instabus EIB

Application program description

September 2001

11 S6 Dimming 261101

Use of the application program Communication objects

Product family: Input


Product type: Binary input, 6-fold
Manufacturer: Siemens

Name: Binary input N 263


Order no.: 5WG1 263-1AB01

Name: Binary input N 265


Order no.: 5WG1 265-1AB01

Functional description
Note:
This application program makes it possible to use con-
ventional push buttons for dimming functions via the 6- The view of the objects can be arranged individually i.e.
fold binary input. this view can vary.
The six inputs are combined functionally in pairs to form
a 2-fold switch sensor. With each input pair, a short push Obj Function Object name Type Flag
button action switches on and off while a longer push
0 On / Off Dimming On/Off 1 Bit CWRTU
button action dims brighter and darker. Input A,B
Each input pair can be assigned the functions of “Dim-
ming with stop telegram” and “Dimming with cyclical 1 On / Off Dimming On/Off 1 Bit CWRTU
Input C,D
sending”.
In the setting “Dimming with stop telegram”, a dimming 2 On / Off Dimming On/Off 1 Bit CWRTU
telegram can be sent after a long push button action to Input E,F
dim darker or brighter by 100%. When the push button is The switching telegrams (On/Off) of the input pairs A/B, C/D
released, a stop telegram is sent. The setting “Dimming and E/F are sent via the group addresses in these objects.
with cyclical sending” generates dimming telegrams 3 Brighter / Dimming 4 Bit CWTU
according to an adjustable transmission frequency for Darker Input A,B
the duration of the push button action. When the push 4 Brighter / Dimming 4 Bit CWTU
button is released, the cyclical sending stops. Darker Input C,D
5 Brighter / Dimming 4 Bit CWTU
Darker Input E,F
The dimming telegrams (Brighter/Darker) of the input pairs
A/B, C/D and E/F are sent via the group addresses in these
objects.

Maximum number of group addresses: 9


Maximum number of associations: 9

Siemens AG 261101, 4 pages Technical manual


Automation and Drives Group
Electrical Installation Technology  Siemens AG 2001 Update: http://www.siemens.de/installationstechnik
P.O. Box 10 09 53, D-93009 Regensburg Subject to change without prior notice
3.6.2.1.2/1
instabus EIB
Application program description

September 2001

11 S6 Dimming 261101

Parameters Input A/B

General

Parameters Settings The function and the parameters of inputs A/B, C/D and
E/F are identical.
Debounce time 10 ms
30 ms
60 ms Parameters Settings
90 ms Contact type normally open contact
120 ms normally closed contact
When a push button is operated, a short bounce occurs This parameter is used to set the contact type of the push
whereby the contact closes and opens several times until it buttons that are connected at the inputs.
finally remains closed. The duration of the contact bounce “normally open contact”: The push button contacts are oper-
depends on the push button action that is used. Due to the ated when they are closed and not operated when they are
fact that the application software is able to scan the inputs open.
rapidly, any multiple push button operations would be de-
“normally closed contact”: The push button contacts are
tected and several switching telegrams are therefore sent.
The debounce time prevents this as after the initial detection operated when they are open and not operated when they are
closed.
of a change in the status at the input, there is a delay for the
set time and the current status is then used for further proc- Function Dimming with stop tele-
essing. gram
Dimming with cyclical sending
Limit number of disabled
telegrams enabled The function of the input pair can be set via this parameter.
It is possible to limit the number of telegrams that are sent per “Dimming with stop telegram”: Briefly pressing the push but-
time unit, so that a defective push button does not ton connected to input A produces On telegrams via object 0
continuously generate switching commands. while a short push button action at input B generates Off
“disabled”: The number of telegrams sent is not limited. telegrams via object 0. A long push button action at input A
“enabled”: The number of telegrams sent per time unit can be produces a “Dim brighter” telegram via object 3. When the
limited. The parameter window changes and the parameter push button is released, a stop command is sent. Input B
“Limit number of telegrams” appears where the number of operates according to the “Dim darker” dimming direction.
telegrams that are sent in a time period can be set. “Dimming with cyclical sending”: A short push button action at
Limit number of 30 telegrams per 17 sec. input A or B generates an On or Off telegram via object 0. A
telegrams 60 telegrams per 17 sec. long push button action at input A produces “Dim brighter”
100 telegrams per 17 sec. telegrams for the duration of the push button action according
127 telegrams per 17 sec. to the setting “Transmission frequency for cyclical sending”.
When the push button is released, the cyclical sending stops.
Depending on the setting selected, a maximum of 30, 60, 100 Input B operates according to the “Dim darker” dimming
or 127 telegrams are sent per 17 seconds. direction.

Short push button action A = On, B = Off

The switching direction of inputs A and B is defined via this


parameter and cannot be modified. The parameter refers to a
short push button action when configuring “Dimming with stop
telegram” and “Dimming with cyclical sending”.
“A = On, B = Off”: A push button action at input A produces
On telegrams while a push button action at input B generates
Off telegrams.

Technical manual 261101, 4 pages Siemens AG


Automation and Drives Group
Update: http://www.siemens.de/installationstechnik  Siemens AG 2001 Electrical Installation Technology
Subject to change without prior notice P.O. Box 10 09 53, D-93009 Regensburg
3.6.2.1.2/2
instabus EIB
Application program description

September 2001

11 S6 Dimming 261101

Parameters Settings Examples of timing diagrams for an input pair


Long push button action adjust by 100%
adjust by 1/2 1. Configured for:
adjust by 1/4 “Dimming with stop telegram”
adjust by 1/8
adjust by 1/16
Push button action < 0.5s 0.5s
adjust by 1/32
input A
adjust by 1/64
Push button action 0.5s < 0.5s
This parameter is only displayed for the function “Dimming
input B
with cyclical sending”.
The dimming step width of the telegrams for a long push Switch object On Off
button action is specified via this parameter. telegrams

The dimming step width should be set according to the dim- Dimming object Darker Stop Brighter Stop
ming time of the actuator together with the parameter telegrams
“Transmission frequency for cyclical sending”. For example, if
the dimming time of 0 to 100% in the switch/dim actuator is
set to 4 seconds, a transmission frequency of 0.5 seconds 2. Configured for:
with an adjustment of 1/8 is selected. This means that a
dimming command of 12.5% brighter or darker is sent every “Dimming with cyclical sending”
0.5 seconds. With an adjustment of 8 x 12.5% and 8 x 0.5
seconds, this concurs with the dimming speed in the actuator Push button action < 0.5s 0.5s
of 100% in 4 seconds. input A

Long push button action 0.3; 0.4; 0.5; 0.6; 0.8; 1.0; Push button action 0.5s < 0.5s
min. 1.2; 1.5; 2.0; 2.5; 3.0; 4.0; input B
5.0; 6.0; 7.0 seconds
Switch object On Off
This parameter defines the time limit for a short/long push telegrams
button action. If a push button action is held down for longer
Dimming object -1/8 -1/8 -1/8 +1/8 +1/8 +1/8 +1/8
than the set time, the software detects a long push button
telegrams
action.
Push button action shorter than the set time: A switching
telegram is sent.
Push button action longer than the set time: Dimming tele-
grams are sent.
Transmission frequency for 0.3; 0.4; 0.5; 0.6; 0.8; 1.0;
cyclical sending 1.2; 1.5; 2.0; 2.5; 3.0; 4.0;
5.0; 6.0; 7.0 seconds
This parameter is only displayed for the function “Dimming
with cyclical sending”.
The transmission frequency or rather the cyclic time is set
here. Dimming telegrams are continually sent for the duration
of the push button action according to the value that is se-
lected. The transmission frequency together with the step
width produces the dimming period. This must match the
dimming time in the actuator.

Siemens AG 261101, 4 pages Technical manual


Automation and Drives Group
Electrical Installation Technology  Siemens AG 2001 Update: http://www.siemens.de/installationstechnik
P.O. Box 10 09 53, D-93009 Regensburg Subject to change without prior notice
3.6.2.1.2/3
instabus EIB
Application program description

September 2001

11 S6 Dimming 261101

Notes

Technical manual 261101, 4 pages Siemens AG


Automation and Drives Group
Update: http://www.siemens.de/installationstechnik  Siemens AG 2001 Electrical Installation Technology
Subject to change without prior notice P.O. Box 10 09 53, D-93009 Regensburg