Professional Documents
Culture Documents
DistributionSystemAnalysis PartI V1 PDF
DistributionSystemAnalysis PartI V1 PDF
Analysis of Distribution
Systems with Distributed
Resources
54.4 A
FEEDER A Shield FEEDER B
Feeder A Feeder B
543.7 A 380.0 A A B C A B C
A A
525.2 A 364.6 A
B B
509.6 A 348.6 A
C C
IAVG=517 A IAVG=358 A
Unbalanced model
A key capability
5000 – 10000 bus systems are routine today
Smart Grid requires solution of multiple
feeders simultaneously
Goal:
100,000 to 800,000 nodes
Parallel computing could enable this
Requires new algorithms
Contents
Models for Load Flow calculations
Power delivery components
Power conversion components
Load Flow Techniques
Deterministic Load Flow methods
Probabilistic Load Flow methods
OpenDSS and Case Studies
EMTP load flow and Case Studies
Studies and Models
Distribution systems are three-phase and radial
Single-phase models must be also considered
Distribution systems can run at either MV or LV
Generation units can be stochastic (intermittent and
non-dispatchable) or deterministic (non-intermittent
and dispatchable)
Generating machine models must be included in
unbalanced three-phase load flow or when load flow
calculations are used as initialization in time-domain
tools (i.e., EMT-type tools)
If the machine is connected via a static converter, the
converter and its control units can be also included in
the model
Studies and Models
Conventional synchronous machine-based generating
unit is represented as a PV node
if voltage control is not allowed, then the node becomes PQ
internal impedance matrix must be included in unbalanced
three-phase calculations
constraints about power ramps may be considered
Load representation
from the simplest voltage-independent PQ node to the most
sophisticated stochastic time-varying dynamic voltage-
dependent load curve
Without energy storage devices, history terms are not
usually required, unless constraints about power
ramps are considered
The states of energy storage devices at one time step
affect the states at the next step, and depend on the
states at the previous step
Models for LF Calculations
Models are by default adequate for unbalanced load
flow calculations (i.e., three-phase models)
Important aspect: the study zone
In general, a single feeder plus a constant voltage source
connected at its root node
When load flow calculations are used for initialization in
further studies (e.g., electromagnetic transients), the
substation or the distribution transformer plus the network
equivalent of the supply side may be required
Components may be classified into two groups:
Power delivery components: they transport energy
They can be represented by either their admittance or their
impedance matrices, depending on the solution technique
used for load flow calculations
Power conversion components: they convert electrical
energy to other form of energy, or vice-versa
They are represented as a single multiphase terminal block
Models for LF Calculations
Lines and Cables
Representation: Multiphase pi model with parameters
calculated at power frequency and considering the
effect of earth return currents
This model may be divided into the series impedance matrix
and the parallel line charging capacitances
Two-terminal model of a LV four-wire overhead line section
will have four nodes plus ground
An underground line section consisting of three concentric
cables will have six nodes plus ground; in some cases Kron
reduction is applied and a three-phase model is derived
Models for one-phase lines/cables can be required
Approximate models of overhead distribution lines
neglect the shunt capacitances, or are derived from
the positive and zero sequence impedances
Models for LF Calculations
Transformers
Three-phase transformer models, considering any
winding connection (even unusual connections)
Approaches for modeling windings compute either the
impedance matrix or the admittance matrix
The core may be ignored or treated as a load that can
be connected at either side of the transformer
Primary
Secondary
Winding
model The core can be modeled as
the usual linear parallel R-X
model or by empirically-deter-
Core mined nonlinear functions
model
Models for LF Calculations
Voltage Regulators
A voltage regulator consists of an autotransformer
and a tap-changing mechanism whose position is
determined by a control circuit
Model implementation is complex; it has to include the
control parameters of the compensator circuit (voltage
level, bandwith, R-X settings, time delay)
Most load flow solutions use a simplified model in
which the voltage regulator is represented by an
impedance in series with an ideal transformer having
taps in the secondary
The tap setting is determined depends on the solution
method. (e.g., backward/forward sweep method,
Newton-like solution methods)
Models for LF Calculations
Capacitors
Usually installed to control voltage or reduce losses
A three-phase capacitor bank may be delta- or wye-
connected (grounded or ungrounded)
In load flow equations, a capacitor bank can be
represented as a PV node or as a constant impedance/
admittance
Models for LF Calculations
Generators
A synchronous generator has been traditionally
modeled as a fixed voltage source (when connected to
the slack node), as a PV source (whose terminal
voltage is known), or as a PQ node (whose terminal
voltage is unknown)
All these models neglect the internal impedances
The internal impedances of a rotating machine unit
can have some effect on system unbalance due to the
rotor turn and the coupling between machine winding
impedances
Internal impedances must be included when
calculating unbalanced three-phase power flows
A synchronous generator can be represented by its
Norton or its Thevenin equivalent (see next slide)
Models for LF Calculations
Generators
Models developed for wind power generators
represent the machine as a balanced PQ node
or calculate P and Q from the wind speed and the power
input curve taking into account the type of wind turbine (Q
can be set to zero)
In case of unbalance, machine equations can be
included in the load flow equations
Single-phase DG models: constant power factor
model, constant voltage model, or variable reactive
power model Positive sequence
voltage source
230 kV 80
Load (kW)
60
40
4.8 kV 799 20
724
0
722 0 6 12 18 24
714
(kWh/m²/d)
5
4
3
706
2
729 744 727 100
703 718
1
0
725
Power (kW)
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
80
728
Photovoltaic 730 60
100
generation
80
40
Power (kW)
20 736
733
0
1 2 3 4 5 6 7
Day
710 734
711
735
737 738 741
740
12 70
60
Wind Speed (m/s)
9
50
Wind
Power (kW)
40
6 generation
30
3 20
10
0 0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec 1 2 3 4 5 6 7
Day
Case Studies
0.8
0.6
0.4
0.2
0.0
0 6 12 18 24
Hour
Load profiles
Monthly load
Case Study 1
60
Constant P-Q
50
Power (kVA)
40
0
500 520 540 560 580 600
Hour
700
Constant P-Q
600
500
Power (kVA)
400
Power flow from the
300 substation terminal
200
Quadratic P-Q
(kVA) - Node 799 –
100 Phase A
0
1080 1085 1090 1095 1100
Hour
Case Study 2
Two renewable generators are connected to the
system
A 400 kW wind power generator is attached to Node
740
A 200 kW photovoltaic generator is attached to Node
728
In both cases, the power factor of the injected power
is unity
HOMER capabilities were initially used to obtain the
wind speed and the solar radiation
These profiles were later used to derive the shapes
of the power injected by both generators
The two load models considered in the previous
study were applied again
Case Study 2
12
Wind Speed (m/s)
6
Wind resource –
3
Wind speed (m/s)
0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
7
Daily Radiation (kWh/m²/d)
Solar resource –
5
3
Daily radiation
2 (kWh/m2/d)
1
0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Case Study 2
150
Wind
120
Photovoltaic
Power (kW)
90
Distributed
60
generation (kVA)
30
– Phase A
0
1800 1820 1840 1860 1880 1900
Hour
600
Constant P-Q
500
Power flow from
Power (kVA)
400
300
the substation
200
terminal (kVA) -
100
Quadratic P-Q Node 799 –
0 Phase A
1080 1085 1090 1095 1100
Hour
Case Study 2
Differences are again about 10%
The values of the energy supplied from
the substation are now 7336 and 6792
MWh (i.e., embedded generators take
10% of the required energy)
Differences between models are again
of about 7%
The connection of generators raises the
minimum voltages to 0.922 and 0.930 pu
Case Study 3
Battery model implemented in HOMER
Considered factors: nominal capacity, state of
charge of batteries, rated power of the rectifier,
power available from the grid
12:00 am
No 1813
February
Nightly
6:00 am
Yes 1697
Low (Nodes March
718, 728, 740) 12:00 am
No 2131
February
Daily
11:00 am
Yes 1867
August
11:00 pm
No 1673
June
Nightly
11:00 pm
Medium (Nodes Yes 1673
June
712, 718, 728,
730, 733, 740) 12:00 am
No 2178
February
Daily
12:00 am
Yes 1944
January
Case Study 3
Table shows the peak value of the active power
supplied from the substation terminals
with low electric vehicle load, the peak power of the
generators is respectively 400 kW (Node 740) and
200 kW (Node 728)
with medium electric vehicle load, the peak power of
the generators is respectively 500 kW (Node 740) and
400 kW (Node 728)
Conclusion: night loading is the best choice to
release substation burden
Table II includes information about the time at which
the substation load is higher for each case; this can
be useful for analyzing the impact of an increasing
photovoltaic generation
Case Study 3
Future scenarios could be different
a very high electric vehicle load during night hours could make
the system unfeasible since many of its sections would not
withstand the load, unless nightly embedded generation was
available (e.g., wind generation) or a high percentage of this
load was shifted to daily hours
a significant penetration of photovoltaic generation could also
motivate this load shift
If energy storage is installed, then part of this solar generation
could be used during night hours, see next study
Vehicle-to-grid (V2G): Some electric vehicles could partially
discharge stored energy to the grid and act as a distributed
source of storage
The electric vehicle load could be mostly connected to the low
voltage grid, and its impact to higher voltage levels could be
lower than assumed here
Exploring the feasibility of all these scenarios will require
simulation capabilities like those applied in this study
More complicated scenarios can arise if price signals are
included in the study
Case Study 4
Peak rated power of PV generator increased to 300
kW
Energy storage device is connected to its terminal
Storage specification:
rated energy storage capacity = 2000 kWh
power output rating = 300 kW
minimum storage capacity hold in reserve is 20%
Rated power of the interconnection transformer
remains the same (i.e., 200 kVA)
The storage device will be controlled to keep the
regulating transformer loading below 100 kVA
As the photovoltaic power decreases below 100 kW,
storage device starts discharging until the energy
level reaches minimum capacity or cycle starts again
Ideal storage device (i.e., round trip efficiency is
100%)
Case Study 4
100
Generator
80
Per phase power
Power (kVA)
60
Transformer generation and power
40 flow through the
20 interconnection
0
transformer
0 20 40 60 80 100
Hour
100 1500
Photovoltaic
80 Generation Stored 1200
Energy
Energy (kVWh)
Power (kVA)
60 900
Per phase power
40 600 generation and stored
20 300 energy
0 0
0 20 40 60 80 100
Hour
Case Study 4
Simulation results
The power flowing through the transformer does not
increase above 100 kW (figures show per phase
results, power factor of generation is unity)
The charge of the energy storage device begins as
soon as the power generated by the photovoltaic
plant increases above 100 kW, and starts discharging
as soon as it decreases below 100 kW
When the generation does not reach the minimum
value during daytime, the stored energy remains at
its minimum level
Case Study 4
Energy storage can be installed to solve key issues in power
systems (e.g., load leveling and shifting, VAR support and
voltage regulation, relief of overloaded lines, release of system
capacity)
The storage device has been used to level the power generation
curve and prevent transformer overloading
The intermittent power injected by the solar array can become
non-intermittent, and a flat power flow curve across the
transformer can be obtained, although a large size storage
device will be usually required
Energy storage can reduce the need for conventional
generation reserve when renewables are unavailable
Other scenarios can be considered (e.g., storing the excess
available energy that has not been consumed can contribute to
an increase of the overall efficiency of the system)
Case Study 5
Load and generation values are generally estimated
or calculated with some uncertainties
Load uncertainty is not usually very high and it can
be generally modeled as a normal distribution
Wind variability is very high, and cannot be
represented by a normal distribution
Wind power generation interdependence is important
due to the fact that generations from wind turbines
are strongly correlated among adjacent wind farms
Probabilistic calculation may be considered
Probabilistic load flow can be solved by using either
a numerical or an analytical method
The numerical option uses a Monte Carlo method, a
capability implemented in OpenDSS and selected in
this work
Case Study 5
Table shows the probability density functions
assumed for loads and generations, as well as the
parameters selected for each load and each
generator
A Gaussian distribution with a mean and a standard
deviation of 50% and 5% of the peak load has been
assumed for all node loads and for the PV generation
A Weibull distribution is generally assumed for the
wind speed
This distribution is further used to derive the power
generation from the power curve of the turbine,
taking into account air density ratio
The mean and the standard deviation of the wind
power generation are also 50 and 5% of the rated
peak power
Case Study 5
Probability Density
Node Parameters
Function
Mean = 50% of the peak load
Loads Gaussian/Normal Standard deviation = 5% of
the peak load (see Table I)
Mean = 200 kW
Wind
Weibull Standard deviation = 5% of
generation
the mean power generation
Mean = 100 kW
Photovoltaic
Gaussian/Normal Standard deviation = 5% of
generation
the mean power generation
Case Study 5
40
30
Frequency
20
Per phase load
variation at Node 728
10
1000 samples
0
20 25 30 35 40 45
Power (kVA)
40
30
Frequency
20
Per phase wind
power variation
10
1000 samples
0
40 45 50 55 60 65 70 75 80 85
Power (kW)
Case Study 5
Simulation results derived from 1000 and 5000
samples with and without distributed generation
As expected, the results after increasing the number
of samples are closer to the theoretical distribution
However, the mean values of the power from the
substation are not significantly improved
For instance, the mean power supplied from the
substation per phase without distributed generation
is respectively 406 and 407 kVA after 1000 samples
and 5000 samples, being the standard deviations
10.6 and 9.8 kVA, respectively
When generators are connected, the mean value of
the substation power decreases to 314 and 315 kVA
after simulating respectively 1000 and 5000 samples,
being standard deviations 12.2 and 10.6 kVA
Case Study 5
Per phase power flow at substation terminal
1000 samples
50
40
Frequency
30
Without
20
10
distributed
0
generation
370 380 390 400 410 420 430 440 450
Power (kVA)
50
40
Frequency
30
With
20
distributed
10
0
generation
270 280 290 300 310 320 330 340 350
Power (kVA)
EMTP Equations for Steady-sate
Solution
Nodal Analysis
It is based on Kirchhoff’s current law; the admittance matrix is
used for computing the sum of currents entering each node
Yn vn in
vn is the vector of node voltages and the members of in hold the
sum of currents entering each node.
The network has a ground node at zero voltage.
The network may contain voltage sources (that is, known node
voltages), so the equation must be partitioned
T
Yn vn in Ys vs vn vn vs
where Yn is the coefficient matrix of unknown node voltages vn ,
in holds the sum of currents entering nodes with unknown
voltage, Ys Yn and relates to known voltages v s .
EMTP Equations for Steady-sate
Solution
Nodal Analysis
Nodal equations have several limitations.
They are restricted to modeling devices with the admittance
matrix representation of and ideal voltage sources connected to
ground.
It is not possible to directly model branch relations such as ideal
transformer units or ideal sources without a ground node.
Ideal transformer units are used as primitive devices for building
three-phase transformer models.
It is not possible to model ideal switches in using a fixed rank
matrix.
Devices with voltage and current relations cannot be directly
represented .
These limitations can be eliminated using modified-augmented-
nodal analysis (MANA).
EMTP Equations for Steady-sate
Solution
Augmented Nodal Analysis (MANA)
Nodal equations are augmented to include generic device
equations
AN xN = bN Yn AN
xn contains both unknown voltage and current quantities
bn contains known current and voltage quantities
The matrix AN is not necessarily symmetric.
These equations can be also written explicitly as
Yn Ac vn in T T
1 xN = vn ix bN in vx
Ar Ad ix vx
Matrices Ar, Ac, and Ad (augmented portion, row, column and
diagonal coefficients) are used to enter model equations which
are not or cannot be included in Yn.
ix is the vector of unknown currents in device models, vx is the
vector of known voltages.
EMTP Equations for Steady-sate
Solution
Augmented Nodal Analysis (MANA)
The MANA formulation is generic and can easily accommodate
the juxtaposition of arbitrary component models in arbitrary
network topologies with any number of wires and nodes.
It is not limited to the usage of the unknown variables presented
above and can be augmented to use different types of unknown
and known variables.
Steady-State Solution
The steady-state version is based on complex numbers, and the
equations are simply rewritten using capital letters to represent
complex numbers (phasors).
If a network contains sources at different frequencies, the
equations can be solved at each frequency and assuming that
the network is linear (linear models are used for all devices).
The solutions of xN can be combined to derive the harmonic
steady-state solution in the form of a Fourier series.
EMTP Equations for Steady-sate
Solution
State-Space Analysis
Some EMTP-like tools are based on the following equations
x Ax Bu
y Cx Du
x is the vector of state variables, u is the vector of inputs and
y is the vector of outputs.
Matrices A, B, C and D are the state matrices.
These matrices can be calculated for given ideal switch
positions and piecewise linear device segments.
Each topological change requires updating the state
matrices.
More generic version of the state-space equations
y C x D u D1 u
EMTP Equations for Steady-sate
Solution
State-Space Analysis
To obtain steady-state conditions the equations can
be transformed via the Laplace operator
1
X sI A BU
s j
1
Y C sI A B D s D1 U
Tilde-upper-case vectors are used to denote phasors
and I is the identity matrix.
EMTP Equations for Steady-sate
Solution
Hybrid Analysis
A generic method for formulating network equations.
It can be used to derive other formulations and to relate and
combine different formulations methods for eliminating
numerical limitations.
Equations characterizing an N–port
Iˆ H H Vˆ H H ˆ
V
v vv vi v va vb a
ˆ
V i
Hiv Hii Iˆ i Hia Hib Iˆ b
Iˆ
i
b
EMTP Equations for Steady-sate
Solution
Hybrid Analysis
This equation is identical to the compensation
method with
T
Zth = Hii ˆ ˆ
Vth H ia H ib Va I b
The compensation method can only use current ports
for representing nonlinear devices, may not be
conformal to network’s topological proper-tree and
may become ill-conditioned.
Hybrid analysis is more generic that the
compensation method and can avoid ill-conditioning
problems by remaining conformal to the topological
proper-tree through the usage of a combination of
nonlinear voltage and current ports.
EMTP Equations for Steady-sate
Solution
Hybrid Analysis
Automatic formulation from MANA: Hybrid analysis equations
can be automatically formulated from MANA equations.
If is augmented to extract and include nonlinear port currents I
and V voltages, then is modified as follows
Yn Ac An
xN bN
Ar Ad 0 =
I V
ATn 0 0
An is the adjacency matrix of ports.
Gaussian elimination is applied at this stage in to extract the
network relations between I , V and independent variables.
The extracted equations are written symbolically as
PI MV SbN
EMTP Equations for Steady-sate
Solution
Hybrid Analysis
Generation of state-space equations: If nonlinear and linear
components are separated in the hybrid formulation, then
I vx H vx vx H vxi x H v x vn H v x in Vvx H v xa H v xb
Vi x H ix vx H ixix H i x vn H i x in I ix H i xa H i xb Va
I vn H vn v x H vn i x H vn vn H vn i n Vvn H vn a H vn b Ib
Vin H in v x H in i x H i n vn H in in I in H in a H inb
The hatted notation is dropped to simplify the presentation.
This formulation allows to separate nonlinear components from
linear components.
n stands for generic nonlinear or nodal in the particular case, x
stands for state variables, v is for voltage ports, i is for current
ports, a indicates independent voltage sources and b indicates
independent current sources. generic nonlinear.
EMTP Equations for Steady-sate
Solution
State-Space Nodal (SSN) method
This method combines state-space groups with nodal
(MANA) equations.
State-space equations are redefined as follows
uit
xt ˆ x Bˆ u
A Bˆ ki Bˆ kn
t
t k t k t
unt t
yit t
Ck i Dk ii Dk in uit t
xt t
y nt t
Ck n Dk ni Dk nn unt t
y nt ˆ x
Ckn A ˆ u
B ˆ u
B Dkni uit ˆ
Ckn B Dknn unt
t k t k t ki it t t kn t
i Vn i khist v nV
Wkn
v In v khist i nI
t t t t
These equations are real, since real and imaginary parts must be
represented separately for load-flow constraints.
ALF
N is constructed from the original complex version of AN by
separating real and imaginary parts of each element
AI is a connectivity matrix for accounting for load-flow devices
LLA and Ld provide load-flow device constraint equations.
The vector function fLF must be minimized (zero) for finding the
load-flow solution
Multiphase Load-Flow Solution and
Initialization in EMTP-like Tools
The solution of
fLF (x) = 0
can be found using the Newton method
Vk 2 Vm 2 g Vk1 g Vm1 f x( j ) 2
This means that the existing submatrices Ar and Ac are not affected and
already constitute the Jacobian terms allowing to account for all single-
phase and three-phase transformer configurations.
When the tap positions are not defined, it is also possible to represent the
transformation ratio g in (2) as a variable and introduce additional Jacobian
terms in (3).
All submatrices used for the construction of are directly reused in (1).
Multiphase Load-Flow Solution and
Initialization in EMTP-like Tools
Initialization from Load-Flow Equations
It is performed by reverting (3) to its linearized version (1).
All loads are replaced by equivalent impedances calculated
at nominal voltages and all generators are replaced by ideal
sources behind their impedances.
This approach yields sufficiently good initial conditions for
the fast convergence of (3).
Initialization from Steady-State Solution
Upon convergence of (3), all steady-state phasors become
available.
The synchronous machine phasors are used to calculate
internal state variables.
The asynchronous machine requires the calculation of slip
for a given mechanical power or torque.
Multiphase Load-Flow Solution and
Initialization in EMTP-like Tools
Initialization from Steady-State Solution
The steady-state module starts with the load-flow solution
and replaces all devices by lumped equivalents to proceed
with a phasor solution.
This is achieved with the complex version of (1).
The resulting solution is the same as with the load-flow
module, except that now the device models have access to
internal phasors for proceeding with initialization.
Steady-state solution phasors are used for initializing all
state-variables at the time-point .
The solution at t = 0 is only from the steady-state and all
history terms for all devices are initialized for the first
solution time-point.
Multiphase Load-Flow Solution and
Initialization in EMTP-like Tools
Initialization from Steady-State Solution
If the network contains harmonic sources or nonlinearities, it
is necessary to perform a harmonic load-flow.
Finding the harmonic steady-state solution can have a
significant impact on computing time under some particular
conditions.
When the network is linear, then the initialization with
harmonics through the linear steady-state constitutes a
simple superposition of all harmonic solutions.
In some special conditions (e.g., different rotor frequencies),
initialization is possible by solving equations independently.
Complex and yet unsolved problems
Initialization with power electronic devices
Initialization of control systems
Case Study
The following case study was carried out with the
EMTP-RV
The presentation summarizes
The main features of the Test System
The Modelling Approach followed in the implementation of
the test system in EMTP-RV
The development of Power-Flow to EMTP-RV Translator
Simulation Results and a Comparison between results
derived from a power flow simulator and the EMTP-RV
Sources: V. Spitsa, R. Salcedo, X. Ran, J. Martinez, R. Uosef, F. de León,
D. Czarkowski, and Z. Zabar, “three–phase time–domain simulation of
very large distribution networks,” IEEE Trans. on Power Delivery, vol. 27,
no. 2, pp. 677-687, April 2012.
F. de León, D. Czarkowski, V. Spitsa, J. A. Martinez, T. Noda, R. Iravani,
X. Wang, A. Davoudi, G. W. Chang, A. Mehrizi-Sani, and I. Kocar,
“Development of data translators for interfacing power-flow programs
with EMTP-type programs: Challenges and lessons learned,” IEEE Trans.
on Power Delivery, vol. 28, no. 2, pp. 1192-1201, April 2013.
Test System
Test System
Electrical power is supplied to the area substation that has a
number of parallel transformers equipped with tap changers.
A backup transformer (TR13) exists which operates when one of
the main transformers is out of service.
The tap changers have scheduling which depends on active
power output of the transformers to the loads.
The transformers are gathered into groups and can be
synchronized by closing substation breakers at the
synchronization (SYN) buses.
There are dozens of primary feeders connecting the area
substation to a secondary grid through network transformers.
The feeders have breakers equipped with overcurrent relays.
The network transformers operate with fixed taps.
Test System
Network protectors (NPs) are installed on the secondary side of
each one of the network transformers.
NPs prevent backfeeding from the secondary grid into the
primary network.
The secondary grid represents interconnections of underground
cables and overhead lines supplying electrical loads.
Some distribution networks can have even more complex
architectures since they include radial feeders, spot networks,
and secondary grids at different voltage levels linked together by
additional network transformers.
Manual modeling of such large and complicated networks using
the EMTP graphical user interface (GUI) is impractical.
An automatic modeling approach was developed at the
Polytechnic Institute of New York University, Brooklyn, NY, to
create models of distribution networks having very large size.
Test System
Actual distribution network that supplies power in Manhattan, NYC.
The network has more than 2503 branches.
Total number of three-phase nodes = 2333.
Transmission-side voltage at area substation = 69 kV.
The primary operates at 13.8 kV whereas the secondary grid
consume power at voltage levels of 120/208 V.
Test System
Operational conditions are summarized in the table II.
Active and reactive power demands given in the table describe an
aggregate load of the distribution network.
Total active and reactive powers stand for power consumption from
the transmission system.
Modelling Approach
EMTP-like tools use a graphical user interface (GUI) to translate
the graphical model into a description language called netlist.
The netlist provides the connectivity of the design.
The EMTP-RV GUI was used only to derive detailed prototype
models for each group of network elements (i.e., one model for
all network transformers, one model for all breakers, etc.).
The created prototype models were converted into the subcircuit
netlist files and the netlist generation process was automated.
The input text data files of the load-flow program, which contain
specifications of network elements and connectivity information,
were used to calculate parameters, update subcircuit prototype
models, and reproduce network architecture in MATLAB.
A special script PF-EMTP Translator was developed.
The translator output is a complete network netlist which can be
automatically loaded into the EMTP to perform the simulation.
The correctness was verified by comparing results derived from
the EMTP-RV to those calculated using the load-flow program.
Modelling Approach
The following prototype models were derived:
Area substation transformer with tap changers
Network transformers
Unit substation transformers
Intermittent energy resources
Circuit breakers
Network protectors
Overcurrent protection
Overvoltage protection
Undervoltage protection
Directional power protection
Directional overcurrent protection.
Some built-in EMTP models were adopted:
RLC branches
PI-sections
Grounding zigzag transformers
Electrical loads
Ideal switches
Synchronous machines
Induction machines.
A flowchart of the data
translation from a power
-flow database to EMTP
Block diagram of the
PF-EMTP translator
Simulation and Validation
Time-domain models must be validated because even small
modelling errors may result in significant changes in steady-
state and dynamic behaviour of large complex systems.
All developed custom models were tested individually using
time-domain simulations.
A tool was written in MATLAB to compare connectivity of the
system, branch impedances, currents, and node voltages
calculated using the EMTP time-domain simulations and PVL
load-flow program.
Comparison results for peak loading are shown in the figures.
A very good match exists between the results since most of the
relative differences in the rms values of the primary feeder
currents shown in the first figure are within 1%. The maximum
relative difference is 3.5%. It corresponds to the absolute current
difference of only 0.07 A.
The maximum absolute difference of 0.92 A introduces a 0.6% of
the relative error in the rms value of the primary feeder current.
Simulation and Validation
Differences in the secondary grid currents are given in the
second figure; most differences are within a few percent.
The largest relative difference of 18.1% corresponds to 0.64 A of
the absolute current difference.
The maximum absolute difference is 18 A, but it makes up
slightly less than 1% of the relative difference.
The small differences are attributed to two reasons:
numeric inaccuracy of the specific database impedances used for the netlist
generation
the display of few significant digits in the load-flow results of PVL.
The maximum relative difference of voltages in all nodes is
0.029%. Similar comparison results were obtained for the light
loading case proving the validity of the derived dynamic model.
Simulation Results
Comparison of primary currents calculated using a commercial PF
program and the EMTP time-domain simulator
Simulation Results
Comparison of secondary currents calculated using a commercial
PF program and the EMTP time-domain simulator
Simulation and Validation
The validation of the EMTP simulation results against the power-
flow program output has been carried out for the cases of three-
phase short circuits in the primary and secondary subnetworks.
Three fault locations were chosen in the primary subnetwork:
head of the feeder (area substation bus);
middle of the feeder branch 2;
end of the feeder branch 3 (primaries of most distant network transformer).
Three-phase short circuits were simulated at service boxes and
transformer vaults in the secondary subnetwork.
A comparison of the fault currents is given in the table.
The maximum relative difference between node voltages was
below 0.05% for all of the cases of the three-phase short circuits
in primary and secondary subnetworks.
Simulation Results
Comparison of the Tree-Phase Short-Circuit Currents