You are on page 1of 44

CT Saturation Tutorial

Presented by
Tony Giuliante

Bushing CT

IS

IP
N Turns

Copyright ATG Consulting 2003 1


Physical Properties of Core

Length L

Area A

B-H Characteristic

Copyright ATG Consulting 2003 2


B-H Characteristic
B

Flux to Volts per Turn

Φ= ∫s B • dA

Φ = B • A sin (ωt)

V = dΦ = ω • B • A cos (ωt)
N dt

Copyright ATG Consulting 2003 3


Flux to Volts per Turn

V = ω•B•A
N

Electric Field to Ampere Turns

ΝΙ = ∫H • dL

ΝΙ = H • L

Copyright ATG Consulting 2003 4


Convert B-H Characteristic
B

V = ω•B•A
N

H
ΝΙ = H • L

V/N vs. NI
V
N

NI

Copyright ATG Consulting 2003 5


CT Exciting Characteristic

2000:5

300:5
VS

IS

Simplified Bushing CT Circuit

IS
IP REB
N

REB = RLEADS + RDEVICES

Copyright ATG Consulting 2003 6


Simplified Bushing CT Circuit
RCT
IS

IP REB
XM
N
IM

Simplified Bushing CT Circuit


IS

IP V = IS RTB RTB
XM
N
IM

Copyright ATG Consulting 2003 7


Flux vs Voltage

V = N dΦ
dt

∫V
1
Φ= N • dt

∫ IS RTB
1
Φ= N • dt

Flux vs Voltage

∫ IS RTB
1
Φ= N • dt

Flux equals the AREA under the Voltage

Copyright ATG Consulting 2003 8


Voltage Demand
IS RTB

Voltage & Flux Waveforms

IS RTB

Copyright ATG Consulting 2003 9


Flux Design Limits

+ ΦS

Φ
- ΦS

Secondary Current
No Saturation

Copyright ATG Consulting 2003 10


Increased Voltage Demand
Five times IS RTB
5*IS RTB

Flux for Ideal CT


No Saturation
5*IS RTB

Copyright ATG Consulting 2003 11


Current Output for Ideal CT
No Saturation

Primary Current Secondary Current

Amperes

Time (Seconds)

Flux Design Limits

+ ΦS
- ΦS

Copyright ATG Consulting 2003 12


Flux Design Limits

+ ΦS
- ΦS

Flux Excursion

Copyright ATG Consulting 2003 13


Current vs Flux

AC Saturation

Copyright ATG Consulting 2003 14


AC Saturation
• Large Fault Current

• Large Burden

• Low CT Kneepoint Voltage

AC Saturation
Relay Applications
• Large Fault Current
– Unit Auxiliary Transformers
• Large Burden
– High Impedance Bus Differentials
• Low CT Kneepoint Voltage
– Compact Distribution Switchgear

Copyright ATG Consulting 2003 15


Unit Auxiliary Transformers

87UAT

DC Offset
Transformer

Fault current includes a dc component, or offset,


that makes the current asymmetrical.
L/R = 100 ms X/R = 37.7

Copyright ATG Consulting 2003 16


Offset Current vs Flux
Primary Current Flux

Sec. Amperes
or
Flux Density

Time (Seconds)

Secondary Current
Primary Current
Secondary Current

Amperes

Time (Seconds)

Copyright ATG Consulting 2003 17


Secondary Current
Observations
• Secondary current is distorted due to the
core flux saturation
• Secondary current distorts after a short time
(time-to-saturation)
• Distortion slowly dissipates as primary dc
offset decays

Secondary Current
100
I PRIM
Amps

50
0
I SEC
-50
0 1 2 3 4 5 6 7
Magnetic Flux Density (B)
2
Tesla

1
0
-1
0 1 2 3 4 5 6 7
Cycles

Copyright ATG Consulting 2003 18


Large Differential Current
Secondary Current
Primary Current

Amperes

Differential Current

Time (Seconds)

DC Saturation Factors
• Large DC Time Constant

• Large Burden

• Low CT Kneepoint Voltage

• High Remanent Flux

Copyright ATG Consulting 2003 19


Remanent Flux
• Trapped magnetic flux in core if a previous
offset current is interrupted before reaching
a symmetrical state
• High X/R ratios make remanent flux more
likely due to the slow decay rates of offset
current

Remanent Flux Survey


Remanent flux Percentage
in % of saturation of cts
0 - 20 39
21 - 40 18
41 - 60 16
61 - 80 27

Copyright ATG Consulting 2003 20


Remanent Flux Example
• CT data
– 1200:5, C800, burden = 1.6 +j 0.7 ohm
• Fault current 24,000 amps with dc offset
• X/R ratio = 19
• Display ct secondary output current for
remanence of 0%, 50% and 75% of
saturation

0% Remanent Flux
Primary Current
Secondary Current

Amperes

Time (Seconds)

Copyright ATG Consulting 2003 21


50% Remanent Flux

Primary Current
Secondary Current

Amperes

Time (Seconds)

75% Remanent Flux

Primary Current
Secondary Current

Amperes

Time (Seconds)

Copyright ATG Consulting 2003 22


Remanent Flux Results
Remanent flux Time-to-saturation

0% 1+ cycles
50% 1/2 cycle
75% 1/3 cycle

IEEE Guide for the Application of


Current Transformers Used for
Protective Relaying Purposes

C37.110-1996

Copyright ATG Consulting 2003 23


CT Classification

CT Accuracy Class
• ANSI defines accuracy rating classes by a
letter and number
C100, C800 or T100, etc.
• Letter designates how the accuracy can be
determined
• Number designates the minimum secondary
terminal voltage under a standard burden

Copyright ATG Consulting 2003 24


Accuracy Class Letter
• “C” means by Calculation
– non-gapped cores with negligible leakage flux,
such as bushing cts
• “T” means by Test
– cts with leakage flux, such as cts with wound
primaries
• Old classes “H” and “L”
H T and L C

Accuracy Class Number


• Minimum secondary terminal voltage
produced
– at 20 times rated current
– into a standard burden
– without exceeding a 10% ratio correction factor

Copyright ATG Consulting 2003 25


What is a Standard Burden?
• IEEE Standard Requirements for Instrument
Transformers C57.13-1993 the standard
relaying burdens are 1, 2, 4 and 8 ohms at a
lagging 0.5 p.f.
• 20 times rated secondary current of 5 A is
100 A, and 100 A times the standard
burdens yield C ratings of 100, 200, 400
and 800 V

CT Knee Point Voltages


45o Tangent
2000:5
B
A
300:5
VS

IS

Copyright ATG Consulting 2003 26


Knee Point Definitions
• Point A is the ANSI knee point voltage
– point tangent to 45 degree slope line
• Point B is the IEC knee point
– where a 10% increase in voltage causes a 50 %
increase in current
• IEC knee point is higher than ANSI knee
point

CT Excitation Impedance
• Excitation curve represents the exciting
impedance in terms of voltage and current

• The ANSI knee point (A) represents the


point of maximum permeability of the iron
core

Copyright ATG Consulting 2003 27


Examples
• Determine Accuracy Class

• Selecting CT Ratings

• Calculating Time to Saturation

Example - Find Accuracy Class


• Find the approximate ct accuracy class from
the excitation curve
– the C class is defined for a 10% ratio correction
factor at 20 times rated current
• 10% of (20 X 5 A) is 10 A
• for IE = 10 A, use the excitation curve to find VS as
about 500 V
– next find the ct terminal voltage by subtracting
the internal voltage drop from VS
» (continued)

Copyright ATG Consulting 2003 28


Example - Equivalent Circuit

IP IS = 100 A

IE = 10 A
VS = 500 VB = ? ZB

Example - continued
– VB (voltage to the burden)
VB = VS - (IS X RS)
VB = 500 - (100 X 0.61)
VB = 439 V

– The approximate ct accuracy class is the next


lowest ANSI class number (C400)

Copyright ATG Consulting 2003 29


Examples
• Determine Accuracy Class

• Selecting CT Ratings

• Calculating Time to Saturation

Avoiding CT Saturation

VX > IS · ZTB (1 + X/R)

VX = saturation voltage
IS = secondary current
ZTB = total ct secondary burden

Copyright ATG Consulting 2003 30


CTs for Generator Differentials
• For generators, typically cts cannot be sized
to avoid saturation because of:
– high fault current
– high X/R ratio
• Common applications would:
– select adequate ct primary rating
– select highest practical C class
– match manufacturer and types of cts

Examples
• Determine Accuracy Class

• Selecting CT Ratings

• Calculating Time to Saturation

Copyright ATG Consulting 2003 31


Transient Response of
Current Transformers
Power Systems Relaying Committee

Time to Saturate Equation

-t -t
VK
I F R TB
( I - KR ) = ω TCT TS
T CT - T S {
e
TCT
-e }
TS
+1

Copyright ATG Consulting 2003 32


VK

VK 2000:5
Tangents
Intersect
300:5
VS

IS

Saturation Parameters
R TB = RCT + R LEADS +R DEVICES

I F = FAULT CURRENT
(SEC RMS AMPS)
KR =
{ .5 - .75 IRON CORE
.1 AIR GAP
ω = 377
L
TCT = M
R TB

Copyright ATG Consulting 2003 33


VM & I M
45o Tangent
2000:5
VM

300:5
VS

IM IS

CT Inductance
LM
TCT =
RTB

VM
XM = IM

XM
LM =
ω

Copyright ATG Consulting 2003 34


DC Offsets

DC Offset Current
• Depends on where in the voltage wave the
fault occurs.

• Fault time is defined as:


F I A => Fault Initiation Angle

Copyright ATG Consulting 2003 35


Voltage Waveform
FIA

0 45 90 135 180 225 270 345 360 Degrees

60 Hz 0 4.16 8.33 12.5 16.67 Time ms

Voltage Waveform
FIA

0 45 90 135 180 225 270 345 360 Degrees

50 Hz 0 5 10 15 20 Time ms

Copyright ATG Consulting 2003 36


Power System
R L

Z = √ R2 + X2
G
θ = ARCTAN (ω L / R)

Power System
R L

G
θ = Characteristic Angle

Copyright ATG Consulting 2003 37


Fault at FIA = θ
No Offset
R L

Current Waveform
No Offset FIA = θ
2

0
Current

-1

-2

-3
0 10 20 30 40 50
Time - Milliseconds

Copyright ATG Consulting 2003 38


Fault at FIA = θ ± 90
Max Offset
R L

Current Waveform
Max Offset FIA = θ + 90
2

0
Current

-1

-2

-3
0 10 20 30 40 50
Time - Milliseconds

Copyright ATG Consulting 2003 39


Total Current
2

0
Current

-1

-2

-3
0 10 20 30 40 50
Time - Milliseconds

Equations
v(t) = Vmax * sin ( Wt + Close_Ang )

i (t) = i ss (t) + i trans (t)

i ss (t) = [ Vmax / Z ] * sin ( Wt + Alpha )

Alpha = Close_Ang - ArcTan ( WL/R )

i trans (t) = [ e^ (-R/L) t ] * [ -Vmax / Z ] * sin ( Alpha )

Copyright ATG Consulting 2003 40


Power System
Time Constants
L/R (MS) X/R Ang (deg) Power System
1 0.377 20.66 High Fault Resistance
2 0.754 37.02
5 1.885 62.05 Distribution Lines
10 3.770 75.14 Subtransmission Lines
30 11.310 84.95 EHV Lines
100 37.699 88.48 Transformers
200 75.398 89.24 Generators
400 150.796 89.62
1000 376.991 89.85 Large Generators

Subtransmission Line
L/R = 10 ms
2

0
Current

-1

-2

-3
0 10 20 30 40 50
Time - Milliseconds

Copyright ATG Consulting 2003 41


Generator
L/R = 200 ms
2

0
Current

-1

-2

-3
0 10 20 30 40 50
Time - Milliseconds

EHV Line
L/R = 30 ms
2

0
Current

-1

-2

-3
0 10 20 30 40 50
Time - Milliseconds

Copyright ATG Consulting 2003 42


Distribution Line
L/R = 5 ms
2

0
Current

-1

-2

-3
0 10 20 30 40 50
Time - Milliseconds

Copyright ATG Consulting 2003 43

You might also like