Professional Documents
Culture Documents
20-May-2020
Development Plan
SYED BILAL AHMED
Content
1. Generator Excitation and protection system
2. Generator Protections
3. Electrical Protection system (General and at our Plant)
4. Protections on motors (LV and MV)
1. Generator Excitation and protection system
Excitation System
Definition: The system which is used for providing the necessary field current to the rotor
winding of the synchronous machine, such type of system is called an excitation system. In
other words, excitation system is defined as the system which is used for the production of the
flux by passing current in the field winding. The main requirement of an excitation system is
reliability under all conditions of service, a simplicity of control, ease of maintenance, stability
and fast transient response.
The amount of excitation required depends on the load current, load power factor and speed of
the machine. The more excitation is needed in the system when the load current is large, the
speed is less, and the power factor of the system becomes lagging.
1. DC Excitation System
2. AC Excitation System
o Rotor Excitation System
o Brushless Excitation System
3. Static Excitation System
1. DC Excitation System
The DC excitation system has two exciters – the main exciter and a pilot exciter. The exciter
output is adjusted by an automatic voltage regulator (AVR) for controlling the output terminal
voltage of the alternator. The current transformer input to the AVR ensures limiting of the
alternator current during a fault.
When the field breaker is open, the field discharge resistor is connected across the field
winding so as to dissipate the stored energy in the field winding which is highly inductive.
The main and the pilot exciters can be driven either by the main shaft or separately driven by
the motor. Direct driven exciters are usually preferred as these preserve the unit system of
operation, and the excitation is not excited by external disturbances.
The voltage rating of the main exciter is about 400 V, and its capacity is about 0.5% of the
capacity of the alternator. Troubles in the exciters of turbo alternator are quite frequent
because of their high speed and as such separate motor driven exciters are provided as standby
exciter.
Advantages
The advantages of the DC system are
• More reliable
• Compact in size
Disadvantages
The disadvantages of the DC system are
• Large size
• Voltage regulation was complex
• Very slow response
2. AC Excitation System
The AC excitation system consists of an alternator and thyristor rectifier bridge directly
connected to the main alternator shaft. The main exciter may either be self-excited or
separately excited. The AC excitation system may be broadly classified into two categories
which are explained below in details.
a. Rotating Thyristor Excitation System
The rotor excitation system is shown in the figure below. The rotating portion is being enclosed
by the dashed line. This system consists an AC exciter, stationary field and a rotating armature.
The output of the exciter is rectified by a full wave thyristor bridge rectifier circuit and is
supplied to the main alternator field winding.
The alternator field winding is also supplied through another rectifier circuit. The exciter
voltage can be built up by using it residual flux. The power supply and rectifier control generate
the controlled triggering signal. The alternator voltage signal is averaged and compare directly
with the operator voltage adjustment in the auto mode of operation. In the manual mode of
operation, the excitation current of the alternator is compared with a separate manual voltage
adjustment.
Advantages
The advantages of the rotating thyristor system are
• Fast response
• Simple
• Low cost
Disadvantages
The main disadvantage is the response rate of the thyristor is very low
The system eliminates the use of a commutator, collector and brushes have a short time
constant and a response time of fewer than 0.1 seconds. The short time constant has the
advantage in improved small signal dynamic performance and facilitates the application of
supplementary power system stabilising signals.
Advantages
The advantages of the brushless system are
• Reliability is excellent
• The flexibility of operation is good
• System responses are good
• There is no moving contact in the brushless system, so maintenance is low
Disadvantages
The disadvantages of the brushless system are
• Response is slow
• There is no fast de-excitation
3. Static Excitation System
In this system, the supply is taken from the alternator itself through a 3-phase star/delta
connected step-down transformer. The primary of the transformer is connected to the
alternator bus and their secondary supplies power to the rectifier and also feed power to the
grid control circuit and other electrical equipment.
This system has a very small response time and provides excellent dynamic performance. This system
reduced the operating cost by eliminating the exciter windage loss and winding maintenance.
An electrical generator can be subjected to either an internal fault or external fault or both. The
generators are normally connected to an electrical power system, hence any fault occurred in
the power system should also be cleared from the generator as soon as possible otherwise it
may create permanent damage in the generator.
The number and variety of faults occur in a generator are huge. That is why generator or
alternator is protected with several protective schemes. Generator protection is of both
discriminative and non-discriminative type. Great care is to be taken in coordinating the
systems used and the settings adopted to ensure that a sensitive, selective and discriminative
generator protection scheme is achieved.
Types of Generator Protection
The various forms of protection applied to the generator can be categorized into two manners,
Other than protective relays, associated directly with the generator and its associated
transformer, there are lightning arrestors, over speed safe guards, oil flow devises and
temperature measuring devises for shaft bearing, stator winding, transformer winding and
transformer oil etc. Some of these protective arrangements are of non-trip type i.e. they only
generate alarm during abnormalities.
But the other protective schemes ultimately operate master tripping relay of the generator.
This should be noted that no protective relay can prevent fault, it only indicates and minimizes
the duration of the fault to prevent high temperature rise in the generator otherwise there may
be permanent damage in it.
It is desirable to avoid any undue tresses in the generator, and for that it is usual practice to
install surge capacitor or surge diverter or both to reduce the effects of lightning and other
voltage surges on the machine. The protection schemes usually applied to the generator are
discussed here below in brief.
This type of protection was considered unnecessary in previous days because breakdown of
insulation between points in the same phase winding, contained in the same slot, and between
which a potential difference exists, very rapidly changes into an earth fault, and then it is
detected by either the stator differential protection or the stator earth fault protection.
A generator is designed to produce relatively high voltage in comparison to its output and
which therefore contains a large number of conductors per slot. With increasing size and
voltage of the generator, this form of protection is becoming essential for all large generating
units.
N when the protection is connected by means of transducers which measure the phase
parameters and the vectoral sum of the parameter to be measured (current or
voltage) is sent to the relay. This connection is generally called residual connection
(Holmgreen);
G when the protection is connected directly to the secondary of a transducer (CT or VT)
which measures the homopolar parameter directly (current or voltage);
R used for different applications: – reactance (for example 87R differential protection);
– undervoltage to indicate residual voltage (27R); – rotor of a synchronous machine
(64R ground rotor);
I. Differential protection for generator (87G)
Any internal fault inside the stator winding is cleared by mainly differential
protection scheme of the generator or alternator. The differential protection is
provided in the generator by using longitudinal differential relay
Motor protection depending on size and voltage level (on photo 3-phase asynchronous motor,
(55 kW)
Short-circuit = disconnection in case of a short-circuit at the motor terminals or inside the
motor windings.
Instantaneous overcurrent = operates with no intentional time delay when the current exceeds
a preset value.
Thermal overload = disconnection of motor in case of sustained operation with a torque
exceeding the nominal value. Overload is detected by measurement of excessive stator current
or by using PTC probes.
Phase current imbalance = disconnection of the motor in case of high current imbalance,
responsible for increased power losses and overheating.
Phase current loss = disconnection of the motor if one phase current is zero, as this is revealing
of cable or connection breaking.
Over-current = alarm or disconnection of the motor in case of high phase current, revealing a
shaft over-torque.
Ground fault / Instantaneous earth fault = disconnection in case of a fault between a motor terminal
and ground. Even if the fault current is limited, a fast action could avoid a complete destruction of the
motor.
Long start (stall) = disconnection in case of a starting time longer than normal (due to mechanical
problem or voltage sag) in order to avoid overheating of the motor.
Jam = disconnection in order to avoid overheating and mechanical stress if motor is blocked while
running because of congestion.
Undercurrent = alarm or disconnection of the motor in case a low current value is detected, revealing a
no-load condition (e.g.: pump drain, cavitation, broken shaft, …)
Phase current reversal = disconnection when a wrong phase current sequence is detected
Motor temperature (by sensors) = alarm or disconnection in case of high temperature detected by
probes.
Rapid cycle lock-out = prevent connection and avoid overheating due to too frequent start-up.
Load shedding = disconnection of the motor when a voltage drop is detected, in order to reduce the
supply load and return to normal voltage.
Notching or jogging / Number of starts = a specified number of successive operations within a given
time.
Phase voltage imbalance = disconnection of the motor in case of high voltage imbalance, responsible
for increased power losses and overheating.
Phase voltage loss = disconnection of motor if one phase of the supply voltage is missing. This is
necessary in order to avoid a single-phase running of a three-phase motor, which results in a reduced
torque, increased stator current, and inability to start.
Phase voltage reversal = prevent the connection and avoid the reverse rotation of the motor in case of a
wrong cabling of phases to the motor terminals, which could happen during maintenance for example.
Under-voltage = prevent the connection of the motor or disconnection of the motor, as a reduced
voltage could not ensure a correct operation of the motor.
Over-voltage = prevent the connection of the motor or disconnection of the motor, as an increased
voltage could not ensure a correct operation of the motor.
Under-power = alarm or disconnection of the motor in case of power lower than normal, as this
situation is revealing a pump drain (risk of destruction of the pump) or broken shaft.
Over-power = alarm or disconnection of the motor in case of power higher than normal, as this situation
is revealing a machine overload.
Under power factor = can be used for detection of low power with motors having a high no-load
current.
Over power factor = can be used for detection of end of the starting phase.
Motor reclosing = controls the automatic reclosing and locking out of a motor.
The relay rating is to be chosen according to the nominal motor current and the calculated starting
time.
• Trip class 10 is adapted to normal duty motors.
• Trip class 20 is recommended for heavy duty motors
• Trip class 30 is necessary for very long motor starting.
Protection of LV Motors
1. Motor Instantaneous Over-Current Protection
2. Motor Timed Over-Current Protection
3. Thermal Overload
4. Motor Ground Fault Protection
5. Motor Stall Protection
6. Motor Over-Fluxing Protection
3. Thermal Overload
Another common type of relay used for timed overload protection is a thermal overload relay.
In this type of relay, the motor current or a fraction of the current through a current
transformer is connected to an in-line heater.
Protection of MV Motors