The main relay contains the sub relays, the measurement elements, the starting element, the polarizing elements, the
directional element for the distance elements, the differential element and the output logic.
More in detail the following functionalities are modelled in the main relay.
Two measurement units (“Measure” and “Delta Measure” block). Please don’t forget to insert the nominal current and
the nominal voltage in all blocks.
One starting unit implementing the phase selection logic (“Starting” block)
One directional element (“Dir-Z” block).
Two polarizing blocks (“Polarizing” and”Polarizing20” block). Please note that no user input is usually needed in these
blocks.
Five trips zone for the phase loops each of them associated to a timer(“Z1P” and “ZT1P”, “Z2P” and “ZT2P”, “Z3P”
and “ZT3P”, “Z4P” and “ZT4P” , “Z5P” and “ZT5P”block)
Five trips zone for the ground loops each of them associated to a timer(“Z1G” and “ZT1G”, “Z2G” and “ZT2G”, “Z3G”
and “ZT3G”, “Z4G” and “ZT4G” , “Z5G” and “ZT5G”block)
One differential element with CT ratio adaption feature (“Differential” block, the CT ratio can be adapted changing the
“CTFact” variable value in the “Logic” tab page of the “CTFactor” block. The default value is 1)
“TOC” subrelay:
One inverse characteristic phase overcurrent element (“TOC Phase” block)
One inverse characteristic residual overcurrent element (“TOC Residual” block)
One not directional inverse characteristic phase overcurrent element with minimum activation threshold and
additional trip delay (“Toc2”, “Toc2 tLow” and “Toc2 I>Low” block)
One time defined phase overcurrent element (“Toc2 I>High” block)
3 Reference material
The model implementation has been based on the information available in the “Application manual ProtectIT Line differential
and distance protection terminal REL 561*2.3 Document No: 1MRK 506 113-UEN Issued: August 2003” document.