1. Introduction
For a long time, i n s u l a t i o n r e s i s t a n c e and
absorbtion r a t i o nave been used as one o f b a s i c I
metnods t o i n s p e c t t h e s i t u a t i o n o f transformer
i n s u l a t i o n i n China. Usually it was considered
t n a t absorbtion r a t i o of a transformer dried was
n o t l e s s than 1.3. I n r e c e n t years it was found
i n p r a c t i c e that some new b i g power transformers
had high i n s u l a t i o n r e s i s t a n c e but low absorbtion
r a t i o ( e v e n l e s s than 1 . 5 ) . Did t h e s e transformers Fig.1 d double-layered d i e l e c t r i c a3del
and equivalent c i r c u i t
absoroed moisture or n o t ?
I n e a s t of China, s t a t i s t i c r e s u l t s from 275
p i e c e s o f transformers above llOKV i n operation In o r d e r t o check whetner t h e simple model
showed t h a t absorbtion r a t i o of 7.0% of t h e m w a s could d e s c r i b e t n e absorbtion proce8s o f a t r a n s -
l e s s than 1.3. I n nortn-west of C h m a , l e s s than former, d a t a measured w i t h a meggemeter i.e.
1 .5 absorbtion r a t i o i n s t a t i s t i c r e s u l t s of 905 p r a c t i c a l absorbtion process o f a transformer a r e
times from 72 pieces o f transformers accounted f i t t e d t o curves by computer according t o absorb-
for 1j.S. But a l l o f t h e s e transformers were t i o n c u r r e n t equation o f a double-layered d i e l e c -
normally i n -service. t r i c model. T y p i c a l d a t a o f 7 pieces o f t r a n s -
The problems which appeared i n measuring insu- formers a r e showed i n Table 1. I n each d a t a group,
l a t i o n r e s i s t a n c e have been analyzed a n d d i f f e r e - r e l e a t i v e e r r o r s between measured p o i n t s and
nces between p o l a r i z a t i o n index and absorbtion p o i n t s o f curve f i t are g e n e r a l l y less tnan 5%,
r a t i o have been compared i n t h i s paper. p o i n t s of about 1% r e l e a t i v e e r r o r s are only one
or two(Here include e r r o r s from measuring). Alth-
2. Model study o f absorbtion phenomena o f ough i n s u l a t i o n c o n s t r u c t i o n i n s i d e a transformer
transformer i n s u l a t i o n is much more complicated oil-paper i n s u l a t i o n
Because i n s u l a t i o n c o n s t r u c t i o n i n s i d e a trans- system tnan a double-layered d i e l e c t r i c model, a
former is very complicated, it is almost impossible dof!ble-layered d i e l e c t r i c model can be approxima-
t o c a l c u l a t e t h e o r i c a l l y absorbtion c u r r e n t accor- t e l y w e d f o r a n a l y s i n g i t s absorbtion Phenomena
d i n g t o its i n s u l a t i o n c o n s t r u c t i o n . When i n s u l a - i n accordance w i t h e x t r a characteristics of i t s
t i o n r e a i s t a n c e o f a apparatus is measured, t r a d i - absorbtion c u r r e n t .
-463-
cmse7-4/ee/oooo- 463 $01 .oo g, 1988 IKEE
Table 1. Typical d a t a of s e v e r a l t r a n s f o m r s
temperature
560 1 220
('c)
31
31
/
.2000
1200
1200
1300
+
1700 2250
2700 5050
2500 2600
3400
2900
5600
4300
3800
5000
6000 ,6500
4650
/
/
4900
4100
3300
120 220 18 1zM- 5250 000 .6500 7000 1250 8ooo
120 220 34 1850 3300 3600 3800 4000 4150 4250
1000 1100 I1160 ~ 1190 1121011220 1225 1227 1228
measured d a t a and.
results calculated
I I
I 7000 I 7300
7 1128 1128
Note: The i n s u l a t i o n r'8rsistances were measured by JKV Ueggexmeter.
-464-
P o l a r i z a t i o n index is r a t i o value o f l O m i n i t can be known that l o w absorbtion r a t i o is c a w -
i n s u l a t i P n r e s i s t a n c e t o lmin i n s u l a t i o n resis- ed by long absorbtion process. According t o P I
c r i t e r i o n it i s sure that i n s u l a t i o n is good.
3 ) I n s u l a t i o n o f transformer No.7 is moist, so
The p r i n c i p l e o f p o l a r i z a t i o n index i s same as K and P I are low.
absorbtion r a t i o , but its time measured i n s u l a t i o n
r e s i s t a n c e i s longer. When absorbtion process o f 5. Model test of oil-paper i n s u l a t i o n
a transformer is long, absorbtion r a t i o c a n ' t The p r a c t i c a l experience showed t h a t q u a l i t y '
of paper
Fig.2 Absorbtion curves o f transformers R-t
-465-
in t h e beginning. It w a s d i f f i c u l t that value of r e s i s t a n c e out low absorbtion r a t i o appaared.
R15,' w a s read acc.Wately. T h e r e f o r e , e r r o r s f o r 5 ) Accuracy of i n s u l a t i o n r e s i s t a n c e and absoro-
measuring absorbtion r a t i o WPB big. P i n a l l y t h e t i o n r a t i o measured with a n e g g e r m e t e r is low,
value which compared with s t a n d a r d w a s n o t real According t o e r r o r s a n a l y s i s it may be explained
absorbtion r a t i o of a t r a n s f o r m e r , it w a s a mea- t n a t absorbtion r a t i o of some t r a n s f o n u e r s
suring result. (?*2%) is l e s s t h a n 1.3, but they are s a f e l y
Generally speaking, e r r o m Of measurements i n service.
obey n o p a l d i s t r i b u t i o n . A @up of absorbtion
r a t i o r e s u i t s being t e s t e d d u r i n g dryingprocees of a Refehnces
transformer is analysed f o r t h e i r e r r o r s . It is ( 1 ) Chang a," C h a r a c t e r i s t i c s of i n s u l a t i o n
suyposed that absorbtion r a t i o i8 approximately r e s i s t a n c e of transformers" proceeding o f
c o n s t a n t d u r i n g the period of end of drying. Dif- E l e c t r i c power Research I n s t i t u t e , 1985
f e r e n c e s o f a b s o r b t i o n r a t i o a r e only caused by ( i n Chinese)
measuring. Max. variance(d) and Min. v a r i a n c e ( a ) ( 2 ) Pong Ciu X i a n , "Insulation resistance of
c a l c u l a t e d by s t a t i s t i c r e s u l t s are s e p a r a t e l y transformer winding t o e a r t h , " Transformer,
0.155 and 0.055. I f average o f v a r i a n c e i s taken, ~ 0 . 6 , 1983 ( i n Chinese)
i.e. ,pS.1, suppose K=1.4, measuring r e s u l t s ( 3 ) ttMoisture e q u i l i b r i u m in p a p e r - o i l i n s u l a t i o n
of absorbtion r a t i o obey normal d i s t r i b u t i o n of system," proceeding of t h e 1 6 t h e l e c t r i c a l -
average 1.4 and variance 0.1, i.e. Kd(1.4,O.l). e l e c t r o n i c s i n s u l a t i o n conf. 1983
Because of a c c i d e n t errors p o s s i b i l i t y o f l e s s ( 4 ) " I n s u l a t i o n c h a r a c t e r i s t i c s o f oil-immersed
th- 1.3 absorbtion r a t i o i n measuring r e s u l t s is: transformers ,It Report o f Sheng Y a n t r a n s -
P (K < 1 -5)' @ ( w ) = l 5 fortner r e s e a r c h i n s t i t u t e , No.7, 1985
(in Chinese)
From t n i s d a t a supposed it can be known t h a t
a b s o r b t i o n r a t i o of some transformers i n p r a c t i c e
w i l l be l e s s than 1.3 because o f t e s t d i s p e r s i t y ,
but they are normal completely.
7. Conclusions
1 ) Although o i l - p a p e r i n s u l a t i o n c o n s t r u c t i o n of
a transformer i s complicated, it has been proved
t h a t a double-layered d i e l e c t r i c model could app-
roximately d e s c r i b e and e x p l a i n its absorbtion
phenomena a f t e r d a t a measured with a Meggermetex
was f i t t e d t o curves.
-466-