Session on
Control Wiring of
North Delhi Power Limited
(A TATA Power & Delhi Govt JV)
Circuit Breakers
By:
SHYAM SINGH
References: SITE Experiences, OEM Drawings
•Closing Circuit
•Anti-Pumping Ckt
North Delhi Power Limited
•Tripping Circuit
(A TATA Power & Delhi Govt JV)
BREAKER
HEATER
CONTROL SWITCH
CLOSING/TRIP
COIL LOCAL REMOTE
TOGGLE SWITCH SWITCH
FUSE
SOCKET
LINK
NC CONTACT MOTOR
NO CONTACT
CAPACITOR
North Delhi Power Limited
TERMINAL OF
APPARATUS
(A TATA Power & Delhi Govt JV)
RESISTOR
TERMINAL BLOCK IN
CONTROL BOX
DRAWOUT
POINT
TERMINAL BLOCK
FOR CUSTOMER
CONNECTIONS
BUTTON
METER
(A TATA Power & Delhi Govt JV)
HOOTER
LIMIT
SWITCH
CURRENT
TRANSFORMER
SWITCH WITH
THERMOSTAT SELECTOR
SWITCH
L/R Switch CB
Main DC Link
-50V DC Main Bus
Y1-CLOSING COIL
K2-CONTACTOR FOR
GAS DESITY
MONITOR
North Delhi Power Limited
K1-ANTIPUMPING
RELAY
C S1-AUX. SWITCH CB
B D
A
NEED:-
Suppose if closing switch of CB will stuck in close position and then
CB trip on some fault, CB aux. contact 52b make the closing ckt
North Delhi Power Limited
(A TATA Power & Delhi Govt JV)
through & after tripping operation CB will again close. But as the fault
persist trip command from relay again trip the CB. This closed loop
operation goes on & damage the CB.
So, there is certainly a need to block the close ckt path by introducing
L/R Switch CB
North Delhi Power Limited
(A TATA Power & Delhi Govt JV)
Tripping Coil, CB
Control Link CP
Main DC Link
-50V DC Main Bus
K2-CONTACTOR
FOR GAS DESITY
MONITOR
North Delhi Power Limited
S1-AUX. SWITCH CB
(A TATA Power & Delhi Govt JV)
Y2-Trip Coil
F3- Density Monitor
Switch