-UL-43279

39 TEL/IT ROOM -3.053 UNDERPLATFORM LEVEL 12.90 3.20 41.28 M006-GDB-ARC-DWG-YWST070-UL-43281