1
REL 521
Philosophy
• Platform concept
ABB India
Utilities - Automation
2
REL 521
Dominant philosophy today
Monitoring
Remote Local Main Back-up Auxiliary
Control Control Protection Protection Functions
ABB India
Utilities - Automation
3
REL 521
Combination of Protection and Control
Integrated with Integrated with Integrated
remote back-up Co-ordinated local back-up duplicated
Block
input (optional)
ABB India
Utilities - Automation
4
REL 521
1 - Distance protection
2 - Three phase power swing unit
1 10 3 - Directional earth fault protection
4 - AC supervision circuits
5 - DC supervision circuits
6 - STUB protection
2 7 - Auxiliary relays
3 11 12 8 - Fault locator
4 5 13 14
C
ABB India
Utilities - Automation
5
REL 521
Numerical design
x
x x
x
Sine wave 4 samples 1 cycle 40 samples 1 cycle
Logic
Signal Measuring
conditioning algorithm Memory
ABB India
Utilities - Automation
6
REL 521
Continuous measurement and calculation of all loops
every millisecond = accurate and adaptive
ABB India
Utilities - Automation
7
REL 521
Benefits of self-supervision technique
MTTR 1 day
With continuous
self-supervision
Protection available
Protection not available
ABB India
Utilities - Automation
8
REL 521
Information Technology
SCS
The right information for the Substation Control System
On-line information
right person at the right time
SMS
Substation Monitoring System
On-demand information
ABB India
Utilities - Automation
9
REL 521
Line distance protection for HV/EHV
3/4 - 6U
ABB India
Utilities - Automation
10
REL 521
Case
E
• Built-in HMI unit with optical PC port
• selection of 1/2, 3/4 and 1/1 of 19” wide
Rear view • 6U =265.9 mm high
X22X20 X18 X16 X11
X13 1
2
3
4
5
• 205-245 mm deep
6
11
12
X23 X21 X19
X12
• Delivery specific configurations e.g. ports
X15 for serial communication or integrated
COMBITEST switch in adjacent case
ABB India
Utilities - Automation
11
REL 521
Common look
C C
E E
Height: 6U/265,9 mm
Depth: 205/245 mm
ABB India
Utilities - Automation
12
REL 521
Mounting
ABB India
Utilities - Automation
13
REL 521
Interface
• Indications
• Event logging and presentation
• Service values from analogue
Ready Start
Ready Start Trip
Trip input modules and protection
RET5xx
REx 521 Ver.2.0
Ver 2.0
E =Enter
E= Enter menu
menu functions, (i.e. differential
C =Reset
C= Reset LED
LED currents, etc.)
• Settings: reading, changing
C • Partial configuration
• Self-monitoring information
E
• Port with optic interface to RS
232 for local PC
ABB India
Utilities - Automation
14
REL 521
Hardware structure
~
~ ~
~ DSP8
Comm-
DSP9 CAN 1Mbit/s
uni-
DSP10
cation
DSP11 I/O I O AI HDLC
I/O
DSP12
TS SMS PC
4BI/5BO 8BI/10BO 16 BI 12 BO 6 AI Fiberoptic
•
SCS HMI x (1-9) x (1-9) x (1- 4) x (1- 6) Galvanic
ABB India
Utilities - Automation
15
REL 521
Hardware structure
Modules for AC input U+I
ABB Network Partner REx5xx
5 Currents
and
5 Voltages
Ready Start Trip
REx5xx Ver.2.0
E= Enter menu
C= Reset LED
C
E
U
5 Voltages
Rated value :
100/110/115/120 or
I 200/220/230/240 V
5 Currents
Rated value :
1 or 5 A
ABB India
Utilities - Automation
16
REL 521
Hardware structure
Modules for communication and signal processing
ABB Network Partner REX5XX
Signal Processing
module
C
E
Power Supply
module
Main processing
module
AD-converter
module
ABB India
Utilities - Automation
17
REL 521
Hardware structure
Modules for I/O
ABB Network Partner REx5XX DCM
serial remote
Ready Start
REx5xx Ver.2.0
E= Enter menu
C= Reset LED
Trip
MIM communication
C
E module
24 binary outputs
16 binary inputs
ABB India
Utilities - Automation
18
REL 521
Binary input module
ABB India
Utilities - Automation
19
REL 521
Binary input module
T = 5 ms
ABB India
Utilities - Automation
20
REL 521
Binary input module
>N
Input signal is suppressed
if the number of valid events
1s within 1s > N = 0 - 40 Hz
ABB India
Utilities - Automation
21
REL 521
ABB India
Utilities - Automation
22
REL 521
Close coil
+ Double Pole Command
-
outputs with supervision
Open coil
-
- Single outputs without
supervision
+
ABB India
Utilities - Automation
23
REL 521
ABB India
Utilities - Automation
24
REL 521
ABB India
Utilities - Automation
25
REL 521
Transformer module
ABB India
Utilities - Automation
26
REL 521
ABB India
Utilities - Automation
27
REL 521
Main processor module
• Memory:
• up to 8 Mb DRAM
• up to 8 Mb CodeFLASH
• 0,5 Mb DataFLASH
• 12 Digital Signal Processors on separate board
• Main Controller/CPU type Motorola 68360, 25
MHz
• 5 independent serial Links:
• CAN bus for I/O 1 Mbit/s
• Built in HMI
• Substation Monitoring via SPA
• Substation Control System via LON
ABB India
Utilities - Automation
28
REL 521
Power supply module
ABB India
Utilities - Automation
29
REL 521
Optical communication connectors
IEC 870-5-103
Glass or SPA
LON
Plastic
ABB India
Utilities - Automation
30
REL 521
Serial remote communication alternatives
ABB India
Utilities - Automation
31
REL 521
Terminal Functions
Platform related functions Basic functions
• Self supervision with internal event • 3 zones phase-phase protection
recording • 3 zones phase -earth protection
• Real time clock with input for external • Phase selection logic
time synchronisation
• Scheme communication logic
• Four groups of setting parameters
• Current reversal and WEI
• Local Human Machine Interface
• Local acceleration logic
• Configuration logic
• Instantaneous phase O/C protection
• Service value reading
• Time-delayed phase O/C protection
• Monitoring of AC measurement
• Instantaneous earth fault O/C protection
( non-directional )
• Time-delayed earth fault O/C protection
( non-directional )
• Three-pole tripping logic
• Event recorder
ABB India
Utilities - Automation
32
REL 521
Terminal Functions
ABB India
Utilities - Automation
33
REL 521
Terminal Functions
ABB India
Utilities - Automation
34
REL 521
Terminal Functions
Control Logic
• Command control (option) • Single or two-pole tripping
• Synchro-check and energising check • Pole discordance logic (option / contact
based)
• Synchro-check with phasing and
energising check (option) • Additional configurable logic
• Autorecloser logic,1 and/or 3 phase • Channel test communication logic
• Autoreclosing logic, 3 phase (option) • Binary signal transfer to remote end
• Binary signal interbay communication
ABB India
Utilities - Automation
35
REL 521
Terminal Functions
• Fault recorder
• Fibre optical modem
Metering
Hardware
• Pulse counter logic • Case size 3/4 or 1/2 x 19”
• 8 I/O, 3/4 x 19” or 3 I/O, 1/2 x 19”
HMI language
• English
ABB India
Utilities - Automation
36
REL 521
Distance protection function
ZM 3
Zone 1
ABB India
Utilities - Automation
37
REL 521
Phase preference logic
R R
S S
T T
ABB India
Utilities - Automation
38
REL 521
Software functions
I >
I t P,Q > U>, t U<, t
ABB India
Utilities - Automation
39
REL 521
Library of Functions
Future
Fault locator
Phase preference logic
Series compensation
Fuse failure
Time delayed o/c protection
Instantaneous o/c protection
Synchro- and dead-line-check
Breaker failure protection
Auto-reclosing
Line differential protection
Earth fault o/c protection
Distance protection
PROTECTION AND
CONTROL FUNCTIONS
ABB India
Utilities - Automation
40
REL 521
Monitoring library
Disturbance overview
Report 2 Report 3
Report 1
Pulse
counter 961201.222 Start L1
961201.333 Trip T3 111111
961203.555 CS L1 22222
961203.666 Block L1 d
33333
P,Q
ABB India
Utilities - Automation
41
REL 521
Communication alternatives
LON
– Commands
Station bus – Settings
LON SPA – Measured values & status information
REx REx – Interbay commands & status information
C
E C
E
– Events & disturbance reports
SPA
LON SPA
SPA
– Commands
REx
C
– Settings
E
SPA
– Measured values & status information
– Events & disturbance reports
MMI / RTU
Station bus
IEC 870-5-103
GW or
LON IEC 870-5-103
LON IEC 870-5-103 – Events & disturbance reports
– Measured values
REx REx
C
E C
E
– Function commands
SPA SPA
ABB India
Utilities - Automation
42
REL 521
Power swing detection and logic
ABB India
Utilities - Automation
43
REL 521
ABB India
Utilities - Automation
44
REL 521
Extension
Extension Autorecloser
Autorecloseror
orLoad
Load
scheme controlled overreach
controlled overreach
scheme
Underreach
Underreach Unblocking
Unblocking
Permissive
Permissive
Unblocking
Unblocking
Overreach
Overreach weak
weakinfeed
infeed
transient
transientblocking
blocking
Blocking
Blocking Overreach
Overreach
ABB India
Utilities - Automation
45
REL 521
CSL1
CSL2 CSL1
• Logic for phase segregated
permissive overreach transfer
L1 trip
CSL1
CSL2 CSL2
• Correct single phase trip at all
simultaneous faults
L2
ABB India
Utilities - Automation
46
REL 521
Distance protection - phase selection
X
• Independent phase selection
Zone 2
criteria, HV, EHV
• Independent setting of
Zone 1 characteristic for:
- reactive reach
- resistive reach
- ground return
R
ABB India
Utilities - Automation
47
REL 521
Extremely inverse
ABB India
Utilities - Automation
48
REL 521
Directional earth fault O/C protection
ABB India
Utilities - Automation
50
REL 521
ABB India
Utilities - Automation
51
REL 521
Broken conductor
IL
• Detects:
- broken line conductors
- open poles of circuit breakers
- broken connections in the
secondary circuits of CTs
- overload conditions during normal
< Z5XX operation
REL
• Function is programmable to trip and
alarm
ABB India
Utilities - Automation
52
REL 521
Current detector
ASD
Current Back-up trip
&
RMS-value (Busbar)
t t2
Start &
t1
Retrip of own
circuit breaker
ABB India
Utilities - Automation
53
REL 521
SSUP - Overload & STUB
ABB India
Utilities - Automation
54
REL 521
Overcurrent protection functions
ABB India
Utilities - Automation
55
REL 521
Voltage protection functions
ABB India
Utilities - Automation
56
REL 521
Synchronism and Energizing check
UBus
ABB India
Utilities - Automation
57
REL 521
Synchrocheck with voltage selection within bay
selection
BUSBAR 1
single breaker
REB551
U5
AI
U-BUS 1 • Voltage selection for 1 ½ circuit
SYNC
VS 1R U5
U-BUS 2
U4
UL
1R
3R
U4
UL
U-Line breaker arrangement
I-Line
BI/BO
B1OPEN
3I
B1CLOSED
B2OPEN
• Selection is made using one
I/O-board
B2CLOSED
U5FF
EXTERNAL FUSE FAILURE(MCB)
U4FF
ABB India
Utilities - Automation
58
REL 521
Auto reclosing (AR)
1 2
ABB India
Utilities - Automation
59
REL 521
Sequential auto-reclosing
Line volt
Fault CB1
REB 551
C
E
Line prot.
WFMASTER
CB1
WAIT
CB1 AR t1
CB2
REB 551
WFMASTER
C
E
CB2
WAIT
t1
CB2AR
t
ABB India
Utilities - Automation
60
REL 521
Single- / Two/ Three-phase reclosing programs
ABB India
Utilities - Automation
61
REL 521
Disturbance report for the last 10 disturbances
• Disturbance Overview
Event Disturbance
• Event Recorder
Recorder Recorder • Disturbance Recorder
• Fault Locator
• Trip Values
Disturbance
Overview • Common functionality:
- Date and time
- Number of stored disturbances
Fault Trip - Triggering conditions
Locator Values
ABB India
Utilities - Automation
62
REL 521
ABB India
Utilities - Automation
63
REL 521
Disturbance summary
Disturbance
DisturbanceReport
Report
Disturbance
Disturbance Disturbance
Disturbance Disturbance
Disturbance
No.
No.11 No.
No.22 No.
No.10
10
General
General Event
Event Disturbance
Disturbance
Indications
Indications Trip
TripValues
Values
Indications
Indications Recorder
Recorder Recorder
Recorder
ABB India
Utilities - Automation
64
REL 521
ABB India
Utilities - Automation
65
REL 521
ABB India
Utilities - Automation
67
REL 521
Disturbance
Overview
Fault Trip
Locator Values
ABB India
Utilities - Automation
68
REL 521
Setting parameters for the distance protection
jX
R1Z1
X1Z1(2,..,5) reach in reactive direction in
ohms
R1Z1(2,..,5) positive sequence
resistance of protected line section in
ohms
X1Z1 RFZ1(2,..,5) fault resistance for phase-
to-phase faults (arc resistance) in
ohms
RFNZ1(2,..,5) fault resistance for phase
to earth faults (arc and tower footing
R resistance) in ohms
RFZ1 RFNZ1
ABB India
Utilities - Automation
69
REL 521
Setting parameters for the distance protection
jX 1
RNZ1 RN = ⋅ ( R 0 − R1 )
3
1
XNZ1 XN = ⋅ ( X 0 − X 1 )
3
ABB India
Utilities - Automation
70
REL 521
Setting parameters - phase selectors
jX
1
RNZn = ⋅ ( R0 Zn − R1Zn)
3
RFNPHS R
ABB India
Utilities - Automation
71
REL 521
Setting parameters - phase selectors
jX
X1PHS
Phase selectors for ph-ph faults
X 1 PHS ≥ X 1Zn
RFPHS ≥ 2 ⋅ R1Zn + RFZn
line
70o
R
RFPHS
ABB India
Utilities - Automation
72
REL 521
Setting parameters - phase selectors
2
A≡ ⋅ RFPHS
A 3
110o
2
R2.sqr(3)
R B≡ ⋅ XFPHS
3
ABB India
Utilities - Automation
73
REL 521
Setting - Overcurrent earth-fault protection (O/C E/F)
ABB India
Utilities - Automation
74
REL 521
Setting - Overcurrent earth-fault protection
ABB India
Utilities - Automation
75
REL 521
Setting - Non directional O/C E/F protection
IX
ABB India
Utilities - Automation
78
REL 521
Directional O/C E/F protection: blocking schemes
ABB India
Utilities - Automation
79
REL 521
Fault locator: settings
Line and source parame-ters are
settable under the line reference
data
ABB India
Utilities - Automation
80
REL 521
ABB India
Utilities - Automation
81
REL 521
CAP 531Configuration tool for REx 5xx
ABB India
Utilities - Automation
82
REL 521
BI
1.1 Z_BLOCK Z_TRZ1
BO • Terminal function block library for
2.1
1.2 Z_CR
Z_CRG Z_TRZ2
REx 5xx
1.3 Z_BC OR
1.4
Z<
Z_T2
• Both hardware and software
START functions
AR_CB_READY
1.8
AR_CLOSE_CB 2.2 • Each terminal function is an
AR
AR_P3PH
independent block in graphic form
1.9 TRIP_EXT_3PH
• Functions are independently
TRIP_CB_A
1.1
tested and documented
TRIP • Consistency check between CAP
configuration file and terminal
function set
ABB India
Utilities - Automation
83
REL 521
ABB India
Utilities - Automation
84