REL 521

Protection and control terminals

ABB India
Utilities - Automation
1
REL 521

Philosophy

• Platform concept

• Flexible functionality selection

• Application well proven


“algorithms”using new technology

ABB India
Utilities - Automation
2
REL 521
Dominant philosophy today

• Stand alone functions


• Distributed intelligence and data base
• Democratic system - no master/slave
• Self monitoring/Fault tolerance
• Co-ordinated protection, control and monitoring

Monitoring
Remote Local Main Back-up Auxiliary
Control Control Protection Protection Functions

ABB India
Utilities - Automation
3
REL 521
Combination of Protection and Control
Integrated with Integrated with Integrated
remote back-up Co-ordinated local back-up duplicated

Protection Protection Protection


Protection

Control Control Control

Block
input (optional)

Remote Local Control


back-up Control back-up
Protection Protection
Protection

ABB India
Utilities - Automation
4
REL 521

1 - Distance protection
2 - Three phase power swing unit
1 10 3 - Directional earth fault protection
4 - AC supervision circuits
5 - DC supervision circuits
6 - STUB protection
2 7 - Auxiliary relays
3 11 12 8 - Fault locator
4 5 13 14
C

E 9 - (Printer for fault locator)


10 - Disturbance recorder
6 7 15 11 - Signaling unit
8 16 12 - Parts of event recorder
13 - Breaker failure protection - 1 CB
9 17 14 - Tripping relays
15 - Autoreclosing for one CB
16 - Synchro check for one CB
Two relay panels 600mm x 650mm x 2250mm 17 - Auxiliary transformers for
disturbance recorder

ABB India
Utilities - Automation
5
REL 521
Numerical design
x

x x

x
Sine wave 4 samples 1 cycle 40 samples 1 cycle

Logic
Signal Measuring
conditioning algorithm Memory

MMI, local or remote communication

ABB India
Utilities - Automation
6
REL 521
Continuous measurement and calculation of all loops
every millisecond = accurate and adaptive

• Full scheme distance Accurate X, R, KN per zone/fault


• Current differential Adaptive CT saturation detector
• Breaker failure protection Adaptive measuring range at current change
• Fault locator Adaptive fault locator with load compensation,
< 2% accuracy
• Event recorder 1ms resolution
• Disturbance recorder 10 Analogue, 48 BI, 40 sec.

ABB India
Utilities - Automation
7
REL 521
Benefits of self-supervision technique

Instant MTTR 1 year


of failure
Long interval
periodic testing
Test interval (2 years)

MTTR 1 day

With continuous
self-supervision

Protection available
Protection not available

ABB India
Utilities - Automation
8
REL 521
Information Technology
SCS
The right information for the Substation Control System
On-line information
right person at the right time

SMS
Substation Monitoring System
On-demand information

ABB India
Utilities - Automation
9
REL 521
Line distance protection for HV/EHV

3/4 - 6U

• Fulfils high requirements on selectivity for


single and double lines
• Directly earthed networks
• Overhead lines
• Cables
• Multi-circuit lines
• Single pole tripping

ABB India
Utilities - Automation
10
REL 521
Case

• Closed cases of common look


• Mother board under the front plate
• Screw connection terminals
C

E
• Built-in HMI unit with optical PC port
• selection of 1/2, 3/4 and 1/1 of 19” wide
Rear view • 6U =265.9 mm high
X22X20 X18 X16 X11
X13 1
2
3
4

5
• 205-245 mm deep
6

• 19” rack, panel and surface mounting


7
8
9
10

11
12
X23 X21 X19
X12
• Delivery specific configurations e.g. ports
X15 for serial communication or integrated
COMBITEST switch in adjacent case

ABB India
Utilities - Automation
11
REL 521
Common look

C C

E E

Height: 6U/265,9 mm
Depth: 205/245 mm

ABB India
Utilities - Automation
12
REL 521
Mounting

Wall Flush Semiflush

ABB India
Utilities - Automation
13
REL 521
Interface

Human Machine Interface, (HMI) functions:

• Indications
• Event logging and presentation
• Service values from analogue
Ready Start
Ready Start Trip
Trip input modules and protection
RET5xx
REx 521 Ver.2.0
Ver 2.0
E =Enter
E= Enter menu
menu functions, (i.e. differential
C =Reset
C= Reset LED
LED currents, etc.)
• Settings: reading, changing
C • Partial configuration
• Self-monitoring information
E
• Port with optic interface to RS
232 for local PC
ABB India
Utilities - Automation
14
REL 521
Hardware structure

Optional Basic Optional


Power Supply Command
Analogue A/D Signal Main
Input Conversion Processing Processing Binary I/O Binary I/O Binary I Output Analog Comm.
Module Module Module Module Module Module Module Module Module Module

10 AI 2 kHz DSP1 DC/DC 8-72 BI 6-36 56/64


4 0.01- 16-144 12-48
DSP2 48-250V 10-90 BO BI BO AI kbit/s
110 In
(2-18
DSP3 ReedBO)
4 DSP4 Logics 4BI
1 5BO 24
DSP5 HV
5I
A/D DSP6 App
5U
1 DSP7

~
~ ~
~ DSP8
Comm-
DSP9 CAN 1Mbit/s
uni-
DSP10
cation
DSP11 I/O I O AI HDLC
I/O
DSP12

TS SMS PC
4BI/5BO 8BI/10BO 16 BI 12 BO 6 AI Fiberoptic

SCS HMI x (1-9) x (1-9) x (1- 4) x (1- 6) Galvanic

ABB India
Utilities - Automation
15
REL 521
Hardware structure
Modules for AC input U+I
ABB Network Partner REx5xx

5 Currents
and
5 Voltages
Ready Start Trip
REx5xx Ver.2.0
E= Enter menu
C= Reset LED

C
E
U

5 Voltages
Rated value :
100/110/115/120 or
I 200/220/230/240 V

5 Currents
Rated value :
1 or 5 A

ABB India
Utilities - Automation
16
REL 521
Hardware structure
Modules for communication and signal processing
ABB Network Partner REX5XX
Signal Processing
module

Ready Start Trip


REx5xx Ver.2.0
E= Enter menu
C= Reset LED

C
E
Power Supply
module

Main processing
module

AD-converter
module

ABB India
Utilities - Automation
17
REL 521
Hardware structure
Modules for I/O
ABB Network Partner REx5XX DCM

serial remote
Ready Start
REx5xx Ver.2.0
E= Enter menu
C= Reset LED
Trip
MIM communication
C
E module

1/2 Case < 3 modules IOM


3/4 Case < 8 modules 6 transducer inputs,
1/1 Case < 13 modules settable range within + 20 mA
BOM
12 binary outputs
and 8 binary inputs
BIM

24 binary outputs

16 binary inputs

ABB India
Utilities - Automation
18
REL 521
Binary input module

• 16 Independet Binary Inputs


• Debounce filter, T = 5 ms
• Oscillation suppr. detection within
1 s; > 0 - 40 Hz
• Pulse counting at all inputs
• Time stamping on each input
• Variants for 24/48/110/220V

ABB India
Utilities - Automation
19
REL 521
Binary input module

Debouncing suppression function for binary inputs

T = 5 ms

Time tagged event

If the time elapsed since the


event occured T > 5 ms,
the event is set to valid

ABB India
Utilities - Automation
20
REL 521
Binary input module

Oscillating suppression/detection for binary inputs

>N
Input signal is suppressed
if the number of valid events
1s within 1s > N = 0 - 40 Hz

<n Input signal previously


oscillating is detected if the
number of valid events
1s within 1s < n = 0 - 40 Hz

ABB India
Utilities - Automation
21
REL 521

Binary output module

• 24 Single Output Relays or


12 Double pole Command
Output Relays

• Auxiliary voltage: 24/48/110/220 V

ABB India
Utilities - Automation
22
REL 521

Binary output module


Command supervision

Close coil
+ Double Pole Command
-
outputs with supervision

Open coil

-
- Single outputs without
supervision
+
ABB India
Utilities - Automation
23
REL 521

Binary in/out module

• 8 Independent Binary Inputs


and
• 12 Binary Output Relays (2 Reed)

• Fix filter time 5 ms

• Auxiliary voltage: 24/48/110/220 V

ABB India
Utilities - Automation
24
REL 521

Analogue input module

• 6 Independent Input channels


• Software selected Input ranges:
0-5, 0-10, 0-20, mA
1-5, 2-10, 4-20, mA
± 5, ± 10, ± 20 mA
• Resolution: 16 bit
• Accuracy: 0,2%
• Independent settable digital filters
• Supervision of:
Limits, Overflow and Max/Min Range

ABB India
Utilities - Automation
25
REL 521

Transformer module

• Isolation barrier prevent disturbance


entering
• Adapts measured values to
electronics circuitry
• Up to 10 analogue inputs 50/60 Hz:
• 5 U, 100-120V or 200-240V
• 5 I, 1A or 5A rated current
• Accuracy U,I 2.5% or 0.25% (factory
calibration) P 5% or 0,5% (factory
calibration)

ABB India
Utilities - Automation
26
REL 521

A/D Conversion module

• 12 bit voltage resolution


• 16 bit current resolution
• 2 kHz sampling frequency
• Transmission of data to CPU via a
supervised link of RS 485 type
• Transmission once every ms
including checksum

ABB India
Utilities - Automation
27
REL 521
Main processor module

• Memory:
• up to 8 Mb DRAM
• up to 8 Mb CodeFLASH
• 0,5 Mb DataFLASH
• 12 Digital Signal Processors on separate board
• Main Controller/CPU type Motorola 68360, 25
MHz
• 5 independent serial Links:
• CAN bus for I/O 1 Mbit/s
• Built in HMI
• Substation Monitoring via SPA
• Substation Control System via LON

ABB India
Utilities - Automation
28
REL 521
Power supply module

• DC/DC Converter providing full isolation


between terminal and external battery
system
• Input range: 48 - 250 V d.c.
• Internal fail relay output (1/1 19” Case)
• Internal fail, 4 Binary inputs and 4 Binary
outputs (3/4 and 1/2 19” Case)

ABB India
Utilities - Automation
29
REL 521
Optical communication connectors

Opto Main processing module


modules

IEC 870-5-103
Glass or SPA

LON
Plastic

ABB India
Utilities - Automation
30
REL 521
Serial remote communication alternatives

REx > • Digital 56/64 kbit/s channel


Galv cable < 4 km
5xx < • Direct fibreoptic or galvanic cable
REx
> • Dedicated or multiplexed channel
Opto fibre < 30 km
5xx < • CCITT standard or route switched
>
communication network
REx >
< FOX < • Supported communication
5xx 20 Opto fibre < 120 km
• CCITT 56 or 64 kbit/s
REx < >
< 100 m MUX • V.36/V11 Co/Contra directional
5xx
• X21/X27
REx >
Modem MUX
• G 703 ( via converter) EIA
< <>
5xx Opto fibre • RS530/RS422
< 30 km

ABB India
Utilities - Automation
31
REL 521
Terminal Functions
Platform related functions Basic functions
• Self supervision with internal event • 3 zones phase-phase protection
recording • 3 zones phase -earth protection
• Real time clock with input for external • Phase selection logic
time synchronisation
• Scheme communication logic
• Four groups of setting parameters
• Current reversal and WEI
• Local Human Machine Interface
• Local acceleration logic
• Configuration logic
• Instantaneous phase O/C protection
• Service value reading
• Time-delayed phase O/C protection
• Monitoring of AC measurement
• Instantaneous earth fault O/C protection
( non-directional )
• Time-delayed earth fault O/C protection
( non-directional )
• Three-pole tripping logic
• Event recorder
ABB India
Utilities - Automation
32
REL 521
Terminal Functions

Line impedance Current measurement


• Additional zone 4 protection • Stub protection
• Additional zone 5 protection • Breaker failure protection
• Power swing detection • Inverse time earth fault O/C protection
• Power swing additional logic • Earth fault directional check and
communication logic
• Automatic switch onto fault logic
• 4-step earth fault O/C protection (option)

ABB India
Utilities - Automation
33
REL 521
Terminal Functions

Voltage measurement Secondary system supervision


• Time-delayed U/V protection (option) • Current circuit supervision
• Time-delayed O/V protection • Fuse failure supervision (zero seq. based)
• Time delayed residual O/V
protection(option)

Power system supervision


• Broken conductor check
• Loss of voltage check (option)
• Overload supervision

ABB India
Utilities - Automation
34
REL 521
Terminal Functions

Control Logic
• Command control (option) • Single or two-pole tripping
• Synchro-check and energising check • Pole discordance logic (option / contact
based)
• Synchro-check with phasing and
energising check (option) • Additional configurable logic
• Autorecloser logic,1 and/or 3 phase • Channel test communication logic
• Autoreclosing logic, 3 phase (option) • Binary signal transfer to remote end
• Binary signal interbay communication

ABB India
Utilities - Automation
35
REL 521
Terminal Functions

Monitoring Communication module alternatives


• Disturbance recorder, 40 seconds • Galvanic interface

• Fault recorder
• Fibre optical modem

• Trip value recorder


Serial communication modules
• Increased measuring accuracy for
• SMS, port IEC 870-5-103 or SPA
U, I, P, Q ( + 0,25% U,I and + 0,5% P)
• SCS, port LON

Metering
Hardware
• Pulse counter logic • Case size 3/4 or 1/2 x 19”
• 8 I/O, 3/4 x 19” or 3 I/O, 1/2 x 19”
HMI language
• English
ABB India
Utilities - Automation
36
REL 521
Distance protection function

ZM 5 • 3 to 5 zones with independent settings,


ZM 4 direction and timers
ZM 2 • Phase-phase and three-phase
ZM 1 measurement loops
• Phase-ground and phase-phase-ground
measurement loops
• Quadrilateral characteristic for maximum
fault resistive coverage
• Directional check using positive voltage
polarisation and memory

ZM 3
Zone 1

ABB India
Utilities - Automation
37
REL 521
Phase preference logic

Practically all cyclic and acyclic phase preferences can be selected by


setting as a parameter within each of four setting groups

R R
S S
T T

ABB India
Utilities - Automation
38
REL 521

Software functions

Z< Z< Id I I>> I>, t


5

I >
I t P,Q > U>, t U<, t

ABB India
Utilities - Automation
39
REL 521

Library of Functions
Future
Fault locator
Phase preference logic
Series compensation
Fuse failure
Time delayed o/c protection
Instantaneous o/c protection
Synchro- and dead-line-check
Breaker failure protection
Auto-reclosing
Line differential protection
Earth fault o/c protection
Distance protection
PROTECTION AND
CONTROL FUNCTIONS
ABB India
Utilities - Automation
40
REL 521

Monitoring library

HMI Station monitoring


On-request

Disturbance overview

Report 2 Report 3
Report 1

Pulse
counter 961201.222 Start L1
961201.333 Trip T3 111111
961203.555 CS L1 22222
961203.666 Block L1 d
33333

Disturbance Event Trip Fault


recording recording values locator

P,Q
ABB India
Utilities - Automation
41
REL 521
Communication alternatives

LON
– Commands
Station bus – Settings
LON SPA – Measured values & status information
REx REx – Interbay commands & status information
C
E C
E
– Events & disturbance reports
SPA

LON SPA
SPA
– Commands
REx
C
– Settings
E

SPA
– Measured values & status information
– Events & disturbance reports
MMI / RTU
Station bus
IEC 870-5-103
GW or
LON IEC 870-5-103
LON IEC 870-5-103 – Events & disturbance reports
– Measured values
REx REx
C
E C
E
– Function commands
SPA SPA
ABB India
Utilities - Automation
42
REL 521
Power swing detection and logic

X • Independent measuring elements in


three phases
• Settable X, R and transition time
• Adaptive timing of sequential swinging
R • One or two out of three logic for
detection
• Controlled by the residual current for
dt inhibit of PSD
0-60 s • Logic permits non-controlled zones to
operate during power swings

ABB India
Utilities - Automation
43
REL 521

Automatic or contact switch-onto-fault logic

• A programmable binary input is always included


and can be connected to the CB aux. contact or
CB control switch
• Separate, automatic SOTF logic measures the
line currents and voltages
• Function is active for 1 s after the closing of the
circuit breaker

ABB India
Utilities - Automation
44
REL 521

Programmable communication schemes

Extension
Extension Autorecloser
Autorecloseror
orLoad
Load
scheme controlled overreach
controlled overreach
scheme

Underreach
Underreach Unblocking
Unblocking
Permissive
Permissive
Unblocking
Unblocking
Overreach
Overreach weak
weakinfeed
infeed
transient
transientblocking
blocking
Blocking
Blocking Overreach
Overreach

ABB India
Utilities - Automation
45
REL 521

Phase selective tripping on parallel lines

CSL1
CSL2 CSL1
• Logic for phase segregated
permissive overreach transfer
L1 trip
CSL1
CSL2 CSL2
• Correct single phase trip at all
simultaneous faults
L2

ABB India
Utilities - Automation
46
REL 521
Distance protection - phase selection

X
• Independent phase selection
Zone 2
criteria, HV, EHV
• Independent setting of
Zone 1 characteristic for:
- reactive reach
- resistive reach
- ground return
R

ABB India
Utilities - Automation
47
REL 521

Non-directional earth fault O/C protection

Definite • Inverse or definite time delay


Logarithmic inverse • Second harmonic restrained
Normal inverse • Settable min operate current
t min and time delay
I min
Very inverse

Extremely inverse

ABB India
Utilities - Automation
48
REL 521
Directional earth fault O/C protection

• Polarising 3Uo > 1% of Ur


• CVT filter
• Inverse or definite
Reverse time delay
operation
• Forward and reverse
3Io = 0,6 x 3Io • Characteristic
3Io
Upol angle + 65o
• Communication logic
- Blocking
3Io - Permissive
- Fault current reversal
Forward
operation - Weak end infeed
echo and trip
ABB India
Utilities - Automation
49
REL 521
Sensitive earth fault protection

• Well proven RXPF 4 relay is


Operate incorporated into the protection
scheme
• Has extremely low power
consumption (0.015mVA)
3Io • Applicable in extensive high
-90o impedance earthed networks
• Has wide setting ranges for:
Upol - operating current
3Io
- voltage release
0o - characteristic angle is 0o or -90o
Operate

ABB India
Utilities - Automation
50
REL 521

Fuse failure supervision

IL • Measuring quantities are


selectable between:
• zero sequence voltage and
current:
U0 > Uref and I0 = 0
• negative sequence voltage and
current:
U2 > Uref and I2 = 0
< Z5xx
REx

ABB India
Utilities - Automation
51
REL 521
Broken conductor

IL

• Detects:
- broken line conductors
- open poles of circuit breakers
- broken connections in the
secondary circuits of CTs
- overload conditions during normal
< Z5XX operation
REL
• Function is programmable to trip and
alarm

ABB India
Utilities - Automation
52
REL 521

Breaker failure protection (BFP)

Current detector
ASD
Current Back-up trip
&
RMS-value (Busbar)

t t2
Start &
t1
Retrip of own
circuit breaker

ABB India
Utilities - Automation
53
REL 521
SSUP - Overload & STUB

• Time delayed O/C protection


• Can trip CB or only inform
the operator
• Instantaneous overcurrent
Line discon.
25 ms protection of STUB when a
open line disconnector is open
& Trip
Ι STUB>

ABB India
Utilities - Automation
54
REL 521
Overcurrent protection functions

• High set instantaneous O/C


protection
I>> - reduces the operate time at heavy
close in faults
• Time delayed O/C protection is a
back-up to distance and differential
t protection in
- normal operation
I> - at fuse failure or
- communication error conditions

ABB India
Utilities - Automation
55
REL 521
Voltage protection functions

t • Phase or summation voltage


measurement
U> • Instantaneous and time delayed
overvoltage protection function
• Instantaneous and time delayed
undervoltage protection function
t • Both functions can be used as
stand alone functions or together
U< with other protection and control
functions

ABB India
Utilities - Automation
56
REL 521
Synchronism and Energizing check

UBus

FreqDiff < 50-300 mHz U Bus


ULine UBus o 1-ph
PhaseDiff < 5-75
UDiff < 5-50% Ur
U Line ULine
UHigh > 50-120% Ur 3-ph (or 1-ph)
ULow < 10-100% Ur
Fuse fail
SYNC-BLOCK

ABB India
Utilities - Automation
57
REL 521
Synchrocheck with voltage selection within bay
selection

BUSBAR 1

• Voltage selection for double bus,


BUSBAR 2

single breaker
REB551

U5
AI
U-BUS 1 • Voltage selection for 1 ½ circuit
SYNC

VS 1R U5
U-BUS 2
U4
UL
1R

3R
U4

UL
U-Line breaker arrangement
I-Line
BI/BO
B1OPEN
3I

B1CLOSED

B2OPEN
• Selection is made using one
I/O-board
B2CLOSED

U5FF
EXTERNAL FUSE FAILURE(MCB)
U4FF

ABB India
Utilities - Automation
58
REL 521
Auto reclosing (AR)

Three phase AR Single phase AR

1 2

Sequential autoreclosing of two circuit breakers

ABB India
Utilities - Automation
59
REL 521
Sequential auto-reclosing

Line volt

Fault CB1
REB 551

C
E

Line prot.
WFMASTER
CB1
WAIT
CB1 AR t1
CB2
REB 551

WFMASTER
C
E

CB2

WAIT
t1
CB2AR
t

ABB India
Utilities - Automation
60
REL 521
Single- / Two/ Three-phase reclosing programs

Program-Shot 1 Program-Shot 2, 3 and 4


• 3-phase AR ⇒ shot 2, 3 and 4: 3-phase AR
• 1or 2or 3-phase AR ⇒ shot 2, 3 and 4: 3-phase AR
• 1or 2-phase AR ⇒ shot 2, 3 and 4: 3-phase AR
• 1-ph AR or one 2-ph AR ⇒ 1-ph AR:shot 2, 3 and 4,3ph AR
(2-ph AR only 1 shot)
• 1 or 2 ph AR or one 3 ph AR ⇒ 1 or 2-ph AR: shot 2, 3 and 4,
3 phase AR.
(3-ph. AR only 1 shot)
• 1ph AR or one 2 or 3 ph AR ⇒ 1-ph AR:shot 2, 3 and 4,3ph AR
(2 or 3-ph AR, only 1 shot)

ABB India
Utilities - Automation
61
REL 521
Disturbance report for the last 10 disturbances

• Disturbance Overview
Event Disturbance
• Event Recorder
Recorder Recorder • Disturbance Recorder
• Fault Locator
• Trip Values
Disturbance
Overview • Common functionality:
- Date and time
- Number of stored disturbances
Fault Trip - Triggering conditions
Locator Values

ABB India
Utilities - Automation
62
REL 521

Disturbance overview (PC):


• Disturbance index
Event Disturbance • Date and time of disturbance
Recorder Recorder • Tripping and triggering signals
• Distance to fault
• Duration of disturbance
Disturbance
Overview Disturbance summary (HMI):
• Date and time of disturbance
Fault Trip
• Appearance of selected
indications
Locator Values
• Distance to fault
• Duration of disturbance

ABB India
Utilities - Automation
63
REL 521
Disturbance summary

Disturbance
DisturbanceReport
Report

Disturbance
Disturbance Disturbance
Disturbance Disturbance
Disturbance
No.
No.11 No.
No.22 No.
No.10
10

General
General Event
Event Disturbance
Disturbance
Indications
Indications Trip
TripValues
Values
Indications
Indications Recorder
Recorder Recorder
Recorder

ABB India
Utilities - Automation
64
REL 521

• On-line or on-request capture of


up to 48 different binary event
Event Disturbance channels
Recorder Recorder • Time stamping of individual
signals
Disturbance • Programmable triggering function
Overview
• Analog inputs may generate
events through limit check, incl.
Fault Trip dead-band supervision
Locator Values

ABB India
Utilities - Automation
65
REL 521

• Typical recording time 40 s


• 10 analogue and 48 binary
Event Disturbance signals (all signals selectable)
Recorder Recorder • Programmable triggering
• Synchronised with other units
Disturbance and functions
Overview • Settable recording times
• On-request by means of PC
Fault Trip
• On-line in station automation
Locator Values
system

• REVAL evaluation software


ABB India
Utilities - Automation
66
REL 521

• RANZA / REL 100 measuring


algorithm
• Accuracy better than 2%
Event Disturbance
Recorder Recorder • Distance to fault presented in
km, miles or % of line length
Disturbance • Algorithm compensates for
Overview double end infeed of fault
current, load current, fault
resistance and mutual coupling
Fault Trip
from parallel line
Locator Values
• Recalculation of distance to
fault possible for different
system conditions

ABB India
Utilities - Automation
67
REL 521

• Phasors of currents and


voltages before and during the
Event Disturbance fault
Recorder Recorder • Settable triggering conditions

Disturbance
Overview

Fault Trip
Locator Values

ABB India
Utilities - Automation
68
REL 521
Setting parameters for the distance protection

jX
R1Z1
X1Z1(2,..,5) reach in reactive direction in
ohms
R1Z1(2,..,5) positive sequence
resistance of protected line section in
ohms
X1Z1 RFZ1(2,..,5) fault resistance for phase-
to-phase faults (arc resistance) in
ohms
RFNZ1(2,..,5) fault resistance for phase
to earth faults (arc and tower footing
R resistance) in ohms
RFZ1 RFNZ1

ABB India
Utilities - Automation
69
REL 521
Setting parameters for the distance protection

jX 1
RNZ1 RN = ⋅ ( R 0 − R1 )
3
1
XNZ1 XN = ⋅ ( X 0 − X 1 )
3

X0Z1(2,..,5) zero sequence reactance of


X1Z1 protected line section

R R0Z1(2,..,5) zero sequence resistance of


RFNZ1 protected line section
KN is calculated automatically

ABB India
Utilities - Automation
70
REL 521
Setting parameters - phase selectors

jX

Phase to earth elements


XNPHS
X 1 PHS ≥ X 1Zn
X 0 PHS ≥ X 0 Zn
RFNPHS ≥ R1Zn + RNZn +
+ RFNZn
line

1
RNZn = ⋅ ( R0 Zn − R1Zn)
3
RFNPHS R

ABB India
Utilities - Automation
71
REL 521
Setting parameters - phase selectors

jX

X1PHS
Phase selectors for ph-ph faults

X 1 PHS ≥ X 1Zn
RFPHS ≥ 2 ⋅ R1Zn + RFZn
line

70o
R
RFPHS

ABB India
Utilities - Automation
72
REL 521
Setting parameters - phase selectors

jX Phase selectors for 3-ph faults

Additional conditions according to


the position of
B X2.sqr(3)
line

2
A≡ ⋅ RFPHS
A 3
110o
2
R2.sqr(3)
R B≡ ⋅ XFPHS
3
ABB India
Utilities - Automation
73
REL 521
Setting - Overcurrent earth-fault protection (O/C E/F)

 Optimum between high sensitivity and unwanted


operation due to unbalance conditions in the
T R network and CT circuits

R S  The minimum operating current IMin must be set


higher than the maximum expected current
S T under unbalanced conditions
• un-transposed lines with strong zero seq.
mutual coupling
• 80A is recommended as a minimum primary
operating value

 Time delay according to normal practice

ABB India
Utilities - Automation
74
REL 521
Setting - Overcurrent earth-fault protection

 The inverse time characteristic is a


compro-mise between short fault
clearing time and selective
Independent operation in a large current range
Logarithmic inverse
 Imin optimizes short opera-ting time
Normal inverse and selectivity against false E/F
t min
currents
I min
Very inverse
 tmin must be coordinated with the
time delay of zone 2 distance
Extremely inverse protection

ABB India
Utilities - Automation
75
REL 521
Setting - Non directional O/C E/F protection

~  Inrush current at energisation of a solidly earthed


power transformers is an example of false earth
fault current

 Its amplitude and duration can operate the O/C


E/F protection

 ABB Network partner uses a built-in second


harmonic stabilization
• prevents unwanted operation when the
content of second harmonic is higher than
20% of the total residual current
• the setting of the operating current must be
increased on very rare occasions
~
ABB India  Coordination with single pole AR
Utilities - Automation
76
REL 521
Setting - Directional O/C E/F protection

IX

 The minimum operating voltage must


Reverse be higher than the expected false
operation
voltage

 Block the directional comparator


during the single phase
autoreclosings
IR
Forward
operation  Communication schemes: IFmin
represents the primary operating
current for the reverse looking
directional element
U sec
U min = IF min⋅ Z 0 min⋅
Uprim
ABB India
Utilities - Automation
77
REL 521
Setting - Directional O/C E/F protection: permissive schemes

 Timer TOEF increases the security against unwanted operation caused


by spurious CR signal
• setting range 0 - 150 ms
• 30 ms is generally sufficient
• be aware of set “reset” time of communication equipment
 Increase the setting of operating 3U0 voltage to avoid unwanted trip by the
weak-infeed logic due to spurious communication signals
• at least two times the false open delta voltage
• measure the false open delta voltage at normal operating conditions

ABB India
Utilities - Automation
78
REL 521
Directional O/C E/F protection: blocking schemes

 Timer T0EF should be set to channel transmission time with 20-30 ms


safety margin

 With the power line carrier equipment T0EF setting is recommended to


be equal to two times the channel transmission time

 Be aware of channel reset times with all communication schemes

ABB India
Utilities - Automation
79
REL 521
Fault locator: settings
 Line and source parame-ters are
settable under the line reference
data

 Set the source resistance

T R  Zero sequence mutual reactance


R S and resistance for parallel lines

S T  Measure the residual current from


parallel circuit

 The fault current measuring time


depends on CB
• 1.75 cycle for moderate CB
• 1.25 cycle for fast CB

ABB India
Utilities - Automation
80
REL 521

Configuration Tool CAP531 and CAP/REx 5xx


for engineering of configuration

ABB India
Utilities - Automation
81
REL 521
CAP 531Configuration tool for REx 5xx

• Based on international standard for


programming tools IEC1131
• Presents the process on different
ways:
- functional block diagrams
- flow charts
- operating networks
- etc.
• Built in testing facilities
• Documentation files and printouts
• Real time signal monitoring

ABB India
Utilities - Automation
82
REL 521

CAP/REx5xx - Terminal function blocks

BI
1.1 Z_BLOCK Z_TRZ1
BO • Terminal function block library for
2.1
1.2 Z_CR
Z_CRG Z_TRZ2
REx 5xx
1.3 Z_BC OR
1.4
Z<
Z_T2
• Both hardware and software
START functions
AR_CB_READY
1.8
AR_CLOSE_CB 2.2 • Each terminal function is an
AR
AR_P3PH
independent block in graphic form

1.9 TRIP_EXT_3PH
• Functions are independently
TRIP_CB_A
1.1
tested and documented
TRIP • Consistency check between CAP
configuration file and terminal
function set
ABB India
Utilities - Automation
83
REL 521

CAP 531 Configuration tool

• Applies to protection as well as control terminals


• Utilises standard PC with MS Windows, Windows 95 or NT
• Provides a graphical overview of the internal configuration
of the terminal
• User-friendly navigation
• Easy to change default configuration
• Automatic downloading of the configuration directly to the
terminal makes safe engineering
• Direct documentation of the configuration
• Monitoring of all internal signals on-line facilitates
commissioning

ABB India
Utilities - Automation
84