You are on page 1of 12

The International Journal Of Engineering And Science (IJES)

|| Volume || 3 || Issue || 10 || Pages || 26-37|| 2014 ||


ISSN (e): 2319 – 1813 ISSN (p): 2319 – 1805

“Performance Evaluation of Domestic Refrigerator Using Hc-


12a Refrigerant as an Alternative Refrigerant to R12 And
R134a”
Rajanikant Y. Mahajan 1, Sanjaykumar A. Borikar 2;
1
M.Tech. IV Semester, Heat Power Engineering, KITS, Ramtek, Nagpur- 441106.
2
Assistant Professor, Mechanical Engineering Department, KITS, Ramtek, Nagpur- 441106.

ABSTRACT: This paper presents a study of different environment friendly refrigerants with zero ozone
depletion potential (ODP) and negligible global warming potential (GWP), to replace R134a in domestic
refrigerator. This work consists of using a hydrocarbon gas mixture which does not deplete ozone layer, is eco
friendly, and can be used in the commonly used refrigerators without any significant change in the system. A
refrigerator designed and developed to work with R134a was tested, and its performance using HC-12a was
evaluated and compared with its performance when R134a was used. The condenser temperature and
evaporator temperature, COP, refrigerating effect, condenser duty, work of compression and heat rejection of
water were investigated. The energy consumption of the refrigerator during experiment with hydrocarbons and
R-134a was measured. The results obtained showed that the alternative refrigerant investigated in experimental
performance HC-12a have higher coefficient of performance and less energy consumption. The design
temperature and pull-down time set by International Standard Organization (ISO) for small refrigerator were
achieved earlier using refrigerant HC-12a than using R-134a. Due to a higher value of latent heat of HCs, the
amount of refrigerant charge was also reduced as compared with HFC-134a. The COP and other result obtain
in this experiment shows a positive indication of using mixed refrigerant as refrigerants in household
refrigerator. The performance of HC-12a in the domestic refrigerator was constantly better than those of
R134a throughout all the operating conditions, which shows that HC-12a can be used as replacement for R134a
in domestic refrigerator. Refrigerant physical and chemical properties of different refrigerants are included in
this paper. This paper also discuses on the C.O.P (coefficient of performance) and RE (Refrigeration Effect).

KEY WORDS: Experimental Domestic refrigerator, Hydrocarbon refrigerant, R134a, COP, Refrigerating
effect, Energy consumption;
---------------------------------------------------------------------------------------------------------------------------------------
Date of Submission: 04 July 2014 Date of Publication: 05 November 2014
---------------------------------------------------------------------------------------------------------------------------------------

I. INTRODUCTION
The Montreal Protocol regulates the production and trade of ozone-depleting substances. Since the
refrigerants used in air conditioning and refrigeration units contain chlorine, which causes the ozone depletion,
the industry and research institutes are challenged to find suitable alternates. The Department of Energy’s
appliance energy standards, designed to contain the global warming effects, is another major challenge facing
the refrigeration industry. The long-term reliability of the proposed alternate refrigerants is yet to be resolved.
Results from many researches show that ozone layer is being depleted due to the presence of
chlorine in the stratosphere. The general consensus for the cause of this is that CFCs and HCFCs are large class
of chlorine containing chemicals, which migrate to the stratosphere where they react with ozone. Later, chlorine
atoms continue to convert more ozone to oxygen. The discovery of the depletion of the earth’s ozone layer,
which shields the earth’s surface from UV radiation, has resulted in a series of international treaties demanding
a gradual phase out of halogenated fluids. The CFCs have been banned in developed countries since 1996, and
in 2030, producing and using of CFCs will be prohibited completely in the entire world. Also, the partially
halogenated HCFCs are bound to be prohibited in the near future.
Many experimental and theoretical studies have been reported regarding the performance of
various alternative refrigerants and their mixtures. A comprehensive survey of the existing literature on the
performance of alternative refrigerants and their mixtures in refrigeration system has presented. An
experimental study on domestic refrigerator with R–134a and replaced it by R–152a and R–32 which have zero
ODP and low GWP. They were concluded that the system performed better than the other two refrigerants this
shows that R–152a can be used to replace R–134a in domestic refrigerators. The plant working efficiency was
first estimated with R–22 and then with three new HFC refrigerants, R–417a, R–422a and R–422d. The

www.theijes.com The IJES Page 26


Performance Evaluation of Domestic…

experimental results showed that R–22 has the least energy consumption among all the refrigerants under trial.
Results also reveal that the three HFC refrigerants can replace R–22 without any change in lubricant or without
any modification in the system and the accessories. The results also verified that despite these advantages, the
performance of the new tested HFCs was not as efficient as with R–22.The hydrocarbons investigated are
propane (R290), butane (R600) and isobutene (R600a). A refrigerator designed to work with R134a was used as
an investigation unit to assess the prospect of using mixed refrigerants. Even the ozone depletion potentials of
R134a relative to CFC-11 are very low; the global warming potentials are extremely high and also expensive.
For this reason, the production and use of R134a will be terminated in the near future. Hydrocarbons are free
from ozone depletion potential and have negligible global warming potential. In this work, an experimental
work was investigated on the nano refrigerant were used in domestic refrigerator without any system
reconstruction. The refrigerator performance was than investigated using energy consumption test and freeze
capacity test. He was concluded TiO2–R600a nano refrigerant may be used in domestic refrigerator with better
performance and lower energy consumption without any alteration of the system. The refrigerator which was
designed to work with 150 gm of R–134a gave best result with 90 gm of hydrocarbon refrigerant that implies a
reduction of 40% in refrigerant charge. The result shows that the new refrigerant mixture offers a better
refrigerating behavior and reduces the energy consumption by 4.4%. This paper aims at development of one
such eco friendly system for domestic refrigerators. The commonly used domestic refrigerators use the gas
which either deplete the ozone layer or contribute in the global warming in the same as CO2 does. This work
consists of using a hydrocarbon gas mixture known as mint gas which does not deplete ozone layer, is eco
friendly, and can be used in the commonly used refrigerators without any significant change in the system.
Efforts have been made to include various aspects to get the maximum knowledge about the refrigerant. This
paper presents an experimental study of R404a and R134a, environment-friendly refrigerants with zero ozone
depletion potential (ODP) and low global warming potential (GWP), to replace R134a in domestic refrigerator.
A refrigerator designed and developed to work with R134a was tested, and its performance using R-404a was
evaluated and compared with its performance when R134a was used.
The researchers are going on to find out some alternate refrigerants which does not harm to the
environment and the protective ozone layer. Research has shown that hydrocarbons are good alternative to
existing refrigerants. Hydrocarbons, propane (R–290) and isobutane (R–600a) were among the first refrigerants,
but due to their flammability and safety purposes, their use was abandoned and the direction of researches was
shifted towards a safer and inert class of refrigerants. Thus the use of HCs as a refrigerant is not a new
technology. Since 15 years, hydrocarbon and their blends are again being used at commercial scale.
A growing awareness of the environmental issues facing our planet has motivated many world
leaders and governments to embrace hydrocarbon technology as a long-term solution to environmental
concerns. The European Common has adopted a new Standard, EN 378, which provides guidelines for the use
and installation of hydrocarbon refrigerants in over 14 European countries. In the past five years alone, more
than 8 million refrigerators and freezers were manufactured in Germany and Denmark utilizing hydrocarbon
technology. The Freon-dependent world was thrust into a dilemma in 1996 when production of the world's most
commonly used refrigerant was banned in developed countries for its link to stratospheric ozone depletion. The
immediate answer to the international refrigeration dilemma was to replace ozone-depleting chlorofluorocarbons
(CFCs) with HFC-134a-a greenhouse gas.

R-134a TECHNOLOGY HYDROCARBON TECHNOLOGY


Relatively lower efficiency than CFC 12 Slightly higher efficiency than CFC 12
Considerable changes in compressor No change in compressor manufacturing processes
manufacturing processes
Highly sensitive to moisture content Negligible sensitivity to moisture content
High degree of cleanliness for the whole Prevalent standards of cleanliness are acceptable
refrigeration system
Higher potential of system malfunction Negligible effect
due to accidental pollution
Relatively higher noise-level Low noise-level with isobutane as refrigerant
Non-flammable Flammable
Higher cost of refrigerant and lubricant Low cost
Essential to upgrade servicing practice Existing service practice maybe followed with additional
safety precautions
No safety measures are required Safety measures are required
Table 1: Comparative study of HFC-134a and Hydrocarbon technologies from the point of view of
manufacturing and servicing

www.theijes.com The IJES Page 27


Performance Evaluation of Domestic…

It turns out that HFC-134a's potential for causing environmental damage is just the beginning of its
inadequacy as a replacement for Freon. Field experience has shown it to be thermally inefficient, energy
consumptive and corrosive to compressor parts. HFCs may be a source of acid rain. HFC degradation can
include hydrofluoric acid and trifluoroacetate (TFA) which could threaten seasonal wetlands in urban areas.
HFC production can leak toxic chemicals. The manufacture of HFCs releases vinyl chloride, ethylene dichloride
(both carcinogens), other chlorinated organics, HFCs and HCFCs into the atmosphere. Liquid traces include
heavy chlorinated residues likely to contain traces of dioxins as well as chromium in catalyst waste.
In addition, HFCs have been shown have toxic effects on refrigeration technicians whilst handling
these refrigerants, leading to skin and stomach disorders and other effects such as headaches and dizziness.
Within a fire situation, HFCs produce poisonous, toxic and corrosive substances when burned. A 1998 study
conducted at Wright Patterson AFB in Ohio found that HFC-134a can be deathly toxic to humans who inhale it
at levels at or above 4 parts per million. The issue of energy efficiency is of crucial importance in relation to the
indirect global warming impact from CO2 emissions arising during energy production. Using a non-HFC
substance or technology may have an important influence on energy usage.
R-12 R-134a HC-12a
Class CFC HFC HC
(ChloroFluorocarbon) (HydroFluoroCarbon) (HydroCarbon)
Isobutane & Propane CH(CH3)2-
Chemical Name Dichlorodifluorom Tetrafluoroethane CH3 i-(C4H10) & CH2CH3CH2
ethane CCl2F2 CH2FCF3
Formula R-12 (100) R- 134a (100) R-600a (40), R-290 (60)
Boiling Point @ 20°C -29.7°C -26.6°C -29.8°C
Toxicity Medium Medium Low
Flammability (auto- ignition 1100°C (non) -800°C (non) ~ 460oC - ~ 470oC (yes)
temperature)
Toxicity after ignition (by-
products) Very High Extremely High Extremely Low

Lubricant Flammability (auto-


ignition temp.) ~ 200°C ~ 200°C ~ 200°C
Global Warming Potential (20
years / 100years) 8500/8500 3100/ 1300 ~ 0/3
Ozone Depletion Potential I Yes No No
Atmosphere Lifetime (Years) ~ 130 ~ 16 <1
Cooling Performance @ 40°C Good Poor Excellent
Energy Efficiency Medium Low High
Power Consumption Medium High Low
Average System Charge by ~ 900 grams ~ 840 grams <300 grams
Weight
Average System Charge by ~ 0.90 Lt ~ 0.86 Lt ~ 0.75 Lt
Volume
Table 2: Properties of R-12, R-134a and HC-12a refrigerants with Comparison chart.
In some cases the effect can be beneficial. However, in other situations there is an energy penalty,
which can actually lead to an increase in COZ emissions that outweigh the benefits of reduced HFC emissions.
These effects are strongly application and design dependent and must be carefully taken into account when
considering HFC emission reduction strategies. This is a topic intense discussion as there is no general rule
because refrigerants and refrigeration technologies can behave differently in different systems under different
conditions. However, numerous research work has illustrated that non-HFC technologies can provide more
efficient refrigeration cycles than those using HFCs.

II. EXPERIMENTAL SETUP AND TEST PROCEDURE


This section provides a description of the facilities developed for conducting experimental work on a domestic
refrigerator. The technique of charging and evacuation of the system is also discussed here. Experimental data
collection was carried out in the research laboratory of our institution. The experimental setup of the test unit
and apparatus is shown in the Figure.

www.theijes.com The IJES Page 28


Performance Evaluation of Domestic…

2.1Experimental System

Figure 1: View of Experimental Refrigerator

Different experimental and theoretical comparison will performed to evaluate the performance of
domestic refrigerator by using different refrigerants. In this experimental study of HC-12a is compared with the
R-134a in a domestic refrigeration system. To perform the experiment 165L refrigerator is selected which was
designed to work with R-134a. It is consists of an evaporator, air cooled condenser, expansion device and
reciprocating compressor. The refrigerator was instrumented with two pressure gauges at inlet and outlet of the
compressor. The temperature at six different points is taken by six temperature sensors are mounted to measure
the compressor inlet temperature, compressor delivery temperature, evaporator inlet temperature, evaporator
outlet temperature, the freezer temperature and cabinet temperature. An ammeter is mounted at the inlet of the
compressor to measure the power supply and voltmeter is also used for voltage of supply.
Firstly cleaning is done with the help of nitrogen gas then evacuation is carried out with the help of
vacuum pump and refrigerant is charged with the help of charging system. The refrigerant charge requirement
with hydrocarbons is very small due to their higher latent heat of vaporization. As per the refrigerator
manufactures recommendation quantity of charge requirement for HFC134a was 100 g. In the experiment,
refrigerant charge is 10% higher due to the presence of instruments and connecting lines etc. To optimize the
mixed refrigerant charge, the refrigerator is charged with 80g and the performance was studied. The
experimental procedures were repeated and take the reading for different mixtures from the various modes.

2.2 Experimental Procedure


Heat flows naturally from a hot to a colder body. In refrigeration system the opposite must occur i.e.
heat flows from a cold to a hotter body. This is achieved by using a substance called a refrigerant, which absorbs
heat and hence boils or evaporates at a low pressure to form a gas. This gas is then compressed to a higher
pressure, such that it transfers the heat it has gained to ambient air or water and turns back (condenses) into a
liquid. In this way heat is absorbed, or removed, from a low temperature source and transferred to a higher
temperature source. The refrigeration cycle can be broken down into the following stages

Figure 2: Schematic of a Basic Vapor Compression Refrigeration System

www.theijes.com The IJES Page 29


Performance Evaluation of Domestic…

1 – 2: Low pressure liquid refrigerant in the evaporator absorbs heat from its surroundings, usually air, water or
some other process liquid. During this process it changes its state from a liquid to a gas, and at the evaporator
exit is slightly superheated.
2 – 3: The superheated vapour enters the compressor where its pressure is raised. There will also be a big
increase in temperature, because a proportion of the energy input into the compression process is transferred to
the refrigerant.
3 – 4: The high pressure superheated gas passes from the compressor into the condenser. The initial part of the
cooling process (3 - 3a) desuperheats the gas before it is then turned back into liquid (3a - 3b). The cooling for
this process is usually achieved by using air or water. A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4), so that the refrigerant liquid is sub-cooled as it enters the expansion device.
4 – 1: The high-pressure sub-cooled liquid passes through the expansion device, which both reduces its pressure
and controls the flow into the evaporator.

III. RESULTS AND DISCUSSIONS


3.1 Observations and calculations for R-134a as a refrigerant at no load condition

Figure 3: Time Vs TR, Tcab, Teo, Tei shows that at no load condition freezer temperature obtained is very low
as compared to other temperature and cabinet temperature is not less than the other temperature.

At 60watt condition

Figure 4: Time Vs TR, Tcab, Teo, Tei shows that at 60w condition freezer temperature obtained is very low as
compared to other temperature

At 120watt condition

Figure 3: Time Vs TR, Tcab, Teo, Tei shows that at 120watt condition freezer temperature obtained is low as
compared to other temperature.

www.theijes.com The IJES Page 30


Performance Evaluation of Domestic…

At 160watt condition

Figure 6: Time Vs TR, Tcab, Teo, Tei shows that at 160watt condition Evaporator inlet temperature obtained is
comparatively low as compared to other temperature and cabinet temperature is higher upto the 30oC.

At 50lit water cabinet condition

Figure 7: Time Vs TR, Tcab, Teo, Tei and Tw shows that at 50lit water inside cabinet condition freezer temp.
obtained is comparatively low as compared to other temperature.

3.2 Observations and calculations for HC-12a as a refrigerant


At no load condition

Figure 8: Time Vs TR, Tcab, Tei and Teo shows that freezer temperature is obtained very low as compared to
other at no load condition.

At 60watt condition

Figure 9: Time Vs TR, Tcab, Tei and Teo shows that cabinet temperature is obtained higher due to 60watt bulb
cond. and evaporator inlet temperature is obtained very low as compared to with each other at 60watt condition.

www.theijes.com The IJES Page 31


Performance Evaluation of Domestic…

At 120watt condition

Figure 10: Time Vs TR, Tcab, Tei and Teo shows that cabinet temperature is obtained higher due to 120watt
bulb condition as compared to other temperature.

At 160watt condition

Figure 11: Time Vs TR, Tcab, Tei and Teo shows that cabinet temperature is obtained higher due to 160watt
bulb condition as compared to other temperature.

At 50lit water cabinet condition

Figure 12: Time Vs TR, Tw, Tcab, Tei, Teo shows that cabinet water temperature is obtained higher and
evaporator inlet temperature is obtained very low as compared to with each other at 50lit water inside cabinet
condition.

www.theijes.com The IJES Page 32


Performance Evaluation of Domestic…

3.3 Comparative analysis of R-134a and HC-12a refrigerant


At no load condition

Figure 13: shows that HC-12a shows higher cop as compared to ref. R-134a. HC-12a ref. occurs in the range of
6.57 to 2.94 and R-134a in the range of 3.77 to 1.8.

Figure 14: shows the observed values of freezer temperature for R-134a and mixed refrigerants (HC-12a). R-
134a shows lower temp to -15.4oC as compared to the mixed refrigerants.

At 60 watt condition

Figure 15: shows that the observed values cop for R-134a and HC-12a. COP of mixed ref. (HC-12a) shows
more cop compared to ref. R-134a.

www.theijes.com The IJES Page 33


Performance Evaluation of Domestic…

Figure 16: shows the observed values of freezer temperature for R-134a Vs mixed refrigerants (HC-12a). HC-
12a shows near about equally temp as compared to the R-134a at 60watt bulb condition.

At 120 watt condition

Figure 17: shows that the observed values cop(HC-12a) Vs cop(R-134a) shows higher cop of HC-12a as
compared to R-134a at the initial cond.

Figure 18: shows the observed values of freezer temperature for R-134a and mixed refrigerants (HC-12a).
Mixed refrigerants shows lower temp to -3.2oC as compared to the R-134a at 120watt condition.

At 160 watt condition

Figure 19: shows that the observed values of cop for R-134 Vs HC-12a at diff temp. cop of the mixed ref. shows
more cop compared to ref R-134a.

www.theijes.com The IJES Page 34


Performance Evaluation of Domestic…

Figure 20: shows the observed values of freezer temperature for R-134a and mixed refrigerants (HC-12a). HC-
12a shows near about equally temp as compared to the R-134a at 160watt bulb condition.

At 50 lit water condition

Figure 21: shows that the observed values of cop for R-134 Vs HC-12a. HC-12a has higher cop as compared to
ref. R-134a at initial condition at 50lit cabinet water cond.

Figure 22: shows the observed values of freezer temperature for R-134a Vs mixed refrigerants (HC-12a). Mixed
refrigerants shows lower temp as compared to the R-134a at 50lit cabinet water condition.

3.4 Comparative analysis of COP for R-134a and HC-12a refrigerant

Figure 23: Time Vs COP of no load, 60watt, 120watt, 160watt, 50lit cabinet water condition shows that all cops
at different conditions are comparatively higher at starting periods and also different type of cop occurs in
between 3.77 to 1.8.

www.theijes.com The IJES Page 35


Performance Evaluation of Domestic…

Figure 24: Time Vs COP of no load, 60watt, 120watt, 160watt, 50lit cabinet and 2lit freezer water condition
shows that all cops at different conditions are comparatively higher at starting periods and all different type of
cop occurs in the range of 6.96 to 2.97.

IV. CONCLUSION
As per the Kyoto and Montreal protocols, the harmful refrigerants are to be phased out and are to be
replaced with alternate environmental friendly refrigerants with zero ozone depletion potential (ODP) and
negligible global warming potential (GWP), to replace R-12 and R134a in domestic refrigerator
1. Hydrocarbons blends may replace R-134a without any system modifications.
2. COP of the system is improved with reduced energy consumption.
3. Hydrocarbon refrigerants are compatible with mineral oils (commonly used lubricants).
4. Hydrocarbon technology provides a simple, sustainable and cost-effective solution for replacing R-134a in
the domestic refrigeration subsector in developing countries.
5. Chemical and thermodynamics properties of hydrocarbon meet the requirement of a good refrigerant. 6. Some
standards allow the use HCs as refrigerant if small amount of refrigerant is used due the latent heat of
vaporization.
7. The only disadvantage associated with this gas is its flammability, which can be an obstacle in its
implementation. This problem can be solved by proper design of the refrigerator..

V. FUTURE SCOPE
Hydrocarbons blends may replace R-134a without any system modifications and COP of the system is
improved with reduced energy consumption. So our future intension is that increase the requirement of HC-12a
as a refrigerant in all types of domestic refrigerators and air conditioning system in near future. Due to the zero
ozone depletion potential (ODP) and negligible global warming potential (GWP), environments becomes a safe
and sweets. In develop countries HC-12a as a refrigerant use in car air conditioning as well as industrial air
conditioning.
REFERENCES
[1]. Sahu R., December-2011, “Comparative analysis of mint gas with R-12 and R-134 refrigerants.” International Journal of
Scientific & Engineering Research, Volume 2, Issue 12, ISSN 2229-5518, Pp:1-4
[2]. Tiwari A., Gupta R.C., 2011,“Experimental study of R-404A and R-134A in Domestic Refrigerator.” International Journal of
Engineering Science and Technology (IJEST), Pp:6390-6393.
[3]. Austin N., Dr. SenthilKumar P., Dr. Diaz P. M., April 2013, “Experimental Study of HC Mixtures to Replace R-134a in a
Domestic Refrigerator with Testing and Training of ANN.” Indian Journal of Applied Research. Volume : 3 | Issue : 4 | ISSN -
2249-555X,pp:163-167.
[4]. Rocca V. L., Panno G., 2011 ”Experimental performance evaluation of a vapour compression refrigerating plant when replacing
R22 with alternative refrigerants.” Applied Energy 88,pp: 2809–2815.
[5]. Bolaji B. O., 2010,“Experimental study of R152a and R32 to replace R134a in a domestic refrigerator,” Energy 35, pp:3793–
3798.
[6]. Jwo C. S., Ting C. C., Wang W. R., 2009 “Efficiency analysis of home refrigerators by replacing hydrocarbon refrigerants,”
Measurement 42, pp:697–701.
[7]. Bi S., GuoK., Liu Z., Wu J., 2011, “Performance of a domestic refrigerator using TiO2–R600a nano–refrigerant as working
fluid,” Energy Conversion and Management 52, pp:733–737.
[8]. Quraishi M. A., Wankhede U. S., Jan-Feb. 2013, “Use of Hydrocarbons and Other Blends as Refrigerant.” International Journal
of Modern Engineering Research (IJMER) Vol.3, Issue.1, pp-250-253,ISSN: 2249-6645.
[9]. Aprea C., Maiorino A., Mastrullo R., 2011 “Change in energy performance as a result of a R–422d retrofit: An experimental
analysis for a vapor compression refrigeration plant for a walk in cooler,” Applied Energy 88, p:4742–4748.
[10]. Llopis R., Cabello R., SánchezD., Torella E., Patino J., Sánchez J. G., 2011, “Experimental evaluation of HCFC–22 replacement
by the drop-in fluids HFC-422a and HFC-417b for low temperature refrigeration applications,” Applied Thermal Engineering 31
pp: 1323–1331.

www.theijes.com The IJES Page 36


Performance Evaluation of Domestic…
[11]. Khorshid E., Alshiraan B., Alsairafi A., Alzemi A., Allahddad A., 2011, “Performance investigation on new refrigerant
mixture”pp15-20.
[12]. Rasti M., Hatamipour M.S., Aghmiri S.F., Tavakoli M., 2012, “Enhancement of domestic refrigerator’s energy efficiency index
using a hydrocarbon mixture refrigerant,” Measurement 45 pp:1807–1813.
[13]. Sattar M. A., Saidur R., Masjuki H. H., 2007 “Performance investigation of domestic refrigerator using pure hydrocarbons and
blends of hydrocarbons as refrigerants,” World Academy of Science, Engineering and Technology 29 pp:223–228.
[14]. Saidur R., Kazi S.N., Hossain M.S., Rahman M.M., Mohammed H.A., 2011, “A review on the performance of nano particles
suspended with refrigerants and lubricating oils in refrigeration systems,” Renewable and Sustainable Energy Reviews 15,pp:
310–323.
[15]. Corberan J. M., Segurado J., Colbourne D., Gonzalvez J., 2008, “Review of standards for the use of hydrocarbon refrigerants i n
A/C, heat pump and refrigeration equipment,” International Journal of Refrigeration 31, pp: 748–756.
[16]. Cengel Y. A., Bole M. A., Thermodynamics, An Engineering Approach 7e. pp:610-611.
[17]. Chen S., Judge J. F., Groll E. A., Radermacher R., 1994, “Theoretical Analysis of Hydrocarbon Refrigerant Mixtures as a
Replacement for HCFC -22 for Residential Uses”, International Refrigeration and Air Conditioning Conference, pp: 225-230.
[18]. Kim M. H., Lim B. H., Chu E. S., 8 Oct 1998, “The Performance Analysis of a Hydrocarbon Refrigerant R -600a in a Household
Refrigerator/Freezer”, KSME International Journal, Vol. 12, No. 4, pp. 753~ 760.
[19]. Liu Z., Haider I., Liu B. Y., Radermacher R., 1994, “Test Results of Hydrocarbon Mixtures in Domestic Refrigerator/Freezers”,
Center for Environmental Energy Engineering (CEEE) University of Maryland College Park, Maryland, USA, PP: 22-31.
[20]. Maclaine-cross I. L., Leonardi E., June 1997, “Why Hydrocarbons Save Energy”, School of Mechanical and Manufacturing
Engineering The University of New South Wales Sydney NSW, Australia 2052, Published in AIRAH Journal, Volume 51 No. 6,
pp. 33–37.
[21]. Baskaran A., Mathews P. K., September 2012, “A Performance Comparison of Vapour Compression Refrigeration System Using
Eco Friendly Refrigerants of Low Global Warming Potential”, International Journal of Scientific and Research Publications,
Volume 2, Issue 9, ISSN 2250-3153, pp: 1-8.
[22]. Almeida I. M. G., Barbosa C. R. F., Fontes F. A. O., December 2010, “THERMODYNAMIC AND THERMOPHYSICAL
ASSESSMENT OF HYDROCARBONS APPLICATION IN HOUSEHOULD REFRIGERATOR”, Engenharia Térmica
(Thermal Engineering), Vol. 9, N o 01 e 02, pp. 19-27,
[23]. Meyersen K., 1996, “HC REFRIGERANT PRODUCTS TRAINING MANUAL”, Northcutt, Inc 5055 N. Broadway, PP: 1 -50.
[24]. Wongwises S., Chimres N., 2005, “ Experimental study of hydrocarbon mixtures to replace HFC-134a in a domestic refrigerator”
Energy Conversion and Management 46, PP: 85–100.
[25]. Khurmi R. S., Gupta J. K., “Refrigration and Air Conditioning” publish by S. Chand, Revised Edition.

www.theijes.com The IJES Page 37