You are on page 1of 44

i-on30EX

i-on30EXD
Security System
Installation Guide

Issue 6
i-on30EX/EXD

© Eaton’s Security Business. 2014


IN NO EVENT WILL EATON’S SECURITY BUSINESS BE LIABLE FOR ANY SPECIAL, CONSEQUENTIAL , OR INDIRECT LOSS OR
DAMAGE, INCIDENTAL DAMAGES, STATUTORY DAMAGES, EXEMPLARY DAMAGES, LOSS OF PROFITS, LOSS OF REVENUE,
LOSS OF ANTICIPATED SAVINGS, LOSS OF BUSINESS OR OPPORTUNTIY, LOSS OF GOODWILL OR INJURY TO
REPUTATION, LIQUIDATED DAMAGES OR LOSS OF USE, EVEN IF INFORMED OF THE POSSIBILITY OF SUCH DAMAGES.
EATON’S SECURITY BUSINESS’S LIABILITY FOR DAMAGES ARISING OUT OF OR RELATED TO A PRODUCT SHALL IN NO
CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT FROM WHICH THE CLAIM ARISES. TO THE EXTENT PERMITTED
BY APPLICABLE LAW, THESE LIMITATIONS AND EXCLUSIONS WILL APPLY WHETHER EATON’S SECURITY BUSINESS’S
LIABILITY ARISES FROM BREACH OF CONTRACT, BREACH OF WARRANTY, TORT (INCLUDING BUT NOT LIMITED TO
NEGLIGENCE), STRICT LIABILITY, BY OPERATION OF LAW, OR OTHERWISE.

Every effort has been made to ensure that the contents of this book are correct. The contents of this book
are subject to change without notice.
This manual applies to the i-on30EX and i-on30EXD control units with version 4.04 software.
For Your Safety
This book contains several passages alerting you to potential problems or hazards. Each of these are
marked by the words Note, Caution or WARNING.:
Note: Describes conditions that may affect the proper functioning of the equipment (but will not
damage the equipment).
Caution: Describes actions that will physically damage the equipment and prevent its proper
function.
WARNING: Describes actions that are hazardous to health, or cause injury or death.
Please pay particular attention to these marked passages.
Other Publications for the i-on30EX:
The following guides are available from the Eaton’s Security Business website: www.coopersecurity.co.uk
Quick User Guide Brief instructions for setting and unsetting alarm systems based on i-
on control units.
i-onEX Range Engineering Guide A detailed description of the Installer’s programming options
available for i-on control units.
i-onEX Range Administrator and Detailed notes for the system administrator of an alarm system
User’s Guide based on the i-on40, i-on30EX/EXD, i-on50EX/EXD and i-on160EX.
Eaton’s Security Business Instructions for how to installer Eaton’s Security Business
Downloader Quick Guide Downloader on your PC or laptop, and connect to i-on Control Units.
i-on Updater Utility Installation and Instructions on how to install i-on Updater on your PC and use it to
User Guide update the software on your i-on40, i-on30EX/EXD, i-on50EX/EXD
and i-on160EX control unit.

Page ii
i-on30EX/EXD

Step 10. Fit and Connect Battery ..................... 26


CONTENTS Step 11. Initial Power-Up ...................................... 27
1. Introduction ....................................................... 1 Transferring to Another Keypad ................... 28
Communications ................................................. 1 Leaving the Installer Menu ........................... 28
Level Setting or Partitioned System ................... 1 Important! Saving Changes ......................... 29
Installer Programming Interface ......................... 2 Alerts After Leaving Installer Mode .............. 29
About this Guide ................................................. 2 Re-Entering the Installer Menu .................... 29
2. Before You Begin .............................................. 3 Defaulting Access Codes ............................. 29
Preparation ......................................................... 3 Restoring Factory Defaults Only .................. 30
Radio Site Survey .......................................... 3 Step 12. Commission the System .................... 31
Siting the Control Unit and Wired Zone Install Detectors and Other Peripherals ....... 31
Expanders ...................................................... 3 Program the System .................................... 31
Siting Keypads ............................................... 3 Handover to the User ................................... 31
Siting Wireless Zone Expanders .................... 3 Installer Menu ................................................... 32
Guided Tour........................................................ 4 4. Maintenance .................................................... 34
Opening the Control Unit Case ...................... 4 Replacing or Removing Wired Keypads ...... 34
i-kp01 Controls and Displays ......................... 7 5. Technical Specification .................................. 35
Opening the i-kp01 Keypad ........................... 7 General ............................................................. 35
Expanders ...................................................... 9 Capacities ......................................................... 35
Power Availability ............................................. 12 Security ............................................................. 35
Bus Cabling Requirements ............................... 12 Power Supply ................................................... 35
Cable Type ................................................... 12 EN50131-6 ratings ....................................... 36
Cable Segregation ....................................... 12 Electromagnetic Compatibility .......................... 36
Cable Configuration and Length .................. 12 Outputs ............................................................. 36
Bus Termination ........................................... 13 Sounder Volume Levels (at 1m) .................. 36
Voltage Drop ................................................ 13 Fuses ................................................................ 36
3. Installation ....................................................... 15 Electrical Safety ................................................ 36
Caution: Static Electricity ............................. 15 Other ................................................................. 36
Step 1. Fit the Control Unit Case...................... 15 Radio Expander and Keypads ..................... 36
Fitting ........................................................... 15 Compliance Statements ................................... 37
Step 2. Run Bus Cable ..................................... 15 Compatible Equipment ..................................... 37
Step 3. Fit and Connect the Keypad(s) ............ 15 HUD ............................................................. 37
Siting the Keypad(s) ..................................... 15 Detectors ...................................................... 37
Fitting Keypads ............................................ 15 Sounders ...................................................... 37
Keypad Addressing ...................................... 16 Setting / Unsetting – Keypads...................... 37
Backlight Control for i-KP01 ......................... 16 Setting / Unsetting - Fobs ............................ 37
Backlight Control for KEY-K01/KP01/KPZ01 16 Communicators ............................................ 37
Tone Volume – All Keypads......................... 18 Accessories .................................................. 37
Engineering Keypad ..................................... 19
Step 4. Fit and Connect Expanders ................. 19
Connecting an Expander to the Bus ............ 19
Addressing Expanders ................................. 19
Expander Loudspeakers .............................. 19
Step 5. Connect Control Unit to Mains ............. 19
Mains Cabling .............................................. 19
Step 6. Connect Wired Zones .......................... 19
Four Wire Closed Circuit Connections ......... 19
Two-Wire Closed Circuit Connections ......... 20
Fully Supervised Loop Connections ............ 20
Step 7. Connect Wired Outputs........................ 22
Control Unit Wired Outputs .......................... 22
Wired External Sounders (Optional) ............ 22
Wired Outputs on Expanders ....................... 22
Wired External Sounders on Expanders ...... 22
Remote Loudspeakers (Optional) ................ 23
Output on KEY-KPZ01 ................................. 23
Step 8. Connect the Internal Communicator (i-
on30EXD only) ................................................. 24
Statutory Information .................................... 24
Safety Notice .................................................... 24
Connecting the Telephone Line ................... 25
Fit ADSL Filter .............................................. 25
Step 9. Fit a Plug-By Communicator ................ 26

Page iii
i-on30EX/EXD

This page is intentionally blank.

Page iv
i-on30EX/EXD

external siren, 4 button remote control, and


1. Introduction remote radio keypad.
This control unit is designed and approved to be
The i-on30EX is a control unit for a hybrid
used as part of a Security Grade 2 system.
wired/wirefree alarm system intended for
commercial or large domestic use. The i-
on30EXD variant contains an internal
Communications
communicator. The i-on30EXD version of the control unit contains
The control unit comprises a steel case containing a built-in ATS2 communicator, allowing it to
the control unit PCB (printed circuit board), power comply with EN50131 at Security Grade 2.
supply and space for a 7Ah backup battery. The i-on30EX/EXD also provides sockets for an
The control unit PCB provides terminals for a add-on communication module. The available
single bus. The bus allows you to connect up to modules are:
10 peripheral devices using standard four wire i-dig02 A switched telephone network
alarm cable. The peripheral devices can be any (ATS2) (PSTN) module that allows the
mixture of keypads, zone expanders (for wireless control unit to report alarm
or wired detectors) or remote power supplies. information using standard
Note that only two of the 10-zone expanders protocols such as Fast Format, SIA
connected to the system can have detectors and Contact ID, and can also send
associated with them. Similarly, only one 30-zone text messages over the Public
expander can have zones allocated to it. Switched Telephone Network
The control unit PCB also provides a range of (PSTN). The i-dig02 also allows
connectors for outputs, communicators, and up to remote maintenance using Eaton’s
10 Fully Supervised Loop (FSL), or 10 two-wire Security Business Downloader
Closed Circuit Loop (CCL) or five four-wire CCL software.
zones. i-sd02 A speech dialler and PSTN module
The i-on30EX/EXD at release 4 uses i-kp01 (ATS2) that allows the control unit to send
keypads with software revision 2.0 and above. recorded speech messages and
The keypads allow end users to set and unset the report alarm information using
system, and the installer to configure the control standard protocols such as Fast
unit. The i-kp01 keypad also contains an integral Format, SIA and Contact ID. The
proximity tag reader, allowing end users to control module can also send text
the system without having to remember access messages over the PSTN. The i-
codes. sd02 also allows remote
maintenance using Eaton’s Security
Note that to work correctly the i-on30EX or i- Business Downloader software.
on30EXD must be fitted with at least one wired
keypad. i-gsm02 A GSM module that allows alarm
(ATS2) reporting, speech messaging and
There are three other types of keypad available SMS text messaging over the
for connection to the i-on30EX/EXD: mobile phone network. Note that a
KEY-K01 This keypad has no internal prox SIM card is not included with the
reader, and is supplied in a square module.
format case. Note: Fitting a plug on module disables the
KEY-KP01 This product, supplied in the same internal communicator in the i-on30EXD.
case as the KEY-K01, has an The control unit also provides outputs that can be
internal prox reader and also used to fit a “plug by” communicator.
provides terminals for an external
prox reader (KEY-EP) Level Setting or Partitioned
KEY-KPZ01 This product, supplied in the same System
case as the KEY-K01, has an
internal prox reader and also The i-on30EX/EXD offers two basic ways of
provides terminals for up to two behaving as an alarm system:
zones, a programmable output, and Part Setting. In a Part Setting system the i-
an external prox reader (KEY-EP) on30EX/EXD can set in one of four ways: either
A range of wireless peripherals is available for Full set or three varieties of Part Set. In Full set
operation with the wireless expanders. The range the control unit pays attention to all detectors. In
includes a door contact/universal transmitter, a each of the three Part Sets the control unit ignores
passive infra red detector, smoke detector, detectors that do not have the appropriate Part
Set attribute.

Page 1
Introduction i-on30EX/EXD

Partitioned System. In a Partitioned system the i-


on30EX/EXD provides the equivalent of 4,
smaller, independent alarm systems. Each system
is a “Partition” of the i-on30EX. You can allocate
any zone to each Partition. Each zone can also
belong to more than one Partition. Each Partition
can have a Full Set level and one Part Set level.
During installation the installer can allocate
keypads, sounders or outputs to any of the
partitions.
For a detailed description of the Installer’s
programming menu please read i-on Range
Engineering Guide available from
www.coopersecurity.co.uk.

Installer Programming
Interface
Once fitted and powered up, you can program the
control unit through any wired keypad connected
to the bus cable. The Installer Menu allows you to
specify all the operating parameters for an
individual installation.
If you wish, you can also connect a PC or laptop
to the mini USB port on the control unit PCB and
use Eaton’s Security Business’s Downloader
software to program the control unit.
Note: Some programming options can make the
installation non-compliant with EN50131. The
relevant options are noted in the “Installer Menu”
section of the i-on Range Engineering Guide.

About this Guide


This guide shows the simple procedure required
to physically install the control unit, connect
keypads, expanders and power supplies and
power up the system for the first time.
When you have completed the physical
installation please consult the i-on Range
Engineering Guide for details of configuring the
system to meet your customer’s requirements. For
your convenience page 32 of this installation
guide contains a condensed reference table of the
Installer menu.

Page 2
i-on30EX/EXD

Siting the Control Unit and Wired Zone


2. Before You Begin Expanders
Do site the unit:
Preparation Upright, battery at the bottom. (This does not
Before installation you should carry out a survey apply to the wired zone expander.)
of the site. You need to know how many and what Within a protected zone.
kind of detectors will be monitored by the control
Do NOT site the unit:
unit. You also need to assess where any radio
expanders must be placed in order to receive In the entry or exit zones, or outside the area
radio signals from their detectors successfully. covered by the alarm system.
Radio Site Survey Next to electronic equipment, particularly
computers, photocopiers or other radio
If you intend to fit radio expanders you should equipment, CAT 5 data lines or industrial
conduct signal strength tests. Eaton’s Security mains equipment.
Business produces the Scantronic 790r hand held
signal strength meter and 734r-01 test transmitter Siting Keypads
for this purpose. Please read the 790r manual for Do site the keypad:
details.
Within the area protected by the alarm
Please be aware of the following: system.
 The 790r signal strength meter readings At a convenient height and location for the
should be used only as an guide when initially user.
checking the site. Out of sight of potential intruders.
 A reading of four green LEDs or higher Do NOT site the keypad:
indicates an acceptable signal strength.
Next to electronic equipment, particularly
 Once you have installed the alarm system you
computers, photocopiers or other radio
should put the control unit in the Installer test
equipment, CAT 5 data lines or industrial
menu and test the received signal strength
mains equipment.
from each radio transmitter.
Where the cable run will exceed the capacity
 A signal strength reading of two or more units
of the bus, see page 12.
by the control unit from each transmitter
should provide reliable operation in the If fitting two or more keypads make sure that you
installed system. (Note: if you take the signal place the keypads more than one metre apart
strength using Eaton’s Security Business from each other, or from any other type of prox
Downloader while the panel is in user mode reader. (At less than one meter separation the
then the minimum acceptable signal strength proximity tag readers will interfere with each
is four units. Ensure that the control unit is in other.) Remember not to place keypads or
Installer mode when reading signal strengths external prox readers on opposite sides of the
remotely.) same wall.
 When you record the signal strength readings If you intend to fit external prox reader KEY-EP to
for later inspection, you should record the a KEY-KPZ01/KP01, then do not site the external
readings taken from the control unit of the prox reader itself closer than one meter to any
installed system while it is in the Installer other keypad or other type of prox reader.
Menu.
Siting Wireless Zone Expanders
Please be aware that the signal strength received
from a transmitter can change after installation Do site the unit:
because of local environmental changes. For Upright.
example, users switching on laptops nearby, or
moving metal cabinets from their original position Within a protected zone.
can all affect the signal from a transmitter. Please As high as possible. However, do make sure
read Eaton’s Security Business publication that the unit is on a similar level to the
”Guidance Notes for Wireless Alarm System transmitters or receivers.
Installations” obtainable from More than 10m from another radio expander.
www.coopersecurity.co.uk for more information Do NOT site the unit:
about the factors affection radio signal strength.
In the entry or exit zones, or outside the area
covered by the alarm system.
Close to or on large metal structures.
Closer than one metre to mains wiring, metal
water or gas pipes, or other metal surfaces.

Page 3
Before You Begin i-on30EX/EXD

Lower than two metres from the floor (ideally).


Inside metal enclosures.
Next to electronic equipment, particularly
computers, photocopiers or other radio
equipment, CAT 5 data lines or industrial
mains equipment.
Note: Some window glasses, especially those
sold as “insulating” or “energy conserving” may be
coated with thin metal or conducting films. These
glasses are particularly poor at transmitting radio
waves.

Guided Tour
CAUTION: All printed circuit boards for the i-
on30EX, its expanders and keypads have been
tested for Electromagnetic Compatibility (EMC).
However, when handling the PCBs you must take
the standard precautions for handling static
sensitive devices.
Opening the Control Unit Case
To gain access to the interior of the control unit
undo the screws at the top and bottom of the lid.
Slide the lid out and away from the case.
WARNING: When connected to the mains with
power applied mains voltages are present on the
shrouded heads of the terminal screws of the
mains connector.

Page 4
i-on30EX/EXD Before You Begin

1. Case back.
2. Fixing holes.
3. Cable entry holes for detector
and keypad wiring.
4. Transformer.
5. Fused mains fuse and
connector block.
6. Mains cable anchor point.
7. Cable entry hole for mains
supply.
8. Printed circuit board (PCB).
9. Cable entry holes for
loudspeakers, siren/strobes and
communicators

Figure 1 Control Unit

1. Connectors for system bus.


2. Zone-, output-, and Aux power
connectors.
3. Plug by output connectors.
4. Tamper switch.
5. ADSL filter pins. (i-on30EXD only.)
6. On board communicator connections.
(i-on30EXD only.)
7. Off-hook LED. (i-on30EXD only.)
8. USB socket (Mini B).
9. Sockets for plug on module.
10.Loudspeaker, Bell and Strobe
connectors.
11. Comms activity LED. (i-on30EXD
only.)
12. Reset Codes pins.
13. Heartbeat LED.
14. Kickstart pins.
15. Battery connectors.
16. RS485 terminator.
17. Engineering keypad connector.
18. 20Vac connector.

Figure 2 Control Unit Printed Circuit Board

Page 5
Before You Begin i-on30EX/EXD

1. Built-in communicator telephone


line connector. (i-on30EXD only.)
2. Siren and strobe.
3. Loudspeaker.
4. Bus cable connector.
5. Output (transistorised).
6. Aux power.
7. Wired zone connectors.

Figure 3 Control Unit Main Connectors

Page 6
i-on30EX/EXD Before You Begin

i-kp01 Controls and Displays 3

1 1
2
3 2
8
4 3
5
7 4

1. LCD display (2 x 20 characters). 1. Central keyhole.


2. Programming keys. 2. Rear tamper shroud.
3. Navigation keys 3. Cable entry.
4. Alert LEDs 4. Fixing holes.
5. Setting and unsetting keys. Figure 6 Keypad Rear Housing
6. Programmable HUA keys.
7. Number/text keys.
8. Set/Unset LEDs.
Figure 4 Controls and Displays
Opening the i-kp01 Keypad
Note: For EN50131-3:2009, 8.7 the keypad is a
type B ACE, fixed.
To open the keypad first gently prise off the trim
on the front and remove the two screws. Next,
carefully lever the front of the keypad (containing
the PCB and display) away from the keypad rear
housing.

4
1. Sounder.
3 2. Sounder volume control.
3. Tamper switch.
4. Jumpers for LED function:
5. RS485 termination jumper
Figure 5 Opening the Keypad 6. Connector for control unit (note that the ET
terminals are inactive).
Figure 7 Keypad PCB

Page 7
Before You Begin i-on30EX/EXD

KEY-K01 and KEY-KPZ01 Controls and 3


Displays

1
2
3 2
1

Figure 9 Opening the Keypad


4
7

5 6 5
1. LCD display
2. Programming keys.
3. Navigation keys. This key has built-in alert
LEDs.
4. Setting and unsetting keys. The ABCD
keys have built-in status LEDs that can show
1. Central keyhole.
the setting status of a part setting system.
2. Fixing holes.
These LEDs can be disabled, see page 16.
3. Cable entry.
5. Plastic caps covering screws (shown
4. Tamper block
closed and open). Figure 10 Keypad Rear Housing
6. Hold Up Alarm (HUA) keys.
7. Number/text keys.
Figure 8 KEY-K01/KP01/KPZ01 Controls and
Displays
Opening the KEY-K01/KP01/KPZ01
To open the unit, unclip the caps covering the
screws on the front. (You may need to gently push
the bottom edge of the caps in with the end of a
small screwdriver to start them.) Remove the two
screws hidden underneath (see Figure 8). Gently
swing the lower side of the front out from the back
box by about 10mm and then slide the front
upwards to disengage the top catches. (Be careful
not to pull the lower side of the front more than 1. Jumpers for addressing and LED function:
about 25mm away from the back while the top 1a Addressing (not used for i-onEX)
catches are engaged, or you may break the 1b LED functions
catches.) 2. Sounder volume control.
3. Tamper switch.
4. Sounder.
5. Connector for control unit.
Figure 11 KEY-K01 Keypad PCB

Page 8
i-on30EX/EXD Before You Begin

1. Tamper switch.
2. Sounder.
3. Connector for KEY-EP.
4. Sounder volume control.
5. Connector for control unit bus.
6. Jumpers for:
6a Addressing (not used in i-onEX
control units).
6b LED functions and RS485 bus
termination.
Figure 12 KEY-KP01 Keypad PCB

1
2
2 3 6a
4
BRIGHT 6b
3 TERM

4 5

Z1 Z2 0V 12V D0 D1 LED 0V 12V A B OP


EXT READER

1. Tamper switch.
2. Sounder.
3. Connector for KEY-EP. Terminals for
zones
4. Sounder volume control
5. Connector for data bus and output
terminal.
6. Jumpers for addressing and LED function:
6a Addressing (not used in i-onEX
control units)
6b LED functions and RS485 bus
termination.
Figure 13 KEY-KPZ01 Keypad PCB
Expanders
To open any of the expander cases undo the
single screw, pull the top of the lid away from the
case and then lift out.
Figures 14, 16 and 15 show the interior of the
wired and radio expanders.

Page 9
Before You Begin i-on30EX/EXD

1 1. Cable entry (also behind PCB).


2 2. Central keyhole.
3. PCB.
1
1 4. Relay card (i-rc01) connector.
3 5. Aux power.
4 19 6. Link to enable/disable front/rear
18 tamper switch.
5 7. Lid tamper (rear tamper behind
6 17 pcb).
8. Zone connectors
7 1
9. Bus termination jumper.
1 16 10. Fixing holes.
11. Addressing button.
8 12. Engineering keypad connector
15 13. Bus cable connector.
14. Sounder.
14 15. Zone connectors.
9
16. Bus address display.
17. Aux power.
10 10
18. Loudspeaker connectors.
19. Outputs.

11 12 13
Figure 14 EXP-W10 Wired Expander

1
1. Cable entry (also behind PCB).
2 2. Central keyhole.
1 3. PCB.
1 4. Relay card (i-rc01) connector.
3
19 5. Aux power.
4 6. Link to enable/disable front/rear
5 18 tamper switch.
7. Lid tamper (rear tamper behind pcb).
6 17
8. Zone connectors
7 1 9. Bus termination jumper.
10. Fixing holes.
1 16 11. Engineering keypad connector.
12. Addressing button.
8 15 13. Bus cable connector.
14. Sounder.
9 15. Zone connectors.
14 16. Bus address display.
17. Aux power.
10 10 18. Loudspeaker connectors.
19. Outputs.

11 12 13
Figure 15 EXP-WCC Wired Expander

Page 10
i-on30EX/EXD Before You Begin

2
3
1. Cable entry (also behind PCB).
1 1 2. Antenna.
3. Central keyhole.
4 4. PCB.
5. Link to enable/disable front/rear
tamper switch.
1 6. Lid tamper (rear tamper behind
PCB).
1 7. Bus termination jumper.
5
8. Addressing button.
6 14 9. Fixing holes.
10. Engineering keypad connector
7 11. Bus cable connector.
13 12. Sounder.
8
13. Loudspeaker terminals.
12 14. Bus address display.
9 9

10 11
Figure 16 EXP-R10/R30 Radio Expander

Page 11
Before You Begin i-on30EX/EXD

Note: All current drawn from the Aux terminals


Power Availability (12V) must be included in the overall calculation.
Before connecting any external devices to the CAUTION: Ensure that the system does not
control unit, you must make sure that the control demand more than the maximum current available
unit can provide sufficient current to power the from the control unit during an alarm, see page
system during a mains failure for the time required 35.
to meet the appropriate standard.
EN51031-1 Grade 2 and PD6662 Grade 2 both Bus Cabling Requirements
require 12 hours standby time.
Cable Type
Note: When calculating the average load during In general, the control unit requires standard 7/0.2
the standby time period you must allow for at least un-screened four core alarm cable for wiring the
two periods in alarm. To take the worst case these bus.
two periods of alarm should each be 15 minutes
For maximum performance in harsh environments
long, the maximum permitted in EN50131-1
use twisted pair screened cable with a
section 8.6.
characteristic impedance of 100-120ohms eg:
The amount of current available from the control Belden 8132 or cable designed for RS485.
unit depends on the size of battery fitted and its
Use one pair for data lines A and B. Use the other
health. The current taken by the control unit PCB,
pair for 12V and 0V. For optimum performance
communicator and keypads is given in Technical
the voltage at the keypads and expanders should
Specifications – EN50131-6 Ratings on page 35.
be greater than 12V.
The following calculation shows a simplified
Screened cable may prove necessary if the
example: in an alarm system with an i-
installation site has equipment that produces high
on30EX/EXD control unit, two i-kp01 keypads,
levels of R.F. (Radio Frequencies). For example,
and 15 wired PIRs the system takes the following
welding equipment is known to produce a large
total quiescent current:
amount of radio interference. If screened cable is
Device Current required, you should keep to the following
Control unit PCB 100mA guidelines:
15 x PIRs at 15mA each 225mA 1. Avoid earth loops by connecting the screen on
1 x (wired expander) 20mA the cable to mains earth at the control unit but
2 x i-kp01 at 30mA each 60mA not at the keypad or expander.
(backlights off) 2. The continuity of the cable screen is most
Siren (quiescent) 25mA important and screens MUST be continuous
along the full length of the cable.
Total 430mA
During an alarm, these figures become: 3. Where the cable enters any metal enclosure,
ensure the screen is isolated from the case.
Device Current
Cable Segregation
Control unit PCB 120mA
15 x PIRs at 15mA each 225mA Segregate the bus cabling from any other wiring,
1 x (wired expander) 20mA such as mains supply cables, telephone cables,
computer network cables and R.F. cables. Use
2 x i-kp01 at 60mA each 120mA cable ties to keep cables separated.
(backlights off)
Siren (in alarm) 400mA Keep the bus cable clear of cables supplying
sounders, extension loudspeakers or any other
Total 885mA
high current devices.
The total amp hours required =
Cable Configuration and Length
(0.430 A x 11.5h) + (0.885A x 0.5h) = 5.39Ah
You can connect up to 10 devices to the control
One new, fully charged, 7Ah battery can provide
unit bus. You may connect the devices either in
the charge required by the example system and
daisy chain (serially), or in star (parallel)
would meet the Grade 2 requirements.
configuration at the control unit connector.

Page 12
i-on30EX Before You Begin

Figure 17 Bus Wiring Configurations


For star configurations the cable length from fit the termination jumper at the devices on
control unit to the most distant bus device should the end of each arm.
be kept short, and should not exceed 100m. If there are more than two arms AND two
There should be no more than four arms in the cables are long while the remaining cables
star. are short (less than 10m) then it is possible to
For a daisy chain configuration the total cable terminate at the two devices on the ends of
length should not exceed 1,000m. the long cables.
If there are more than two arms BUT each
Bus Termination
cable is more than 10m then DO NOT fit the
The i-on30EX/EXD bus uses the RS485 interface. termination jumpers on any of the devices.
Because of this the ends of the line in some
Voltage Drop
configurations may be terminated to improve
performance in electrically noisy environments or In order for the system to work correctly, the
where there are long cable runs. The control unit. voltage at each device must NOT drop below
expanders and keypads have a termination link on 10.5V even when running on the standby battery.
their PCBs (see 16 in Fig 2 for the control unit, 5 Eaton’s Security Business recommends that the
in Fig 7 for the keypad, 12 in Fig 14 for the wired voltage at each device should stay above 12V.
expander and 11 in Fig 16 for the radio expander).
Standard 7/0.2 alarm cable has a resistance of 8
Fitting a jumper to the pins adds a termination to
Ohms per 100m per core. The voltage drop is
the cable.
calculated using the following formula: V Drop =
In a daisy chain configuration fit the termination Current drawn x cable length x 0.08 x 2.
jumpers in the devices at each end of the chain
Table 1 shows the voltage drop against the
(see Fig 17 ).
current drawn and cable length.
In a star configuration:
The shaded area shows where the voltage drop
If there are only two arms on the star then this would cause the bus voltage to fall from 13.8V to
is the same as a daisy chain configuration below 12.0V when using a single core.
(see “Daisy Chain 1” in Figure 17). If required

Page 13
Before You Begin i-on30EX/EXD

Table 1. Voltage Drop


Current Cable Length (Standard 7/0.2 alarm cable)
Drawn
10m 20m 30m 40m 50m 60m 70m 80m 90m 100m
60mA 0.10V 0.19V 0.29V 0.38V 0.48V 0.58V 0.67V 0.77V 0.86V 0.96V
80mA 0.13V 0.26V 0.38V 0.51V 0.64V 0.79V 0.90V 1.02V 1.15V 1.28V
100mA 0.16V 0.32V 0.48V 0.64V 0.80V 0.96V 1.12V 1.28V 1.44V 1.60V
120mA 0.19V 0.38V 0.58V 0.79V 0.96V 1.15V 1.34V 1.54V 1.74V 1.92V
140mA 0.22V 0.45V 0.67V 0.90V 1.12V 1.34V 1.57V 1.79V 2.02V 2.24V
160mA 0.26V 0.51V 0.77V 1.02V 1.28V 1.54V 1.79V 2.05V 2.30V 2.56V
180mA 0.29V 0.58V 0.86V 1.15V 1.44V 1.73V 2.02V 2.30V 2.59V 2.88V
200mA 0.32V 0.64V 0.96V 1.28V 1.60V 1.92V 2.24V 2.56V 2.88V 3.20V
220mA 0.35V 0.70V 1.06V 1.41V 1.76V 2.11V 2.46V 2.82V 3.17V 3.52V
240mA 0.38V 0.79V 1.15V 1.54V 1.92V 2.30V 2.69V 3.07V 3.46V 3.84V
260mA 0.42V 0.83V 1.25V 1.66V 2.08V 2.50V 2.91V 3.33V 3.74V 4.16V
280mA 0.45V 0.90V 1.34V 1.79V 2.24V 2.69V 3.14V 3.58V 4.03V 4.48V
300mA 0.48V 0.96V 1.44V 1.92V 2.40V 2.88V 3.36V 3.84V 4.32V 4.80V
320mA 0.51V 1.02V 1.55V 2.05V 2.56V 3.07V 3.58V 4.10V 4.61V 5.12V
340mA 0.54V 1.09V 1.63V 2.18V 2.72V 3.26V 3.81V 4.35V 4.90V 5.44V
360mA 0.58V 1.15V 1.73V 2.30V 2.88V 3.46V 4.03V 4.61V 5.18V 5.76V
380mA 0.61V 1.22V 1.82V 2.43V 3.04V 3.65V 4.26V 4.86V 5.47V 6.08V
400mA 0.64V 1.28V 1.92V 2.56V 3.20V 3.84V 4.48V 5.12V 5.76V 6.40V
Reducing Voltage Drop - Method 1: Remote Power Supplies
Double up the supply connections (12V and 0V), When you cannot reduce voltage drops by
which will halve the resistance on each core and method 1 or 2, or the demand on the control unit
therefore halve the voltage drop. When using power supply exceeds its capacity (see Technical
Table 1 to calculate the expected voltage drop, Specifications –page 35), you should install one or
simply divide the voltage drop for a single core by more remote power supplies. The supply must
two. have a "floating zero Volt rail" if connected to the
bus, otherwise an earth fault will occur. Eaton’s
Reducing Voltage Drop - Method 2:
Security Business recommends the EXP-PSU.
Supply the detection devices from the Aux output
When installing a remote power supply, fit it close
on separate cores. This is the preferred method of
to the equipment it is powering.
reducing voltage drop as detectors generally
operate at lower voltages (9.5V). When using this Figure 18 shows the recommended method of
method, the bus cable must have at least two connecting a remote power supply.
spare cores.

Figure 18. Connecting Remote Power Supply Units

Page 14
i-on30EX/EXD

KEY-EP, or prox readers used by other systems


3. Installation (for example access control systems). If you
mount prox readers closer together than one
Note: The installation steps listed below assume meter (including on the other side of walls) then
that you have already decided on the required the two prox readers will interfere and may not
number and location for all keypads, expanders work correctly.
and power supplies.
Fitting Keypads
Caution: Static Electricity
Select which cable entry you are going to use and
Like many other electronic products, the control break out the appropriate plastic sections.
unit, keypads and expanders contain components
Use 4mm x 25mm countersunk screws with a
that are sensitive to static electricity. Try not to
thread suitable for the wall material in at least
handle their PCBs directly. If you must handle a
three fixing holes when mounting the back of the
PCB, take the standard precautions against
keypad on the wall.
damage by static electricity.
i-KP01
Step 1. Fit the Control Unit For i-KP01 keypads on Grade 3 systems drill out
the hole for the back tamper using a 7mm bit (see
Case Figure 19).
Fitting
To prevent access to the inside of the control unit
through the holes in the rear of the case you must
mount the control unit on a wall or other flat
surface.
Mount the case vertically, as shown in Figure 1.
Use all three fixing holes. Use No8/M4 dome or
pan head screws at least 30mm long, inserted into
wall anchors appropriate for the type of wall.
Figure 1 shows the fixing holes and cable entries.
Protect the unit from dust and drilling debris when
drilling the fixing holes.
Figure 19 Screw i-KP01 Back Box to Wall
Step 2. Run Bus Cable KEY-K01/KP01/KPZ01
Please read “Cabling Requirements on page 12. Make sure the backplate is level and mark, drill
and plug at least three fixing holes. Screw the
Step 3. Fit and Connect the backplate to the wall through the fixing holes
using the M4 screws.
Keypad(s)
Siting the Keypad(s)
Do site the keypad(s):
Within the area protected by the alarm
system.
At a convenient height and location for the
user.
Out of sight of potential intruders.
Do NOT site the keypad(s):
Next to electronic equipment, particularly
computers, photocopiers or other radio
equipment, CAT 5 data lines or industrial
mains equipment.
Where the cable run from the control unit will
be longer than 100m (see Cable
Configuration and Length).
Note: Do not fit any keypad with an internal prox Figure 20 Screw KEY-K01/KEY-KPZ01 Back Box
reader closer than one meter to any other type of to Wall
prox reader. This includes other keypads with
prox readers, external prox readers such as the

Page 15
Installation i-on30EX/EXD

Connection on the keypad pcb (see 1b in Figure 11 or 6b in


Figure 21 shows the wiring connections at the Figure 13).
keypad and control unit.
Jumper OFF The keypad backlights glow at
normal intensity.
Jumper ON The keypad backlights glow extra
bright.
To program whether the backlights are on or off
see below.
Programming Backlight, ABCD LEDs and
Navigation Key LEDs
You can set the function of the backlights in either
of two ways:
a) Use the Installer Menu – Detectors/Devices –
Wired Keypads – Edit Keypad – (Keypad n) –
Backlight option. See the Engineering Guide for
Figure 21 Connecting a Keypad to the Bus more details.
Keypad Addressing b) Enter a local keypad programming mode (this
The control unit assigns addresses to all devices replaces the use of jumpers on the keypad PCB in
connected to the bus cable. You must start this the i-kp01).
process off once all bus devices are connected, In addition, the local keypad programming mode
during the initial power up. See page 27 for allows you to enable or disable the LEDs in the
instructions. ABCD keys and the Navigation key.
Backlight Control for i-KP01 It is possible to enter keypad programming mode
You can control the appearance of the keypad when the keypad is not connected to a control
backlights and set/unset LEDs by fitting links over unit, but simply powered by 12VDC connected to
the appropriate jumpers on the keypad PCB (see the keypad bus terminal (see Figures 11 and 13).
Figure 7 on page 7 for the position of the If the keypad IS connected to a control unit then
jumpers). make sure that the control unit is in Installer Menu
before entering the keypad’s local programming
The jumpers have the following functions: mode.
ABCD-ON
ABCD-ON
ABCD-ON The set/unset LEDs
ABCD-ON
ABCD-ON Entering Local Programming Mode
are disabled.
1. Apply 12Vdc to the keypad.
The set/unset LEDs
ABCD-ON
ABCD-ON shows the setting 2. Enter Installer Menu on the
ABCD-ON status of the system.
ABCD-ON
ABCD-ON control unit, if the
(Full set is the left keypad is connected to a
hand LED.) See Note system.
below.
3. Open the keypad tamper.
ON ON
BACKLIGHT
BL BRIGHT
BRIGHT The key backlights are
BACKLIGHT ON 4. Press and hold down B and
ON
BACKLIGHT
BL ON
BRIGHT disabled. They will
BRIGHT
BRIGHT  together for at
glow briefly for five
least two seconds.
seconds when a user MENU
presses a key. The keypad is now in local ABCD 
BACKLIGHT ON
BL ON
BRIGHT programming mode,
BRIGHT
BACKLIGHT ON
The key backlights the display shows the
ON
BACKLIGHT ON
BL BRIGHT
BRIGHT
glow all the time at current status.
BRIGHT
normal intensity.

BACKLIGHT ON The keypad backlights To Switch ABCD LEDs ON or OFF


BL ON
BRIGHT glow all the time, extra MENU
BRIGHT ON bright. 1. Enter local programming
BACKLIGHT ON ABCD 
BACKLIGHT
BL ON
BRIGHT mode (see above).
To BRIGHT
Note:BRIGHT
comply with PD6662:2010 at Grade 2,
disable the ABCD LEDs. 2. Press  or  to enable or
disable the ABCD LEDs.
Backlight Control for KEY-K01/KP01/KPZ01 The character at the right of
You can control the brightness of the keypad the display shows “” when
backlights by fitting links over the BRIGHT jumper the LEDs are disabled and MENU
“” when the ABCD 

Page 16
i-on30EX/EXD Installation

LEDs are enabled. For mode. ABCD 


example: MENU
2. Press  repeatedly until
STATUS FLT LED 
3. Leave local programming the display shows:
mode and save your
changes (see page 17). 3. Press  repeatedly to
select one of the
following:
To Change Backlight Settings
Status Fault LED ON (). MENU
1. Enter Local Programming MENU
STATUS FLT LED 
ABCD 
mode (see above) MENU
Status Fault LED OFF
STATUS FLT LED 
2. Press . The display shows MENU ().
BACKLIGHT 
the current status of the The red Fault LED under
backlight LEDs, for the navigation key is
example: disabled, and will not
3. Press  repeatedly to select glow for any fault reports.
one of the following: 4. Leave local programming
Backlight LEDs ON (). MENU mode and save your
BACKLIGHT  changes (see below).
Backlight timed (). MENU
BACKLIGHT 
The backlight will glow for
12 seconds after the last To Leave Local Programming Mode
keypress. The action of and Save Changes
the backlight depends on EITHER:
the programming of the Press 
control unit (which must
have Release 3 software OR
or higher installed). Close the keypad tamper.
4. Leave local programming The keypad saves the changes you have made in
mode and save your its local memory.
changes (see below).
You can now remove 12Vdc power, if required, or
To Disable/Enable the Status OK LED leave Installer Menu on the control unit.
1. Enter Local Programming MENU KEY-EP External Prox Reader
ABCD 
mode. Figure 22 shows the outside details of the external
MENU prox reader KEY-EP:
2. Press  repeatedly until
STATUS OK LED  3
the display shows:
3. Press  repeatedly to
select one of the
following:
Status OK LED ON (). MENU
STATUS OK LED  4
Status OK LED OFF (). MENU
STATUS OK LED  1
The green status LED
under the navigation key
will glow for 20 seconds
after the last press (this
may be useful when the
keypad is placed in
bedrooms that should be
completely dark at night).
2
4. Leave local programming
mode and save your 1. LED window.
changes. 2. Retaining Screw.
3. Removable Fixing Plate.
4. Permanently attached cable.
To Disable/Enable the Status Fault Figure 22 External Prox Reader KEY-EP
LED
1. Enter Local Programming MENU Siting the External Prox Reader

Page 17
Installation i-on30EX/EXD

Do site the External Prox Reader:


At a convenient height and location for the user.
Out of sight of potential intruders. 1
Note that the external prox reader is fitted with a
length of 2m of the appropriate cable. The cable
can be extended up to 50m by connecting an
additional length of 7/0.2 un-screened alarm
cable. 2
Do NOT site the External Prox Reader:
Next to electronic equipment, particularly 1
computers, photocopiers or other radio
equipment, CAT 5 data lines or industrial mains 3
equipment.
Note: Do not site the external prox reader closer
1. Fixing hole.
than one meter to any other kind of prox reader
(for example an i-kp01, KEY-KPZ01/KP01 or
2. Cable entry.
another external prox reader). If you do so then 3. Anchor for retaining screw.
the prox readers will interfere and be unable to Figure 24 External Prox Reader Fixing Plate
read tags.
Fit External Prox Reader
Opening the External Prox Reader Use M4 25mm countersunk screws at both fixing
To open the external prox reader (see Figure 23): holes when mounting the back of the keypad on
the wall. Ensure the screw has a thread suitable
1. Undo the single retaining screw. for the wall material.
2.Tilt the edge of the fixing plate and then slide it a
short distance parallel to the body of the prox Connecting Remote Prox Reader to
reader. Keypad
3. Slide the fixing plate away from the reader Segregate the external prox reader cable from
body, along the cable. any other wiring such as mains supply cables,
telephone cables, computer network cables and
R.F. cables. Use cable ties to keep cables
separated.
Keep the prox reader cable clear of cables
supplying sounders or extension loudspeakers.
Figure 25 shows the wiring connections at the
keypad.

Figure 23 Opening External Prox Reader


Figure 24 shows the details of the external prox
reader backplate:

Figure 25 Connecting the External Prox Reader


Tone Volume – All Keypads
To alter the volume of non-alarm tones from the
keypad adjust the keypad sounder volume control
(2 in Fig 7):

Page 18
i-on30EX/EXD Installation

Louder Expander Loudspeakers


Note: This control changes the During normal operation loudspeakers on
volume of non-alarm tones (for expanders repeat setting and entry tones for the
example Exit/Entry tone). The partition that the expander is allocated to. During
volume of alarm tones is fixed. an alarm the loudspeakers repeat alarm tones.
Softer Each loudspeaker draws up to 280mA in
operation. if there is more than one expander
Engineering Keypad loudspeaker then the bus may not be able to
supply sufficient current during an alarm.
An Engineering Keypad is a modified i-kp01 that
can be plugged into a dedicated connector on the Note that you must enable entry exit tones from
control unit PCB (see 17 on Figure 2) or any of the expander loudspeakers from Installer Menu.
the expanders (see 13 on Figure 14 or 10 on
Figure 16). An Engineering Keypad does not need Step 5. Connect Control Unit
to be addressed, and will always be recognised by to Mains
the control unit as an engineering keypad.
WARNING: ENSURE THAT THE MAINS
You can use an Engineering Keypad to program
SUPPLY IS DISCONNECTED AND ISOLATED
the system without being tied to any of the
BEFORE MAKING ANY MAINS CONNECTIONS.
installed keypads. If you wish to move an
All mains electrical connections must be carried
Engineering keypad from one connection point to
out by a qualified electrician and must comply with
another then you can do so without removing
the current local regulations (e.g. IEE).
power from the system.
Mains Cabling
Step 4. Fit and Connect Note: To avoid mains interference, the mains
Expanders cable must enter the control unit through its own
cable entry hole (7 in Fig 1) and must not be
Both wired and radio expanders are supplied in mixed with other cables.
the same plastic case. Use M4 25mm
countersunk screws in all three fixing holes when Mains Connection
mounting the back of the case on the wall. See Figure 27 shows the mains connection. Connect
Figures 14 or 16 for the position of fixing holes to a suitable supply using a double pole
and cable entries. disconnect (isolation) device in accordance with
EN60950-1.
Connecting an Expander to the Bus Caution: Do not apply power at this point.
Both wired and radio expanders provide a Anchor the mains cable with a strain-relief tie.
connector for the bus at the bottom of their PCBs There is a eye located near the mains cable entry
(item 4 on Figures 14 and 16 ) . hole for this purpose (6 in Fig 1).

Figure 27 Mains Connection

Step 6. Connect Wired Zones


The control unit and the wired expander
Figure 26 Wiring Expanders connectors can be used for either four-wire CCL
Addressing Expanders detectors, two-wire CCL detectors or two-wire
FSL detectors.
The control unit assigns addresses to all devices
connected to the bus cable. You must start this Four Wire Closed Circuit Connections
process off from the Installer Menu, during the Figure 28 shows the wiring for four-wire CCL
initial power up. See page 27 for instructions. zones on the control unit.
Figure 29 shows the wiring for four-wire CCL
zones on the wired expander. Note that the

Page 19
Installation i-on30EX/EXD

connections are different on the expander Alarm Zone 0


compared to the control unit.
Figure 31 shows wiring for four-wire CCL zones Tamper Zone 0

on the KEY-KPZ01.
Alarm Zone 1

Tamper Zone 1

Figure 30 EXP-WCC CCL Zone Wiring


Figure 31 shows the wiring for CCL zones on the
KEY-KPZ01.
KEY-KPZ01

Tamper Zone 1

Alarm Zone 1

Figure 31 KEY-KPZ01 CCL Zone Wiring


Two-Wire Closed Circuit Connections
With version 4.02 and higher software you can
connect two-wire CCL detectors to each pair of
zone terminals. To specify the zone wiring type
use the Installer Menu – System Options – Wire Zone
Figure 28 Control Unit CCL Zone Wiring Type option and select “2-wire CC”.

Figure 29 shows the wiring for four-wire CCL On the control unit, EXP-W10 and EXP-WCC, if
zones on the wired expander. Note that the required you can use one pair of zone terminals
connections are different on the expander as a common tamper, provided you program that
compared to the control unit. Also note that zones zone with the type “Tamper” from the Installer
0, 6,7,8 and 9 are not available on the control unit, Menu.
and zones 5-9 are not available on the expander. The EXP-WCC does not specifically have a 2-wire
Alarm Zone 0 CC zone type. However you can mimic the setting
by using “4k7/2k2/4-wire CC” zone wiring option,
Tamper Zone 0 and then connecting the detector to the alarm
Z0

terminals and placing a short across the tamper


Z9

Alarm Zone 1 terminals.


Z8
Z1

Wired Expander
Z2

Z7

Tamper Zone 1 Fully Supervised Loop Connections


Z6
Z3

Figure 32 shows the wiring connections for FSL


Alarm Zone 2
Z5
Z4

zones on the control unit. Note that the resistance


values shown are examples.
Tamper Zone 2

Figure 29 Wired Expander CCL Zone Wiring


Figure 30 shows the wiring for CCL zones on the
EXP-WCC wired expander. Note that the EXP-
WCC provides connectors for a total of ten
separate 4-wire CCL detectors, and that there are
separate terminals for both alarm and tamper.

Page 20
i-on30EX/EXD Installation

Wired Expander

100 Ohms
4K7

Alarm contacts
Zone 1 2K2 EOL
Tamper contacts

4K7

Alarm contacts
Zone 0 2K2 EOL
Tamper contacts

Figure 32 FSL Zone Wiring – Control Unit Figure 34 FSL Zone Wiring – EXP-WCC
Figure 33 shows the wiring connections for FSL The allowed values for Alarm Contact/End of Line
zones on the expander. Note that the connections are the same as for the EXP-W10.
are different on the expander compared with the
Figure 35shows the wiring connections for FSL
control unit.
zones on a KEY-KPZ01. Note that the resistance
values shows are examples.
Z0

100 Ohms
Z1

4K7
Wired Expander
Z2

KEY-KPZ01
Alarm contacts
2K2 EOL
Z3

Zone 1 Tamper contacts


Z4

Zone 0
4K7

100 Ohms Alarm contacts


2K2 EOL
4K7 Tamper contacts

Alarm contacts Figure 35 Wiring FSL Zones on KEY-KPZ01


2K2 EOL
Zone 1 Tamper contacts When programming select the FSL resistor values
for the control unit in Installer Menu - System
Zone 0 Options - Wired Zone Type. To select the resistor
4K7
values for a wired expander use Installer Menu –
Detectors Devices – Wired Expanders - Edit Expander.
Alarm contacts
2K2 EOL If you wish to connect two or more detectors to a
Tamper contacts FSL zone, Figure 36 shows the connections
required.
Figure 33 FSL Zone Wiring - Expander
The allowed values for Alarm Contact/End of Line
resistors are: 4k7/2k2. 1k0/1k0, 2k2/2k2, or
4k7/4k7.
Note: Use the same pair of values for ALL FSL
wired circuits on the control unit. Each wired
expander can use a different pair of resistor
values, but ALL circuits on an expander must Figure 36 Wiring Two Detectors per Zone FSL.
have the SAME values.
Figure 37 shows an example of wiring double
Figure 34 shows The wiring connections for FSL doors with two door contacts to one FSL zone.
zones on the EXP-WCC. Each door contact is a reed switch, connected

Page 21
Installation i-on30EX/EXD

between the outer terminals. The inner (shaded) active, +12V when inactive. If you wish to reverse
terminal is not connected, and provides a spare the polarity of this output see Changing the Polarity
terminal. of a Wired Output in the i-on Range Engineering
Guide.

Spare
Figure 39 shows an example of using the wired
Blue outputs to drive an indicator LED.
To zone
contacts Yellow
2K2 EOL Wired External Sounders (Optional)
Red
Wired external sounders differ in their methods of
connection. Figure 39 shows an example of a
Black
4K7 general method of using the outputs to connect a
Figure 37 Example: Wiring Two Door Contacts to wired sounder.
One FSL Zone.
It is possible to program the TR terminal on the
Figure 38 shows an example of wiring a control unit (see item 10 in Figure 3) as either CC
trouble/masking output using the “3-resistor or FSL. Use Installer Menu – System Options – Panel
method”. Note that you must use 2k2 and 4k7 Tamper Rtn. By default the terminal is CC. If you
resistors as shown. Other values will not work program the TR terminal as FSL then make sure
(See System Options – Masking in the i-on Range you connect a 2k2 resistor in series with the wire
Engineering Guide). to the sounder.
Note: If you do not wish to connect a wired
external sounder then leave TR programmed as
CC and make sure you link TR to 0V on the
control unit. This prevents the control unit
reporting Bell Tamper unnecessarily.
Figure 38 Example: Wiring a Trouble/Masking Wired Outputs on Expanders
Zone, 3 Resistor Method. Each EXP-W10 wired expander provides
connections for up to four transistor driven
Step 7. Connect Wired outputs. Each output has a maximum rating of
Outputs 500mA (but note that the bus may not be able to
supply this much current). By default the outputs
are 0V when active, +12V when inactive. If you
wish to reverse the polarity of these two outputs
see Changing the Polarity of a Wired Output in the
i-on Range Engineering Guide. Figure 40 shows an
example of using an expander output to drive an
LED.
16 Ohm minimum
Typical loudspeake r
for example 09040

1K0 Resistor

LED
(Light
Emitting
Diode)
12V
0V AUX OUTPUTS LS
Out 1 2 3 4 - +

Figure 40 Using Wired Expander Outputs.


Wired External Sounders on Expanders
Figure 39 Connecting Wired Peripherals Figure 41 shows a general method of using the
Control Unit Wired Outputs outputs on a wired expander to connect a wired
external sounder.
The control unit PCB provides one connector for
wired outputs. Outputs 1 is driven by a transistor, Connect the tamper wiring to an unused zone
and is capable of sinking a maximum 500mA connection on the expander. For 4-wire CC zones
when active. By default output 1 is 0V when

Page 22
i-on30EX/EXD Installation

use the alarm contacts only and link the tamper


contacts together with a short length of wire.
In the Installer Menu, program the zone with a
type of “Tamper”. Program the outputs used to
trigger the siren and strobe with the appropriate
output types. See the i-onEX Range Engineering
Guide for more details.
Single Wire Tamper Return
If the external sounder provides a single –TR
connection, then use the zone type “Tamper
Return” for the zone terminals which receive the
connection at the expander.

Figure 42 Wiring –TR from External Sounder to a


Zone on the Expander.
Remote Loudspeakers (Optional)
If you wish to add a 16 Ohm wired Loudspeaker
unit, then connect it as shown in Figures 39 or 40.
The control unit provides connections for one
loudspeaker. Expanders provide connections for
one loudspeaker each. Do not connect another
loudspeaker in parallel. You may connect another
loudspeaker in series, but this will decrease the
Figure 41 Wiring External Sounder to Expander maximum volume from the speakers.

FSL wiring. Connect –TR to the left hand terminal Note: Loudspeakers are not warning devices as
described by EN50131-4. Although loudspeakers
of a zone connector, see Figure 42. (The left hand
may mimic alarm tones, they also give alert tones
terminal is the one next to the “Z” on the terminal
and other progress tones when setting and
label.) The maximum length of wire is 50m when
unsetting the alarm system.
using 2k2/4k7 or 4k7/4k7 FSL wiring and a single
core of standard 6-core alarm cable. Fit EITHER a Output on KEY-KPZ01
2k2 resistor if using 2k2/4k7 FSL, OR a 4k7
resistor if using 4k7/4k7 FSL. Do not use any Figure 43 shows the wiring required to connect an
other FSL resistor combinations. output the output terminal on the KEY-KPZ01.
0V 12V

CC wiring Eaton’s Security Business does NOT


recommend that you use CC wiring for this
application. The maximum length of wire LED
A B OP
RS485

allowable is only 6m. Instead Eaton’s Security (Light Emitting Diode)


Business recommends using FSL wiring, as
described above. 1K0 Ohm Resistor

Figure 43 KEY-KPZ01 Output Wiring

Page 23
Installation i-on30EX/EXD

Approval
Step 8. Connect the Internal The built-in communicator is manufactured to
Communicator (i-on30EXD meet all European Economic Area
telecommunication networks requirements.
only) However, due to differences between the
The i-on30EXD version of the control unit has an individual PSTNs provided in different countries,
internal communicator on its main PCB. This is an the approval does not, of itself, give an
auto-dialling modem. unconditional assurance of successful operation
on every PSTN network termination point.
If necessary, a standalone communication device
can be connected through a wiring harness to The built-in communicator has been approved for
interface pins on the main PCB (this is known as a the following usage:
plug-by communicator, see page 26). (a) Automatic call initialisation.
The communicator can be used for: (b) Operation in absence of indication to proceed.
• Transmitting alarm signals to alarm receiving (c) Automatic dialling.
equipment at a central monitoring station (d) Modem.
using Scancom Fast Format, Scancom SIA (e) Serial connection.
(Security Industry Association) or Contact ID.
(f) Multiple repeat attempts.
• Connecting to a PC based at a remote
(g) Line status monitoring.
engineering centre. Using Scantronic
Downloader software, the remote PC can Usage other than approved usage or failure to
upload and download system parameters comply with the installation and programming
(including the event log and diagnostics), set instructions may invalidate any approval given to
and unset the alarm system, and carry out the apparatus if, as a result, the apparatus ceases
other special functions. to comply with the standards against which
approval was granted. Note the approval label on
Telephone Line the main PCB.
Ideally, the internal communicator should be
connected to an ex-directory line used exclusively In the event of problems you should contact your
for alarm communications. equipment supplier in the first instance.

Line Monitoring for the Internal Communicator Ringer Equivalence Number


The control unit provides a line monitoring The Ringer Equivalence Number (REN) of the
function to check that a telephone line connected built-in communicator is 1. As a guide to the
directly to the control unit is working, and to number of items that can be simultaneously
indicate a line failure if it is not. While enabled, connected to an exclusive line, the sum of the
this function continually checks the line voltage to REN values should not exceed 4. A standard
ensure that the line is connected. If it detects a telephone (as provided, for example, by BT in the
failure, the system gives the Line Fault Response UK) has a REN value of 1.
selected in the Installer Menu.
Safety Notice
Test Calls
The control unit can be programmed to make test Figure 44 identifies connectors for Safety Extra-
report calls to an ARC. "Static" test calls can be Low Voltage (SELV) and Telecommunications
programmed to occur at set times or intervals. Network Voltage (TNV) circuits on the control
"Dynamic" test calls occur 24 hours after the last unit's main PCB. These terms are used in
call made by the unit. See the i-on Range accordance with the definitions in Safety Standard
Engineering Guide for details on how to program EN60 950.
these functions. The Installer must ensure that TNV terminals are
Statutory Information connected only to other circuits designated as
TNV circuits (for example, the PSTN) and that
Applications SELV terminals are connected only to other
The built-in communicator is suitable for circuits designated as SELV circuits. Strict
connection to the following types of networks: adherence to the installation instructions will
(a) Direct exchange lines (PSTN) supporting ensure that the equipment continues to comply
DTMF (tone) dialling. with the safety regulations to which it was
approved.
(b) PABX exchanges (with or without secondary
proceed indication).
Note: The built-in communicator is not suitable for
connection as an extension to a pay-phone or to 1
+ 1 carrier systems.

Page 24
i-on30EX/EXD Installation

(ii) Connect the other end of the two cores to


the corresponding terminals on the BT
master box.

Figure 45 Connecting the Internal Communicator

Fit ADSL Filter


If the telephone line is being shared by a
broadband service then you should fit a
broadband filter to the line. Eaton’s Security
Business provides the ADSL01 filter that plugs
onto pins provided for the purpose on the main
circuit board of the control unit (see 5 on Figure
2). Figure 46 shows how to fit the filter.

TNV - Telephone line connector.


SELV – All other connectors.
Figure 44 SELV and TNV connectors
Connecting the Telephone Line
Connecting the telephone line directly to the
terminals on the internal communicator, or
indirectly through other apparatus, can produce
hazardous conditions on the telephone network.
Always seek advice from a competent telephone
engineer if in any doubt about connecting to these
terminals.
Example – connecting a line in the UK:
The internal communicator must be connected to
the telephone network by:
a) If the wiring is owned by British Telecom:
British Telecom.
b) If the wiring is not owned by British Telecom,
one of:
(i) British Telecom.
(ii) The authorised maintainer.
(iii) A professional Installer, after 14 days
written notice to the authorised
maintainer.
To connect the telephone line (see Figure 45):
(i) Using a two-core telephone cable, strip off
5mm and feed the cable through one of
the entries (marked “10” in Fig. 2) in the
rear of the control unit. Connect the two
cores to terminals A and B on the main
PCB. Figure 46 Fitting the ADSL01 Filter.
Note: If you remove the ADSL01 filter then re-fit
the jumpers to the outermost pairs of pins. If you

Page 25
Installation i-on30EX/EXD

fail to re-fit the jumpers the internal communicator 3. Plug the Communication Wiring Harness onto
will not connect to the phone line. the communications connector on the main
PCB.
Step 9. Fit a Plug-By If the system has already been installed:
Communicator 4. Re-connect the battery.
The control unit can be connected to a separate 5. Fit the case lid.
communicator or speech dialler (for example, the 6. Apply mains power.
Scantronic 8400, 8440, 660 or RedCare STU). 7. Test communicator operation.
Figure 47 shows the connections provided by the
communications wiring harness. Note that the Note: You will need to speak to the ARC in order
output types shown in Figure 47 are the Factory to confirm that the communicator has worked
default types. See the i-on Range Engineering correctly.
Guide for details on how to change the defaults. Line Fail Input
Com Connector Cable, This input is designed to allow a plug by
Part number 485210 communicator to indicate to the control unit that
the communications link has failed. The
Brown O/P1 (Fire) communicator should have an output capable of
Orange O/P 2 (Hold Up Alarm) applying +12V to the Line Fail input while a line
fault is present and 0V when the fault is absent.
Yellow O/P 3 (Burglar Alarm)
Green O/P 4 (Open/Close) Tell Back Input
This input is designed to allow a plug by
Blue O/P 5 (Zone Omit (System))
Con 7 communicator to indicate to the control unit that
Purple O/P 6 (Tamper) the user can reset the system after a system
White O/P 7 (Confirmed) tamper. The communicator should have an output
Grey O/P 8 (General Fault) that, when triggered remotely, can apply +12V for
White/Brown Line Fault input
at least 100ms to the input. See “Remote Reset
(Redcare Reset)” in the i-on Engineering Guide
White/Orange Tell Back input
for more information.
Black 0V
Line Monitoring for a Dual-Path Communicator
Red 12V
If a standalone dual-path (landline and mobile)
communication device, such as a RedCARE STU,
is connected to the plug-by connector, you need
Com Connector Cable, to do the following to obtain correct line fault
Part number 11960058 reporting that complies with BSIA Form No.175,
April 2005 (this is not necessary if you are using a
Brown O/P 9 (AC Fail)
plug-on module):
Orange O/P 10 (Battery Fault)
Con 8
Yellow O/P 11 (Technical Alarm)
1. Reprogram one of the plug by outputs to type
“ATS Test” and wire that output to the ATS
Green O/P 12 (Alarm Abort) Test input of the communicator.
2. Wire the Line Fault output of the
Figure 47 Plug-By Communicator Wiring communicator to the Line Fault input of the
Note: Comms O/P4 will be active when the plug-by connector. The communicator must
system is unset. This is normal. provide +12Vdc to indicate a line fault (for
example, if the Line Fault output at the
To fit a communicator, follow the instructions communicator uses a relay, connect the
below. common terminal of the relay to +12Vdc and
Caution: Follow the instructions in the order the normally-open terminal to the Line Fault
shown, or you may damage the input of the plug-by connector).
control unit and/or communicator. The control unit will generate an "ATE L.F. Single"
1. Disconnect mains power from the control unit, alert if only one of the networks is not available, or
remove the case lid, and disconnect the "ATE L.F. All" if both networks are not available.
battery (if the system has already been
installed). Step 10. Fit and Connect
2. Make any necessary connections from the Battery
communicator to the communication wiring
harness. The default is a 12V positive voltage Fit a 7Ah Lead Acid battery into the battery
when the output is inactive. compartment in the bottom of the control unit (see
Figure 48).
Refer to the next section if you are using a
dual-path communicator.

Page 26
i-on30EX/EXD Installation

See page 12 for example calculations of battery be “b1-d51”(bus 1 device 51). Keypads take
requirements. bus device addresses 51 upwards.
Connect the battery leads, red to the positive, (If you are installing a UK control unit please
black to the negative terminals of the battery. go to step 6.)
Connect the other ends of the leads to BATT (15
On an EUR control unit the keypad display
on Figure 2).
then shows:


3. Press  or  followed by  to select the
language you want. (In the i-on30EX/EXD
English is the only language available.)
From this point on, the display operates in the
selected language. If you want to change the
language later use Installer Menu - System
Options - Language.
On an EUR control unit the display shows:


4. Press  or  to show other countries, for
example
Figure 48 Fitting the Batteries 

Note: Connecting the battery without mains power 5. Press  to select the country you wish to use.
will not start the system. (See “Programming
The display shows:
Before Installation” in the i-on Range Engineering
Guide.) 

Step 11. Initial Power-Up 6. Press A or B to select either a Partitioned
system or a Part Setting system.
Please see the i-on Range Engineering Guide for Note: To change to Partition or Part Set mode at a
an explanation of bus addressing. later date you will have restore factory defaults.
WARNING: During initial power-up all the keypad 
sounders, internal loudspeakers and wired sirens 
MAY give an alarm tone. If you are working at the 7. Press  or  to show the range of zone
top of a ladder make sure that the sudden noise wiring types available, for example:
does not startle you and cause a fall. 

1. Apply mains power to the control unit.
8. Press  to select the wiring type you intend to
The keypads and internal sounder may give use for the wired zones.
an alarm tone. The heartbeat LED on the
control unit PCB (see 13 on Fig 2) starts Note: This initial choice fixes the wiring type for
flashing. The navigation keys on any attached the control unit and any attached wired
keypad start flashing. expanders. If you wish to use a different wiring
type on the expanders then use Installer Menu –
All connected keypads briefly show the Detectors/Devices – Wired Expander after the
software revision of the keypad itself, followed initial power up to change the wiring type for each
by the words “Please wait...” for several expander.
seconds while the control unit scans the bus.
When the control unit has finished scanning If the control unit lid is open then the display
the bus the keypads show: shows:




2. Press and hold keys A and  simultaneously Note that the alert LEDs round the navigation
on the keypad that you wish to use for initial key glow red. This is because the control unit
programming. NOTE: Hold the keys down lid is off and the tamper is active.
for at least three seconds. 9. Press .
After a short pause the keypad gives a The display shows:
confirmation tone. The display briefly shows

the bus address of the keypad. If there are no

other keypads connected to the bus it should
10. Press .

Page 27
Installation i-on30EX/EXD

The display shows: No. Flashes Meaning


 One Communication with control unit
 over bus is OK
11. Press .
Two No communication over the bus
The display shows:
in the last 10 seconds.

 Three No bus address allocated to
12. Press . expander
The display shows: Four No poll request received from
control unit in the last minute.


At this point you must make the control unit Transferring to Another Keypad
allocate an address to each of the connected While in the Installer Menu, you can transfer to
bus devices, as follows: any other wired keypad without leaving the
13. Go to each bus device. You can visit the Installer Menu. To do this simply go to any other
devices in any order, but if you visit them in keypad and enter the Installer access code. The
the order you want their address numbers to new keypad will pick up your position in the
appear then it will make subsequent Installer Menu. The keypad you have left will
programming easier. The control unit assigns briefly display the message “Installer session
the next free bus address to a bus device transferred” for 5 seconds before reverting to the
when you make the device request a bus time and date.
address. Leaving the Installer Menu
For keypads:
If you wish to leave the Installer Menu at any time.
Hold down keys A and  until the display
shows a bus and device number. For example 1. Press  until the display shows the words:.
the second keypad would be:  
   

For expanders: 2. Press  to leave Installer menu.
(Press  if you do not want to leave the
Open the lid (to make sure that the tamper
menu.)
switch is open) and hold down the addressing
button (see Figures 14 and 16 ). When you do The display shows:
so the control unit assigns the next free 
address to that expander. The expander gives 
a double “beep” confirmation tone and shows After a delay of anywhere between a few
its assigned address on the two-digit LED seconds to a few 10s of seconds (depending
display. Replace the lid. on the number of expanders fitted) the display
shows the time and date:
NOTE: DO NOT request a bus address from two

different devices at the same time.

14. When you have visited all the connected bus The system is ready for further programming.
devices, go back to the keypad and press . 3. If the control unit finds a bus device missing,
The display shows: or one with an address that has not been
 added using the Installer Menu then the
 display shows, for example:
15. Replace the control unit lid, making sure that 
the lid tamper closes. 
16. At this point you should leave the Installer The top line of the display shows the number
Menu to save the changes you have made, of new devices found, and the number of
see overleaf. existing devices missing (lost). The bottom
line of the display shows the first in the list of
Note: To set the time and date use Installer Menu
found and lost devices. Press  to see any
- System Options – Set Date & Time. See i-on
other items in the list.
Range Engineering Guide for more information.
4. Either: Press  to go back into Installer Menu
Diagnostic LED on Expanders
(so that you can go and check that all the bus
You may notice the DIAGNOSTIC LED flashing
devices you have installed are connected,
on an expander PCB. The LED gives one, two,
powered up and addressed correctly).
three or four flashes a second. Each of these
sequences has the following meaning. Note: To check an expander address remove the
expander’s lid and briefly press the addressing

Page 28
i-on30EX/EXD Installation

button. The two digit display will show the bus 1. Make sure the system is unset and showing
address for a few seconds. the standby screen (time and date).
OR: Press  to make the control unit update 2. Key in the Installer access code. The default
its internal record of devices attached to the Installer access code is “7890”.
bus. The display shows: As you start to key in the code the display
 shows:
 
5. Press  to accept the change to the bus. 
(You can still press  to return to the installer When you key in the last digit of the Installer
menu if you do not want to change the access code the display shows:
number of devices on the bus.)

Note: If you attempt to leave the Installer Menu 
when a detector/device tamper is active then the Notes:
keypad displays a fault message telling you which 1. You will see this screen the first time you enter
detector/device is causing the problem. Press  the Installer menu on a new control unit, or if you
have restored Factory Defaults. You can disable
to return to the Installer Menu. You must either
this feature by using the Installer menu option
close the detector/device tamper or delete it from
System Options - User Access – User Code Required.
the system before you can leave the Installer
2. If you set User Code Required to NO then the
Menu.
control unit no longer complies with EN50131.
Important! Saving Changes This option complies with BS8243 only if the user
has given written consent.
When you make changes to the Installer Menu the
3. If you key in an access code incorrectly, the
control unit holds those changes in temporary
display shows four “stars”. Key in the code again.
memory until you leave the Installer Menu. As you
If you key in a total of four incorrect codes then
leave the Installer Menu the control unit writes
the system locks you out for 90 seconds.
those changes into a permanent store. If you
remove all power BEFORE you leave the Installer 3. Key in the default user code (“1234”).
Menu then the control unit will lose your changes. The display shows:
Note that this does not apply if you restore
Factory Defaults, that change takes place 

immediately.
4. Press  or  to display more items from the
Alerts After Leaving Installer Mode menu.
Once you have left the Installer Menu you may Each item appears on the bottom line of the
see the red LEDs around the navigation key display in turn, for example:
glowing. A common cause of this alert is that 
there is no telephone line connected to the built-in 
communicator. If you do not intend to use the 5. Press  to select that item of the menu.
built-in communicator then re-enter the Installer The option you selected now appears on the
Menu and disable the communicator by setting top line. If there are any sub-options for that
Communications – ARC Reporting – Call Mode to selection, then the first of them appears on
“Disabled”. See the i-on Range Engineering Guide the bottom line, for example:
for more information.

Re-Entering the Installer Menu 

When you enter the Installer Menu from a keypad, You can press  or  to display the other
the alarm system is effectively disabled. While the sub-options.
system is in Installer Menu:
Defaulting Access Codes
Any other user trying to set the system from a
keypad will see the message “Installer on If the User 1 and/or Installer codes are lost then
Site”. you must restore all user information to its factory
defaults. All prox tags, remotes and radio HUDs
All HUAs (including radio HUAs), fire alarm will be deleted.
zones, 24 hour zones and tampers are
disabled. 1. If possible, enter the Installer menu.
If you have logged into the system from a PC then Note: If you cannot enter Installer Menu then the
the alarm system is active. control unit will start a tamper alarm when you
open the control unit lid.
If you need to re-enter the Installer Menu:
2. Remove mains power, then open the case
and disconnect the battery.

Page 29
Installation i-on30EX/EXD

Note: This procedure will not work if the control 3. Press A or B to select the desired mode.
unit lid tamper remains closed. The display shows:
3. Identify the Reset Codes pins on the main 
PCB (see item 12 in Figure 2). 
4. Short the Reset Codes pins together using a 4. Press  or  to display the desired wiring
screwdriver or jumper link. (Keep the short on type on the bottom line of the display and then
until step 6.) press  to select it.
5. Apply mains power. The system loads all defaults except for
The control unit loads the factory default Access Codes and the Log.
access codes: The display briefly shows:
User 1=1234, Installer=7890.

After a short pause the system starts a a 
tamper alarm and the display shows the Followed by:
words “Please wait...”. The red LEDs glow to 
show an alert that the control unit lid is open. 

6. Remove the short from the Reset Codes pins. 5. Press  until the display shows:

7. Reconnect the battery. 
8. Close the control unit lid (to restore the tamper 6. Press .
switch). The display shows:
The display shows the time and date, for 
example: 
 The control unit scans the bus to see what
 devices are attached and powered up. After
9. Key-in the default user 01 code to silence the several seconds (depending on the number of
sounders. devices connected to the bus) the display
The display shows: shows, for example:




10. Enter Installer Menu and then leave it again. The top line of the display shows the number
of new devices found. Because you have
The LEDs around the navigation key should restored factory defaults the control unit has
now be green. If they glow red then there may erased its internal list of bus devices and the
be an alert for a missing battery that needs display will not show any devices as missing.
acknowledgement. To force the control unit to (If a device is attached to the bus but not
check the battery: powered up then the control unit will not
11. Press , key in 1234, press  again. detect it.) The bottom line of the display
shows the first in the list of found devices.
The navigation key LEDs should now glow
green. Press  to see any other items in the list.

Note: The log is protected and cannot be erased 7. Press .


by the Installer. The display shows:

Restoring Factory Defaults Only 
If you wish to restore all factory default options, 8. Press .
without defaulting the user and installer access The keypad sounder gives “dee dah”
codes then: confirmation tone and the display shows the
1. From the Installer Menu select System Options time and date, for example:
– Restore Defaults – Factory Defaults. 
The display shows: 
The control unit has saved all the changes
 you have made.

2. EITHER: Press  to go back to the Installer Menu
without changing defaults.
OR: Press  to load defaults.
If you press  the display shows:



Page 30
i-on30EX/EXD Installation

Step 12. Commission the


System
Install Detectors and Other Peripherals
1. Use the Installer Menu to teach the system
the identity of any radio detectors or other
peripherals. (Note that you must have a radio
expander already connected and installed on
the bus to do this.) See the installation
instructions supplied with each detector or
peripheral.
2. Install detectors and peripherals at their
selected locations.
3. Use the Installer Menu – Test option to:
a) carry out a walk test of the detectors.
b) test the operation of any other peripherals.
Program the System
Program the system to suit user requirements.
Page 32 is a summary of the Installer Menu on
the i-on30EX. Please see the i-on Range
Engineering Guide for a more detailed description.
Note: make sure that you allocate keypads
correctly to partitions. For more information see
“Assigning Wired Keypads to Partitions” in the i-on
Range Engineering Guide.
Assemble and close the control unit:
a) Fit the lid of the control unit into the back of
the case
b) Fit and tighten the lid fixing screw.
NOTE: It is possible, for convenience, to place
links over tamper contacts to inhibit tamper alarm
during installation. Because of this feature make
sure you test all lid tampers before completing
installations, to ensure that no links are left fitted.
Leave the Installer Menu.
The red LEDs should go out, and the rim of
the navigation keys glow green. The system is
now ready to hand over to the user.
Handover to the User
Instruct the user on how to operate the system.
See the i-on Range Administrator’s Guide. If
necessary, show them how to set the time and
date on the system.
Remember to leave the i-on Range
Administrator’s Guide with the user.

Page 31
i-on30EX/EXD

Installer Menu
1 DETECTORS/ DEVICES 3 SETTING OPTIONS
3 User reset Phone Book
6
Zone alarms Triggers
Detectors Full Set
Zone tampers Destinations
Add/Del Detectors Name
System tampers Call Acknowledge
Program Zones Exit mode 13
4 Confirmation (-UK) SMS
Address Bus Device Settle time
5 Confirmation Mode Call Mode
Wired Expanders Exit time
Basic Messages
Address Bus Device Entry time
DD243 Phone Book
Edit Expander Siren delay
BS8243 Triggers
Delete Expander Siren time 7 13
Confirmation time PSTN SMS
Enable Expander Strobe on Set 7 12
After entry Line Fail Response
Replace Expander Strobe on Unset 7 12
Entry keypad lock Line Fail Delay
Radio Expanders Part Set B 13
Sounder on GPRS
Address Bus Device Name 13
Siren on Ethernet
Edit Expander Exit Mode 7
4 Unconfirmed reset Downloading
Delete Expander Settle time 7
5 Confirmed reset Account
Enable Expander Exit time 8
HUA Confirm Time Connection Type
Replace Expander Entry time 8 13
Tamper as Tamper only Rings to Answer
Wired Keypads Alarm Response 13
Confirmation (-EUR) Answer on one ring
Address Bus Device Siren delay 13
Sounder on Access Mode
Edit Keypad Siren time 13
Siren on Phone Book
Keypad 01...10 Part Set Final Exit 13
Masking Secure Callback
Name Part Set Entry Route 9 13
2 Mask Override Modem Baud Rate
Partitions Strobe on Set 10 20
2 Language Remote Servicing
Key A...D Strobe on Unset
21 Restore defaults Plug-by
Zones Volume
21 Staged defaults 6 TEST
Wired zone type Part C, D
22 Factory defaults
Backlight (See Part Set B) Sirens & Sounders
23 Installer name
External Prox 3 PARTITIONS
2 Wired Keypad
Installer code
Delete Keypad Radio Keypads
Partition 1 Keypad text
Enable Keypad Expanders
Name Remote needs Entry
Replace Keypad Walk Test
Exit mode Remote Entry PrtSt
Radio Keypads 4 Zone Resistances
Settle time RKP needs Entry
Add/Del Radio Keypad 5 Signal Strengths
1 Exit time RKP Entry PrtSt
Edit Keypads 11 Detectors
1 Entry time HUA Response
Radio Keypad 01...04 6 Radio Keypads
Alarm response Auto Rearm
Name External Sirens
2 HUA response Panel Loudspeaker
Partitions WAMs
2 Siren delay Entry alarm delay
Key A...D Outputs
Siren time Abort Time
External Sirens Radio Outputs
Strobe on Set Supervision
Add/Delete Ext. Siren Wired Outputs
Strobe on Unset Jamming
Edit external siren Plug-by Outputs
Part set exit mode Force Set
WAMs 4 Expander Outputs
Part set settle time Tamper Omit
Add/Del WAM 5 Remotes
Part set exit time CSID Code
Edit WAM User HUA
Part set entry time Silence Alerts
2 OUTPUTS Prox Tags
Part set alarm resp. Mains Fail Delay 13
ARC Reporting
Radio outputs Part set siren delay Set Date & Time 13
Speech Dialler
Add Outputs Part set siren time Panel Tamper Rtn
PSU Current
Edit Outputs Part set final exit 5 COMMUNICATIONS
12
Battery(s)
Wired outputs Part set entry route 13
ARC Reporting Locate Bus Device
Panel Part set strobe set
Call Mode 7 VIEW LOG
Siren Part set strobe unset
Phone book All Events
Strobe Partition 2....4 13
IP Network Mandatory Events
PAN>OP1 Full Set Link
Account Number Non Mandatory Events
Exp. x1-nn... Partition 2...4
Report Type
O/P x1>nn>1...4 4 SYSTEM OPTIONS 14 8 ABOUT
Fast Format channels
Name 15 Panel
Wired Zone type CID/SIA Events
Type Expanders
Panel Zones Restorals
Polarity 18 Keypads
All Zones Burg Comms Rearm
Pulsed 14 Comms
2 User Access 21CN FF Ack time
Partitions 15 Module:
19
HUA keys active Send tamper as burg
Plug-by outputs 16 Panel PSTN (i-on30EXD
Quick set Dynamic Test Call
Output 01...12 17 only)
Quick omit Static Test Call
Name Zone Mapping
User code reqd Unset Comms
Type 13
2 Way Replies Speech Dialler (For notes see below.)
Polarity
2 Way Set Instant Call Mode
Pulsed
2 Duress Enable Messages
Partitions

Page 32
i-on30EX Installer Menu

1
Appears only when device learned in.
2
Appears only in a Partitioned system.
3
Appears only in a Level Setting system.
4
Appears only if Exit Mode is “Final Door” “Lock Set” or “Exit Terminate”.
5
Appears only if Exit Mode is “Timed Set” or “Silent Set”.
6
Appears only when System Options – Confirmation Mode is “Basic”.
7
Appears only if System Options – Confirmation Mode is either “DD243” or “BS8243”.
8
Appears only if System Options – Confirmation Mode is “BS8243”.
9
Appears only when Masking is ON.
10
Appears only in EUR version.
11
Appears in this position only in a part setting system.
12
Appears only if communications module fitted, or if using i-on30EXD with certain commands (see Table 2).
13
Options visible depend on communications module fitted, see Table 2.
14
Appears only when Report Type=Fast Format
15
Appears when Report Type=CID or SIA
16
Appears only when Static Test call disabled.
17
Appears only when Dynamic Test Call is disabled.
18
Appears only if Report Mode = Fast Format AND Confirmation Mode = Basic
19
Shows “None” on i-on30EXD.
20
Must be activated by a Eaton’s Security Business External Support Manager.
21
Appears only for KEY-KPZ01 keypads
22
Appears for KEY-K01, KEY-KP01 and KEY-KPZ01.
23
Appears for KEY-KP01 and KEY-KPZ01.

Table 2. Menu Options Available with Communications Modules


With Communications Module
Communications Menu Options: i-on30EX i-on30EXD i-sd02 i-dig02 i-gsm02 8750 GPRS
ARC No Yes Yes Yes Yes Yes Yes
ARC – IP Network No No No No No Yes Yes
Speech Dialler No No Yes No Yes No No
SMS No Yes Yes Yes Yes No No
PSTN SMS No Yes Yes Yes No No No
Line Fail No Yes Yes Yes Yes Yes Yes
Line Fail Delay No Yes Yes Yes Yes Yes Yes
GPRS No No No No No No Yes
Ethernet No No No No No Yes No
Downloading - Rings to answer No Yes Yes Yes No No No
Downloading - Answer on one ring No Yes Yes Yes No No No
Downloading - Access Mode No Yes Yes Yes Yes No Yes
Downloading - Phone Book No Yes Yes Yes Yes No No
Downloading - Secure Callback No Yes Yes Yes Yes No Yes
Downloading - Modem Baud Rate No Yes Yes Yes Yes No No
Downloading - IP address No No No No No Yes Yes

Page 33
i-on30EX/EXD

Note: If you are replacing a keypad on a single-


4. Maintenance keypad system then you will have to re-program
the new keypad with all the functions of the old
The control unit should be inspected once per keypad, including any non-default ABCD key
year. At each inspection: functions.
Check the control unit for obvious signs of
damage to the case or its lid.
Check the condition of the control unit
standby battery.
Check the cabling to the keypad(s) and
expander(s) for signs of damage or wear.
Check the keypads for obvious signs of
damage.
Test the action of all buttons on all keypads.
Clean the keypad surface and display. To
clean the keypad wipe the surface with a
clean soft dry cloth. Do not use water,
solvents or any proprietary cleaning materials.
Monitor the signal strength and battery
condition of all detectors, radio keypads,
remote controls, HUAs and radio sounders.
Test each device. Replace batteries as
recommended by the manufacturer’s
instructions.
Gently clean the lenses of any PIRs with a
clean, soft dry cloth. Do not use water,
solvents or any proprietary cleaning materials.
Walk test all detectors.
Test any external sounders and strobes.
Note that if you wish to find the location of any
keypad or expander you can employ the Test –
Locate Bus Device option in the Installer Menu. Use
this option to make a selected bus device give a
continuous tone from its sounder. Once you have
found the bus device you can silence the tone
either by opening the case and so activating the
device’s tamper, or by pressing  on the keypad
from which you are carrying out the test.
Replacing or Removing Wired Keypads
If you need to remove or replace a wired keypad
from the system at any point then you must follow
the correct procedure. Before physically
disconnecting the keypad enter the Installer
Menu. Then:
To permanently remove a keypad:
Use the Devices/Detectors-Wired Keypads-Delete
Keypad option. This ensures that the system does
not report a missing keypad and the keypad’s
internal address is erased (allowing it to be used
on another system).
To replace a keypad:
Use the Devices/Detectors-Wired Keypads-Replace
Keypad option. This ensures that the replacement
keypad will retain the programming of the old
keypad.
See the i-on Engineering Guide for more details.

Page 34
i-on30EX/EXD

Log capacity Up to 350 events: 250


5. Technical Specification mandatory events, 100 non-
mandatory. Stored in EEPROM
General memory, available for at least 10
years without power.
Product name i-on30EX. Internal Clock ±10 minutes over one year
Product 30 zone hybrid endstation with (depending on the accuracy of
Description remote keypads. the mains supply frequency).
Manufacturer Eaton’s Security Business. User Codes 50 (plus installer code)
Environmental Class II. Remote controls 50 (one per user)
Operating Tested -10 to +55°C. Panic Alarms 50 (one per user)
temperature Proximity tags 50 (one per user)
Humidity 0 to 93% RH, non-condensing. Notes:
Case material Steel. 1. Wired keypads, wired zone expanders, and
radio zone expanders are all bus devices. You
Dimensions: can connect any combination of these devices
Control unit 240 x 250 x 87, mm HxWxD. to the bus.
i-KP01 115 x 156 x 30, mm HxWxD 2. The system can be used as EITHER a
KEY- 128 x 128 x 29, mm HxWxD partitioned system OR a part setting system.
K01/KP01/KPZ01 When used as a part setting system there are
EXP-W10, EXP- 230 x 144 x 44, mm HxWxD four setting levels available: Full Set and Part
WCC, EXP-R10, Sets B, C and D.
EXP-R30
Weight: Security
Control unit 2.72 kg (without stand-by Security Grade Grade 2
batteries). Radio detector 16,777,214 (224 -2).
i-KP01 0.26 kg differs
KEY-K01 0.19 kg Radio Programmable.
KEY-KP01 0.19 kg Supervision
KEY-KPZ01 0.19 kg Number of 50 plus one installer
EXP-W10, 0.42 kg access codes
EXP-WCC, 0.43 kg Access code 10,000 differs with 4 digit
EXP-R10, EXP- 0.39 kg differs codes.
R30 0.39 kg All digits may be any number 0
Capacities to 9.
Code blocking Blocked for 90s after four
Zones 30 max (with expanders) incorrect codes in series.
32
Outputs 12 plug-by communicator Proximity tag 4,294,967,296 (2 )
outputs on control unit, plus differs
30 max for the rest of the
system, comprising:
Power Supply
1 wired on control unit This product complies with the requirements of EN50131-6
(transistor) Type A power supply at Grade 2 and environmental class II.
4 transistor based on each wired
expander Power supply type A
8 radio outputs on each 768/769 Mains power supply 230VAC +10%/-15%,
2 radio outputs on each 762 requirements 200mA max, 50Hz.
Expanders and 10 max devices (see note 1) Total power supply 1.0A
Wired Keypads capacity: (of which 200mA is used
Radio Keypads 4 max (two per radio expander) for battery recharge and
External Radio 4 max (two per radio expander) 800mA is available for
Sirens powering the system).
WAMs 1 max (repeater mode only) 12V Aux supply*: 550mA max
Loudspeakers 1 on control unit, 1 per expander 12V Bell supply* 550mA max
Plug on One Comms power 400mA max
communication supply*:
modules 12V Expander Bus*: 400mA max
Other ports 1 x USB LS connectors 280mA in alarm.
Partitions 4 (see note 2) *Note: The ratings given here represent the
maximum current that can be drawn before
triggering over-current protection.

Page 35
Technical Specification i-on30EX/EXD

EN50131-6 ratings
The i-on30EX/EXD provides space for one 7Ah
Electromagnetic
battery. Compatibility
For Security Grade 2 the required battery standby
Immunity Conforms to EN50130-4.
time is 12 hours. This means that all the devices
Emissions Conforms to EN61000-6-3.
powered by the backup battery, including the
control unit and at least one keypad, should Outputs
together draw no more in total than an average of
580mA over a 12 hour standby time. Panel: Open collector transistor,
O/P 1, Bell, +12VDC when inactive, 0V
The table below shows the current consumption of
Strobe when active. 500mA max.
the control unit and each device that can be fitted
Plug-by O/P 1- Open collector transistor
to it.
12 +12VDC when inactive, 0V
CIE power 100mA min. when active, 50mA max.
requirement: 120mA max LS Min impedance 16 Ohm per
i-kp01 power 30mA (backlight off) (loudspeaker) output, current consumption =
requirement: 45mA/65mA (backlight 280mA in alarm.
norm/bright) Expander: Open collector transistor,
60mA in alarm Outputs +12VDC when inactive, 0V
KEY- 35mA backlight OFF, when active. 500mA max.
KPZ01/KP01/K01 internal prox reader only. Note: The current is limited by
power requirement 65mA max backlight ON, the amount available from the
external prox reader power supply driving the
connected expander.
Wired Expander 20mA max quiescent.
requirement 300mA in alarm if KEY-KPZ01 Open collector transistor,
sounder connected. Outputs +12VDC when inactive, 0V
Radio Expander 40mA max quiescent when active, 500mA max.
requirement 320mA in alarm if Sounder Volume Levels (at 1m)
sounder connected.
Battery charging 200mA (recharge within i-kp01 (at max volume) 70dB
requirement: 72 hrs) Expander piezo sounder 70dB
Plug-on i-sd02, i-dig02: Panel/Expander 16 Ohm loudspeaker 93dB
Communicator power
requirement:
20mA quiescent
50mA max
Fuses
Plug-on i-gsm02: The control unit has a replaceable T250mA mains
Communicator power 150mA quiescent fuse.
requirement and max.
Plug-by 5mA each when active. Electrical Safety
Communicator pins Conforms to EN60950-1.
require:
10 FSL zones 20mA Other
5 four-wire CCL zones 30mA If you wish to connect the i-on30EX/EXD control
12V Bus output 10±0.5V to 13.8V unit to a PC using the USB port then make sure
voltage range : that the cables have the following specifications:
12V Aux output 10±0.5V to 13.8V
voltage range: USB Mini-B plug for control unit end,
12V Bell output 10±0.5V to 13.8V USB-A for PC end. Max length
voltage range 3m.
Max p-to-p ripple 0.5V
voltage: Radio Expander and Keypads
Standby Battery: 12V, 7Ah sealed lead Radio Operating frequency
acid (not supplied). 868.6625MHz Narrowband.
‘Low battery’ fault at: < 12V EN 300 220-3.
Aux power output fault < 9V EN 300 330-2
at: Transmitter The range of the transmitters
Deep discharge 10±0.5V range compatible with this control unit
protection at: depends on the environment in
Serviceable Mains fuse: 250mA (T) which they are installed. As a
components: guideline, most transmitters will
Standby time: See “Power Availability” work at in excess of 200m
on page 12. range in free space conditions.

Page 36
i-on30EX/EXD Technical Specification

xcelwpt Pet tolerant wired PIR


Compliance Statements
Sounders
The i-on30EX and i-on30EXD are compliant with
EN50130-5 environmental class II. 760ES External Wireless sounder
The i-on30EX and i-on30EXD are suitable for use 9040UK-00 Speaker boxed
in systems designed to comply with PD 6662: Setting / Unsetting – Keypads
2010 at grade 2.
i-rk01 Radio Keypad
When fitted with radio devices the i-on30EX and i-
i-kp01 Keypad (with internal prox
on30EXD are capable of compliance with
reader, but without zones or
EN50131 at Grade 2.
external prox reader)
The built in communicator in the i-on30EXD is KEY-EP External prox reader for
compliant with EN50136-1 as an ATS2 KEY-KPZ01/KP01
communicator.
KEY-K01 keypad
At Grade 2 the built in communicator provides a KEY-KP01 keypad with internal prox
compliant communicator for the i-on30EXD reader and terminals for
provided that: external prox reader
a) It is connected in accordance with the KEY-KPZ01 keypad, with internal prox
installation instructions. reader, two zones, one
b) The connected PSTN is functioning normally. output and terminals for
external prox reader
When using its built in communicator this product
provides options A, B and C at Grade 2 as noted Setting / Unsetting - Fobs
in Table 10 of EN50131-1:2006+A1:2009.
FOB-2W-4B Two-way keyfob
If the installer selects a non-compliant i-fb01 Four button remote control
configuration then they must remove or adjust
727rEUR-00 Four button remote control
compliance labelling
with encrypted code (HUD
Third party testing carried out by Anpi. function not compatible with
BS8243 or DD243)
Compatible Equipment Communicators
HUD i-dig02 PSTN Communication (ARC
705rEUR-00 Two button HUD (single only).
channel, top button is i-gsm02 GSM communications
disabled) module
706rEUR-00 Two button HUD/tilt switch i-sd02 PSTN Communication
transmitter module with speech dialling
710rEUR-00 Two button HUD Accessories
726rEUR-50 Long range hand held HUD
703rEUR-00 4-channel (2 zone)
726rEUR-60 Short range hand held HUD transmitter
Detectors 762rEUR-00 Two Channel Receiver
713rEUR-00 Pet tolerant PIR 768rEUR-50 Eight Channel Receiver
714rEUR-00 PIR Transmitter (Small case) 770rEUR-00 Wireless Accessory Module
720rEUR-00 Smoke Detector Transmitter 771rEUR-00 Info Module
734rEUR-00/01 CC/FSL Door Contact i-rc01 Relay Card
Transmitter (white)
734rEUR-05/06 CC/FSL Door Contact
Transmitter (brown)
738rEUR-00/04 Spyder shock sensor
(white/brown)
739rEUR-50 Sentrol glass break detector
DET-RDCS Combined door contact
shock sensor transmitter
xcelr Radio PIR
xcelrpt Pet tolerant radio PIR
xcelw Wired PIR

Page 37
i-on30EX/EXD

NOTES:

Page 38
i-on30EX/EXD

NOTES:

Page 39
i-on30EX/EXD

Product Support (UK) Tel: +44 (0) 1594 541978.


Available between:
08: 30 to 17:00 Monday to Friday.
Product Support Fax: (01594) 545401
email: techsupport@coopersecurity.co.uk
Part Number 12435139 21/1/2014
A

Page 40

You might also like