Overview of Turbine
2 CRH HPH-7
During loss of Control Oil pressure, Bush & Traction of Pilot valve
travels up shutting off head pressure oil supply to C.V.
servomotors, resulting control valve closing
During S.V. ATT, bush & Traction do not travel up due to slide
valve downward movement by ATT motor
Components of EHC
1. Speed Controller
2. Pressure Controller
3. Load Controller
4. Position Controller
Selection of Controls
EHC can be kept in Manual / Auto Mode as per
operator’s choice
Manual mode can be selected only when Generator is
connected to grid
Logic - 2
Logic-1
Actual Speed
Speed Set (Mv3)
Point = 0
Logic 1: Turbine protection operated / 2v4 stop valves closed / 2v3 speed
measuring channels faulty / Deviation between actual speed and set point
during run-up exceeded allowable value*
Logic 2: Speed gradient is controlled by minimum of TSE margin &
gradient from selected Start up curve, given by the Turbine Manufacturer
Contd….
Rolling Speed Gradient Curve
Speed gradients as per Manufacturer’s start up curve are as follows:
Rolling Condition Target Speed Preset Time Min. Halt Time
Islanding Mode:
If actual speed exceeds speed reference by a
preset limit under Generator Breaker in
closed condition, Islanding mode occurs –
Transferring Turbine to Speed Control mode
Load Control Circuit
Load Control On: Load Controller will be switched on
automatically if Turbine controller is kept on auto and
connected to the grid under “Turbine Latched” condition.
Logic-1: CMC ON, when load ref. will come from CMC circuit, where TSC
Margin calculation controls the gradient
Logic-2: The Load reference tracks actual load for bump less transfer
once it is connected to the grid.
Contd…
Load Control Circuit
Logic-3: Load Reference will be stopped under the following
Conditions:
1. TSC Margin is less than permissible value*
2. The difference between the actual and reference value is
not in allowable range
Logic-4: Maximum and minimum load set points, set by the Operator
HPC On: The point at which the HP Control Valves starts Opening
(12% of full load)
1. GCB Open
2. The frequency is more than allowable value*
3. M.S. pressure transducers failed (2V3)
4. Manual Control switched on
5. Load control is On
6. HPC is out of operation
Pressure Control
Actual Pr. Value + PI
Adder Block MIN MAX O/P
- Controller
M. S. Pr. Set Point
1 Y N Y Y N Y (HPC) Y
2 Y N Y Y N
3 Y N Y Y N
4 Y N Y Y Y Y (IPC) Y
5 Y N Y Y Y
6 Y N Y Y Y Y (LPC-1) Y
7 Y N Y Y Y
8 Y N Y Y Y Y (LPC-2) Y
9 Y N Y Y Y
10 Y N Y Y N
11 N Y Y Y N
12 N Y Y Y N
TSC System
The Stress Margin of the Turbine is
calculated by measuring the temperatures of
following components:
Contd..
Turbine Protection System
Contd…
Turbine Protection System
Axial shift Very High (2V3) [-1.7mm, +1.2mm]
Lube oil tank level very Low (2V3)* Td=3sec (Arming with two
stop valves open)
Lub oil pressure Very Low (2V3) < 0.3 Ksc; Td =3 sec (Arming
with two stop valves open)
Contd..
Turbine Protection System
M.S. temp Very Low (2V3) < 470 deg C (arming > 512 deg
C)*
HRH temp Very Low (2V3) < 500deg C (arming > 535 deg
C)*
Contd…
Turbine Protection System
Gen seal oil level of any seal oil tank Very Low (2V3)* <
0 mm;Td=15 sec (Arming with any two stop valves
open)
All Generator seal oil pumps OFF (3V3)* Td: 9 sec
(Arming with any two stop valves open)
Generator Stator winding flow Very Low (2v3) < 17.3
m3/hr; Td =120 sec (Arming with any two stop valves
open)
Generator hot gas coolers flow Very LOW (2V3)* :
<180m3/hr; Td=300sec(Arming with any two stop
valves open)
Generator cooler hot gas temp. Very High(2V4) > 85
deg (Td = 300sec
Contd…
Turbine Protection System
MFT operated: (2V3)
Contd…