Rel 511 - B524 PDF
Rel 511 - B524 PDF
Published by
DIgSILENT GmbH, Germany
Table of Contents
- EF4
- IOC
- TEF
- TOC
- TOC2
- TOC3
- Voltage
- WEF1
The main relay contains the sub relays, the measurement elements, the starting element, the polarizing elements, the
directional element for the distance elements and the output logic.
More in detail the following functionalities are modelled in the main relay.
Two measurement units (“Measure” and “Delta Measure” block). Please don’t forget to insert the nominal current and
the nominal voltage in all blocks.
One starting unit implementing the phase selection logic (“Starting” block)
One directional element (“Dir-Z” block).
Two polarizing blocks (“Polarizing” and”Polarizing20” block). Please note that no user input is usually needed in these
blocks.
Five trips zone for the phase loops each of them associated to a timer(“Z1P” and “ZT1P”, “Z2P” and “ZT2P”, “Z3P”
and “ZT3P”, “Z4P” and “ZT4P” , “Z5P” and “ZT5P”block)
Five trips zone for the ground loops each of them associated to a timer(“Z1G” and “ZT1G”, “Z2G” and “ZT2G”, “Z3G”
and “ZT3G”, “Z4G” and “ZT4G” , “Z5G” and “ZT5G”block)
“TOC” subrelay:
One inverse characteristic phase overcurrent element (“TOC Phase” block)
One inverse characteristic residual overcurrent element (“TOC Residual” block)
One not directional inverse characteristic phase overcurrent element with minimum activation threshold and
additional trip delay (“Toc2”, “Toc2 tLow” and “Toc2 I>Low” block)
One time defined phase overcurrent element (“Toc2 I>High” block)
3 Reference material
The model implementation has been based on the information available in the “Technical reference manual ProtectIT Line
distance protection terminal REL 511*2.5 Document No: 1MRK 506 166-UEN Issued: November 2003” and in the “Application
manual ProtectIT Line distance protection terminal REL 511*2.5 Document No: 1MRK 506 168-UEN Issued: December 2003”
document.