Standard PLC
Built-in I/O Specifications - Inputs
C0-01DD1-D Inputs per Module 8 (Sink/Source)
+
X1-2: > 19VDC
ON Voltage Level
+
X3-8: > 19VDC
PWR
X1-2: < 4VDC
RUN OFF Voltage Level X3-8: < 7VDC
ERR
X1-2: 4.5 mA
+
Minimum ON Current X3-8: 3.5 mA
+
PORT1
X1-2: 0.1 mA
TX1 Maximum OFF Current X3-8: 0.5 mA
RX1
X1-2: Typ 5µs Max 20µs
OFF to ON Response X3-8: Typ 2ms Max 10ms
TX2 L
X1-2: Typ 5µs Max 20µs
RX2 L ON to OFF Response X3-8: Typ 3ms Max 10ms
PORT2
+
L 5 - 27VDC
L Status Indicators Logic Side (8 points, green LED)
RS-485
PORT3 Commons 2 (4 points/common) Isolated
TX3
L
+
L
Built-in I/O Specifications - Outputs
+
RX3
5 - 27VDC 24VDC
To X6-X8
Current Consumption at 24VDC 140mA
commons
Terminal Block Replacement Part No. C0-16TB
Equivalent Output Circuit Weight 5.0 oz (140g)
Internal Module Circuitry
ZIPLink Pre-Wired PLC
24 VDC C0-01DD1-D Temperature Derating Chart
+ +V
Optical Isolator Connection Cables and Modules
OUTPUT
+
L
Y1 8
High response
Inputs
5 - 27 VDC
* circuit
6
Outputs ZL-RTB20 20-pin
Points
4 feed-through
Optical Isolator 2
* connector module
OUTPUT
+ Y2-Y4
L
5 - 27 VDC * 0
C3 COM 0 10 20 30 40 50 55 °C
32 50 68 85 104 122 131 °F
Surrounding Temperature (°C/°F)
Optical Isolator * Use every other input/output.
OUTPUT
+ Y5-Y6
L
5 - 27 VDC
* 20-pin connector cable
C4 COM
ZL-C0-CBL20 (0.5 m length)
Note: C3 & C4 are not internally connected.
ZL-C0-CBL20-1 (1.0 m length)
ZL-C0-CBL20-2 (2.0 m length)
* Zener Diode Power Dissipation: 200 mW